FLOWMETERSELECTION

SEMINAR

AlanGraff
RLStoneCo
I&CSalesManager
UpstateNY&NewEngland

A Leading Supplier of Flowmeters


to HVAC & Industrial Marketplace

Magmeters
Vortex & Swirl
Turbine
Thermal & Coriolis Mass
BTU Meter
Pitot, Wedge
Orifice Plates, Venturi
Positive Displacement
Rotameter, Variable Area

DefineApplication BasicFacts
FlowingMedia(Steam,Water,Air,Gasetc)
Density pressureandtemperature
FlowRange,minimumtomaximum(turndown
needed)
Accuracy howstated?%ofrangeorspan
Repeatability
Straightrunrequirements&available
EconomicConsiderations Initialcost,maintenance
cost&operatingcosts

Whyarewehere?
Thereisno 1meterthatwillmeetevery
application
Everyapplicationneedstobelookedat
individually
Wecanmakesomegeneralizations!!!!!!

FLOWMEASUREMENT

HOWMUCH (TOTAL)
HOWFAST (RATE)

Flow Through A Pipe

Idealized

Real World

Pipe

Velocity Profile

Flow Profile Correlation

Steam
Water
Heavy Crude

Velocity profile is a predictable function of Reynolds


number. Fluids with the same Reynolds number will have
similar velocity profiles.

General Flow Terminology

Reynolds Number (RE) A single dimensionless


parameter formed as the ratio of inertial to
viscous forces . Magnitude indicates whether
flow is laminar or turbulent
RE=

Inertia Forces
Viscous Forces

Fluid
Density
(p)

Fluid
Velocity
(V)

Characteristic
Dimension*
(D)

Fluid Viscosity ()

* Usually inside pipe diameter.

Characterization of Fluid Flow

Types of Flow
RE < 2100

Laminar

Transitional

RE >3000

Turbulent ***

*** Well documented & proven fully


developed flow profiles

Volumetric Flowrate (Q)

V
A

Volume = Area x Length


Volume Flow = Area x Velocity

Mass Flowrate (m)


Q=VA
Mass Flow m =

Qp
= AV

V
A

Where

m
Q

= Mass Flow
= Volume Flow
= Fluid Density

Mass = Volume x Density

MassvsVolumeFlowmeters
Whyareweconcerned?
Howmuchdoesitreallymatter?
Flowthrougha4linemeasuredinaAveragingPitot
Flow Rate

1000 cfm

1000 cfm

Pressure

5 psi

5 psi

Temperature

100 F

70 F

DP in WC

12.181

11.532

Thereisa6%errorjustbychangingdensity/temperatureslightlycan
youmetercope??

General Flow Terminology

Factors affecting flowmeter performance


Process
Liquid
Gas

Density

media

Temperature
Velocity

(Specific Gravity)
Viscosity
Pressure

Flowmeter Performance

Accuracy
Repeatability
Linearity
Rangeability

Types of Accuracy

% Rate
% Full Scale
% Span
% Max DP

Accuracy
% Rate

The percent accuracy value is constant and


applied to the actual (or indicated) flowrate

Flowrate
Example: 100 GPM
50 GPM
10 GPM

1% rate
1 GPM
0.5 GPM
.01 GPM

% Full Scale The absolute value of error (as expressed in


engineering units)
Flowrate
Example: 100 GPM
50 GPM
10 GPM

1% Full Scale
1 GPM
1 GPM
1 GPM

% Rate
1%
2%
10%

Accuracy
Percent Error Versus Flow

Poor Repeatability Means


Poor Accuracy
Good Accuracy Means
Good Repeatability
Good Repeatability Does Not
Necessarily Mean Good Accuracy

VolumetricFlowmeters

DP
Turbine
Vortex/Swirl
Magnetic
Target
Ultrasonic
Displacement

Note:canbeinferredmasswithcompensatingtransmitter

Differential Pressure Flowmeters


Flow Measurement Principles
Q=K
ORIFICE PLATE
(or FLOW TUBE)

VENA
CONTRACTA

Direction of Flow

MANOMETER
(or DP TRANSMITTER)

DP Primary Elements

Various
Orifice
Configuration

Flow
Tube

Flow
Nozzle

Venturi
Flowmeter

DPPrimaryElements
AveragingPitot

Accelabar Combined
Pitot&Venturi

WedgeElement

Secondary Flow / DP Transmitter

Differential Pressure /
Flow Transmitter
Square Root Extraction

DP Flowmeters
DIFFERENTIAL PRESSURE

ADVANTAGES
Use On Liquid, Gas, and Steam
Suitable for Extreme Temperatures
and Pressures
No Moving Parts
Low Cost

DISADVANTAGES
Limited Rangeability
Effected By Changes In Density,
Pressure, and Viscosity
Maintenance Intensive

Magnetic Flowmeters

Theory of Operation

Magmeter Requirements

Process must be a liquid


Minimum conductivity
Meter must be full

Magnetic Flowmeters
MAGNETIC

ADVANTAGES
No Moving Parts
Very Wide Rangeability
Ideal For Slurries
Unobstructed Flow Path

