Design Manual Post bases

Post bases

Fast, simple and precise: for the best result

Welcome to
the world of PITZL
This is Pitzl
As a leading full-range supplier for wood connection systems, we are consistently trying to develop and optimise our products
further. The Pitzl range includes post bases, balcony and fence posts, plug-in connector systems as well as post-purlin connections.
Naturally, we also offer individual, custom-made solutions for your specific range of applications.
All Pitzl post bases and connectors can be used with screws from different manufacturers.

ETA-10/0413
European Technical Approval
All post bases and post-purlin connectors of Pitzl GmbH & Co. KG have been approved through ETA -10/0413
Holder of approval:

Pitzl GmbH & Co. KG, Siemensstrae 26, DE-84051 Altheim


Tel.: +49 (0) 8703 9346-0, Fax: +49 (0) 8703 9346-55, Internet: www.pitzl.de
Generic type and use of construction product:

Three-dimensional nailing plate (Post bases for the support of timber columns and Connectors for posts and purlins
as load-bearing elements as load-bearing elements)
(Valid from: 2013-05-09 to: 2018-05-09)
Manufacturing plant:

Pitzl GmbH & Co. KG, Siemensstrae 26, DE-84051 Altheim

Seite 2

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Post bases

Contents
A/ Design values
1.

General

p.4

2.

Design concept

p.8

3.

Design values of the post bases ETA-10/0413 (CE)

p.11

3.1.

System 10930/10931

p.11

3.2.

Right/left thread

p.15

3.3

Stainless steel V2A

p.18

3.4

Heavy-duty version

p.19

3.5

Threaded rod

p.27

3.6

2 parts

p.32

3.7

Rigid version, hot-dip galvanized

p.38

3.8

For embedding in concrete

p.40

4.

Design values of the post-purlin connectors ETA-10/0413 (CE)

p.43

5.

Compressive load-carrying capacity of post bases following structural standards

p.44

B/ Characteristic values
1.

Characteristic load-carrying capacity of the post bases acc. to ETA-10/0413 (CE)

p.46

2.

Characteristic load-carrying capacity of the post bases acc. to Eurocode

p.57

3.

Characteristic load-carrying capacity of the post-purlin connectors acc. to ETA-10/0413 (CE)

p.59

Seite 3

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

A/ Design values
1. General
Pitzl post bases are intended to fasten timber pillars and posts as
load-bearing elements in light-weight structures (such as carports,
pergolas, terraces etc.) or for larger timber pillars.
The load-carrying capacities of the Pitzl post bases were determined
through static calculations and approval notifications referring to the
post bases listed in the ETA-10/0413.
European Technical Approval: ETA-10/0413
Construction materials:
Timber:
Solid timber from softwood, min. strength class C24 in accordance
with EN 338:2010-02
Fasteners:
Wood plate screws for the post bases, wood countersunk head screws
for the SPP connectors, 10 x min 120 mm (thread length 100 mm)
acc. to EN 14592 or ETA, dowels 12 mm with Rm 360 N/mm
Steel quality of the post bases and SPP connectors:
steel grade S235JR acc. to EN 10025-2:2005-04 ReH 235 N/mm,
Rm 360 N/mm
steel grade 1.4301 acc. to EN 10088-3:2005-09 Rp0,2 190 N/mm
and Rm 500 N/mm
Threaded rod:
Strength class 4.8 acc. to DIN EN ISO 898-1:2009-08
Rpf 320 N/mm and Rm 400 N/mm, for stainless steel:
Property class 70 acc. to EN ISO 3506-1:2009
Tube profile:
Steel grade P235 acc. to EN 10216-1:2004 or EN 10217-1:2005
ReH 235 N/mm, Rm 360 N/mm

Fasteners:
Dowels, 12 mm, fully-threaded wood screws (plate screws for post
bases and countersunk head screws for the SPP connectors), 10 x
min. 120 mm (minimum thread length: 100 mm) acc. to EN 14592
(DIN 571 and threads acc. to DIN 7998) or with ETA are used as
fasteners. The wood screws require pre-drilling in accordance with the
provisions in EN 1995-1-1, Fig. 10.4.5. Alternatively, the pre-drilling
details in the screws' ETA should be observed.
Posts:
The characteristic values for solid timber of strength class C24
according to EN 338:2003-09 were used as the basis for the posts.
The minimum dimensions for the posts must be observed here. The
end grain face of the post has to lie flat against the base plate, unless
stated otherwise.
Post base installation:
The load is transferred into the ground either via a threaded rod or a
tube profile. The minimum insertion depth of the threaded rods into
the turnbuckle is equal to the single diameter of the threaded rod.
Proper anchoring of the post base in the concrete is to be demonstrated with the stated tie bolt tensile force.
The post base and the column must be installed plumb. Unintended
skewed positioning of the support was not taken into account when
determining the load-carrying capacities. The post base shall be
installed centrically in the crosssection of the timber column and with
the end grain plane on the base plate.
Tables A.1 and A.2 contain the technical data for the post bases and
the post-purlin connectors of ETA-10/0413.

Page 4

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Corrosion protection:
Zinc coating protects the post bases from corrosion. If the post bases
are to be used indoors (service class 1) or in roofed outdoor areas
(service class 2), galvanic zinc coating is sufficient. When in unprotected outdoor areas (service class 3), corrosion protection is ensured
through hot-dip galvanized coating with a minimum thickness of 70
microns in accordance with EN ISO 1461 or through ZiNiP coating
with a minimum thickness of 8 microns. Fasteners must also be
protected by zinc coating for outdoor use (zinc-coating Fe/Zn 25c in
accordance with EN ISO 2081) or be made of stainless steel.
Anchorage of the post bases in the foundation:
No performance has been determined in relation to the anchorage of
the post bases in the foundation. It must be checked by the designer
of the structure to ensure it is not less than the post base capacity
and, if necessary, the post base capacity reduced accordingly. (Loadcarrying capacity of the bolt anchors: cf. p.9)

Page 5

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Table A.1: Technical data of the post bases of ETA-10/0413


Fasteners:
For all post bases: 4 fully threaded plate screws 10 x min. 120 mm (thread length: min. 100 mm)
For the post bases 1003.00 and 1007.00: 1 dowel 12 mm in the upper hole
Post bases

Post

Post bases

Post

Type

Item no.

Adjustment range
[mm]

1001

1001.00

125

120/120

10921.00

142 - 207

120/120

1003

1003.00

125

120/120

10921.00 A

167 - 232

120/120

1005

1005.00

160

140/140

10921.00 B

227 - 292

120/120

1007

1007.00

160

140/140

10921.00 C

257 - 322

120/120

1008
1014

1015

1016

10920

min w/h [mm]

Type

Item no.

Adjustment range
[mm]

min w/h [mm]

1008.08

250

150/150

10921.00 D

327 - 392

120/120

1014.00

40 - 156

120/120

10921.10

82 - 92

120/120

1014.08

40 - 156

100/100

10921.30

150 - 210

120/120

1015.00

40 - 256

120/120

10921.36

160 - 220

120/120

1015.08

40 - 256

100/100

10921.36 A

185 - 245

120/120

1016.00

40 - 256

120/120

10921.36 B

245 - 305

120/120

1016.10

40 - 336

120/120

10921.36 C

275 - 335

120/120

1016.20

40 - 506

120/120

10921.36 D

345 - 405

120/120

1016.08

40 - 256

100/100

10921.40

190 - 255

120/120

1016.18

40 - 336

100/100

10930.00

170 - 285

120/120

1016.28

40 - 506

100/100

10930.00 A

195 - 310

120/120

1016.30

40 - 260

120/120

10930.00 B

255 - 370

120/120

1016.31

40 - 340

120/120

10930.00 C

285 - 400

120/120

1016.32

40 - 510

120/120

10930.10

110 - 200

120/120

10920.00

142 - 207

120/120

10930.30

195 - 285

120/120

10920.00 A

167 - 232

120/120

10930.35

bis 200

120/120

10920.00 B

227 - 292

120/120

10930.45

bis 300

120/120

10920.00 C

257 - 322

120/120

10930.36

205 - 300

120/120

10920.00 D

327 - 392

120/120

10930.36 A

230 - 325

120/120

10920.30

150 - 210

120/120

10930.36 B

290 - 385

120/120

10930.36 C

320 - 415

120/120

10921

10930

Page 6

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Post bases
Type

10930

10931

Post

Post bases

Item no.

Adjustment range
[mm]

min w/h [mm]

10930.50

125

10930.51

160

10930.52

200

120/120

10930.55

125

120/120

10930.56

160

10930.57

200

10930.70
10930.71

Post
Item no.

Adjustment range
[mm]

min w/h [mm]

120/120

10933.00

125

140/140

120/120

10933.10

160

140/140

10933.20

200

140/140

10933.50

125

140/140

120/120

10933.60

160

140/140

120/120

10933.70

200

140/140

bis 100

120/120

10934.00

bis 100

140/140

bis 180

120/120

10934.10

bis 180

140/140

10930.73

bis 100

120/120

10934.30

bis 100

140/140

10930.74

bis 180

120/120

10934.31

bis 180

140/140

10931.00

170 - 285

140/140

10935.00

bis 200

140/140

10935.50

bis 200

120/120

10945.00

bis 300

140/140

bis 300

120/120

10931.00 A

195 - 310

140/140

10931.00 B

255 - 370

140/140

Type

10933

10934

10935

10945

10931.00 C

285 - 400

140/140

10945.50

10931.10

110 - 200

140/140

10950.00

125

120/120

10950.10

160

120/120

10950.20

200

120/120

125

120/120

10931.30

195 - 285

140/140

10931.36

205 - 300

140/140

10950

10931.36 A

230 - 325

140/140

10950.50

10931.36 B

290 - 385

140/140

10950.60

160

120/120

10931.36 C

320 - 415

140/140

10950.70

200

120/120

10952.00

146 - 211

120/120

10952

Table A.2: Technical data of the SPP connectors (ETA-10/0413)


Fasteners:
- 4 fully threaded countersunk head screws 10 x min. 120 mm (thread length: min. 100 mm)
- Threaded rod: M10, M12 or M16 depending on the SPP connector
Post-purlin connector

Fasteners

Post [mm]

Purlin [mm]

Type

Dimensions

Item no.

