ON
SUBMITTED BY:
NAME: KARAN GUPTA
ENROLLMENT NO.:F15 (L&D-P-02)
PROGRAMME: B.TECH (EE)
DECLARATION BY STUDENT
I hereby declare that this Internship Project Report
is an authentic record of my own work carried out
at TATA POWER-DDL, DELHI as requirement of 6
weeks Industrial Training. This is my own study
done under the guidance of staff and Managers of
the company.
I hereby declare that the contents of this report are
true and best to my knowledge
Karan Gupta
Department Of Electrical Engineering
Deen Bandhu Chhotu Ram University Of Science &
Technology
Murthal, ( Sonepat).
DECLARATION BY ORGANIZATION
This is to certify that the Internship project
report is prepared by Karan Gupta of Deen
Bandhu Chhotu Ram University Of Science And
Technology with TATA POWER -DDL is his original
work. This has been carried out as Summer
Internship as a part of Bachelor of Technology
at Electrical Engineering Department under my
guidance for the period of 1st june- 11th july
His performance here was satisfactory and I wish
him a successful and a bright future.
Place: Delhi
Date: 14TH JULY
Mr. K.K. Jain (HOD, North-West distribution,
TP-DDL)
Mr. Sandeep Bhardwaj ( senior manager,
North-West distribution, TP-DDL)
Mr. Vijender Rathore ( manager, TP-DDL)
PREFACE
Industrial training is a vital part in the progress of
fledgling engineers. For me this is the first rendezvous of
practical knowledge with the theoretical concepts
acquired during the years in college. I was very fortunate
that I got the opportunity of undergoing training in one of
the most sophisticated and modern Grid Substation.
Industrial training is a vital part in the progress of
fledgling engineers. The experience gained during this
short stay here was fascinating to say the list. It was a
tremendous feeling to see the practical operation of
different equipment and processes, which until now
existed for us only in books. I was deputed in Protection &
Testing Department for my training.
In this short stay it was possible for me to wholly decipher
the detailed functioning of the Grid Substation; but still I
am fortunate enough to get a sound overview of the unit,
thanks to the guidance extended by the people of
Protection & Testing Department.
KARAN GUPTA
INDEX
Executive
summary
..10
Introduction
..11
Main
objectives
of
taking
this
project..12
Definition
of
faults
13
Reasons
of
faults
.14
Fault
statistics
...16
Main
kind
of
faults....1
7
Harmful
effects
of
faults.19
Methods of controlling the tripping in the lines
and
grids
.21
Types of insulators to be used in the circuits i.e
in
the
lines
..23
Brief overview of equipments used in the
grids29
Since
privatization,
the
Aggregate
Technical
&
Commercial (AT&C) losses in TPDDL areas have shown a
record decline. AT&C loss is a measure of overall
efficiency of the distribution business which is the
difference between units input into the system and the
units for which the payment is collected. Today, AT&C
losses stand at 11% which is an unprecedented reduction
of around 79% from an opening loss level of 53% in July
2002.
10
11
Executive Summary
12
INTRODUCTION
13
MAIN OBJECTIVES OF TAKING THIS PROJECT WAS: To identify the see what are the main reasons due to
which tripping occurs
To schedule the maintenance program, basically1)Of equipments surrounding the lines which may be
the threat for it
2)Pinpointing Breakers that have anomalies in their
Mechanical operations.
To provide proper measures so that it may not occur
again
14
WHAT IS A FAULT?
Faults in an electrical circuit is defined as a defect in a
electrical circuit due to which current is diverted from its
intended path.
An electrical power system is comprising of transformers ,
generators, transmission and distribution circuits, it is
inevitable that sooner or later some failure will occur in
the system. The propability of the failure or occurrence of
abnormal condition is more on power lines, nearly about
one half. This can be explained by the fact that power
lines are more branched, have greater length, operate
under variable weather conditions.
15
There are many factors that are responsible for the faults
in the circuits that we will see ahead but , it mainly
occurs when the current in the circuit becomes
intentionally high and since our components are not
designed to handle this much amount of current, so at
that point tripping becomes necessary otherwise it may
damage the equipments.
REASONS OF FAULTS
According to the causes of the incidence,
causes of failure may be classified as
mentioned below:Breakdown may occur at normal voltage due to
- Ageing or deterioration of insulation
- Damages due to unpredictable happenings such as:-
16
17
FAULT STATISTICS
It is useful to have some ideas of % of various
types if faults and frequency of fault occurrence in
power system.
18
CAUSES
% OF TOTAL
Lightening
12
20
Apparatus failure
20
Switching to fault
20
miscellaneous
28
19
TYPES
REASONS
Due
to
breakdown
of
insulation b/w either of 2
phase and due to birdage
also.
to
insulation
20
EQUIPMENTS
% OF TOTAL
10
Cables
overhead lines
50
Transformers
10
Switchgear
15
Control equipment
Ct s and Pts
miscellaneous
10
7070
15
10
21
2 or 3
2 or 3
2 or 3
the
other
equipments
22
LOCATION
FAULTS
ENCOUNTERED
23
IN GRIDS GRID
Faults generally
encountered aretransformer failure,
circuit breaker failure,
LA failure, birdage, L-G
fault, L-L fault, L-L-G
fault.fac.
Faults generally
encountered are L-L, LG , insulators failure,
conductor breakdown,
and transients faults.
UNDER GROUND
LINES
24
25
26
Insulators
Electrical Insulator must be used in electrical system to
prevent unwanted flow of current to the earth from its
supporting points. The insulator plays a vital role in
electrical system. Electrical Insulator is a very high
resistive path through which practically no current can
flow.
The main cause of failure of overhead line insulator, is
flash over, occurs in between line and earth during
abnormal over voltage in the system. During this flash
over, the huge heat produced by arcing, causes puncher
in insulator body. Viewing this phenomenon the materials
used for electrical insulator, has to posses some specific
properties.
27
1.
28
Properties
property
Value
Dielectric Strength
60 KV / cm
Compressive Strength
70,000 Kg / cm2
Tensile Strength
500 Kg / cm2
2.
Glass insulator
29
Dis-advantages
1. Moisture can easily condensed on glass surface and
hence air dust will be deposited on the wed glass surface
which will provide path to the leakage current of the
system.
2. For higher voltage glass cannot be cast in irregular
shapes since due to irregular cooling internal cooling
internal strains are caused.
30
Properties
Property
Value
Dielectric Strength
140 KV / cm
Compressive Strength
10,000 Kg / cm2
Tensile Strength
35,000 Kg / cm2
31
Advantages
It is very light weight compared to porcelain and
glass insulator
As the composite insulator is flexible the chance of
breakage becomes minimum
It has higher tensile strength compared to porcelain
insulator
Its performance is better particularly in polluted
areas
Due to lighter weight polymer insulator imposes less
load to the supporting structure .
Dis- advantages
1. Moisture may enter in the core if there is any unwanted
gap between core and weather sheds. This may cause
electrical failure of the insulator.
32
4.
5. Current chopping in Circuit breaker is the incident of arc current
interruption before normal current zero is reached. Current chopping has
associated high rate of rise of recovery voltage .If this recovery voltage is
higher than the arcing voltage then the arc will continue again. But gradually
the current falls and certainly the voltage also reduce and finally fall below
the arcing voltage and ultimately arc is extinguished because of the resistive
component of the system, which dissipates energy. It results in voltage
oscillation in the line which affects the electrical equipments. It is severe in
Air blast circuit breaker (ABCB), Vacuum circuit -breakers (VCB) because
ABCB and VCB gain di-electric strength at a very rapid rate.
33
34
TIMER TEST
Timer test is carried out to measure the opening, closing and closing-opening
time.
MAIN CONTACT
These are the contacts in charge of establishing or interrupting the current flow in
power circuits. They include a fixed and a moving contact.
The contact's material has to be chosen to have minimum resistance when closed,
to minimize the losses by joule's effect when transiting nominal currents.
The best-suited material is silver plated copper.
ARCING CONTACT
For breakers, the arc can be a powerful generator of heat energy. This heat can
cause fast deterioration of main contact's material. To extend life of the main
contacts, breaker designers tend to separate the permanent current carriers,
called "Main Contacts", from those subjected to the arc effect, and called "Arcing
35
Contacts".
The most common material for arcing contacts is, in general, tungsten alloys,
reputed to have high arc resistant quality, but is less conductive than silver-plated
copper.
OPENING TIME
For a circuit breaker tripped by any form of auxiliary power, the opening time is
the interval of time between the instant of energizing the opening release, the
circuit breaker being in the closed position, and the instant when the arcing
contacts have separated in all poles.