DISADVANTAGES
Liquid Must Be Conductive
Physical Pressure and Temperature
Limits

Magnetic Flowmeters
Advantages Over Other Technologies

No moving parts
No pressure drop
Flowrate independent of viscosity, temperature, and density
Minimum upstream piping requirements
Electronics interchangeable without regard to size
Measure dirty liquids with solids
Measure highly corrosive fluids
Very large turndown
Linear output

Vortex Meter

Vortex Meter
Principle of Operation
Q=VxA

Vortex

Vortex/Swirlmeter
VORTEX / SWIRLMETER
ADVANTAGES
No Moving Parts
For Liquid, Gas, or Steam
Uneffected by Pressure, Temperature,
or Density Changes.
Wide Rangeability

DISADVANTAGES
Span Limitations Due to Viscosity
Flow Profile Sensitive (Vortex)

Swirlmeter
Principle of Operation
Preamplifier
Housing
Swirler

Sensor Deswirler
Backflow

r
VA
VT
p

=
=
=
=

local radius
axial velocity of flow
angular velocity of flow
static pressure

Swirlmeters

Benefits
High Accuracy 0.50% of Rate
No Moving Parts
Minimal Upstream Piping
Measures Low Flows
Versatile
Electronics can be used for Diagnostics
Works with Entrained Liquids

Swirlmeter
Cut-Away View

Technical Data
Measures liquids, gases and steam
Available integral, remote, or flow
computer electronics
Accuracy 0.50% rate
Sizes 0.75" thru 16.0"
Minimal upstream piping req.
Flow as low as 1 GPM
Excellent in light gas applications

Installation Length
Swirlmeter
Swirlmeter

Vortex 4
Process
control valve

5D

1D

3D

1D

50 D

5D

25 D

5D

15 D

5D

90 elbow

min. 1.8 D

Reduction
3D

1D

Turbine Meter

Turbine Meter
Principle of Operation

Rotor velocity is proportional to fluid velocity

Turbine Meter

High accuracy (.5% of rate)


High rangeability (up to 50:1)
Compact design
Fast response time
Broad range of sizes
Clean water applications only
NIST Traceable Factory Calibration
Low cost, Easy to install
In and out of line, under pressure

Turbine Meter

Performance Considerations

Straight pipe run requirements


Process fluid lubricity
Reynolds number constraints
Viscosity
Density
Maintenance & recalibration

Turbine Flowmeters
TURBINE
ADVANTAGES
High Accuracy
Suitable for Extreme
Temperatures and Pressures
Can Be Used On Gas or Liquid

DISADVANTAGES
Only For Low Viscosities
Moving Parts
Sensitive to Flow Profile

Positive Displacement Flowmeters

PD Flowmeters

Types
Helical gear
Nutating disk
Oscillating
piston
Oval gear
Rotary

Positive Displacement Meter


Typical Principle of Operation

Schematic of a
nutating-disk meter

Schematic of a
rotary-vane flowmeter

Schematic of a
lobed-impeller flowmeter

PD Flowmeters

Advantages
Ideal for viscous fluids
Custody transfer
Batching
Minimal straight piping
requirements

Ultrasonic Flowmeters

Types

Doppler
Time of
flight

Ultrasonic Flowmeters
Principle of Operation

Doppler
Flowmeter

Ultrasonic Flowmeters
Principle of Operation

Transit-Time
Flowmeter

Ultrasonic Flowmeters

Performance Considerations

Reynolds number constraints


Entrained gas or particles for doppler
Clean liquids for time of flight
Installed without process shut down
Straight upstream piping
requirements

Ultrasonic
ULTRASONIC
ADVANTAGES
No Moving Parts
Unobstructed Flow Passage
Wide Rangeability

DISADVANTAGES
For Liquids Only (limited gas)
Flow Profile Dependent
Errors Due To Deposits

MassFlowmeter
DirectMeasurement

ThermalDispersion
Coriolis

CoriolisMassFlowmeter

Coriolis

Coriolis
CORIOLIS

ADVANTAGES
Direct Mass Measurement
High Accuracy
Additional Density Measurement
Uneffected By Flow Profile

DISADVANTAGES
High Purchase Price
High Installation Cost
Size Limitations
Vibration Sensitive

ThermalDispersion

ThermalDispersionMassFlowmeter

Gasapplicationonly
Relativelyinexpensive
Easytoinstallandremoveunderpressure
Accuracy0.5%
Turndown,100:1
Capableofmonitoringextremelylowflows
Truemassflowmeter(compensatesfor
temperature/pressure)

PipingConsiderations
Alwaysneedafullpipe

Properup/downdiameter

BTUMonitoring

Summary Each Application is


Different
FlowingMedia(egSteam,Water,Air,Gasetc)
Density pressureandtemperature
FlowRange,minimumtomaximum(turndownneeded)
Accuracy howstated?%ofrangeorspan
Repeatability
Straightrunrequirements&available
Maintenanceandreliability

GeneralHVACRecommendations

Steam:AccelabarorSwirl
ChilledorHotWater:HotTapInsertTurbine
NaturalGasorAir:ThermalDispersion
FuelOil:CoriolisorWedge