Anda di halaman 1dari 48

PT.

GUNON INTENATIONAL
TAMAN TEKNO H3 NO. 1-2
BSD CITY TANGERANG
INDONESIA 15134
PHONE : +62 21 7562680 FAX : +62 21 7562685
gunon@gunon.com
pranoto@gunon.com

PT. GUNON INTENATIONAL


We are dealing in the Fire Protection and Detection System. We
provide the systems based on Guideline Standards and Approval
Bodies :

PT. GUNON INTENATIONAL


We are also a distributor and agent of famous brands in the world
as follows :

PT. GUNON INTENATIONAL


Based on the standard design guidelines, approval bodies,
factorys supports and our experiences, we provide :
* Consultation
* System Design
* Budget Estimation
* Sales
* Maintenance
* and after sales services

PT. GUNON INTENATIONAL


On the markets :
* High Rise Building
* Telecommunication and Data Centre
* Industrial, Petrochemical and Power Plant
* Oil and Gas

PT. GUNON INTENATIONAL


Projects Reference

JANUS FIRE SYSTEMS

YOUR GATEWAY TO A NEW KIND OF SERVICE


Established by four leading experts in the fire protection industry with a combined
experience of over 120 years, Janus Fire Systems is based on the principle of offering
its clients superior products and services.
Address: 1102 Rupcich, Crown Point, IN 46307, United States
Phone:(219) 663-1600

JANUS FIRE SYSTEMS


Janus Fire Systems fire suppression products are available
worldwide :

JANUS FIRE SYSTEMS


Janus Fire Systems fire suppression products are available
worldwide :

JANUS FIRE SYSTEMS


Janus Fire Systems fire suppression products are available
worldwide :

10

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
Typical Clean Agent System Layout

11

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
When to use Clean Agents ?
* Protecting high value assets
- Energized electrical areas
- Artifacts and archived data
* Continuous operations must be
maintained
* Life safety is a concern
- Emergency communications
- Occupied or may be occupied
* Must be a clean agent
12

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
Typical areas of fire protection:
* Computer Rooms
* Data Storage Facilities
* Telecommunications
* Oil & Gas Petrochemical Facilities
* Museums
* Libraries and Archives
* Medical Facilities
* Manufacturing Facilities
* Storage Areas
13

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components:
* NovecTM 1230 Fire Protection Fluid
* Agent Storage Components and Accessories
*Agent Fluid Distribution Components
* Control Panels
* Detection and Alarm Devices
* Flow Calculation Software

14

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
What are Clean Agents?
Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave a
residue upon evaporation
(NFPA 2001, Sec. 3.3.6)
* Does not conduct electricity
* Gaseous
* Does not leave a residue behind
* Is not carbon dioxide

15

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Novec 1230 is a highly-efficient clean agent :
* Wont Damage Equipment:
- Electrically non-conductive
- Non-corrosive
* No Downtime or Cleanup:
- Evaporates cleanly, leaving no residue
- Does not damage electronics
- Can be safely used on energized equipment,
helping to ensure continuity of operations
during a fire emergency
16

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Novec 1230 is a highly-efficient clean agent :

17

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Designed to Provide a Large Margin of Human Safety

Clean agents fire suppression applications often include the presence of people, so
safety to human life is a critical issue when selecting a fire suppression product. 3M
Novec 1230 Fire Protection Fluid is a highly efficient fire extinguishant that's safe for
use in occupied spaces. The large margin between Novec 1230 fluid's use
concentration and "Non Observed Adverse Effects Level" provides the largest margin
of safety relative to other chemical clean agents, CO2, and inert gas mixtures.

18

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Designed to Provide a Large Margin of
Human Safety

19

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Novec 1230 Fluid Performance

Dont Just Manage a Fire. Extinguish It.


3M Novec 1230 Fire Protection Fluid is a highly-effective clean agent fire
suppressant, designed to extinguish a fire in its incipient stage before it has a chance to
spread. It is applied as a gas, but is liquid at room temperature, and can be effectively
used in streaming, flooding systems, or for use in inerting and explosion suppression
applications.

