heat and superheat changes, due to sudden operation of FCS control valves the BFP discharge pressure
will change and there will be drop in feed water temperature. Operators should take the attemparation
control into manual and control the temperature. Fine control of MS pressure leads to easy control of
temperature. Further the attemparation pressure (i.e. FW pressure) to be adjusted.
3) Re-heater pressure and temperature: Due to sudden opening the HP bypass valve the pressure of
reheater will increase. The pressure to be controlled by operating the LP bypass and re-heater startup
vents. Due to sudden opening of HP bypass the reheater inlet temperature will increase this will be
controlled by HP bypass attemparation. If the temperature couldnt control by HP bypass attemparation
then urgent attemparation to be operated.
4) Drum level: