VEGAPULS 62
4 20 mA/HART - two-wire
Quick start
Quick start
1. Distance from the vessel wall > 200 mm, the antenna should
protrude > 10 mm into the vessel
ca. 10 mm
Mounting
The quick start enables a quick setup with many applications. You
can find further information in the respective chapters of the operating
instructions manual.
> 200 mm
(7.87")
1. Make sure that the power supply corresponds to the specifications on the type label.
2. Connect the instrument according to the following illustration
2
3
4...20mA
(+)1
2(-)
Set parameters
2. In the menu item "Medium"you select the medium of your application, for example "Aqueous solution".
36503-EN-121011
Quick start
3. Select in the menu item "Application" the vessel, the application
and the vessel form, for example, storage tank.
4. Carry out the adjustment in the menu items "Min. adjustment" and
"Max. adjustment".
100%
5m
(196.9")
0,5 m
(19.68")
Parameterization example The radar sensor measures the distance from the sensor to the
product surface. For indication of the real level, an allocation of the
measured distance to the percentage height must be carried out.
0%
Further steps
For this adjustment, the distance is entered with full and virtually
empty vessel. If these values are not known, an adjustment with
distances, for example, of 10 % and 90 % is also possible. Starting
point for these distance specifications is always the seal surface of
the thread or flange.
36503-EN-121011
The quick start is then finished. For further information see chapter
"Parameter adjustment".
Contents
Contents
About this document
1.1 Function ............................................................................. 6
1.2 Target group ....................................................................... 6
1.3 Symbolism used ................................................................. 6
Product description
3.1 Configuration .................................................................... 10
3.2 Principle of operation........................................................ 11
3.3 Packaging, transport and storage ..................................... 12
3.4 Accessories and replacement parts ................................. 12
Mounting
4.1 General instructions ......................................................... 14
4.2 Mounting preparations - Horn antenna ............................. 14
4.3 Mounting preparations - Parabolic antenna ...................... 15
4.4 Instructions for installation ................................................ 16
36503-EN-121011
Contents
9.1
9.2
9.3
9.4
9.5
9.6
9.7
Maintenance .................................................................... 54
Diagnosis memory ........................................................... 54
Asset Management function ............................................. 55
Rectify faults ..................................................................... 58
Exchanging the electronics module .................................. 62
Software update ............................................................... 62
How to proceed in case of repair ...................................... 63
10 Dismounting
10.1 Dismounting steps............................................................ 64
10.2 Disposal ........................................................................... 64
36503-EN-121011
11 Supplement
11.1 Technical data .................................................................. 65
11.2 Dimensions ...................................................................... 73
1.1
Function
1.2
Target group
1.3
Symbolism used
Ex applications
This symbol indicates special instructions for Ex applications.
List
The dot set in front indicates a list with no implied sequence.
Action
This arrow indicates a single action.
Sequence
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of batteries and accumulators.
36503-EN-121011
2
2.1
2.2
Appropriate use
2.3
2.4
The safety instructions in this operating instructions manual, the national installation standards as well as the valid safety regulations and
accident prevention rules must be observed by the user.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modifications are explicitly forbidden.
36503-EN-121011
The safety approval markings and safety tips on the device must also
be observed.
2.5
CE conformity
The device fulfills the legal requirements of the applicable EC guidelines. By affixing the CE marking, we confirm successful testing of the
product.
You can find the conformity certificate in the download section of our
homepage.
2.6
NAMUR recommendations
2.7
2.8
36503-EN-121011
2.9
Environmental instructions
36503-EN-121011
3 Product description
3
Type label
Product description
3.1 Configuration
The type label contains the most important data for identification and
use of the instrument:
16
15
14
4
5
6
7
8
9
13
12
11
10
Fig. 4: Layout of the type label (example)
1 Instrument type
2 Product code
3 Approvals
4 Power supply and signal output, electronics
5 Protection rating
6 Measuring range
7 Process and ambient temperature, process pressure
8 Material, wetted parts
9 Hardware and software version
10 Order number
11 Serial number of the instrument
12 Symbol of the device protection class
13 ID numbers, instrument documentation
14 Note to observe the instrument documentation
15 Notified authority for CE marking
16 Approval directive
Serial number
With the serial number of the instrument on the type label you have
access to the following data on our homepage:
10
36503-EN-121011
3 Product description
Versions
Scope of delivery
Application area
The VEGAPULS 62 radar sensor can be used in a wide variety of applications for continuous level measurement of liquids. It is suitable for
applications in storage vessels, reactors and process vessels, even
under extremely difficult process conditions.
Radar sensor
Documentation
this operating instructions manual
Test certificate measuring accuracy (optional)
Operating instructions manual "Indicating and adjustment
module" (optional)
Supplementary instructions "GSM/GPRS radio module"
(optional)
Supplementary instructions manual "Heating for indicating and
adjustment module" (optional)
Supplementary instructions manual "Plug connector for continuously measuring sensors" (optional)
Ex-specific "Safety instructions" (with Ex versions)
if necessary, further certificates
3.2
Principle of operation
Antenna
Small tanks and process vessels, measurement of virtually all
products: Horn antenna 40 mm
Storage tanks and process vessels, measurement of products
such as solvents, hydrocarbons and fuels under extremely difficult process conditions: Horn antenna 48 95 mm
Products with low r value with large measuring distances:
Parabolic antenna
Electronics
Products with an r value 1.8: Standard electronics
Products with an r value < 1.8, 1.5; applications with very bad
reflective properties: Electronics with increased sensitivity
36503-EN-121011
The antenna of the radar sensor emits short radar pulses with a
duration of approx. 1 ns. These pulses are reflected by the product
and received by the antenna as echoes. The transit time of the radar
pulses from emission to reception is proportional to the distance and
hence to the level. The determined level is converted into an appropriate output signal and outputted as measured value.
