CHAS MUNICIPALITY
WATER SUPPLY IMPROVEMENTS SCHEME
Design of 1200 KL Capacity Clear Water Sump at Filtration Plant, Chas
Capacity of the Sump
1200 KL
21.00m
3.50m
GL
+ 160.45 M
MWL
+ 161.10 M
LWL
+ 157.60 M
Free Board
0.30 m
Dead Storage
0.15 m
+ 157.45 M
+161.40 m
0.38 m
0.40 m
Density of RCC
2
Total height of side wall
[3.50+0.15+0.30]
3.95/. m
Grade of reinforcement
Fe-415
Structural Design
1.2 N/mm2
cbc
7 N/mm2
13.33 N/mm2
0.289;
j =
0.904;
R =
0.914
=
21.00 m
0.38 m
0.38 m
0.38 m
3.65 m
0.15 m
3.80 m
164.00 mm
SAFE
Side Wall
= 300
1 Sin
Ka = 1 Sin = 0.333
Pa =
1
x 0.333 x 19 x 3.02
2
(160.45-157.45 = 3.00)
= 28.47 KN/M
M = 28.47 x
3 .0
= 28.47 KNM / M
3
Uncracked section =
1
fbd2 = 2847
6
d=
2847
2.50
Ast =
28471x100
= 4.38 Cm2
1900 x0.9 x38
= 33.74 < 38 cm
Provide 10 Tor @ 140 mm c/c (Ast = 560 mm2) upto 1.50 m from base
Provide 10 Tor @ 280 mm c/c from 1.50 m above base upto top
From MWL
Reqd.min.reinf (sqmm/m)
Thickness (mm)
0.0 H to 0.5 H
380
Total
484
0.5 H to 1.0 H
380
484
On each face
242
242
H2 / (DT)
=1.955
coeff*10*21/2*3.95KN/m
414.75
W*D / 2*H
Height
above
Floor
Height
below
MWL
Hoop
coefficient
Hoop
tension
(KN/m)
Reqd.
total Ash
(mm2/m)
3.650
2.520
2.240
1.960
1.680
1.400
1.120
1.140
0.730
0.365
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
0.212
0.265
0.323
0.372
0.410
0.428
0.412
0.363
0.275
0.148
88
110
134
155
171
178
171
151
115
62
Both
face
Spacing
mm c/c
587
734
893
1033
1140
1187
1140
1000
767
414
10
10
10
10
10
10
10
10
10
10
200
190
170
140
130
120
130
140
190
200
826
785
slab (m)
Total area
on two
faces
(sqmm)
785
826
924
1121
1208
1308
1208
1121
380 mm
VERTICAL BM
Coeff3
0.044
27.12 KN-m/m
Coeff4
0.012
7.39 KN-m/m
798 mm2/m
399 mm2/m
Max. vertical BM
27.12 KN-m/m
5
Total thickness of side wall at base (T)
380 mm
Clear cover
30 mm
10 mm
Effective cover
35 mm
345 mm
d/ T
0.91
32.94 Cm < 38 Cm
380 mm
SAFE
588 mm2/m
160 mm2/m
798 mm2/m
399 mm2/m
588 mm2/m
160 mm2/m
Reinforcement
Vertical Reinforcement
6
On water face
From base upto 1.5 m above base
Diameter of reinforcement
10 mm
90 mm c/c
10 mm
180 mm c/c
On outer face
From base upto 1.5 m above base
Diameter of reinforcement
10 mm
140 mm c/c
From 1.50 m above base upto top Provide 10 Tor @ 280 mm c/c
HAUNCHES INSIDE AND OUTSIDE
Provide haunches of 200 x 200 mm size with 8mm Tor @ 150 mm c/c both ways
7
Design of Roof Dome: (12mm thick @ crown & 15 Cm thick @ sprining)
Chord width
14.00 m c/c
Rise
2.00 m c/c
Thickness
12 Cm @ crown
R=
7.0 2 2.0 2
2 x2
Sin =
= 13.25 m
7.0
= 0.528 = 31.890
13.25
3.315 KN/ m2
Live load
1.50 KN/ m2
Finishings
1.50 KN/ m2
(W) =
6.315 KN/ m2
WR
1 Cos
6.315 x13.25
= 45.25 KN/ m
1 0.849
Hoop stress =
45.25
= 0.377 N/ mm2 < 1.6 N/ mm2
120
WR (Cos 2 Cos 1)
t
1 Cos
6.315 13.25 (0.8492 0.849 1)
120
1 0.849
= 1.81 KNM/ m
Uncracked depth =
Ast =
181
= 8.51 Cm < 12 Cm (OK)
2. 5
181x100
= 0.72 Cm2
2300 x 0.904 x12
Rt
= 0.76 x
13.25 x 0.15
= 1.07 m
Provide 15 Cm thickness at the springing reduced to 12 Cm at 1.50 m from
springing.
