Karl Tornroos
GE Energy Services
Atlanta, GA
g
© 2004 General Electric Company. GER-4223 (01/04)
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
GE Generator Fleet Demographics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Reasons for Generator Upgrades and Rewinds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Generator Reliability and Aging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
How to Improve the Reliability of Aging Generators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Rewinding for Higher Output and Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Rewinding for Reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Generator Service Issues and GE Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Generator Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
List of Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Introduction
Since the 19th century GE has manufactured All GE turbine generators can be subdivided
and placed in service over 8000 medium and into two main groups: large and medium tur-
large power generators, many of them still in bine- generators designed and manufactured by
service today. By utilizing progressive designs GE factories in Schenectady, NY and Lynn, MA.
and developing reliable materials that have been GE has manufactured a number of large steam
proven in a large number of installations, GE turbine driven generators (LSTG), rated from
has amassed reliability records for GE genera- 100 to 1600 MVA. The nucleus of this fleet are
tors that have provided decades of sustained the liquid-cooled stator winding design genera-
service. tors, which have been in service since the late
1950s.
The 1980s saw a dramatic growth in the rebuild-
ing and upgrading of turbine-driven generators
driven by the need to reduce maintenance on
Reasons for Generator Upgrades and
aging fleets—while also adding reliable power Rewinds
at minimal cost. As today’s operators face the When evaluating generator upgrade alterna-
same urgent requirements, the pace of the tives, plant operators must consider many alter-
rebuild and upgrade activity continues to accel- natives, including:
erate. ■ Planned service life
■ Base-load or start-stop cyclic duty
GE Generator Fleet Demographics
■ Load requirements (megawatts and
Despite a sharp increase in the number of the
megavars)
new generators placed in service during the past
few years, many GE generators currently in serv- ■ Reliability requirements
ice are 30 years old or older. Figure 1 represents Using these critical parameters to establish the
all GE turbine-generators in service, regardless type and extent of the required upgrade, GE
of design or size, grouped according to age seg- performs a comprehensive review of the total
ments. generator design and offers a complex of
upgrades that can meet the objective. This practices and advanced technology proce-
review includes the requirements for the gener- dures—based on our up-to-date experience with
ator coolers, excitation system, auxiliaries and worldwide fleets—that can be applied to gener-
monitoring systems, as well as the stator and ator upgrades and rewinds. This enables GE to
field windings. provide customers with coherent and compre-
While the intended use of the unit will provide hensive generator protection systems as part of
guidelines for the rebuild, the existing condi- our full service offerings.
tion of the equipment is usually an equally In recent years there has been a noticeable
important factor in determining the extent of increase in the number of generator forced out-
the rebuild that is necessary. Proper mainte- ages. While a variety of reasons contribute to this
nance on a regularly scheduled basis as recom- increase, two key causes have been clearly iden-
mended by the OEM will help retain the excel- tified: operational incidents and aging of the
lent reliability of GE turbine-generators. generators. Since age is the most common cause
Conversely, lack of regular maintenance, not fol- of generator failures, this paper primarily focus-
lowing the manufacturer’s instructions, or oper- es on aging generators and optimum solutions
ating the generator beyond the prescribed limits to improve their reliability.
can result in accelerated wear and the need for
more extensive rebuild at a later date. Generator Reliability and Aging
This paper also refers the reader to relevant GE Older units constitute an increasingly higher
publications that address generator reliability percentage of installed industry capacity and
concerns in more detail—including GER-4212 reserve margins on typical systems—and they
(Generator Rotor Design, Operational Issues and represent an important segment of the industry.
Refurbishment Options) and GER-3751A (Under- Examination of industry data reveals several
standing, Diagnosing and Repairing Leaks in Water- important facts about this segment.