11
3 Product description
Packaging
3.3
Transport
Transport inspection
Storage
Storage and transport temperature see chapter "Supplement Technical data - Ambient conditions"
Relative humidity 20 85 %
3.4
The indicating and adjustment module PLICSCOM is used for measured value indication, adjustment and diagnosis. It can be inserted
into the sensor and removed at any time.
You can find further information in the operating instructions "Indicating and adjustment module PLICSCOM" (Document-ID 27835).
Interface adapter
12
36503-EN-121011
3 Product description
It is suitable for measured value indication and adjustment of plics
sensors and is connected to the sensor with a four-wire standard
cable up to 50 m long.
You can find further information in the operating instructions "VEGADIS 61" (Document-ID 27720).
External indicating and
adjustment unit with
HART protocol
Protective cover
The protective cover protects the sensor housing against soiling and
intense heat from solar radiation.
You will find additional information in the supplementary instructions
manual "Protective cover" (Document-ID 34296).
Flanges
Electronics module
Antenna impedance cone The antenna impedance cone is used for optimum transmission of
microwaves and for sealing against the process.
36503-EN-121011
13
4 Mounting
4
Screwing in
4.1
Mounting
General instructions
Moisture
4.2
Note:
The plastic cone may not be pulled out of the antenna socket.
3. Insert the antenna from below into the vessel socket and secure it
against falling off
4. Retighten the antenna with hexagon screws to the antenna
socket; torque max. 2.5 Nm (1.8 lbf ft)
14
36503-EN-121011
Note:
The radar sensor with rinsing air connection or antenna extension
is provided with a notch on the antenna socket. This notch must be
aligned with the marking on the process fitting (the marking specifies
the position of the polarisation plane of the radar signal).
4 Mounting
2
3
4
4.3
2. Hold the connection piece (3) with a wrench on the flat surfaces
(width across flats 22 mm)
3. Loosen counter nut (2) completely with a wrench (width across
flats 36 mm) in the direction of the antenna
4. Loosen compression nut (1) completely with a wrench (width
across flats 41 mm) in the direction of the antenna
5. Remove the parabolic antenna (4) axially
36503-EN-121011
9. Fasten compression nut (1) with a wrench (width across flats 41),
torque max. 50 Nm
10. Fasten counter nut (2) with a wrench (width across flats 36),
torque max. 40 Nm
Note:
On the version with rinsing air connection, make sure that the holes
in the antenna and in the process fitting coincide. This ensures a sufVEGAPULS 62 4 20 mA/HART - two-wire
15
4 Mounting
ficient air flow (the air is led through the holes to the feed system. A
rinsing of the whole parabolic antenna is not intended).
1
2
3
4
Connection piece
Compression nut
Locknut
Parabolic antenna
4.4
Polarisation plane
Installation position
If you cannot keep this distance you should carry out a false echo
storage before setup. This applies mainly if buildup on the vessel wall
16
36503-EN-121011
4 Mounting
is expected. In this case, we recommend repeating a false echo storage later with existing buildup.
> 200 mm
(7.87")
Do not mount the instruments in or above the filling stream. Make sure
that you detect the product surface, not the inflowing product.
36503-EN-121011
Inflowing medium
17
4 Mounting
ca. 10 mm
Socket
> 10 mm
(0.39")
36503-EN-121011
4 Mounting
sensor increases. Additional false reflections may be generated which
can influence the measuring result at close range.
Fig. 13: Distance between antenna and socket with horn antenna
Fig. 14: Distance between antenna and socket with parabolic antenna
36503-EN-121011
h max.
d
Fig. 15: Deviating socket dimensions
19
4 Mounting
Socket diameter d
Socket length h
40 mm
100 mm
40 mm
50 mm
150 mm
48 mm
80 mm
250 mm
75 mm
100 mm
500 mm
95 mm
150 mm
800 mm
95 mm
Socket diameter d
Socket length h
1"
3.9 in
1"
2"
5.9 in
2"
3"
9.8 in
3"
4"
19.7 in
4"
6"
31.5 in
4"
Tip:
The instrument is also optionally available with an antenna extension.
The antenna length can be selected (either ex works or later) to allow
the antenna to protrude slightly out of the end of the mounting socket.
Due to the antenna extension however, disturbing reflections are
generated in the close-up range. This can lead to an increase in the
required minimum distance, especially with poorly reflecting media
such as plastic powder. In practice, a cleanly constructed mounting
socket, if necessary with rounded edges, introduces fewer disturbing
influences than an antenna extension.
Sensor orientation
Align the sensor in liquids as vertical as possible to the product surface to achieve optimum measurement.
Vessel installations
36503-EN-121011
Vessel installations, such as e.g. ladders, limit switches, heating spirals, struts, etc., can cause false echoes and impair the useful echo.
Make sure when planning your measuring site that the radar sensor
has a "clear view" to the measured product.
4 Mounting
Small, inclined sheet metal baffles above the installations scatter the
radar signals and prevent direct interfering reflections.
Agitators
Foam generation
Through the action of filling, stirring and other processes in the vessel,
compact foams that considerably damp the emitted signals may form
on the product surface.
If foams are causing measurement errors, the biggest possible radar
antennas, the electronics with increased sensitivity or low frequency
radar sensors (C band) should be used.
36503-EN-121011
Measurement in a surge
pipe
When using a surge pipe in a vessel, influences from vessel installations and turbulences can be excluded. Under these prerequisites,
the measurement of products with low dielectric values (r value
1.6) is possible. In very adhesive products, measurement in a surge
pipe is not recommended.
21
4 Mounting
4
100%
5
6
7
9
0%
1
2
3
4
5
6
7
8
9
Radar sensor
Marking of the polarisation plane
Thread or flange on the instrument
Vent hole
Holes
Weld joint
Welding neck flange
Ball valve with complete opening
Fastening of the surge pipe
22
36503-EN-121011
The 100 % point must be below the upper vent hole and the
antenna edge
The 0 % point is the end of the surge pipe
For the parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate errors due to running time
shift
A false signal suppression with integrated sensor is recommended
but not mandatory
The measurement through a ball valve with complete run is possible
4 Mounting
Constructional requirements on the surge pipe:
Measurement in the
bypass
1
2
3
4
100 %
5
0%
36503-EN-121011
1
2
3
4
5
6
Radar sensor
Marking of the polarisation plane
Instrument flange
Distance sensor reference plane to upper tube connection
Distance of the tube connections
Ball valve with complete opening
23
4 Mounting
Instructions for orientation:
The 100 % point must not be above the upper tube connection to
the vessel
The 0 % point must not be below the lower tube connection to the
vessel
Min. distance sensor reference plane to the upper edge upper
tube connection > 300 mm
For the parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate errors due to running time
shift
A false signal suppression with integrated sensor is recommended
but not mandatory
The measurement through a ball valve with complete run is possible
36503-EN-121011
24
4 Mounting
max. 50 mm
(1.97")
1
2
1
dmin
3 ... 4 hmax
90
50 mm
2 2
33
90
2 mm x hmax hmax
Electronics housing
Distance piece
Vessel insulation
Fig. 22: Flow measurement with rectangular flume: dmin. = min. distance of the
sensor (see chapter "Technical data"); hmax. = max. filling of the rectangular
flume
1
2
3
4
36503-EN-121011
25
4 Mounting
Flow measurement with
Khafagi Venturi flume
3 ... 4 x hmax
d
90
hmax
Fig. 23: Flow measurement with Khafagi-Venturi flume: d = Min. distance to sensor; hmax. = max. filling of the flume; B = tightest constriction in the flume
1 Position sensor
2 Venturi flume
36503-EN-121011
26
5
Safety instructions
Voltage supply
5.1
Power supply and current signal are carried on the same two-wire
cable. The voltage supply range can differ depending on the instrument version.
The data for power supply are specified in chapter "Technical data".
Provide a reliable separation between the supply circuit and the
mains circuits according to DIN VDE 0106 part 101.
Keep in mind the following additional factors that influence the operating voltage:
Connection cable
Output voltage of the power supply unit can be lower under nominal load (with a sensor current of 20.5 mA or 22 mA in case of fault
message)
Influence of additional instruments in the circuit (see load values in
chapter "Technical data")
With plastic housing, the NPT cable gland or the Conduit steel tube
must be screwed without grease into the threaded insert.
Max. torque for all housings see chapter "Technical data"
36503-EN-121011
27
To avoid this in such applications, the cable screen must be connected to ground potential only at one end (in the switching cabinet). The
cable screen must not be connected to the internal ground terminal in
the sensor and the outer ground terminal on the housing must not be
connected to the potential equalisation!
Information:
The metal parts of the instrument (process fitting, transmitter, concentric tube, etc.) are conductively connected with the inner and outer
ground terminal on the housing. This connection exists either directly
via connecting metallic parts or, in case of instruments with external
electronics, via the screen of the special connection cable.
You can find specifications on the potential connections inside the
instrument in chapter "Technical data".
Connection technology
5.2
Connecting
The voltage supply and signal output are connected via the springloaded terminals in the housing.
The connection to the indicating and adjustment module or to the
interface adapter is carried out via contact pins in the housing.
Information:
The terminal block is pluggable and can be removed from the electronics. To do this, lift the terminal block with a small screwdriver and
pull it out. When inserting the terminal block again, you should hear it
snap in.
Connection procedure
Proceed as follows:
36503-EN-121011
28
6. Insert the wire ends into the terminals according to the wiring plan
Information:
Solid cores as well as flexible cores with cable end sleeves are
inserted directly into the terminal openings. In case of flexible cores
without end sleeves, press the terminal head with a small screwdriver;
the terminal opening is freed. When the screwdriver is released, the
terminal closes again.
You can find further information to the max. wire cross-section under
"Technical data/Electromechanical data"
7. Check the hold of the wires in the terminals by lightly pulling on
them
9. Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
10. Place probably existing indicating and adjustment module back
on
11. Screw the housing cover back on
5.3
36503-EN-121011
29
2
3
4...20mA
(+)1
2(-)
1
Fig. 25: Electronics and connection compartment, single chamber housing
1
2
3
4
5.4
4...20mA
(+)1
2(-)
7 8
Information:
The connection of an external indicating and adjustment unit is not
possible with this double chamber housing.
36503-EN-121011
30
4...20mA
(+)1
2(-)
1
Fig. 27: Connection compartment, double chamber housing
1
2
3
Status
SIM-Card
Test
USB
Bus
(+)1
2 (-)
1
Fig. 28: CConnection of the voltage supply of the radio module
1
Voltage supply
5.5
Electronics compartment
4...20mA
(+)1
2(-)
7 8
36503-EN-121011
31
4...20mA
(+)1
2(-)
1
Fig. 30: Connection compartment, Ex-d double chamber housing
1
2
Pin 1
Pin 2
Pin 3
Pin 4
Contact pin
Terminal, electronics
module
Pin 1
Brown
Pin 2
White
Pin 3
Blue
Pin 4
Black
5.6
1
2
Fig. 32: Wire assignment fix-connected connection cable
1
2
brown (+) and blue (-) to power supply or to the processing system
Shielding
Switch-on phase
32
36503-EN-121011
5.7
36503-EN-121011
33
6
6.1
The indicating and adjustment module can be inserted into the sensor and removed any time. Four positions displaced by 90 can be
selected. It is not necessary to interrupt the power supply.
