DOWNSTREAM WORKS
Sl. No.
Description of Items
QTY
Unit
Supply
A
of Cubicle type, Indoor type, floor mounting, free standing, M.V/L.T sub panels
compartmentalised design and fabricated with 2mm CRCA sheet steel for main frames, folded
sections and load bearing members and 1.6mm CRCA sheet steel for doors & covers and
base channel 75mm X 40mmX 3.25mm and removable Gland plates at bottom and top entry
complete with adequate rating Al busbars, single busbar system, interconnections, cable
chamber, powder coated painting, earthing etc., with mechanical/electrical interlocks as
Erection
required.
Main Lighting Panel & Raw power panel.
Incoming
125 A TP&N 25KA MCCB with all other required necessary accessories - 1No
Instruments Panel
Digital type Load Manager, CTs, control fuses, one set of R,Y,B Indicating Lamps with control
switches and one set of ON/OFF/TRIP indicating lamp with protective fuses for incomer.
200A TPN Copper busbars:All the Neutral busbars shall have the same capacity of
Phase busbars.
Outgoings
LARSEN
LARSEN&&TOUBRO
TURBO LIMITED
LARSEN
LIMITED
ECC DIVISION - EDRC&
(MECHANICAL)
TOUBRO
LIMITED
ECC
DIVISION EDRC
(MECHANI
CAL)
OPTION-1
40A TP&N 25KA MCCB with all other required accessories with one set of ON/OFF/TRIP
indicating lamp with protective fuses
- 3Nos
Each
Each
Each
PAC PanelIncoming
160A TP&N 25KA MCCB with all other required necessary accessories - 1No
Instruments Panel
Digital type Load Manager, CTs, control fuses, one set of R,Y,B Indicating Lamps with control
switches and one set of ON/OFF/TRIP indicating lamp with protective fuses for incomer.
160A TPN Copper busbars:All the Neutral busbars shall have the same capacity of
Phase busbars.
Outgoings
40A TP&N 25KA MCCB with all other required accessories with one set of ON/OFF/TRIP
indicating lamp with protective fuses with DLM meters with RS 485 port
- 6Nos With
CAHU Panel
Incoming
125A TP&N 25KA MCCB with all other required necessary accessories - 1No
Instruments Panel
Digital type Load Manager, CTs, control fuses, one set of R,Y,B Indicating Lamps with control
switches and one set of ON/OFF/TRIP indicating lamp with protective fuses for incomer.
200A TPN Copper busbars:All the Neutral busbars shall have the same capacity of
Phase busbars.
Outgoings
32 A TP&N 25KA MCB with all other required accessories.-3Nos, & 32 Amps DP MCBs - 5
Nos. With necessary Copper busbars, interconnections, earthing etc.,with
required
315A TP+N 35KA MCCB with all other required necessary accessories - 3Nos
Instruments Panel
Digital type Load Manager, CTs, control fuses, for common load side & one set of R,Y,B
Indicating Lamps with control switches and one set of ON/OFF/TRIP indicating lamp with
protective fuses for each incomer
400A TPN Copper busbars:All the Neutral busbars shall have the same capacity of
Phase busbars.BUS COUPLER : 400 Amps 4 pole
electrical interlocking
Outgoings
315A TP&N 25KA MCCB with all other required accessories with one set of ON/OFF/TRIP
indicating lamp with protective fuses - 3 Nos with DLM meter and RS 485 port output With
necessary Copper busbars, interconnections,earthing etc.,with required accessories as per
the specifications.
Total for Sub Head -A
Distribution Boards
Supply, Installation, Testing and Commissioning of the following distribution boards shall be
designed for 415V,3Ph,50Hz, 4 wire AC system sheet steel , dust and vermin proof suitable for
wall mounting type (recessed) compartmentalised designed and fabricated made up of 2mm
CRCA sheet steel for main frame, folded sections and load bearing numbers and 1.6mm
CRCA sheet steel for doors and covers with suitable knockouts for incoming and outgoing
cable/ conduits provision of 2Nos. body earthing terminals with powder coated painting ,
danger board,sign writing including minor civil works etc as required.
