Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

CONTENT
Sl. No.

Section No.

Single line diagram

33 kv Line

2.1

CTs for metering

2.2

CTs for Backup Protection - 67/67N & 51/51N

2.3

CTs for Distance protection - 21

3.1

CTs for 20 MVA Transformer Differential prot. - 87T

3.2

CTs for 20MVA Transformer metering

3.3

CTs fpr 20 MVA Transformer Backup Protection50/50N & 51/51N

10

3.4

CTs for Buscoupler Backup Protection -51/51N

11

3.5

CTs for Buscoupler Metering

12

13

4.1

PT for Incomer Line feeder PT

14

4.2

Bus PT

15

16

5.1

17

5.2

18

5.3

CTs for Transformer REF protection - 64 REF

19

5.4

CTs for 20 MVA Transformer Differential prot. - 87T

20

21

6.1

CTs for Buscoupler Backup Protection -50/51

22

6.2

CTs for metering

23
24
25
26
27
28
29

6.3
6.4
6.5
6.6
7
7.1
8

CTs for Buscoupler Protection -51/51N


CT's for metering
CTs for Backup Protection-50/51
CTs for metering
11kV PT
PT for Incomer Line feeder PT
Catalogue

Discription

33 kV Transformer incomer

33kV PT

11kV Transformer Incomer


CT's for metering
## CTs for Backup Protection-67/51

11kV Transformer Outgoing

Ppd.: AKR
Chkd: AKSM/SRKR

1 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Section - 1 : Single Line Diagram

Ppd.: AKR
Chkd: AKSM/SRKR

2 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

3 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Section - 2 : 33kV Line

Ppd.: AKR
Chkd: AKSM/SRKR

4 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

5 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

2.1 CTs for - Metering


(33kV switchgear incomer)
1.0 Meters connected
a.
b.
c.
d.
e

DA
--0.5
1
0.5

Make
Model
VA Burden
Qty. (Nos.)
Net VA

------

2.0 CT Details
CT Ratio
IPN

CORE-1
400

ISN

CT Class: 1.0
ISF 10

Primary

A
Secondary
Rated Burden:
15 VA
Voltage (kV): 33
Rated system fault current (in kA & time in sec.) :
25

3 sec.

3.0 Calculation of VA Burden of the CT Core


Sum of the VA Burden of the Meters connected, R m

0.5

VA

----(1)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT to Meters mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
----(2)

=
=
=

Rm + RL
(0.5 + 0.558)
1.058
VA

----(3)

PBC

=
=
=

1.5 x External Burden


(1.5 x 1.058)
2
VA

----(5)

PBN

15
VA
- is sufficient

The external Burden

Hence connected VA to CT Core


(with design margin of 50%)

Hence Selected VA Burden for CT core

30

----(6)

4.0 Conclusion :
1
2

The 'Connected CT burden' is 2 while the 'Rated CT burden' is 15


As 'Rated CT burden' >'Connected CT burden' the selected CT is ACCEPTABLE
Summary of CT parameters
CT Ratio : 400/1 A
Class : 1
Rated Burden : 15
ISF< 10

Ppd.: AKR
Chkd: AKSM/SRKR

6 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

2.2 CTs for Backup Protection - 67/67N & 51/51N


(33kV Switchgear Incomer)
1.0 Application
Protection : Dir.O/C & E/F Protection (67/67N & 51/51N)

2.0 Relay Proposed


a.
b.
c.

Make
Model
Type

Siemens
7SJ602
Numerical, IDMTL Type

3.0 CT Details
Voltage Class :
33 kV
Frequency :
50 Hz
Short time rating :
25 kA for 3 sec.
Mounting: CTs are mounted in 33kV sw.gear
CT Ratio : Core-2
Ipn
400 A
Primary
Isn
CT Class:
ALF:
Rated
Burden:
Rct =
Iscc.max =

1 A

Secondary

5P
20
15
4

VA
Ohm
25 kA

(Assumed)

4.0 Calculation of VA Burden of the CT Core


Rr =

VA Burden of the Relay (Siemens)

0.05

VA at ISN
----(1)
(Ref. Siemens SIP.2006)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT - Relay mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

CT's internal Resistance (400/1 Tap at 75C) Rct


CT's internal Burden

Connected CT External Burden

=
Pi =

=
=
=

Ppd.: AKR
Chkd: AKSM/SRKR

30

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
----(2)
4

Ohm

(Isn^2) x [Rct]
(1^2) x [4]
4

VA

----(3)

VA

----(4)

(Rr + RL)
(0.05+0.558)
0.608

7 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Hence connected VA to CT Core


(with design margin of 20%)
PBC

=
=
=

1.2 x External Burden


(1.2 x 0.608)
0.73
VA

PBN =

Selected VA Burden for CT core

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

15

VA

- is sufficient

5 Calculation of minimum required 'Accuracy Limit Factor' for the CT:


(refer SIP-2004, Chapter 2, Pg.53)
Minimum required CT symmetrical short-circuit current factor -

K ' ssc 1 max

[(

I highset po int
I pn

, 20

Where K'scc1

minimum required symmetrical short-circuit current factor

Ihigh-set point

=
=
=
=

maximum short-circuit current (in Ampere)


25000
Amp
Nominal CT primary current (in Ampere)
400
Amp

Ipn

Kssc1

=
max[(Ihigh-set point / Ipn), 20]
=
max[(25000 / 400), 20]
=
62.5
Thus the minimum required CT symmetrical short-circuit current factor Kscc1
=
63

----(6)

6 Calculation of operating 'Accuracy Limit Factor' for the CT:

K ' ssc = K ssc

R BC +R ct
R BN +R ct

Where Kssc

RBN
RBC
Rct
K'ssc

=
=
=
=
=
=
=
=
=
=

Rated symmetrical short-circuit current factor


KnALF
20
Rated resistive burden of CT (in Ohm)
15
Connected resistive burden (in Ohm)
0.73
CT sec. wdg. resistance (in Ohm)
4
Effective symmetrical short-circuit current factor

Now based on the above formula the 'effective symmetrical short-circuit current factor' is calculated as follows K'ssc
Kssc x [(RBN + Rct) / (RBC + Rct)]
=
=
20 x [(15+4) / (0.73+4)]
=
20 x [19 / 4.73]
=
80.33827
Thus the effective CT ALF
K'ssc
=
80.34
----(5)

Ppd.: AKR
Chkd: AKSM/SRKR

8 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

6.0 Conclusion :
1

From (5) & (6) above, the 'Operating CT ALF' is 80.34 while the 'Required CT ALF' is 63
i.e. As 'Operating CT ALF' > 'Required CT ALF' the selected CT is ACCEPTABLE

2 Summary of CT parameters
CT Ratio : 400/1 A
Class : 5P20
Rct (max.) : 4
Rated Burden: 15

Ohm
VA

Ppd.: AKR
Chkd: AKSM/SRKR

9 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

2.3 CTs FOR DISTANCE PROTECTION - 21


(33kV OHL FEEDERS)
1. System Data
1 System Voltage & Frequency: 33kV, 3Ph, 50Hz, 3 wire (RYB) system
2. CT Data: data as per Schneider
a CT Ratio = 400/1 A; Class X, CT internal burden/resistance : R ct = 5.4 Ohm
b CT magnetizing current = 50mA @ Vk/2
CT primary current

400 CT Sec. Current= 1

CT Class:

5P

ALF:

KnALF

Rated Burden:

PBN

CT int. res.:

Rct <

20

(Assumed)

10 VA
5.4 Ohm

3. Fault level
Sorce fault current

25 kA

If=

for 3 Sec.

4. Feeder Data:
a Cable terminated on to an existing 33kV OHL
33kV Cable particulars: 1runx3Cx300 sq. mm, Cu, XLPE;
= 0.059+0.11j

Impedance zcab

Ohm/km

b 33kV OHL particulars: "PANTHER" ACSR conductor;


= 0.175+0.323j

Impedance zline

Ohm/km

5. Relay Data:
SIEMENS make 7SA522 Distance Protection Relay
(Ref: SIEMENS SIP-2006 Chapter-2, page 53)

II. Calculation of Zone1 Fault Level for 33kV Incomer OHL/UG Cable to MADINAT AL NAHDAH S/s
The existing 33kV Incomer-1 feeder from JEHAT S/S consist of OHL feeder and the proposed 33kV
Incomer-2 feeder from JEHAT s/s consists of 33kV Cable followed by a 33kV OHL. The approximate
lengths are as follows:
Incomer-1
Total Cable length
= 0.4
Total OHL
= 29.1
Ref: Consultant letter EPE-LTO-11/2006-06/071 dt. 11.09.06

km
km

Incomer-2
Total Cable length
Total OHL

= 3.799
= 21.073

Ppd.: AKR
Chkd: AKSM/SRKR

km
km

10 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

(a) Source Impedance Calculations


For Source Impedance for 25kA at JLHAT S/s 33kV Busbars
= 20
33kV System X/R ratio:

..

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

(Assumed)

33kV System L/R ratio: (X/R)s/(2.p.f) = 20/(2xpx50)


= 63.6739891754 msec

33kV Source Impedance (zs):


SCMVA = sqrt(3) x 33 x 25 =

= 1428.94191624 MVA

0.0006998185
zs (in pu) = 1/ SCMVA = [1/1428.942] =
on 33kV & 1MVA Base
zs (in Ohm) = zs (in pu) x 332/1
= (6.9982 x 10-4) x 332/1

pu

= 0.7621023553

Source impedance zs = 0.7621 arctan[(X/R)s]


= 0.7621023553
Source impedance zs

87.14

Ohms

zs = zs x cosq + j.zs x sinq


= 0.7621 x cos(87.13) + j.0.7621 x sin(87.13)
= 0.0381+0.7612j

Ohms

(b) Line & Cable Impedance Calculations


The OHL/UG Cable impedance in Ohm is calculated as follows zcab1 =

zline1 =

(0.059+0.11j) x 0.4
= 2.36E-002+4.4E-002j
61.79
= 0.0499
(0.175+0.323j) x 29.1

= 5.0925+9.3993j
= 10.6902
zcab2 =

zline2 =

61.55

(0.059+0.11j) x 3.799
= 0.224141+0.41789j
61.79
= 0.4742
(0.175+0.323j) x 21.073

= 3.687775+6.806579j
61.55
= 7.7414
Zone1 protection reach envisaged
Z1P = 80% [zcab2 + zline2 +zline1+zcab2]
= 0.8(0.224141+0.41789j + 3.687775+6.806579j + 5.0925+9.3993j + 2.36E-002+4.4E-002j)
= 0.8 x (9.028016+16.667769j)
Ohm
= 7.2224128+13.3342152j

Ppd.: AKR
Chkd: AKSM/SRKR

33/11kV AL NAHDAH PRIMARY SUBSTATION

11 of 88

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

(c) Zone1-end Fault Condition


33/11kV AL NAHDAH PRIMARY SUBSTATION
33kV SWITCHGEAR

(EXISTING)

TO 21
CT-1
400/1A,CL:PS

I/C OHL
0.8xZline1

33kV SOURCE
JEHAT S/S
25kA
ZONE1-END
FAULT

NC
TO 21

I/C OHL

Zs

CABLE

Zline2

CT-2
400/1A,CL:PS

(PROPOSED)

33/11kV AL NAHDAH SUBSTATION BUS


(EXISTING)
CT-1
400/1A,CL:PS

I/C OHL
0.8xZline1

I1

33kV SOURCE
JEHAT S/S
25kA

I2

CLOSE-IN
FAULT

Zs

I1
If=I1+I2
Zline2
I/C OHL

CT-2
400/1A,CL:PS

Zcab2
CABLE

+
(PROPOSED)

For a 3phase fault at the end of the Zone1 reach


Zfault zs
0.0381+0.7612j

I1 0 Amp and I2 If
Thus CT1 (and CT2) will see negligibly low current. This case is therefore not considered for CT sizing.