Note: The opening time includes the operating time of any auxiliary equipment
necessary to open the circuit breaker and forming an integral part of the circuit
breaker.
CLOSING TIME
The interval of time between energizing the closing circuit, the circuit breaker
being in the open position, and the instant when the contacts touch in all poles.
Note: The closing time includes the operating time of any auxiliary equipment
36
necessary to close the circuit breaker forming an integral part of the circuit breaker.
CLOSE-OPEN TIME
The interval of time between the instant when the contacts touch in the first pole
during a closing operation and the instant when the arcing contacts have separated
in all poles during the subsequent opening operation.
Note: Unless otherwise stated, it is assumed that the opening release incorporated
in the circuit breaker is energized at the instant when the contacts touch in the first
pole during closing. This represents the minimum close-open time.
Breaker opening time should be less than the closing time of the breaker it should
come on the range of 30-45ms. while closing time should be 40-60ms.
CO- time for breaker should at the middle of the closing and opening time.
Opening time < closing Opening time < closing time
37
Then, using Ohm's law, the resistance value is calculated. The resistance value
needs to be compared with the value given by the manufacturer. This value turns
up to be in the range of Micro ohms.
38
39
It may increase the arc voltage by lengthening the arc path. As the
length of arc path is increased, the resistance of the path is increased,
and hence to maintain the same arc current more voltage is required to
be applied across the arc path. That means arc voltage is increased.
Splitting up the arc into a number of series arcs also increases the arc
voltage
There are mainly two types of ACB available.
1) Plain Air circuit breaker
2) Air-blast circuit breaker
40
41
42
extensively in high voltage circuit breakers and other switchgear employed by the
power industry. Applications for SF6 include gas insulated transmission lines and
gas insulated power distribution substations. The combined electrical, physical,
chemical and thermal properties offer many advantages when used in power
switchgear. Some of the outstanding properties of SF 6 which make its use in power
applications desirable are:
High dielectric strength
Unique arc-quenching ability
Excellent thermal stability
Good thermal conductivity
Disadvantage of the SF6 gas as an arc quenching medium is that, it has been
identified as a greenhouse gas and hence it must be prevented from releasing out
into atmosphere.
43
maintenance, but life is expected to be about 20 years, provided that the vacuum is
maintained. Because of the high dielectric strength of vacuum, the interrupters are
small. The gap between the contacts is about 1 cm for 15 kV interrupters, 2 mm for
3 kV interrupters.
44
There are two types of arc shapes. For interrupting current up to 10KA, the arc
remains diffused and the form of vapor discharge and cover the entire contact
surface .Above 10 KA the diffused arc is constricted considerably by its own
magnetic field and it contracts. The phenomena then gives rise to over heating of
contact at its center. In order to prevent this, the design of the contacts should be
such that the arc does not remain stationary but keeps travelling by its own
magnetic field .Specially designed contact shape of vacuum circuit breaker make
the constricted stationary arc travel along the surface of the contacts, thereby
causing minimum and uniform contact erosion.
ADVANTAGES OF VCB:
45
46
Ni = f (Ii)
REFERENCE [1]
47
REFERENCE [2]
48
49
For a given value of x, say x1, there will be a difference between the value y1 and
the corresponding value as determined by the best fitting curve. This distance,
D1, is referred to as a residual. A residual is the difference from the actual y-value
and the value obtained by plugging the x-value (that goes with the y-value) into the
best fitting curve.
50
REFERENCE [1]
51
REFERENCE [1]
The total wear Qg of a VCB contact system is certain once contact material and
Structure type is determined. The electrical endurance function can be drawn by
the method proposed based on the least square method.
FIG: 3
REFERENCE [1]
52
This diagram represents the relationship between the total electrical wear Qg and
different breaking current for a circuit breaker which is rated for 1600A (Normal
Load Current).
As stated earlier, the total Electrical Wear, a Circuit breaker can
sustain remains constant once contact material and structure type is determined. So
whatever may be the breaking current magnitude the total electrical wear the
breaker can sustain would be constant. So the value of current index is unique
and can also be obtained by analyzing the diagram as in figure 3.