Proceed as follows:
Fig. 33: Insertion of the indicating and adjustment module with single chamber
housing into the electronics compartment
36503-EN-121011
34
Fig. 34: Insertion of the indicating and adjustment module with double chamber
housing
1
2
Note:
If you intend to retrofit the instrument with an indicating and adjustment module for continuous measured value indication, a higher
cover with an inspection glass is required.
6.2
Adjustment system
1
36503-EN-121011
Key functions
1
2
LC display
Adjustment keys
[OK] key:
Move to the menu overview
Confirm selected menu
35
Adjustment system
Edit parameter
Save value
[->] key:
Presentation change measured value
Select list entry
Select editing position
[+] key:
Change value of the parameter
[ESC] key:
interrupt input
Jump to next higher menu
The sensor is adjusted via the four keys of the indicating and adjustment module. The LC display indicates the individual menu items. The
functions of the individual keys are shown in the above illustration.
Approx. 10 minutes after the last pressing of a key, an automatic reset
to measured value indication is triggered. Any values not confirmed
with [OK] will not be saved.
6.3
Parameter adjustment
The main menu is divided into five sections with the following functions:
Setup: Settings, e.g., for measurement loop name, medium, application, vessel, adjustment, signal output
Further settings: Instrument unit, false signal suppression, linearisation curve, reset, date/time, reset, copy function
Info: Instrument name, hardware and software version, calibration
date, instrument features
36
36503-EN-121011
Information:
In this operating instructions manual, the instrument-specific parameters in the menu sections "Setup", "Diagnosis" and "Additional settings" are described. The general parameters in these menu section
are described in the operating instructions manual "Indicating and
adjustment module".
In the main menu point "Setup", the individual submenu points should
be selected subsequently and provided with the correct parameters
to ensure the optimum adjustment of the measurement. The procedure is described in the following.
Setup/Medium
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Setup/Application
In addition to the medium, also the application, i.e. the measuring site,
can influence the measurement.
With this menu item, the sensor can be adapted to the applications.
The adjustment possibilities depend on the selection "Liquid" or "Bulk
solid" under "Medium".
36503-EN-121011
37
Dosing vessel:
38
36503-EN-121011
Standpipe:
Bypass:
Product speed:
Fast up to slow filling with short up to long bypass tube possible
Often the level is hold via a control facility
Vessel:
Lateral outlets and inlets
Joins like flanges, weld joints
Shifting of the running time in the tube
Process/measurement conditions:
Condensation
Buildup
Separation of oil and water possible
Overfilling into the antenna possible
Plastic tank:
Vessel:
Measurement fix mounted or integrated
Measurement depending on the application through the vessel
top
With empty vessel, the measurement can be carried out
through the bottom
Process/measurement conditions:
Condensation on the plastic ceiling
In outside facilities water and snow on the vessel top possible
36503-EN-121011
Vessel:
Material and thickness different
Measurement through the vessel top
Process/measurement conditions:
Measured value jump with vessel change
39
Demonstration:
Adjustment for all applications which are not typically level measurement
Sensor accepts all measured value changes within the measuring
range immediately
Typical applications:
Instrument demonstration
Object recognition/monitoring (additional settings required)
Caution:
If a separation of liquids with different dielectric figure occurs in the
vessel, for example through condensation, the radar sensor can
detect under certain circumstances only the medium with the higher
dielectric figure. Keep in mind that layer interfaces can cause faulty
measurements.
If you want to measure the total height of both liquids reliably, please
contact our service department or use an instrument specially designed for interface measurement.
The following options are available when "Bulk solid" is selected:
40
36503-EN-121011
Heap:
Crusher:
Demonstration:
36503-EN-121011
Adjustment for all applications which are not typically level measurement
Sensor accepts all measured value changes within the measuring
range immediately
Typical applications:
Instrument demonstration
Object recognition/monitoring (additional settings required)
Through this selection, the sensor is adapted optimally to the application or the location and measurement reliability under the various
basic conditions is increased considerably.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
41
Also the vessel form can influence the measurement apart from the
medium and the application. To adapt the sensor to these measurement conditions, this menu item offers you different options for vessel
bottom and ceiling in case of certain applications.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Setup/Vessel height,
measuring range
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Setup/Adjustment
36503-EN-121011
42
100%
5m
(196.9")
0,5 m
(19.68")
0%
If these values are not known, an adjustment with the distances of for
example 10 % and 90 % is possible. Starting point for these distance
specifications is always the seal surface of the thread or flange. By
means of these settings, the real level will be calculated.
The real product level during this adjustment is not important, because the min./max. adjustment is always carried out without changing the product level. These settings can be made ahead of time
without the instrument having to be installed.
Setup/Min. adjustment
Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].
Now select with [->] the menu item "Min. adjustment" and confirm
with [OK].
36503-EN-121011
2. Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
43
5. Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.
Setup/Max. adjustment
Proceed as follows:
1. Select with [->] the menu item max. adjustment and confirm with
[OK].
2. Prepare the percentage value for editing with [OK] and set the
cursor to the requested position with [->].
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
The respective min. and max. measured value is saved in the sensor.
The values are displayed in the menu item "Peak values".
