Transformer Chemistry Services [TCS]

PO Box 1265, Westville 3630


Kwa-zulu Natal, South Africa
Email: satcs@iafrica.com

Tel: +27 31 2668682

Reg No: CK92/24218/32

Fax: +27 31 2671372

TRANSFORMER DETAILS
Client:

MUTANDA MINE

Region:

DRC

District:

Substation:

MUM1 1

Transformer No:

Sample Point:

MAIN TANK

Report Number:

1523025

KATANGA
TX1

Cooling Type:

Unspecified

Serial No:

1083100A0001

Sample Date:

2014/05/08

Analyses Date:

2014/05/27

Primary Voltage: 120 kV

Secondary Voltage:

22 kV

VA Rating:

24 MVA

Vector Group:

YNd1

Impedence:

10.300

Make:

HANGZHOU QIANTANG Year Manufactured:


RIVER ELEC
Oil Volume Litres:

2008

Tap Changer:
Conservator:

Off load
No

11820

Oil Type:

Mineral

Breather Size:

C.S.U.S. (Abnormal)

TRANSFORMER INTERNAL CONDITION: Dissolved Gas (DGA) vpm @ NTP


Hydrogen
H2
Oxygen
O2
Nitrogen
N2
Methane
CH4
Carbon Monoxide
CO
Carbon Dioxide
CO2
Ethylene
C2H4
Ethane
C2H6
Acetylene
C2H2
Propane
C3H8
Total % Gas
Total Gas Combustibles
TRANSFORMER INSULATING OIL CONDITION
Water Content:
Breakdown Voltage:
Acidity:
Interfacial Tension:
Oil Quality Index:
Dissipation Factor @ 90C:

27
10674
54604
13
726
2590
1
2
1
6.86
770

* Age Compensated
IEC 60422 Category B

mg/Kg
kV

7
58

< 20 (Good)
> 50 (Good)

mg KOH/g oil

0.01

< 0.10 (Good)

mN/m

> 25 (Good)

OQIN (IFT/NN)

160 (min)

DDF

< 0.10 (Good)

Oil Colour:

Clear

Total Polychlorinated Biphenyl:


Transformer Oil Temp:

mg/1 PCB
Deg C
mg/Kg

0.1
51

Water@20C
Corrosive Sulfur:
TRANSFORMER INSULATING PAPER CONDITION
Furan

50 (max)
80 (max)
IEC 60422

2
Unknown

0.04

Water in paper: % Dry Weight


Water in paper: Total Litres
TRANSFORMER EXTERNAL CONDITION
Oil Level:
Transformer Leaks:

> 1000
> 0.5%
N/a
> 80
> 1000
> 15000
> 100
> 350*
> 70

No

2.0 (max)

Silica Gel:

Purple 100%

Paint Work:

Fair

The DGA indicates normal internal operation.


See diagnosis: IEC 60599: Westinghouse TCG: CSUS-no abnormal fault gases: Condition Code 1.
The oil condition conforms to the STD (IEC 60422).
Paper insulation: Mild to Moderate deterioration (see Furan). Retest in 1 year.
PCB Analysis: N/D<2 ppm (Class-Refer Local regulations)
RECOMMEND: Resample on a routine basis
Methods of Analysis

Water Content:

IEC 60814

Acidity:

ASTM D974

Dissolved Gas Analysis: IEC 60567

Dielectric Strength:

IEC 60156

Interfacial Tension:

ASTM D971

Dissipation Factor:

IEC 60247

/GasConcentrations

Polychlorinated Biphenyl:

ASTM D4059

2014-06-06 09:31

Transformer Chemistry Services [TCS]

PO Box 1265, Westville 3630


Kwa-zulu Natal, South Africa
Email: satcs@iafrica.com

Tel: +27 31 2668682

Reg No: CK92/24218/32

Fax: +27 31 2671372

TRANSFORMER DETAILS
Client:

MUTANDA MINE

Region:

DRC

District:

Substation:

MUM1 1

Transformer No:

Sample Point:

MAIN TANK

Report Number:

1523031

KATANGA
TX4

Cooling Type:

Unspecified

Serial No:

1103100A0001

Sample Date:

2014/05/08

Analyses Date:

2014/05/27

Primary Voltage: 120 kV

Secondary Voltage:

22 kV

VA Rating:

24 MVA

Vector Group:

YNd1

Impedence:

10.300

Make:

HANGZHOU QIANTANG Year Manufactured:


RIVER ELEC
Oil Volume Litres:

Tap Changer:
Conservator:

Off load
No

Oil Type:

Mineral

Breather Size:

2010

C.S.U.S. (Abnormal)

TRANSFORMER INTERNAL CONDITION: Dissolved Gas (DGA) vpm @ NTP


Hydrogen
H2
Oxygen
O2
Nitrogen
N2
Methane
CH4
Carbon Monoxide
CO
Carbon Dioxide
CO2
Ethylene
C2H4
Ethane
C2H6
Acetylene
C2H2
Propane
C3H8
Total % Gas
Total Gas Combustibles
TRANSFORMER INSULATING OIL CONDITION
Water Content:
Breakdown Voltage:
Acidity:
Interfacial Tension:
Oil Quality Index:
Dissipation Factor @ 90C:

0
22756
69740
7
361
1914
1
1
0
6
9.48
370

5
71

< 15 (Good)
> 60 (Good)

mg KOH/g oil

0.01

< 0.10 (Good)

mN/m

> 25 (Good)

OQIN (IFT/NN)

160 (min)

DDF

< 0.10 (Good)


Clear

Total Polychlorinated Biphenyl:


Transformer Oil Temp:

mg/1 PCB
Deg C
mg/Kg

0.1
54

Water@20C
Corrosive Sulfur:
TRANSFORMER INSULATING PAPER CONDITION

50 (max)
80 (max)
IEC 60422

1
Unknown

0.04

Water in paper: % Dry Weight


Water in paper: Total Litres
TRANSFORMER EXTERNAL CONDITION
Oil Level:
Transformer Leaks:

* Age Compensated
IEC 60422 Category A

mg/Kg
kV

Oil Colour:

Furan

> 1000
> 0.5%
N/a
> 80
> 1000
> 15000
> 100
> 350*
> 70

No

2.0 (max)

Silica Gel:

Purple 100%

Paint Work:

Fair

The DGA indicates normal internal operation.


See diagnosis: IEC 60599: Westinghouse TCG: CSUS-no abnormal fault gases: Condition Code 1.
The oil condition conforms to the STD (IEC 60422).
Paper insulation: Mild to Moderate deterioration (see Furan). Retest in 1 year.
PCB Analysis: N/D<2 ppm (Class-Refer Local regulations)
RECOMMEND: Resample on a routine basis
Methods of Analysis

Water Content:

IEC 60814

Acidity:

ASTM D974

Dissolved Gas Analysis: IEC 60567

Dielectric Strength:

IEC 60156

Interfacial Tension:

ASTM D971

Dissipation Factor:

IEC 60247

/GasConcentrations

Polychlorinated Biphenyl:

ASTM D4059

2014-06-06 09:31

Transformer Chemistry Services [TCS]

PO Box 1265, Westville 3630


Kwa-zulu Natal, South Africa
Email: satcs@iafrica.com

Tel: +27 31 2668682

Reg No: CK92/24218/32

Fax: +27 31 2671372

TRANSFORMER DETAILS
Client:

MUTANDA MINE

Region:

DRC

District:

Substation:

MUM1 1

Transformer No:

Sample Point:

MAIN TANK

Report Number:

1523028

KATANGA
TX3

Cooling Type:

Unspecified

Serial No:

1103100A0002

Sample Date:

2014/05/08

Analyses Date:

2014/05/27

Primary Voltage: 120 kV

Secondary Voltage:

22 kV

VA Rating:

24 MVA

Vector Group:

YNd1

Impedence:

Make:

HANGZHOU QIANTANG Year Manufactured:


RIVER ELEC
Oil Volume Litres:

2010

Tap Changer:
Conservator:

Off load
No

11820

Oil Type:

Mineral

Breather Size:

C.S.U.S. (Abnormal)

TRANSFORMER INTERNAL CONDITION: Dissolved Gas (DGA) vpm @ NTP


Hydrogen
H2
Oxygen
O2
Nitrogen
N2
Methane
CH4
Carbon Monoxide
CO
Carbon Dioxide
CO2
Ethylene
C2H4
Ethane
C2H6
Acetylene
C2H2
Propane
C3H8
Total % Gas
Total Gas Combustibles
TRANSFORMER INSULATING OIL CONDITION
Water Content:
Breakdown Voltage:
Acidity:
Interfacial Tension:
Oil Quality Index:
Dissipation Factor @ 90C:

0
26433
80817
6
266
927
1
1
1
10.85
275

12
59

< 20 (Good)
> 50 (Good)

mg KOH/g oil

0.01

< 0.10 (Good)

mN/m

> 25 (Good)