Each
Each 63A DP MCB 'C' Curve with RCCB outgoing consist of 8 Nos of 16/20A 10 KA SP MCB
'C' Curve in a separate compartment with necessary phase segregation as required.
With necessary tinned copper busbars, interconnections, separate earth bus & separate
neutral bus for each phases. The board shall be powder coated type fixed with concealed
system in wall. The rate shall include necessary connected minor civil works as required.
Lighting Distribution Boad
Each
Each
Each
The double door type 6 Way TPN Compartmental Horizontal ( 7 Segment Phase
Segregation ) MCB DB comprising of the following :
Incoming
63A 4P 'C' Curve 10KA MCB 1 No.
Outgoings
63A DP MCB 'C' Curve with 63A DP 30 mA RCCB 3 Nos as outgoing with 18Nos 6/10A SP
MCB 'C' Curve
Each 32A DP MCB 'C' Curve with RCCB outgoing consist of 6 Nos of 6/10A 10 KA SP MCB 'C'
Curve in a separate compartment with necessary phase segregation as required.
With necessary tinned copper busbars, interconnections, separate earth bus & separate
neutral bus for each phases. The board shall be powder coated type fixed with concealed
system in wall. The rate shall include necessary connected minor civil works as required.
Emergency Lighting Distribution Boad
The double door type 8Way SPN Compartmental Horizontal MCB DB comprising of the
following :
Incoming
32A DP MCB 'C' Curve with 32A DP 30 mA RCCB 1 Nos
Outgoings
6Nos. 6/10A 10 KA SP MCB 'C' Curve.
With necessary tinned copper busbars, interconnections, The board shall be powder coated
type fixed with concealed system in wall. The rate shall include necessary connected minor
Incoming
63A TP & 2N 16KA MCCB with all other required accessories 1 No.
Outgoings
63A SP & 2N MCB 'D' Curve with 3 Nos as outgoing with 24Nos 10/16A SP MCB 'D' Curve
Each 63A SP & 2N MCB 'D' Curve with outgoing consist of 8 Nos of 10/16A 10 KA SP MCB 'D'
Curve in a separate compartment with necessary phase segregation as required. neutral bus
shall have the 200% capacity of phase busbars for each phases. The board shall be powder
coated type fixed with concealed system in wall. The rate shall include necessary connected
minor civil works as required.With necessary tinned copper busbars, interconnections,
separate earth bus & separate
Each
Each
Each
Each
Each
QRO
Each
480
Mtr
165
Mtr
165
Mtr
a)
b)
c)
d)
6
c)
1
etc., with necessary frame works & fixing accessories near the equipments as required
LT Cables and End Terminations
Supply, Laying, Testing And Commissioning of the following size PVC insulated and PVC
sheathed/XLPE
Power
cable
of
1.1KV
grade
Aluminium/Copper
conductor
armoured/unarmoured cables. Cables shall be laying on the existing cable trench in ground,
existing hume pipe, existing Masonary cable duct, existing cable tray and partially laid on
a)
b)
c)
wall/ceiling with suitable clamps & necessary fixing accessories etc. as required.
4 Core 25 Sq.mm PVC Copper Armoured Cable
4 Core 16 Sq.mm PVC Copper Armoured Cable
4 Core 4 Sq.mm PVC Copper un Armoured Cable
d
e)
f)
4600
Mtr
300
Mtr
150
Mtr
1800
Mtr
200
Mtr
250
Mtr
750
Mtr
100
Mtr
100
Mtr
16
Each
Each
20
Each
310
Each
40
Each
16
Each
80
Each
12
Each
18
Each
12
Each
20
Each
300
Each
Colour coding shall be used for 1 Core PVC copper unarmoured cable to differentiate
a)
b)
c)
d
n
o)
2
A)
B)
C)
D)
E)
F)
G)
H)
I)
j)
K)
L)
D
Supply, Laying, Testing and commissioning of following size and numbers of Power and
Lighting Circuit mains by using 1.1KV grade PVC insulated Flexible Multistrand
copper
conductor wires (FRLS) including earthing conductor drawn in 2mm thick Rigid PVC conduit
for concealed system below the false ceiling & on wall/floor and drawn in 16G M.S conduit for
open conduit system on the above false ceiling and drawn in existing cable trays/raceways and
drawn in PVC sleeves through modular furniture work stations including minor civil works etc.,
with interconnections, painting, sign writing as required. The rates quoted shall include supply
of PVC conduits/PVC sleeves/M.S conduits, wires & other required necessary conduiting
accessories with suitable fixing arrangements.Circuit mains shall be measured from respective
DB to the nearest control switch /socket/switch board & sub mains reckoned for looping from
switch / socket to another switch /socket/switch board.