Screws *

Threaded rod

min w/h

min w/h

8710

M10

8710

4x F 10x120mm

M10 4.8
+ washer 58 mm

120/120

120/90

8712

M12

8712

4x F 10x120mm

M12 4.8
+ washer 58 mm

120/120

120/90

8716

M16

8716

4x F 10x120mm

M16 4.8
+ washer 68 mm

120/120

120/90

* F = full-thread wood screw

Page 7

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

2. Design concept
Post bases by Pitzl must be designed in accordance with the applicable timber and steel construction standards Eurocode 5 and Eurocode 3 or
with an equivalent national code.
The following design values for the load-carrying capacity were determined in accordance with the European standards Eurocode 5: Design
of timber structures (EN 1995-1-1:2010-12) and Eurocode 3 Design of steel structures (EN 1993-1:2010-12), which means they reflect the
current state of technology regarding safety concept, cross-section determination and design.
The characteristic loads on the load side are increased by partial safety factors (G= 1,35 for constant loads, Q= 1,5 for variable loads). While
on the resistance side, the characteristic load-carrying capacities are reduced by dividing through the partial safety coefficient M.

where:



(basic combination) acc. to EN 1990








Page 8



Pitzl

DIN


18 800


Metallbau
GmbH & Co. KG

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Eurocode 5:
"Design of timber structures"

For wood materials, the effect of the service class and the load duration is taken into account additionally through the modification coefficient
k .

mod



M = 1,3 for solid timber


and glued laminated timber acc. to DIN EN 1995-1-1/NA:2010-12 (national Annex: Germany)

k acc. to EN 1995-1-1:2010-12
cient
Modification coeffi
mod

Material

service
class

Load duration class

Permanent action

Long term action

Medium term action

Short term action

instantaneous action

0,60

0,70

0,80

0,90

1,10

0,70

0,80

0,90

1,10

0,55

0,65

0,70

0,90

Solid timber and glued


0,60
laminated timber 2
3
0,50

Eurocode

3:
of steel

"Design
structures"




coefficients
Partial
safety
M for steel
failure acc. to DIN EN 1993-1-1/NA:2010-12:

M0 = 1,0

M1
= 1,1
Eurocode 3 - National Annex: Germany


M2 =1,25

 value

load-carrying capacity of the post bases:

Design
of
the

In


of failure

the case
of
the timber part or the metal fasteners, the design value for the load-carrying capacity shall be calculated in accordance
with EN 1995-1-1.
To
do
so, the characteristic load-carrying capacity values have to be divided by the partial safety coefficient and in addition

with

multiplied
the
coefficient kmod.
In the case of steel
the design value for the load-carrying capacity shall be calculated in accordance with EN 1993-1-1 by reducing the

failure,
load-carrying capacity values through different partial safety coefficients.
characteristic


The design
value

for the
load-carrying capacity of the post base is always the lowest of all load-carrying capacity values.

value
of the load
Design value of the load-carry Design


carrying capacity in the case of


ing capacity in the case of steel
failure ofthe
timber
part
or
of
failure acc. to Eurocode 3

5
the fasteners acc.
to Eurocode

This means that the load-duration class and


the service class are taken into account for the case of failure of the timber and the fasteners.

Also,
the
different
partial
safety
coeffi
cients

M for steel or timber failure are correctly taken into account, as well.

Load-carrying capacity of the bolt anchors:


load-carrying capacity of the post base under tensile load F (Tension) and horizontal load H1 / H2 is valid on condition that the load-carryThe

ing capacity of the bolt
anchors in concrete is sufficient.
RAnchor,ax,d > FA+Fd,Tension /4
where:
RAnchor,ax,d
FA
Fd, Tension

Design value of the tensile load-carrying capacity per bolt anchor


Tensile force per bolt anchor under horizontal load
Design value of the tensile load of the post base
Page 9

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

 Design


Post
bases

Manual

Fast, simple and precise: for the best result








load:

Combined

Forthe load-carrying
capacity of the post bases and the SPP connectors with a combination
of horizontal loads H and vertical loads F, the

following applies:


where:


EF,d
Design value
of the load
in load cases F (Compression) or F (Tension) in N
or

RF,d
Design value
load-carrying capacity in load cases
F (Compression)
F
(Tension)

 in N

ofthe

EH,d
Design value
of the load
in load
cases H1 or H2 in N



RH,d
Design value of
the
load-carrying
capacity in load cases H1 or H2 in N

Increase of the tensile load-carrying capacity:

capacityof
The load-carrying
the fasteners in the timber was calculated assuming an effective thread length
of 100 mm for the screws.

When using
screws
value
for the
capacity may be calculated using
effective thread lengths, the

tensile
load-carrying
dimensioning

with larger

the following formula:


and 

where:

RFd, (Tension)
Design value of the load-carrying capacity in the load case F (Tension) for the thread length ef in kN
ef
Effective length of the screws in mm
Rd,(Tension),steel failure
Design value of the load-carrying capacity due to steel failure in kN


 

NB:
Possible for all post bases "System 10930/10931", "Heavy-duty Version", "2 parts", "Rigid version, hot-dip galvanized", "For embedding in
1015.08
and all post-purlin connectors
concrete", the post bases 1015.00,

 

Example:


  



Design value of the tensile load-carrying capacity with 200mm full-thread screws (ef= 190mm),
Short term

action:

  


 and  

Designvalues in service
class 3 (outdoor use):
 
Design values for the load-carrying capacity if the timber failure case (timber part or fastener) is decisive:
In service class 3, the values from the table must be reduced in accordance with the modification coefficients kmod to apply.
Example with post base 1001.00 for Fd (Compression) in service class 3:
LDC permanent: Fd = 41,5 x 0,5/0,6
LDC long:
Fd = 48,5 x 0,55/0,7
LDC medium:
Fd = 55,4 x 0,65/0,8
LDC short:
Fd = 62,3 x 0,7/0,9
LDC instantaneous: Fd = 76,2 x 0,9/1,1
Design values of the load-carrying capacity if the steel failure case is decisive:
In service class 3: no correction factors required.
Page 10

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


3. Design values of the post bases ETA-10/0413 (CE)
The following design values of the load-carrying capacity per post base are calculated with maximum clearance between base plate and foundation in accordance with the Eurocodes (EN 1993-1-1:2010-12 and EN 1995-1- 1:2010-12) and the National Annexes: Germany (DIN EN
1993-1-1/NA:2010-12 and DIN EN 1995-1-1/NA:2010-12). For smaller clearances, the load-carrying capacity in the case of a decisive steel
failure can be increased by linear interpolation (see Characteristic load carrying capacity, p. 47)

3.1 System 10930/10931


Post base 10930.00 A/B/C:
Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

medium 0,8

10930.00
Fd (Compression)

10930.00 A
10930.00 B

41,5

H1,d

All Types

11,3*

10930.00

1,3

10930.00 A

1,2

10930.00 B

1,0

1,3**

10930.00 A

1,2**

10930.00 B

1,0**

All Types

13,2*

0,9

10930.00

10930.00 C
FA

64,7

52,0

10930.00 C

H2,d

68,4

56,1

10930.00 C
Fd (Tension)

instantaneous 1,1

62,3

55,4

48,5

short 0,9

0,9**
Tensile force per bolt anchor under maximum horizontal load (Hd): 2,7kN

* In case of a longer ground plate, l=220mm, the design value is: 13,2 x 0,6= 7,9kN (steel failure)
** In case of a longer ground plate, l=220mm, the design value is:
Post bases 10930.00: 1,6 x 0,6= 1,0kN
Post bases 10930.00 A: 1,4 x 0,6= 0,8kN
Post bases 10930.00 B: 1,2 x 0,6= 0,7kN
Post bases 10930.00 C: 1,1 x 0,6= 0,7kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Tension) in service class 3, LDC short: Fd = 11,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

10930.00

170 - 285

10930.00 A

195 - 310

10930.00 B

255 - 370

10930.00 C

285 - 400

10930.00

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10
Page 11

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post base 10930.10:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)
H1,d

permanent 0,6

long 0,7

41,5

48,5

medium 0,8
55,4
-

10930.10

short 0,9

instantaneous 1,1

62,3

76,2

11,3*

13,2*

1,8

H2,d

1,8**

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,6kN

* In case of a longer ground plate, l=220mm, the design value is: 13,2 x 0,6= 7,9kN (steel failure)
** In case of a longer ground plate, l=220mm, the design value is: 2,2 x 0,6= 1,3kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

10930.10

110 - 200
10930.10

Page 12

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Post base 10931.00 A/B/C:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

medium 0,8

10931.00
Fd (Compression)

10931.00 A
10931.00 B

41,5

H1,d

All Types

52,0
-

11,3*

10931.00

1,3

10931.00 A

1,2

10931.00 B

1,0

10931.00 C

H2,d

1,3**

10931.00 A

1,2**

10931.00 B

1,0**

All Types

13,2*

0,9

10931.00

10931.00 C
FA

64,7
56,1

10931.00 C
Fd (Tension)

instantaneous 1,1
68,4

62,3

55,4

48,5

short 0,9

0,9**
Tensile force per bolt anchor under maximum horizontal load (Hd): 2,7kN

* In case of a longer ground plate, l=220mm, the design value is: 1,32 x 0,6= 7,9kN (steel failure)
** In case of a longer ground plate, l=220mm, the design value is:
Post bases 10931.00: 1,0kN
Post bases 10931.00 A: 0,8kN
Post bases 10931.00 B and C: 0,7kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Tension) in service class 3, LDC short: Fd = 11,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no

Adjustment range [mm]

10931.00

170 - 285

10931.00 A

195 - 310

10931.00 B

255 - 370

10931.00 C

285 - 400

10931.00

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10
Page 13

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post base 10931.10:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

Fd (compressive)
Fd (tensile)
H1,d

permanent 0,6

long 0,7

41,5

48,5

medium 0,8
55,4
-

10931.10

short 0,9

instantaneous 1,1

62,3

76,2

11,3*

13,2*

1,8

H2,d

1,8**

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,6kN

* In case of a longer ground plate l= 220mm, the design value is: 13,2 x 0,6= 7,9kN (steel failure)
** In case of a longer ground plate, l=220mm, the design value is: 1,3kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

10931.10

110 - 200
10931.10

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10

Page 14

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


3.2 Right/left thread
Post base 10920.00 A/B/C/D:
Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

medium 0,8

short 0,9

55,4

62,3

instantaneous 1,1

10920.00

76,2

10920.00 A
Fd (Compression)

10920.00 B

41,5

48,5

67,8

10920.00 C

63,5

10920.00 D
Fd (Tension)

H1,d

H2,d

All Types

53,5
-

7,4*

10920.00

1,8

10920.00 A

1,6

10920.00 B

1,3

10920.00 C

1,1

10920.00 D

1,0

10920.00

1,2*

10920.00 A

1,1*

10920.00 B

0,9*

10920.00 C

0,8*

10920.00 D

0,6*

10920.00
10920.00 A
FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,7kN

10920.00 B
10920.00 C

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,5kN

10920.00 D

Tensile force per bolt anchor under maximum horizontal load (Hd): 3,1kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Post bases 10920.00/A/B/C: Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no

Adjustment range [mm]