Provide 8 dia 15 Cm c/c (3.35 Cm2) both ways radially and circumferentially at
bottom and provide additional reinforcement 8 dia @ 15 Cm c/c both radially and
circumferentially at top face upto 1.30 m from springing.
22 Cm
Span
3.69 m c/c
Load
Self weight = 0.22 x 25.50
5.61 KN/ m2
3.00 KN/ m2
Finishings
1.50 KN/ m2
10.11 KN/ m2
Uncracked depth =
11.47
= 21.42 Cm < 22 Cm
2.5
1147 x100
= 3.42 Cm2
0.904 x19.5 x1900
Reinforcement:
Provide 8 dia @ 13 Cm c/c at mid span and crank alternate bars near supports.
Provide extra bars 8 dia at top in between cranked bars @ inner & outer supports.
Provide distribution steel 8 dia @ 20 Cm c/c
1051.00 KN
10.11 KN
179.45 KN
2189.95 KN
Load per RM =
2189.95
= 49.79 KN/ m (or) say 501 KN/ m
x14
Case (a):
Due to hoop tension
Horizontal thrust = MT x Cos = 45.25 x 0.849
38.41 KN
269.00 KN
10
26900
1500
17.93 Sqcm
Hoop stress:
Provide 10 # 16 dia (20.10 Cm2) as hoop rods > 17.93 Cm2
Eq.cross section = (40 x 62) + (8 x 20.10) = 2640.80 Cm 2
Tensile stress in concrete =
26900
= 10.2 Kg/ Cm2 < 15 KSC
2640.80
Case (b):
Load per RM = 500 K
Width of support = 40 Cm
The beam is circularly supported by 16 Nos columns and the point of contraflecture
coefficients for moments and torsion in the beams are given below for 16 columns
configuration.
Span BM = 0.00645 x 5000 x 7.02
1580.25 Kgm
3156.00 Kgm
119.50 Kgm
Width of support = 40 Cm
=
0 .2
= 0.02 rad
7 .0
53.90
62
(1 +
)
1.70
40
= 2323 Kgm
Area of steel at support =
2323x100
= 2.29 Cm2
0.904 x1900 x59
11
1580.25 x100
= 1.60 Cm2
0.904 x1900 x59
5000x 2.75
= 6875 Kg
2
6875
(1.37 0.2) = 5872 Kg
1.37
Ve = 5872 + 1.6 x
Tve =
Pt =
53.90
= 6088 Kg
0.40
6088
= 2.56 Kg/ Cm2
40 x59
100 x 6.03
= 0.25%
40 x59
1.00 x1500
= 104 Cm c/c
40 x( 2.56 2.20)
(16 # 40 Cm x 40 Cm columns)
2189.95
16
2189.95 KN
136.87 KN
16.40 KN
153.27 KN
12
Say 15.50 t
SAFE
Reinforcement
Provide 8mm Tor at 120mm c/c at bottom at mid span and crank alternate bars near
supports, spacing measured at mid span). Also provide extra 8mm Tor at 240mm c/c on
top at supports.
Ast provided
418 mm2/m
SAFE
114 mm2/m
Reinforcement
Provide 8mm Tor at 200mm c/c as distribution reinforcement
Ast provided = 251 mm2/m
SAFE
707 mm2
13
6.26 Nos
7 Nos
Provide 4 Nos of 12mm Tor on each vertical side face of beam as hoop
reinforcement.