(d) Close-in Fault Condition

33/11kV AL NAHDAH PRIMARY SUBSTATION


33kV SWITCHGEAR

(EXISTING)

TO 21

I/C OHL
Zline1

CT-1
400/1A,CL:PS

33kV SOURCE
JEHAT S/S
25kA

CLOSE-IN
FAULT

NC
TO 21
CT-2
400/1A,CL:PS

Zs
I/C OHL

Zline2

CABLE
Zcab2

(PROPOSED)

Ppd.: AKR
Chkd: AKSM/SRKR

12 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

33/11kV AL NAHDAH SUBSTATION BUS


(EXISTING)
CT-1
400/1A,CL:PS

I/C OHL
Zline1
33kV SOURCE
JEHAT S/S
25kA

I2
CLOSE-IN
FAULT

Zs
I1
If=I1+I2

CT-2
400/1A,CL:PS

Zline2
I/C OHL

Zcab2
CABLE

(PROPOSED)

Ppd.: AKR
Chkd: AKSM/SRKR

13 of 88

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

33/11kV AL NAHDAH SUBSTATION BUS


(EXISTING)
CT-1
400/1A,CL:PS

I/C OHL
Zline1
33kV SOURCE
JEHAT S/S
25kA

I2
CLOSE-IN
FAULT

Zs
I1
If=I1+I2

CT-2
400/1A,CL:PS

Zline2
I/C OHL

Zcab2
CABLE

(PROPOSED)

For a 3 phase close-in (close to CT1) fault


Zfault (Zf1) =Zs + (Zline2+ Zcab2)
(0.0381+0.7612j) + (0.224141+0.41789j + 3.687775+6.806579j)
3.950016+7.985669j
8.9092

63.68

Zfault (Zf2) =Zs + (Zline1+Zcab1))


(0.0381+0.7612j) + (5.0925+9.3993j) + (2.36E-002+4.4E-002j)
5.1542+10.2045j
11.4323

63.20

Total fault current (If) from the source


If = Vsys / (3 x Zf1)
I1 33*1000 / (3 x8.90918266609328)
63.68
2139
If = Vsys / (3 x Zf2)
I2 33*1000 / (3 x11.4323050121137)
63.20
1667

Thus the max fault current thru CT1 is 2139 A approximately. The CT design knee point voltage shall be such that
the CT does not saturate for this fault current

III. CT knee point calculations based on Relay Manufacturers (SIEMENS) Recommendation


make 33kV Swgr. :Data)
CT internal resistance/burden
R
- Control cable data: 4Cx4 sq. mm, Cu, 1.1kV grade PVC;
50 m
(go & return lengths)
Max. Length = 2x25m =
5.79 Ohm/km
Cable resistance as per Oman Cable Catalogue =
0.2895
Ohm/km
Lead resistance:RL = (50/1000)x 5.79 =
- Relay burden: RB = 0.05VA
SIEMENS
or
7SA522 relay data, refer attached sheets)
Refer attached sheets for SIEMENS recommendations for selection of Knee Point Voltage for distance relay.

Ppd.: AKR
Chkd: AKSM/SRKR

14 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Where;

P BC + Pi
K nALF
K oALF
P BN + Pi

KnALF =
=
KoALF =
PBN =
=
PBC =
=

Nominal CT Accuracy Limiting Factor


20
Actual or operating CT Accuracy Limiting Factor
Nominal Burden of CT
10
(assumed conservatively on lower side)
Connected Burden on CT = (RB + RL)
= 0.3395 Ohm or 0.3395VA on 1A CT secondary.
0.3395
0.3395Ohm or 0.3395 VA on 1A CT Secondary
5.4 Ohm
Pi =
Internal CT Burden =
=
5.4 Ohm or 5.4VA on 1A CT secondary
From the above Actual ALF (KoALF) can be calculated as follows
Now based on the above formula the operating or effective CT accuracy limiting factor is calculated as follows KoALF
[(PBN + Pi) / (PBC + Pi)] x KnALF
=

Thus Operating ALF

KoALF

=
=

[(10+5.4) / (0.3395+5.4)] x 20
54.000

54.000

Thus Actual CT ALF (KoALF) is 54(A)


For SIEMENS 7SA522 distance protection relay Minimum required CT Accuracy Limiting Factor is calculated as
follows

K oALF = a

I SCC . max .( close in

fault )

IN

and
K oALF = b

I SCC . max .( Zone 1 end


IN

fault )

Where;
IN = Nominal Primary CT current (i.e.; equal to 400A)
ISCC.max.(close-in
= Fault
fault) current for close-in faults
= 2139
(refer calculations above)
ISCC.max.(Zone1-end
= Fault
fault)
current at the end of Zone1 reach

= 0 A(refer calculations above)


63.674 msec.
The system time constant is T s =
a = 4 & b = 5 (values for Ts 200 msec)
Thus KoALF can be calculated (for close-in fault condition) as follows K oALF( min) = a

I SCC . max .( closein fault )


IN

4 x (2139/400) =

21.39

Considering an over dimensioning margin, K OF = 5%, the required KoALF is


KoALF =
KOF x KoALF(min)
Ppd.: AKR
Chkd: AKSM/SRKR

15 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

1.05 x 21.39=

22.46

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

.B

From above it is very clear that the Actual CT ALF =54 (refer A) is greater than the Minimum required CT
ALF=22.4595 (refer B), thus the selected CT is acceptable
As per SIEMENS (conversion from IEC60044 definition to BS3938 definition) the required knee point voltage V k for
the connected burden can be approximately calculated as follows
Vk= KoALF (b) x Iscc max(Zone1-end fault) x (Rct + R'b) x Isn
1.3 x Ipn

Vk= ( 5 x 2139x ( 5.4 + 0.3395) x1 ) / (1.3 x400)


= 119
Minimum required knee Point Voltage, Vkph = 119 Volt

IV.
Conclusions / Recommendations.
For 33kV Cable/OHL feeder CT core (for distance protection) shall have the following parameters
Application: 33kV, 3Phase, 50Hz, 3 wire, 25kA/3sec. system;
Distance protection.
CT ratio = 400/1A;
CT Class = Class X;
5.4 Ohm;
Internal CT Burden (in Ohm) =
Magnetizing current: Imag = 50 mA @ Vk/2
119 Volt
Knee Point Voltage: Vk =
The CTs (for distance protection application) offered by 33kV Switchgear manufacturer M/s Schneider have a knee
point voltage = 300 Volt/Ph much greater than that required119 Volt and thus the same is ACCEPTABLE

Ppd.: AKR
Chkd: AKSM/SRKR

16 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Section - 3 : 33kV Transformer Incomer

Ppd.: AKR
Chkd: AKSM/SRKR

17 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

18 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

3.1 CTs for 20MVA Transformer Differential Protection - 87T


(33kV Switchgear Outgoing)
1.0 Relay Proposed
a.
b.
c.
d.

ANSI No.
Make
Model
Type

87T
SIEMENS
7UT6121
Numerical, Differential (Low Imepdance type)

2.0 CT Ratio
11kV Line Side CTs
Voltage Class :
33 kV
Frequency :
50 Hz
Short time rating :
25 kA for 3 sec.
Mounting: CT mounted in 33kV Switchgear
CT Ratio : Core-3
IPN
400
A
Primary
Isn
CT Class:
CT int. res.:
kPV :
Exc. Current:

Secondary
X
5.4 Ohm
300 Volt
50 mA

Rct
Vk
Imag

@ Vk/2

3.0 System Information


System Voltage Vsys
Transformer rating
Transformer Impedance at Principal Tap (%Zpt)
Transformer Impedance at negative tolerance
Transformer full load current
FLC

=
=
=
=
=
=
=

33 kV
20 MVA
12.5 %
10.625 %
(with -ve 15% tolerance)
Trafo. Rating / [sqrt(3) x Vsys]
20MVA / [1.732 x 33kV]
349.91 A

Calculation of Maximum through fault current (Itf), assuming infinite power source
Itf
Vsys
Where
Zlt
Zlt
Where,

MVA(base)
kV(base)
Hence

Zlt

Thus,

Zlt

Hence

Itf-max

Thus

=
=

Vsys / [sqrt(3) x Zlt]


33 kV

=
=
=
=
=
=
=
=

Impedance of the transformer at negative tolerance


(%Zlt/100) x [kV(base)^2 / MVA(base)]
20
MVA
33
kV
(10.625/100) x [(33^2)/20]
0.10625 x (1089/20)
0.10625 x 54.45
5.78
Ohm

=
=
=
=
which is =
Itf-max
=

Vsys / [sqrt(3) x Zlt]


33000 / [1.732 x 5.78]
33000/10.011
3296.29046
Amp
8.241
x CT rated primary current
3296.29046
Amp

4.0 Calculation of Burden connected to the CT Core


4.1 Connected Relays Burden (Rr)
VA Burden of the Relay 64REF

Pr
Rr

=
=

0.1
0.10

Ppd.: AKR
Chkd: AKSM/SRKR

VA at In=1A
Ohm

----(1)

19 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

4.2 Lead Burden (RL)


(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
=
9.30
Ohms/km
Single Lead Length of the cable from BCT to CRP

50

Mtr

Hence 2 way lead Burden

=
=
=
RL =

(2 x Impd. of the cable x 50) / 1000


(2 x 9.3 x 50) / 1000
(930)/1000
0.93
Ohm
----(2)

Hence External Connected Burden


(with 20% margin)

