off completely.
All exposed chilled water piping would be inspected for rust to ensure no rust on
All the chilled water piping would be made clean and dry to ensure there is no
moisture and other foreign material before the commencement of the new
insulation.
All insulation material would be cut to diameter of the various sizes as
installed/existing.
Pipe insulation would be kept at dry & clean place.
If pipe insulation is not dirty then can be installed, if pipe insulation is dirty,
clean the internal and external surface to reasonable free from other foreign
material.
Before install insulation, the pipes should be tested and painted completely.
SLIP INSULATION
Jointing between pipe insulation should be coated with adhesive, allow the
adhesive to set for 3 to 5minutes, before pressing the joints together.
SLIT INSULATION
Slit insulation tube lengthwise on one side, for pipe up to 150 mm. dia. and snap
SHEET INSULATION
Use for large pipe above 150 mm. diameter, fittings, valves & equipment.
In case of the thickness of insulation over 32 mm., the installation must use 2
layers of insulation
Joint between insulation sheets should be coated lengthwise slit surface and butt
joints with adhesive, allow the adhesive to set for 3 to 5 minutes, before pressing
the joints together both 1st layers but the lengthwise slit surface and butt joints of
MATERIALS
o Armaflex sheet, closed cell expanded foam insulation with a calculated
thickness to retard heat gain and control condensation drip from chilled
o
o
o
o
o
water systems or
Polystyrene.
Aerotape.
Adhesives Gum.
Vapour barrier.
Abro sealants.
PERSONNEL