TestingPreventsSurgeinArresterFailures

Connect

Formorethan30years,ManitobaHydrohasbeentestingsurgearresterson
delivery,atinstallationandduringoperation.
RegGamblin,ManitobaHydro,andKeithHill,DobleEngineeringCo.|T&DWorldMagazine
SHARE

Tweet

Recommend

Dec1,2009

COMMENTS 1

EMAIL

SURGEARRESTERSAREOFTENOVERLOOKEDWHENPERFORMING
POWERFACTORTESTSontransformers,breakersandotherapparatusina
substation.Oftentimes,thetestersareawareofhowatransformerorabreakerfunctions
butunawareoftheintendedpurposeofthesurgearresters.Becausetherearenomoving
partstomaintainoranoilsampletopull,itisoftenpolicynottoperformanyarrester
testing.
ManitobaHydro(MHManitoba,Canada)hasbeenfollowingasurgearrestertesting
programformorethan30years.Undertheprogram,typically30to40arrestersare
identifiedeachyearasrequiringreplacement.Thiscanbeduetoanincreasein10kV,
60Hzwattslossesadecreasedvoltagetoproduce1mAand2mAofresistivecurrenta
reducedsparkoverwithstandvoltageoranincreasedsparkoveroperatingvoltage.MH's
arrestertestingprogramhasbeenespeciallysuccessfulinidentifyingmoistureingress
concernsbecauseofdesigninadequaciesspecificallyrelatedtothenewergenerationof
polymerhousedmetaloxidearresters.
MHpurchasesanaverageofseveralhundredsurgearrestersperyear.Thesearemainly
distributionandstationclassbutalsoincludesomespecialtyunitsforinstallationat
generationandconverterstations.Thearrestertestprogramrequiresthatarrestersbe
acceptancetestedpriortothesupplierbeingpaid.MH'sacceptancetestincludesthe
Doble(Boston,Massachusetts,U.S.)wattslosstest,apartialdischargetestanda
characterizationofthevoltagecurrent(VI)responseofeachunit.Themaintenancetests
arelimitedtotheDoblewattslosstestand,whenpractical,theVIcharacterizationor
sparkovertest.Whenreviewingtestresults,limitsareappliedasspecifiedinstandards
IEC60099andIEEEC62.Also,themethodologyforthequalificationoftestresults
requiresthatresultsforsimilarmodelsandsisterunitsbecomparable.
ACCEPTANCETESTPROGRAM

AllnewstationclassandspecialtyarrestersareacceptancetestedbyMHupondelivery.
Typically,onnewordersofboththestationanddistributionclassesofarresters,MH
experiencesfailureratesbelow0.1%,althoughproblemordershavebeendiscoveredat
times.Anexampleofthiswasforanorderof54polymerhousedstationclassarresters
forinstallationatsystemvoltagesof115kV,138kVand230kV.Thearrestersoriginally
passedacceptancetests,butseveralofthemfailedtheDoblewattslosstestonsiteprior
toenergization.Theproblemwasrevealedtobemoistureingressduetoavulnerable
weatherseal.Themanufacturerreplacedtheentireorderwithporcelainhousedunits
andaddressedthecauseofthevulnerability.
Inanotherinstance,anunusualnumberofpolymerhouseddistributionclassarresters
werefailingacceptancetests.Thesesuspectunitsshowedincreasedwattslosses,low
voltagesatthe1mAresistivecurrentandexcessivepartialdischarge.Theentireorder
wasreturnedtothemanufacturer,whichidentifiedthecauseofthefailuresashaving
beenrelatedtotheassemblyoftheunits.

LatestNews
VIDEO

DEC10,2015

RestoredCustomer
Connection

NEWS

DEC10,2015

TorontoHydroto
LaunchWorld'sFirst
UnderwaterEnergy
StorageSystem
NEWS

DEC10,2015

TVASeeksComment
onProposed
TransmissionProject

NEWS

DEC10,2015

NationalGrid
Awarded23Million
forThreeMajor
InnovationProjects

LatestonT&DHow
VIDEO

DEC10,2015

RestoredCustomer
Connection

VIDEO

DEC10,2015

HowtoHostaTailgate
Session

VIDEO

DEC10,2015

CableReplacementat
MeritexCavesPart5

VIDEO

DEC2,2015

CableReplacementat
MeritexCavesPart4

MAINTENANCETESTPROGRAM

AllserviceagedarrestersarefieldtestedbyMHstaffeitheronan8or10yearcycle,
dependingonthearrester'smakeandhistory.The10kV,60Hzwattslosstestis
http://tdworld.com/substations/testingpreventssurgearresterfailures