=
=
Rb =

RL
1.116
1.116

Ohm
VA

----(3)

Rct =

5.4

Ohms

----(4)

4.3 CT Burden (Rct)


CT's int. res. 400/1 Tap at 75C

5.0 Calculation of various CT parameters


5.1 Calculation of CT knee point voltage Vk(min) requirement
Trafo. maximum thru fault current on CT primary
Ifs(pri)
=
Hence Ifs(sec)

Min. relay setting voltage (Vstab)

Vstab(min)
Say Selected Setting voltage : Vs
Minimum Knee point voltage Vk(min)
Vk(min)

3296.3 Amp

=
=
=

Ifs(pri) / (400/1)
3296.3/[(400/1)]
8.241 Amp

=
=
=
=
=

Ifs(sec) x (Rct + Rb)


8.241 x (5.4+1.116)
8.241 x (6.516)
53.69836 Volt
65 Volt

=
=
=

2 x Vs
2 x 65
130

On CT Primary side
On CT Secondary side

(with 20% security margin)

Volt
Volt

----(5)

5.2 Calculation of Magnetising Current requirement


The relay setting current corresponding to the relay setting voltage, as per SIEMENS catalogue Ir
=
0.02 A
Relay setting current (including varistor)
Relay setting voltage selected
Vr
= Vs =
65 V
No. of spill (parallel) paths
n
=
3 nos.
Selected CT's Magnetizing Characteristics : (33kV Line Side CTs)
Magnetizing current @ Vk/2
Imag
=
0.05 A
@ Vk/2 (in Volt) = 150
Magnetizing current @ Vs = 65V
Imag1
=
0.0217 A
(since BH curve is linear upto Vk)
The Imag1 for both side CTs is same. The relay operating characteristics shall be checked for these CTs.
Based on the above, the relay operating current can now be calculated as follows Iop
=
Ir + (n x Imag1)
=
0.02 + 3x0.0217
=
0.085 A
On CT primary,
Iop (prim) =
Iop x (Ipn/Isn)
34.0 A
which is =
(Iop (prim) / FLC) x 100
=
(34 / 349.91) x 100
=
9.72 %
or
10% of FLC roughly.

5.3 Calculation of External Series Stabilising Resistance


Relay Impedance
The relay impedance can be calculated as follows relay setting current
Ir
=
relay setting voltage
Vr
=
relay burden
Pr
=
thus relay impedance
Rr
=

0.02 A
(this is a fixed value)
65 Volt
0.1 VA (for Isn = 1A)
Pr / Ir^2
Ppd.: AKR
Chkd: AKSM/SRKR

20 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Rr

250 Ohm

250 Ohm

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

External Stabilising Resistance


The required external series resistance value can be calculated as follows Rst
=
(Vr / Ir) - Rr
=
(65 / 0.02) - 250
=
3000.00
Ohm
Rst
Total relay circuit branch impedance

3000.00

Ohm

=
=

Rst + Rr
3250.00 Ohm

----(6)

6.0 Conclusions & Summary


1.

Conclusion
From (5) above, minimum required CT knee point voltage = 130 Volt

2.

Summary of CT parameters
On Trafo. Line Side
CT Ratio :
Class :
Rct (max.) :
Vk (min.) :
Imag (@ Vk/2) :

3.

400 / 1 A
X
5.4 Ohm
300 Volt
50 mA

Stabilising Resistor Requirement

3000 Ohm

Ppd.: AKR
Chkd: AKSM/SRKR

21 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

3.2 CTs for - 20MVA Transformer Metering


(33kV switchgear Outgoing)
1.0 Meters connected
a.
b.
c.
d.
e

DA
--0.5
1
0.5

Make
Model
VA Burden
Qty. (Nos.)
Net VA

------

2.0 CT Details
CT Ratio
IPN

Core-1
400

ISN

CT Class: 1.0
ISF 10

Primary

A
Secondary
Rated Burden:
15 VA
Voltage (kV): 33
Rated system fault current (in kA & time in sec.) :
25

3 sec.

3.0 Calculation of VA Burden of the CT Core


Sum of the VA Burden of the Meters connected, R m

0.5

VA

----(1)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT to Meters mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
----(2)

=
=
=

Rm + RL
(0.5 + 0.558)
1.058
VA

----(3)

PBC

=
=
=

1.5 x External Burden


(1.5 x 1.058)
2
VA

----(5)

PBN

15
VA
- is sufficient

The external Burden

Hence connected VA to CT Core


(with design margin of 50%)

Hence Selected VA Burden for CT core

30

----(6)

4.0 Conclusion :
1
2

The 'Connected CT burden' is 2 while the 'Rated CT burden' is 15


As 'Rated CT burden' >'Connected CT burden' the selected CT is ACCEPTABLE
Summary of CT parameters
CT Ratio : 400/1 A
Class : 1
Rated Burden : 15
ISF< 10

Ppd.: AKR
Chkd: AKSM/SRKR

22 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

3.3 CTs for 20 MVA Transformer Backup Protection - 50/50N & 51/51N
(33kV Switchgear Outgoing)
1.0 Application
Protection : O/C & E/F Protection (50/50N & 51/51N)

2.0 Relay Proposed


a.
b.
c.

Make
Model
Type

Siemens
7SJ6021
Numerical, IDMTL Type

3.0 CT Details
Voltage Class :
33 kV
Frequency :
50 Hz
Short time rating :
25 kA for 3 sec.
Mounting: CTs are mounted in 33kV sw.gear
CT Ratio : Core-3
Ipn
400 A
Primary
Isn
CT Class:
ALF:
Rated
Burden:
Rct =
Iscc.max =

1 A

Secondary

5P
20
15
4

VA
Ohm
25 kA

4.0 Calculation of VA Burden of the CT Core


Rr =

VA Burden of the Relay (Siemens)

0.05

VA at ISN
----(1)
(Ref. Siemens SIP.2006)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT - Relay mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

CT's internal Resistance (400/1 Tap at 75C) Rct


CT's internal Burden

Connected CT External Burden

=
Pi =

=
=
=

Ppd.: AKR
Chkd: AKSM/SRKR

30

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
----(2)
4

Ohm

(Isn^2) x [Rct]
(1^2) x [4]
4

VA

----(3)

VA

----(4)

(Rr + RL)
(0.05+0.558)
0.608

23 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Hence connected VA to CT Core


(with design margin of 20%)
PBC

=
=
=

1.2 x External Burden


(1.2 x 0.608)
0.73
VA

PBN =

Selected VA Burden for CT core

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

15

VA

- is sufficient

5 Calculation of minimum required 'Accuracy Limit Factor' for the CT:


(refer SIP-2004, Chapter 2, Pg.53)
Minimum required CT symmetrical short-circuit current factor -

K ' ssc 1 max

[(

I highset po int
I pn

, 20

Where K'scc1

minimum required symmetrical short-circuit current factor

Ihigh-set point

=
=
=
=

maximum short-circuit current (in Ampere)


25000
Amp
Nominal CT primary current (in Ampere)
400
Amp

Ipn

Kssc1

=
max[(Ihigh-set point / Ipn), 20]
=
max[(25000 / 400), 20]
=
62.5
Thus the minimum required CT symmetrical short-circuit current factor Kscc1
=
63

----(6)

6 Calculation of operating 'Accuracy Limit Factor' for the CT:

K ' ssc = K ssc

R BC +R ct
R BN +R ct

Where Kssc

RBN
RBC
Rct
K'ssc

=
=
=
=
=
=
=
=
=
=

Rated symmetrical short-circuit current factor


KnALF
20
Rated resistive burden of CT (in Ohm)
15
Connected resistive burden (in Ohm)
0.73
CT sec. wdg. resistance (in Ohm)
4
Effective symmetrical short-circuit current factor

Now based on the above formula the 'effective symmetrical short-circuit current factor' is calculated as follows K'ssc
Kssc x [(RBN + Rct) / (RBC + Rct)]
=
=
20 x [(15+4) / (0.73+4)]
=
20 x [19 / 4.73]
=
80.33827
Thus the effective CT ALF
K'ssc
=
80.34
----(5)

Ppd.: AKR
Chkd: AKSM/SRKR

24 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

6.0 Conclusion :
1

From (5) & (6) above, the 'Operating CT ALF' is 80.34 while the 'Required CT ALF' is 63
i.e. As 'Operating CT ALF' > 'Required CT ALF' the selected CT is ACCEPTABLE

2 Summary of CT parameters
CT Ratio : 400/1
Class : 5P20
Rct (max.) : 4
Rated Burden: 15

Ohm
VA

Ppd.: AKR
Chkd: AKSM/SRKR

25 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

3.4 CTs for Bus coupler Backup Protection - 51/51N


(33kV Switchgear)
1.0 Application
Protection : O/C & E/F Protection ( 51/51N)

2.0 Relay Proposed


a.
b.
c.

Make
Model
Type

Siemens
7SJ6021
Numerical, IDMTL Type

3.0 CT Details
Voltage Class :
33 kV
Frequency :
50 Hz
Short time rating :
25 kA for 3 sec.
Mounting: CTs are mounted in 33kV sw.gear
CT Ratio : Core-2
Ipn
1200 A
Primary
Isn
CT Class:
ALF:
Rated
Burden:
Rct =
Iscc.max =

1 A

Secondary

5P
10
15
4

VA
Ohm
25 kA

4.0 Calculation of VA Burden of the CT Core


Rr =

VA Burden of the Relay (Siemens)

0.05

VA at ISN
----(1)
(Ref. Siemens SIP.2006)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT - Relay mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

CT's internal Resistance (1200/1 Tap at 75C) Rct


CT's internal Burden

Connected CT External Burden

=
Pi =

=
=
=

Ppd.: AKR
Chkd: AKSM/SRKR

30

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
----(2)
4

Ohm

(Isn^2) x [Rct]
(1^2) x [4]
4

VA

----(3)

VA

----(4)

(Rr + RL)
(0.05+0.558)
0.608

26 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Hence connected VA to CT Core


(with design margin of 20%)
PBC

=
=
=

1.2 x External Burden


(1.2 x 0.608)
0.73
VA

PBN =

Selected VA Burden for CT core

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

15

VA

- is sufficient

5 Calculation of minimum required 'Accuracy Limit Factor' for the CT:


(refer SIP-2004, Chapter 2, Pg.53)
Minimum required CT symmetrical short-circuit current factor -

K ' ssc 1 max

[(

I highset po int
I pn

, 20

Where K'scc1

minimum required symmetrical short-circuit current factor

Ihigh-set point

=
=
=
=

maximum short-circuit current (in Ampere)