For the circuit breakers having normal load current equal to 630A, 800A, 1200A
(using figure 2) the relation between breaking current Ib and breaking numbers Ns
turns out to be
N (I) = (174.44/I)2.2
Circuit Breakers having normal load current equal to 630A are used in outgoing
feeders and capacitor bank.
53
Having done this much, we now turn towards calculating the total cumulative
breaking current the breaker would see, had it witnessed its whole life-time.
For Breakers rated at 1600 A, a fault current value of 6.5 KA is taken as the most
probable fault current and the total cumulative breaking current is calculated as
follows:
54
That is, these much number of operations on a fault current level of 5.5KA, counts
for complete life time of vacuum circuit breaker.
Hence, the total cumulative breaking current a 12KV,630A vacuum circuit breaker
can see in its entire life-time can be calculated using simple mathematics as
follows
(KA)2 = 2008*(5.5)2
=60742
An alarm signals will pop up on SCADA, as the cumulative breaking current value
reaches 70% of this value.
70% OF (60742)
=0.7*(60742)
=42519
RG-5 -11KV
55
(KA)2
900
800
7 00
600
500
400
300
200
100
0
(KA)2
56
PUSA -11KV
(KA)2
7 00
600
500
400
300
200
100
0
(KA)2
57
KHAMPUR
(KA)2
3000
2500
2000
1500
1000
500
0
(KA)2
58
59
RG-6
(KA)2
3500
3000
2500
2000
1500
1000
500
0
(KA)2
BADLI GRID
60
(KA)2
5000
45 00
4000
35 00
3000
25 00
2000
500
11000
5 00
0
MANGOLPURI GRID -1
(KA )2
61
(KA)2
8000
7 000
6000
5000
4000
3000
2000
1000
0
MANGOLPURI GRID -2
(KA)2
62
(KA)2
1800
1600
1400
1200
1000
800
600
400
200
0
RG -3
(KA)2
63
(KA)2
1600
1400
1200
1000
800
600
400
200
0
(KA)2
64
CENNET (NSP)
65
(KA)2
900
800
7 00
600
500
400
300
200
1 00
0
(KA)2
66
(KA)2
2000
1
800
1
600
1
400
1
200
1 000
800
600
400
200
0
(KA)2
67
Based on data from last two years in 50 grids, average fault current experienced by
11KV vacuum circuit breakers in incoming feeders is 6.5 KA.
Referring to electrical endurance curve of 12 KV,1600A vacuum circuit breaker,
the permissible number of operations (NS) for this value of fault current can be
calculated as follows N (I) = (273.53/I)1.93
N(I) = (273.53/6.5)1.93
=1363
RG-5 -11KV
68
(KA)2
800
(KA)2
600
400
200
0
BUS SECTION -1
PUSA -11KV
I/C TRF -2
I/C TRF-3
69
(KA)2
2000
(KA)2
1500
1000
500
0
I/C -1
RG-6
BUS SECTION-1
70
(KA)2
2000
1500
(KA)2
1000
500
0
BUS COUPLER 11KV I/C NO-2 BUS COUPLER 11KV I/C NO-1
BADLI GRID
71
(KA)2
1800
1600
1400
1200
1000
800
600
400
200
0
(KA)2
72
MANGOLPURI GRID -1
(KA)2
600
500
400
300
200
100
0
MANGOLPURI GRID -2
(KA)2
73
(KA)2
1400
1200
1000
800
600
400
200
0
(KA)2
INCOMER -1
RG -3
BUS SEC-2
INCOMER -2
74
(KA)2
1400
1200
1000
(KA)2
800
600
400
200
0
I/C TR. NO-3
CENNET (NSP)
BUS SEC -2
I/C TRF NO -2
75
(KA)2
2500
2000
1500
1000
500
0
(KA)2
76
(KA)2
3000
2500
(KA)2
2000
1500
1000
500
0
11KV I/C NO-2
77
LOCAL TRANSFORMER
78
CUMULATIVE BREAKING
CURRENT
50
0
WAY FORWARD
PROCESS FLOW CHART FOR ON-LINE MONITORING
79
CONCLUSION
With this project, a study on life cycle of vacuum circuit breaker (VCB) based on
current rating and make has been done. This type of study has been done for the
first time. The possibility of propagation of monitored parameter to SCADA has
been studied. This will enable the conditioning monitoring of circuit breaker in real
time domain.
We have done:
1.
2.
3.
4.
REFERENCES
80
81