Project Objectives were to identify complementary cooling technologies and associated controls,
Thermal Energy Storage (TES): Several technical options (right) exist for a
TES sub-system to enable load-shifting schemes such as night pre-cooling. For the
scoping task at hand, an idealized room-temperature phase-change material applied to all
room surfaces, is postulated. This idealized model has the intrinsic TES properties of low
transport energy and low losses, but is limited to one-day storage.
FLEOH
T (C)
FLEOH
F)
2000 m
Office prototype
\chimodel\20070320\map5.xls EER|x
90F
70F
0.8
60F
80F
50F
0.6
70F
60F
0.4
Component
Wall-Roof U-Factor(a)
Window U-Factor and SHGC(a)
Window-to-Wall-Ratio
Light and Plug Loads (W/m2)
Fan Power (W/(m2/s))
50F
Chiller Solver: given load and conditions
must determine the maximum-COP operating point: 0.2
Tsource = 52F
Compressor, fan and pump shaft speeds
Tsource = 72F
Suction and Discharge pressures
(a)
0
ASHRAE Standard 90.1-2004 prescribed U-factor varies by climate
Refrigerant mass flow rate
0
10
20
30
40
50
60
70
80
90
100
(b)
To completely shade the solar direct beam at all times
Condenser fraction for desuperheating
90000
Part Load Percent
2-Speed Chiller, VAV
A bicubic response surface of COP is fit to data computed on a grid of part-load fraction and outdoor temperature. The bicubic
Var-Speed Chiller, VAV
Baseline
form, which evaluates very fast, is critical to the peak shifting control algorithm within which chiller performance is evaluated Standard Building: Annual energy savings for 80000
2-Speed Chiller, VAV, TES
Var-Speed Chiller, VAV, TES
millions of times. The response surfaces for load-side temperatures of 22C (radiant panel case) and 11C (fan coil case) are
the RCP system with variable-speed chiller and TES 70000
2-Speed Chiller, RCP/DOAS
Full
TOS
shown above. Note the inflections at low part-load fraction for 22C load-side temperature on the 10C and 15.6C outdoor
Var-Speed Chiller, RCP/DOAS
compared to the VAV system with two-speed chiller
temperature lines; the compressor is bypassed and refrigerant-side economizer mode is invoked below these inflection points.
2-Speed Chiller, RCP/DOAS, TES
range from 74% for a hot climate (represented by 60000
Var-Speed Chiller, RCP/DOAS, TES
Houston) to 70% for milder cooling climates (represented
50000
by Los Angeles and Chicago). Note, moreover, that the
savings for the full TSC compared to the next best partial 40000
Outdoor
Refrigerant-Side Economizer: All-air systems use
TSCin which the chiller operates in 2-speed in-stead of
Air
cool outside air for free cooling when conditions permit; this is
full variable-speed modeare significant ranging from 30000
Sight
Condenser
Glass
not possible with RCP systems. Connecting to a maintenance27% (Houston) to over 32% (Los Angeles). Note also that
20000
intensive cooling tower is costly. An alternative--which may make
RCP/DOAS performs the best of partial TSC systems
Outdoor
RCP-based cooling more attractive to building owners--is to use
involving one element, and TES with RCP/DOAS 10000
Air
Bypass
air-cooled chillers with refrigerant-side economizers. This
performs the best of systems involving two elements.
Bypass
0
Compressor
approach is illustrated to the right. Our model solves condenser
TXV
Houston
Memphis
Los Angeles
Baltimore
Chicago
fan and chilled water pump speeds that satisfy a given load
Climate (Represented by City)
with minimum transport energy. Separate bicubic response
High-Performance Building: Savings for
2-Speed Chiller, VAV
surface is fit to the performance data computed on a grid of partVar-Speed
Chiller,
VAV
the full TSC are 71% for Houston, 57% for Chicago, and 30000
Evaporator
2-Speed Chiller, RCP/DOAS
load fraction and outdoor temperature. When outdoor temperature
34.5% for Los Angeles. The percent savings for the full
2-Speed Chiller, VAV, TES
Chilled Water
is above room temperature the vapor-compression chiller map
Var-Speed Chiller, VAV, TES
TSC compared to the next best partial TSC are 25000
Var-Speed Chiller, RCP/DOAS
applies; when outdoor temperature is below room temperature
significantly better than those of the standard and mid2-Speed Chiller, RCP/DOAS, TES
both are evaluated and the less power intensive result is applied.
performance buildings, ranging from 30% (Chicago) to
Var-Speed Chiller, RCP/DOAS, TES
20000
35% (Houston). The RCP/DOAS configuration again
DOAS Conditioning: A dedicated outdoor air system
Exhaust
Return
performs
best
of
the
partial
TSC
systems
involving
one
circulates about 15% of the air required by an all-air systemjust
Air
Air
element, and TES with RCP/DOAS still performs the best 15000
enough to remove and maintain acceptably low air contaminant
of systems involving two elements. For Los Angeles,
concentrations. 100% of this reduced air flow is outside air.
however, VAV is retained in the best-performing one- and 10000
Enthalpy recovery equipment has been shown capable, in tight
two-element configurations. This reflects the reduced
buildings, of saving 50-80% of the heating and cooling energy
specific-fan-power design of the high-performance
needed to condition outside air. In cooling mode the DOAS must
5000
building, which benefits the air-side economizer (VAV
Outdoor
Supply
satisfy any remaining latent cooling (dehumidification) load. A
Air
Air
cases), while refrigerant-side economizer (RCP/DOAS)
variable-speed vapor-compression machineas shown at right
0
performance is unchanged. Thus the best partial TSC
EXV
downstream of the supply-air-conditioning enthalpy wheelcan be
Houston
Memphis
Los Angeles
Baltimore
Chicago
involving one element in Los Angeles is the TES system.
Climate (Represented by City)
used to convert the latent load to sensible load by cooling the
Sponsors. MIT work funded by Masdar Institute of Science and Technology; initial work funded by U.S. Dept. of Energy.
supply air to the required dew point and then reheating the air by rejecting all of the heat produced in the
Pacific Northwest National Laboratorys Wei Jiang, S. Katipamula and Dave Winiarski made substantial contributions.
dehumidification process. Thermally regenerated desiccant dehumidification will also be evaluated.
P2
E2
H3, T7
T5
E1
E3
P1
T3
T2
Condenser
Compressor
Evaporator
F3
T4