EB MAIN

NAGA LIMITED (DETERGENTS) VEDASANDUR,


CHECK LIST FOR MAINTENANCE OF HT EQUIPMENTS TO BE CARRIED OUT BY OUR TEAM
AND OUT SOURCED AGENCY

I) EB'S MAIN / CHECK METER 2P STRUCTURE


ATTENDED BY :
DATE :
WARNING -1 : Utmost care / double check of isolation of 22 KV feeder line clearance(by
WARNING - 2 : Earth rod must be hooked up( connected ) to copper / ACSR conductor and
commonly lopped wire should effectively connected to earth
WARNING - 3 :The work must be carried out under the personal supervision of a Qualified
Engineer preferably having 'c'-License

S.NO DESCRIPTION OF CHECK POINTS

DONE ON

1 Condition of bi metal clamp loose connection


2 Zero copper / ACSR conductor connectivity
3 HG fuse horn gap clearance and fuse wire used
4 AB switch knives & copper braid connectivity
5 Applying petroleum jelly in knives&nuts
6 Tightness of all live connection bolt& nut
Structure complete aluminum painting and sandozmat
7 green coat for concrete poles
8 Testing of earth electrodes pretending to the equpt.

Page 1

NEXT DUE

HT VCB

NAGA LIMITED (DETERGENTS) VEDASANDUR,


CHECK LIST FOR MAINTENANCE OF HT EQUIPMENTS TO BE CARRIED OUT BY OUR
TEAM AND OUT SOURCED AGENCY
II) HT VCB 22 KV ( OVERHAULING)
ATTENDED BY :

DATE :

WARNING - 1 : Utmost care / double check of isolation of 22kv feeder line clearance ( by
opening ab switch) at consumers two pole structure is absolutely neccessary carring out the
below said work
common looped wire should effectively connected to earth
qualified engineer preferably having 'c' license

S.NO

DESCRIPTION OF CHECK POINTS

DONE ON

1 Through cleaning using blower


Check condition of door beading and inspection glass
2 windows
3 General over hauling of kiosk mechanism
4 Function of space heaters
5 Function of thermostat of space heaters
Roof top bushing / rod changing gaskets incomer and out
6 going termination and bus bar joint tightening
7 Spout internal tight checking by using special spanner
8 C.T primary bus rod loose conduct tight checking
9 Control terminal loose conduct tight checking
10 Condition of epoxy fiber shrouding and proper fixing
11 Surface painting
Checking function of shunt trip coil 110 v ac by creating
12 temperature controller bucholz / surge relays activation
13 Testing of earth electrodes pertaining to the equpt.

Page 2

NEXT DUE

HT 6 POLE

NAGA LIMITED (DETERGENTS) VEDASANDUR,


CHECK LIST FOR MAINTENANCE OF HT EQUIPMENTS TO BE CARRIED OUT BY OUR TEAM
AND OUT SOURCED AGENCY
III) HT 6 POLE STRUCTURE

WARNING-1 :Utmost care / double check of isolation of 22kv feeder line clearance ( by opening
AB switch) at consumers six pole structure is absolutely necessary carrying out the
below said work
common looped wire should effectively connected to earth
engineer preferably having 'C' license

ATTENDED BY :
S.NO

DATE :

DESCRIPTION OF CHECK POINTS


DONE ON
Through cleaning rust removing i section poles and coating
1 zinc primer
2 Bimetal clam loose connection
3 Zero copper conductor connectivity
Drop out fuse conduct leaf spring plate temper checking and
4 replace them if required
Check condition of drop out fuse burrels and replace if
5 required
6 Replace all drop out fuse elements by a new one
7 AB switch knives and copper braid connectivity
8 Apply petroleum jelly in knives and bolts
9 Tightens of all live connections bolts and nut

10 Check condition drop out fuse burrels and replace if required


Check condition of 22kv lighting surge arrestor and replace if
11 required
12 Testing of earth electrodes pertaining to the equpt.

Page 3

NEXT DUE

TRANFORMER OLTC

NAGA LIMITED (DETERGENTS) VEDASANDUR,


CHECK LIST FOR MAINTENANCE OF HT EQUIPMENTS TO BE CARRIED OUT BY OUR TEAM
AND OUT SOURCED AGENCY
IV ) TRANSFORMER AND OLTC
WARNING-1: Utmost care / double check of isolation of 22kv feeder line clearance ( by opening ab
switch) at consumers two pole structure is absolutely neccessary carring out the
below said work
looped wire should effectively connected to earth
engineer preferably having 'c' license

ATTENDED BY :

DATE :