1.13 N/mm2
< 1.5 N/mm2
SAFE
Loading:
Load from roof dome
609.9 KN
30 KN
262 KN
69 KN
971 KN
29.44 KN/m
No. of supports = 12 2A = 30
Degree: A
15 Degrees
0.261799 radians
Degrees
0.109083 radians
14
Max Torsion = w*(D2/2)2*[TT/n* CosB TT/n*Cot A x Sin B (TT/n TT/180*B)]
=
0.86 KNm
Design of beam
At face of support
Size of beam = 300 x 420 mm
Effective depth (d) = (D-30-12-8-16/ 2)
0.86 KNm
Mt = T / 1.7* (1+ D/ b)
1.22 KNM
Me = (BM+Mt)
18.12 KNm
t = 190 N/mm2;
362 mm
56.22 KNm
375 mm2
239 mm2
Top reinforcement: Provide 2 Nos of 12mm Tor through and 1 No. of 16mm Tor
15
T = 0.860 KNM Ve = V + 1.6*T/ b
34.4 KN
0.32 N/mm2
=
Corresponding tc =
427 mm2
0.274 N/mm2
1274 mm c/c
Asv = T*Sv/(b1*d11*tsv)+V*Sv/(2.5*d11*tsv)
b1 = 204mm; d1 = 324 mm
2. Sv
302 mm c/c
372 mm
3. Sv = Least of X1 or Y1
252 mm c/c
4. Sv = (X1+Y1)/4
156 mm c/c
347 mm c/c
Max Sv
156 mm c/c
Sv
156 mm c/c
fy = 415 N/mm2
Min Asv condition; Sv = Asv*fy/ (0.4*b)
16
Mid span BM = 8.48 KNM
T = 150 N/mm2; c = 10 N/mm2; m = 9; k = 0.375; j = 0.875; Q = 1.64
Balance BM = Qbd2 = 64.4736 KNM
Required Ast = M*106 / (150*0.875*d)
179 mm2
277.2 mm2
SAFE
971 KN
86 KN
1057 KN
Min As = 565 mm 2
Longitudinal reinf. of 6 Nos of 12 Tor with 8mm Tor lateral ties at 150mm c/c
OK
1.034
>
88.09 KN
SAFE
350 mm
17
Outside projection of base slab
450 mm
22.86 mm
2190.00 KN
1443.20 KN
Loadings
pi/4*(21.00^2-14.0^2)*7.5
DL of cylindrical side wall 3.142*(21.0+0.38)*0.38*4.32*25 =
Weight of water 0.786*21.0^2*(3.5+0.3)*10
2757.00 KN
13161.80 KN
Pressure on soil
23146.00 KN
56.40 KN/m2
< 200 KN/m2
SAFE
3940.00 KN
pi/4*(21.002-182)*10.11 = 1183
pi()*(21.00+0.38)*0.38*4.32*25 = 2757 KN
Thickness of side wall at base
0.38 m
0.55 m
0.35 m
1.48 m
21.38 m
18
Load per metre run from side wall 3940 / (PI()*21.38) =
58.66 KN
12.95 KN
Total per 1 RM
33.44 KN
22.089 KN/m2
22.089 KN/m2
22.089 KN/m2
24.96/ 1.13
0.45 m
0.30 M
0.45 m
0.30 m
Bottom level base slab
1.13 m
0.45 m
0.45 m
2.237 KN-m/m
19
Max BM
2.237 KN-m/m
300 mm
Clear cover
60 mm
10 mm TOR
Effective cover
75 mm
225 mm
d/D
0.75
M / BD2
0.3444
81 mm
Provided thickness
300 mm
SAFE
77 mm2/m
583 mm2/m
291.50 mm2/m
=
=
225 mm
0.0221 N/mm2
0.15%
337.5 mm2/m
225 mm
0.0331 N/mm2
20
From Cl. 316.3.1 of IS:456-2000
Max. allowable punching shear stress = 0.16*sqrt(fck) =
0.8764 N/mm2
SAFE
376 mm
500 mm
Required Ast
337.5 mm2/m
232 mm c/c
291.50 mm2/m
Provide 10mm Tor radial reinforcement @ 200mm c/c. At bottom same as top mat of
bottom level base slab
Provided Asd = 392 mm2/m > 291.5 mm2/m
SAFE
Distribution reinf.
Avg thickness of annular raft slab
300mm
360 mm2/m
291.50 mm2/m
21
Circumferential reinforcement each at top and bottom
Provide 10mm Tor @ 200mm c/c as distribution reinf.(in the form of circumferentials)
Provided Asd = 392 mm2/m > 360 mm2/m
SAFE
300 mm
583 mm2/m as per IS:3370
291.5 mm2/m
22