10920.00

142 - 207

10920.00 A

167 - 232

10920.00 B

227 - 292

10920.00 C

257 - 322

10920.00 D

327 - 392

10920.00

Page 15

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post base 10921.00 A/B/C/D:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

medium 0,8

short 0,9

55,4

62,3

instantaneous 1,1

10921.00

68,6

10921.00 A
Fd (Compression)

10921.00 B

41,5

48,5

67,8

10921.00 C

63,5

10921.00 D
Fd (Tension)

H1,d

H2,d

FA

53,5

All Types

7,4*

10921.00

1,8

10921.00 A

1,6

10921.00 B

1,3

10921.00 C

1,1

10921.00 D

1,0

10921.00

1,2*

10921.00 A

1,1*

10921.00 B

0,9*

10921.00 C

0,8*

10921.00 D

0,6*

10921.00

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,7kN

10921.00 A

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,4kN

10921.00 B

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,2kN

10921.00 C

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,3kN

10921.00 D

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,8kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Post bases 10921.00 A/B/C: Fd (Compression) in NKL3, KLED kurz: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no

Adjustment range [mm]

10921.00

142 - 207

10921.00 A

167 - 207

10921.00 B

227 - 292

10921.00 C

257 - 322

10921.00 D

327 - 392

10921.00

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10

Page 16

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Post base 10921.10:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)
H1,d

permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

41,5

48,5

55,4

62,3

68,6

10921.10

7,4*
4,0

H2,d

2,8*

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,6kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

10921.10

82 - 92

Post base 10921.40:


Dimensioning values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

Fd (Comression)
Fd (Tension)
H1,d

permanent 0,6

long 0,7

41,5

48,5

medium 0,8

short 0,9

55,4

62,3

10921.40

instantaneous 1,1
68,6
7,4*

1,4

H2,d

1,0*

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 1,8kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

10921.40

190 - 255

10921.10

10921.40

Page 17

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

3.3 Stainless steel V2A


Post base 10952.00:
Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)
H1,d

permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

41,5

48,5

55,4

62,3

67,0

11,3**

11,8**

10952.00

2,5

H2,d

2,5*

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 3,8kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6
** In case of a longer ground plate, l=220mm, the design value is: 7,1kN (steel failure)

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

10952.00

146 - 211

10952.00

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10

Page 18

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


3.4 Heavy-duty version
Post base 1016.30:
Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction
Fd (Compression)
Fd (Tension)

Load duration class (LDC), kmod

Type
All Types
Nut, welded
Tension plate

H1,d

All Types

H2,d

All Types

FA

All Types

permanent 0,6

long 0,7

medium 0,8

73,5

85,7

98,0

short 0,9

instantaneous 1,1

110,2

128,6

11,3

13,8**

6,0

7,4

2,6
2,6*
Tensile force per bolt anchor under maximum horizontal load (Hd): 6,7kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6
** In case of a longer ground plate l= 220mm, the design value is: 12,4kN (steel failure)

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 110,2 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1016.30

40 - 260

Post base 1016.31:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

73,5

85,7

98,0

110,2

115,1

Nut, welded

Tension plate

H1,d

All Types

2,0

H2,d

All Types

2,0*

FA

All Types

11,3

13,8**

6,0

7,4

Tensile force per bolt anchor under maximum horizontal load (Hd): 4,9kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6
** In case of a longer ground plate l= 220mm, the design value is: 12,4kN (steel failure)

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 110,2 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1016.31

40 - 340

1016.30

1016.31

Page 19

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post base 1016.32:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Type

Fd (Compression)

alle Typen

Fd (Tension)

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

84,5

73,5

Nut, welded

Tension plate

H1,d

All Types

1,4

H2,d

All Types

1,4*

FA

All Types

11,3

13,8**

6,0

7,4

Tensile force per bolt anchor under maximum horizontal load (Hd): 5,1kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6
** In case of a longer ground plate l= 220mm, the design value is: 12,4kN (steel failure)

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Tension) with Nut, welded in service class 3, LDC short: Fd = 11,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1016.32

40 - 510

Post base 10920.30:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)
H1,d

permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

67,4

78,7

89,9

101,1

123,6

11,3

13,8**

10920.30

3,0

H2,d

3,0*

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 3,1kN

* In case of a longer ground plate, l=220mm, the design value is: 3,3 x 0,6= 2,0kN
** In case of a longer ground plate l= 220mm, the design value is: 12,4kN (steel failure)

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 101,1 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

10920.30

150 - 210

1016.32

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

10920.30

see p. 9
see p. 10
see p. 10

Page 20

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Post base 10921.30:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)
H1,d

permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

60,5

70,6

80,7

90,8

97,9

11,3

13,8**

10921.30

3,0

H2,d

3,0*

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 4,5kN

* In case of a longer ground plate, l=220mm, the design value is: 3,3 x 0,6= 2,0kN
** In case of a longer ground plate l= 220mm, the design value is: 12,4kN (steel failure)

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 90,8 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

10921.30

150 - 210

10921.30

Page 21

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post base 10921.36 A/B/C/D:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

medium 0,8

10921.36

10921.36 B

instantaneous 1,1
149,3

128,6

10921.36 A
Fd (Compression)

short 0,9

85,7

134,2

114,3

100,0

124,5

10921.36 C

119,5

10921.36 D
Fd (Tension)

Hd

All Types

11,3

10921.36

3,1

10921.36 A

2,8

10921.36 B

2,2

10921.36 C

2,1

10921.36 D

1,7

10921.36
10921.36 A
FA

107,1

10921.36 B

13,8

Tensile force per bolt anchor under maximum horizontal load (Hd): 5,1kN
Tensile force per bolt anchor under maximum horizontal load (Hd): 5,0kN

10921.36 C

Tensile force per bolt anchor under maximum horizontal load (Hd): 5,3kN

10921.36 D

Tensile force per bolt anchor under maximum horizontal load (Hd): 5,1kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Tension) in service class 3, LDC short: Fd = 11,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no

Adjustment range [mm]

10921.36

160 - 220

10921.36 A

185 - 245

10921.36 B

245 - 305

10921.36 C

275 - 335

10921.36 D

345 - 405

10921.36

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10

Page 22

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Post base 10930.30:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)
H1,d

permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

58,1

67,7

77,4

87,1

106,4

11,3

13,8**

10930.30

2,2

H2,d

2,2*

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 4,5kN

* In case of a longer ground plate, l=220mm, the design value is: 2,5 x 0,6= 1,5kN
** In case of a longer ground plate l= 220mm, the design value is: 12,4kN (steel failure)

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 87,1 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

10930.30

195 - 285

10930.30

Page 23

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post base 10930.36 A/B/C:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

medium 0,8

short 0,9

140,5

10921.36
Fd (Compression)

10921.36 A
10921.36 B

77,8

90,8

127,5

116,7

103,8

117,5

10921.36 C
Fd (Tension)

Hd (Horizontal)

112,1

All Types

11,3

10921.36

2,5

10921.36 A

2,0

10921.36 B

1,7

10921.36 C

1,5

10921.36
FA

instantaneous 1,1

13,8

Tensile force per bolt anchor under maximum horizontal load (Hd): 5,4kN

10921.36 A
10921.36 B
10921.36 C

Tensile force per bolt anchor under maximum horizontal load (Hd): 4,7kN
Tensile force per bolt anchor under maximum horizontal load (Hd): 4,5kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in NKL3, KLED mittel: Fd = 103,8 x 0,65/0,8
Steel failure is decisive, no correction factors required in service class 3.
Item no

Adjustment range [mm]

10930.36

205 - 300

10930.36 A

230 - 325

10930.36 B

290 - 385

10930.36 C

320 - 415

10930.36

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10

Page 24

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Post base 10931.30:
Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)
H1,d

permanent 0,6

long 0,7

56,7

66,1

medium 0,8

short 0,9

instantaneous 1,1

75,6

85,0

103,9

11,3

13,8**

10931.30

2,2

H2,d

2,2*

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 4,5kN

* In case of a longer ground plate, l=220mm, the design value is: 2,5 x 0,6= 1,5kN
** In case of a longer ground plate l= 220mm, the design value is: 12,4kN (steel failure)

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 85,0 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

10931.30

195 - 285

10931.30

Page 25

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post base 10931.36 A/B/C:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

medium 0,8

short 0,9

10931.36
Fd (Compression)

140,5

10931.36 A
10931.36 B

77,8

90,8

127,5

116,7

103,8

117,5

10931.36 C
Fd (Tension)

Hd (Horizontal)

instantaneous 1,1

112,1

All Types

11,3

10931.36

2,5

10931.36 A

2,0

10931.36 B

1,7

10931.36 C
FA

13,8

1,5
Tensile force per bolt anchor under maximum horizontal load (Hd): 5,6kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC medium: Fd = 103,8 x 0,65/0,8
Steel failure is decisive, no correction factors required in service class 3.
Item no

Adjustment range [mm]

10931.36

205 - 300

10931.36 A

230 - 325

10931.36 B

290 - 385

10931.36 C

320 - 415

Post base 1008.08:


Design values of the load-carrying capacity in kN per post base
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)

permanent 0,6

long 0,7

medium 0,8

176,1

205,4

234,8

5,4

6,2

1008.08

Hd (Horizontal)

4,6

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 11,1kN

short 0,9

instantaneous 1,1
253,9

11,3

13,8

6,9

8,5

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC medium: Fd = 234,8 x 0,65/0,8
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Height [mm]

1008.08

250
10931.36

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

1008.08

see p. 9
see p. 10
see p. 10

Page 26

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


3.5 Threaded rod
Post base 1014.00:
Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction
Fd (Compression)
Fd (Tension)
H1,d

Load duration class (LDC), kmod

Type
All Types

permanent 0,6

long 0,7

medium 0,8

short 0,9

41,5

48,5

55,4

62,3

Nut, welded

3,6

All Types

H2,d

All Types

FA

All Types

76,2
7,4*

Tension plate

instantaneous 1,1

2,8
1,7*
Tensile force per bolt anchor under maximum horizontal load (Hd): 3,1kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1014.00

40 - 156

Post base 1014.08:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction
Fd (Compression)
Fd (Tension)
H1,d

Load duration class (LDC), kmod

Type
All Types
Nut, welded
Tension plate

permanent 0,6

long 0,7

medium 0,8

short 0,9

26,1

30,4

34,8

39,1

H2,d

All Types

FA

All Types

47,8
7,4*

All Types

instantaneous 1,1

3,6
2,8
1,7*

Tensile force per bolt anchor under maximum horizontal load (Hd): 3,1kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 39,1 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1014.08

40 - 156

1014.00
1014.08

Page 27

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post base 1015.00:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

41,5

48,5

55,4

62,3

73,5

Nut, welded

Hd

All Types

FA

All Types

11,3

Tension plate

13,8
3,6

1,7
Tensile force per bolt anchor under maximum horizontal load (Hd): 3,3kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1015.00

40 - 256

Post base 1015.08:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

26,1

30,4

34,8

39,1

47,8

Nut, welded

Hd

All Types

FA

All Types

11,3

Tension plate

13,8
3,6

1,7
Tensile force per bolt anchor under maximum horizontal load (Hd): 3,3kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 39,1 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1015.08

40 - 256

1015.00
1015.08

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10

Page 28

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Post base 1016.00:
Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)
H1,d