Colour coding shall be used for conduits to differentiate lighting, Rawpower, UPS and
emergency lighting circuits. All circuit terminations shall be provided with solder less crimping
type copper sockets / lugs,PVC sleeves, ferrules indicating source code on load side & load
code on source side. There shall not be any joints in the circuits, only looping is allowed in
a)
terminal blocks & in switches / socket outlets and junction boxes etc., as required.
2R - 2.5 Sq.mm + 1R - 2.5 Sq.mm Copper conductor in a suitable MS conduit as required
b)
2R - 2.5 Sq.mm + 1R - 2.5 Sq.mm Copper conductor in a suitable PVC conduit as required
g)
h)
400
Mtr
180
Mtr
350
Mtr
200
Mtr
All switches / sockets shall be provided with printed labels / stickers indicating source code.
Colour code for UPS socket plates : White/ as per architect's approval, Colour code for
Rawpower socket plates:Black/Grey/ as per architect's approval. All switch / sockets including
front plate & frame which will be mounted on the metal boxes shall have removable film coat to
a)
b)
1No 6A 2/3 Pin combined socket outlet with 6A SP switch control without metal box
c)
2Nos 6A 2/3 Pin combined socket outlet with combined 6A SP switch control with metal box
d)
2Nos 6A 2/3 Pin combined socket outlet with combined 6A SP switch control without metal box
e)
1No 6/16A 3 Pin combined socket outlet with 16A SP switch control with metal box
f)
1No 25A 3 Pin 1Phase Industrial type socket with plug top (Metal Clad)
g)
1No 20/32A 3 Pin 1Phase Industrial type socket with plug top (Metal Clad) - SAMPLE SHALL
BE SUBMITTED
1No 32/3/ 5 Pin 1/3Phase Industrial type socket with plug top (Metal Clad) (supply)
h)
I)
1No 63/3/ 5 Pin 1/3Phase Industrial type socket with plug top (Metal Clad) (supply)
j)
3
12
Each
16
Each
15
Each
26
Each
Each
12
Each
150
Each
10
Each
10
Each
26
Each
24
Pts
Point Wiring
Point wiring to the light points/ceiling & exhaust fan point/6A socket point by using 2Runs of 2.5
Sq.mm + 1Run of 1.5 Sq.mm 1.1KV grade PVC insulated Flexible Multistrand
copper
conductor conductor (FRLS) drawn in 2mm thick Rigid PVC conduit for concealed system
below the false ceiling & on wall/floor and drawn in 16G M.S conduit for open conduit system
on the above false ceiling and drawn in existing cable trays/raceways including minor civil
works.Where the false ceiling is not available, recessed PVC conduit system shall be used.
The rates quoted shall be inclusive of supply of PVC/M.S conduits, wires & other conduiting
accessories, supply and fixing of 6A modular type switch in a suitable size modular box with
front plate suitable for surface/recess system including wiring with teriminal blocks upto the
light fittings in GI flexible hose with gland . minor civil works, making interconnections, wiring
a)
b)
c)
d)
e)
j)
k)
l)
1No 6A socket outlet point controlled by a 6A SP switch including providing and fixing of 1No
Pts
Pts
Pts
Pts
Pts
Pts
Pts
150
Mtr
90
Mtr
45
Mtr
50
Mtr
25
Mtr
40
Mtr
10
Mtr
10
Mtr
10
Mtr
10
Mtr
12
Supply and Fixing of following size ISI Marked Approved make of 16G MS conduits in floor /
wall /ceiling/cable tray etc., with all required necessary conduit accessories on surface above
the false ceiling and 2mm thick rigid PVC conduits in floor / wall etc.,with all required necessary
conduit accessories on recessed below the false ceiling including minor civil works, painting
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
E
etc as required.