Diagnosis/Measurement
reliability
44
The "Echo curve" shows the signal strength of the echoes over the
measuring range in dB. The signal strength enables an evaluation of
the quality of the measurement.
The "False signal suppression" displays the saved false echoes (see
menu "Additional settings") of the empty vessel with signal strength in
"dB" over the measuring range.
Diagnostics/Echo curve
memory
With the function "Echo curve memory" the echo curve can be saved
at the time of setup. This is generally recommended; for using the Asset Management functions it is absolutely necessary. If possible, the
curve should be saved with a low level in the vessel.
36503-EN-121011
With the adjustment software PACTware and the PC, the high resolution echo curve can be displayed and used to recognize signal
changes over the operating time. In addition, the echo curve of the
setup can be also displayed in the echo curve window and compared
with the actual echo curve.
Additional adjustments/
False signal suppression
High sockets
45
Note:
A false signal suppression detects, marks and saves these false signals so that they are no longer taken into account for level measurement.
This should be done with the low level so that all potential interfering
reflections can be detected.
Proceed as follows:
1. Select the menu item "Additional settins" with [->] and confirm
with [OK]. With [->] you have to select the menu item "False
signal suppression" and confirm with [OK].
4. Confirm again with [OK] and enter the actual distance from the
sensor to the product surface.
46
36503-EN-121011
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [ESC] and [->] key.
Caution:
Note the following if the instrument with corresponding approval is
used as part of an overfill protection system according to WHG:
36503-EN-121011
Additional adjustments
- Reset
Delivery status: Restoring the parameter settings at the time of shipment from the factory incl. the order-specific settings. A created false
VEGAPULS 62 4 20 mA/HART - two-wire
47
The following table shows the default values of the instrument. Depending on the instrument version, not all menu items are available or
differently assigned:
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Medium
Liquid/Water
Applications
Storage tank
Vessel form
Vesell height/
Measuring range
Min. adjustment
Max. adjustment
0,000 m(d)
Damping
0.0 s
Current output
mode
Current output
Min./Max.
Lock operation
Released
36503-EN-121011
48
Menu item
Default value
Display
Language
Like order
Displayed value
Distance
Display unit
Scaling size
Volume
Scaling
0.00 lin %, 0 l
Additional adjustments
6.4
Backlight
Switched off
Distance unit
Temperature unit
Probe length
Linearisation
curve
Linear
HART mode
Standard
Address 0
36503-EN-121011
The function can also be used to transfer settings from one instrument to another instrument of the same type. If it is necessary to
exchange a sensor, the indicating and adjustment module is inserted
into the replacement instrument and the data are likewise written into
the sensor via the menu item "Copy sensor data".
49
7.1
Connect the PC
Fig. 37: Connection of the PC directly to the sensor via the interface adapter
1
2
3
Information:
The interface adapter VEGACONNECT 3 is not suitable for connection to the sensor.
Via the interface adapter
and HART
USB
N
OPE
TWIST
LO
CK
Sensor
HART resistance 250 (optional depending on processing)
Connection cable with 2 mm pins and terminals
Processing system/PLC/Voltage supply
Interface adapter, for example VEGACONNECT 4
50
36503-EN-121011
Note:
With power supply units with integrated HART resistance (internal
resistance approx. 250 ), an additional external resistance is not
necessary. This applies, e.g. to the VEGA instruments VEGATRENN
149A, VEGAMET 381, VEGAMET 391. Common Ex separators are
also usually equipped with a sufficient current limitation resistance. In
Prerequisites
7.2
For parameter adjustment of the sensor via a Windows PC, the configuration software PACTware and a suitable instrument driver (DTM)
according to FDT standard are required. The up-to-date PACTware
version as well as all available DTMs are compiled in a DTM Collection. The DTMs can also be integrated into other frame applications
according to FDT standard.
Note:
To ensure that all instrument functions are supported, you should
always use the latest DTM Collection. Furthermore, not all described
functions are included in older firmware versions. You can download
the latest instrument software from our homepage. A description of
the update procedure is also available in the Internet.
Further setup steps are described in the operating instructions manual "DTM Collection/PACTware" attached to each DTM Collection and
which can also be downloaded from the Internet. Detailed descriptions are available in the online help of PACTware and the DTMs.
36503-EN-121011
Standard/Full version
In the full version there is also an extended print function for complete
project documentation as well as a save function for measured value
VEGAPULS 62 4 20 mA/HART - two-wire
51
7.3
36503-EN-121011
52
8
8.1
8.2
36503-EN-121011
53
9.1
Maintenance
9.2
Diagnosis memory
The instrument has several memories which are available for diagnosis purposes. The data remain even with voltage interruption.
Measured value memory
Distance
Filling height
Percentage value
Lin. percent
Scaled
Current value
Meas. reliability
Electronics temperature
The requested values and recording conditions are set via a PC with
PACTware/DTM or the control system with EDD. Data are thus read
out and also reset.
Event memory
Modification of a parameter
Switching on and off times
Status messages (according to NE 107)
Error messages (according to NE 107)
The data are read out via a PC with PACTware/DTM or the control
system with EDD.
The echo curves are stored with date and time and the corresponding
echo data. The memory is divided into two sections:
54
PC with PACTware/DTM
Control system with EDD
Indicating and adjustment module
36503-EN-121011
Echo curve of the setup: This is used as reference echo curve for
the measurement conditions during setup. Changes in the measurement conditions during operation or buildup on the sensor can thus
be recognized. The echo curve of the setup is stored via:
PC with PACTware/DTM
Control system with EDD
9.3
Failure
Function check
Out of specification
Maintenance requirement
Failure - red
Function check - orange
Out of specification - yellow
Maintenance - blue
36503-EN-121011
55
The following table shows the error codes in the status message
"Failure" and gives information on the reason and rectification. Keep
in mind that some information is only valid with four-wire instruments.