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

41,5

48,5

55,4

62,3

73,5

Nut, welded

7,4*

Tension plate

3,6

All Types

H2,d

All Types

FA

All Types

1,7
1,0*
Tensile force per bolt anchor under maximum horizontal load (Hd): 3,1kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1016.00

40 - 256

Post base 1016.08:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)
H1,d

Load duration class (LDC), kmod

Nut, welded
Tension plate

permanent 0,6

long 0,7

medium 0,8

short 0,9

26,1

30,4

34,8

39,1

H2,d

All Types

FA

All Types

47,8
7,4*

All Types

instantaneous 1,1

3,6
1,7
1,0*

Tensile force per bolt anchor under maximum horizontal load (Hd): 3,1kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 39,1 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1016.08

40 - 256

1016.00
1016.08

Page 29

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post base 1016.10:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction
Fd (Compression)
Fd (Tension)

Load duration class (LDC), kmod

Type
All Types

permanent 0,6

long 0,7

medium 0,8

41,5

48,5

55,4

Nut, welded

All Types

H2,d

All Types

FA

All Types

instantaneous 1,1
62,0
7,4*

Tension plate

H1,d

short 0,9

3,6
1,3
0,8*

Tensile force per bolt anchor under maximum horizontal load (Hd): 3,1kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1016.10

40 - 336

Post base 1016.18:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

26,1

30,4

34,8

39,1

47,8

Nut, welded

7,4*

Tension plate

3,6

H1,d

All Types

1,3

H2,d

All Types

0,8*

FA

All Types

Tensile force per bolt anchor under maximum horizontal load (Hd): 3,1kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 39,1 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1016.18

40 - 336

1016.10
1016.18

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10

Page 30

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Post base 1016.20:
Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction
Fd (Compression)
Fd (Tension)
H1,d

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

medium 0,8

All Types

7,4*

Tension plate

3,6

All Types
All Types

FA

All Types

instantaneous 1,1

39,9

Nut, welded

H2,d

short 0,9

0,8
0,5*
Tensile force per bolt anchor under maximum horizontal load (Hd): 2,9kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Steel failure is decisive, no correction factors required in service class 3.


Item no.

Adjustment range [mm]

1016.20

40 - 506

Post base 1016.28:


Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction
Fd (Compression)
Fd (tensile)
H1,d

Load duration class (LDC), kmod

Type
All Types
Nut, welded
Tension plate

permanent 0,6

long 0,7

medium 0,8

short 0,9

26,1

30,4

34,8

39,1

H2,d

All Types

FA

All Types

39,9
7,4*

All Types

instantaneous 1,1

3,6
0,8
0,5*

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,9kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 39,1 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Adjustment range [mm]

1016.28

40 - 506

1016.20
1016.28

Page 31

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

3.6 2 parts
Post bases 10930.50, 10930.51 and 10930.52:
Design values of the load-carrying capacity in kN per post base
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)

All Types

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

41,5

48,5

55,4

62,3

76,2

11,3

13,8

10930.50
Hd (Horizontal)

10930.51

3,4

3,9

4,5

6,2

5,1

5,6

10930.52

4,5

10930.50
FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 3,5kN

10930.51

Tensile force per bolt anchor under maximum horizontal load (Hd): 4,1kN

10930.52

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Height [mm]

10930.50

125

10930.51

160

10930.52

200

10930.50
10930.51
10930.52

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10

Page 32

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Post bases 10930.55, 10930.56 and 10930.57:


Design values of the load-carrying capacity in kN per post base
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)

All Types

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

41,5

48,5

55,4

62,3

76,2

10930.55
H1,d

3,4

10930.56

4,5

3,9

11,3

13,8

5,1

6,2
4,9

10930.57

3,9

10930.55
H2,d

3,4

3,8*

10930.56

3,0*

10930.57
FA

2,3*

All Types

Tensile force per bolt anchor under maximum horizontal load (Hd): 5,6kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Height [mm]

10930.55

125

10930.56

160

10930.57

200

10930.55
10930.56
10930.57

Page 33

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post bases 10933.00, 10933.10 and 10933.20:


Design values of the load-carrying capacity in kN per post base
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)

All Types

Fd (Tension)

All Types

10933.10

FA

All Types

long 0,7

41,5

48,5

medium 0,8
55,4
-

10933.00
Hd (Horizontal)

permanent 0,6

4,6

6,2

5,4

short 0,9

instantaneous 1,1

62,3

76,2

11,3

13,8

6,9

7,3
5,6

10933.20

4,5
Tensile force per bolt anchor under maximum horizontal load (Hd): 4,2kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Height [mm]

10933.00

125

10933.10

160

10933.20

200

10933.00
10933.10
10933.20

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

see p. 9
see p. 10
see p. 10

Page 34

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Post bases 10933.50, 10933.60 and 10933.70:
Design values of the load-carrying capacity in kN per post base
Load direction

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

medium 0,8

48,5

55,4

Fd (Compression)

All Types

41,5

Fd (Tension)

All Types

10933.50

4,6

H1,d

10933.60

4,6

H2,d
FA

5,4

instantaneous 1,1

62,3

76,2

11,3

13,8

6,2

6,4
4,9

10933.70

3,9

10933.50

3,8*

10933.60

3,0*

10933.70

2,3*

All Types

short 0,9

Tensile force per bolt anchor under maximum horizontal load (Hd): 5,7kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Height [mm]

10933.50

125

10933.60

160

10933.70

200

10933.50
10933.60
10933.70

Page 35

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post bases 10950.00, 10950.10 and 10950.20:


Design values of the load-carrying capacity in kN per post base
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)

All Types

Fd (Tension)

All Types

permanent 0,6

long 0,7

41,5

48,5

medium 0,8
55,4
-

10933.00

4,6

5,4

Hd (horizontal)

10933.10

4,6

5,4

FA

All Types

6,2

short 0,9

instantaneous 1,1

62,3

76,2

11,3

13,8

6,9

7,3
5,6

10933.20

4,5
Tensile force per bolt anchor under maximum horizontal load (Hd): 4,2kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62.3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.

Item no.

Height [mm]

10950.00

125

10950.10

160

10950.20

200

10950.00
10950.10
10950.20

Page 36

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Post bases 10950.50, 10950.60 and 10950.70:
Design values of the load-carrying capacity in kN per post base with maximum adjustment height
Load direction

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

41,5

48,5

Fd (Compression)

All Types

Fd (Tension)

All Types
10950.50

4,6

H1,d

10950.60

4,6

H2,d
FA

medium 0,8
55,4
-

5,4

instantaneous 1,1

62,3

76,2

11,3

13,8

6,2

6,4
4,9

10950.70

3,9

10950.50

3,8*

10950.60

3,0*

10950.70

2,3*

All Types

short 0,9

Tensile force per bolt anchor under maximum horizontal load (Hd): 5,7kN

* In case of a longer ground plate, l=220mm, the values must be reduced by the factor 0.6

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.

Item no.

Height [mm]

10950.50

125

10950.60

160

10950.70

200

10950.50
10950.60
10950.70

Page 37

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

3.7 Rigid version, hot-dip galvanized


Post base 1001.00:
Design values of the load-carrying capacity in kN per post base
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)

permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

41,5

48,5

55,4

62,3

76,2

11,3

13,8

1001.00

Hd (Horizontal)

3,5

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 3,1kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Height [mm]

1001.00

125

Post base 1003.00:


Design values of the load-carrying capacity in kN per post base
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)
H1,d

permanent 0,6

long 0,7

41,5

48,5

medium 0,8
55,4
-

1003.00

short 0,9

instantaneous 1,1

62,3

76,2

11,3

13,8

2,2

H2,d

2,7

3,2

3,2

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 3,1kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Height [mm]

1003.00

125

1001.00

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

1003.00

see p. 9
see p. 10
see p. 10

Page 38

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Post base 1005.00:
Design values of the load-carrying capacity in kN per post base
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)

permanent 0,6

long 0,7

41,5

48,5

1005.00

medium 0,8

short 0,9

instantaneous 1,1

55,4

62,3

76,2

11,3

13,8

3,2

Hd (Horizontal)
FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,8kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Height [mm]

1005.00

160

Post base 1007.00:


Design values of the load-carrying capacity in kN per post base
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)
H1,d

permanent 0,6

long 0,7

41,5

48,5

medium 0,8
55,4
-

1007.00

short 0,9

instantaneous 1,1

62,3

76,2

11,3

13,8

2,2

H2,d

3,1

FA

Tensile force per bolt anchor under maximum horizontal load (Hd): 2,8kN

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.
Item no.

Height [mm]

1007.00

160

1005.00

1007.00

Page 39

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

3.8 For embedding in concrete


Post bases 10930.35 and 10930.45:
Design values of the load-carrying capacity in kN per post base with maximum distance between base plate and foundation
Load direction

Type

Fd (Compression)

10930.35
10930.45

Fd (Tension)

10930.35
10930.45

Hd (Horizontal)

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

41,5

48,5

55,4

62,3

76,2

11,3

13,8

5,1

6,2

10930.35

3,4

3,9

10930.45

3,4

3,9

4,5

4,4

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.

Item no.

Clearance between base plate and foundation [mm]

10930.35

to 200

10930.45

to 300

Post bases 10930.70 and 10930.71:


Design values of the load-carrying capacity in kN per post base with maximum distance between base plate and foundation
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)

All Types

Hd (Horizontal)

Load duration class (LDC), kmod


permanent 0,6

long 0,7

41,5

48,5

medium 0,8

short 0,9

instantaneous 1,1

55,4

62,3

76,2

11,3

13,8

10930.70

2,4

10930.71

1,5

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.

Item no.

Clearance between base plate and foundation [mm]

10930.70

to 100

10930.71

to 180

10930.35
10930.45

NB:
Minimal anchoring depth in concrete: 150mm

Load-carrying capacity of the bolt anchor:


Combined load:
Increase of the tensile load-carrying capacity:

10930.70
10930.71

see p. 9
see p. 10
see p. 10

Page 40

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Post bases 10930.73 and 10930.74:
Design values of the load-carrying capacity in kN per post base with maximum distance between base plate and foundation
Load direction

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

medium 0,8

66,1

75,6

Fd (Compression)

All Types

56,7

Fd (Tension)

All Types

10930.73

3,4

Hd (Horizontal)

3,9

short 0,9
85,0

103,9

11,3

13,8

4,5

10930.74

instantaneous 1,1

4,7
2,9

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 85,0 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.

Item no.

Clearance between base plate and foundation [mm]

10930.73

to 100

10930.74

to 180

Post bases 10934.00 and 10934.10:


Design values of the load-carrying capacity in kN per post base with maximum distance between base plate and foundation
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)

All Types

Hd (Horizontal)

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

41,5

48,5

55,4

62,3

76,2

11,3

13,8

10934.00

2,4

10934.10

1,5

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62,3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.

Item no.