S.NO DESCRIPTION OF CHECK POINTS

DONE ON

Filteration of transformer oil in main / oltc tank by stream line


maintaining 55 to 60 deg . c to withstand bdv @ 40 kv for a
1 minute
Check for any oil leak and replace the gaskets (rubberized cork)
2 of suitable tick
3 Check and replace membrane of explosion vent
Check internal terminal lead wire / strips of hv / lv by opening of
4 top covers for tightness by using the special spanner
Bus duct opening of rope / sides of the duct,unscrewing bolt
nuts apply petroleum jelly and tightening of all solid bar / flexible
5 joints and re fixing of the roof / sides of the duct
Testing of bucholz / oil surge relays by applying 1 kg / sq.cm air
6 pressure
Check condition of silica gel breather housing (1 bsp) and
7 replace if required
Check accuracy level of transformer oil temperature controller
8 and its function of mercury switch
General over hauling of oltc mechanism , opening top covet ,
removing carbon sludges , checking condition conducts and
9 changing gaskets of top cover / bottom cover if required
Replacement of fixed conducts and moving conducts hinges
10 assembly
11 Testing of earth electrodes pertaining to the equipments

Page 4

NEXT DUE

MV 1 AND 2

NAGA LIMITED (DETERGENTS) VEDASANDUR,


CHECK LIST FOR MAINTENANCE OF HT EQUIPMENTS TO BE CARRIED OUT BY OUR TEAM
AND OUT SOURCED AGENCY
V) M.V PANEL 1 AND 2

WARNING - 1 : Utmost care / double check of isolation of 22kv feeder line clearance ( by opening ab
switch of transformer 1 & 2 ) at consumers two pole structure is absolutely necessary carrying out the
below said work
WARNING 2 : The following work must be carried out under the personal supervision of a qualified
engineer preferably having 'c' license

ATTENDED BY :

DATE :

S.NO DESCRIPTION OF CHECK POINTS

DONE ON

Isolate the incoming power supply and do the double check of


1 the isolation by using twin test lamp
2 Clean the outer shell with soap powder
3 Clean the EB and genset chamber
4 Check and tight all bus bar joints and jumper joints
5 Clean the metering chamber and tight all electrical connections
6 Clean all switches ,and checking / out termination
7 Apply petroleum jelly to switch conducts
8 Check the matching of fixed and moving conducts of all switch
9 Check the condition of all fuse links and tightens
Check all switch on/off mechanism and lubricate wherever
10 required
11 Check the castle interlock key functions
12 Check the earth connection
13 Clean the cable chamber
Check all hylum / fiber shroud are properly fixed in all exposed
14 live metal parts

Page 5

DUE ON

Sheet8

POWDER PLANT POWER PANEL

DATE

MV
CAPACITOR CAPCITOR
MCC 1 MCC 2 MCC 3 MCC 4 PANEL BANK 1
BANK 2
CLEANED BY

01/09/15
02/09/15
03/09/15
04/09/15
05/09/15
06/09/15
07/09/15
08/09/15
09/09/15
10/09/15
11/09/15
12/09/15
13/09/15
14/09/15
15/09/15
16/09/15
17/09/15
18/09/15
19/09/15
20/09/15
21/09/15
22/09/15
23/09/15
24/09/15
25/09/15
26/09/15
27/09/15
28/09/15
29/09/15
30/09/15

Page 6

Sheet6

POWDER PLANT POWER PANEL


DATE

MCC 1 MCC 2 MCC 3 MCC 4 MCC 5 MCC 6 MCC 7 CLEANED BY

01/09/15
02/09/15
03/09/15
04/09/15
05/09/15
06/09/15
07/09/15
08/09/15
09/09/15
10/09/15
11/09/15
12/09/15
13/09/15
14/09/15
15/09/15
16/09/15
17/09/15
18/09/15
19/09/15
20/09/15
21/09/15
22/09/15
23/09/15
24/09/15
25/09/15
26/09/15
27/09/15
28/09/15
29/09/15
30/09/15

Page 7

Sheet6

LEANED BY

Page 8

Sheet7

BAR PLANT POWER PANEL


DATE

PSM 1

LIGHTIN CAPACITOR SOLAR


PSM 2 MV PANEL -1 G PANEL BANK
PANEL CLEANED BY

01/09/15
02/09/15
03/09/15
04/09/15
05/09/15
06/09/15
07/09/15
08/09/15
09/09/15
10/09/15
11/09/15
12/09/15
13/09/15
14/09/15
15/09/15
16/09/15
17/09/15
18/09/15
19/09/15
20/09/15
21/09/15
22/09/15
23/09/15
24/09/15
25/09/15
26/09/15
27/09/15
28/09/15
29/09/15
30/09/15

Page 9

Sheet9

DIESEL GENERATOR
DATE
DG-1 (725KVA)
01/09/15
02/09/15
03/09/15
04/09/15
05/09/15
06/09/15
07/09/15
08/09/15
09/09/15
10/09/15
11/09/15
12/09/15
13/09/15
14/09/15
15/09/15
16/09/15
17/09/15
18/09/15
19/09/15
20/09/15
21/09/15
22/09/15
23/09/15
24/09/15
25/09/15
26/09/15
27/09/15
28/09/15
29/09/15
30/09/15

DG 2 (650 KVA)

CLEANED BY

Page 10