20

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Novec 1230 Fluid Performance
Knocks down fires fast
Novec 1230 Fluid has a very low heat of vaporization, approximately 25 times less than
that of water. This, along with a higher vapor pressure, causes Novec 1230 Fluid to
evaporate more than 50 times faster than water. It also allows the clean agent to
transition from a liquid to a gaseous state very rapidly when discharged through a
nozzle, and readily achieve vapor extinguishing concentrations in air. With high
extinguishing efficiency and a wide margin of safety, Novec 1230 fluid is a great
alternative to water sprinkler systems, foam and dry chemicals due to:
* Low toxicity (no harm to personnel)
* Extinguishes fires in less than half the time of CO2 & inert gases
* No damage to sensitive equipment
* Not targeted for emission reduction or phaseout

21

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Sustainability :
From its inception, 3M Novec 1230 Fire Protection Fluid
was designed to address the global demand for a sustainable
clean agent. It is effective at extinguishing fires and
is not targeted for emission reduction, phase-out or
phase-down. Novec 1230 fluid offers the sustainable clean
agent properties you need, such as:
* Zero ozone depletion potential (ODP)
* An atmospheric lifetime of 5 days, compared to 65 years for halons
* A global warming potential (GWP) of less than 1 about the same as naturallyoccurring carbon dioxide

22

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Sustainability :

23

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Agent Storage Components
Janus Fire Systems provides 500 Series Novec 1230 Clean Agent Cylinders.
Cylinders are charged with the clean agent to a maximum filling density of up to 70
lb./ft.3 (1121 kg/m3) of cylinder volume.
Each cylinder is super-pressurized with dry nitrogen to 500 psi (34.48 bar)
All cylinders are equipped with an identification nameplate indicating the initial fill
quantity of the clean agent.

24

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Agent Storage Components
Janus Fire Systems have 3 (three) cylinder series :
* Sv Series : filling capacity 10.00 - 59.40 kg
* Mv Series : filling capacity 57.20 191.40 kg
* Lv Series : filling capacity 137.9 453.6 kg
Sv

Mv

Lv

25

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Agent Storage Components
500 Series Novec 1230 Clean Agent Cylinders offer Enhanced Design Capability
compared with 360 psig (25 bars) cylinders :
* Less required Clean Agent
An additional Clean Agent required when the pressure and flow rate of agent in the pipe
and nozzles has been met the limitation of Pipe Size and Flow Rate
* Smaller Size and Lower Quantity of Cylinders
Increasing Size and Quantity of Cylinders is required to get more pressure as the
smaller size and lower quantity of cylinders can not meet the requirement of listed
system such as Discharge Time, Design Concentration, Flow Rate and Pressure at the
distribution pipe and nozzles
* Longer Pipe Length and Larger Pipe Network
* Smaller Pipe Diameters

26

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Agent Storage Components
* Other features provided and affixed to the cylinders :
- Cylinder Low Pressure Supervisory Switch
- Level Liquid Indicator
The features is designed to monitor Pressure and Agent are in good condition and
ready for used when its needed. With this features, no need to do daily inspection
therefore more effective and efficient on maintenance purpose.
* Janus

Fire Systems 500 Series offer more effective, efficienct


and flexibility

27

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Sv Series Agent Storage Components

28

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Sv Series Agent Storage Components
Cylinder Valve:
Controls release of the clean agent
Differential pressure operated valve
Forged brass body and cap
Shipped with anti-recoil safety plug installed in
the discharge outlet

Cylinder
Valve
Dip Tube

Dip Tube:
Extends from cylinder neck down to the bottom of
the cylinder
Cylinder Bracket
One strap and rail with accompanying twirl nuts
and cap screws
Cylinder:
Welded seam cylinder
Manufactured to requirements of USDOT
(Department of Transportation) and Transport
Canada for compressed gas
Designed for vertical mounting only

Cylinder
Bracket

Cylinder

29

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Sv Series Agent Storage Components
Valve Actuation Connection (1)
Attachment point for electric (primary) or
pneumatic (slave) valve actuator.

Pressure Gauge (2) Monitors


cylinder pressure.

Pilot Actuation Port


(6) Applies
actuation pressure to
slave cylinders or
discharge pressure
switch. 3/8 in (10 mm)
female NPT
connection.

Discharge Outlet (5)


Connects valve to
discharge piping. 11/4 in (32 mm) female
NPT connection.

Low-Pressure Supervisory Switch (3) Mounted


to cylinder valve. Monitor and annunciates low
cylinder pressure.

Rupture Disc (4)


Protects cylinder
from over pressure.
Rupture point
between 850 psi
(58.6 bar) and 1000
psi (68.9 bar)

30

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Mv Series Agent Storage Components

31

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Mv Series Agent Storage Components
Has features identical to Sv
Series Cylinder Assembly

Cylinder
Valve
Dip
Tube

Liquid Level Indicator:


Nonmagnetic tube
containing a measurement
tape attached to a magnet
As tape is removed, magnet
engages at the liquid surface
where a floating metallic ball
sits
Measurement can be
compared with the
appropriate chart in the
design manual to determine
the current fill

Liquid
Level
Indicato
r

Cylinder
Bracket

Cylinder

32

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Mv Series Agent Storage Components
Valve Actuation Connection (1)
Attachment point for electric (primary) or
pneumatic (slave) valve actuator.

