General
Specications

I/O Module Nest


I/O Module
(for RIO)

GS 33Y06K40-31E

GENERAL

This GS covers the specications of I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and
CENTUM CS 1000 systems.

STANDARD SPECIFICATIONS
I/O Module Nest
Power Supply: 5.0 V DC supplied from Model AND50, ANS50, AND20, ANS20 Node Interface Unit or Model PFCS/
PFCD Field Control Station
Installation:
Node Interface Unit, I/O Expansion Rack, or Model PFCS/PFCD Field Control Station
External Dimensions: 125 (W) x 130 (D) x 248 (H); AMN51: 137.5 (W) x 225 (D) x 254 (H); AMN52: 233.3 (W) x 225
(D) x 254 (H)
Weight: Max. 2.5 kg (AMN52. This weight does not include I/O Modules.)

Models
AMN11
AMN12
AMN21
AMN31
AMN32
AMN33
AMN34
AMN51
AMN52

Names

CS 1000

Nest for Analog I/O Modules


High-Speed Nest for Analog I/O Modules
Nest for Relay I/O Modules
Nest for Terminal I/O Modules
Nest for Connector I/O Modules
Nest for Communication Modules
Nest for Multipoint Control Analog I/O Modules
Nest for Communication Cards
Nest for PROFIBUS Communication Module

X
X
X
X
X
X
X
X (*5)

CS 3000
AFS10S,AFS10D
AFS20S,AFS20D
AFG10S,AFG10D
AFG20S,AFG20D
X
X
X
X
X
X
X

PFCS
PFCD

Installation Restrictions
(See next page)

X
(*1)
X
X
X
X
X
X
X (*5)

(*2)

(*3)
(*4)

X:
Installable
*1, *2, *3, *4: See next page.
*5:
Installable in R2.10 or later.

Yokogawa Electric Corporation


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802

GS 33Y06K40-31E
Copyright Jan. 2001
12th Edition Oct. 22, 2007

<<Contents>> <<Index>>

Installation Restrictions for I/O Module Nest


Model AMN12 High-speed Nest for Analog I/O Modules (*1)
-Always install in Nest No. 1 (See Figures 1, 2 and 5).
-Do not install any I/O module nests in Nests No. 2 through No. 4 (See Figures 1, 2 and 5).
-When using non-AMN12 I/O Module Nest with AMN12, always install it in Nest No. 5 (See Figures 2 and 5).
Model AMM22T, AMM22TJ (*2)
-Do not install non-AMM22T, AMM22TJ I/O module below AMM22T, AMM22TJ (See Figures 3, 4 and 8) because
AMM22T, AMM22TJ is a module for thermocouple entry. If there were a heat source below AMM22T, AMM22TJ, a
reference junction compensation error occur.
-If there is another module (heat source) below AMM22T, AMM22TJ when using 19 Rack Mountable Type, a thermal
shield must be inserted between AMM22T, AMM22TJ and the heat source (See Figures 6 and 7).
Model AMN51 Nest for Communication Cards (*3)
-Only one nest is installable in PFCS/PFCD. Its position is xed as Nest No. 2.
Cabinet Mountable Type
Figure 2
(Permitted)

Figure 1
(Permitted)

Figure 3
Figure 4
(Permitted) (Not Permitted)

Model
AMN12

Model
AMN12

Nest No.1

Empty

Empty

Nest No.2

Empty

Empty

Nest No.3

Empty

Empty

Nest No.4

Non-AMM22T,
: AMM22TJ
I/O module

Module nest
for non-AMN12

Nest No.5

: All I/O modules

Model AMM22T,
AMM22TJ

F01E.ai

ANS50/AND50 connected to
AFS10S/AFS10D 19-inch Rack Mountable Type FCU
Figure 5
(Permitted)
Model
AMN12

19-inch Rack Mountable Type ANS50, AND50, PFCS and PFCD


Figure 6
(Permitted)

Figure 7
(Not permitted)

Figure 8
(Not permitted)

Nests No.1 and 2


from the left

Heat Source

Nests No.3, 4 and 5


from the left
Empty
Module nest for non-AMN12
Thermal Shield

:
Heat Source

Model AMM22T,
AMM22TJ

Non-AMM22T,
: AMM22TJ
I/O module

: All I/O modules


Note: Figure 7 will be applied to only PFC.
F02E.EPS

AMN52 Nest for PROFIBUS Communication Module


-Only one nest is installable in PFC. Its position is xed as Nests No. 1 and 2. AMN52 cannot be combined with
AMN51.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Apr. 1, 2006-00

<<Contents>> <<Index>>

l I/O Modules to be Installed in Control Stations

Models

I/O Module Names

AAM10
AAM11
AAM11B
AAM21

Analog I/O Modules


Current/Voltage Input Module (Simplied Type)
Current/Voltage Input Module
Current/Voltage Input Module (supports BRAIN)
mV, Thermocouple, and RTD Input Module
mV, Thermocouple, and RTD Input Module (supports IEC584-1995,
AAM21J
IEC751-1995)
APM11
Pulse Input Module
AAM50
Current Output Module
AAM51
Current/Voltage Output Module
AMC80
Multipoint Control Analog I/O Module
Relay I/O Modules
ADM15R Relay Input Module
ADM55R Relay Output Module
Multiplexer Modules (16 Points, Terminal Type)
AMM12T Voltage Input Multiplexer Module
AMM22M mV Input Multiplexer Module
AMM22T Thermocouple Input Multiplexer Module
AMM22TJ Thermocouple Input Multiplexer Module (supports IEC584-1995)
AMM32T RTD Input Multiplexer Module
AMM32TJ RTD Input Multiplexer Module (supports IEC751-1995)
AMM42T 2-Wire Transmitter Input Multiplexer Module
AMM52T Output Multiplexer Module
Multiplexer Modules (Connector Type)
AMM12C Voltage Input Multiplexer Module
AMM22C mV Input Multiplexer Module
mV Input Multiplexer Module with Thermocouple Interface (15 Points,
AMM25C
RJC Input port added)
AMM32C RTD Input Multiplexer Module (16 Points)
AMM32CJ RTD Input Multiplexer Module (16 Points, conforms to IEC751-1995)
Digital I/O Modules
ADM11T
Contact Input Module (16 Points, Terminal Type)
ADM12T Contact Input Module (32 Points, Terminal Type)
ADM51T Contact Output Module (16 Points, Terminal Type)
ADM52T Contact Output Module (32 Points, Terminal Type)
ADM11C Contact Input Module (16 Points, Connector Type)
ADM12C Contact Input Module (32 Points, Connector Type)
ADM51C Contact Output Module (16 Points, Connector Type)
ADM52C Contact Output Module (32 Points, Connector Type)
Communication Modules
ACM11
RS-232C Communication Module
ACM12
RS-422/RS-485 Communication Module
ACM21
RS-232C General-purpose Communication Card
ACM22
RS-422/RS-485 General-purpose Communication Card
ACM71
Ethernet Communication Module (for PFCS/PFCD)
ACF11
Fieldbus Communication Module
ACP71
PROFIBUS Communication Module
X:
- :