Clearance between base plate and foundation [mm]

10934.00

to 100

10934.10

to 180

10930.73
10930.74

10934.00
10934.10

NB:
Minimal anchoring depth in concrete: 150mm

Page 41

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Post bases 10934.30 and 10934.31:


Design values of the load-carrying capacity in kN per post base with maximum distance between base plate and foundation
Load direction
Fd (Compression)

All Types

Fd (Tension)

All Types

Hd

Load duration class (LDC), kmod

Type

permanent 0,6

long 0,7

56,7

66,1

medium 0,8
75,6
-

10934.30

4,6

short 0,9

instantaneous 1,1

85,0

103,9

11,3

13,8

4,7

10934.31

2,9

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 85,0 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.

Item no.

Clearance between base plate and foundation [mm]

10934.30

to 100

10934.31

to 180

Post bases 10935.00 and 10935.50:


Design values of the load-carrying capacity in kN per post base with maximum distance between base plate and foundation
Load direction

Type

Fd (Compression)

All Types

Fd (Tension)

All Types

Hd

All Types

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

41,5

48,5

55,4

62,3

76,2

4,6

5,4

11,3

13,8
6,2

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62.3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.

Item no.

Clearance between base plate and foundation [mm]

10935.00

to 200

10935.50

to 200

NB:
Minimal anchoring depth in concrete: 150mm

10934.30
10934.31

10935.00

10935.50

Page 42

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Post bases 10945.00 and 10945.50:
Design values of the load-carrying capacity in kN per post base with maximum distance between base plate and foundation
Load direction

Load duration class (LDC), kmod

Type

Fd (Compression)
Fd (Tension)

permanent 0,6

long 0,7

41,5

48,5

10945.00
10945.50

medium 0,8

short 0,9

instantaneous 1,1

55,4

62,3

76,2

11,3

13,8

Hd

4,4

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Compression) in service class 3, LDC short: Fd = 62.3 x 0,7/0,9
Steel failure is decisive, no correction factors required in service class 3.

Item no.

Clearance between base plate and foundation [mm]

10945.00

to 300

10945.50

to 300

NB:
Minimal anchoring depth in concrete: 150mm

4. Design values of the


post-purlin connectors ETA-10/0413 (CE)
post-purlin connectors 8710, 8712 and 8716 according to Eurocodes and national annex Germany:
Design values of the load-carrying capacity in kN per Post-purlin connectors
Load duration class (LDC), kmod

Load direction

Type

Fd (Compression)

All Types

to calculate in acc. with EC5

Fd (Tension)

All Types

H1,d (parallel to the


purlin)

All Types

3,4

3,9

8710

2,9

3,4

H2,d (perpendicular to
the purlin)

permanent 0,6

8712

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

11,3

13,8

4,5

5,1

6,2

3,9

4,4

5,3

same values as H1,d

8716

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
Fd (Tension) in service class 3, LDC short: Fd = 11,3 x 0,7/0,9
10945.00

10945.50

Application example

Combined load:

see p. 10

Increase of the tensile loadcarrying capacity:


see p. 10

Page 43

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

5. Compressive load-carrying capacity of


post bases following structural standards
Design values of the compressive load-carrying capacity in kN per post base with maximum adjustment height
Item no.

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

1000.00

27,3

31,9

32,4

32,4

32,4

1001.20

41,5

48,5

55,4

62,3

64,2

1002.00

41,5

48,5

55,4

62,3

67,9

1004.00

41,5

48,5

55,4

62,3

67,9

1006.00

41,5

48,5

55,4

62,3

66,2

1009.00

41,5

48,5

55,4

57,9

57,9

1009.80

26,6

27,3

27,3

27,3

27,3

1010.00

41,5

48,5

55,4

57,9

57,9

1011.00

33,9

33,9

33,9

33,9

33,9

1012.00

33,9

33,9

33,9

33,9

33,9

1013.00

41,5

48,5

55,4

62,3

72,0

1019.00

36,6

42,8

44,0

44,0

44,0

1020.00

58,9

58,9

58,9

58,9

58,9

1021.00

58,9

58,9

58,9

58,9

58,9

1022.00, 1022.10

41,5

48,5

55,4

62,3

69,2

1022.20

41,5

48,5

55,4

59,0

59,0

1023.00, 1023.10

25,6

29,8

34,1

35,2

35,2

1050.00 /A/B

28,8

33,6

38,4

41,8

41,8

1050.00 C

28,8

33,6

38,2

38,2

38,2

1051.00 /A/B/C

27,3

31,9

36,4

36,6

36,6

1052.00 /A/B

29,9

34,9

39,9

41,8

41,8

1052.00 C

29,9

34,9

38,2

38,2

38,2

1060.00

41,5

48,5

55,4

62,3

72,0

1060.00 A

41,5

48,5

55,4

59,4

59,4

1060.00 B

41,5

48,5

51,8

51,8

51,8

1060.00 C

38,2

38,2

38,2

38,2

38,2

1061.00

41,5

48,5

55,4

62,3

72,0

1061.00 A

41,5

48,5

55,4

59,4

59,4

1061.00 B

41,5

48,5

51,8

51,8

51,8

1061.00 C

38,2

38,2

38,2

38,2

38,2

1061.10

41,5

48,5

55,4

62,3

72,0

1061.10 A

41,5

48,5

55,4

59,4

59,4

1061.10 B

41,5

48,5

51,8

51,8

51,8

1061.10 C

38,2

38,2

38,2

38,2

38,2

1062.00 /A/B

41,5

41,5

41,5

41,5

41,5

1062.00 C

38,2

38,2

38,2

38,2

38,2

1070.00

41,5

48,5

55,4

62,3

72,0

1070.00 A

41,5

48,5

55,4

59,4

59,4

1070.00 B

41,5

48,5

51,8

51,8

51,8

1070.00 C

38,2

38,2

38,2

38,2

38,2

Page 44

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Design values of the compressive load-carrying capacity in kN per post base with maximum adjustment height
Item no.

Load duration class (LDC), kmod


permanent 0,6

long 0,7

medium 0,8

short 0,9

instantaneous 1,1

1071.00

41,5

48,5

55,4

62,3

72,0

1071.00 A

41,5

48,5

55,4

59,4

59,4

1071.00 B

41,5

48,5

51,8

51,8

51,8

1071.00 C

38,2

38,2

38,2

38,2

38,2

1071.10

41,5

48,5

55,4

62,3

72

1071.10 A

41,5

48,5

55,4

59,4

59,4

1071.10 B

41,5

48,5

51,8

51,8

51,8

1071.10 C

38,2

38,2

38,2

38,2

38,2

1072.00 /A/B

41,8

41,8

41,8

41,8

41,8

1072.00 C

38,2

38,2

38,2

38,2

38,2

1073.00 /A/B

41,8

41,8

41,8

41,8

41,8

1073.00 C

38,2

38,2

38,2

38,2

38,2

10900.00

41,5

48,5

49,1

49,1

49,1

10901.00

41,5

48,5

49,1

49,1

49,1

10980.00

27,3

27,3

27,3

27,3

27,3

Failure of the timber part or the fasteners:


In service class 3 (outdoor use), the values from the table have to be reduced in accordance with the modification coefficients kmod to apply.
(See p. 10).
Steel failure is decisive, no correction factors required in service class 3.

Page 45

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

B/ Characteristic values
Post bases by Pitzl must be designed in accordance with the applicable timber and steel construction standards Eurocode 5 and Eurocode 3 or
with an equivalent national code.
(cf. Design concept p. 8)

1. Characteristic load-carrying capacity of


the post bases acc. to ETA-10/0413 (CE)
Determining the characteristic load-carrying capacities:
The characteristic properties of the post bases were determined by combining calculations in accordance with Eurocode 3 and Eurocode 5 with
test results.
The characteristic values of the load-carrying capacity of the connection assembly, which consists of screws and threaded rods or tubes, were
determined using test results of the Karlsruhe Institute of Technology.
Definition of the directions of force
- Force F1: tensile or compressive load

F1

- Force F2 / F3: horizontal load in parallel with the inner plate (if any) or the longest side of the lower plate

F2 / F3

- Force F4 / F5: horizontal load, perpendicular to the inner plate (if any) or to the longest side of the lower plate

F4 / F5

Page 46

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Increase through linear interpolation of the load-carrying capacity under compressive or horizontal load for
the case of steel failure being decisive for height-adjustable post bases:
The load-carrying capacity under compressive or horizontal load, for which steel failure is decisive at a maximum adjustment height (see blue
cells in design value tables, p. 11 to 39) can be increased for smaller adjustment heights by linear interpolation.
Example using the threaded rod post base 1016.20:
Characteristic compressive load-carrying capacity at steel failure:
- at maximum adjustment height (a = 500mm): F1,Rk, steel failure (Compression)= 43,9kN
- at adjustment height a = 250mm: F1,Rk, steel failure (Compression)= 80,8kN
- at adjustment height a = 300mm:

 



 





Design value of the compressive load-carrying capacity at steel failure


with a = 300mm:


 








 


  
at
Design
value
of the compressive
load-carrying
capacity
failure:


timber



Medium LDC in service class 1 or 2:

 

The design value of the compressive load-carrying capacity of the post base 1016.20 with medium load duration class in service class 1 or 2 at
an adjustment height of a = 300mm is therefore 55.4kN (timber failure).
Note:
This method can be used to increase the compressive load-carrying capacity with medium, short and instantaneous LDC of the following post
bases:
1016.20, 1016.32, 10921.00 D, 10921.36 D, 10930.00 C, 10931.00 C
Increasing the compressive load-carrying capacity with short and instantaneous LDC is possible for the following additional post bases:
10930.00B, 10921.36B, 10921.36.C, 1016.10.

Page 47

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Characteristic load-carrying capacity in kN per post base


Post base

F1 (Compression)

F1 (Tension)***

F2/F3

F4/F5

Timber

Steel

Timber

Steel

Type

Item no.