25000
Amp
Nominal CT primary current (in Ampere)
1200
Amp

Ipn

Kssc1

=
max[(Ihigh-set point / Ipn), 20]
=
max[(25000 / 1200), 20]
=
20.8
Thus the minimum required CT symmetrical short-circuit current factor Kscc1
=
21

----(6)

6 Calculation of operating 'Accuracy Limit Factor' for the CT:

K ' ssc = K ssc

R BC +R ct
R BN +R ct

Where Kssc

RBN
RBC
Rct
K'ssc

=
=
=
=
=
=
=
=
=
=

Rated symmetrical short-circuit current factor


KnALF
10
Rated resistive burden of CT (in Ohm)
15
Connected resistive burden (in Ohm)
0.73
CT sec. wdg. resistance (in Ohm)
4
Effective symmetrical short-circuit current factor

Now based on the above formula the 'effective symmetrical short-circuit current factor' is calculated as follows K'ssc
Kssc x [(RBN + Rct) / (RBC + Rct)]
=
=
10 x [(15+4) / (0.73+4)]
=
10 x [19 / 4.73]
=
40.16913
Thus the effective CT ALF
K'ssc
=
40.17
----(5)

Ppd.: AKR
Chkd: AKSM/SRKR

27 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

6.0 Conclusion :
1

From (5) & (6) above, the 'Operating CT ALF' is 40.17 while the 'Required CT ALF' is 21
i.e. As 'Operating CT ALF' > 'Required CT ALF' the selected CT is ACCEPTABLE

2 Summary of CT parameters
CT Ratio : 1200/1
Class : 5P10
Rct (max.) : 4
Rated Burden: 15

Ohm
VA

Ppd.: AKR
Chkd: AKSM/SRKR

28 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

3.5 CTs for - Buscoupler Metering


(33kV switchgear)
1.0 Meters connected
a.
b.
c.
d.
e

DA
--0.5
1
0.5

Make
Model
VA Burden
Qty. (Nos.)
Net VA

Ammeter
------

2.0 CT Details
CT Ratio
IPN

1200

ISN

CT Class: 1.0
ISF< 10

Primary

A
Secondary
Rated Burden:
15 VA
Voltage (kV): 33
Rated system fault current (in kA & time in sec.) :
25

3 sec.

3.0 Calculation of VA Burden of the CT Core


Sum of the VA Burden of the Meters connected, R m

0.5

VA

----(1)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT to Meters mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
----(2)

=
=
=

Rm + RL
(0.5 + 0.558)
1.058
VA

----(3)

PBC

=
=
=

1.5 x External Burden


(1.5 x 1.058)
2
VA

----(5)

PBN

15
VA
- is sufficient

The external Burden

Hence connected VA to CT Core


(with design margin of 50%)

Hence Selected VA Burden for CT core

30

----(6)

4.0 Conclusion :
1
2

The 'Connected CT burden' is 2 while the 'Rated CT burden' is 15


As 'Rated CT burden' >'Connected CT burden' the selected CT is ACCEPTABLE
Summary of CT parameters
CT Ratio : 1200/1 A
Class : 1
Rated Burden : 15
ISF< 10

Ppd.: AKR
Chkd: AKSM/SRKR

29 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Section - 4 :33 kV PT

Ppd.: AKR
Chkd: AKSM/SRKR

30 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

31 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

4.1 PT for Incomer line feeders PT


(33kV Switchgear)
1.0 Application
Metering and protection

2.0 PT Ratio & Details


Ratio
33000/3

Cl

VPN

Unit
V

Connection
Star

Location
Primary

VSN

110/3

Cl: 1.0

Star

Secondary

VSN

110/3

Cl: 3P

Open delta

Secondary

3.0 Lead Burden


(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Reactance of 2.5sqmm Cable at 70C
0.111
Ohms/km
Hence Impedance of 2.5Sqmm Cable
:
SQRT[(9.3^2)+(0.111^2)]
=
SQRT[86.49+0.012321]
=
SQRT[86.502321]
=
9.30066
Ohms/km
Single Lead Length of the VT cable from 33kV Swgr to 33kV
Protection / Control / Metering Panel
=
Hence 2 way Lead impedance of the cable

=
=
=
=

50

Mtr

[2 x Impd. of the cable x 50 / 1000]


[2 x 9.30066 x 50 / 1000]
0.930066
0.930066
Ohms
----(1)

4.0 VA Burden for Protection VT Core


4.1 Details of Relays burden connected to VT core
Slno

Relay

Make

Model

67/67N - Back
up directional
Protection

SIEMENS

7SJ6211

0.2

0.6

Neutral
displacement
relay

SIEMENS

7SJ600

0.1

0.3

Burden

0.9

Connected 3ph Burden


Connected Relays Resistance
Lead Resistance of cable
Hence total Resistance in VT circuit

=
=
=
=

Current through the VT Circuit


Hence Lead cable's 3Ph VA Burden

=
=

Hence total burden on VT core

=
=

0.9
4481.481
0.930066
4482.412

VA
Ohms
Ohms
Ohm

0.0081801205 Amps
0.0001867043 VA

4481.481

----(2)

(Ph-N)

----(3)

(2) + (3)
0.9001867043 VA

With 20% Design Margin required VA Burden =


Selected VA Burden of VT Core

Quantity
(No)

Ohmic
Net 3 Ph VA
Impedance
burden on
value (Ohm)
VT Core
(Ph-N)

VA/Ph Burden
in VT Circuit

1.0802240452 VA
=

100 VA & Hence sufficient

Ppd.: AKR
Chkd: AKSM/SRKR

32 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

33 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

5.0 VA Burden for Main Metering VT Core


5.1 Details of Meter burden connected to VT core
Slno

Meter

Make

Model

Voltmeter
Voltage
transducer
Frequency
transducer
MW
Transducer
MVAR
Transducer

0.5

1.5

0.5

1.5

0.00134

0.00403

0.00134

0.00403

Burden

6.00806667

2
3
4
5

Connected 3ph Burden


Connected Metering Resistance
Lead Resistance of cable
Hence total Resistance in VT circuit

=
=
=
=

6.0080666667
671.320
0.930066
672.250

Current through the VT Circuit


Hence Lead cable's 3Ph VA Burden

=
=

0.0944716319 Amps
0.0249022081 VA

Hence total burden on VT core

=
=

Selected VA Burden of VT Core

VA
Ohms
Ohms
Ohm

671.320

----(4)

(Ph-N)

----(5)

(4) + (5)
6.0329688747 VA

With 20% Design Margin required VA Burden =

6.0

Quantity
(No)

Ohmic
Net 3 Ph VA
Impedance
burden on
value (Ohm)
VT Core
(Ph-N)

VA/Ph Burden
in VT Circuit

7.2395626497 VA
=

100 VA & Hence sufficient

Recommended 33kV Switchgear PT Details for 33kV Incomers


Application
Protection
Core
Metering
Core

Primary
voltage (VPN)

Secondary
voltage (VSN)

Connection

Class

VA Burden

110/3

Open Delta

3P

100

110/3

Star

1.0

100

33000/3

Ppd.: AKR
Chkd: AKSM/SRKR

34 of 88

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

4.2 Bus PT
(33kV Switchgear)
1.0 Application
Metering and protection
2.0 PT Ratio & Details
Ratio

Cl

VPN

33000/3

VSN

110/3

Cl: 1.0

VSN

110/3

Cl: 1.0

Unit

Connection

Location

Star

Primary

Star

Secondary

Star

Secondary

3.0 Lead Burden


(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Reactance of 2.5sqmm Cable at 70C
0.111
Ohms/km
Hence Impedance of 2.5Sqmm Cable
:
SQRT[(9.3^2)+(0.111^2)]
=
SQRT[86.49+0.012321]
=
SQRT[86.502321]
=
9.30066
Ohms/km
Single Lead Length of the VT cable from 33kV Swgr
to 33kV Protection Panel / Control panel
=
Hence 2 way Lead impedance of the cable

50

=
=
=
=

Mtr

[2 x Impd. of the cable x 50 / 1000]


[2 x 9.30066 x 50 / 1000]
0.930066
0.930066
Ohms
----(1)

4.0 VA Burden for Protection VT Core


As of now no protection realy is envisaged in Bus PR Protection Core. However, for future use the VA Burden of the
same is chosen as
Selected VA Burden of VT Core
=
100 VA
5.0 VA Burden for Metering VT Core
5.1 Details of Meters burden connected to VT core
Slno

Meter

Make

Model

Voltmeter

Frequency
transducer

0.5

1.5

Voltage
transducer

0.5

1.5

MW Transducer

0.00134

0.00403

MVAR
Transducer

0.00134

0.00403

Burden

9.00806667

Connected 3ph Burden


Connected Metering Resistance
Lead Resistance of cable
Hence total Resistance in VT circuit
Current through the VT Circuit
Hence Lead cable's 3Ph VA Burden

=
=
=
=
=
=

9.0080666667
447.747
0.930066
448.677
0.1415462431
0.0559025626

Ppd.: AKR
Chkd: AKSM/SRKR

Quantity
(No)

Ohmic
Net 3 Ph
Impedance
VA burden
value (Ohm)
on VT Core
(Ph-N)

VA/Ph Burden
in VT Circuit

VA
Ohms
Ohms
Ohm
Amps
VA

447.747

----(2)

(Ph-N)
----(3)

35 of 88

Hence total burden on VT core

=
=

(2) + (3)
9.0639692293 VA

With 20% Design Margin required VA Burden =


Selected VA Burden of VT Core
6.0

Doc. No.:11/2006/MAN/E/007/A4
Rev.2
Date: 09.11.2006

Proj.: MADINAT AL NAHDAH PH-7 PR.S/S


Doc.: 33kV Current/Voltage Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

10.8767630752 VA
=

100 VA & Hence sufficient

Recommended PT Details for 33kV Bus PTs in 33kV Switchgears


Application
Protection
Core
Metering
Core

Primary
voltage (VPN)

Secondary
voltage (VSN)

Connection

Class

VA Burden

110/3

Star

3P

100

110/3

Open Delta

1.0

100

33000/3

Ppd.: AKR
Chkd: AKSM/SRKR

36 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Section - 5 : 11kV Transformer Incomer

Ppd.: AKR
Chkd: AKSM/SRKR

Page 37 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 38 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

DDoc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

5.1 CTs for - Metering


(20 MVA Transformer feeder in 11kV switchgear)
1.0 Meters connected
a.
b.
c.
d.
e

DA
--0.5
1
0.5

Make
Model
VA Burden
Qty. (Nos.)
Net VA

------

2.0 CT Details
CT Ratio
IPN

Core-4
1200

ISN

CT Class: 1.0
ISF< 10

Primary

A
Secondary
Rated Burden:
15 VA
Voltage (kV): 11
Rated system fault current (in kA & time in sec.) :
18.5

3 sec.

3.0 Calculation of VA Burden of the CT Core


Sum of the VA Burden of the Meters connected, R m

0.5

VA

----(1)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT to Meters mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
----(2)

=
=
=

Rm + RL
(0.5 + 0.558)
1.058
VA

----(3)

PBC

=
=
=

1.5 x External Burden


(1.5 x 1.058)
2
VA

----(5)

PBN

15
VA
- is sufficient

The external Burden

Hence connected VA to CT Core


(with design margin of 50%)

Hence Selected VA Burden for CT core

30

----(6)

4.0 Conclusion :
1
2

The 'Connected CT burden' is 2 while the 'Rated CT burden' is 15


As 'Rated CT burden' >'Connected CT burden' the selected CT is ACCEPTABLE
Summary of CT parameters
CT Ratio : 1200/1 A
Class : 1
Rated Burden : 15
ISF< 10

Ppd.: AKR
Chkd: AKSM/SRKR

Page 39 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

5.2 CTs for Backup Protection - 67/51


(20MVA Transformer feeder in 11kV sw.gear)
1.0 Relay Proposed
a.
b.
c.

Make
Model
Type

Siemens
7SJ6021
Numerical,Dir. OC & EF IDMTL Type

2 CT Details
Voltage Class :
11 kV
Frequency :
50 Hz
Short time rating :
18.5 kA for 3 sec.
Mounting: CTs are mounted in 11kV Switchgear Cubicle.
CT Ratio : Core - 3
Ipn
1200
A
Primary
Isn
CT Class:
ALF
Rated
Burden:
Rct =
Iscc.max =

Secondary

5P
10
15
5

VA
Ohm
18.5 kA

3 Calculation of VA Burden of the CT Core


Rr =

VA Burden of the Relay (7SJ6021)

0.1

VA at ISN
(Ref Ch.5, Pg. 41 : Siemens
SIP 2006)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT - Relay mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

CT's internal Resistance(1200/1 Tap at 75C) Rct


CT's internal Burden

=
Pi =

The external Rated Burden

Hence connected VA to CT Core


(with design margin of 20%)
PBC

30

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
5

Ohm

(Isn^2) x [Rct]
(1^2) x [5]
5

VA

(Rr + RL)

=
=
=

(0.1+0.558)
0.658

=
=
=

1.2 x External Burden


(1.2 x 0.658)
0.79
VA

Ppd.: AKR
Chkd: AKSM/SRKR

VA

Page 40 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 41 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

PBN =

Selected VA Burden for CT core

15

5 Calculation of CT 'Required Accuracy Limiting Factor'

VA

- is sufficient

(refer SIP-2004, Chapter 2, Pg.53)

Minimum required CT symmetrical short-circuit current factor -

K ' ssc 1 max

[(

I highset po int
I pn

, 20

Where K'scc1

minimum required symmetrical short-circuit current factor

Ihigh-set point

=
=
=
=

maximum short-circuit current (in Ampere)


18500
Amp
Nominal CT primary current (in Ampere)
1200
Amp

Ipn

Kssc1

=
max[(Ihigh-set point / Ipn), 20]
=
max[(18500 / 1200), 20]
=
20.00000
Thus the minimum required CT symmetrical short-circuit current factor Kscc1
=
20

6 Calculation of CT 'Operating Accuracy Limiting Factor'

K ' ssc = K ssc

R BC +R ct
R BN +R ct

Where Kssc

RBN
RBC
Rct
K'ssc

=
=
=
=
=
=
=
=
=
=

Rated symmetrical short-circuit current factor


KnALF
15
Rated resistive burden of CT (in Ohm)
15
Connected resistive burden (in Ohm)
0.79
CT sec. wdg. resistance (in Ohm)
5
Effective symmetrical short-circuit current factor

Now based on the above formula the 'effective symmetrical short-circuit current factor' is calculated as follows K'ssc
Kssc x [(RBN + Rct) / (RBC + Rct)]
=
=
15 x [(15+5) / (0.79+5)]
=
15 x [20 / 5.79]
=
51.81347
Thus the Operating CT ALF
K'ssc
=
51.82

Ppd.: AKR
Chkd: AKSM/SRKR

Page 42 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

6.0 Conclusion :
1

From (5) & (6) above, the 'Operating CT ALF' is 51.82 while the 'Required CT ALF' is 20
i.e. As 'Operating CT ALF' > 'Required CT ALF' the selected CT is ACCEPTABLE

2 Summary of CT parameters
CT Ratio : 1200/1 A
Class : 5P10
Rct (max.) : 5
Rated Burden: 15

Ohm
VA

Ppd.: AKR
Chkd: AKSM/SRKR

Page 43 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

or Backup Protection - 67/51


former feeder in 11kV sw.gear)

----(1)
(Ref Ch.5, Pg. 41 : Siemens

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]

----(2)

----(3)

----(4)

Ppd.: AKR
Chkd: AKSM/SRKR

Page 44 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 45 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

- is sufficient

minimum required symmetrical short-circuit current factor

----(6)

tive symmetrical short-circuit current factor' is calculated as follows -

----(5)

Ppd.: AKR
Chkd: AKSM/SRKR

Page 46 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 47 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

5.3 CTs for Transformer Restricted Earth Fault Protection - 64REF


(20MVA Transformer in 11kV Switchgear)
1.0 Relay Proposed
a.
b.
c.
d.

ANSI No.
Make
Model
Type

64REF
SIEMENS
7SJ6022
Numerical, REF (High Imepdance type)

2.0 CT Ratio
11kV Line Side CTs
Voltage Class :
11 kV
Frequency :
50 Hz
Short time rating :
18.5 kA for 3 sec.
Mounting: CT mounted in 11kV Switchgear
CT Ratio : Core-2
IPN
1200
A
Primary
Isn
CT Class:
CT int. res.:
kPV :
Exc. Current:

Secondary
X
6 Ohm
200 Volt
40 mA

Rct
Vk
Imag

@ Vk/2

15MVA Trafo. HV Neutral Side CT


Voltage Class :
11 kV
Frequency :
50 Hz
Short time rating :
18.5 kA for 3 sec.
Mounting: CT mounted in 11kV Side Trafo. Bushing
CT Ratio : Core - 2
IPN
1200
A
Primary
Isn

CT Class:

Secondary
X
6 Ohm
200 Volt
40 mA

Rct
Vk
Imag

(same as that for 11kV line side CTs)


(same as that for 11kV line side CTs)
@ Vk/2

3.0 System Information


System Voltage Vsys
Transformer rating
Transformer Impedance at Principal Tap (%Zpt)
Transformer Impedance at negative tolerance
Transformer full load current
FLC

=
=
=
=
=
=
=

11 kV
20 MVA
12.5 %
10.625 %
(with -ve 15% tolerance)
Trafo. Rating / [sqrt(3) x Vsys]
20MVA / [1.732 x 11kV]
1049.73 A

Calculation of Maximum through fault current (Itf), assuming infinite power source
Itf
Vsys
Where
Zlt
Zlt
Where,

MVA(base)
kV(base)
Hence

Zlt

Thus,

Zlt

=
=

Vsys / [sqrt(3) x Zlt]


11 kV

=
=
=
=
=
=
=
=

Impedance of the transformer at negative tolerance


(%Zlt/100) x [kV(base)^2 / MVA(base)]
20
MVA
11
kV
(10.625/100) x [(11^2)/20]
0.10625 x (121/20)
0.10625 x 6.05
0.64
Ohm

Ppd.: AKR
Chkd: AKSM/SRKR

Page 48 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Hence

Itf-max

=
=
=
=
which is =
Itf-max
=

Thus

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Vsys / [sqrt(3) x Zlt]


11000 / [1.732 x 0.64]
11000/1.109
9923.20775
Amp
8.269
x CT rated primary current
9923.20775
Amp

4.0 Calculation of Burden connected to the CT Core


4.1 Connected Relays Burden (Rr)
VA Burden of the Relay 64REF

Pr
Rr

=
=

0.1
0.10

VA at In=1A
Ohm

----(1)

4.2 Lead Burden (RL)


(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
=
9.30
Ohms/km
Single Lead Length of the cable from BCT to CRP

50

Mtr

Hence 2 way lead Burden

=
=
=
RL =

(2 x Impd. of the cable x 50) / 1000


(2 x 9.3 x 50) / 1000
(930)/1000
0.93
Ohm
----(2)

Hence External Connected Burden


(with 20% margin)

=
=
Rb =

RL
1.116
1.116

Ohm
VA

----(3)

Rct =

Ohms

----(4)

4.3 CT Burden (Rct)


CT's int. res. 1200/1 Tap at 75C

5.0 Calculation of various CT parameters


5.1 Calculation of CT knee point voltage Vk(min) requirement
Trafo. maximum thru fault current on CT primary
Ifs(pri)
=
Hence Ifs(sec)

Min. relay setting voltage (Vstab)

Vstab(min)
Say Selected Setting voltage : Vs
Minimum Knee point voltage Vk(min)
Vk(min)

9923.2 Amp

=
=
=

Ifs(pri) / (1200/1)
9923.2/[(1200/1)]
8.270 Amp

=
=
=
=
=

Ifs(sec) x (Rct + Rb)


8.27 x (6+1.116)
8.27 x (7.116)
58.84932 Volt
71 Volt

=
=
=

2 x Vs
2 x 71
142

On CT Primary side
On CT Secondary side

(with 20% security margin)

Volt
Volt

----(5)

5.2 Calculation of Magnetising Current requirement


The relay setting current corresponding to the relay setting voltage, as per SIEMENS catalogue Ir
=
0.02 A
Relay setting current (including varistor)
Relay setting voltage selected
Vr
= Vs =
71 V
No. of spill (parallel) paths
n
=
4 nos.
Selected CT's Magnetizing Characteristics : (11kV Line Side CTs)
Magnetizing current @ Vk/2
Imag
=
0.04 A
@ Vk/2 (in Volt) = 100
Magnetizing current @ Vs = 71V
Imag1
=
0.0284 A
(since BH curve is linear upto Vk)
Selected CT's Magnetizing Characteristics : (Zigzag Trafo. 11kV HV side neutral BCT)
Magnetizing current @ Vk/2
Imag
=
0.04 A
@ Vk/2 (in Volt) =
100
Magnetizing current @ Vs = 71V
Imag1
=
0.0284 A
(since BH curve is linear upto Vk)

Ppd.: AKR
Chkd: AKSM/SRKR

Page 49 of 88

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

The Imag1 for both side CTs is same. The relay operating characteristics shall be checked for these CTs.
Based on the above, the relay operating current can now be calculated as follows Iop
=
Ir + (n x Imag1)
=
0.02 + 4x0.0284
=
0.134 A
On CT primary,
Iop (prim) =
Iop x (Ipn/Isn)
160.3 A
which is =
(Iop (prim) / FLC) x 100
=
(160.32 / 1049.73) x 100
=
15.28 %
or
16% of FLC roughly.
Normally REF setting is between 10-60% FLC is enough for satisfactory operation.