Pressure Gauge Connection (2) Attachment point for


pressure gauge

Rupture Disc (4)


Protects cylinder from
over pressure. Rupture
point between 850 psi
(58.6 bar) and 1000 psi
(68.9 bar)

Discharge Outlet (5)


Connects valve to
discharge piping. 2 in
(50 mm) grooved
connection

Pilot Actuation Port


(6) Applies
actuation pressure to
slave cylinders or
discharge pressure
switch. in (8 mm)
female NPT
connection

Low-Pressure Supervisory
Switch Connection (3)
Attachment point for lowpressure supervisory switch.

33

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Lv Series Agent Storage Components

34

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Lv Series Agent Storage Components
Has features identical to Mv Series
Cylinder Assembly except:

Cylinder
Valve

Lv Series 1000 lb Cylinder not


Transport Canada approved.

Dip Tube

Rupture Disc:
Protects cylinder from overpressure
Rupture point is between 850 psi (58.6 bar)
and 1000 psi (68.9 bar)

Rupture Disc

Liquid Level
Indicator

Cylinder
Bracket
Cylinder

35

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Lv Series Agent Storage Components
Valve Actuation Connection (1)
Attachment point for electric (primary) or
pneumatic (slave) valve actuator.
Pressure Gauge Connection (2) Attachment point for
pressure gauge

Discharge Outlet (4)


Connects valve to
discharge piping. 3 in
(80 mm) grooved
connection.
Pilot Actuation Port
(5) Applies
actuation pressure to
slave cylinders or
discharge pressure
switch. in (8 mm)
female NPT
connection

Low-Pressure Supervisory
Switch Connection (3)
Attachment point for lowpressure supervisory switch.

36

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Multi Cylinders Application
Multi Cylinders application is provided for the enclosures with the volume is larger than
can be covered by single cylinder.
* Up to fifteen slave cylinders may be actuated from one primary cylinder
* Maximum length of 100 ft (30.4 m) of pilot hose or (8 mm) copper
tubing on either side of the primary cylinder
* Maximum length of 25 ft (7.62 m) of (8 mm) pilot piping on either
side of the primary cylinder

37

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Multi Cylinders Application

38

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Multi Zones Application
Multiple hazards can often be protected with a common set of cylinders by using
selector valves. Selector valves components are required in these specific cylinder
arrangements that utilize selector valves to allow the protection of multiple hazards or
hazard zones by one set of clean agent cylinder.

39

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Multi Zones Application

40

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Agent Fluid Distribution Components
These components consist of the discharge nozzles used to atomize the liquid Novec
1230 fluid and introduce it into a protected hazard along with the associated piping
system.
* Discharge Nozzle Ports : 4, 6, or 8 port (90, 180, 360)
* Maximum nozzle height for a protected space is 18 ft 4 in (5.59 m) per tier of nozzles.
* Additional tiers are required for nozzle heights greater than 18 ft 4 in.
* Nozzles must be mounted within 4 ft 5 in (1.35 m) of the ceiling

41

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Components : Agent Fluid Distribution Components

42

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Component : Control Panel
* For systems requiring UL listing, the control panel must be UL listed and compatible
with the electrical valve actuator as indicated in the control panel manual.
* For systems requiring FM approval, the control panel must be FM approved and
compatible with the electric valve actuator as indicated in the control panel manual.
* The control panel should be located in an accessible area and installed in compliance
with NFPA 72 (National Fire Alarm Code).

43

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Component : Control Panel

44

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Component : Detection and Alarm Devices
* Detector selection is dependent upon hazard occupancy and environmental
conditions.
* Systems are designed to extinguish a fire rapidly in its incipient stage. The use of
smoke detectors of appropriate type must be considered to provide the earliest
possible indication of a fire detection with a low susceptibility to false alarms.
* For systems requiring UL listing, detectors must be UL listed and compatible with the
control panel as indicated in the control panel manual.
* Air sampling detection systems can also be utilized.
* In most applications, the detection devices are installed in a cross-zone (double
knock) or voting configuration. Cross-zoning of early warning detectors affords
stability yet provides early detection.

45

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Component : Detection and Alarm Devices
* Audible and visual devices may be utilized to indicate alarm conditions, system
status, or trouble conditions within the system.
* Audible alarm devices must be of a sufficient decibel level to be heard over the
maximum noise level in the protected hazard.

46

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System
System Component : Flow Calculation Software

47

JANUS FIRE SYSTEMS


NovecTM 1230 Clean Agent Suppression System

48