OQIN (IFT/NN)

160 (min)

DDF

< 0.10 (Good)


Clear

Total Polychlorinated Biphenyl:


Transformer Oil Temp:

mg/1 PCB
Deg C
mg/Kg

0.1
30

Water@20C
Corrosive Sulfur:
TRANSFORMER INSULATING PAPER CONDITION

50 (max)
80 (max)
IEC 60422

8
Unknown

0.03

Water in paper: % Dry Weight


Water in paper: Total Litres
TRANSFORMER EXTERNAL CONDITION
Oil Level:
Transformer Leaks:

* Age Compensated
IEC 60422 Category B

mg/Kg
kV

Oil Colour:

Furan

> 1000
> 0.5%
N/a
> 80
> 1000
> 15000
> 100
> 350*
> 70

No

2.0 (max)

Silica Gel:

Orange 100%

Paint Work:

Fair

The DGA indicates normal internal operation.


See diagnosis: IEC 60599: Westinghouse TCG: CSUS-no abnormal fault gases: Condition Code 1.
The oil condition conforms to the STD (IEC 60422).
Paper insulation: Mild to Moderate deterioration (see Furan). Retest in 1 year.
PCB Analysis: N/D<2 ppm (Class-Refer Local regulations)
RECOMMEND: Resample on a routine basis
Methods of Analysis

Water Content:

IEC 60814

Acidity:

ASTM D974

Dissolved Gas Analysis: IEC 60567

Dielectric Strength:

IEC 60156

Interfacial Tension:

ASTM D971

Dissipation Factor:

IEC 60247

/GasConcentrations

Polychlorinated Biphenyl:

ASTM D4059

2014-06-06 09:31

Transformer Chemistry Services [TCS]

PO Box 1265, Westville 3630


Kwa-zulu Natal, South Africa
Email: satcs@iafrica.com

Tel: +27 31 2668682

Reg No: CK92/24218/32

Fax: +27 31 2671372

TRANSFORMER DETAILS
Client:

MUTANDA MINE

Region:

DRC

District:

Substation:

MUM1 1

Transformer No:

Sample Point:

MAIN TANK

Report Number:

1523022

KATANGA
TX2

Cooling Type:

Unspecified

Serial No:

11103100A0002

Sample Date:

2014/05/08

Analyses Date:

2014/05/27

Primary Voltage: 120 kV

Secondary Voltage:

22 kV

VA Rating:

24 MVA

Vector Group:

YNd1

Impedence:

10.300

Make:

HANGZHOU QIANTANG Year Manufactured:


RIVER ELEC
Oil Volume Litres:

2008

Tap Changer:
Conservator:

On load
No

11820

Oil Type:

Mineral

Breather Size:

C.S.U.S. (Abnormal)

TRANSFORMER INTERNAL CONDITION: Dissolved Gas (DGA) vpm @ NTP


Hydrogen
H2
Oxygen
O2
Nitrogen
N2
Methane
CH4
Carbon Monoxide
CO
Carbon Dioxide
CO2
Ethylene
C2H4
Ethane
C2H6
Acetylene
C2H2
Propane
C3H8
Total % Gas
Total Gas Combustibles
TRANSFORMER INSULATING OIL CONDITION
Water Content:
Breakdown Voltage:
Acidity:
Interfacial Tension:
Oil Quality Index:
Dissipation Factor @ 90C:

0
24996
82062
8
442
2268
2
1
1
4
10.98
454

9
69

< 20 (Good)
> 50 (Good)

mg KOH/g oil

0.01

< 0.10 (Good)

mN/m

> 25 (Good)

OQIN (IFT/NN)

160 (min)

DDF

< 0.10 (Good)


Clear

Total Polychlorinated Biphenyl:


Transformer Oil Temp:

mg/1 PCB
Deg C
mg/Kg

0.1
40

Water@20C
Corrosive Sulfur:
TRANSFORMER INSULATING PAPER CONDITION

50 (max)
80 (max)
IEC 60422

4
Unknown

0.06

Water in paper: % Dry Weight


Water in paper: Total Litres
TRANSFORMER EXTERNAL CONDITION
Oil Level:
Transformer Leaks:

* Age Compensated
IEC 60422 Category B

mg/Kg
kV

Oil Colour:

Furan

> 1000
> 0.5%
N/a
> 80
> 1000
> 15000
> 100
> 350*
> 70

No

2.0 (max)

Silica Gel:

Orange 100%

Paint Work:

Fair

The DGA indicates normal internal operation.


