5.
CONTROL SYSTEM
17
5.1 General
Good, low-impedance earthing is essential for any
kind of low-level signal handling system. Pay great
attention, therefore, to good earth binding of
control panels, desks, free-standing power supplies
and PCs / terminals with peripherals. Modular
desks and panels should be reliably bound
together and furnished equipment bound to the
frame with dedicated terminals wired to PE
terminal blocks or bars.
Check from the installation manual that the
earthing / screening diagram has been strictly
followed using low-impedance bindings and that
there are no unintentional connections or leaks
connecting different earth-bound systems.
5.3 Powering up
18
programmed for correct signal types, delays, alarm
levels and grouped relaying to sound/flash and
remote alarms. A signal-specific check should be
made as soon as installations are complete,
systematically checking through each connected
signal.
Check that the monitoring system, PLC and UPS
faults actuate the correct system fault alarms in the
local / remote alarm system by simulating power,
communication interrupts and other similar faults.
Any system check facilities provided by control
software / hardware should be run to check for
system faults. Set the monitoring system / PLC
clocks to the correct date and time. Test that event
and alarm reporting is functional by simulating a
signal on some connected circuit. Watchdog
checks and program running indications should
indicate full functionality before now proceeding to
testing connected systems and circuits.
While testing other parts of the entire controlgear,
you will have to return to the centralised control to
check those parts of tested circuits which are
located in the desk/panel and also to check alarms
and indication signals transferred to these desks/
panels.
19
generating set control
auto
engine
start
Starting sequence:
Starts engine to off line
Automatic synchronisingby the PLC
Loading toremote reference level (MMI)
Cancels STOPorder
manual
Engine control:
kWenableinGRID,
Isoch enable in Island
Generator control:
P.F. enable
engine control
stop
Stopping sequence:
Automatic unloading
Automatic breaker open
2 minutes off line running
Stop
speed
kW/isoch
voltage
pf
droop
droop
fuel
excitation
increase decrease
breaker
closed
open
generator control
engine
start
increase
synchronising
stop
engine start
engine stop
breaker close
breaker open
engine shutdown reset
breaker trip reset
lamp test
- 2 stage overcurrent
- 2 stage earth fault
- Reverse power
- Over/underfrequency
- Over/undervoltage
- Unbalance
- Underreactance
decrease
select/start
Initiates manual
synchroinising
Actual synchronising is
made at common section
20
The figure 5.8 shows a typical connection of the
protection relay.