Code
Cause
Rectification
F013
F017
Change adjustment according to the limit values (difference between min. and
max. 10 mm)
F025
F036
F040
Hardware defect
F080
F105
F113
EMC interferences
Transmission error with the
external communication
with 4-wire power supply
unit
F125
F260
F261
Repeat setup
Repeat reset
Text message
no measured
value available
Adjustment
span too small
Error in the
linearization
table
No operable
software
Error in the
electronics
Determine
measured
value
Communication error
Unpermissible electronics
temperature
Error in the
configuration
56
36503-EN-121011
Error in the
calibration
Cause
F264
Text message
Installation/
Setup error
F265
Function check
Code
Cause
Rectification
C700
A simulation is active
Finish simulation
Wait for the automatic end
after 60 mins.
Simulation active
The following table shows the error codes and text messages in the
status message "Out of specification" and provides information on
causes as well as corrective measures.
Code
Cause
Rectification
S600
S601
Text message
Unpermissible electronics
temperature
Overfilling
Maintenance
The following table shows the error codes and text messages in the
status message "Maintenance" and provides information on causes
as well as corrective measures.
Code
Cause
Rectification
M500
Repeat reset
Load XML file with sensor
data into the sensor
Text message
36503-EN-121011
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Text message
Out of specification
Rectification
57
Cause
Rectification
M501
M502
M503
Reliability too
low
M504
Hardware defect
Check connections
Exchanging the electronics
Send instrument for repair
M505
Text message
Error in the
non-active
linearization
table
Error in the
diagnosis
memory
Error on an
device interface
No echo available
9.4
Rectify faults
The operator of the system is responsible for taking suitable measures to rectify faults.
Further comprehensive diagnostics options offer a PC with the software PACTware and the suitable DTM. In many cases, the reasons
can be determined in this way and faults can be rectified.
58
36503-EN-121011
Check the 4 20 mA
signal
Rectification
Set damping according to the
instrument via the indicating and
adjustment module or PACTware/
DTM
Voltage supply
missing
Electronics
module in the
sensor defective
Cause
The below tables show typical examples of application-related measurement errors with liquids. The measurement errors are differentiated
according to the following:
Constant level
Filling
Emptying
Level
The images in column "Error pattern" show the real level with a broken line and the level displayed by the sensor as a continuous line.
1
2
0
1
2
time
Real level
Level displayed by the sensor
Instructions:
36503-EN-121011
59
9.4
1. Measured value
shows a too low or too
high level
Error pattern
Level
Fault description
Rectification
time
time
Level
3. Measured value
jumps towards 100 %
Cause
Level
2. Measured value
jumps towards 0 %
time
Error pattern
Level
Fault description
Rectification
time
36503-EN-121011
60
time
Level
time
Level
Cause
7. Measured value
jumps towards 0 %
during filling
Error pattern
Cause
Rectification
Level
Fault description
time
8. Measured value
jumps towards 100 %
during filling
Level
Level
9. Measured value
jumps sporadically to
100 % during filling
time
Level
0
time
9.4
36503-EN-121011
Level
Error pattern
Rectification
time
Level
time
Fault description
time
61
Error pattern
Level
Fault description
Cause
Rectification
time
Depending on the reason for the fault and the measures taken, the
steps described in chapter "Setup" must be carried out again or must
be checked for plausibility and completeness.
9.5
In the factory
Or on site by the user
In both cases, the serial number of the sensor is needed. The serial
numbers are stated on the type label of the instrument, on the inside
of the housing as well as on the delivery note.
When loading on site, first of all the order data must be downloaded
from the Internet (see operating instructions manual "Electronics
module").
9.6
Software update
62
Sensor
Voltage supply
Interface adapter VEGACONNECT 4
PC with PACTware
Current sensor software as file
36503-EN-121011
9.7
By doing this you help us carry out the repair quickly and without having to call back for needed information.
If a repair is necessary, please proceed as follows:
36503-EN-121011
63
10 Dismounting
10 Dismounting
10.1 Dismounting steps
Warning:
Before dismounting, be aware of dangerous process conditions such
as e.g. pressure in the vessel, high temperatures, corrosive or toxic
products etc.
Take note of chapters "Mounting" and "Connecting to power supply"
and carry out the listed steps in reverse order.
10.2 Disposal
The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have
designed the electronics to be easily separable.
Correct disposal avoids negative effects on humans and the environment and ensures recycling of useful raw materials.
Materials: see chapter "Technical data"
36503-EN-121011
64
11 Supplement
11 Supplement
11.1 Technical data
General data
316L corresponds to 1.4404 or 1.4435
Materials, wetted parts
Process fitting
Antenna
Process seal
Plastic housing
316L
Ohmic contact
Process fittings
Weight
1 NPT, 2 NPT
36503-EN-121011
65
11 Supplement
Input variable
Measured variable
Reference plane
Measured variable, max. measuring range
Antenna length
Useful measuring range
Standard electronics
Max. measuring range
35 m (114.83 ft)
up to 15 m (49.21 ft)
up to 20 m (65.62 ft)
75 m (246.1 ft)
up to 15 m (49.21 ft)
up to 40 m (131.23 ft)
Parabolic antenna
up to 75 m (246.1 ft)
up to 20 m (65.62 ft)
up to 50 m (164 ft)
4 20 mA/HART
Signal resolution
0.3 A
7.0
Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
66
36503-EN-121011
Output variable
Output signal
11 Supplement
Max. output current
22 mA
Load
Starting current
0 999 s
TV (Third Value)
SV (Secondary Value)
QV (Fourth Value)
Resolution, digital
Air pressure
Relative humidity
45 75 %
False reflections
Reflector
10 mm (0.394 in)
2 mm (0.079 in)
0
- 2 mm (- 0.079 in)
- 10 mm (- 0.394 in)
1 2
Reference plane
Antenna edge
Recommended measuring range
36503-EN-121011
Reproducibility
1 mm
67
11 Supplement
Temperature drift - Digital output
< 15 A
< 150 A
The following table shows the resulting deviation for some typical gases and vapours. The specified
values refer to the distance. Positive values mean that the measured distance is too large, negative
values that the measured distance is too small.