See diagnosis: IEC 60599: Westinghouse TCG: CSUS-no abnormal fault gases: Condition Code 1.
The oil condition conforms to the STD (IEC 60422).
Paper insulation: Mild to Moderate deterioration (see Furan). Retest in 1 year.
PCB Analysis: N/D<2 ppm (Class-Refer Local regulations)
RECOMMEND: Resample on a routine basis
Methods of Analysis

Water Content:

IEC 60814

Acidity:

ASTM D974

Dissolved Gas Analysis: IEC 60567

Dielectric Strength:

IEC 60156

Interfacial Tension:

ASTM D971

Dissipation Factor:

IEC 60247

/GasConcentrations

Polychlorinated Biphenyl:

ASTM D4059

2014-06-06 09:31

Transformer Chemistry Services [TCS]

PO Box 1265, Westville 3630


Kwa-zulu Natal, South Africa
Email: satcs@iafrica.com

Tel: +27 31 2668682

Reg No: CK92/24218/32

Fax: +27 31 2671372

TRANSFORMER DETAILS
Client:

MUTANDA MINE

Region:

DRC

District:

Substation:

MUM1 1

Transformer No:

Sample Point:

MAIN TANK

Report Number:

1523029

KATANGA
TX5

Cooling Type:

Unspecified

Serial No:

11131000A0001

Sample Date:

2014/05/08

Analyses Date:

2014/05/27

Primary Voltage: 120 kV

Secondary Voltage:

22 kV

VA Rating:

24 MVA

Vector Group:

YNd1

Impedence:

10.300

Make:

HANGZHOU QIANTANG Year Manufactured:


RIVER ELEC
Oil Volume Litres:

2011

Tap Changer:
Conservator:

Off load
No

11820

Oil Type:

Mineral

Breather Size:

C.S.U.S. (Abnormal)

TRANSFORMER INTERNAL CONDITION: Dissolved Gas (DGA) vpm @ NTP


Hydrogen
H2
Oxygen
O2
Nitrogen
N2
Methane
CH4
Carbon Monoxide
CO
Carbon Dioxide
CO2
Ethylene
C2H4
Ethane
C2H6
Acetylene
C2H2
Propane
C3H8
Total % Gas
Total Gas Combustibles
TRANSFORMER INSULATING OIL CONDITION
Water Content:
Breakdown Voltage:
Acidity:
Interfacial Tension:
Oil Quality Index:
Dissipation Factor @ 90C:

0
29745
80449
1
11
520
0
0
0
11.07
12

7
66

< 20 (Good)
> 50 (Good)

mg KOH/g oil

0.01

< 0.10 (Good)

mN/m

> 25 (Good)

OQIN (IFT/NN)

160 (min)

DDF

< 0.10 (Good)


Clear

Total Polychlorinated Biphenyl:


Transformer Oil Temp:

mg/1 PCB
Deg C
mg/Kg

0.1
23

Water@20C
Corrosive Sulfur:
TRANSFORMER INSULATING PAPER CONDITION

50 (max)
80 (max)
IEC 60422

6
Unknown

0.06

Water in paper: % Dry Weight


Water in paper: Total Litres
TRANSFORMER EXTERNAL CONDITION
Oil Level:
Transformer Leaks:

* Age Compensated
IEC 60422 Category B

mg/Kg
kV

Oil Colour:

Furan

> 1000
> 0.5%
N/a
> 80
> 1000
> 15000
> 100
> 350*
> 70

No

2.0 (max)

Silica Gel:

Purple 100%

Paint Work:

Fair

The DGA indicates normal internal operation.


See diagnosis: IEC 60599: Westinghouse TCG: CSUS-no abnormal fault gases: Condition Code 1.
The oil condition conforms to the STD (IEC 60422).
Paper insulation: Mild to Moderate deterioration (see Furan). Retest in 1 year.
PCB Analysis: N/D<2 ppm (Class-Refer Local regulations)
RECOMMEND: Resample on a routine basis
Methods of Analysis

Water Content:

IEC 60814

Acidity:

ASTM D974

Dissolved Gas Analysis: IEC 60567

Dielectric Strength:

IEC 60156

Interfacial Tension:

ASTM D971

Dissipation Factor:

IEC 60247

/GasConcentrations

Polychlorinated Biphenyl:

ASTM D4059

2014-06-06 09:31

Transformer Chemistry Services [TCS]

