CHAPTER 7
STUDIES ON CORROSION RESISTANCE OF
STAINLESS STEEL CLADDINGS
7.1
INTRODUCTION
Corrosion is the destructive result of chemical or electrochemical
reactions between a metal or metal alloy and its surroundings. The nature of
this reaction depends not only on the chemistry of the system but also on the
structure of the metal. The grain boundaries, which are imperfect and high
energy regions, generally weaken the corrosion resistance of materials due to
the depletion of corrosion resistance alloying elements on the grain
boundaries.
There are several test methods for determining the Pitting and Inter
Granular Corrosion (IGC) of stainless steel claddings. The weight loss acid
test in which the Pitting and IGC rates are determined by measuring the
weight loss of the sample as per ASTM G-48-practice-A and ASTM A-262practice-C respectively for the stainless steel cladding. Another test method of
measuring the degree of sensitization to intergranular corrosion involves
electrochemical reactivation of the samples as defined in ASTM G-108. This
reactivation process is called Electrochemical Potentiokinetic Reactivation
(EPR) and has been developed in to two types: Single loop (SLEPR) and
Double loop (DLEPR). The SLEPR test is usually accounted to detect the
susceptibility of the cladding towards pitting corrosion resistance and the
135
PLAN OF INVESTIGATION
The investigations are carried out in the following sequence:
1.
attack
in
stainless
steel
claddings
as
per
3.
7.3
7.3.1
7.3.1.1
low (4.10 KJ/mm), high (6.81 KJ/mm), optimum (4.61 KJ/mm) heat input
condition as well as at optimum dilution (4.61 KJ/mm) and liquidnitrided
condition for conducting the test. The top surface of the specimens were
ground flat to facilitate maximum surface exposure to the corrosive test
solution. The test solution was prepared by adding 100 gm of Ferric Chloride
136
(Fecl3) to 900 ml of distilled water (6% Fecl3 by wt) as per ASTM standards.
The solution was considered appropriate because, the effect of Fecl3 was more
pronounced and also aggressive in the environments that could formulate
pitting corrosion.
7.3.1.2
Experimental procedure
The total immersion ferric chloride test was conducted as per ASTM
137
7.3.2
Experimental procedure
Intergranular attack in nitric acid is associated with the intergranular
precipitation of chromium carbides. The specimen was polished with 120 grit
abrasive paper and weighed initially. It was placed in a glass cradle is
presented in Figure 7.1 (a) and kept inside the Erlenmeyer flask fitted with an
Allihn condenser with four bulbs as presented in Figure 7.1 (b) to dissipate
the heat developed during boiling of the acid.
138
(a)
Figure 7.1
(b)
The flask was filled with sufficient quantity of the test solution to
cover the specimen and to provide a volume of 20 ml/cm2 of the specimen
surface. Cooling water was passed through the condenser for dissipating the
heat generated and the flask is electrically heated and maintained at 60C
thereby keeping the test solution boiling throughout the test period. The test
period was of 48 hours duration and after the end of each test period the
specimen was rinsed with water and scrubbed with a nylon brush under
running water to remove any adhering corrosion products. Then the specimen
was dried by dipping in acetone and weighed in an analytical balance. The
difference in weight is recorded for estimating the corrosion rate. This test
procedure was repeated for five consecutive boiling periods with duration of
48 hours for each period for every specimen. Fresh test solution was used
every time during the entire testing period.
139
7.4
7.4.1
conducting EPR tests. Figure 7.2 shows the surface of these specimens (I)
before and (II) after the EPR test.
(I)
Figure 7.2
(II)
Specimen with: (a) low heat input, 4.10 KJ/mm (b) high
heat input, 6.81 KJ/mm (c) optimum heat input, 4.61
KJ/mm and (d) optimum (4.61 KJ/mm) and liquid nitrided
condition, (I) before and (II) after Single loop EPR test
The top surface of the specimen was ground flat to facilitate 1 cm2
of the surface was exposed to the corrosive test solution. It was first polished
by a 600 grit SiC paper and further wet polished with 1 m alumina slurry on
a micro cloth mounted polishing wheel to a surface roughness of 6 m as per
ASTM E13 standards. Then they were washed with distilled water and dried
in a stream of cool air before immersing them in to the corrosive test solution.