Timber

Steel

1001.00

1001.00

90,0

93,0

16,3

30,4

10,0

3,5

M,1

M(C)

M,0

90,0

93,0

16,3

30,4

M,1

M(C)

M,0

90,0

93,0

16,3

M,1

90,0

93,0

1003.00

1005.00

1007.00

1008.08

1014.00

1003.00

1005.00

1007.00

1008.08

Timber

Steel

10,0

3,5

M,0

M,0

12,6

2,2

5,9

3,2

M,0

M,0

16,6

10,0

3,2

10,0

3,2

M(C)

M,0

M,0

M,0

16,3

16,6

10,0

2,2

10,0

3,1

M,1

M(C)

M,0

M,0

M,0

381,5

279,3

16,3

10,0

14,8

10,0

14,8*

M,1

M(C)

M,0

M,0

M,0

a 150 mm (a = Clearance between base plate and foundation)


Nut, welded 90,0

94,9

16,3

7,4*

10,0

2,8

3,5

10,0

1,7*

3,5

Tension lug 90,0

94,9

8,7

3,6

4,5

10,0

2,8

3,5

10,0

1,7*

3,5

a 75 mm (a = Clearance between base plate and foundation)


90,0

103,8

10,0

5,6

7,0

10,0

3,4*

7,0

Nut, welded 90,0

103,8

16,3

7,4*

10,0

5,6

7,0

10,0

3,4*

7,0

Tension lug 90,0

103,8

8,7

3,6

4,5

10,0

5,6

7,0

10,0

3,4*

7,0

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

M
1014.08

a 150 mm (a = Clearance between base plate and foundation)


Nut, welded 56,5

94,9

16,3

7,4*

6,9

2,8

3,5

6,9

1,7*

3,5

Tension lug 56,5

94,9

8,7

3,6

4,5

6,9

2,8

3,5

6,9

1,7*

3,5

a 75 mm (a = Clearance between base plate and foundation)


56,5

103,8

6,9

5,6

7,0

6,9

3,4*

7,0

Nut, welded 56,5

103,8

16,3

7,4*

6,9

5,6

7,0

6,9

3,4*

7,0

Tension lug 56,5

103,8

8,7

3,6

4,5

6,9

5,6

7,0

6,9

3,4*

7,0

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

* In case of a longer ground plate l=220 mm, the values have to be reduced with a factor of 0,6
*** The load-carrying capacity in the load case F1 (Tension) applies only for the load duration classes short and very short

Page 48

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Characteristic load-carrying capacity in kN per post base
Post base

F1 (Compression)

F1 (Tension)***

F2/F3

Timber

Timber

Timber

Steel

Type

Item no.

Steel

Steel

1015.00

a 250 mm (a = Clearance between base plate and foundation)

F4/F5
Timber

Steel

Nut, welded 90,0

80,8

16,3

16,8

10,0

1,8

2,1

10,0

1,8

2,1

Tension lug 90,0

80,8

8,7

3,6

4,5

10,0

1,8

2,1

10,0

1,8

2,1

a 125 mm (a = Clearance between base plate and foundation)


90,0

98,2

10,0

3,4

4,2

10,0

3,4

4,2

Nut, welded 90,0

98,2

16,3

16,8

10,0

3,4

4,2

10,0

3,4

4,2

Tension lug 90,0

98,2

8,7

3,6

4,5

10,0

3,4

4,2

10,0

3,4

4,2

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

M
1015.08

a 250 mm (a = Clearance between base plate and foundation)


Nut, welded 56,5

80,8

16,3

16,8

6,9

1,8

2,1

6,9

1,8

2,1

Tension lug 56,5

80,8

8,7

3,6

4,5

6,9

1,8

2,1

6,9

1,8

2,1

a 125 mm (a = Clearance between base plate and foundation)


56,5

98,2

6,9

3,4

4,2

6,9

3,4

4,2

Nut, welded 56,5

98,2

16,3

16,8

6,9

3,4

4,2

6,9

3,4

4,2

Tension lug 56,5

98,2

8,7

3,6

4,5

6,9

3,4

4,2

6,9

3,4

4,2

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

M
1016.00

a 250 mm (a = Clearance between base plate and foundation)


Nut, welded 90,0

80,8

16,3

7,4*

10,0

1,7

2,1

10,0

1,0*

2,1

Tension lug 90,0

80,8

8,7

3,6

4,5

10,0

1,7

2,1

10,0

1,0*

2,1

a 125 mm (a = Clearance between base plate and foundation)


90,0

98,2

10,0

3,4

4,2

10,0

2,0*

4,2

Nut, welded 90,0

98,2

16,3

7,4*

10,0

3,4

4,2

10,0

2,0*

4,2

Tension lug 90,0

98,2

8,7

3,6

4,5

10,0

3,4

4,2

10,0

2,0*

4,2

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

* In the case of the lower plate being larger, l=220mm, the values must be reduced by the factor 0.6
*** The load-carrying capacity in the load case F1 (Tension) applies only for the load duration classes short and very short

Page 49

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Characteristic load-carrying capacity in kN per post base


Post base

F1 (Compression)

F1 (Tension)***

F2/F3

Timber

Timber

Timber

Steel

Type

Item no.

Steel

Steel

1016.08

a 250 mm (a = Clearance between base plate and foundation)

F4/F5
Timber

Steel

Nut, welded 56,5

80,8

16,3

7,4*

6,9

1,7

2,1

6,9

1,0*

2,1

Tension lug 56,5

80,8

8,7

3,6

4,5

6,9

1,7

2,1

6,9

1,0*

2,1

a 125 mm (a = Clearance between base plate and foundation)


56,5

98,2

6,9

3,4

4,2

6,9

2,0*

4,2

Nut, welded 56,5

98,2

16,3

7,4*

6,9

3,4

4,2

6,9

2,0*

4,2

Tension lug 56,5

98,2

8,7

3,6

4,5

6,9

3,4

4,2

6,9

2,0*

4,2

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

M
1016.10

a 330 mm (a = Clearance between base plate and foundation)


Nut, welded 90,0

68,2

16,3

7,4*

10,0

1,3

1,6

10,0

0,8*

1,6

Tension lug 90,0

68,2

8,7

3,6

4,5

10,0

1,3

1,6

10,0

0,8*

1,6

a 165 mm (a = Clearance between base plate and foundation)


90,0

92,9

10,0

2,6

3,2

10,0

1,5*

3,2

Nut, welded 90,0

92,9

16,3

7,4*

10,0

2,6

3,2

10,0

1,5*

3,2

Tension lug 90,0

92,9

8,7

3,6

4,5

10,0

2,6

3,2

10,0

1,5*

3,2

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

M
1016.18

a 330 mm (a = Clearance between base plate and foundation)


Nut, welded 56,5

68,2

16,3

7,4*

6,9

1,3

1,6

6,9

0,8*

1,6

Tension lug 56,5

68,2

8,7

3,6

4,5

6,9

1,3

1,6

6,9

0,8*

1,6

a 165 mm (a = Clearance between base plate and foundation)


56,5

92,9

6,9

2,6

3,2

6,9

1,5*

3,2

Nut, welded 56,5

92,9

16,3

7,4*

6,9

2,6

3,2

6,9

1,5*

3,2

Tension lug 56,5

92,9

8,7

3,6

4,5

6,9

2,6

3,2

6,9

1,5*

3,2

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

M
1016.20

a 500 mm (a = Clearance between base plate and foundation)


Nut, welded 90,0

43,9

16,3

7,4*

10,0

0,8

1,1

10,0

0,5*

1,1

Tension lug 90,0

43,9

8,7

3,6

4,5

10,0

0,8

1,1

10,0

0,5*

1,1

a 250 mm (a = Clearance between base plate and foundation)


90,0

80,8

10,0

1,7

2,1

10,0

1,0*

2,1

Nut, welded 90,0

80,8

16,3

7,4*

10,0

1,7

2,1

10,0

1,0*

2,1

Tension lug 90,0

80,8

8,7

3,6

4,5

10,0

1,7

2,1

10,0

1,0*

2,1

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

* In the case of the lower plate being larger, l=220mm, the values must be reduced by the factor 0.6
*** The load-carrying capacity in the load case F1 (Tension) applies only for the load duration classes short and very short

Page 50

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Characteristic load-carrying capacity in kN per post base
Post base

F1 (Compression)

F1 (Tension)***

F2/F3

Timber

Timber

Timber

Steel

Type

Item no.

Steel

Steel

1016.28

a 500 mm (a = Clearance between base plate and foundation)

F4/F5
Timber

Steel

Nut, welded 56,5

43,9

16,3

7,4*

6,9

0,8

1,1

6,9

0,5*

1,1

Tension lug 56,5

43,9

8,7

3,6

4,5

6,9

0,8

1,1

6,9

0,5*

1,1

a 250 mm (a = Clearance between base plate and foundation)


56,5

80,8

6,9

1,7

2,1

6,9

1,0*

2,1

Nut, welded 56,5

80,8

16,3

7,4*

6,9

1,7

2,1

6,9

1,0*

2,1

Tension lug 56,5

80,8

8,7

3,6

4,5

6,9

1,7

2,1

6,9

1,0*

2,1

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

M
1016.30

a 250 mm (a = Clearance between base plate and foundation)


Nut, welded 159,2

141,5

16,3

20,6*

13,1

3,6

3,3

13,1

2,8*

3,3

Tension lug 159,2

141,5

8,7

7,9

9,4

13,1

3,6

3,3

13,1

2,8*

3,3

a 125 mm (a = Clearance between base plate and foundation)


159,2

162,6

13,1

9,4

6,6

13,1

5,6*

6,6

Nut, welded 159,2

162,6

16,3

20,6*

13,1

9,4

6,6

13,1

5,6*

6,6

Tension lug 159,2

162,6

8,7

7,9

9,4

13,1

9,4

6,6

13,1

5,6*

6,6

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

* In case of a longer ground plate l=220 mm, the values have to be reduced with a factor of 0,6
*** The load-carrying capacity in the load case F1 (Tension) applies only for the load duration classes short and very short

Page 51

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Characteristic load-carrying capacity in kN per post base


Post base

F1 (Compression)

F1 (Tension)***

F2/F3

Timber

Timber

Timber

Steel

Type

Item no.

Steel

Steel

1016.31

a 330 mm (a = Clearance between base plate and foundation)

F4/F5
Timber

Steel

Nut, welded 159,2

126,6

16,3

20,6*

13,1

2,7

2,5

13,1

2,1*

2,5

Tension lug 159,2

126,6

8,7

7,9

9,4

13,1

2,7

2,5

13,1

2,1*

2,5

a 165 mm (a = Clearance between base plate and foundation)


159,2

156,0

13,1

5,5

5,0

13,1

4,3*

5,0

Nut, welded 159,2

156,0

16,3

20,6*

13,1

5,5

5,0

13,1

4,3*

5,0

Tension lug 159,2

156,0

8,7

7,9

9,4

13,1

5,5

5,0

13,1

4,3*

5,0

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

M
1016.32

a 500 mm (a = Clearance between base plate and foundation)


Nut, welded 159,2

92,9

16,3

20,6*

13,1

1,8

1,7

13,1

1,4*

1,7

Tension lug 159,2

92,9

8,7

7,9

9,4

13,1

1,8

1,7

13,1

1,4*

1,7

a 250 mm (a = Clearance between base plate and foundation)


159,2

141,5

13,1

3,6

3,3

13,1

2,8*

3,3

Nut, welded 159,2

141,5

16,3

20,6*

13,1

3,6

3,3

13,1

2,8*

3,3

Tension lug 159,2

141,5

8,7

7,9

9,4

13,1

3,6

3,3

13,1

2,8*

3,3

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

M,2

M
10920

With maximum clearance between base plate and foundation**


10920.00

10920

90,0

87,4

16,3

7,4*

11,0

2,1

2,2

11,0

1,2*

10920.00 A 90,0

83,8

16,3

7,4*

11,0

1,8

2,0

11,0

1,1*

10920.00 B 90,0

74,6

16,3

7,4*

11,0

1,5

1,6

11,0

0,9*

10920.00 C 90,0

69,8

16,3

7,4*

11,0

1,3

1,4

11,0

0,8*

10920.00 D 90,0

58,8

16,3

7,4*

11,0

1,1

1,2

11,0

0,6*

10920.30

146,1

148,5

16,3

20,6*

13,1

4,3

3,8

13,1

3,3*

3,8

M,1

M(C)

M,0

M,0

M,2

M,0

M,2

With minimum clearance between base plate and foundation**


10920.00

90,0

96,2

16,3

7,4*

11,0

3,0

3,2

11,0

1,8*

10920.00 A 90,0

92,9

16,3

7,4*

11,0

2,6

2,7

11,0

1,5*

10920.00 B 90,0

84,5

16,3

7,4*

11,0

1,9

2,0

11,0

1,1*

10920.00 C 90,0

80,0

16,3

7,4*

11,0

1,7

1,8

11,0

0,9*

10920.00 D 90,0

69,0

16,3

7,4*

11,0

1,4

1,4

11,0

0,8*

10920.30

146,1

158,5

16,3

20,6*

13,1

6,0

5,4

13,1

4,7*

5,4

M,1

M(C)

M,0

M,0

M,2

M,0

M,2

* In case of a longer ground plate l=220 mm, the values have to be reduced with a factor of 0,6
** Linear interpolation may be applied for interim values
*** The load-carrying capacity in load case F1 (Tension) is only valid in short-term and instantaneous load-duration classes

Page 52

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Characteristic load-carrying capacity in kN per post base
Post base

F1 (Compression)

F1 (Tension)***

F2/F3

Timber

Timber

Timber

Steel

Type

Item no.