1/4

11/12/2015

ManitobaHydroTestsSurgeArrestersatDelivery

performedand,whenpracticable,eithertheVIresponseischaracterizedorasparkover
testisperformed.TheVIcharacterizationisperformedonmetaloxidearresters,while
sparkovertestsareperformedongappedarresters.TheVIandsparkovertestsconfirm
anarrester'sprotectivecharacteristicsareatacceptablevalues.Itisimportanttonotethat
gappedarrestersmorethan25yearsoldaregenerallyrecommendedforreplacement
becauseoftheirage.Also,allarrestersundergoaninfraredscanbiannually.Arresters
withtemperaturevariationsbetweenadjacentunitsabove5C(41F)areinvestigated.
Allarresterskeptinstockforunplannedreplacementpurposesaretestedeveryfiveyears,
whilesalvagedstationclassarrestersarereacceptancetestedandreturnedtostock.
RELIABILITYIMPROVEMENT

Throughthisarrestertestphilosophy,MHhasfoundmanyunitsthateitherhavehad
designvulnerabilitiesorsufferedfromtheeffectsofdeterioration.Bothofthesesituations
generallyleadtounintentionalarresteroperation,which,becauseoftheproximityofthe
arrester,cancausedamagetoimportantequipment.Thistestprogramhastheadded
benefitofimprovingMH'selectricalsystemsreliabilityaswellasreducingthecosts
associatedwithforcedoutages.Additionally,theacceptancetestprogramhasenabled
MHtoextendthetimebetweenoutagesformaintenancetestsonarresters.This
acceptancetestprogramalsohastheaddedbenefitoffosteringthedevelopmentofin
houseexpertisebymakingavailablethenecessarytestequipmenttothoroughly
investigateproblemarresters.
RegJ.Gamblin(rgamblin@hydro.mb.ca)isatechnicalofficerintheInsulation
Engineering&TestingdepartmentofManitobaHydro,whereheisresponsibleforthe
conditionassessmentofgenerators,transformers,insulatingoil,surgearresters,bushings
andinstrumenttransformers.In1998,heearnedadiplomainelectricalengineering
technologyfromRedRiverCollege.Hehasauthoredandcoauthoredseveralpapersfor
industryconferencesonconditionassessmentandhighvoltagetesting.
KeithHill(khill@doble.com)hasbeenemployedatDobleEngineeringsince2001and
currentlyworksasaprincipalengineerintheClientServicedepartment.Heissecretary
oftheDobleClientCommitteeonArresters,Capacitors,CablesandAccessories.Priorto
joiningDoble,Hillhadover25yearsoftestingexperience,withthelast18yearsasthe
electricalsupervisorofengineeringservicesatLyondellCITGORefining(formerly
ARCO).AtARCO,Hillstartedthetestinggroupthatwasresponsiblefortheplantpower
distributionsystem,electricaltesting,powerquality,plantwideelectricalreliabilityand
infrared.Hillreceivedhisbachelor'sdegree,withamajorinpower,fromtheUniversityof
Houston.HillisamemberofIEEE,aLevelIandIIthermographer,andaformerNETA
certifiedtechnician.
pleasesendadditionalreviewpdftoLiisaColbylcolby@doble.com
SurgeArresters

Surgearrestershelppreventdamagetoapparatusduetotransientovervoltages.The
arresterprovidesalowimpedancepathtogroundforthecurrentfromalightningstrike
orswitchingovervoltageandthenrestorestoanormaloperatingcondition.Asurge
arrestermaybecomparedtoareliefvalveonaboilerorhotwaterheater.Itreleaseshigh
pressureuntilanormaloperatingconditionisreached.Whenthepressureisreturnedto
normal,thesafetyvalveisreadyforthenextoperation.Whenahighvoltage(greater
thanthenormallinevoltage)existsontheline,thearresterimmediatelyfurnishesapath
togroundandthuslimitsanddrainsofftheexcessvoltage.Thearrestermustprovidethis
reliefandthenpreventanyfurtherflowofcurrenttoground.Thearresterhastwo
functions:itmustprovideapointinthecircuitatwhichanovervoltagepulsecanpassto
ground,anditmustpreventanyfollowupcurrentfromflowingtoground.
Thetechnologyofsurgearrestershasundergonemajorchangesinthelast100years.In
theearly1900s,sparkgapswereusedtosuppressovervoltages.Inthe1930s,silicon
carbidearrestersreplacedthesparkgaps.Inthemid1970s,zincoxidegaplessarresters,
whichpossessedsuperiorprotectioncharacteristics,replacedsiliconcarbidearresters.