Gas phase
Air
Hydrogen
Temperature
20 C/68 F
Pressure
1 bar
(14.5 psig)
10 bar
(145 psig)
50 bar
(725 psig)
100 bar
(1450 psig)
200 bar
(2900 psig)
0.00 %
0.22 %
1.2 %
2.4 %
4.9 %
0.13 %
0.74 %
1.5 %
3.0 %
0.08 %
0.52 %
1.1 %
2.1 %
20 C/68 F
-0.01 %
0.10 %
0.61 %
1.2 %
2.5 %
0.05 %
0.37 %
0.76 %
1.6 %
0.03 %
0.25 %
0.53 %
1.1 %
2.1 %
1.44 %
9.2 %
1.01 %
5.7 %
13.2 %
76.0 %
2)
68
700 ms
3s
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).
36503-EN-121011
450 ms
11 Supplement
Tracking speed of the measuring window 1 m/min
max.
Beam angle3)
20
10
15
8
Ambient conditions
Ambient, storage and transport tempera- -40 +80 C (-40 +176 F)
ture
Process conditions
For the process conditions, please also note the specifications on the type label. The lowest value
always applies.
Seal
Antenna impedance
cone
PTFE
PTFE5)
PEEK6)
PTFE
PEEK
PTFE
PEEK
PTFE
PEEK
Graphite
Ceramic
Ceramic
36503-EN-121011
3)
4)
5)
6)
Outside the specified beam angle, the energy of the radar signal has a level which is reduced by 50 % (-3 dB)
EIRP: Equivalent Isotropic Radiated Power
Not with steam
Not with steam
69
11 Supplement
Antenna impedance cone PEEK
Parabolic antenna
Shock resistance
Horn antenna
Parabolic antenna
Data on rinsing air connection
Pressure max.
2.0 m3/h
4.5 m3/h
Thread
Closure, with
Non-Ex
Ex
3.5 m3/h
5 m3/h
5.5 m3/h
G A
Reflux valve - unmounted (as option with non-Ex version, included in the scope of delivery with Ex
version)
Material
316Ti
6 mm
Seal
opening pressure
Cable gland
Blind stopper
Cable entry
Closing cap
70
NPT
36503-EN-121011
11 Supplement
Plug options
Signal circuit
Indication circuit
Blind stopper
Cable entry
Connection cable
NPT
Wire cross-section
Tensile strength
Wire resistance
Standard length
Max. length
Size of digits
Adjustment elements
Protection rating
unassembled
< 0.036 /m
5 m (16.4 ft)
W x H = 7 x 13 mm
4 keys
IP 20
Materials
Housing
36503-EN-121011
Inspection window
ABS
Polyester foil
Integrated clock
Date format
Day.Month.Year
CET
Time format
12 h/24 h
71
11 Supplement
Measurement electronics temerature
Resolution
1 C (1.8 F)
Accuracy
1 C (1.8 F)
Voltage supply
Operating voltage
Non-Ex instrument
9.6 36 V DC
Ex-ia instrument
9.6 30 V DC
Ex-d-ia instrument
14 36 V DC
15 36 V DC
Non-Ex instrument
16 36 V DC
Ex-d-ia instrument
20 36 V DC
16 30 V DC
Interpolation protection
Integrated
Load
see diagram
1200
927
750
500
250
4
9,6
12
14 15,1 16
18
20
22
24
26
28
30
32
34
36
HART load
Voltage limit Ex-ia instrument
Voltage limit non-Ex/Ex-d instrument
Operating voltage
7)
72
IP 66/IP 67
The prerequisites for maintaining the protection rating are a suitable cable as well as correct mounting.
36503-EN-121011
Plastic housing
11 Supplement
Aluminium and stainless housing, in- IP 66/IP 68 (1 bar)
vestment casting (optionally available)
Overvoltage category
III
Protection class
III
Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments must be carefully noted.
They are part of the delivery or can be downloaded under www.vega.com and "VEGA Tools" as
well as under "Downloads" and "Approvals".
11.2 Dimensions
The following dimensional drawings represent only an extract of the possible versions. Detailed
dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings".