PO Box 1265, Westville 3630


Kwa-zulu Natal, South Africa
Email: satcs@iafrica.com

Tel: +27 31 2668682

Reg No: CK92/24218/32

Fax: +27 31 2671372

TRANSFORMER DETAILS
Client:

MUTANDA MINE

Region:

DRC

District:

Substation:

MUM1 1

Transformer No:

Sample Point:

MAIN TANK

Report Number:

1523026

KATANGA
TX6

Cooling Type:

Unspecified

Serial No:

1113100A0002

Sample Date:

2014/05/08

Analyses Date:

2014/05/27

Primary Voltage: 120 kV

Secondary Voltage:

22 kV

VA Rating:

24 MVA

Vector Group:

YNd1

Impedence:

10.300

Make:

HANGZHOU QIANTANG Year Manufactured:


RIVER ELEC
Oil Volume Litres:

2011

Tap Changer:
Conservator:

Off load
No

11820

Oil Type:

Mineral

Breather Size:

C.S.U.S. (Abnormal)

TRANSFORMER INTERNAL CONDITION: Dissolved Gas (DGA) vpm @ NTP


Hydrogen
H2
Oxygen
O2
Nitrogen
N2
Methane
CH4
Carbon Monoxide
CO
Carbon Dioxide
CO2
Ethylene
C2H4
Ethane
C2H6
Acetylene
C2H2
Propane
C3H8
Total % Gas
Total Gas Combustibles
TRANSFORMER INSULATING OIL CONDITION
Water Content:
Breakdown Voltage:
Acidity:
Interfacial Tension:
Oil Quality Index:
Dissipation Factor @ 90C:

11
21691
76195
6
380
2109
1
1
0
1
10.04
399

16
59

< 20 (Good)
> 50 (Good)

mg KOH/g oil

0.01

< 0.10 (Good)

mN/m

> 25 (Good)

OQIN (IFT/NN)

160 (min)

DDF

< 0.10 (Good)


Clear

Total Polychlorinated Biphenyl:


Transformer Oil Temp:

mg/1 PCB
Deg C
mg/Kg

0.1
51

Water@20C
Corrosive Sulfur:
TRANSFORMER INSULATING PAPER CONDITION

50 (max)
80 (max)
IEC 60422

5
Unknown

0.03

Water in paper: % Dry Weight


Water in paper: Total Litres
TRANSFORMER EXTERNAL CONDITION
Oil Level:
Transformer Leaks:

* Age Compensated
IEC 60422 Category B

mg/Kg
kV

Oil Colour:

Furan

> 1000
> 0.5%
N/a
> 80
> 1000
> 15000
> 100
> 350*
> 70

No

2.0 (max)

Silica Gel:

Purple 100%

Paint Work:

Fair

The DGA indicates normal internal operation.


See diagnosis: IEC 60599: Westinghouse TCG: CSUS-no abnormal fault gases: Condition Code 1.
The oil condition conforms to the STD (IEC 60422).
Paper insulation: Mild to Moderate deterioration (see Furan). Retest in 1 year.
PCB Analysis: N/D<2 ppm (Class-Refer Local regulations)
RECOMMEND: Resample on a routine basis
Methods of Analysis

Water Content:

IEC 60814

Acidity:

ASTM D974

Dissolved Gas Analysis: IEC 60567

Dielectric Strength:

IEC 60156

Interfacial Tension:

ASTM D971

Dissipation Factor:

IEC 60247

/GasConcentrations

Polychlorinated Biphenyl:

ASTM D4059

2014-06-06 09:31

Transformer Chemistry Services [TCS]

PO Box 1265, Westville 3630


Kwa-zulu Natal, South Africa
Email: satcs@iafrica.com

Tel: +27 31 2668682

Reg No: CK92/24218/32

Fax: +27 31 2671372

TRANSFORMER DETAILS
Client:

MUTANDA MINE

Region:

DRC

District:

Substation:

MUM1

Transformer No:

Sample Point:

MAIN TANK

Report Number:

1523023

KATANGA
TX2

Cooling Type:

Unspecified

Serial No:

11131790001

Sample Date:

2014/05/08

Analyses Date:

2014/05/27

Primary Voltage: 120 kV

Secondary Voltage:

22 kV

VA Rating:

24 MVA

Vector Group:

YNd1

Impedence:

10.300

Make:

HANGZHOU QIANTANG Year Manufactured:


RIVER ELEC
Oil Volume Litres:

2011

Tap Changer:
Conservator:

Off load
No

12391

Oil Type:

Mineral

Breather Size:

C.S.U.S. (Abnormal)

TRANSFORMER INTERNAL CONDITION: Dissolved Gas (DGA) vpm @ NTP


Hydrogen
H2
Oxygen
O2
Nitrogen
N2
Methane
CH4
Carbon Monoxide
CO
Carbon Dioxide
CO2
Ethylene
C2H4
Ethane
C2H6
Acetylene
C2H2
Propane
C3H8
Total % Gas
Total Gas Combustibles
TRANSFORMER INSULATING OIL CONDITION
Water Content:
Breakdown Voltage:
Acidity:
Interfacial Tension:
Oil Quality Index:
Dissipation Factor @ 90C:

8
24064
66976
2
78
540
0
0
0
1
9.17
88

7
63

< 20 (Good)
> 50 (Good)

mg KOH/g oil

0.01

< 0.10 (Good)

mN/m

> 25 (Good)

OQIN (IFT/NN)

160 (min)

DDF

< 0.10 (Good)


Clear

Total Polychlorinated Biphenyl:


Transformer Oil Temp:

mg/1 PCB
Deg C
mg/Kg

0.1
42

Water@20C
Corrosive Sulfur:
TRANSFORMER INSULATING PAPER CONDITION

50 (max)
80 (max)
IEC 60422

3
Unknown

0.05

Water in paper: % Dry Weight


Water in paper: Total Litres
TRANSFORMER EXTERNAL CONDITION
Oil Level:
Transformer Leaks:

* Age Compensated
IEC 60422 Category B

mg/Kg
kV

Oil Colour:

Furan

> 1000
> 0.5%
N/a
> 80
> 1000
> 15000
> 100
> 350*
> 70

No

2.0 (max)

Silica Gel:

Purple 100%

Paint Work:

Good

The DGA indicates normal internal operation.


See diagnosis: IEC 60599: Westinghouse TCG: CSUS-no abnormal fault gases: Condition Code 1.
The oil condition conforms to the STD (IEC 60422).
Paper insulation: Mild to Moderate deterioration (see Furan). Retest in 1 year.
PCB Analysis: N/D<2 ppm (Class-Refer Local regulations)
RECOMMEND: Resample on a routine basis.
Methods of Analysis

Water Content:

IEC 60814

Acidity:

ASTM D974

Dissolved Gas Analysis: IEC 60567

Dielectric Strength:

IEC 60156

Interfacial Tension:

ASTM D971

Dissipation Factor:

IEC 60247

/GasConcentrations

Polychlorinated Biphenyl:

ASTM D4059

2014-06-06 09:31

Transformer Chemistry Services [TCS]

PO Box 1265, Westville 3630


Kwa-zulu Natal, South Africa
Email: satcs@iafrica.com

Tel: +27 31 2668682

Reg No: CK92/24218/32

Fax: +27 31 2671372

TRANSFORMER DETAILS
Client:

MUTANDA MINE

Region:

DRC

District:

Substation:

MUM1 1

Transformer No:

Sample Point:

MAIN TANK

Report Number:

1523030

KATANGA
TX3

Cooling Type:

Unspecified

Serial No:

11131790002

Sample Date:

2014/05/08

Analyses Date:

2014/05/27

Primary Voltage: 120 kV

Secondary Voltage:

22 kV

VA Rating:

24 MVA

Vector Group:

YNd1

Impedence:

10.380

Make:

HANGZHOU QIANTANG Year Manufactured:


RIVER ELEC
Oil Volume Litres:

2011

Tap Changer:
Conservator:

Off load
No

10780

Oil Type:

Mineral

Breather Size:

C.S.U.S. (Abnormal)

TRANSFORMER INTERNAL CONDITION: Dissolved Gas (DGA) vpm @ NTP


Hydrogen
H2
Oxygen
O2
Nitrogen
N2
Methane
CH4
Carbon Monoxide
CO
Carbon Dioxide
CO2
Ethylene
C2H4
Ethane
C2H6
Acetylene
C2H2
Propane
C3H8
Total % Gas
Total Gas Combustibles
TRANSFORMER INSULATING OIL CONDITION
Water Content:
Breakdown Voltage:
Acidity:
Interfacial Tension:
Oil Quality Index:
Dissipation Factor @ 90C:

0
33181
83567
1
22
894
0
0
0
11.77
23

12
47

< 20 (Good)
40-50 (Fair)

mg KOH/g oil

0.01

< 0.10 (Good)

mN/m

> 25 (Good)

OQIN (IFT/NN)

160 (min)

DDF

< 0.10 (Good)


Clear

Total Polychlorinated Biphenyl:


Transformer Oil Temp:

mg/1 PCB
Deg C
mg/Kg

0.1
41

Water@20C
Corrosive Sulfur:
TRANSFORMER INSULATING PAPER CONDITION

50 (max)
80 (max)
IEC 60422

5
Unknown

0.21

Water in paper: % Dry Weight


Water in paper: Total Litres
TRANSFORMER EXTERNAL CONDITION
Oil Level:
Transformer Leaks:

* Age Compensated
IEC 60422 Category B

mg/Kg
kV

Oil Colour:

Furan

> 1000
> 0.5%
N/a
> 80
> 1000
> 15000
> 100
> 350*
> 70

No

2.0 (max)

Silica Gel:

Unspecified 100%

Paint Work:

Good

The DGA indicates normal internal operation.


See diagnosis: IEC 60599: Westinghouse TCG: CSUS-no abnormal fault gases: Condition Code 1.
The oil condition conforms to the STD (IEC 60422).
Paper insulation: Mild to Moderate deterioration (see Furan). Retest in 1 year.
PCB Analysis: N/D<2 ppm (Class-Refer Local regulations)
RECOMMEND: Resample on a routine basis
Methods of Analysis

Water Content:

IEC 60814

Acidity:

ASTM D974

Dissolved Gas Analysis: IEC 60567

Dielectric Strength:

IEC 60156

Interfacial Tension:

ASTM D971

Dissipation Factor:

IEC 60247

/GasConcentrations

Polychlorinated Biphenyl:

ASTM D4059

2014-06-06 09:31

Transformer Chemistry Services [TCS]

PO Box 1265, Westville 3630


Kwa-zulu Natal, South Africa
Email: satcs@iafrica.com

Tel: +27 31 2668682

Reg No: CK92/24218/32

Fax: +27 31 2671372

TRANSFORMER DETAILS
Client:

MUTANDA MINE

Report Number:

1523027

Region:

KATANGA
TX2

Cooling Type:

Unspecified

Substation:

DEMOCRATIC REP. OF District:


CONGO
MUM1 2
Transformer No:

Serial No:

11131790003

Sample Point:

MAIN TANK

Sample Date:

2014/05/08

Analyses Date:

2014/05/27

Primary Voltage: 120 kV

Secondary Voltage:

22 kV

VA Rating:

24 MVA

Vector Group:

YNd1

Impedence:

10.300

Make:

HANGZHOU QIANTANG Year Manufactured:


RIVER ELEC
Oil Volume Litres:

2011

Tap Changer:
Conservator:

Off load
No

12391

Oil Type:

Mineral

Breather Size:

C.S.U.S. (Abnormal)

TRANSFORMER INTERNAL CONDITION: Dissolved Gas (DGA) vpm @ NTP


Hydrogen
H2
Oxygen
O2
Nitrogen
N2
Methane
CH4
Carbon Monoxide
CO
Carbon Dioxide
CO2
Ethylene
C2H4
Ethane
C2H6
Acetylene
C2H2
Propane
C3H8
Total % Gas
Total Gas Combustibles
TRANSFORMER INSULATING OIL CONDITION
Water Content:
Breakdown Voltage:
Acidity:
Interfacial Tension:
Oil Quality Index:
Dissipation Factor @ 90C:

0
27973
78287
1
44
438
0
0
0
10.67
45

6
67

< 20 (Good)
> 50 (Good)

mg KOH/g oil

0.01

< 0.10 (Good)

mN/m

> 25 (Good)

OQIN (IFT/NN)

160 (min)

DDF

< 0.10 (Good)


Clear

Total Polychlorinated Biphenyl:


Transformer Oil Temp:

mg/1 PCB
Deg C
mg/Kg

0.1
41

Water@20C
Corrosive Sulfur:
TRANSFORMER INSULATING PAPER CONDITION

50 (max)
80 (max)
IEC 60422

3
Unknown

0.16

Water in paper: % Dry Weight


Water in paper: Total Litres
TRANSFORMER EXTERNAL CONDITION
Oil Level:
Transformer Leaks:

* Age Compensated
IEC 60422 Category B

mg/Kg
kV

Oil Colour:

Furan

> 1000
> 0.5%
N/a
> 80
> 1000
> 15000
> 100
> 350*
> 70

No

2.0 (max)

Silica Gel:

Purple 100%

Paint Work:

Good

The DGA indicates normal internal operation.