WhitePapers
WhitePaper:TheEnergyRevolution
TheImportanceofWeatherReadinessfor
Utilities

MOREWHITEPAPERS

Featured Video
3MACCRCorrosionPerformanceHawaiiField
Test

SHARE

SponsoredBy:

MORET&DTVVIDEO

T&DWLearningCenter
HandbookofEnergyEngineering
Calculations
SOLVEENERGYPROBLEMS
QUICKLYANDACCURATELY

AmericanElectrician'sHandbook
SixteenthEdition
Foracentury,theAmericanElectricians'
Handbookhasservedasthedefinitive
industryreferencefor...

TemporaryGroundingfor
LineworkerProtection
Thisessentialsafetyreferenceshows
howtoinstallgrounds...

VIEWCATALOG VIEWSHOPPINGCART

FeaturedJobs

SILICONCARBIDEARRESTERS

Leidos
Orlando,Florida

Siliconcarbidearrestersarecurrentlylesspopularthanthemetaloxidevaristor(MOV),
yetagreatnumberofthemarestillinservice.

Engineer(SubstationDesign)(IIV)
TriStateGeneration&Transmission
Westminster,Colorado

IntheOctober1996issueofIEEETransactionsonPowerDelivery,Dr.M.Darveniza

SeniorProtection&ControlEngineer
Leidos
Houston,

http://tdworld.com/substations/testingpreventssurgearresterfailures

2/4

11/12/2015

ManitobaHydroTestsSurgeArrestersatDelivery

recommendedallsiliconcarbidearrestersthathavebeeninserviceformorethan13years
bereplacedbecauseofmoistureingress.Histestsrevealedthatdegradationwasevident
in75%ofarresterstested.
Todetermineifasiliconcarbidearresterwarrantsreplacement,fieldtestingmustbe
performed.Theidealmethodistodeterminetheprotectivelevelofthearresterthisisnot
practicalsinceanimpulsegeneratorisrequired.Aneffectiveandmorepracticalmethod
istodeterminethewattslossofthearresterandcomparetolikearresters.

Houston,
ConstructionEngineer
U.S.DepartmentofState
,

MoreJobs>>

Bet You Haven't Seen


This

MOVARRESTERS

TheMOVarresteristhearresterusuallyinstalledtoday.Doble(Boston,Massachusetts,
U.S.)documentationrevealsthatMOVtypearrestersenteredthemarketintheUnited
Statesaround1976.Themetaloxidearrestersarewithoutgaps,unlikesiliconcarbide
arresters.Thisgaplessdesigneliminatesthehighheatassociatedwiththearcing
discharges.TheMOVarresterhastwovoltageratingsdutycycleandmaximum
continuousoperatingvoltageunlikethesiliconcarbidearrester,whichjusthasthe
dutycyclerating.Ametaloxidesurgearresterusingzincoxideblocksprovidesthebest
performance,assurgevoltageconductionstartsandstopspromptlyataprecisevoltage
level,therebyimprovingsystemprotection.Failureisreduced,asthereisnoairgap
contaminationpossibilityhowever,thereisalwaysasmallvalueofleakagecurrent
presentattheoperatingfrequency.
Itisimportantforthetestpersonneltobeawarethatwhenametaloxidearresteris
disconnectedfromanenergizedline,asmallamountofstaticchargecanberetainedby
thearrester.Asasafetyprecaution,thetestershouldinstallatemporarygroundto
dischargeanystoredenergy.

JuryFindsUtilitiesto
BlameinLasConchas
Fire
Ajurydecidedlast
monththattwoutility
companiesholdmostof
theliabilityinoneofthelargestwildfiresinNew
Mexicosrecordedhistory....
More

Signuptoreceiveourfreenewsletters
Energizing(Weekly)ViewSample
TheSmarterGrid:Initiatives,Insights,
Innovations(BiWeekly)ViewSample
Test,Monitor&Control(BiWeekly)
ViewSample

