Anda di halaman 1dari 14

Majan Electricity Company

Distribution Control Center

Appendix -A

DCC SCADA Input /Output List


For Indoor 33/11 kV Primary
Substations

TABLE OF CONTENTS :

Appendix-A SCADA I/O List For Indoor Substation

Page 1 of 14

Majan Electricity Company


Distribution Control Center

33KV INCOMER FEEDER---------------------------------------------------------------- 3


33KV BUS SECTION & BUSBAR SIGNALS:------------------------------------------ 5
33 KV TRANSFORMER FEEDER:------------------------------------------------------- 7
33/11 KV TRANSFORMER--------------------------------------------------------------- 8
11KV INCOMER FEEDER :-------------------------------------------------------------- 9
11KV BUS SECTION & BUS BAR SIGNALS:--------------------------------------- 10
11KV OUTGOING FEEDER SIGNALS:----------------------------------------------- 11
11KV CAPACITOR BANK /FEEDER:-------------------------------------------------- 12
11KV AUXILIARY TRANSFORMER FEEDER:--------------------------------------- 14
STATION COMMON SIGNALS:-------------------------------------------------------- 15

Appendix-A SCADA I/O List For Indoor Substation

Page 2 of 14

Majan Electricity Company


Distribution Control Center

33KV Incomer Feeder (Not Applicable)


Signa Signal Name
l Type
A- Measurements

Remarks

Current (A)

AMI

Voltage (kV)
Active power (MW)
Reactive power (MVAr)

B- Energy Metering
(ITI)

Active energy (+MWh)


Reactive energy (+MVArh)

C- Status Indications
Circuit Breaker status (Closed /Opened)

DPI

Earth Switch status (Closed /Opened)


Control Level status (Station /DCC)
Synchrocheck status (On / Off / Override)

D- Controls
DCO
SCO

Circuit Breaker control (Close /Open)


Synchrocheck selection (On /Off / Override)
Trip relay Reset

E- Alarms
Trip relay operated
Circuit Breaker Out of Service

CB Racked Out

CB alarm (SF6 Low or Spring Discharged)


Circuit Breaker faulty
Trip Circuit Faulty
Cable Diff protection operated

SPI

Over Current O/C protection operated


Earth Fault E/F protection operated
Protection faulty / pilot cable faulty
Bay AC MCB off /supply fail
Bay DC MCB off /supply fail
VT failure

Appendix-A SCADA I/O List For Indoor Substation

Page 3 of 14

Majan Electricity Company


Distribution Control Center

33kV Bus Section & Busbar Signals: (Not Applicable)

Signa Signal Name


l Type
A- Measurements

Remarks

Bus Section Current (A)


Busbar 1 Voltage (kV)

AMI

Busbar 2 Voltage (kV)


Active power (MW)
Reactive power (MVAr)

B- Status Indications
Circuit Breaker status (Closed /Opened)
Earth Switch-1 status (Closed /Opened)

DPI

Earth Switch-2 status (Closed /Opened)


Control Level status (Station /DCC)
Synchrocheck status (On /Off / Override)

C- Controls
DCO
SCO

Circuit Breaker control (Close /Open)


Synchrocheck selection (On /Off / Override)
Trip relay Reset

D- Alarms
SPI

Trip relay operated


Circuit Breaker Out of Service

CB Racked Out

CB alarm (SF6 Low or Spring Discharged)


Circuit breaker faulty
Trip Circuit Faulty

Over Current O/C protection operated


Earth Fault E/F protection operated
Over current Protection faulty
Busbar Protection operated
Busbar Protection faulty

Appendix-A SCADA I/O List For Indoor Substation

Page 4 of 14

Majan Electricity Company


Distribution Control Center

Bay AC MCB off /supply fail


Bay DC MCB off /supply fail
BB-1 VT failure
BB-2 VT failure

Appendix-A SCADA I/O List For Indoor Substation

Page 5 of 14

Majan Electricity Company


Distribution Control Center

33 KV Transformer Feeder:

Signa Signal Name


l
A- Measurements
AMI

Remarks

Current (A)
Voltage (kV)

B- Status Indications
DPI

Circuit Breaker status (Closed


/Opened)
CB Control Level status (Station /DCC)
Earth Switch status (Closed /Opened)

C- Controls
DCO

Circuit Breaker control (Close /Open)

SCO

Trip relay Reset

D- Alarms
Trip Relay Operated
Circuit Breaker faulty (inoperative)
Circuit Breaker Out of Service

CB Test or Service /Racked-out position

CB alarm (SF6 Low or Spring Discharged)

