Measuring current transformer


Range of rated currents

Measuring CTs should work properly within the rated


current range (< 2 x In)

range

continuous thermal
loadings

additional
ordering
information

standard

120 %

100 %

none

IEC/VDE

120 %

120 %

ext. 120 %

IEC/VDE

1.5 x In

150 %

150 %

ext. 150 %

IEC/VDE

2 x In

200 %

200 %

ext. 200 %

IEC/VDE

measurement

Power Transmission and Distribution

Copyright SIEMENS AG. P TD SE P T 2005. All rights reserv ed.

Power Technogies
Instrument Transformer
Dimensioning, Page 2

Seite 1

Measuring current transformer


Definitions of error margins IEC 44
limits of current error and phase displacement acc. to IEC 600 44-1 (classes from 0.1 to1)

+/- percentage current


(ratio) error at percentage
of rated current

accuracy class

+/- phase displacement at percentage


of rated current

minutes

centiradians

20

100

120

20

100

120

20

100

120

0.1

0.4

0.2

0.1

0.1

15

0.45

0.24

0.15

0.15

0.2

0.75

0.35

0.2

0.2

30

15

10

10

0.9

0.45

0.3

0.3

0.5

1.5

0.75

0.5

0.5

90

45

30

30

2.7

1.35

0.9

0.9

1.5

180

90

60

60

5.4

2.7

1.8

1.8

Power Transmission and Distribution

Copyright SIEMENS AG. P TD SE P T 2005. All rights reserv ed.

Power Technogies
Instrument Transformer
Dimensioning, Page 3

Measuring current transformer


Definitions of error margins IEC 600 44-1
limits of current error and phase displacement acc. to IEC 600 44-1
for special applications

accuracy class

+/- percentage current


(ratio) error at percentage
of rated current

+/- phase displacement at percentage


of rated current

%
1

20

minutes
100

120

20

100

centiradians
120

20

100

120

0.2S

0.75

0.35

0.2

0.2

0.2

30

15

10

10

10

0.9

0.45

0.3

0.3

0.3

0.5S

1.5

0.75

0.5

0.5

0.5

90

45

30

30

30

2.7

1.35

0.9

0.9

0.9

Note: This table is applicable only to transformers having a rated secondary current of 5A.

Power Transmission and Distribution

Copyright SIEMENS AG. P TD SE P T 2005. All rights reserv ed.

Power Technogies
Instrument Transformer
Dimensioning, Page 4

Seite 2

Measuring current transformer


Accuracy classes acc. to IEEE/ANSI C57.13 and CAN3-C13
Accuracy classes: 0.3 - 0.6 - 1.2

Measurement ranges: 1 - 1.33 - 1.5 - 2 - 3 - 4 x In


1.0 x In
1.5 x In
...

- without special indication


- factor 1.5 at indication of rated current

the specification of an accuracy limiting factor is unusual


Indication of power ratings: B 0.1 - B 0.2 - B 0.5 - B 0.9 - B 1.8
The rated power is not indicated directly. Instead of that the impedance of the rated burden
is mentioned on the name plate. The rated burden is always related to a secondary current
of 5 Amps.
B 0.5

rated burden = 0.5 Ohm

rated power = 25 x 0.5 = 12.5 VA

The required accuracy has to be maintained only with rated burden.

Power Transmission and Distribution

Copyright SIEMENS AG. P TD SE P T 2005. All rights reserv ed.

Power Technogies
Instrument Transformer
Dimensioning, Page 5

Measuring current transformer


limits of errors under overcurrent conditions acc. to IEC 600 44-1

range of
rated current

Under overcurrent conditions the


downstream measurement devices
should be protected against
impermissible thermal overloadings

range of overcurrent

With rated burden (cos = 0.8) and


rated factor of security (FS) the
composite error has to result to
10% at least to the CT is under
saturated condition

Power Transmission and Distribution

Copyright SIEMENS AG. P TD SE P T 2005. All rights reserv ed.

Power Technogies
Instrument Transformer
Dimensioning, Page 6

Seite 3

Measuring current transformer


Comparison of CTs for measurement and protection purpose
Measurement CT
range of
rated current

Protection CT
range of
rated current

range of overcurrent

Power Transmission and Distribution

range of overcurrent

Copyright SIEMENS AG. P TD SE P T 2005. All rights reserv ed.

Power Technogies
Instrument Transformer
Dimensioning, Page 7

Measuring current transformer


Comparison of CTs for measurement and protection purpose
Measurement CT

Protection CT

Under overcurrent conditions the


downstream measurement devices
should be protected against
impermissible thermal overloadings

Under overcurrent conditions the


CT should work errorless as
possible ensuring a proper
protection function.

With rated burden (cos = 0.8)


and rated factor of security (FS) the
composite error has to result to
10% at least to the CT is under
saturated condition.

With rated burden (cos = 0.8) and


rated overcurrent the composite
error limits must be maintained.
The CT must not be under
saturated conditions.

Power Transmission and Distribution

Copyright SIEMENS AG. P TD SE P T 2005. All rights reserv ed.

Power Technogies
Instrument Transformer
Dimensioning, Page 8

Seite 4

Measuring current transformer


Dimensioning

Measuring CTs should be dimensioned that the connected burden including the
connecting cables is not exceeding the rated CT-burden.

Low burdened CTs jeopardize the connected measurement devices because of a


non occurring saturation.

Power Transmission and Distribution

Copyright SIEMENS AG. P TD SE P T 2005. All rights reserv ed.

Power Technogies
Instrument Transformer
Dimensioning, Page 9

Measuring current transformer


Examples for ordering indications

100/1 5 VA

-cl.

0.5

FS 5

100/1 5 VA

-cl.

0.5

FS 10 ext. 120%

200/1 5 VA

-cl.

0.2

FS 5

ext. 200%

(FS = Factor of security IEC 600 44-1)

There is also the classes S FS. The accuracy is also specified at 0.001 In (only for 5 Amps
secondary current) e.g.

100/ 5 20 VA -cl.

0.5S

FS 5

Power Transmission and Distribution

Copyright SIEMENS AG. P TD SE P T 2005. All rights reserv ed.

Power Technogies
Instrument Transformer
Dimensioning, Page 10

Seite 5