Detailed Specifications &

Technical Data
Part No:
1.50mm, Instrumentation Cable Twisted Pair & Overall Shielded, 300/500V
For more information please
call 1-800-Belden1 See Put-ups
and Colors Related Documents:
No.2 and 2R (ICEA).pdf

Jacket
Pair

AL-mylar
Drain wire

DESCRIPTION:
1.50mm, Stranded Bare Copper conductors, Twisted Pairs, Overall Beldfoil Shield (100% coverage), XLPE insulation, LSLH PVC
Jacket.
PHYSICAL CHARACTERISTICS:
CONDUCTOR:
Number of Triads
Conductor Material
Nominal Conductor Area
No. of Strand / Strand Size

Refer Table Below


Annealed bare copper as per IEC 60228 (Class -5 Flexible conductor)
1.50 mm2
30/0.25

INSULATION:
Insulation Material
Nom. Insulation Thickness

XLPE Insulation
3.03 mm

DRAIN WIRE:
Drain Wire
Construction (mm)

Stranded Tinned Copper


16/0.20

OUTER SHIELD:
Outer Shield Name
Type
Coverage

Al-Mylar Shield
Tape
25% Overlap

OUTER JACKET:
Outer Jacket Material
Overall Nominal Diameter

LSLH-Low Smoke Low Halogen PVC


See Table Below

PAIRS
1
2
3
4
5

OVERALL
NOMINAL
DIAMETER (mm)
8.10
9.40
13.50
14.90
16.40

Min. BEND RADIUS


(mm)

Max. PULLING
TENSION (N)

BULK CABLE
WEIGHT (kg/km)

81
94
135
149
164

190
370
555
735
920

76.1
119.4
186.8
232.6
278.3

Detailed Specifications &


Technical Data
Part No:
1.50mm, Instrumentation Cable Twisted Pair & Overall Shielded, 300/500V
6
8
10
12
14
16
18
20

18.50
20.20
22.70
24.80
26.40
27.90
29.30
30.40

185
202
227
248
264
279
293
304

1100
1465
1825
2185
2550
2910
3270
3635

348.8
435.3
528.0
646.7
734.3
822.2
931.7
1016.2

MECHANICAL CHARACTERISTICS:
Operating Temperature Range

- 15 To + 90

Temperature Rating

+ 90

Min. Insulation Resistance

100 M*KM

APPLICABLE SPECIFICATION AGENCY COMPLIANCE:

APPLICABLE STANDARDS:
Applicable Specifications
EU RoHS Compliant (Y/N)
EU RoHS Compliant Date

BS 5308-1
Y
2009/3/4

FLAME TEST:
Flame Test
Smoke Density (ASTMD 2843)
Acid gas generation (IEC 60754-1):

IEC 60332-3C
40%
40%

ELECTRICAL CHARACTERISTICS:
Max. Conductor DC Resistance @ 20

13.3 /km

Nom. Outer Overall Shield DCR @ 20

30.8 /km

Ref. mutual capacitance between conductors

85.0 pF/m

PUT-UPS AND COLORS:


Part Number

Description

Put-Up (metre)

Jacket Color

YJ53812

1P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53813

2P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53814

3P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53815

4P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53816

5P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53817

6P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53818

8P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53819

10P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53820

12P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

Detailed Specifications &


Technical Data
Part No:
1.50mm, Instrumentation Cable Twisted Pair & Overall Shielded, 300/500V
YJ53821

14P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53822

16P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53823

18P x 1.5 SQMM XLPE/PVC 300/500V

500 / 100

Grey

YJ53824

20P x 0.75 SQMM XLPE/PVC 300/500V

500 / 100

Grey

Revision Number: 2
Revision Date: 3/12/2009
Copyright 2006 Belden, Inc
All Rights Reserved.
Although Belden ("Belden") makes every reasonable effort to ensure their accuracy at the time of this publication,
information and specifications described herein are subject to error or omission and to change without notice, and the
listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties,
whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential,
indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the
possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in
connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with the following environmental regulations: California Proposition
65 Consent Judgment For Wire & amp; Cable Mfgs.(San Francisco Superior Court Nos. 312962 And 320342); EU
RoHS (Directive 2002/95/EC, 27-Jan2003); Material manufactured prior to the compliance date may still be in stock at
Belden facilities and in our Distributor's inventory. EU ELV (Directive 2000/53/EC, 18-Sept-2000); EU WEEE
(Directive 2002/96/EC, 27-Jan-2003); And EU BFR (Directive 2003/11/EC, 6-Feb2003). The information provided in
this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product
Disclosure, is correct to the best of Belden's knowledge, information and belief at the date of its publication. The
information provided in the Product Disclosure is designed only as a general guide for the safe handling, storage, and
any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be
considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are
responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by
directive 93/68/EEC.