SPI

Trip Circuit Faulty


Over Current O/C protection operated
Earth Fault E/F protection operated
CB Protection faulty
AC MCB off /supply fail
DC MCB off /supply fail

Appendix-A SCADA I/O List For Indoor Substation

Page 6 of 14

Majan Electricity Company


Distribution Control Center

33/11.5 kV Transformer
Signa Signal Name
l
A- Measurements

Remarks

AMI

In case of Analogue Measurements

Tap Position indication

B- Status Indications

DPI

Transformer tap change control mode


status (Auto/Manual)
TC Operation Mode status (Master
/Follower /Independent)

(TX1-Master, TX2-Follower &


TX3-Independent) Normal Operations.

TC Control Level status (Station /DCC)

STI

Tap Position indication

In case of Digital Measurements

C- Controls
DCO

Tap change control mode selection


(Auto/Manual)

RCO

TC Step control (Raise /Lower)

D- Alarms
TX Pressure relief alarm
TX Pressure relief protection operated
TX Buchholtz alarm
TX Buchholtz protection operated
TX Temperature alarm
TX Oil Temp. Alarm
TX Oil Temp. Protection operated

SPI

TX Winding Temperature alarm


TX Winding Temp protection operated
TX Oil Level low
TX Tap Change operation fault

Incomplete , or Out of Step operation

TX Tap Change protection operated


TX Forced cooling Fail
TC AC MCB off /supply fail
TC DC MCB off /supply fail

Appendix-A SCADA I/O List For Indoor Substation

Page 7 of 14

Majan Electricity Company


Distribution Control Center

11KV Incomer Feeder:

Signa Signal Name


l
A- Measurements

Remarks

Current (A)
Voltage (kV)

AMI

Active Power (MW)


Reactive Power (MVAr)
Power Factor (PF)

B- Energy Metering
Active energy (MWh)

ITI

Reactive energy (MVArh)

C- Status Indications
DPI

Circuit Breaker status (Closed


/Opened)
CB Control Level status (Station /DCC)
Earth Switch status (Closed /Opened)

D- Controls
DCO

Circuit Breaker control (Close /Open)

SCO

Trip relay reset

E- Alarms
CB alarm (SF6 Low or Spring Discharged)
Circuit Breaker Out of Service

Test or racked out position

Trip Circuit Faulty


Directional Over Current O/C protection
operated

SPI

Directional Earth Fault protection


SBEF Protection operated
Differential Relay Protection operated
Restricted Earth Fault protection
operated
Bay AC MCB off /supply fail
Bay DC MCB off /supply fail
VT failure

Appendix-A SCADA I/O List For Indoor Substation

Page 8 of 14

Majan Electricity Company


Distribution Control Center

11kV Bus Section & Bus bar Signals:


Signa Signal Name
l Type
A- Measurements
AMI

Remarks

Current (A)

B- Status Indications
Circuit Breaker status (Closed /Opened)
Earth Switch-1 status (Closed /Opened)

DPI

Earth Switch-2 status (Closed /Opened)


Control Level status (Station /DCC)
Synchrocheck status (On /Off / Override)
Cross tripping Selector Switch

C- Controls
DCO

Circuit Breaker control (Close /Open)


Synchrocheck Selector (On /Off / Override)

D- Alarms
Trip relay operated
Circuit Breaker Out of Service

Test position / CB Racked Out

CB alarm (SF6 Low or Spring Discharged)


Trip Circuit Faulty

SPI

Over current and earth fault relay faulty


Under Frequency (U/F) BB1 operated
Under Frequency (U/F) BB2 operated
Bay AC MCB off /supply fail
Bay DC MCB off /supply fail
VT-1 & VT-2 Fail
Over Current O/C protection operated
Earth Fault E/F protection operated

Appendix-A SCADA I/O List For Indoor Substation

Page 9 of 14

Majan Electricity Company


Distribution Control Center

11kV Outgoing Feeder Signals:

Signa Signal Name


l
A- Measurements

Remarks

3 Phase Current (A)

AMI

Active Power (MW)


Reactive Power (MVAr)
Power Factor (PF)

B- Energy Metering
Active energy (MWh)

ITI

Reactive energy (MVArh)

C- Status Indications

DPI

Circuit Breaker status (Closed


/Opened)
CB Control Level status (Station /DCC)
Earth Switch status (Closed /Opened)
Autorecloser relay status ( In/Out )

D- Controls
DCO

Circuit Breaker control (Close /Open)