10921

With maximum clearance between base plate and foundation**


10921.00

10921

Steel

Steel

F4/F5
Timber

Steel

90,0

87,4

68,6

16,3

7,4*

10,0

2,1

2,2

10,0

1,2*

10921.00 A 90,0

83,8

68,6

16,3

7,4*

10,0

1,8

2,0

10,0

1,1*

10921.00 B 90,0

74,6

68,6

16,3

7,4*

10,0

1,5

1,6

10,0

0,9*

10921.00 C 90,0

69,8

68,6

16,3

7,4*

10,0

1,3

1,4

10,0

0,8*

10921.00 D 90,0

58,8

68,6

16,3

7,4*

10,0

1,1

1,2

10,0

0,6*

10921.10

90,0

102,7

68,6

16,3

7,4*

10,0

4,7

5,0

10,0

2,8*

10921.30

131,1

148,5

97,9

16,3

20,6*

10,0

4,3

3,8

10,0

3,3*

3,8

10921.36

185,7

164,2

171,4

16,3

10,0

4,9

3,9

10,0

4,9

3,9

10921.36 A 185,7

147,6

171,4

16,3

10,0

4,2

3,5

10,0

4,2

3,5

10921.36 B 185,7

137,0

171,4

16,3

10,0

3,3

2,8

10,0

3,3

2,8

10921.36 C 185,7

131,4

171,4

16,3

10,0

3,0

2,6

10,0

3,0

2,6

10921.36 D 185,7

117,8

171,4

16,3

10,0

2,5

2,1

10,0

2,5

2,1

10921.40

90,0

80,8

68,6

16,3

7,4*

10,0

1,7

1,8

10,0

1,0*

M,1

M(C)

M,0

M,0

M,2

M,0

M,2

With minimum clearance between base plate and foundation**


10921.00

90,0

96,2

68,6

16,3

7,4*

10,0

3,0

3,2

10,0

1,8*

10921.00 A 90,0

92,9

68,6

16,3

7,4*

10,0

2,6

2,7

10,0

1,5*

10921.00 B 90,0

84,5

68,6

16,3

7,4*

10,0

1,9

2,0

10,0

1,1*

10921.00 C 90,0

80,0

68,6

16,3

7,4*

10,0

1,7

1,8

10,0

0,9*

10921.00 D 90,0

69,0

68,6

16,3

7,4*

10,0

1,4

1,4

10,0

0,8*

10921.10

90,0

103,8

68,6

16,3

7,4*

10,0

5,3

5,6

10,0

3,2*

10921.30

131,1

158,5

97,9

16,3

20,6*

10,0

6,0

5,4

10,0

4,7*

5,4

10921.36

185,7

175,3

171,4

16,3

10,0

7,0

5,4

10,0

7,0

5,4

10921.36 A 185,7

157,7

171,4

16,3

10,0

5,5

4,7

10,0

5,5

4,7

10921.36 B 185,7

147,6

171,4

16,3

10,0

4,2

3,5

10,0

4,2

3,5

10921.36 C 185,7

142,4

171,4

16,3

10,0

3,7

3,1

10,0

3,7

3,1

10921.36 D 185,7

129,5

171,4

16,3

10,0

3,0

2,5

10,0

3,0

2,5

10921.40

90,0

90,2

68,6

16,3

7,4*

10,0

2,3

2,4

10,0

1,4*

M,1

M(C)

M,0

M,0

M,2

M,0

M,2

* In case of a longer ground plate l=220 mm, the values have to be reduced with a factor of 0,6
** Linear interpolation may be applied for interim values
*** The load-carrying capacity in load case F1 (Tension) is only valid in short-term and instantaneous load-duration classes

Page 53

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Characteristic load-carrying capacity in kN per post base


Post base

F1 (Compression)

F1 (Tension)***

F2/F3

Timber

Timber

Timber

Steel

Type

Item no.

10930

Maximum clearance between base plate and foundation see Table A.1

10930

Steel

Timber

Steel

10930.35

90,0

106,5

16,3

106,5

86,7

7,3

6,2

7,3

6,2

10930.45

90,0

106,5

16,3

106,5

86,7

7,3

4,4

7,3

4,4

10930.50

90,0

106,5

16,3

41,8

7,3

7,3

7,3

7,3

10930.51

90,0

106,5

16,3

41,8

7,3

5,6

7,3

5,6

10930.52

90,0

106,5

16,3

41,8

7,3

4,5

7,3

4,5

10930.55

90,0

106,5

16,3

25,6*

7,3

6,4

7,3

3,8*

10930.56

90,0

106,5

16,3

25,6*

7,3

4,9

7,3

3,0*

10930.57

90,0

106,5

16,3

25,6*

7,3

3,9

7,3

2,3*

10930.70

90,0

101,4

16,3

103,8

88,1

7,3

2,4

7,3

2,4

10930.71

90,0

90,8

16,3

103,8

88,1

7,3

1,5

7,3

1,5

10930.73

122,8

166,1

16,3

88,1

7,3

4,7

7,3

4,7

10930.74

122,8

153,5

16,3

88,1

7,3

2,9

7,3

2,9

M,1

M(C)

M,0

M,2

M,0

M,2

M,0

With maximum clearance between base plate and foundation**


10930.00

90,0

75,2

16,3

13,2*

7,3

1,6

1,6

7,3

1,6*

1,6

10930.00 A 90,0

71,2

16,3

13,2*

7,3

1,4

1,5

7,3

1,4*

1,5

10930.00 B 90,0

61,7

16,3

13,2*

7,3

1,2

1,2

7,3

1,2*

1,2

10930.00 C 90,0

57,2

16,3

13,2*

7,3

1,1

1,1

7,3

1,1*

1,1

10930.10

90,0

87,9

16,3

13,2*

7,3

2,2

2,3

7,3

2,2*

2,3

10930.30

125,8

154,6

16,3

20,6*

7,3

3,2

2,8

7,3

2,5*

2,8

10930.36

168,6

154,6

16,3

7,3

3,7

3,1

7,3

3,7

3,1

10930.36 A 168,6

140,3

16,3

7,3

2,8

2,5

7,3

2,8

2,5

10930.36 B 168,6

129,2

16,3

7,3

2,4

2,1

7,3

2,4

2,1

10930.36 C 168,6

123,3

16,3

7,3

2,2

1,9

7,3

2,2

1,9

M,1

M(C)

M,0

M,0

M,2

M,0

M,2

M
10930

Steel

F4/F5

With minimum clearance between base plate and foundation**


10930.00

90,0

92,0

16,3

13,2*

7,3

2,6

2,6

7,3

2,6*

2,6

10930.00 A 90,0

88,6

16,3

13,2*

7,3

2,3

2,3

7,3

2,3*

2,3

10930.00 B 90,0

79,8

16,3

13,2*

7,3

1,8

1,8

7,3

1,8*

1,8

10930.00 C 90,0

75,2

16,3

13,2*

7,3

1,6

1,6

7,3

1,6*

1,6

10930.10

90,0

99,9

16,3

13,2*

7,3

4,1

4,0

7,3

4,1*

4,0

10930.30

125,8

172,2

16,3

20,6*

7,3

4,6

4,1

7,3

3,6*

4,1

10930.36

168,6

172,2

16,3

7,3

5,5

5,6

7,3

5,5

5,6

10930.36 A 168,6

156,5

16,3

7,3

3,9

3,5

7,3

3,9

3,5

10930.36 B 168,6

146,4

16,3

7,3

3,1

2,8

7,3

3,1

2,8

10930.36 C 168,6

141,2

16,3

7,3

2,8

2,5

7,3

2,8

2,5

M,1

M(C)

M,0

M,0

M,2

M,0

M,2

* In case of a longer ground plate l=220 mm, the values have to be reduced with a factor of 0,6
** Linear interpolation may be applied for interim values
*** The load-carrying capacity in load case F1 (Tension) is only valid in short-term and instantaneous load-duration classes
Page 54

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


Characteristic load-carrying capacity in kN per post base
Post base

F1 (Compression)

F1 (Tension)***

F2/F3

Timber

Timber

Timber

Steel

Type

Item no.