5.3 Calculation of External Series Stabilising Resistance


Relay Impedance
The relay impedance can be calculated as follows relay setting current
Ir
=
relay setting voltage
Vr
=
relay burden
Pr
=
thus relay impedance
Rr
=
=
Rr

0.02
71
0.1
Pr / Ir^2
250

A
(this is a fixed value)
Volt
VA (for Isn = 1A)
Ohm

250 Ohm

External Stabilising Resistance


The required external series resistance value can be calculated as follows Rst
=
(Vr / Ir) - Rr
=
(71 / 0.02) - 250
=
3300.00
Ohm
Rst
Total relay circuit branch impedance

3300.00

Ohm

=
=

Rst + Rr
3550.00 Ohm

----(6)

5.4 Checks for Requirement of Varistor (non-linear shunt resistor) & Calculation of Parameters
As per SIEMENS CT Sizing recommendation for REF - High Impedance Application,
Maximum voltage for internal fault Vpk = 2 x sqrt([2xVk(min) x (Vfs-Vk(min))]

Vfs

Max. theoretical voltage across the relay circuit in case of internal fault
[Itf-max / (Ipn/Isn)] x (Rct + Rb + Rst + Rr)
[9923.20775 / (1200/1) ] x (6 + 1.116 + 3300 + 250)
Volt
29415

Hence Vpk

5766.63932 Volt

Vfs

Thus,

>

2kV, hence varistor REQUIRED.

6.0 Conclusions & Summary


1.

Conclusion
From (5) above, minimum required CT knee point voltage = 142 Volt

2.

Summary of CT parameters
On Trafo. Line Side
CT Ratio : 1200 / 1 A
Class :
X
Rct (max.) :
6 Ohm
Vk (min.) :
200 Volt
Imag (@ Vk/2) :
40 mA
On Trafo. Neutral Side
CT Ratio : 1200 / 1 A
Class :
X
Rct (max.) :
6 Ohm
Vk (min.) :
200 Volt
Imag (@ Vk/2) :
40 mA

3.

Stabilising Resistor Requirement

3300 Ohm

4.

Varistor (non-linear shunt resistor)

Required :

Yes

Ppd.: AKR
Chkd: AKSM/SRKR

Page 50 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

5.4 CTs for 20MVA Transformer Differential Protection - 87T


(33kV Switchgear Outgoing)
1.0 Relay Proposed
a.
b.
c.
d.

ANSI No.
Make
Model
Type

87T
SIEMENS
7UT6121
Numerical, Differential (Low Imepdance type)

2.0 CT Ratio
11kV Line Side CTs
Voltage Class :
11 kV
Frequency :
50 Hz
Short time rating :
18.5 kA for 3 sec.
Mounting: CT mounted in 11kV Switchgear
CT Ratio : Core-1
IPN
1200
A
Primary
Isn
CT Class:
CT int. res.:
kPV :
Exc. Current:

Secondary
X
7 Ohm
250 Volt
40 mA

Rct
Vk
Imag

@ Vk/2

3.0 System Information


System Voltage Vsys
Transformer rating
Transformer Impedance at Principal Tap (%Zpt)
Transformer Impedance at negative tolerance
Transformer full load current
FLC

=
=
=
=
=
=
=

11 kV
20 MVA
12.5 %
10.625 %
(with -ve 15% tolerance)
Trafo. Rating / [sqrt(3) x Vsys]
20MVA / [1.732 x 11kV]
1049.73 A

Calculation of Maximum through fault current (Itf), assuming infinite power source
Itf
Vsys
Where
Zlt
Zlt
Where,

MVA(base)
kV(base)
Hence

Zlt

Thus,

Zlt

Hence

Itf-max

Thus

=
=

Vsys / [sqrt(3) x Zlt]


11 kV

=
=
=
=
=
=
=
=

Impedance of the transformer at negative tolerance


(%Zlt/100) x [kV(base)^2 / MVA(base)]
20
MVA
11
kV
(10.625/100) x [(11^2)/20]
0.10625 x (121/20)
0.10625 x 6.05
0.64
Ohm

=
=
=
=
which is =
Itf-max
=

Vsys / [sqrt(3) x Zlt]


11000 / [1.732 x 0.64]
11000/1.109
9923.20775
Amp
8.269
x CT rated primary current
9923.20775
Amp

Ppd.: AKR
Chkd: AKSM/SRKR

Page 51 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

4.0 Calculation of Burden connected to the CT Core


4.1 Connected Relays Burden (Rr)
VA Burden of the Relay 64REF

Pr
Rr

=
=

0.1
0.10

VA at In=1A
Ohm

----(1)

4.2 Lead Burden (RL)


(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
=
9.30
Ohms/km
Single Lead Length of the cable from BCT to CRP

50

Mtr

Hence 2 way lead Burden

=
=
=
RL =

(2 x Impd. of the cable x 50) / 1000


(2 x 9.3 x 50) / 1000
(930)/1000
0.93
Ohm
----(2)

Hence External Connected Burden


(with 20% margin)

=
=
Rb =

RL
1.116
1.116

Ohm
VA

----(3)

Rct =

Ohms

----(4)

4.3 CT Burden (Rct)


CT's int. res. 1200/1 Tap at 75C

5.0 Calculation of various CT parameters


5.1 Calculation of CT knee point voltage Vk(min) requirement
Trafo. maximum thru fault current on CT primary
Ifs(pri)
=
Hence Ifs(sec)

Min. relay setting voltage (Vstab)

Vstab(min)
Say Selected Setting voltage : Vs
Minimum Knee point voltage Vk(min)
Vk(min)

9923.2 Amp

=
=
=

Ifs(pri) / (1200/1)
9923.2/[(1200/1)]
8.270 Amp

=
=
=
=
=

Ifs(sec) x (Rct + Rb)


8.27 x (7+1.116)
8.27 x (8.116)
67.11932 Volt
81 Volt

=
=
=

2 x Vs
2 x 81
162

On CT Primary side
On CT Secondary side

(with 20% security margin)

Volt
Volt

----(5)

5.2 Calculation of Magnetising Current requirement


The relay setting current corresponding to the relay setting voltage, as per SIEMENS catalogue Ir
=
0.02 A
Relay setting current (including varistor)
Relay setting voltage selected
Vr
= Vs =
81 V
No. of spill (parallel) paths
n
=
3 nos.
Selected CT's Magnetizing Characteristics : (11kV Line Side CTs)
Magnetizing current @ Vk/2
Imag
=
0.04 A
@ Vk/2 (in Volt) = 125
Magnetizing current @ Vs = 81V
Imag1
=
0.0259 A
(since BH curve is linear upto Vk)
The Imag1 for both side CTs is same. The relay operating characteristics shall be checked for these CTs.
Based on the above, the relay operating current can now be calculated as follows Iop
=
Ir + (n x Imag1)
=
0.02 + 3x0.0259
=
0.098 A
On CT primary,
Iop (prim) =
Iop x (Ipn/Isn)
117.3 A
which is =
(Iop (prim) / FLC) x 100
=
(117.312 / 1049.73) x 100
=
11.18 %
or
12% of FLC roughly.

5.3 Calculation of External Series Stabilising Resistance


Relay Impedance
Ppd.: AKR
Chkd: AKSM/SRKR

Page 52 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

The relay impedance can be calculated as follows relay setting current


Ir
=
relay setting voltage
Vr
=
relay burden
Pr
=
thus relay impedance
Rr
=
=
Rr

0.02
81
0.1
Pr / Ir^2
250

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

A
(this is a fixed value)
Volt
VA (for Isn = 1A)
Ohm

250 Ohm

External Stabilising Resistance


The required external series resistance value can be calculated as follows Rst
=
(Vr / Ir) - Rr
=
(81 / 0.02) - 250
=
3800.00
Ohm
Rst
Total relay circuit branch impedance

3800.00

Ohm

=
=

Rst + Rr
4050.00 Ohm

----(6)

6.0 Conclusions & Summary


1.

Conclusion
From (5) above, minimum required CT knee point voltage = 162 Volt

2.

Summary of CT parameters
On Trafo. Line Side
CT Ratio : 1200 / 1 A
Class :
X
Rct (max.) :
7 Ohm
Vk (min.) :
250 Volt
Imag (@ Vk/2) :
40 mA

3.

Stabilising Resistor Requirement

3800 Ohm

Ppd.: AKR
Chkd: AKSM/SRKR

Page 53 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Section - 6 : 11kV Transformer Outgoing

Ppd.: AKR
Chkd: AKSM/SRKR

Page 54 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 55 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

6.1 CTs for Backup Protection - 50/51


(Outgoing & Capacitor feeder in 11kV sw.gear)
1.0 Relay Proposed
a.
b.
c.

