MV network management - Easergy range

Technical data sheet

2008

Flair 310, Flair 370


Directional fault passage indicators
for underground networks

PE41001

Application

The Flair 3xx directional fault passage indicators are designed for underground MV
networks with isolated or compensated earthing.
They can also be used on underground MV networks with impedant earthing.
They provide a light indication allowing to localize the fault.
Flair 370: 220 Vac + lithium battery power supply.
Flair 310: lithium battery power supply (when no LV power supply available).

Description

Flair 3xx fault passage indicators are made of ABS polycarbonat sealable box.
b Operation mode and functions:
v adaptation to the voltage sensors using dip-switches,
v various user configurable parameters: detection parameters, reset functions
and output contact behaviour,
v optional settings, test and reset functions by magnetic button.
b Light indication
Green, Red or alternate Green/Red blinking according to fault type and location.
b Fault counters
Number of transient and permanent faults.
b Display: 4x12.7 mm digits
Displays fault counters and optional settings.
b 2 output contacts
Indication of transient and/or permanent faults.

b Directional detection
of phase-to-earth faults

Sensors

b Default settings fitting


most applications

PE55552

b Fully user configurable

PE55553

b 2 types of current sensors installation are possible:


v single CT installation: phase-to-earth faults only (installation on 3-core cable),
v 3 phase CTs installation: phase-to-earth and phase-to-phase faults.

b Detection of phase-to-phase faults

b Lithium battery power supply

MFD standard phase CT


MFH 2200 earth fault CT

TCR resin phase CT

b Voltage sensors are capacitive dividers situated:


v on MV/LV substations switchgears or transformers separable elbow connectors,
v on air insulated substations busbars.

Standard

PE55557

PE55556

PE55555

Light indicators

Flush mounted
(wall < 6 mm)

Anti-vandalism

DE55561

Flair 3xx detection principle is based on the analysis of


transients of residual voltage Vr (= 3 V0) and residual
current Ir (= 3 I0), in the next ms following the fault.
b At the time when the phase-to-earth fault occurs,
the fault direction is determined according to phase
comparison of Vr and Ir.
kV

10

100

Ir

Vr
-100

-10

b The fault will be confirmed if Vr is still present after


a configurable time delay (default 50 ms). Indication
of transient fault (counter and optionally output contact)
will follow.
b The fault will be confirmed as permanent (protection
tripping or power presence under earth fault conditions)
after the possible reclosing cycles before starting
permanent fault indication (light indication and optionally
output contact).
This detection algorithm allows detecting earth faults
up to approximately 200 .

Light indication
DE55562

b Phase-to-earth fault
MV feeder

Green or off

b Phase-to-phase or double phase-to-earth fault


MV feeder

Characteristics

Application
Network (standard: others, on request) (kV)
Frequency (Hz)
Neutral
Phase-to-earth fault detection
Residual current detection threshold (A peak)
Residual voltage detection threshold (kV peak)
Residual voltage required for fault confirmation
(kV rms)
Residual voltage rms minimum duration (ms)
Minimum total capacitive current required (A)
Minimum capacitive current for indication
downstream fault (A)
Light indication
Double phase-to-earth fault detection
Tripping threshold (A)

10 to 25 (according to voltage sensor)


50
Compensated - isolated - impedant
40
0.3 x Un (e.g.: 6 kV peak for Un = 20 kV)
0.18 x Un (e.g.: 3.5 kV rms for Un = 20 kV)
50* to 500
50
30
Red: earth fault towards cable
Green: earth fault towards busbar
100, 120, 140, 160*, 180, 200, 220, 240,
260, 280, 300
50, 60, 70*, 80, 90, 100, 120,140, 160, 180,
200, 250, 300, 350, 400, 450, 500
Alternate Red/Green

Time delay (ms)


Light indication
Phase-to-phase fault detection
Tripping threshold (A)
Time delay (ms)
Light indication
Time delays
Before indication of transient fault
(counter and output contact) (s)
Before indication of permanent faults
(light indication and output contact) (s)
Duration of MV required for any fault detection
(inrush restraint) (s)
Reset of fault indication
By restoration of MV without fault
for a duration of (s)
After configurable time delay (h)
Manual
Light indication
Flashing period (s)
Dry output contact
Breaking capacity
Environment
Vibration withstand (IEC 68-2-6 & 68-2-29) (g)
Operating temperature (C)
Storage temperature (C)
Protection grade
Mechanical characteristics
Dimension H x L x P (mm)
Weight (kg)

200, 250, 300, 350, 400, 450, 500*


50, 60, 70*, 80, 90, 100, 120,140, 160, 180,
200, 250, 300, 350, 400, 450, 500
Alternate Red/Green
1.1
Off-10-40-70*-120-240
5

5 (note: can be disabled)


2, 4*, 6, 8, 12, 16
With a magnet
1
8 A/250 Vac; 5 A/30 Vdc
2
25 to + 55
25 to + 70
IP 21 IK 9
270 x 203 x 110
1.5

(*) Default value.


Device

Power supply
Lithium battery

Reference
220 Vca ( 10%),
+ lithium battery
(10 kV isolated)

Battery life
duration

Flair 310
Flair 370

CTs
MFD
TCR
MFH 2200
IC 30C

Internal (mm) External (mm)


70
160
55
120
130
200
3 m cable for MFH 2200

59990**
C2991753**
59927
59998

Light indicators
BVE-D
LED-D
BVD

Type
Standard
Flush-mounted into wall < 6 mm
Anti-vandalism

59988
59989
59961

> 7 years*
> 10 years*

59979
59980

ART.95988 Schneider Electric Industries SAS - All rights reserved

Detection principle

(*) Including 200 hours blinking.


(**) Kit of 3 CTs with connection bundle.
Consult us for voltage sensors, if necessary.

Schneider Electric Industries SAS


89, boulevard Franklin Roosevelt
F-92505 Rueil-Malmaison Cedex
Tl. : +33 (0)1 41 29 85 00
www.schneider-electric.com
www.easergy.com
AMTED304009EN

As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
Publishing: Schneider Electric
Production: Schneider Electric
Printing: Imprimerie du Pont de Claix

This document has been


printed on ecological paper