10931

With maximum clearance between base plate and foundation**


10931.00

Steel

Timber

Steel

90,0

75,2

16,3

13,2*

10,0

1,6

1,6

10,0

1,6*

1,6

10931.00 A 90,0

71,2

16,3

13,2*

10,0

1,4

1,5

10,0

1,4*

1,5

10931.00 B 90,0

61,7

16,3

13,2*

10,0

1,2

1,2

10,0

1,2*

1,2

10931.00 C 90,0

57,2

16,3

13,2*

10,0

1,1

1,1

10,0

1,1*

1,1

10931.10

90,0

87,9

16,3

13,2*

10,0

2,2

2,3

10,0

2,2*

2,3

10931.30

122,8

154,6

16,3

20,6*

10,0

3,2

2,8

10,0

2,5*

2,8

10931.36

168,6

154,6

16,3

10,0

3,7

3,1

10,0

3,7

3,1

10931.36 A 168,6

140,3

16,3

10,0

2,8

2,5

10,0

2,8

2,5

10931.36 B 168,6

129,2

16,3

10,0

2,4

2,1

10,0

2,4

2,1

10931.36 C 168,6

123,3

16,3

10,0

2,2

1,9

10,0

2,2

1,9

M,1

M(C)

M,0

M,0

M,2

M,0

M,2

M
10931

Steel

F4/F5

With minimum clearance between base plate and foundation**


10931.00

90,0

92,0

16,3

13,2*

10,0

2,6

2,6

10,0

2,6*

2,6

10931.00 A 90,0

88,6

16,3

13,2*

10,0

2,3

2,3

10,0

2,3*

2,3

10931.00 B 90,0

79,8

16,3

13,2*

10,0

1,8

1,8

10,0

1,8*

1,8

10931.00 C 90,0

75,2

16,3

13,2*

10,0

1,6

1,6

10,0

1,6*

1,6

10931.10

90,0

99,9

16,3

13,2*

10,0

4,1

4,0

10,0

4,1*

4,0

10931.30

122,8

172,2

16,3

20,6*

10,0

4,6

4,1

10,0

3,6*

4,1

10931.36

168,6

172,2

16,3

10,0

5,5

5,6

10,0

5,5

5,6

10931.36 A 168,6

156,5

16,3

10,0

3,9

3,5

10,0

3,9

3,5

10931.36 B 168,6

146,4

16,3

10,0

3,1

2,8

10,0

3,1

2,8

10931.36 C 168,6

141,2

16,3

10,0

2,8

2,5

10,0

2,8

2,5

M,1

M(C)

M,0

M,0

M,2

M,0

M,2

* In case of a longer ground plate l=220 mm, the values have to be reduced with a factor of 0,6
** Linear interpolation may be applied for interim values
*** The load-carrying capacity in load case F1 (Tension) is only valid in short-term and instantaneous load-duration classes

Page 55

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Characteristic load-carrying capacity in kN per post base


Post base

F1 (Compression)

F1 (Tension)***

F2/F3

F4/F5

Timber

Steel

Timber

Steel

Type

Item no.

Timber

Steel

10933

10933.00

90,0

106,5

16,3

41,8

10,0

7,3

10933.10

90,0

106,5

16,3

41,8

10,0

10933.20

90,0

106,5

16,3

41,8

10933.50

90,0

106,5

16,3

25,6*

10933.60

90,0

106,5

16,3

10933.70

90,0

106,5

M,1

10934.00

90,0

10934.10

10934

10935

10945

10950

10952

Timber

Steel

10,0

7,3

5,6

10,0

5,6

10,0

4,5

10,0

4,5

10,0

6,4

10,0

3,8*

25,6*

10,0

4,9

10,0

3,0*

16,3

25,6*

10,0

3,9

10,0

2,3*

M(C)

M,0

M,0

M,0

101,4

16,3

103,8

88,1

10,0

2,4

10,0

2,4

90,0

90,8

16,3

103,8

88,1

10,0

1,5

10,0

1,5

10934.30

122,8

166,1

16,3

88,1

10,0

4,7

10,0

4,7

10934.31

122,8

153,5

16,3

88,1

10,0

2,9

10,0

2,9

M,1

M(C)

M,0

M,2

M,0

M,0

10935.00

90,0

106,5

16,3

106,5

86,7

10,0

6,2

10,0

6,2

10935.50

90,0

106,5

16,3

106,5

86,7

10,0

6,2

10,0

6,2

M,1

M(C)

M,0

M,2

M,0

M,0

10945.00

90,0

106,5

16,3

106,5

86,7

10,0

4,4

10,0

4,4

10945.50

90,0

106,5

16,3

106,5

86,7

10,0

4,4

10,0

4,4

M,1

M(C)

M,0

M,2

M,0

M,0

10950.00

90,0

106,5

16,3

41,8

10,0

7,3

10,0

7,3

10950.10

90,0

106,5

16,3

41,8

10,0

5,6

10,0

5,6

10950.20

90,0

106,5

16,3

41,8

10,0

4,5

10,0

4,5

10950.50

90,0

106,5

16,3

25,6*

10,0

6,4

10,0

3,8*

10950.60

90,0

106,5

16,3

25,6*

10,0

4,9

10,0

3,0*

10950.70

90,0

106,5

16,3

25,6*

10,0

3,9

10,0

2,3*

M,1

M(C)

M,0

M,0

M,0

90,0

118,7

83,8

16,3

11,8*

10,0

2,5

10,0

2,5*

M,1

M,2

M(C)

M,0

M,0

M,0

10952.00

* In case of a longer ground plate l=220 mm, the values have to be reduced with a factor of 0,6
*** The load-carrying capacity in load case F1 (Tension) is only valid in short-term and instantaneous load-duration classes

Page 56

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases


2. Characteristic load-carrying capacity
of the post bases acc. to Eurocode
Characteristic Compressive load-carrying capacity of the post bases acc. to Eurocode in kN
Post base

F1 (Compression)

Post base

F1 (Compression)

Item no.

max. height
[mm]

Timber

Steel

Steel

Item no.

max. height
[mm]

Timber

Steel

Steel

1000.00

100

59,2

37,4

40,5

1023.00

100

55,4

109,4

44,0

M,1

M,0

M,1

M,0

1001.20

200

90,0

70,6

90,0

1023.10

200

55,4

56,8

44,0

M,1

M,0

M,1

M,0

1002.00

125

90,0

74,7

90,0

1050.00

200

62,4

85,5

52,3

M,1

M,0

1050.00 A 250

62,4

65,3

52,3

1004.00

125

90,0

74,7

90,0

1050.00 B 280

62,4

57,0

52,3

M,1

M,0

1050.00 C 350

1006.00

160

90,0

72,8

90,0

M,1

M,0

1051.00

90,0

63,7

M,1

57,7

63,7

34,1

1051.00 C 350

M,1

M,0

90,0

63,7

90,0

1052.00

200

64,8

85,5

52,3

M,1

M,0

1052.00 A 250

64,8

65,3

52,3

90,0

37,3

90,0

1052.00 B 280

64,8

57,0

52,3

M,1

M,0

1052.00 C 350

64,8

42,0

52,3

90,0

37,3

90,0

M,1

M,0

M,1

M,0

1060.00

200

90,0

85,5

90,0

90,0

103,0

90,0

1060.00 A 250

90,0

65,3

90,0

M,1

M,0

1060.00 B 280

90,0

57,0

90,0

79,4

60,4

55,0

1060.00 C 350

M,1

M,0

145,5

75,9

73,6

1061.00

200

90,0

85,5

90,0

M,1

M,0

1061.00 A 250

90,0

65,3

90,0

145,5

75,9

73,6

1061.00 B 280

90,0

57,0

90,0

M,1

M,0

1061.00 C 350

90,0

42,0

90,0

90,0

76,1

90,0

M,1

M,0

M,1

M,0

1061.10

200

90,0

85,5

90,0

90,0

70,6

90,0

1061.10 A 250

90,0

65,3

90,0

M,1

M,0

1061.10 B 280

90,0

57,0

90,0

90,0

64,9

90,0

1061.10 C 350

M,1

M,0

1009.00

1009.80

1010.00

1011.00

1012.00

1013.00

1019.00

1020.00

1021.00

1022.00

1022.10

1022.20

150

150

150

250

250

150

125

160

160

100

200

300

62,4

42,0

52,3

M,1

M,0

200

59,2

85,5

45,8

90,0

1051.00 A 250

59,2

65,3

45,8

M,0

1051.00 B 280

59,2

57,0

45,8

59,2

42,0

45,8

M,1

M,0

90,0

42,0

90,0

M,1

M,0

90,0

42,0

90,0

M,1

M,0

Page 57

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

Fast, simple and precise: for the best result

Characteristic Compressive load-carrying capacity of the post bases acc. to Eurocode in kN


Post base

F1 (Compression)

Post base

F1 (Compression)

Item no.

max. height
[mm]

Timber

Steel

Steel

Item no.

max. height
[mm]

1062.00

200

97,0

85,5

51,9

1072.00

200

102,6

85,5

52,3

1062.00 A

250

97,0

65,3

51,9

1072.00 A 250

102,6

65,3

52,3

1062.00 B

280

97,0

57,0

51,9

1072.00 B 280

102,6

57,0

52,3

1062.00 C

350

97,0

42,0

51,9

1072.00 C 350

102,6

42,0

52,3

M,1

M,0

M,1

M,0

1070.00

200

90,0

85,5

90,0

1073.00

200

134,1

85,5

52,3

1070.00 A

250

90,0

65,3

90,0

1073.00 A 250

134,1

65,3

52,3

1070.00 B

280

90,0

57,0

90,0

1073.00 B 280

134,1

57,0

52,3

1070.00 C

350

1073.00 C 350

90,0

42,0

90,0

M,1

M,0

1071.00

200

90,0

85,5

90,0

1071.00 A

250

90,0

65,3

90,0

1071.00 B

280

90,0

57,0

90,0

1071.00 C

350

90,0

42,0

90,0

M,1

M,0

1071.10

200

90,0

85,5

90,0

1071.10 A

250

90,0

65,3

90,0

1071.10 B

280

90,0

57,0

90,0

1071.10 C

350

90,0

42,0

90,0

M,1

M,0

10900.00

10901.00

10980.00

180

180

180

Timber

Steel

Steel

134,1

42,0

52,3

M,1

M,0

90,0

54,0

90,0

M,1

M,0

90,0

54,0

90,0

M,1

M,0

62,4

54,0

34,1

M,1

M,0

Page 58

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Design Manual Post bases

3. Characteristic load-carrying capacity


of the post-purlin connectors acc. to ETA-10/0413 (CE)
Characteristic Compressive load-carrying capacity of the post-purlin connectors in kN
post-purlin connectors

F1 (Compression)

F1 (Tension)

Type

Item no.

Timber

Steel

Timber

Steel

8710

8710

to calculatein acc.
with EC5

16,3

16,7

M(C)

to calculate in acc. with


EC5

8712

8716

8712

8716

to calculatein acc.
with EC5

F2/F3

F4/F5

Timber

Steel

Timber

Steel

7,3

6,3

M,0

M(C)

16,3

7,3

7,3

M(C)

16,3

7,3

7,3

M(C)

*** The load-carrying capacity in load case F1 (Tension) is only valid in short-term and instantaneous load-duration classes

Page 59

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to support@pitzl.de

Fast, simple and precise: for the best result

Manufacturer:

We recommend our distributor:

Pitzl GmbH & Co. KG


Siemensstrae 26
DE-84051 Altheim - Germany
Tel.: +49 8703 9346-0
Telefax: +49 8703 9346-55
Email: info@pitzl.de
www.pitzl.de

Pitzl
Metallbau
GmbH & Co. KG

DIN
18 800

For more information and technical details, downloads and helpful video tutorials: www.pitzl.de
Alternatively, our competent staff are always available for advice:
+49 8703 9346-0 or via e-mail to info@pitzl.de

All rights reserved. Reprint in part or whole only with express permission of Pitzl GmbH

Connectors for timber construction


Post bases
Balcony posts / fence posts
always up to date with www.pitzl.de

Modifications and errors reserved. Images are similar. Version as of 11/2013, v250/fo-DE