Make
Model
Type

Siemens
7SJ6021
Numerical, IDMTL Type

2 CT Details
Voltage Class :
11 kV
Frequency :
50 Hz
Short time rating :
18.5 kA for 3 sec.
Mounting: CTs are mounted in 11kV Switchgear Cubicle.
CT Ratio : Core - 1
Ipn
400
A
Primary
Isn
CT Class:
ALF
Rated
Burden:
Rct =
Iscc.max =

Secondary

5P
10
15
5

VA
Ohm
18.5 kA

3 Calculation of VA Burden of the CT Core


Rr =

VA Burden of the Relay (7SJ6021)

0.1

VA at ISN
(Ref Ch.5, Pg. 41 : Siemens
SIP 2006)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT - Relay mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

CT's internal Resistance(400/1 Tap at 75C) Rct


CT's internal Burden

=
Pi =

The external Rated Burden

Hence connected VA to CT Core


(with design margin of 20%)
PBC

30

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
5

Ohm

(Isn^2) x [Rct]
(1^2) x [5]
5

VA

(Rr + RL)

=
=
=

(0.1+0.558)
0.658

=
=
=

1.2 x External Burden


(1.2 x 0.658)
0.79
VA

Ppd.: AKR
Chkd: AKSM/SRKR

VA

Page 56 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 57 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

PBN =

Selected VA Burden for CT core

15

5 Calculation of CT 'Required Accuracy Limiting Factor'

VA

- is sufficient

(refer SIP-2004, Chapter 2, Pg.53)

Minimum required CT symmetrical short-circuit current factor -

K ' ssc 1 max

[(

I highset po int
I pn

, 20

Where K'scc1

minimum required symmetrical short-circuit current factor

Ihigh-set point

=
=
=
=

maximum short-circuit current (in Ampere)


18500
Amp
Nominal CT primary current (in Ampere)
400
Amp

Ipn

Kssc1

=
max[(Ihigh-set point / Ipn), 20]
=
max[(18500 / 400), 20]
=
46.25000
Thus the minimum required CT symmetrical short-circuit current factor Kscc1
=
47

6 Calculation of CT 'Operating Accuracy Limiting Factor'

K ' ssc = K ssc

R BC +R ct
R BN +R ct

Where Kssc

RBN
RBC
Rct
K'ssc

=
=
=
=
=
=
=
=
=
=

Rated symmetrical short-circuit current factor


KnALF
15
Rated resistive burden of CT (in Ohm)
15
Connected resistive burden (in Ohm)
0.79
CT sec. wdg. resistance (in Ohm)
5
Effective symmetrical short-circuit current factor

Now based on the above formula the 'effective symmetrical short-circuit current factor' is calculated as follows K'ssc
Kssc x [(RBN + Rct) / (RBC + Rct)]
=
=
15 x [(15+5) / (0.79+5)]
=
15 x [20 / 5.79]
=
51.81347
Thus the Operating CT ALF
K'ssc
=
51.82

Ppd.: AKR
Chkd: AKSM/SRKR

Page 58 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

6.0 Conclusion :
1

From (5) & (6) above, the 'Operating CT ALF' is 51.82 while the 'Required CT ALF' is 47
i.e. As 'Operating CT ALF' > 'Required CT ALF' the selected CT is ACCEPTABLE

2 Summary of CT parameters
CT Ratio : 400/1
Class : 5P10
Rct (max.) : 5
Rated Burden: 15

Ohm
VA

Ppd.: AKR
Chkd: AKSM/SRKR

Page 59 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

or Backup Protection - 50/51


apacitor feeder in 11kV sw.gear)

----(1)
(Ref Ch.5, Pg. 41 : Siemens

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]

----(2)

----(3)

----(4)

Ppd.: AKR
Chkd: AKSM/SRKR

Page 60 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 61 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

- is sufficient

minimum required symmetrical short-circuit current factor

----(6)

tive symmetrical short-circuit current factor' is calculated as follows -

----(5)

Ppd.: AKR
Chkd: AKSM/SRKR

Page 62 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 63 of 88

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

6.2 CTs for - Metering


(Outgoing feeders & Capacitor feeder in 11kV sw.gear)
1.0 Application
Metering

2.0 Meters connected


a.
b.
c.
d.
e

DA
xx
xx
0.5
1
0.5

Make
Model
VA Burden
Qty. (Nos.)
Net VA

3.0 CT Details
CT Ratio
IPN

Core-2
400

ISN

CT Class: 1.0
ISF < 10

Primary

A
Secondary
Rated Burden:
15 VA
Voltage (kV): 11
Rated system fault current (in kA & time in sec.) :
18.5

3 sec.

4.0 Calculation of VA Burden of the CT Core


Sum of the VA Burden of the Meters connected, R m

0.5

VA

----(1)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
=
CT to Meters mounted in Swgr. LV Cubicle & 33kV CRP

50

Hence 2 way Lead Burden of the cable

(Isn^2) x [2 x Impd. of the cable x 50 / 1000]


(1^2) x [2 x 9.3 x 50 / 1000]
(1) x 0.93
0.930
Ohm
----(2)

=
=
=
RL =
=
=
=

Rm + RL
(0.5 + 0.93)
1.430
VA

----(4)

PBC

=
=
=

1.5 x External Burden


(1.5 x 1.43)
3
VA

----(5)

PBN

15
VA
- is sufficient

The external Burden

Hence connected VA to CT Core


(with design margin of 50%)

Hence Selected VA Burden for CT core

Mtr

----(6)

5.0 Conclusion :
The 'Connected CT burden' is 3 while the 'Rated CT burden' is 15
i.e. As 'Rated CT burden' is > 'Connected CT burden' the selected CT is ACCEPTABLE

Ppd.: AKR
Chkd: AKSM/SRKR

Page 64 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

6.3 CTs for Backup Protection - 51/51N


(Bus coupler feeder in 11kV sw.gear)
1.0 Relay Proposed
a.
b.
c.

Make
Model
Type

Siemens
7SJ6021
Numerical, IDMTL Type

2 CT Details
Voltage Class :
11 kV
Frequency :
50 Hz
Short time rating :
18.5 kA for 3 sec.
Mounting: CTs are mounted in 11kV Switchgear Cubicle.
CT Ratio : Core - 1
Ipn
1200
A
Primary
Isn
CT Class:
ALF
Rated
Burden:
Rct =
Iscc.max =

Secondary

5P
10
15
5

VA
Ohm
18.5 kA

3 Calculation of VA Burden of the CT Core


Rr =

VA Burden of the Relay (7SJ6021)

0.1

VA at ISN
(Ref Ch.5, Pg. 41 : Siemens
SIP 2006)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT - Relay mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

CT's internal Resistance(1200/1 Tap at 75C) Rct


CT's internal Burden

=
Pi =

The external Rated Burden

Hence connected VA to CT Core


(with design margin of 20%)
PBC

30

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
5

Ohm

(Isn^2) x [Rct]
(1^2) x [5]
5

VA

(Rr + RL)

=
=
=

(0.1+0.558)
0.658

=
=
=

1.2 x External Burden


(1.2 x 0.658)
0.79
VA

Ppd.: AKR
Chkd: AKSM/SRKR

VA

Page 65 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 66 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

PBN =

Selected VA Burden for CT core

15

5 Calculation of CT 'Required Accuracy Limiting Factor'

VA

- is sufficient

(refer SIP-2004, Chapter 2, Pg.53)

Minimum required CT symmetrical short-circuit current factor -

K ' ssc 1 max

[(

I highset po int
I pn

, 20

Where K'scc1

minimum required symmetrical short-circuit current factor

Ihigh-set point

=
=
=
=

maximum short-circuit current (in Ampere)


18500
Amp
Nominal CT primary current (in Ampere)
1200
Amp

Ipn

Kssc1

=
max[(Ihigh-set point / Ipn), 20]
=
max[(18500 / 1200), 20]
=
20.00000
Thus the minimum required CT symmetrical short-circuit current factor Kscc1
=
20

6 Calculation of CT 'Operating Accuracy Limiting Factor'

K ' ssc = K ssc

R BC +R ct
R BN +R ct

Where Kssc

RBN
RBC
Rct
K'ssc

=
=
=
=
=
=
=
=
=
=

Rated symmetrical short-circuit current factor


KnALF
15
Rated resistive burden of CT (in Ohm)
15
Connected resistive burden (in Ohm)
0.79
CT sec. wdg. resistance (in Ohm)
5
Effective symmetrical short-circuit current factor

Now based on the above formula the 'effective symmetrical short-circuit current factor' is calculated as follows K'ssc
Kssc x [(RBN + Rct) / (RBC + Rct)]
=
=
15 x [(15+5) / (0.79+5)]
=
15 x [20 / 5.79]
=
51.81347
Thus the Operating CT ALF
K'ssc
=
51.82

Ppd.: AKR
Chkd: AKSM/SRKR

Page 67 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

6.0 Conclusion :
1

From (5) & (6) above, the 'Operating CT ALF' is 51.82 while the 'Required CT ALF' is 20
i.e. As 'Operating CT ALF' > 'Required CT ALF' the selected CT is ACCEPTABLE

2 Summary of CT parameters
CT Ratio : 1200/1
Class : 5P10
Rct (max.) : 5
Rated Burden: 15

Ohm
VA

Ppd.: AKR
Chkd: AKSM/SRKR

Page 68 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

r Backup Protection - 51/51N


pler feeder in 11kV sw.gear)

----(1)
(Ref Ch.5, Pg. 41 : Siemens

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]

----(2)

----(3)

----(4)

Ppd.: AKR
Chkd: AKSM/SRKR

Page 69 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 70 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

- is sufficient

minimum required symmetrical short-circuit current factor

----(6)

tive symmetrical short-circuit current factor' is calculated as follows -

----(5)

Ppd.: AKR
Chkd: AKSM/SRKR

Page 71 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 72 of 88

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

6.4 CTs for - Metering


(Bus coupler feeder in 11kV sw.gear)
1.0 Application
Metering

2.0 Meters connected

a.
b.
c.
d.
e

DA (11kV
Swgr.)
xx
xx
0.5
1
0.5

Make
Model
VA Burden
Qty. (Nos.)
Net VA

3.0 CT Details
CT Ratio
IPN

Core-2
1200

ISN

CT Class: 1.0
ISF < 10

Primary

A
Secondary
Rated Burden:
15 VA
Voltage (kV): 11
Rated system fault current (in kA & time in sec.) :
18.5

3 sec.

4.0 Calculation of VA Burden of the CT Core


Sum of the VA Burden of the Meters connected, R m

0.5

VA

----(1)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
=
CT to Meters mounted in Swgr. LV Cubicle & 33kV CRP

50

Hence 2 way Lead Burden of the cable

(Isn^2) x [2 x Impd. of the cable x 50 / 1000]


(1^2) x [2 x 9.3 x 50 / 1000]
(1) x 0.93
0.930
Ohm
----(2)

=
=
=
RL =
=
=
=

Rm + RL
(0.5 + 0.93)
1.430
VA

----(4)

PBC

=
=
=

1.5 x External Burden


(1.5 x 1.43)
3
VA

----(5)

PBN

15
VA
- is sufficient

The external Burden

Hence connected VA to CT Core


(with design margin of 50%)

Hence Selected VA Burden for CT core

Mtr

----(6)

5.0 Conclusion :
The 'Connected CT burden' is 3 while the 'Rated CT burden' is 15
i.e. As 'Rated CT burden' is > 'Connected CT burden' the selected CT is ACCEPTABLE

Ppd.: AKR
Chkd: AKSM/SRKR

Page 73 of 88

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

6.5 CTs for Backup Protection - 50/51N


(500kVA Outgoing feeder in 11kV sw.gear)
1.0 Relay Proposed
a.
b.
c.