POLYMER/PORCELAINARRESTERS

ProjectsinProgress(Monthly)View
Sample

Polymerarrestersaregaininginpopularityovertheporcelainarresters.Whenareclose
operationoccursandthefaulthasnotcleared,thearresterissubjectedtoasecondfault
current.Thissecondoperationcanleadtoarresterexplosion,iftheporcelainhadalready
beenweakenedbythefirstfault.Ifthepressurereliefratingofthearresterisexceeded,
thearrestermayfailviolently,sinceitcannotcontrollablyventtheexcessgasses.Thistype
offailurecanleadtootherequipmentbeingdamagedorinjurytopersonnelwhomaybe
inthevicinityofthefailure.Becauseoftheabilityofthepolymerstationarrestertovent
outtheside,thehousingisnotweakenedwhenexposedtothefaultcurrent.Therefore,a
polymerarrestercanbereclosedonmultipletimeswithoutriskingaviolentfailure.The
polymerarrestersarelessexpensivethanporcelainarrestersandappeartoavoidsomeof
theinserviceproblems,suchasmoistureingress,oftenoccurringinporcelainarresters.
Onemanufacturerreportsthatmoistureingressisthedirectcauseoffailurein86%ofall
failures.

Etrain(BiWeekly)ViewSample

TESTINGSURGEARRESTERS

TwoofthemostcommonteststoperforminthefieldonsurgearrestersaretheDoble
powerfactortestandinfraredanalysis.Somemanufacturersstatethatnosingletestwill
indicatethecompleteoperatingcharacteristicsofanarrester.Referenceserviceadvisories
fromsomemanufacturersrecommendpowerfactortestingandinfraredasmethodsto
detectpossibleproblemscausedbymoistureingress.Fieldtestingofarrestersbypower
factor,infraredorothermethodsisusedasareference.

GridOptimization(Weekly)View
Sample
VegetationManagementInsights
(Monthly)ViewSample
ProductInsider(Monthly)View
Sample
ExperienceStationNewsletter
(Monthly)ViewSample
DailyEnergyFix(Daily)View
Sample
IEEEPESShowUpdate(ShowDaily)
ViewSample
TheEnergyTimes(Weekly)View
Sample
Lineman'sRodeoNews(Weekly)
ViewSample
EMAIL*
COUNTRY*

UnitedStates

Enteryouremailabovetoreceivemessagesabout
offeringsbyPenton,itsbrands,affiliatesand/orthird
partypartners,consistentwithPentonsPrivacyPolicy.

Differentmodelsandmakesofarresterswillhavedifferentwattslossreadings.Thetester
isattemptingtoidentifyavarianceinthepastwattslossreadings.Powerfactorisnot
calculatedbecausethecurrentissosmall.Thearrestershouldhaveavisualinspectionto
detectcracksintheporcelain,abnormalruststainingandanyabnormalphysical
conditionofthearresterthatisobserved.Incorrectfactoryinstallationofarrestergaskets
hasbeendetectedbyvisualinspectionuponreceiptofthearresters.
HANDLINGSUSPECTARRESTERS

Adamagedsealgappedarrestershouldbehandledwithcare.Becauseofincreased
pressurecausedbythedestructionofinternalelements,adefectivearrestercouldbean
explosivehazard.Ifthedecisionismadetoperformaninternalinspectionofafailed
arrester,ensurethearresterhasventedproperly.Likewise,donotthrowawayadefective
arresterthearrestershouldbeproperlyventedbeforedisposing.

http://tdworld.com/substations/testingpreventssurgearresterfailures

3/4

11/12/2015

ManitobaHydroTestsSurgeArrestersatDelivery
SHARE

PRINT

REPRINTS

Tweet

Recommend

FAVORITE EMAIL

DiscussthisArticle

onDec9,2013

vipinmehta(notverified)

Pleaseprovidesupportingdocumenttoestablishthattheporcelainsurgearrestersareproneto
moistureingress.
reply LogInorRegistertopostcomments

NAME:

Anonymous

SignInorregistertouseyourTDWorldID
EMAIL:

YOURCOMMENT:*

SUBMITCOMMENT

Related Articles
LaserScanningisSubstationBound
ABBWinsPowerOrderinCanada
HVSurgeArresterRetrofitServiceProvidesLightningProtectionforOutdoorSubstations
MegaMonitoringInitiative
Canada:ALSTOMWinsHVDCTransformerContract

TDWorld.com
OverheadDistribution OverheadTransmission UndergroundT&D Substations SmartGrid Business SmartEnergyConsumer
Renewables

Site Features

Penton Corporate

MediaCenter

AboutUs

Subscribe

Advertise

Newsletters

TermsofService

RSS

PrivacyPolicy

Sitemap

Follow Us

ViewMobileSite

Search TDWorld.com

Related Penton Sites


EC&M ElectricalWholesaling ElectricalMarketing TDCompare Lineman'sRodeo

Copyright2015Penton

http://tdworld.com/substations/testingpreventssurgearresterfailures

4/4

Anda mungkin juga menyukai