maximum (charging current is zero) and minimum energy stored is when the
voltage is zero.
The energy gets stored in inductor is proportional to the current in the
inductor and maximum energy stored is when the instantaneous current is
maximum (voltage is zero) and minimum energy stored is when the current
is zero.
The electrostatic energy stored in capacitor is transformed to the magnetic
energy in the inductor and vice-versa. No energy is consumed for creation of
RkVAh. No coal is burnt to create RkVAh energy as in the case of kWh
where the coal is consumed.
Depending on the amount of capacitor and the inductor the power factor will
be leading if capacitor is more (the currents lead the voltage) or lagging if
inductor is more (the currents lag the voltage).
Inductance and capacitance exists in each and every part of power system.
Unity power factor maintained at the terminal will not ensure unity power
factor at the junction pillar or at substation.
Transformer also generates inductive currents to magnetise its winding.
Equivalent circuit of Transmission line is also a network of inductance and
capacitance.
Power Factor incentive/penalty applied to consumers is based on the meter
reading.
The present meter used by most of the utilities (including BEST RINFRA,
TATA & MSEDCL) measures RkVAh inductive(lagging) only to calculate
power factor penalty. RkVAh capacitive (leading) is not
measured/considered (not reflected in the bill of consumer).
So to maintain the power factor unity in bill and avail power factor incentive
a leading power factor should be maintained. Level of leading power factor
could be to which ever level 0-100% (90-0).Connection of more capacitor
than required is more harmful to the transmission & distribution Network
than inductive current flow in the circuit. Extremely high voltage could be
generated by series resonance of capacitor with the line (network)
inductance completely damaging all electric Equipment connected to the
line.
The Power factor of 0.85 lagging is the cut off factor denoted in Electricity
Rule 1956 section 22 (k).
Power Factor of Apparatus- The apparatus shall have a power factor of
not less than 85 per cent at normal working load.
Intending consumers are advised to consult the Engineer of the licensee
before ordering their motors, as in some cases it may be practicable to relax
the starting current limit dependent on the location and conditions of
working.
It is the responsibility of the electric company to maintain higher power
factor as auto power factor correction panel is included in capital
expenditure.
There is a provision in section 62(3) of Electricity Act 2003 to differentiate
consumer based on the power factor. Electricity Act 2003 also directs the
tariff to reflect the cost of supply. The distribution loss is proportional to the
square of current flowing in the network. It is ideal not to have reactive
current flowing in the network and the power factor is corrected as close to
the place where the reactive currents are generated (preferably at the low
tension substation).
The loss (T&D) should be never more than 10% ( 5% max transmission loss
5% maximum for distribution loss)of the power supplied. And increase in
distribution loss due to not maintaining power factor is further less. So the
RkVAh charge or the penalty due to power factor should not increase more
than 8% of the cost of Electricity.
The balancing the three phase current / reducing the reactive loading or
injecting reactive current could be well maintained by the licensee as
demanded by the Power system for stability. Insertion of reactive
components to control harmonics is also a practice followed in the power
system. Unity Power factor cannot be maintained in any power system by
any utility. The bulk consumers, high end consumers and the licensee have
the knowledge and capacity to maintain power factor near unity and the
harmonics as per the IEEE STD 519-1992 stated in clause 12.1 &12.2 of the
MERC Supply Code Regulations 2006.
12. Power factor / Harmonics
12.1 It shall be obligatory for the consumer to maintain the average power
factor of his load at levels prescribed by the Indian Electricity Rules, 1956
with such variations, if any, adopted by the Distribution Licensee in
accordance with Rule 27 of the Indian ElectricityRules, 1956 and in
accordance with the relevant orders of the Commission.
Provided that it shall be obligatory for the HT consumer and the LT
consumer (Industrial and Commercial only) to control harmonics of his load
at levels prescribed by the IEEE STD 519-1992, and in accordance with the
relevant Orders of the Commission.
12.2 The Distribution Licensee may require the consumer, within a
reasonable time period, which shall not be less than three months, to take
such effective measures so as to raise the average power factor or control