I/O Module(s) to be Installed


CENTUM CS 1000
CENTUM CS 3000
AFS10S,AFS10D
PFCS-S, PFCS-E, PFCS-H, AFS20S,AFS20D
PFCD-S PFCD-E PFCD-H AFG10S,AFG10D
AFG20S,AFG20D
X
X
X
X

X
X
X
X

X
X
X
X

X
X
X
X

X
X
X
X

X
X
X
X

X
X
X
X

X
X
X
X

X
X

X
X

X
X

X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
-

X
X
X
X
X
X
X

X
X
X
X
X
X
X

X
X
X
-

Installable
Not installed

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Feb. 1, 2004-00

<<Contents>> <<Index>>

Types of I/O Modules and Max. No. of Modules to be Installed into I/O Module Nests
Models

I/O Module Names

Max. No. of Modules to be Installed in I/O Module Nests


AMN11
AMN12

Analog I/O Modules


Current/Voltage Input Module (Simplied
AAM10
Type)
AAM11
Current/Voltage Input Module
Current/Voltage Input Module (supports
AAM11B
BRAIN)
Up to
mV, Thermocouple, and RTD Input
16
AAM21
Module
modules
mV, Thermocouple, and RTD Input Mod- can be
installed
ule (supports IEC584-1995, IEC751AAM21J
1995)
APM11
Pulse Input Module
AAM50
Current Output Module
AAM51
Current/Voltage Output Module
Multipoint Control Analog I/O Module
AMC80
(*5)
Relay I/O Modules
ADM15R Relay Input Module
ADM55R Relay Output Module
Multiplexer Modules (16 Points, Terminal Type) (*1)
AMM12T Voltage Input Multiplexer Module
AMM22M mV Input Multiplexer Module
AMM22T Thermocouple Input Multiplexer Module
Thermocouple Input Multiplexer Module
AMM22TJ
(supports IEC584-1995)
AMM32T RTD Input Multiplexer Module
RTD Input Multiplexer Module (supports
AMM32TJ
IEC751-1995)
2-Wire Transmitter Input Multiplexer
AMM42T
Module
AMM52T Output Multiplexer Module
Multiplexer Modules (Connector Type) (*1)
AMM12C Voltage Input Multiplexer Module
AMM22C mV Input Multiplexer Module (16 Points)
mV Input Multiplexer Module with
AMM25C Thermocouple Interface (15 Points, RJC
Input port added)
RTD Input Multiplexer Module (16
AMM32C
Points)
RTD Input Multiplexer Module (16
AMM32CJ
Points, conforms to IEC751-1995)

AMN21 AMN31

AMN32

AMN33 AMN34 AMN51 AMN52

*1:
*4:
*5:
*7:

*8:

Up to 2
(*4)

Only 1

Up to 2
(*7)

Up to 2

Up to 4
(Up to 2
modules
can be
installed in
AFS0
or
AFG0)
(*8)

The Multiplexer Module and Digital I/O Module cannot be installed in the same I/O Module Nest.
Installing two modules in one nest allows one to use a pair of redundant modules or two sets of module.
These modules cannot be installed on CENTUM CS 1000 Release 1.
The module can be installed in Slots 1 and 3 only. Other IOMs cannot be installed in Slot 2 or 4. The module can be combined with AMM12C, AMM22C, AMM32C, AMM32CJ and AMM25C in the same I/O module nest, and AMM12T, AMM22M,
AMM22T and AMM22TJ can be installed in Slots 1 and 3. When using AFS10S/AFS10D/AFS20S/AFS20D/AFG10S/
AFG10D/AFG20S/AFG20D, Terminal Type Multiplexer Modules cannot be installed in AMN32.
AMM12C, AMM22C, AMM25C, AMM32C, and AMM32CJ can be combined with AMM12T, AMM22M, AMM22T and
AMM22TJ in the PFCS/PFCD Field Control Station (Use AMN32 Nest). In this case, one Terminal Type Multiplexer Module
and up to two Connector Type Multiplexer Modules can be installed. When combining these modules, the Terminal Type
is installed in Slot 1 or 3 and no module can be installed in Slot 2 or 4 (right slot of Slot 1 or 3). In the AFS10S/AFS10D/
AFS20S/AFS20D/AFG10S/AFG10D/AFG20S/AFG20D, up to two modules can be installed in Slot 1 and 2.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

<<Contents>> <<Index>>

Models

I/O Module Names

Digital I/O Modules (*1)


Contact Input Module (16 Points, Terminal Type)
Contact Input Module (32 Points, Terminal Type)
Contact Output Module (16 Points,
Terminal Type)
Contact Output Module (32 Points,
Terminal Type)
Contact Input Module (16 Points, Connector Type)
Contact Input Module (32 Points, Connector Type)
Contact Output Module (16 Points, Connector Type)
Contact Output Module (32 Points, Connector Type)
Communication Modules
RS-232C Communication Module
RS-422/RS-485 Communication Module
RS-232C General-purpose Communication Card (*5)
RS-422/RS-485 General-purpose Communication Card (*5)
Ethernet Communication Module (for
PFCS/PFCD)

ADM11T
ADM12T
ADM51T
ADM52T
ADM11C
ADM12C
ADM51C
ADM52C
ACM11
ACM12
ACM21
ACM22
ACM71

Max. No. of Modules to be Installed in I/O Module Nests


AMN11
AMN12

AMN21 AMN31

AMN32

Up to 2
(*4)

Up to 2
(*2)

Up to 4
(*3)

ACF11

Fieldbus Communication Module

ACP71

PROFIBUS Communication Module

*1:
*2:
*3:

*4:
*5:
*6:
*9:
Models

AMN33 AMN34 AMN51 AMN52

Up to 2
(*6)
-

Up to 2
(*5)

4 (*9)

The Multiplexer Module and Digital I/O Module cannot be installed in the same I/O Module Nest.
When the operation mode of Model ADM52T is in time-proportioning ON/OFF in installing in AFS10S/AFS10D/AFS20S/
AFS20D/AFG10S/AFG10D/AFG20S/AFG20D, only one module can be installed in Slot 1 (see table below).
The table in next page shows installation restrictions by operation mode when installing in AFS10S/AFS10D/AFS20S/
AFS20D/AFG10S/AFG10D/AFG20S/AFG20D (No modules can be installed in Slots marked N/A).
When the operation mode of ADM51C is time-proportioning ON/OFF, two modules can be installed in Slots 1 and 3. However, when installing one module only, a general ADMC can be installed in Slots 3 and 4.
When the operation mode of ADM52C is pulse -width-output, two modules can be installed in Slots 1 and 3. However,
when installing one module only, a general ADMC can be installed in Slots 3 and 4.
When the operation mode of ADM52C is in time -proportioning ON/OFF, only one module can be installed in Slot 1.
Installing two modules in one nest allows one to use a pair of redundant modules or two sets of module.
These modules cannot be installed on CENTUM CS 1000 Release 1.
This module and ACM11/ACM12 cannot be installed in the same AMN33 Nest for Communication Modules.
Up to four ACP71 modules can be installed in the PFCS/PFCD Field Control Station. AMN52 is used for ACP71 only.
Functions

ADM52T Time-proportioning ON/OFF output


ADM51C Time-proportioning ON/OFF output
One-shot Pulse-width-output
ADM52C
Time-proportioning ON/OFF output

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

Slot 1
X
X
X

AMN32
Slot 2
Slot 3
N/A
N/A
N/A

X
X
N/A

Slot 4

AMN31
Slot 1
Slot 2
X
N/A

N/A
N/A
N/A

GS 33Y06K40-31E Oct. 22, 2007-00

<<Contents>> <<Index>>

Communication Module Installation Restrictions in Control Stations


CS 1000
Nest

AMN33 (*1)
AMN51 (*6)
AMN52 (*6)
*1:
*2:

*3:
*4:
*5:
*6:

Module
Total of ACM11 and ACM12
ACF11 (*5)
Total of ACM21, ACM22 and ACM71
ACP71

PFCS-S
PFCD-S

PFCS-E
PFCD-E

(*2)
No restriction
-

Max. 4 (*3) (*4)


No restriction
Max. 2 (*4)
Max. 4 (*4)

CS 3000
AFS10S, AFS10D
PFCS-H
AFS20S, AFS20D
PFCD-H
AFG10S, AFG10D
AFG20S, AFG20D
Max. 4 (*3) (*4)
Max. 6 (*3)
No restriction
No restriction
Max. 2 (*4)
Max. 4 (*4)
-

ACM11/12 cannot be combined with ACF11 in the same AMN33 nest.


The maximum number of ACM11/12 modules to be installed in PFCS-S/PFCD-S is restricted by subsystem communication
packages.
-Up to two modules can be used for a single communication.
-Up to three modules can be used for one pair of redundant communications (two modules) and a single communication
(one module).
-Up to four modules can be used for two pairs of redundant communications.
Up to four ACM11/ACM12 modules can be installed in the PFCS-E, PFCD-E, PFCS-H, and PFCD-H. Up to six ACM11/
ACM12 modules can be installed in the AFS0, AFG0. Redundant conguration does not affect the maximum
number of ACM11/ACM12 modules.
ACM11/ACM12, ACM21/ACM22/ACM71, and ACP71 can be combined in the same control station. Up to the maximum
number of modules can be installed.
The maximum number of ACF11 modules is restricted by physical space of control stations or application capacity.
AMN51 and AMN52 cannot be combined in the same control station (Only one of them can be installed).

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun. 1, 2007-00

<<Contents>> <<Index>>

Restrictions on Loading of Input/Output Modules by Heating Volume


When you install I/O modules in ANS/AND50 Node, the following conditions for heating volume must also be met. Pay
particular attention if you install many power-supply type APM11 Pulse Input Modules.
Condition A: Check that the I/O module nest (IOU) meets the following condition:
(I/O module evaluation point) 4.8
Condition B: Check that the node interface unit (NIU) meets the following condition:
(I/O module evaluation point) 24.0
How to Evaluate
1. Calculate an evaluation point in IOU units from Table I/O Module Evaluation Point. When all IOUs evaluation
points meet the above Condition A, it is not required to check if Condition B is met. If there is an IOU which does
not meet Condition A, go to Step 2.
2. If there is an IOU which does not meet Condition A, calculate an evaluation point in NIU units to check if Condition
B is met. If Condition B is not met, add NIUs to meet Condition B.
Table I/O Module Evaluation Point
Module Model
AAM10
AAM11/AAM11B
AAM21/AAM21J
APM11
AAM50
AAM51
AMC80
AMM12C/AMM12T
AMM22T/AMM22TJ
AMM22M/AMM22C
AMM25C
AMM32T/AMM32TJ
AMM32C/AMM32CJ
AMM42T
AMM52T
ADM11C/ADM11T
ADM12C/ADM12T
ADM51C/ADM51T
ADM52C/ADM52T
ADM15R
ADM55R
ACM11
ACM12
ACM21
ACM22
ACM71
ACP711
ACF11

Heat Dissipation Factor


0.25
0.3
0.15
0.4
0.25
0.3
2.0
0.5
0.5
0.5
0.5
0.5
4.0
4.0
0.6
0.6
0.6
0.6
2.0
2.0
1.0
1.0
1.0
1.0
1.2
1.2
1.4

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

<Installation Example>
Lets check if you can install the following I/O modules
in ANS50:
No. 1 IOU:
16 APM11 modules
No. 2 IOU:
16 AAM10 modules
No. 3 IOU:
16 AAM50 modules
No. 4 IOU:
2 ADM11T modules
No. 5 IOU:
2 ADM51T modules
How to Calculate
No. 1 IOU:
0.4 x 16 = 6.4 4.8
(Condition A is not met)
No. 2 IOU:
0.25 x 16 = 4.0 4.8
(Condition A is met)
No. 3 IOU:
0.25 x 16 = 4.0 4.8
(Condition A is met)
No. 4 IOU:
0.6 x 2 = 1.2 4.8
(Condition A is met)
No. 5 IOU:
0.6 x 2 = 1.2 4.8
(Condition A is met)

No. 1 IOU does not meet Condition A. Therefore,


(I/O module evaluation point)
= 6.4 + 4.0 + 4.0 + 1.2 + 1.2
= 16.8 24.0 (Condition B is met)
Result
These I/O modules can be installed in ANS50.

GS 33Y06K40-31E

Jun. 1, 2007-00

<<Contents>> <<Index>>

Protection of RIO Module Vacant Slots


When I/O modules are not installed, dummy covers should be provided for the backboard connectors to protect them
against corrosion.
T9081EF: Dummy frame for AMN1 Nest (Analog I/O Module )
T9081FB: Dummy frame for RJC (AMN1 Nest )
T9081CV(*1): Dummy plate for AMN3 Nest (Digital I/O Module, Multiplexer Module, etc.)
T9081PV: Dummy plate for AMN5 Nest (Communication Module)
*1:

The width of T9081CV is same as that of Multiplexer Module (Connector Type) or Digital I/O module (Connector type). So,
in some cases, two T9081CV are required for one vacant slot.
AMM31

AMM12T
T9081CV

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

F16E.ai

GS 33Y06K40-31E

Jun. 1, 2007-00

<<Contents>> <<Index>>

Analog I /O Module
Current/Voltage Input Modules
These modules receive 4-20 mA from 2-wire transmitters and 1-5 V standardized signals. They can also receive
signals other than standard 4-20 mA or 1-5 V signals. AAM11B can be combined with a transmitter which supports
BRAIN communications. Use our BRAIN terminal to specify parameters for a transmitter.

Analog I/O module

F03E.ai

Items

Specications
AAM11, AAM11B
0 to 20 mA DC (*1) (*2)
Input signal
0 to 10 V DC
(It is possible to supply power to a transmitter.)
Input resistance
1 M at power-up (100 k at power-down)
250
Allowable input voltage/current -10 to 30 V DC
40 mA DC or less
25.0 to 25.5 V DC (Output current limit: 60 mA DC
Supplying power to transmitter
or less )
1 to 5 V DC; Output resistance: 1 or less;
Auxiliary voltage output
Allowable load resistance: 10 k or more; Signal ground is shared with system
Square root extraction
Specify whether to use square root extraction.
Accuracy
Voltage input: 4 mV; Current input: 16 A; Auxiliary voltage output: 12 mV
For 10C change:
Effect of ambient temperature
Voltage input: 4 mV + 0.15 % of specied value
change
Current input: 32 A
Auxiliary voltage output: 24 mV
Data update period
50 ms
Current consumption
300 mA or less (5.0 V DC)
Input signals are isolated between systems
Signal isolation
Withstanding voltage: 1500 V AC/min
How installed
Installed in the I/O Module Nest
How connected
Connected to the terminals of the I/O Module Nest with M4 screws
How input signals are specied Specify input signals and range by software setting.
Model

*1:
*2:

This module can be combined with MTL barrier 728. In this case, wiring resistance must be 10 or less and the minimum
operating voltage of the 2-wire transmitter must be 12 V DC or less.
When the power of AAM11 is OFF or an abnormal condition occurs, the current input loop is open.
Do not share current signals with other receivers. To share signal, attach Shunt Resistance (250 ) to current-output module and share voltage output.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

10

<<Contents>> <<Index>>
Current/Voltage Input Module (Simplied Type)
This module receives 4-20 mA from 2-wire transmitters and 1-5 V standardized signals.
Items

Specications
AAM10
4 to 20 mA DC (*1) (*2)
Input signal
1 to 5 V DC
(It is possible to supply power to a transmitter)
Input resistance
1 M at power-up (100 k at power-down)
250
Allowable input voltage/current -10 to 30 V DC
40 mA DC or less
25.0 to 25.5 V DC
Transmitter power supply
(Output current limit: 60 mA DC or less )
Auxiliary voltage output
None
Square root extraction
None
Accuracy
Voltage input: 4 mV; Current input: 16 mA
Effect of ambient temperature For 10 C change: Voltage input: 8 mV
change
Current input: 32 A
Data update period
50 ms
Current consumption
250 mA or less (5.0 V DC)
Signal isolation
Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min
How installed
Installed in the I/O Module Nest.
How connected
Connected to the terminals of the I/O Module Nest with M4 screws.
How input signals are specied Specify input signals and range by software setting.
Model

*1:
*2:

This module can be combined with MTL barrier 728. At this time, wiring resistance must be 10 or less and the lowest
operating voltage of the 2-wire transmitter must be 12 V DC or less.
When the power of AAM10 is OFF or an abnormal condition occurs, the current input loop is open.
Do not share current signals with other receivers. To share signal, attach Shunt Resistance (250 ) to current-output module and share voltage output.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

11

<<Contents>> <<Index>>
Small Electric Power Input Module
This module receives signals from mV, thermocouple, RTD and potentiometer.
Item

Specications
AAM21, AAM21J (*4)
JIS,IEC Standard
RTD JIS JPt100 or
Thermocouple type K, T,
JIS Pt100 (DIN Pt100)
J, E, B (*1), R, S, IEC
3-wire type
Standard type N

Model
Input signal

Input range

mV

-50 to 150 mV

-50 to 150 mV

3-wire potentiometers
The total residence is
within 100 to 2000 , and
the span is 50 % or more
of the total resistance.
(*2)