Plastic housing
~ 69 mm
(2.72")
79 mm
(3.03")
~ 84 mm (3.31")
M20x1,5/
NPT
M16x1,5
M20x1,5/
NPT
112 mm (4.41")
112 mm (4.41")
79 mm
(3.31")
Fig. 58: Housing versions in protection IP 66/IP 68 (0.2 bar) - with integrated indicating and adjustment module the
housing is 9 mm/0.35 in higher
Single chamber version
Double chamber version
36503-EN-121011
1
2
73
11 Supplement
Aluminium housing
~ 87 mm (3.43")
~ 116 mm (4.57")
86 mm
(3.39")
M16x1,5
120 mm (4.72")
116 mm (4.57")
86 mm (3.39")
M20x1,5
M20x1,5/
NPT
M20x1,5/
NPT
Fig. 59: Housing versions in protection IP 66/IP 68 (0.2 bar) - with integrated indicating and adjustment module the
housing is 9 mm/0.35 in higher
1
2
~ 150 mm (5.91")
84 mm (3.31")
84 mm
(3.31")
M20x1,5
120 mm (4.72")
116 mm (4.57")
M16x1,5
M20x1,5
M20x1,5/
NPT
Fig. 60: Housing versions in protection IP 66/IP 68 (1 bar) - with integrated indicating and adjustment module the
housing is 9 mm/0.35 in higher
1
2
36503-EN-121011
74
11 Supplement
~ 59 mm
(2.32")
80 mm
(3.15")
~ 87 mm (3.43")
86 mm
(3.39")
M20x1,5/
NPT
M20x1,5/
NPT
120 mm (4.72")
117 mm (4.61")
112 mm (4.41")
M16x1,5
M20x1,5/
NPT
Fig. 61: Housing versions in protection IP 66/IP 68 (0.2 bar) - with integrated indicating and adjustment module the
housing is 9 mm/0.35 in higher
1
2
2
~ 105 mm (4.13")
80 mm
(3.15")
~ 103 mm
(4.06")
84 mm
(3.31")
77 mm
(3.03")
120 mm (4.72")
112 mm (4.41")
M20x1,5/
NPT
117 mm (4.61")
M16x1,5
M20x1,5
M20x1,5/
NPT
Fig. 62: Housing versions in protection IP 66/IP 68 (1 bar) - with integrated indicating and adjustment module the
housing is 9 mm/0.35 in higher
Single chamber version, electropolished
Single chamber version, precision casting
Double chamber version, precision casting
36503-EN-121011
1
2
2
75
11 Supplement
144 mm (5.67")
G1A / 1 NPT
x
100
40
3"
216
75
2"
4"
1"
inch
1"
2"
3"
4"
120
430
y
3.94"
4.72"
8.50"
16.93"
48
95
x
1.58"
1.89"
2.95"
3.74"
mm
22 mm (0.87")
38 mm (1.50")
SW 46 mm
(1.81")
22 mm (0.87")
Standard
With temperature adapter up to 250 C
36503-EN-121011
76
11 Supplement
2
165 mm (6.5")
60 mm
(2.36")
x
mm
inch
48
2"
1"
100
40
3"
216
75
2"
4"
120
430
95
1"
3"
4"
3.94"
4.72"
8.50"
16.93"
1.58"
1.89"
2.95"
3.74"
36503-EN-121011
1
2
77
11 Supplement
260 mm (10.24")
y
120
216
287
y
inch
4.72"
2"
3" 8.50"
4" 11.30"
x
48
75
95
mm
2"
3"
4"
x
1.89"
2.95"
3.74"
x
Fig. 65: VEGAPULS 62, horn antenna in flange version with temperature adapter up to 450 C
36503-EN-121011
78
11 Supplement
(0.59")
20 m
m
(0.79
")
146 m
m (5.7
5")
40 m
m
(1.58
")
100
40
3"
216
75
4"
inch
1"
2"
3"
4"
120
430
y
3.94"
4.72"
8.50"
16.93"
48
95
20 m
m
(0.79
")
2"
1"
1.58"
1.89"
2.95"
3.74"
mm
36503-EN-121011
1
2
79
11 Supplement
(0.59")
243
130 m
m
(5.12
")
120 m
m
(4.72
")
40 m
m
(1.58
")
mm (9
.57")
Standard
With temperature adapter up to 200 C
36503-EN-121011
80
11 Supplement
.
VEGA
<
>
11.4 Trademark
36503-EN-121011
All the brands as well as trade and company names used are property of their lawful proprietor/
originator.
81
INDEX
INDEX
A
Accessories
External indicating and adjustment unit 12,
13
External radio unit 13
Flanges 13
Indicating and adjustment module 12
Interface adapter 12
Protective cover 13
Adjustment
Max. adjustment 44
Min. adjustment 43
Adjustment system 36
Agitator 21
Application area 11
Applications
Bulk solid 40
Liquid 37
Standpipe 38
Cable entry 27
Check signal 58
Connection cable 27
Connection procedure 28
Connection technology 28
Curve indication
Echo curve 45
False signal suppression 45
DD (Device Description) 53
Default values 48
Grounding 27
HART resistor 50
Inflowing medium 17
Installation position 16
Key function 35
Linearisation curve 47
Main menu 36
Meas. reliability 44
Measured value memory 54
Measurement error 59
Measurement in a surge pipe 21
Measurement in the bypass 23
Medium
Liquid Bulk solid 37
Moisture 14
NAMUR NE 107
Failure 56
Function check 57
Maintenance 57
Out of specification 57
Packaging 12
Peak value 44
Polarisation plane 16
Potential equalisation 27
Reflection properties 37
VEGAPULS 62 4 20 mA/HART - two-wire
36503-EN-121011
Flow measurement
Khafagi-Venturi flume 26
Rectangular flume 25
Foam generation 21
Functional principle 11
INDEX
Repair 63
Replacement parts
Antenna impedance cone 13
Electronics module 13
Reset 47
Sensor orientation 20
Service hotline 62
Shielding 27
Socket 18
Status messages 55
Storage 12
Type label 10
36503-EN-121011
Vessel form 42
Vessel height 42
Vessel installations 20
Vessel insulation 24
Voltage supply 27
83
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information
available at the time of printing.
Subject to change without prior notice
VEGA Grieshaber KG, Schiltach/Germany 2012
VEGA Grieshaber KG
Am Hohenstein 113
77761 Schiltach
Germany
36503-EN-121011
Printing date: