Anda di halaman 1dari 3

BOSCH PAVIRO - PVA-4CR12 System Controller

Architects and Engineers Specifications


The system controller shall be an EN54-16 compliant and certified device in a 2 RU,
19-cabinet. The TCP/IP capable network device shall contain all controlling and
monitoring functions of a voice evacuation system.
The controller shall manage the supervision of its own operation and that of the
connected devices. It shall control and activate the connected amplifiers and spare
amplifier and shall replace an amplifier routing and channel that has reported a fault.
A failsafe mode shall ensure that emergency calls are passed through to the
amplifiers even if the controller itself fails.
The controller shall support single line switching or redundant group A/B switching.
Network connectivity status and fault conditions shall be displayed via LEDs on the
front panel.
>1000 fault, warning and event conditions shall be logged internally and shall be
reported with the possibility to look real-time into the logging and save the log with
logging tools. Four 100V audio inputs shall be routed to 12 speaker line outputs.
Each block of 6 loudspeaker zones shall allow separate two-channel operation to
ensure continuous business music. The controller shall operate as a 4-4-2-2 matrix
(4 channel matrix controller, 4 channel amplifier input, separte 2 channels per 6
zones on the output)
In case of too much amplifier power, it shall be possible to also transfer overrun
amplifier power to additional system routers. The controller shall provide an internal
32x 4 Audio matrix with full DSP functionally on each of the 4 outputs.
It shall be possible to adjust channel delays up to 10s per channel.
A single system controller shall be able to manage up to 20 routers, 16 call stations
and up to 468 loudspeaker circuits.
It shall administrate up to 80 local audio inputs.
A built in message manager shall be able to store up to 100 emergency- or businesscalls, with a total storage time up to 85 minutes.
It shall be possible to send two different messages simultaneously to individual
destinations.
In combination with VAS4, license free spoken word evac sound files shall be
provided in 7 languages.
A separate included tool shall provide on the fly replacing non-evac messages at any
time without system interruption or system restart; So called hot swappable
messages.
Loudspeaker supervison shall be fully controlled by the controller and executed from
the router. The user shall be able to choose between impedance measurement,
simple EOL boards with pilot tone supervision (requires return wires) or via advanced
addressable EOL supervision boards, which does require a ground connection but no
additional return wires.
Zones outputs shall be able to handle a load from 2-500 Watt.
Max 500 Watt per 6 zones shall be provided, if required.
The controller shall be able to handle up to 1000 Watt load.

The controller shall have the following specifications:


4-4-2-2 Matrix mixing and switching
Priority mixing with ducking, attack and release
3 band parametric PEQ in the inputs
5 band parametric PEQ in the outputs
up to 10s delay per output
Gain adjustment in the in- and output
Compressor on the inputs
Limiters on the inputs
Cross point matrix level adjustment with ducking level, fade in and fade out
time
2 mic/line inputs (System s/n >= 106dB) 2x Euro Style - 2x cinch
4 separate call station RJ45 input busses, each can be daisy chained up to 4
call stations
4 output channels to amplifiers via Euro Style connectors and RJ45
12 input contacts; 6x voltage free (isolated) + 6x Supervised, to ensure
compliancy to all different standards (like VDE0833 & NEN2575)
12 output contacts; 1x Relay + 12 Open Collector
6 High power output contacts (1A)
8 Analog input contacts with 256 steps resolution
Four input channels LSP level + 2 spare channel inputs (100V, 70V)
Real time clock with summertime and wintertime switching
DCF77 receiver sync input
Event schedular
12 zone outputs (100/70V)
12 zone status LED (active green, fault yellow, alarm red)
6 system status LED (general fault, system fault, alarm mode, power
indicator, standby mode, network connection status)
Internal router pcb: 1x 2 channel 12zone or 2x 2ch x 6zone (2 separate
channels can be provided on each 6 zones)
Controller shall be configurable as 6 A/B zones or 12 single zones
Internal sounder
System access shall have password protection
CAN bus between system components
Based on a fully digital platform
Network prepared (remote system racks)
24V DC Input

Audio:

Safety:
Software:

Audio input specifications:


Audio output specifications:
Frequency response:
Signal-to-noise ratio (A-weighted):
THD+N:
Crosstalk:
Samplerate:
DSP Processing:
Ethernet:
CAN:
Networking:
Control Port:

Power supply:
Operating temperature:
Product dimensions (W x H x D):
Colour:
Weight:

16 (internal) audio Channels


4 Aux input channels
4 Callstation input channels
4 audio output channels
System s/n >= 104dB
Internal supervision, system monitoring,
watchdog, fault output
Basic mode (Wizard) & expert Mode
(IRISNet; Intelligent Remote & Integrated
Supervision Net)
Integration of controller, amplifiers, call
stations and peripheral control
Configuration, control and supervision for
complete audio systems
Message swapper
Programmable user control,
GUI and access levels
+6dBu/ 1,55V
+6dBu/ 1,55V
20Hz to 20kHz (-0,5dB)
analog in to analog out: >106 dB typical
0.01%
>100dB @ 1 kHz
48 kHz; 24bit
3 DSPs (480 MIPS) internal
10/100 MB, RJ-45 (PC control)
10 to 500 kbit/s, 2x RJ-45
(remote and control)
Module slot for optional Network / OMNEO
interface
1 slave clock output (max. 1 A)
1 time sync input (DCF-77 standard)
12 control inputs (logic control)
12 control outputs
6 analog inputs 0-10V
+24 V DC (wide range tolerance:
18 V to 58 V DC)
-5 C to +45 C
19, 2 HU, 483 x 88 x 376 mm
Black/Silver front rear black
3.5 kg

Anda mungkin juga menyukai