0 to 333

Allowable input voltage


Input resistance
Accuracy
Data update period
Signal source resistance
RJC input
RJC accuracy
Measuring current

-0.5 to 4.0 V DC (between terminals B-C)


1 M V at power-up (3 k V at power-down)
20 V
20 V
0.08 V
0.2 %
100 ms
1000 or less
150 or less (wiring resistance per wire)
-10 to 70 C
Within 1 C (*3)
1 mA
1 to 5 V DC (Signal ground is shared with system)
Output resistance: 1 or less
Auxiliary voltage output
Allowable load resistance: 10 k or more
Output range: 0.5 to 5.5 V DC
Accuracy: 12 mV
Burnout detection
Select from UP/DOWN/OFF (*5)
Burnout detection time
Within 60 sec
Burnout detection current 0.1 A (terminal B only) (*5)
How installed
Installed in AMN11 Nest for Analog I/O Modules
How connected
Connected to the terminals of the I/O module nest with M4 screws
Signal isolation
Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min
Current consumption
150 mA or less (5.0 V DC)
Input linearization
None
Available
Available
None
Wiring resistance 10
for terminals A and C: InEffect of signal source re1 k of signal source resistance: Input conversion
put conversion 40 m or
sistance/wiring resistance
20 V or less
less (Wiring of terminals
(burnout is OFF)
A and C must have the
same resistance)
For 10 C change:
mV input:
40 V
Thermocouple input:
40 V
Effect of ambient temRTD input:
0.16
perature change
Potentiometer input:
0.4 % of span
Auxiliary voltage output:
24 mV
How input signals are
Specify input signals and range by software setting.
specied
*1:
*2:
*3:

Type B does not carry out temperature compensation.


Though allowable input range is within 0 to 30000 , in case of keeping accuracy, use within input range.
If measured temperature is lower than 0 C, multiply the above value by the following coefcient (K):
K=

*4:
*5:

Thermoelectric power per degree at 0 C


Thermoelectric power per degree at measured temperature

F04E.ai

The use of AAM21J as termocouple input and RTD input conforms to IEC584-1995, IEC751-1995.
Disable the burnout detection function when using it with a Zener barrier etc. The voltage drop by the measurement impedance and the burnout current may cause an error.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

12

<<Contents>> <<Index>>
Option Specications for Thermocouple
When using the AAM21 for thermocouple input, order the temperature compensation module for each channel.
Description
Model
Option Code

AAM21, AAM21J
/RJ

Temperature Compensation Module for Thermocouple Input

Pulse Input Module


This module receives contact ON/OFF, voltage pulse and current pulse.
Item

Specications
APM11
2-wire type: Contact ON/OFF, voltage pulse, current pulse (It is possible to supply power to a transmitter)
Input signal
3-wire type: Power supply type voltage pulse
Input frequency
0 to 10 kHz (*1)
Data update period
10 ms
Min. input pulse width
40 s or more
Contact input
Relay contact, transistor contact
Detecting level open: 100 k or more; Closed: 200 or less
Contact capacity : 15 V DC, 15 mA or more at 12 V power supply; 30 V DC, 30 mA or more at 24 V
power supply
Input signal level
Voltage/current pulse input (The values of voltage converted from current input are as follows:)
VH (high level) 3 to 24 V DC
VL (low level) -1 to 8 V DC
Swing VH-VL 3 V
Signal source resistance 1 k or less
Shunt resistance
Select from 200/510/1000 /OFF
Pull-up resistance
68 k (12 V or 24 V)
Transmitter power supply
12 V DC 10%, 35 mA or less; 24 V DC 10%, 24 mA or less (Output current limit: 40 mA DC or less)
Output signal: Transistor contact (Open collector); Output contact capacity: 30 VDC, 30 mA or less
Auxiliary output signal
Signal ground is shared with the system.
Current consumption
400 mA or less (5.0 V DC)
Signal isolation
Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min
How installed
Installed in the I/O Module Nest.
How connected
Connected to the terminal of the I/O Module Nest with M4 screws.
How input signal sare specied Specify input signals and range by software setting.
Model

*1:

Input frequency is 0 to 800 Hz to receive no-voltage contact signals between terminal B and C.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

13

<<Contents>> <<Index>>
Current/Voltage Output Module
This module outputs 4 to 20 mA DC and 0 to 10 V DC.
Item
Model
Output signal
Output resistance
Allowable load resistance
Output range
Output voltage limit
Output current limit
Output open detection
Accuracy
Effect of ambient temperature
change
Effect of load resistance
change
Data update period
Current consumption
Signal isolation
How installed
How connected
How output signals are specied

0 to 10 V DC
1 or less
10 k or more
-0.3 to 10.3 V DC
-

Specications
AAM51
4 to 20mA DC
500 k or more
0 to 750
1.0 to 21.5 mA DC
25.5 V DC or less
-

60 mA DC or less
-

0.65 mA or less
Voltage output: 12 mV
Current output: 48 A
For 10 C change: Voltage output: 4 mV + 0.15 % of specied value
Current output: 32 A
2 k load connection: 4 mV

0 to 750 load resistance change: 16 A

20 ms; Step response is 150 ms


300 mA or less (5.0 V DC)
Output signals are isolated between systems. Withstanding voltage: 1500 V AC/min
Installed in the I/O Module Nest.
Connected to the terminas of the I/O Module Nest with M4 screws.
Specify output signals and range by software setting.

Current Output Module


This module outputs 4 to 20 mA DC.
Item
Model
Output signal
Output resistance
Allowable load resistance
Output range
Output voltage limit
Output open detection
Accuracy
Effect of ambient temperature
change
Effect of load resistance
change
Data update period
Current consumption
Signal isolation
How installed
How connected
How output signals are specied

Specications
AAM50
4 to 20mA DC
500 k or more
0 to 750
1.0 to 21.5 mA DC
25.5 V DC or less
0.65 mA or less
Current output: 48 A
For 10C change: Current output 32 A
For 0 to 750 load resistance change: 16 A
20 ms; Step response is 100 ms
250 mA or less (5.0 V DC)
Output signals are isolated between systems. Withstanding voltage: 1500 V AC/min
Installed in the I/O Module Nest.
Connected to the terminals of the I/O ModuleNest with M4 screws.
Specify output signals and range by software setting.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun. 1, 2007-00

14

<<Contents>> <<Index>>
Multipoint Control Analog I/O Module
This module controls 8-point analog loop. It can be made redundant.