The corrosion medium for the present investigation has been selected based
on the basis of corrosion environments as cited in the available literatures.
140
Experimental procedure
The potentiodynamic polarisation test was conducted to predict the
(a)
(b)
Figure 7.3
141
the test. The double loop EPR test was done according to ASTM G-108
standard and the recommendations made by Majidi and Streicher (1984). The
standard solution was modified to suit the austenitic stainless steel and
consisted of 2M H2SO4 + 0.5MNaCl + 0.01MKSCN at 30 1 C and a scan
rate of 15 V/h. The test was performed by running the sample from a potential
lower than Ecorr in the cathodic region. The potential is scanned in the anodic
direction from Ecorr to a point of 0.250 V in the middle of the passive region.
The scanning direction is then reversed and the potential is reduced back to
the cathodic region. Two loops are generated, an anodic loop and a
reactivation loop. The peak activation current (Ia) and the peak reactivation
current (Ir) were measured during the forward and backward scans,
respectively. The degree of sensitization was measured as the ratio of peak
activation current to the maximum current densities generated in the double
loop test (Majidi and Streicher, 1984).
142
7.6
7.6.1
7.6.1.1
the specimen after the test period and the weight loss was calculated for each
specimen. The corrosion rate was calculated by using the relation,
Corrosion rate = 7290 x W / A t, mm/month,
where W= the total weight loss of the specimen in grams,
A= the area of the specimen exposed in cm2,
= the density of the overlay material in grams / cm3 and
t= the time of exposure in hours.
The corrosion rate was calculated for each test period and the
average corrosion rate was referred against the ASTM acceptance limits for
all the four specimens cladded at different heat input conditions. The results
of the Total immersion ferric chloride test are presented in Table 7.1.
143
Table 7.1
No
Final weight
of the
specimen,
gm
Difference
in weight,
gm
Corrosion
rate,
mm/month
ASTM
acceptance
limit,
mm / month
Cladded at low
heat input
(4.10 KJ / mm)
30.8201
30.8111
0.009
0.0447
0.10 0.12
Cladded at high
heat input
(6.81 KJ / mm)
30.8112
30.7952
0.016
0.1142
0.10 0.12
30.8224
30.7994
0.023
0.0982
0.10 0.12
30.8212
30.8102
0.011
0.0459
0.10 0.12
Thermal history
of the specimen
Cladded at
optimum heat
input
(4.61 KJ / mm)
Cladded at
optimum heat
input
(4.61 KJ / mm)
and liquid
nitrided
condition
From Table 7.1 it is found that cladding produced at low heat input
and optimum conditions are having lower corrosion rates than that of other
claddings in ferric chloride solution.
7.6.1.2
144
No
Description
of the specimen
Total
corrosion
Total weight
rate,
loss , gms
mm / month
Average
corrosion
rate, mm /
month
ASTM
acceptance
limit,
mm /
month
0.5497
0.4101
0.0921
0.14 0.16
0.8855
0.5623
0.1182
0.14 0.16
0.9104
0.5912
0.1125
0.14 0.16
0.5738
0.4902
0.0881
0.14 0.16
Cladded at optimum
heat input (4.61 KJ /
mm)
Cladded at optimum
heat input (4.61 KJ /
mm) and liquid
nitrided condition
145
Figure 7.4
Figure 7.5
146
Figure 7.6
The slower cooling rates of the cladding due to higher heat input
promoted a coarser grain structure which does not have the normal
mechanical and metallurgical properties. Also, the slower cooling rates
promoted the formation of coarser grains with ditched structure. Their
bonding strength may not be evenly distributed due to the formation of
coarser grains with a lathy morphology (Arikan and Doruk 2008). The SEM
images reveal that the ditched type microstructure are highly prone to the
intergranular corrosion attack or sensitization than the stepped type structure.
The ditched type microstructure is presented at a higher
magnification for clearly visualising the corrosion debris after the Hueys teat,
in Figure 7.7.
147
Figure 7.7
7.6.2
along X-axis and potential along Y-axis using the analysis software. Typical
potentiodynamic anodic polarization curves of the specimens cladded at
corresponding conditions are shown in Figure 7.8 7.11. For each specimen,
the test was repeated twice in different areas and the average value was
recorded for the analysis. The current density was measured continuously
using commercial data acquisition software provided with the instrument.