SCO

Trip Relay and Autoreclose relay Reset

E- Alarms
CB alarm (SF6 Low or Spring Discharged)
Circuit Breaker Out of Service

Test or racked out position

Circuit breaker faulty (Inoperative)


Trip Circuit Faulty (inoperative)
Over Current protection operated
Earth Fault protection operated

SPI

Broken Conductor Protection operated


Autorecloser relay operated
Autorecloser relay Lockout
Trip Relay Operated
Protection Operated
Protection relay faulty
Bay AC MCB off /supply fail
Bay DC MCB off /supply fail
VT failure

Appendix-A SCADA I/O List For Indoor Substation

Page 10 of 14

Majan Electricity Company


Distribution Control Center

11kV Capacitor Bank /Feeder:


Signa Signal Name
l
A- Measurements

Remarks

Current (A)

AMI

Voltage (KV)
Active Power (MW)
Reactive Power (MVAr)

B- Status Indications
Circuit Breaker status (Closed
/Opened)
CB Control Level status (Station /DCC)
Earth Switch status (Closed /Opened)
Capacitor bank control mode status
(Auto/Manual)
Capacitor Bank stage 1 status (In /Out)

DPI

Capacitor Bank stage 2 status (In /Out)


Capacitor Bank stage 3 status (In /Out)
Capacitor Bank stage 4 status (In /Out)
Capacitor Bank stage 5 status (In /Out)
Capacitor Bank Control Level status
(Station /DCC)

C- Controls
Circuit Breaker control (Close /Open)

DCO

SCO

Capacitor bank control mode selection


(Auto/Manual)
Capacitor Bank stage 1 control (In
/Out)
Capacitor Bank stage 2 control (In
/Out)
Capacitor Bank stage 3 control (In
/Out)
Capacitor Bank stage 4 control (In
/Out)
Capacitor Bank stage 5 control (In
/Out)
Trip Relay reset

D- Alarms
SPI

CB alarm (SF6 Low or Spring Discharged)


Circuit Breaker Out of Service

Test or racked out position

Appendix-A SCADA I/O List For Indoor Substation

Page 11 of 14

Majan Electricity Company


Distribution Control Center

Circuit breaker faulty (Inoperative)


Trip Circuit Faulty
Over Current protection operated
Earth Fault protection operated
Trip Relay Operated
Under voltage protection operated
Capacitor bank Under Voltage Trip
Capacitor bank Over Voltage Trip
Voltage Out of Balance alarm
Capacitor Bank AC MCB off /supply fail
Capacitor Bank DC MCB off /supply fail
Bay AC MCB off /supply fail
Bay DC MCB off /supply fail
VT failure

Appendix-A SCADA I/O List For Indoor Substation

Page 12 of 14

Majan Electricity Company


Distribution Control Center

11kV Auxiliary Transformer Feeder:


Signa Signal Name
l
A- Measurements
AMI

Remarks

Current (A)

B- Status Indications
DPI

Circuit Breaker status (Closed


/Opened)
CB Control Level status (Station /DCC)
Earth Switch status (Closed /Opened)

C- Controls
DCO

Circuit Breaker control (Close /Open)

D- Alarms
CB alarm (SF6 Low or Spring Discharged)
Circuit Breaker Out of Service

Test or racked out position

Circuit breaker faulty (Inoperative)


Trip Circuit Faulty
Trip Relay Operated

SPI

Over Current protection operated


Earth Fault protection operated
Auxiliary Transformer alarm

Common signal for Aux Transformer alarms

Bay AC MCB off /supply fail


Bay DC MCB off /supply fail

Appendix-A SCADA I/O List For Indoor Substation

Page 13 of 14

Majan Electricity Company


Distribution Control Center

Station Common Signals:


Signa Signal Name
l
A- Measurements

Remarks

415V SWBD Voltage (V)

AMI

415V SWBD Current (I)


Humidity
Room Temperature

B- Status Indications
DPI

Dummy Breaker status (Closed


/Opened)
Station Attended / Unattended

Station Door Open / Close

C- Controls
DCO

Dummy Breaker control (Close /Open)

D- Alarms
Station LVAC supply system alarm
110V DC Charger 1 Alarm
110V DC Charger 2 Alarm
110V DC Load MCB trip
110V DC Battery Circuit Fault

SPI

110/48 V DC Converter Power supply


fail
110 /48 V DC Outgoing MCB
LVAC Supply fail
Telecommunication Fail
Smoke /Fire Detecting System operated
5 Spare signals

To be agreed

Appendix-A SCADA I/O List For Indoor Substation

Page 14 of 14