AMC80

F12E.ai

Input

Output

Common

Item
Model
No. of input points
Input signal
Input resistance
Allowable input voltage
Accuracy
Effect of ambient temperature change
Input data update period
Step response time
Input signal isolation
Allowable common mode voltage
No. of output points
Output signal
Output resistance
Allowable load resistance
Output range
Output current
Output open detection
Output accuracy
Effect of ambient temperature change
Output data update period
Output step response
Output signal isolation
Current consumption
How installed
Wiring

Specications
AMC80
8
1 to 5 V DC (differential, non-isolated inputs)
500 k or more (at power-up)/100 k or more (at power-down)
-30 to 30 V DC
64 mV
For 10 C change: 8 mV
45 mS
300 mS
No isolation between system and eld, and between channels
5 V or less
8
4 to 20 mA DC
500 k or more
0 to 750
1.25 to 22 mA
25.5 V DC or less
0.65 mA or less
648 A
For 10 C change: 32 A
45 mS
100 mS
No isolation between system and eld, and between channels
2 A or less (5 V DC)
Installed in the AMN34 Nest for Multipoint Control Analog I/O Modules
KS1 cable

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

15

<<Contents>> <<Index>>

Relay I/O Modules


These modules receive or output digital signals from/to the eld through relays. They have 16 relay points.
Relay
I/O Module

F05E.ai

Item
Model
Input rating
Input format
Relay operation time
Relay return time
Current consumption
How installed
How connected
*1:
*2:

Specications
ADM15R
24 V DC 8.3 mA10 % Induction load (*1)
Non-voltage contact (between terminals A-B)
Terminal B is common with system common.
10 msec or less (*2)
10 msec or less (*2)
2 A or less (5.0 V DC)
Installed in the relay I/O module nest.
Connected to the terminal of the relay I/O module nest with M4 screws.

24 V DC is supplied from the built-in power supply.


Operation and return time of the relay; must add communication process time between supervisory computer and module.
Item
Model

Sufx codes
Output rating
Output format
Relay operation time
Relay return time
Current consumption
How installed
How connected
*1:
*2:

Specications
ADM55R
-1: Reset action during on-line maintenance
-2: Hold action during on-line maintenance (*2)
250 V AC 1.5 A or less
125 V DC 0.1 A or less
24 V DC
1.5 A or less
A contact between terminals AC
B contact between terminals BC
10 msec or less (*1)
10 msec or less (*1)
2 A or less (5.0 V DC)
Installed in the relay I/O module nest.
Connected to the terminal of the relay I/O module nest with M4 screws.

Operation and return time of the relay; must add communication process time between supervisory computer and module.
Output hold action of ADM55R-2 is effective in status output mode.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

16

<<Contents>> <<Index>>

Multiplexer Module
These modules receive up to 16 points from DC voltage, mV, thermocouple and RTD. Measuring inputs can be specied per point.
AMM32T
AMM32TJ

AMM12T
AMM22M
AMM22T
AMM22TJ

AMM12C
AMM22C
AMM32C
AMM32CJ
AMM25C

Terminal Type
Multiplexer Module

Connector Type
Multiplexer Module

Item

Specications
AMM12T
AMM12C

Model
Input

16

Input signal

F06E.ai

AMM22M
AMM22C
16

AMM22T
AMM22TJ (*2)
16

AMM32T
AMM32TJ (*3)
AMM32C
AMM32CJ (*3)
16

AMM25C (*2)

15
Termocouple IEC
Thermocouple IEC
RTD
Standard Type K, T, J, E,
Standard Type K, T,
JIS JPt100 or JIS B, R, S
DC voltage
mV
J, E, B, R,
Pt100 (DIN Pt 100) IEC Standard Type N, mV.
IEC Standard
3-wire type
Channel 16 is used for RJC
Type N
port.
-10 to 10 V DC -100 to 100 mV DC -100 to 100 mV DC -200 to 600C
-100 to 100 mV
-30 to 30 V DC -0.5 to 4.0 V DC
-0.5 to 4.0 V DC
-0.5 to 4.0 V DC
1 M
1 M
Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min
1s
4 mV
40 V
40 V
0.15
40 V

Input range
Allowable input voltage
Input resistance
Signal isolation
Data update period
Accuracy
Disconnection detection
10 sec. Max.
time
Disconnection detection
0.1 A
current
Allowable signal source
1 k Max.
1 k Max.
resistance
150 max. (per
Allowable wiring resistance
wire)
RJC input
-10 to 70 C
RJC accuracy
1 C (*1)
15 V 10 %
Allowable common
200 V AC
200 V AC
mode voltage
Measuring current
1 mA
Select from UP/DOWN/OFF.
Burnout detection
Input parallel connection Permitted (burnout OFF)
Not permitted
Permitted (burnout OFF)
How installed
Installed in the I/O module nest.
Connected to the terminal of the I/O module with M4 screws. Use a KS1, KS2 or KS3 cable for AMM12C, a
How connected
KS1 cable for AMM22C/AMM25C, and a KS8 cable for AMM32C.
For 10 C change :
Effect of ambient temFor 10 C change :
DC voltage: 8 mV or less
mV input: 80 V or less
perature change
80 V or less
Thermocouple input: 80 V or less RTD Input: 0.3 or less
Current consumption
500 mA or less (5.0 V DC)
How input signals are
Specify input signals and range by software setting.
specied
*1:

If measured temperature is lower than 0 C, multiply the above value by the following coefcient (K):
K=

*2:
*3:

Thermoelectric power per degree at 0 C


Thermoelectric power per degree at measured temperature

F04E.ai

AMM22TJ and AMM25C conform to IEC584-1995.


AMM32TJ and AMM32CJ conform to IEC751-1995.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

17

<<Contents>> <<Index>>

2-Wire Transmitter Input/Output Multiplexer Modules


AMM42T receives up to sixteen 4-20 mA DC signals from a 2-wire transmitter. AMM52T outputs up to sixteen 4-20 mA
DC signals to a 2-wire transmitter.
Input/output signals are not isolated between system and eld, and between channels.
AMM 42T
AMM 52T

Do not
use

F07E.ai

Item
Model
Input signal
Output signal
Allowable input voltage
Transmitter power supply
Input resistance
Output resistance
Allowable load resistance
Output range
Output voltage limit
Signal isolation
Data update period
Accuracy
Current consumption
How installed
How connected
Effect of ambient temperature
change

Specications
AMM42T

AMM52T
-

4 to 20 mA DC
40 mA or less
23.5 to 24.5 V DC
(output power limit: 60 mA or less)
250
(can be changed to 70 when connected to
barrier)
No isolation between system and eld, and between channels
1 second
16 A
4 A or less (5.0 V DC)
Installed in the I/O module nest.
Connected to the terminals of the I/O module nest
with M4 screws.

4 to 20 mA DC

For 10 C change: 32 A

For 10 C change: 32 A

500 k or over
0 to 750
1.0 to 21.5 mA DC
25.5 V DC or less
No isolation between system and eld, and between channels
1 second
48 A
4 A or less (5.0 V DC)
Installed in the I/O module nest.
Connected to the terminals of the I/O module nest
with M4 screws.

Note: These modules can be combined with MTL Barrier 787S by setting input resistance to 70 . In this case, wiring resistance
must be 10 or less and the minimum operating voltage of 2-wire transmitter must be 12 V DC or less.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

18

<<Contents>> <<Index>>

Digital I/O Modules


These modules receive and output 16 or 32 contact I/O points.

Digital I/O module


(connector type)

Digital I/O module


(terminal type)

F08E.ai

Item
Type
Model
No. of I/O points
Input signal
Contact rating
Pulse width
Pulse period
Current consumption
Function Status input
Push-button input
Signal isolation
How installed
How connected
Terminal board
*1:

Specications
Terminal type

Connector type
ADM11T (*1)
ADM12T (*1)
ADM11C
ADM12C
16 points
32 points
16 points
32 points
Contact input: OFF signal 100 k or more; ON signal 200 or less
Voltage input: OFF signal 4.5 to 25 V DC; ON signal 1 V DC, 200 or less
5 V DC, 20 mA or more (external contact standard)
40 ms or more
10 Hz or less
600 mA or less (5.0 V DC)
Detection function of ON/OFF status
Function which counts edges of push-button pulses
Common minus side
Common minus side
Each point
Each point
every 16 points
every 16 points
Installed in the I/O module nest
Connected to the I/O module nest terminal with M4
KS2 or KS3 cable
KS9 or KS10 cable
screws
TE16
TE32

Specify the option code /CE1 to comply with the EMC Standards.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

19

<<Contents>> <<Index>>
Item
Type
Model
Sufx codes
No. of I/O points
Output signal
Contact rating
Pulse width
Pulse width resolution
Current consumption
Function
Status output
Pulse type output
Pulse width output
Time proportional ON/OFF
Signal isolation
How installed
How connected
CPU halt status / Communication bus termination status
Terminal board
*1:
*2:

Specications
Terminal type
Connector type
ADM51T (*1)
ADM52T (*1)
ADM51C
ADM52C
-1 :Reset action during on-line maintenance
-2 :Hold action during on-line maintenance (*2)
16 points
32 points
16 points
32 points
Transistor contact
Resistive load/Inductive load: 30 V DC, 100 mA or less
0.1 to 7200 s: Setting at time of pulse type, pulse width mode
20 ms
600 mA or less (5.0 V DC)
Output function of ON/OFF status
Pulse type output function of status
One-shot pluse width output function
Time proportional ON/OFF
Common minus side
every 16 points
Installed in the I/O module nest
Connected to the I/O module nest terminal with M4
screws
Each point

Each point

Common minus side


every 16 points

KS2 or KS3 cable

KS9 or KS10 cable

Detection time and output mode can be set when selecting the abnormal detection mode.
-

TE16

TE32

Specify the option code /CE1 to comply with the EMC Standards.
Output hold action of ADM51T-2, ADM52T-2, ADM51C-2, ADM52C-2, is effective in status output mode.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E Oct. 22, 2007-00

20

<<Contents>> <<Index>>

Communication Module
With subsystem communication packages, data is sent/received to/from subsystems such as PLCs via serial communications.
ACM11

F09E.ai

Item
Model
Interface
How connected
How communicates
How synchronizes
Communication speed
Transmission code
Character length
Stop bit length
Parity check
When a signal is received after
data transmission
Transmission distance
How installed
Wiring
How connected
Current consumption

Specications
ACM11
ACM12
RS-232C (1 port)
RS-422 or RS-485 (1 port)
Point-to-point
Point-to-point, Multipoint
Half-duplex
Start-stop synchronization
1200/2400/4800/9600/19200 bps
ASCII/binary
7/8 bit
1/2 bit
None/odd/even (Note: No parity cannot be specied at 19200 bps.)
1 ms (standard); immediately (in special case)

1 ms

Max. 15 m
Max. 1200 m (Total length)
Installed in the Communication Module Nest
(These modules cannot be combined with ACF11. ACM11 can be combined with ACM12.)
KB3, AKB141, AKB143 (RS-232C modem)
3 pairs shielded cable
KB4, AKB142, AKB144 (RS-232C null-modem)
AKB161 (Cable to connect ACM12 and FA500;
cable
Max. 100 m)
Connected to the terminal (6 poles) with M4
D-sub 25 pin (female)
screws.
1 A (5.0 V DC)

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun. 1, 2007-00

21

<<Contents>> <<Index>>

Communication Card
With user programs, subsystems such as PLCs are connected to the Field Control Station via serial communications.
ACM21
RDY
RCV
SND

CN1

F10E.ai

Item
Model
Interface
How connected
How communicates
How synchronizes
Communication speed
Transmission code
Character length
Stop bit length
Parity check
When a signal is received after
data transmission
Transmission distance
How installed
Wiring
How connected
Current consumption

Specications
ACM21
RS-232C (1 port)
Point-to-point
Half-duplex
Start-stop synchronization
1200/2400/4800/9600/19200/38400 bps
ASCII/binary
7/8 bit
1/2 bit
None/odd/even
1 ms (usually)

ACM22
RS-422 or RS-485 (1 port)
Point-to-point, Multipoint

1 ms

Max. 15 m
Max. 1200 m (Total length)
Installed in the Communication Card Nest (Can be combined with ACM71)
KB3, AKB141, AKB143 (RS-232C modem)
3 pairs shielded cable
KB4, AKB142, AKB144 (RS-232C null-modem)
AKB161 (Cable to connect ACM12 and FA500;
cable
Max. 100 m)
Connected to the terminal (6 poles) with M4
D-sub 25 pin (female)
screws.
1 A (5.0 V DC)

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun. 1, 2007-00

22

<<Contents>> <<Index>>

Ethernet Communication Module (for PFCS/PFCD)


Subsystems are connected to the Field Control Station via Ethernet communications.
ACM71
RDY
RCV
SND

CN1

F14E.ai

Item

Specications
ACM71

Model
Physical Layer Interface
How connected
Connector
Communication speed
Transmission route
Transmission distance
No. of ports
Media access control
Display spec
Current consumption
Weight
How installed

IEEE802.3
10BASE-T
Point-to-point. Connected to hub.
RJ45
10 Mbps
100 V twisted-pair cable (not shielded)
100 m per segment
One port
CSMA/CD
SND: Displays that data is sent to a network.
RCV: Displays that data is received from a network.
RDY: Displays that hardware is normal.
1.2 A or less (5.0V DC)
0.3 kg
Installed in the Communication Module Nest. The module can be combined with ACM21, ACM22

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun. 1, 2007-00

23

<<Contents>> <<Index>>

Fieldbus Communication Module


The Fieldbus Communication Module sends/receives data to/from eldbus-connected eld devices.
ACF11

F13E.ai

Item
Model
Interface
Communication speed
Function
Field Device Connection
Network power supply
Current consumption
Signal isolation
Bus connection
How installed

Specications
ACF11
FOUNDATIONeldbus (Low speed voltage mode)
31.25 kbps
LAS function Network power supply function
CS 3000: See Foundation Fieldbus Communication Package (for ACF11) (GS 33Q03L50-31E).
CS 1000: See Foundation Fieldbus Communication Package (for ACF11) (GS 33S03L50-31E).
Output voltage: 18 to 20 V DC
Continuous output current: 80 mA or less
Transient output current: 100 mA or less (20 msec or less)
Output ON/OFF: Specify in the card (When using external power supply, the output is OFF.
1.4 A or less (5.0 V DC)
Signals are isolated between eld and system. Withstanding voltage: 1500 V AC/min.
Connect two terminals with M4 screws. Terminal: detachable
Compliant terminator: YCB138
Installed in the Communication ModuleNest. The module cannot be combined with ACM11/ACM12
Communication Module.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun. 1, 2007-00

24

<<Contents>> <<Index>>

ACP71 PROFIBUS Communication Module


The ACP71 PROFIBUS Communication Module sends/receives data to/from I/O devices which support PROFIBUSDP.
ACP71

F15E.ai

Item
Model
Transmission spec
Communication speed
Signal isolation
Connector
How connected
Transmission route
Transmission distance
No. of ports
Display spec
Conguration port
Current consumption
*1:

Specications
ACP71
EIA-RS485-compliant
9600 bps to 12 Mbps
Yes
D-Sub 9 pin (Female)
T connector (Detachable on line.)
Shielded twisted-pair cable (*1)
Max. 1.2 km per segment (when communication speed is 9600 bps)
One port
RDY: Displays that ACP71 is ready.
MRDY: Displays that communication modules are ready.
MRUN: Displays that data is now sent/received.
MERR: Displays that an error is detected on the media.
Connector: D-Sub 9 pin (male)
Interface: RS-232C (not isolated)
1.2 A or less (5.0V DC)

Refer to PROFIBUS Specication EN50170 Volume 2.

NI-compliant I/O Modules and Their Parameters


I/O modules are compliant with Non-Incendive (NI) rule of CSA Standards. This means that I/O modules can be
installed in Class I, Division 2 hazardous area by installing ANS50/AND50 Node Unit with I/O modules in a cabinet
approved by CSA or local explosion-proof auditor; and directly connected with NI-compliant local devices installed in
hazardous area. I/O modules installed in a device other than ANS50/AND50 Node Unit cannot be installed in hazardous area, but if you install the device in non-hazardous area, I/O modules can be directly connected with NI-compliant
local devices.
For the detailed information of compliance, see System Overview (GS 33Q01B10-31E, GS 33S01B10-31E).
I/O Modules and Parameters
For I/O modules, its parameters, and connectivity, refer to Installation Guidance (TI 33Q01J10-01E or TI 33S01J1001E).

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun. 1, 2007-00

25

<<Contents>> <<Index>>

EXTERNAL DIMENSIONS OF THE I/O MODULE NEST


AMN11, AMN12, AMN21, AMN31, AMN32, AMN33, AMN34, AMN51
Unit:mm
(inch)

M4 screw

236 248
(9.3) (9.8)

113(4.4)

100(3.9)

(0.2)

125(4.9)

30
(1.2)

130(5.1)
F11E.ai

AMN52
233.3(9.19)
19.3
(0.76)

Unit: mm
(inch)

9.8
(0.39)

145(5.71)

222.3(8.75)

11
(0.43)

254
(10)
236
(9.29)

9
(0.35)

Weight: approx. 2.5 kg (5.51lb)


Normal Allowable Deviation =

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

(Value of JIS B 0401-1986 Tolerant Class IT 18)


2

F17E.ai

GS 33Y06K40-31E Oct. 22, 2007-00

26

<<Contents>> <<Index>>

ORDERING INFORMATION
Specify model and sufx codes.

TRADEMARK

FOUNDATION eldbus is a registered trademark of Fieldbus Foundation.


CENTUM is a registered trademark of Yokogawa Electric Corporation.
Other product and company names appearing in this document are trademarks or registered trademarks of their
respective holders.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation


Subject to change without notice.

GS 33Y06K40-31E