Make
Model
Type

Siemens
7SJ6021
Numerical, IDMTL Type

2 CT Details
Voltage Class :
11 kV
Frequency :
50 Hz
Short time rating :
18.5 kA for 3 sec.
Mounting: CTs are mounted in 11kV Switchgear Cubicle.
CT Ratio : Core - 1
Ipn
50
100
A
Primary
Isn
CT Class:
ALF
Rated
Burden:
Rct =
Iscc.max =

Secondary

5P
20
5
2

VA
Ohm
2.5 kA

Note:As per SIEMENS relay 7SJ6021 recommendation - Siemens SIP 3.3-1999 the maximum high set available is
25 times "In". With CT rating In=50A the maximum high set current to which the relay will sense is 25 x 50= 1250A.
For fast pick-up time the the curr

3 Calculation of VA Burden of the CT Core


Rr =

VA Burden of the Relay (7SJ6021)

0.1

VA at ISN
(Ref Ch.5, Pg. 41 : Siemens
SIP 2006)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
CT - Relay mounted in 33kV CRP

Hence 2 way Lead Burden of the cable

=
=
=
RL =

CT's internal Resistance(50/1 Tap at 75C) Rct


CT's internal Burden

The external Rated Burden

=
Pi =

=
=
=
Ppd.: AKR
Chkd: AKSM/SRKR

30

Mtr

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]


(1^2) x [2 x 9.3 x 30 / 1000]
(1) x 0.558
0.558
Ohm
2

Ohm

(Isn^2) x [Rct]
(1^2) x [2]
2

VA

(Rr + RL)
(0.1+0.558)
0.658

VA
Page 74 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 75 of 88

Larsen & Toubro (Oman) LLC

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Hence connected VA to CT Core


(with design margin of 20%)
PBC

=
=
=

1.2 x External Burden


(1.2 x 0.658)
0.79
VA

PBN =

Selected VA Burden for CT core

5 Calculation of CT 'Required Accuracy Limiting Factor'

VA

- is sufficient

(refer SIP-2004, Chapter 2, Pg.53)

Minimum required CT symmetrical short-circuit current factor -

K ' ssc 1 max

[(

I highset po int
I pn

, 20

Where K'scc1

minimum required symmetrical short-circuit current factor

Ihigh-set point

=
=
=
=

maximum short-circuit current (in Ampere)


2500
Amp
Nominal CT primary current (in Ampere)
50
Amp

Ipn

Kssc1

=
max[(Ihigh-set point / Ipn), 20]
=
max[(2500 / 50), 20]
=
50.00000
Thus the minimum required CT symmetrical short-circuit current factor Kscc1
=
50

6 Calculation of CT 'Operating Accuracy Limiting Factor'

R BC +R ct
K ' ssc = K ssc
R BN +R ct

Where Kssc

RBN
RBC
Rct
K'ssc

=
=
=
=
=
=
=
=
=
=

Rated symmetrical short-circuit current factor


KnALF
20
Rated resistive burden of CT (in Ohm)
5
Connected resistive burden (in Ohm)
0.79
CT sec. wdg. resistance (in Ohm)
2
Effective symmetrical short-circuit current factor

Now based on the above formula the 'effective symmetrical short-circuit current factor' is calculated as follows K'ssc
Kssc x [(RBN + Rct) / (RBC + Rct)]
=
=
=
=

20 x [(5+2) / (0.79+2)]
20 x [7 / 2.79]
50.17921

50.18

Thus the Operating CT ALF


K'ssc

Ppd.: AKR
Chkd: AKSM/SRKR

Page 76 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

6.0 Conclusion :
1

From (5) & (6) above, the 'Operating CT ALF' is 50.18 while the 'Required CT ALF' is 50
i.e. As 'Operating CT ALF' > 'Required CT ALF' the selected CT is ACCEPTABLE

2 Summary of CT parameters
CT Ratio : 50-100/1
Class : 5P20
Rct (max.) : 2
Rated Burden: 5

Ohm
VA

Ppd.: AKR
Chkd: AKSM/SRKR

Page 77 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

r Backup Protection - 50/51N


going feeder in 11kV sw.gear)

mmendation - Siemens SIP 3.3-1999 the maximum high set available is


aximum high set current to which the relay will sense is 25 x 50= 1250A.

----(1)
(Ref Ch.5, Pg. 41 : Siemens

(Isn^2) x [2 x Impd. of the cable x 30 / 1000]

----(2)

----(3)

----(4)
Ppd.: AKR
Chkd: AKSM/SRKR

Page 78 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 79 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

- is sufficient

minimum required symmetrical short-circuit current factor

----(6)

tive symmetrical short-circuit current factor' is calculated as follows -

----(5)

Ppd.: AKR
Chkd: AKSM/SRKR

Page 80 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 81 of 88

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

6.6 CTs for - Metering


(500kVA Outgoing feeder in 11kV sw.gear)
1.0 Application
Metering

2.0 Meters connected

a.
b.
c.
d.
e

DA (11kV
Swgr.)
xx
xx
0.5
1
0.5

Make
Model
VA Burden
Qty. (Nos.)
Net VA

3.0 CT Details
CT Ratio
IPN

Core-1
50

ISN

CT Class: 1.0
ISF < 10

100

Primary

1
A
Secondary
Rated Burden:
15 VA
Voltage (kV): 11
Rated system fault current (in kA & time in sec.) :
18.5

3 sec.

4.0 Calculation of VA Burden of the CT Core


Sum of the VA Burden of the Meters connected, R m

0.5

VA

----(1)

Lead Burden
(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Single Lead Length of the cable from
=
CT to Meters mounted in Swgr. LV Cubicle & 33kV CRP

50

Hence 2 way Lead Burden of the cable

(Isn^2) x [2 x Impd. of the cable x 50 / 1000]


(1^2) x [2 x 9.3 x 50 / 1000]
(1) x 0.93
0.930
Ohm
----(2)

=
=
=
RL =
=
=
=

Rm + RL
(0.5 + 0.93)
1.430
VA

----(4)

PBC

=
=
=

1.5 x External Burden


(1.5 x 1.43)
3
VA

----(5)

PBN

15
VA
- is sufficient

The external Burden

Hence connected VA to CT Core


(with design margin of 50%)

Hence Selected VA Burden for CT core

Mtr

----(6)

5.0 Conclusion :
The 'Connected CT burden' is 3 while the 'Rated CT burden' is 15
i.e. As 'Rated CT burden' is > 'Connected CT burden' the selected CT is ACCEPTABLE

Ppd.: AKR
Chkd: AKSM/SRKR

Page 82 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Section - 7 : PT

Ppd.: AKR
Chkd: AKSM/SRKR

Page 83 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 84 of 88

DDoc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

7.1 PT for Incomer line feeders PT


(11kV Switchgear)
1.0 Application
Metering and protection

2.0 PT Ratio & Details


Ratio
11000/3

Cl

VPN

Unit
V

Connection
Star

Location
Primary

VSN

110/3

Cl: 1.0

Star

Secondary

VSN

110/3

Cl: 3P

Open delta

Secondary

3.0 Lead Burden


(Referring to Table - 68 of Oman Cable Catalogue for PVC insulated LT/Control cables)
Resistance of 2.5sqmm Cable at 70C
:
9.30
Ohms/km
Reactance of 2.5sqmm Cable at 70C
0.111
Ohms/km
Hence Impedance of 2.5Sqmm Cable
:
SQRT[(9.3^2)+(0.111^2)]
=
SQRT[86.49+0.012321]
=
SQRT[86.502321]
=
9.30066
Ohms/km
Single Lead Length of the VT cable from 33kV Swgr to 33kV
Protection / Control / Metering Panel
=
Hence 2 way Lead impedance of the cable

=
=
=
=

50

Mtr

[2 x Impd. of the cable x 50 / 1000]


[2 x 9.30066 x 50 / 1000]
0.930066
0.930066
Ohms
----(1)

4.0 VA Burden for Protection VT Core


4.1 Details of Relays burden connected to VT core
Slno

Relay

Make

Model

VA/Ph Burden
in VT Circuit

67/67N - Back
up directional
Protection

SIEMENS

7SJ6211

0.2

0.6

Burden

0.6

Connected 3ph Burden


Connected Relays Resistance
Lead Resistance of cable
Hence total Resistance in VT circuit

=
=
=
=

0.6
6722.222
0.930066
6723.152

Current through the VT Circuit


Hence Lead cable's 3Ph VA Burden

=
=

0.0054537909 Amps
8.299119E-005 VA

Hence total burden on VT core

=
=

(2) + (3)
0.6000829912 VA

With 20% Design Margin required VA Burden =


Selected VA Burden of VT Core

Ohmic
Net 3 Ph VA
Impedance
burden on
value (Ohm)
VT Core
(Ph-N)

Quantity
(No)

VA
Ohms
Ohms
Ohm

6722.222

----(2)

(Ph-N)

----(3)

0.7200995894 VA
=

200 VA & Hence sufficient

Ppd.: AKR
Chkd: AKSM/SRKR

Page 85 of 88

DDoc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Larsen & Toubro (Oman) LLC

5.0 VA Burden for Main Metering VT Core


5.1 Details of Meter burden connected to VT core
Slno

Meter

Make

Model

Voltmeter
Voltage
transducer
Frequency
transducer
MW
Transducer
MVAR
Transducer

0.5

1.5

0.5

1.5

0.00134

0.00403

0.00134

0.00403

Burden

6.00806667

2
3
4
5

Connected 3ph Burden


Connected Metering Resistance
Lead Resistance of cable
Hence total Resistance in VT circuit

=
=
=
=

6.0080666667
671.320
0.930066
672.250

Current through the VT Circuit


Hence Lead cable's 3Ph VA Burden

=
=

0.0944716319 Amps
0.0249022081 VA

Hence total burden on VT core

=
=

Selected VA Burden of VT Core

VA
Ohms
Ohms
Ohm

671.320

----(4)

(Ph-N)

----(5)

(4) + (5)
6.0329688747 VA

With 20% Design Margin required VA Burden =

6.0

Quantity
(No)

Ohmic
Net 3 Ph VA
Impedance
burden on
value (Ohm)
VT Core
(Ph-N)

VA/Ph Burden
in VT Circuit

7.2395626497 VA
=

200 VA & Hence sufficient

Recommended 11kV Switchgear PT Details for 11kV Incomers


Application
Protection
Core
Metering
Core

Primary
voltage (VPN)

Secondary
voltage (VSN)

Connection

Class

VA Burden

110/3

Open Delta

3P

200

110/3

Star

1.0

200

11000/3

Ppd.: AKR
Chkd: AKSM/SRKR

Page 86 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Section - 8 : CATALOGUE

Ppd.: AKR
Chkd: AKSM/SRKR

Page 87 of 88

Larsen & Toubro (Oman) LLC

Proj.: MADINAT AL NAHDAH PH-7 PR-S/S


Doc.: 11KV Current Transformer Sizing Calculations

Ppd.: AKR
Chkd: AKSM/SRKR

Doc. No.:11/2006/MAN/E/007/A4
Rev.1
Date:09.11.06

Page 88 of 88