Schedule of Point BMS

Project : Building Automation System

Panel

Location

Description

Control Panel AHU.PR-Z.7X-1


LINE 7 EXT
- Start/stop
- Status
- Trip alarm
- Duct Humidity Sensor
- Duct Temperature Sensor
- Air Flow Meas.Transmitter
- Command Inverter
- Feedback Inverter
- C/C-2 way valve
- Dirty Filter Alarm c/w Display
- Duct Smoke Sensor
- Panel Auto/Manual Status
- SPV L7
- Room Humidity Monitor
- PJL L7
- Room Temperature Monitor
Kemas L7 Ext - Room Diff.Press. Monitor
AHU.PR-Z.7X-2
(GREY)
- Start/stop
- Status
- Trip alarm
- Duct Humidity Sensor
- Duct Temperature Sensor
- Air Flow Meas.Transmitter
- Command Inverter
- Feedback Inverter
- C/C-2 way valve
- Panel Auto/Manual Status
Gowning
- Dirty Filter Alarm c/w Display
Buffer
- Duct Smoke Sensor
Corridor Out 7X - Room Humidity Monitor
Corridor In 7X - Room Temperature Monitor
- Tangga Grey - Room Diff.Press. Monitor
RF.PR-Z.7X-2
- Status
- Trip alarm
AHU.PR-Z.7X-3
(GREY)
- Start/stop
- Status
- Trip alarm
- Duct Humidity Sensor
- Duct Temperature Sensor
- Air Flow Meas.Transmitter
- Command Inverter
- Feedback Inverter
- C/C-2 way valve
- Dirty Filter Alarm c/w Display
- Duct Smoke Sensor
- Panel Auto/Manual Status
- Room Humidity Monitor
Filling 1-5
- Room Temperature Monitor
R. Suppo
- Room Diff.Press. Monitor
RF.PR-Z.7X-3
- Status
- Trip alarm

Digital
Input
Output

Analog
Input
Output

1
1
1
1
1
1
1
1
1
1
1
2
1
1
1

1
1
1
1
1
1
1
1
1
2
2
1
4
4
4
1
1

1
1
1
1
1
1
1
1
1
2
1
2
6
6
6
1
1

Schedule of Point BMS


Project : Building Automation System

Panel

Location

Description

AHU.PR-Z.7X-4
(GREY)
- Start/stop
- Status
- Trip alarm
- Duct Humidity Sensor
- Duct Temperature Sensor
- Air Flow Meas.Transmitter
- Command Inverter
- Feedback Inverter
- C/C-2 way valve
- Dirty Filter Alarm c/w Display
- Duct Smoke Sensor
- Panel Auto/Manual Status
- Room Humidity Monitor
Mixing 5,6,7,8,9 - Room Temperature Monitor
Staging RM
- Room Diff.Press. Monitor
RF.PR-Z.7X-4
- Status
- Trip alarm
AHU.PR-Z.7X-5
(GREY)
- Start/stop
- Status
- Trip alarm
- Duct Humidity Sensor
- Duct Temperature Sensor
- Air Flow Meas.Transmitter
- Command Inverter
- Feedback Inverter
- C/C-2 way valve
- Panel Auto/Manual Status
IPC
- Dirty Filter Alarm c/w Display
Storage
- Duct Smoke Sensor
Mixing 1,2,3,4 - Room Humidity Monitor
Cuci
- Room Temperature Monitor
WIP
- Room Diff.Press. Monitor
RF.PR-Z.7X-5
- Status
- Trip alarm

Digital
Input
Output
1
1
1

1
1
1
1
1
1
2
1
2
6
6
6
1
1

1
1
1
1
1
1
1
1
1
2
2
1
8
8
8
1
1

Alarm indicator - 3 indicator lamps


- buzzer
TOTAL POINT

Analog
Input
Output

3
1
33

104

10

Schedule of Point BMS


Project : Building Automation System

Panel

Location

Description

Control Panel AHU.PR-WG.1


WG
(GREY)
- Start/stop
- Status
- Trip alarm
- Duct Humidity Sensor
- Duct Temperature Sensor
- Air Flow Meas.Transmitter
- Command Inverter
- Feedback Inverter
- C/C-2 way valve
- Dirty Filter Alarm c/w Display
- Duct Smoke Sensor
- Panel Auto/Manual Status
Gowning
- Room Humidity Monitor
Buffer
- Room Temperature Monitor
Gd. Timbang
- Room Diff.Press. Monitor
RF.PR-WG.1
- Status
- Trip alarm
AHU.PR-WG.2
(GREY)
- Start/stop
- Status
- Trip alarm
- Duct Humidity Sensor
- Duct Temperature Sensor
- Air Flow Meas.Transmitter
- Command Inverter
- Feedback Inverter
- C/C-2 way valve
- Dirty Filter Alarm c/w Display
- Duct Smoke Sensor
- Panel Auto/Manual Status
Washing Timb. - Room Humidity Monitor
Tool Storage
- Room Temperature Monitor
Weighing 24-27 - Room Diff.Press. Monitor
RF.PR-WG.2
- Status
- Trip alarm
AHU.PR-WG.3
(GREY)
- Start/stop
- Status
- Trip alarm
- Duct Humidity Sensor
- Duct Temperature Sensor
- Air Flow Meas.Transmitter
- Command Inverter
- Feedback Inverter
- C/C-2 way valve
- Dirty Filter Alarm c/w Display
- Duct Smoke Sensor
- Panel Auto/Manual Status
- Room Humidity Monitor
Ctrl RH R.1,2,3 - Room Temperature Monitor
Corridor Ctrl RH - Room Diff.Press. Monitor
RF.PR-WG.3
- Status
- Trip alarm