Corrosion behaviour was investigated using potentiodynamic polarisation
measurements in 3.5 wt. % NaCl.
148
Figure 7.8
Figure 7.9
149
Figure 7.10
Figure 7.11
150
The rest potential (the potential at which the current becomes zero)
and the pitting potential are considered as a measure of the material
dissolution from the surface being tested. It has been referred that the passive
film on the surface was destroyed progressively with time and as a result
more and more of the metal (which is active) is exposed in the electrolyte.
The results are presented in Table 7.3. All potentials are vs. saturated calomel
electrode.
Table 7.3 Results of Single Loop EPR test
Sample
description
Corrosion
current
density,
(Icorr)
A cm-2
Rest
Potential,
mV
Pitting
Potential,
mV
-180
+410
7.2X10 -6
0.00202
0.07945
-120
+280
6.1X10 -6
0.04889
0.93534
-240
+ 260
8.3X10 -5
0.02378
1.92301
-120
+395
9.1X10 -6
0.00341
0.13413
Corrosion Corrosion
rate,
rate,
mils/yr
mm/year
Low heat
input of
4.10 KJ/mm
High heat
input of
6.81 KJ/mm
Optimum
heat input
4.61 KJ/mm
Optimum
heat input
4.61 KJ/mm
and nitrided
151
Figure 7.12
152
Figure 7.13
at high heat input condition showing ditched structure are presented in Figure
7.14 and 7.15 respectively.
Figure 7.14
153
Figure 7.15
cladded with optimum heat input (4.61 KJ/mm) and nitrided condition and a
ditched type microstructure with pits was noticed for the specimen cladded
with high heat input (6.81 KJ/mm). Stepped type microstructure might have
formed due to the faster cooling of the cladding at low heat input conditions.
The ditched type microstructure might have formed due to the slow cooling of
the cladding produced during higher heat input condition. It is found that the
stepped type microstructure possesses comparatively better resistance to
pitting corrosion than the ditched type microstructure.
7.6.3
logarithmic scale along X-axis and potential along Y-axis using the analysis
software. Typical potentiodynamic anodic polarization curves of the
claddings produced at the specified heat input conditions are presented in
Figure 7.16 7.19.
154
Figure 7.16
Figure 7.17
Figure 7.18
155
Figure 7.19
For each specimen, the test was repeated twice in different areas and
the average value was recorded for the analysis. The current density was
measured continuously using commercial data acquisition software provided
with the instrument. All potentials are vs. saturated calomel electrode. The
degree of sensitization was measured from the ratio of maximum current
densities generated in the double loop test (Majidi and Streicher 1984). The
results of the double loop EPR test is presented in Table 7.4.
156
No
Description
Low heat
input of
4.10 KJ/mm
High heat
input of
6.81 KJ/mm
Optimum
heat input
4.61 KJ/mm
Optimum
heat input
4.61 KJ/mm
and nitrided
7.7
Activation
peak
potential,
Ea ,(mV)
Activation
peak
current
density,
Ia, (mA/cm2)
Reactivation
Reactivation Passivation
peak
peak current
current
potential,
density,
density,
Er,(mV)
2
Ipass ,(mA/cm2)
Ir,(mA/cm )
Degree of
sensitization
( Ir /Ia
x100) %
-201.59
16.2439
-196.26
0.0096
0.0266
0.0589
-214.66
24.1534
-218.19
0.8752
0.0338
3.6236
-194.27
26.7205
-227.99
0.0089
0.0253
0.0334
-212.78
23.1305
-267.33
0.0064
0.0014
0.0276
SUMMARY
From the weight loss test with ferric chloride it can be concluded
that the nitrided cladding deposited at optimum heat input condition possessed
better pitting corrosion resistance. In the Hueys test, the claddings deposited
at low and optimum heat input conditions possessed better resistance to IGC.
Also from the single loop EPR test an increase in pitting potential is noticed
in the cladding deposited with optimum heat input condition. The positive
value of pitting potential indicates that a stable film is formed over the surface
of the cladding which confirms that the material is more nobler with increased
pitting corrosion resistance. In the double loop EPR test the ratio of the degree
of sensitisation (Ir/Ia) was found to be very lower in the cladding deposited at
157
optimum heat input condition, which reveal that the cladding possesses better
resistance to IGC.