25mm dia MS Conduit
32mm dia MS Conduit
25mm dia rigid GI Flexible Hose
32mm dia rigid GI Flexible Hose
25mm dia PVC Conduit
32mm dia PVC Conduit
50mm dia PVC Conduit
25mm dia rigid PVC Flexible Hose
32mm dia rigid PVC Flexible Hose
50mm dia rigid PVC Flexible Hose
Earthing system, GI Cable Trays / Supports, M.S Items
Earth electrodes
Earth flats & rounds
Supply and Fixing of the following size of GI/Cu earth flats/rounds as per IS and local electrical
authorities on surface/recess or on existing cable tray or on existing cable duct or below
ground as per site conditions. All Copper flats shall be run in PVC heat shrinkable sleeves &
mounted on insulation mounting supports. Cost of civil works shall be included for flats laid
below ground. All GI earth flat joints shall be welded & bolted. Anticorrosion chemical
2
3
4
300
Mtr
150
Mtr
150
Mtr
Each
Each
300
Mtr
300
Mtr
80
Mtr
1.00
M.Ton
Supply, Fixing of the following size Copper flat earth Station with 2 Nos DMC supporting
Insulator clamp with predrilled machine made holes of 12mm & 6 mm dia at 25mm intervals for
fixing earth flat including Nuts,Bolts & Washers complete as required. (2Nos DMC supporting
a)
b)
Supply and installation of following size LADDER TYPE GI ready made cable trays of 14 SWG
GI sheet. The Quoted rates for installation shall including necessary anchor fasteners and 'L'
a)
b)
c
Supply and Installation of MS flat / angle iron supports for various purpose if required with
various sizes including cutting,welding, grinding, fixing accessories and one coat of primer &
two coats of enamel paints, minor civil works etc. as required.(Note: The flat / angle iron weight
will be arrived on the basis of theoretical calculation only).
Supply, fixing, testing and commissioning of 2 x 36 W mirroroptics (Fueson -) )light fitting with
necessary control gear, lamps, louvers, loop and loop out terminal blocks etc with fixing
40
Each
40
Each
18
Each
Each
Each
Each
LS
necessary control gear, lamps, louvers, loop and loop out terminal blocks etc with fixing
accessoreies (in false celing)- Similar to or equivalent WVP 79236
Supply and fixing of following type light fitting with suitable size fixing arrgements from
celing/wall with all control gears, lamps, all other fixing accessoreies etc. like chain suspendor,
3
4
5
6
7
TOTAL
TOTAL FOR SUPPLY & INSTALLATION
LARSEN
LARSEN&&TOUBRO
TURBO LIMITED
LARSEN
LIMITED
ECC DIVISION - EDRC&
(MECHANICAL)
TOUBRO
LIMITED
ECC
DIVISION EDRC
(MECHANI
CAL)
AD
LIMITED
ARSEN
RC&
OUBRO
IMITED
ECC
IVISION EDRC
MECHANI
CAL)
LIMITED
ARSEN
MITED
RC&
OUBRO
IMITED
ECC
IVISION EDRC
MECHANI
CAL)
OPTION-1
Amount in Rs.
Supply
Erection
Total
LIMITED
ARSEN
MITED L
RC&
A
OUBRO R
IMITED S
ECC
E
IVISION - N
EDRC
MECHANI
CAL) &
T
O
U
B
R
O
L
I
M
B
R
O
L
I
M
I
T
E
D
E
C
C
D
I
V
I
S
I
O
N
E
D
R
C
(
M
E
C
H
A
N
I
C
A
L
)
A
N
I
C
A
L
)