Digital
Input
Output

Analog
Input
Output

1
1
1
1
1
1
1
1
1
2
1
2
3
3
3
1
1

1
1
1
1
1
1
1
1
1
2
1
2
6
6
6
1
1

1
1
1
1
1
1
1
1
1
2
1
2
4
4
4
1
1

Schedule of Point BMS


Project : Building Automation System

Panel

Location

Description

AHU.PR-WG.4
(BLACK)
- Start/stop
- Status
- Trip alarm
- Duct Humidity Sensor
- Duct Temperature Sensor
- Air Flow Meas.Transmitter
- Command Inverter
- Feedback Inverter
- C/C-2 way valve
- Dirty Filter Alarm c/w Display
- Duct Smoke Sensor
- Panel Auto/Manual Status
- Room Humidity Monitor
- Room Temperature Monitor
Prep. 24-29
- Room Diff.Press. Monitor
TOTAL POINT

Digital
Input
Output

Analog
Input
Output

1
1
1
1
1
1
1
1
1
1
1
2
5
5
5
26

77

To

Date
Reference
Page

:
:
:

29 May 2012
SIQA111112AR3
2 of 2

Attention
Project
No
Model
A BMS SYSTEM
1 007308120
2 007301012
3 007302011
4 007302450
5 007302850
6 NYS3D12103P
7 ABL1REM24062
8 WIRING PANEL
B
9
10
11
12
13
14
15
16
17
18
19
20
21
22
C
23
24
25
26
27
28
29
30
31
32

Description
Electronic + Terminal Part TAC Xenta 511-B (Web server TCP/IP controller)
Electronic + Terminal Part TAC Xenta 401 V3 (Programmable controller)
Electronic + Terminal Part TAC Xenta 411 (Digital I/O module)
Electronic + Terminal Part TAC Xenta 421A (Digital I/O module)
Electronic + Terminal Part TAC Xenta 451A (Analog I/O module)
Sarel IP66 Enclosure (size: 1200 x 1000 x 300mm) - 4 set for DDC, 2 set for HMI Gateway
Telemecanique Power Supply 24 Vdc, 150 Watt
Enclosure wiring, accessories & installation

Unit price
###
###
###
###
###
###
###
###

PERIPHERAL
EPP101
TAC Differential Air Pressure Transmitters bidirectional (0 - 100 Pa, including calibration)
###
HD2XMSX-T1
TAC Veris Duct Humidity Transmitter (including calibration)
###
TDDAM
TAC Veris Duct Temperature Transmitter (including calibration)
###
004700360
TAC Differential Air Pressure Transmitters c/w Display (0 - 1000 Pa, including calibration)
###
MFS / MF-FD
Micatrone or Eq. Air Flow Transmitter c/w 2 sticks of pitot tubes
###
MFS / MF-FD
Micatrone or Eq. Air Flow Transmitter c/w 3 sticks of pitot tubes
###
RXZE
Telemecanique Relay + Socket 24Vac
###
RXZE
Telemecanique Relay + Socket 220Vac
###
XVM Series
Telemecanique 3 Color Beacon + Buzzer
###
OF + SD
Merlin Gerin / Telemecanique Auxiliary Contact
###
SL2000 or Eq.
Optical Smoke Detector for Duct
###
HMISTU655
Touch Panel Screen 3,5" Color c/w Stainless Steel Enclosure
###
LINKSYS
Ethernet Gateway for Touch Panel Screen up to 24 Ports, Auto-sensing, Stand-alone
###
LINKSYS
Ethernet Gateway for Touch Panel Screen up to 16 Ports, Auto-sensing, Stand-alone
###
ENGINEERING, TEST & COMM
ANALOG POINT
NYMHY 2x0.75mm, Analog Point Installation c/w Conduit & Accessories
###
RELAY 220 IN PTS NYMHY 2x0.75mm, Relay Point Installation c/w Conduit & Accessories
###
DIGITAL IN PTS
ITC 2x0.6mm, Digital Point Installation c/w Conduit & Accessories
###
DIGITAL OUT PTS NYM 2x0.75mm, Digital Output Point Installation c/w Conduit & Accessories
###
COMM POINT
CAT5e, Communication Point Installation c/w Conduit & Accessories
###
POWER POINT
NYM 2x1.5mm, Power Cable for HMI, Smoke Dect, and DDC Panel c/w Conduit & Accessories###
SENSOR INSTALL Sensor & field devices installation & termination
###
CABLE TRAY
Cable tray works including accessories for cabling arrangement (per Line)
###
ENGINEERING
Drawing, Programming, Engineering, & Testing Commisioning
###
VALIDATION
Design & Qualification Documents protocol, comply with FDA 21 Part 11
###