OPGW
Ref: s011
Introduction
Features and benefits
This cable has been custom designed to best match
with customer requirements from optical, electrical,
mechanical, quality and cost point of view,
optimizing diameter, weight, breaking load and
short circuit capacity.
Cable structure
Optical core is made of optical fibres [1] covered by
one or more stainless steel tubes [2] that leave the
fibres free from strain even at highest operating
loads.
The wires of...
aluminium clad steel [3].
aluminium alloy [4]
[1]
[2]
[3]
[4]
Fibre characteristics
See our technical document reference 4377
SMLight G.652.B, FreeLight G.655.D, multimode
50/125 and multimode 62.5/125 optical fibers and
document reference 4647 MagniLight G.652.D.
[3]
Rev.:
01
Date:
21-oct-2011
Issued by:
E. Castillo
page 1 of 2
OPGW
Ref: s011
Cable characteristics
FIBER (max)
OPGW
REFERENCE
FAULT
CURRENT
TOTAL
CONDUCTOR
AREA
OVERALL
DIAMETER
WEIGHT
RBS
SAG10
CHART #
(kA)sec
in
mm
in
mm
lbs/ft
kg/m
lbs
kg
24
20A42Ds (7978)
41
0.1233
79.53
0.472
12.0
0.282
417
14947
6780
1-1461
36
20A37Ds (7979)
41
0.1180
76.12
0.472
12.0
0.251
370
12269
5565
1-350
24
41F47Ds (7975)
96
0.1764
113.81
0.555
14.1
0.320
473
15621
7086
1-1438
24
46H47Ds (7976)
116
0.1896
122.32
0.575
14.6
0.321
474
14782
6705
1-430
96
60J62Ds (7977)
137
0.2140
138.05
0.630
16.0
0.420
620
20091
9113
1-1170
96
64J67Ds (7980)
152
0.2254
145.45
0.646
16.4
0.452
668
22191
10066
1-917
96
70K71Ds (7981)
177
0.2412
155.63
0.669
17.0
0.478
706
23303
10570
1-917
144
60H62Ds (7982)
118
0.2017
130.12
0.630
16.0
0.417
616
19866
9011
1-1440
144
64J66Ds (7983)
132
0.2131
137.51
0.646
16.4
0.449
663
22059
10006
1-350
144
70K70Ds (7984)
152
0.2289
147.7
0.669
17.0
0.474
700
23051
10456
1-1440
192
60G61Ds (7985)
100
0.1894
122.18
0.630
16.0
0.415
612
19641
8909
1-536
192
64H66Ds (7986)
114
0.2008
129.58
0.646
16.4
0.446
659
21642
9817
1-420
192
70J70Ds (7987)
134
0.2166
139.76
0.669
17.0
0.472
697
22800
10342
1-536
288
60D60Ds (7990)
71
0.1654
106.72
0.630
16.0
0.405
598
19048
8663
1-1166
288
60E64Ds (7992)
80
0.1764
113.81
0.630
16.0
0.435
642
21131
9585
1-1461
288
66G68Ds (7991)
98
0.1931
124.57
0.653
16.6
0.461
680
22300
10115
1-1166
Routine tests
100% of optical fibers will be measured by OTDR technique before leaving factory.
Installation procedure
Prysmian recommends to install the cable described in this specification following the latest version of our
"Installation procedures for OPGW fiber optic cable" reference SIG-07-PE-PA-013, "Instruction for the installation of
the EWMJ joint box" reference SIG-07-PE-PA-015 and "Instruction for the installation of the EWJ joint box"
reference SIG-07-PE-PA-008.
Rev.:
01
Date:
21-oct-2011
Issued by:
E. Castillo
page 2 of 2