See diagnosis: IEC 60599: Westinghouse TCG: CSUS-no abnormal fault gases: Condition Code 1.
The oil condition conforms to the STD (IEC 60422).
Paper insulation: Mild to Moderate deterioration (see Furan). Retest in 1 year.
PCB Analysis: N/D<2 ppm (Class-Refer Local regulations)
RECOMMEND: Resample on a routine basis
Methods of Analysis

Water Content:

IEC 60814

Acidity:

ASTM D974

Dissolved Gas Analysis: IEC 60567

Dielectric Strength:

IEC 60156

Interfacial Tension:

ASTM D971

Dissipation Factor:

IEC 60247

/GasConcentrations

Polychlorinated Biphenyl:

ASTM D4059

2014-06-06 09:31

Transformer Chemistry Services [TCS]

PO Box 1265, Westville 3630


Kwa-zulu Natal, South Africa
Email: satcs@iafrica.com

Tel: +27 31 2668682

Reg No: CK92/24218/32

Fax: +27 31 2671372

TRANSFORMER DETAILS
Client:

MUTANDA MINE

Region:

DRC

District:

Substation:

MUM1 2

Transformer No:

Sample Point:

MAIN TANK

Report Number:

1523024

KATANGA
TX1

Cooling Type:

Unspecified

Serial No:

11131790004

Sample Date:

2014/05/08

Analyses Date:

2014/05/27

Primary Voltage: 120 kV

Secondary Voltage:

22 kV

VA Rating:

24 MVA

Vector Group:

YNd1

Impedence:

10.330

Make:

HANGZHOU QIANTANG Year Manufactured:


RIVER ELEC
Oil Volume Litres:

2011

Tap Changer:
Conservator:

Off load
No

12391

Oil Type:

Mineral

Breather Size:

C.S.U.S. (Abnormal)

TRANSFORMER INTERNAL CONDITION: Dissolved Gas (DGA) vpm @ NTP


Hydrogen
H2
Oxygen
O2
Nitrogen
N2
Methane
CH4
Carbon Monoxide
CO
Carbon Dioxide
CO2
Ethylene
C2H4
Ethane
C2H6
Acetylene
C2H2
Propane
C3H8
Total % Gas
Total Gas Combustibles
TRANSFORMER INSULATING OIL CONDITION
Water Content:
Breakdown Voltage:
Acidity:
Interfacial Tension:
Oil Quality Index:
Dissipation Factor @ 90C:

9
23600
72598
3
161
919
0
0
0
2
9.73
173

7
73

< 20 (Good)
> 50 (Good)

mg KOH/g oil

0.01

< 0.10 (Good)

mN/m

> 25 (Good)

OQIN (IFT/NN)

160 (min)

DDF

< 0.10 (Good)


Clear

Total Polychlorinated Biphenyl:


Transformer Oil Temp:

mg/1 PCB
Deg C
mg/Kg

0.1
32

Water@20C
Corrosive Sulfur:
TRANSFORMER INSULATING PAPER CONDITION

50 (max)
80 (max)
IEC 60422

4
Unknown

0.19

Water in paper: % Dry Weight


Water in paper: Total Litres
TRANSFORMER EXTERNAL CONDITION
Oil Level:
Transformer Leaks:

* Age Compensated
IEC 60422 Category B

mg/Kg
kV

Oil Colour:

Furan

> 1000
> 0.5%
N/a
> 80
> 1000
> 15000
> 100
> 350*
> 70

2.0 (max)

Silica Gel:
No

Unspecified 100%

Paint Work:

The DGA indicates normal internal operation.


See diagnosis: IEC 60599: Westinghouse TCG: CSUS-no abnormal fault gases: Condition Code 1.
The oil condition conforms to the STD (IEC 60422).
Paper insulation: Mild to Moderate deterioration (see Furan). Retest in 1 year.
PCB Analysis: N/D<2 ppm (Class-Refer Local regulations)
RECOMMEND: Resample on a routine basis
Methods of Analysis

Water Content:

IEC 60814

Acidity:

ASTM D974

Dissolved Gas Analysis: IEC 60567

Dielectric Strength:

IEC 60156

Interfacial Tension:

ASTM D971

Dissipation Factor:

IEC 60247

/GasConcentrations

Polychlorinated Biphenyl:

ASTM D4059