Anda di halaman 1dari 11

RDOL Starter

RAJ FABRICATOR

DATSON PROJECTS PVT. LTD.

Bill of Material for 0.5HP RDOL STARTER


Sr.No.

Description

Prepared
JRV

Checked
SAG

Approved
SAG

REV 0

24-Jul-14

Doc No.:
RAJFAB/DOL

Make

Qty.

Unit

Datson

No.

Schneider
Mimic

No.

Set

Wall Mounting Panel Size : 400H X 400W X 200D

II
1
2

MAIN INCOMER
TPN MCB 10 A
R,Y,B Lamp

III

FEEDER 0.5HP RDOL

TP MCB 6 A

Schneider

No.

Power Contactor 6A, Coil Voltage 230V AC, 1NO Contact,

Schneider

No.

3
4
5
6
7
8
9

Thermal Overload Relay (1 1.6A) with Base


On Indicating Lamps, Red, 230VAC
Trip Indicating Lamps, Amber, 230VAC
Start Push Button
Stop Push Button
Forward/Reverse selector switch
Emergency Stop push button mushroom head

Schneider
Teknic
Teknic
Teknic
Teknic
Teknic
Teknic

1
1
1
1
1
1
1

No.
No.
No.
No.
No.
No.
No.

IV

Panel Accessories
Panel accessories, wires, Terminals,
Hardware,Lugs,Ferrules,Name plates,pvc ducts &
markers etc.

STD

LOT

Page 1

Forward-Reverse panel logic


1. Interlock of Emergency stop PB will be provided to the total
control circuit. After pressing it, control circuit of the panel will be
disabled.
2. In Manual mode:
I.
Through Forward/Reverse Selector switch Direction of
motor will be decided.
II. Motor will be given start command through Start PB from
panel. Motor will run in selected direction and after reaching to
forward/reverse limit switch it will stop and run in the
opposite direction. Again in reverse direction, after reaching to
forward/reverse limit switch it will stop and run in the
opposite direction.
III. This process will be repeated N-number of times.
IV. In case motor is required to stop before reaching to
forward/reverse limit switch this will be done by Stop
PB
3. In Auto mode:
I.
Start command will be given to the motor & it will run in
Forward mode initially.
II.
Then while motor is running in forward mode, after some time
conveyor will come across a Forward/Reverse limit
switch. As soon as it touches this Forward/Reverse limit
switch it will start running in Reverse mode.
III. Now in Reverse mode same thing will happen, conveyor will
hit the same Forward/Reverse limit switch again and
motor will start rotating in Forward mode. This ForwardReverse (point II & III) cycle will run until Stop PB is
pressed.
IV.
Now when Stop PB is pressed, Motor will still be running in
the same direction (Forward or reverse) as it was, untill
conveyor comes across "Parking limit switch". When
conveyor touches this "Parking limit switch" then Motor will
stop.

List of DI/DOs :
A. Digital Inputs:
Sr. No.
1
2
3
4
5
6

DI
DI-1
DI-2
DI-3
DI-4
DI-5
DI-6

DI used for
Emergency CMD (Push Button)
Auto/Manual CMD (selector switch)
Start CMD (Push button)
Forward/Reverse limit switch
Stop CMD (Push button)
Parking limit switch

B. Digital Outputs:
Sr. No.
1
2

DI
DO-1
DO-2

DI used for
Motor Start/Stop CMD in F/W
Motor Start/Stop CMD in R/W

Anda mungkin juga menyukai