Cooled Generator Stator Windings). In addition to Figure 2a illustrates a typical trend of component
these reference publications, GE maintains a failure rates with age for one manufacturer.
continually expanding knowledge base of best Though highly reliable, turbine-generator units
Figure 2a. Turbine-generator reliability trend Figure 2b. Turbine-generator reliability improvement trend
are not immune to age deterioration. During its ■ Field shorted turns, vibration
normal life expectancy most technical equip- ■ Field top turn break
ment exhibits a basic pattern of failure rate,
■ Field winding failure due to H2S
which is commonly referred to as a “bathtub”
corrosion
curve. For example, after an initial operating
period called the “debugging” stage, the power ■ Generator stator winding and core
generator has a normal operating period where damage
unit reliability remains fairly constant. However, ■ Stator winding insulation failure
after many years of service the failure rate tends ■ Field winding failure
to increase in the “wear-out” period.
■ Stator winding ground failure, core
Replacement of the worn components will
damage
improve reliability of the generator, resetting
the failure rate, as shown on Figure 2b. ■ Field motoring incident, shaft damage
With Water-Cooled Stator Windings). Many of these original equipment manufacturer to enhance
stator windings have already been replaced with the performance of the machine and support a
the new, improved design windings. turbine uprate. The economics of such design
upgrades can often help to justify the cost of
How to Improve Reliability of Aging the rewind activity. By considering the vintage
Generators and type of the original machine design, tur-
bine output, and uprate objectives, GE can
The preceding information leads to the ques-
develop an optimized solution that is specific to
tion, "What is needed to prevent a forced outage
the generator.
and to extend the operating life of a generator?" To
answer this question, and make a meaningful Rewinding for Reliability
assessment of the condition of an operating
unit, a thorough inspection and test must be Stators
performed. In addition to these procedures, GE Advances in the area of non-metallic materials,
also reviews inspection reports from prior years insulation systems and composites allow signifi-
to look for evidence of mechanical or electrical cant reliability improvements and life extension
wear, distress, and aging. By comparing the to be achieved by replacing old materials that
inspection results of a particular generator with are approaching the end of their useful lives. An
our database of information for similar units, we example of this type of enhancement is the
can identify components likely to impact the replacement of an asphalt-insulated stator wind-
generator’s future reliability and make correc- ing with a modern epoxy-based insulation sys-
tive recommendations. tem. Since the insulation is life-limited, by
If a unit has not had an inspection for several replacing the stator winding with a new one—
years, or there has been a recent incident that often of a higher thermal class insulation sys-
potentially affected the condition of the gener- tem—it is possible to reset the "time clock" on
ator, it would be prudent to perform an inspec- the stator winding. Beyond simple replacement
tion before making any final decisions on of materials, significant reliability enhancement
rebuild workscope. This could avoid a forced can be obtained through upgrading the design
outage and an extended rebuild workscope. If of the winding insulation and the winding sup-
a customer has several GE generators we may port system. With the new winding GE will
also perform a fleet study, addressing the design and supply the new stator slot support sys-
upgrade and reliability options applicable to all tem as well as the endwinding support.
of them. Depending upon the generator design, a new
wedging system may include pressure wedges
Rewinding for Higher Output and that are made of non-shrinkable non-abrasive
Efficiency material, top and side ripple springs. These
While nearly all of the generator components components will effectively secure winding in
may be upgraded during the service life, stator the slot, while allowing certain axial movement
rewind and field rewind are by far the most of the endwinding basket due to the normal
convenient and powerful means of achieving thermal growth or abnormal currents.
both a higher efficiency and a higher output. One goal of this paper is to detect a trend in the
Rewinds always present an opportunity for the stator rewinds, based on GE rewind experience.
Figure 4 represents the experience data for con- groups of the air- and hydrogen-cooled genera-
ventionally-cooled stator rewinds performed by tors, suggesting that hydrogen-cooled genera-
GE for the last decade, using Class F epoxy-glass tors sustain a longer time between rewinds
insulation systems. Major drivers for these (TBR). Though hydrogen gas indeed provides a
rewinds were output increase and reliability cleaner environment, this is partly due to the
increase. Other reasons included test failures, mode of operation. Most of these hydrogen-
operational incidents, system faults, and envi- cooled generators are base load steam turbine
ronmental causes. driven generators, whereas some of the air-
Though a variety of reasons forced these stators cooled generators were the gas turbine driven,
to be rewound, the histogram in Figure 5 clearly cycling generators.
shows the peaks at two distinct age groups with- The same main objectives—reliability and/or
in the total lot of data. Further breakdown by a uprates—were pursued by GE customers effect-
generator-cooling medium detects the sub- ing liquid-cooled stator rewinds. Figure 6 repre-
sents the frequency of liquid-cooled rewinds per- However, owners should not lose sight of other
formed by GE for its customers in the past considerations. Load level, type of duty, and
decade. An age histogram of the water-cooled number of stop-start cycles are the main factors
generators rewound by GE shown below indi- affecting the wear of the generator field. Other
cates that currently, the peak rewind frequency factors include prime mover type (gas or steam
occurs mostly in the generator age group from turbine), ambient air conditions (for air-cooled
20 to 30 years in service. generators), cooling and maintenance of a gen-
erator.
Many generators referenced in TIL-1098 and
recommended for inspection and rewind are It is common for older units to be operated at
still operating with the original winding in place. lower power factors to carry more reactive power.
GE recommends that inspection of these gener- Frequent load cycling common for the peaking
ators should be performed. GE publication units also may contribute to accelerated wear and
GER-3751A (Understanding, Diagnosing and distortion of the field winding, and, at times, lead
Repairing Leaks in Water-Cooled Generator Stator to a field current sensitive vibration – thermal sen-
Windings) provides details regarding recom- sitivity. (GER-3809 [Generator Rotor Thermal
mended maintenance, inspection and testing, Sensitivity: Theory and Experience] provides a
and test data. detailed description of this phenomena). A com-
plete replacement of the old field winding may be
Field Rewinds preferred as a retrofit option in such cases.
Experience has shown the generator field is a Reliability of the generator field is increased
component that requires maintenance. This is with a rewind. New modern insulating material
not surprising considering that it is operating will replace the original worn out insulation and
under very high centrifugal load and thermal address the latest service concerns. The new
cycling. Also, typical operating incidents have copper coils would usually have a higher cross
the greatest impact on the field (motoring, con- section, reducing the current density and heat-
tamination, etc.). Rebuild of the field normally ing. Conversion from indirect to direct cooling
focuses on re-insulation of the field winding. of the rotor may also be effected in order to per-
If not used for an emergency, the kit may be Pareto charts shown in Figure 8 and Figure 9 may
used later at the time of scheduled outage. illustrate the contribution of various stator and
field components to the overall number of the
Generator Service Issues and GE
generator stator and generator field service
Recommendations issues.
Not all generator service concerns may be solved
with rewinds. Careful attention must be paid to Generator Monitoring
the generator auxiliaries, exciter, collector and Monitoring generator condition and parame-
brushes, hydrogen seals, frame, end shields, ters on-line provides the opportunity to detect a
water-cooling system, and hydrogen system. trend in behavior of a monitoring parameter;
Time and wear of the generator components assess the rate of deterioration and possibly pre-
has a combined effect on the generator avail- dict the time to failure; and detect faults of the
ability. Based on statistics for recent months, the generator components. While an array of gener-
ator monitoring schemes and devices are used content. It consists of a flow meter, gas analyzer,
by the industry, the following three are data acquisition and control system and a system
employed most widely: Generator Flux Probe, piping modification package. Since on-line leak
Stator Leak Monitoring System, and Partial detection is important in avoiding catastrophic
Discharge Analysis: stator winding failure from wet insulation and in
Generator Flux Probe outage planning, the SLMS is designed to detect
In order to provide an effective early-detection developing water leaks in a water-cooled stator
system, GE developed the Flux Probe to detect winding and maintain the cooling water's oxy-
shorted turns that might exist in the field during gen content.
operation. The permanent Flux Probe permits As described in TIL-1098, GE has identified the
continuous on-line monitoring of the field. The potential for water leaks to develop in this class
pickup coil is mounted to a stator wedge; no of generators. When a leak develops, higher
rewedging is required. Electrical leads from the pressure hydrogen escapes into the water system
pickup probe are brought out through the end and can accumulate in the water storage tank on
windings to an electrical pressure connector the cooling water skid. As the hydrogen accu-
that is welded to the wrapper. This allows condi- mulates, it creates a "blanket" effect, keeping
tions in the field coils to be monitored while the atmospheric oxygen from entering the water
generator is operating, so problems can be dis- and leading to deoxygenated water and the
covered early enough to avoid major opera- problems described above.
tional issues—such as rotor vibration caused by Addition of an SLMS will require a modification
linear thermal sensitivity. to the Stator Water Cooling System (SWCS).
Stator Leak Monitoring System The SLMS module will be mounted to the SWCS
To help prevent catastrophic stator winding fail- hydrogen detraining tank and will connect to a
ure, GE developed the Stator Leak Monitoring gas analyzer and a flow meter which are added
System (SLMS). This system has two functions: to the existing piping. The system will induce
on line detection of water-cooled stator winding fresh filtered air into the cooling water, which
leaks and maintaining cooling water oxygen provides a measurable gas flow and maintains
water oxygen content. Measurement of the investigated during a maintenance outage test
hydrogen content and gas flow will provide an and inspection program. On-line PDA testing
accurate measurement of hydrogen leakage gives a relative assessment of the generator con-
through the stator winding. The level of hydro- dition that can augment more conventional tests
gen leakage is directly related to a leak in the and inspection methods in order to plan condi-
water cooled stator winding. Recent upgrades tion-based maintenance outages and to help
included the on-line oxygen monitoring and avoid forced outages. The PRPDA method de-
updated data acquisition system. tects discharges with sophisticated signal pro-
cessing, noise gating and pulse shaping, and dis-
Partial Discharge Analysis plays the activity as it occurs in relation to the
High frequency (40 KHz – 100 MHz) low voltage 50/60 Hz power sine wave. The resulting phase-
(micro volts) partial discharge activity exists in resolved patterns allow for discrimination
essentially all high voltage equipment. Phase between internal discharge activity, external dis-
Resolved Partial Discharge Analysis (PRPDA) is charge activity, and noise activity. The superior
a powerful tool to monitor this activity on-line signal discrimination of PRPDA simplifies meth-
and identify trends on specific machines and/or ods for coupling to the generator, while the
compare activity in identical machines that can enhanced signal presentation of PRPDA simpli-
be used for condition- based maintenance and fies using partial discharge for condition- based
forced outage avoidance. Recent developments maintenance and forced outage avoidance.
in measurement hardware, software and analysis
techniques show great potential for identifying Conclusion
the specific sites of partial discharge activity with- A recent increase in the number of forced out-
in generators and quantifying the partial dis- ages can be attributed to the aging of GE’s gen-
charges at each site in order to discriminate erator fleet. With many of these generator units
between normal and destructive activity. 30 years or older, early diagnosis and correction
There are several conditions which can occur of a problem is important for reliable operation.
within a generator that can generate PD activity The best approach in preventing forced outages
that is of interest and relates to the condition of is a proactive one.
the generator: Based on the expertise and knowledge base
■ Stator bar vibration accumulated from our worldwide fleet of gener-
■ End winding contamination ators, GE has the ability to help customers deter-
mine the optimum reliability solution for their
■ Damage to the end winding voltage
specific units—with a comprehensive range of
suppresser system
offerings that provide everything from mainte-
■ Connection ring vibration nance and monitoring through upgrades and
■ Broken conductors rewinds.
■ Insulation delamination/damage Though there is no hard data pointing to a date
■ Slot discharge when a generator must be rewound, GE recom-
mends to follow relevant publications such as
■ Collector brush sparking
Technical Information Letters and reference
These are some typical conditions that would be manuals that correspond to a particular unit.
Appendix
A. 1) Generator Source Book Articles
Many of the following Generator Source Book articles may be accessed online at www.gepower.com by
selecting the Online Tools page and choosing Outage Optimizer—or by contacting your GE sales rep-
resentative.
A. 2) Sample Generator Source Book optimized to lower its resistance and net operat-
Article ing temperatures for the same output level. By
replacing the old coils with new ones, the design
CODE: GFFRCU64
of the winding is improved. Class "F" insulation
DESCRIPTION: FULL FIELD REWIND WITH systems are used to improve the insulation sys-
COPPER tem's temperature capability.
INTRODUCTION: BENEFITS:
A full field rewind with a new copper winding ■ New Class "F" insulation systems
replaces the old, worn ground and turn insula- improve temperature capability
tion with the latest systems and provides for a ■ Existing shorted turns can be
new field winding. Since these new insulation eliminated
systems are typically thinner than what they are
■ Possible uprate potential
replacing, additional space is made available
and optimized by designing the new field coils ■ Field operating temperature can be
with a larger cross-section. This provides an reduced
uprate potential for the generator. Even if the ■ Reduced down-time, increased
customer is not interested in an uprate at this reliability
time, a full field rewind with copper will typical- ■ Increased life expectancy of the
ly reduce the operating temperatures of the insulation system
field, which will improve machine reliability and
REFERENCES:
the life expectancy of the machine.
GER-3707, Generator Upgrades and Rewinds
APPLICABLE UNITS:
SCOPE OF SUPPLY:
All generators.
■ New field coils (100%)
TECHNICAL DESCRIPTION:
■ Slot armors (100%) plus two
A full field rewind with copper allows for the full contingency spares for coil #1 above
implementation of the latest ground and turn
■ Turn insulation - slot and end winding
insulation systems, along with the latest field
(105%)
winding design technology. Technically, this
rewind option provides the greatest potential for ■ New distance blocks when existing
improved generator output when the field is blocks are asbestos or unit is a medium
limiting. A stator rewind, cooler upgrade or generator (100%)
excitation upgrade may be required in addition ■ Pole-to-pole connectors (100%)
to the field rewind if their capability is also lim- ■ Coil-to-coil connectors (100%)
iting.
■ Fan lock plates for axial flow fans
By rewinding the field with new copper, the reli- (100%)
ability of the field is greatly increased. New hard
■ Main terminal nuts (50%)
coils are installed to reduce coil distortion dur-
ing operation, while Class "F" insulating materi- ■ One retaining ring installation kit (see
als are installed to improve the temperature GFRRIK63)
capability of the winding design. When the coils ■ Temporary wood (international orders
are replaced, the field winding design can be only)
■ Temporary wood drawing (domestic ■ Rewind field with new coils and new
orders only) insulation
■ Rewind accessories and miscellaneous ■ Install retaining rings
materials needed to perform rewind ■ Insert field into the stator
(100%)
SITE INFORMATION REQUIRED:
NOTES:
■ Turbine, generator and field serial
A field high-speed balance is strongly recom- numbers
mended (SEE GFHSBN62).
■ Notification of any modifications
SCOPE OF WORK: previously performed on the field
This Scope Of Work lists the required steps to forging or winding
perform the subject installation only. It assumes OPTIONS:
that generator disassembly is for no other pur-
■ Retaining Ring Replacement (See
pose than the installation. Typically, conver-
GFRRRP67)
sions, modifications and uprates are scheduled
by a customer to coincide with other turbine- ■ Field High-Speed Balance (See
generator maintenance activity. GFHSBN62)
Foreign Material/Contamination
Blocked Ventilation
Tape Migration
Core Tightness
Bar Sparking
Broken Tiles
Cleanliness
Worn Parts
Movement
Corrosion
Burning
Cracks
Stator All Components X X X X X X
Bars X X X X X X
EW Support System X X X
Slot Support System X X X
Conn. Rgs & Lower Lds. X X X X X
High Voltage Bushings X X X X
O – Optional test
X* – Pertains only to water-cooled units
R – These tests are performed while the unit is running
List of Figures
Figure 1. GE generator fleet demographics
Figure 2a. Turbine-generator reliability trend
Figure 2b. Turbine-generator reliability improvement trend
Figure 3. Water-cooled winding failures (TIL-1098)
Figure 4. Air-cooled stator rewind orders
Figure 5. Hydrogen-cooled stator rewind orders
Figure 6. Age of rewound liquid-cooled generators
Figure 7. Medium generator rewinds
Figure 8. Stator components service issues
Figure 9. Field components service issues
List of Tables
Table B-1. Recommended generator inspections
Table B-2. Recommended generator standard tests