http://electrical-engineering-portal.com/applications-and-characteristics-of-overcurrent-relays-ansi-50-51
1/6
10/13/2014
The pickup level is set by the tap setting, which is usually set in CT secondary amperes but may be
set in primary amperes on some microprocessor-based relays.
Each relay curve has a time dial setting which allows the curve to be shifted up or down
on the time-current characteristic curve.
In Figure 1, the time dial settings are different to give enough space between the curves to show
their differences.
The above are IEEE-standard curves; others are available, depending upon the relay make and
model. A solid state electronic or microprocessor-based relay will have all of these curves available
on one unit; electromechanical relays must be ordered with a given characteristic that cannot be
changed.
The 50 instantaneous function is only provided with a pickup setting. The 30ms delay shown in figure
1 for the 50 function is typical and takes into account both the relay logic operation and the output
contact closing time.
http://electrical-engineering-portal.com/applications-and-characteristics-of-overcurrent-relays-ansi-50-51
2/6
10/13/2014
Most microprocessor-based units will also have an adjustable delay for the 50
function; when an intentional time delay is added the 50 is referred to as a
definite-time overcurrent function. On solid-state electronic and microprocessorbased relays, the 50 function may be enabled or disabled.
On electromechanical relays, the 50 function can be added as an instantaneous
attachment to a 51 time-overcurrent relay. If a relay has both 50 and 51 functions
present and enabled is referred to as a 50/51 relay.
Typically, overcurrent relays are employed as one per phase. In solidly-grounded medium voltage
systems, the most common choice for ground fault protection is to add a fourth relay in the residual
connection of the CTs to monitor the sum of all three phase currents. This relay is referred to as
a residual ground overcurrent or 51N (or 50/51N) relay.
The CT arrangement for 50/51 and 50/51N relays for a solidly-grounded system is shown in Figure
2 below.
http://electrical-engineering-portal.com/applications-and-characteristics-of-overcurrent-relays-ansi-50-51
3/6
10/13/2014
For ungrounded systems, the ground detection methods are recommended since little ground
current will flow during a single phase-to-ground fault. Low voltage solidly-grounded systems are
discussed below.
The typical application of phase and residual neutral ground overcurrent relays in one-line diagram
form is shown in figure 4.
Figure 4 Typical
application of overcurrent
relays
http://electrical-engineering-portal.com/applications-and-characteristics-of-overcurrent-relays-ansi-50-51
4/6
10/13/2014
In Figure 4, the designation 52 is the IEEE Std. C37.2-1996 designationfor a circuit breaker.
The phase relays are designated 51 and the residual ground overcurrent relay is designated 51N
(both without instantaneous function). The bracketed denotes that there are three phase overcurrent
relays and three CTs. The dotted line from the relays to the circuit breaker denotes that the relays
are wired to trip the circuit breaker on an overcurrent condition.
The 51C relay does not operate on overcurrent unless the voltage is below a preset value. The 51
V relay pickup current shifts as the voltage changes, allowing it to only respond to overcurrents at
reduced voltage. Both require voltage inputs, and thus require voltage transformers for operation.
http://electrical-engineering-portal.com/applications-and-characteristics-of-overcurrent-relays-ansi-50-51
5/6
10/13/2014
http://electrical-engineering-portal.com/applications-and-characteristics-of-overcurrent-relays-ansi-50-51
6/6