LV circuit-breakers

Multi 9 C60, C120

At our place,
protection is a
natural legacy
In the field of protection,
the new C120’s performances
are going to amaze you
With the new C120, direct descendent from the C60, the
Multi 9 system now offers a completely uniform range
of circuit-breakers and earth leakage modules (1 to 125 A).
The C120 has all the advantages of the C60: a wide range of
possible solutions, connection dependability, auxiliaries are
simple to connect, and a few innovative products waiting to be
discovered. In the field of protection, offering the best solutions to
respond to electricians’ needs has always been a spontaneous
reaction for Merlin Gerin.
Innovations

Circuit-breaker Vigi module combination conform Circuit-breaker Vigi module connection using
with EN 61009 standard ridgid wires; Common C60/C120 indication and
tripping auxiliaries
f u l]
c c ess
[ s u Success of a tested
and approved range
It’s not by pure chance that Multi 9 devices
are renowned throughout the world for their
quality.

c Development centres, production and


distribution units have been certified
according to the ISO 9000 standard.

c The C60/C120 range must be conform


with internal qualification tests that have
been elaborated by Schneider Electric’s
quality departments. A complement to
standards, these tests qualify products in
harsh environmental conditions (extreme
cold, heat, dust, humidity) and operating
conditions (falls, shocks, tearing out,
vibrations, etc.).
Moreover, as the proud descendent of
Merlin Gerin traditions, the C60/C120 range
presents high performances according to
industrial standards (IEC 60947-2).

The C60 opened the path to success by


becoming the most sold modular circuit-
breaker in the world. With the C120, the
range is extended to give you a wide
choice from 1 to 125 A.
[Discover]a complet and coherent

p l e ]
[ s im The priority is
simplifying installation
The C60/C120 range offers an infinite
number of possible combinations that are
simple to carry out.

c Residual current device assembly is


simple, fast and safe for minimum
dimensions.

c Snap-on auxiliaries are adapted in a


wink. Common to all Multi 9 protective
switchgear, they are always available. The
new changover, double SD/OF auxiliary
makes the choice even easier. But
simplicity also means being able to verify
the correct functioning of light indicators
and open circuit indicators.

c For all power connections, all you need is


a single screwdriver whatever the device
rating.
circuit-breaker range from 1 to 125 A

a fe]
[s All of Merlin Gerin’s
know-how in the field
of protection
For user safety, the C60/C120 range is
completely conform with EN 60898 and
EN 61009 standards. Circuit-breakers,
residual current devices from 1 to 125 A,
all of the C60/C120 devices have their
place in switchboards that can be
“accessed by non-specialists”.

Essential for the safety of persons,


earth leakage protection is advancing
by leaps and bounds thanks to the
Vigi C60/C120.
c The first range that is completely
conform with the EN 61009 standard:
v residual current device assembly can be
carried out without the risk of making
mistakes,
v technical data for circuit-breakers that are
fitted out with RCDs remain unchanged
(no derating).
c New variations of the Vigi module of the
“si” type to optimise the continuity of
electrical power supply.
Capable of distinguishing real dangers
from false alerts, they are recommended,
for example, for the protection of
micro-computers, fluorescent lighting and
in systems that are exposed to lightening
or low temperatures.
oic e ]
[ ch A wide choice
in response to all
your needs
With over 800 product references to meet
your specific needs and common
auxiliaries to simplify your purchases,
the C60/C120 range is truely your systems
partner.
It is available at your local retailer - a
Schneider Electric partner chosen for its
sense of service; someone will be there
to give you the best advice in the field
as well.
The Guiding System,
the new way to make your
electrical installations
Multi 9 C60, C120 are part of a comprehensive product offer
with a consistent design.
The Guiding System is first a Merlin Gerin product offer covering all
the needs of LV and MV electrical distribution: SM6 electrical
switchboards from 1 to 36 kV, Satia ultra compact MV/LV substation
from 250 to 360 kV A, Compact and Masterpact circuit-breakers
from 100 to 3 200 A, modular enclosures and switchgear up to
125 A, Prisma + distribution switchboard functional system up to
3 200 A. All these products are designed to operate together:
electrical, mechanical and communication consistency.
Thus the electrical installation is both optimised and more efficient:
better continuity of supply, enhanced safety for people and
equipment, guaranteed open-endedness, effective supervision
and control.

Tools for simplified design and implementation


With the Guiding System you have a complete range of tools
– the Guiding Tools – that accompany you in knowledge and
implementation of Merlin Gerin products, while complying with
current standards and proper procedures.
These tools, technical books and guides, design aid software,
training courses, etc. are updated regularly.

For a genuine partnership with you


Because each electrical installation is a special case, there is no
universal solution. With the Guiding System, the variety of
combinations allows a genuine customisation of technical solutions.
You can express your creativity and enhance your know-how in
design, production and operation of an electrical installation.
You and Merlin Gerin’s Guiding System form a genuine partnership.
M9DP30Ben © 2004 Schneider Electric - All rights reserved

Schneider Electric SAS


89, boulevard As standards, specifications and designs develop from time to time, always ask for
Franklin-Roosevelt confirmation of the information given in this publication
92506 Rueil-Malmaison Cedex
(France) this document has been printed
Tel.: +33 (0)1 41 29 85 00 on ecological paper
http://www.schneider-electric.com
Published by: Communication BTT-S2E
Design and layout by: Paco - Sedoc
Photos by: Schneider Electric, Arnaud Childeric
Printed by:

11/2004
C60H circuit-breaker
Multi 9 Merlin Gerin

The C60H circuit-breaker is a miniature circuit-breaker used for the


protection of circuits in industry and the tertiary sector.
It ensures the following functions: protection against short-circuit and
overload currents, isolation, protection of persons against indirect contact
with IT and TN earthing systems.

Operation
c 1 to 4-pole circuit-breakers.
c Control and protection:
v B curve: against circuit overcurrents including protection of persons with
IT and TN earthing systems for larger longer cables,
C60H: 25870 v C curve: against the overcurrents of circuits feeding conventional loads,
v D curve: against the current of installations containing loads with high
inrush currents (motors, transformers).

Advantages
c Conformity with international standards: IEC 898 and IEC 947-2.
c Ratings from 0.5 to 63 A.
c Breaking capacity of 10 000 A under 400 V.
c Clip-on electrical auxiliaries and add-on accessories.

The range
Remote control C60H circuit-breaker
(M9 FP 37/A .en
product sheet) A1

MERLIN GERIN

multi 9

Tm

S
A

230V
a
C60 1-2
MERLIN GERIN
multi 9
C60H
C63
400Va
6000
Vigi C60 module
(M9 FP 73/A .en
D
10kA IEC 947.2
auto
A
18310 25652

O - OFF

product sheet)
A2 1P

+
MERLIN GERIN
MERLIN GERIN multi 9

and/or multi 9 vigi C60

Auxiliaries
C60H I∆N 0,030A a T02
C40 N/1 3 T
400Va N 1
6000 4
N/2
10kA IEC 947.2
26509 test
25719 N 2

O - OFF O - OFF

(M9 FP 74/A .en


product sheet) 2P 2P

+ +
MERLIN GERIN
MERLIN GERIN MERLIN GERIN MERLIN GERIN multi 9
OF SD multi 9 multi 9 multi 9 vigi C60
MX OF MN C60H I∆N 0,030A a T02
N/1 3 5
D1 D2 C25 T

Test U< 400Va 1 3 5


110.130V 6000 N/2 4 6
220.415Va 220.415Va 10kA IEC 947.2
reset 26531 test
26924 26927 26946 26960 25731 2 4 6

O - OFF O - OFF O - OFF

3P 3P
OF SD MX + OF MN or
MNs
MERLIN GERIN
multi 9
C60H
C63
400Va
6000
10kA IEC 947.2

25223

O - OFF
1 3 5 7

2 4 6 8

O - OFF O - OFF O - OFF


+ MERLIN GERIN
multi 9
vigi C60
I∆N 0,300A a
N/1 3

26533
5 7
T02

N/2 4
test
6 8
T

4P 4P

C 2

C 2
1 1 1 1 1 1 1 1 1 1 1 1 1

Comb busbars Clip-on markers Padlocking


device

Rotary
handle

Accessories
Terminal shield Screw shield (M9 FP 75/A .en product sheet)

We do more with electricity.


Selection table Implementation
type width in rating curves c Designed for installation in modular enclosures and switchboards.
mod. of (A) ref. c Easy mounting on symmetrical rail.
9 mm B C D c Easy connection using serrated tunnel terminals with flap.
1P 2 0.5 24900 25171 c Captive screws with mixed +/- indent.
1 0.75 24901 c Simplified clip-on combination of circuit-breaker with auxiliaries.
1 25839 25639 25695 c Use of comb busbars to simplify circuit-breaker connection.
2 25840 25640 25696
4 25841 25642 25698
6 25842 25643 25699
10 25843 25644 25700
C 2
C 2

2 16 25844 25645 25701


20 25845 25646 25702
MERLIN GERIN MERLIN GERIN
multi 9

25 25846 25647 25703 OF

Test
multi 9
C60N
C25
400Va 1 3
C60N
C25
400Va
6000
1 3
6000
10kA IEC 947.2
10kA IEC 947.2 MERLIN GERIN MERLIN GERIN

32 25847 25648 25704 26924


24204

O - OFF
2 4

O - OFF
multi 9
MN
D1 D2
multi 9
C60N
C25
400Va 1 3
24204

O - OFF
2 4

O - OFF

U<
6000

40 25848 25649 25705


10kA IEC 947.2
220.415Va
26960 24204 2 4

O - OFF O - OFF

50 25849 25651 25707


63 25850 25652 25708
2P 4 0.5 24902 25172
1 3 0.75 24903
Example: upstream comb busbar connection
1 25852 25653 25709
2 25853 25654 25710
4 25854 25656 25712 Technical data
6 25855 25657 25713 Electrical data
10 25856 25658 25714 c Power circuit:
2 4 16 25857 25659 25715 v voltage rating: 440 V AC,
20 25858 25660 25716 v ratings from 0.5 to 63 A set at 30°C,
25 25859 25661 25717 v breaking capacity:
32 25860 25662 25718 - as in IEC 898 - as in IEC 947-2 (Icu)
40 25861 25663 25719 rating number voltage breaking rating number voltage breaking
50 25862 25665 25720 (A) of poles (V) capacity (A) (A) of poles (V) capacity (A)
63 25863 25666 25722 0.5 to 63 1P 230 to 400 10 000 0.5 to 63 1P 230 to 240 15 000
3P 6 0.5 24906 25173 2P, 3P, 4P 400 to 415 10 000 415 4 000 (1)
1 3 5 0.75 24907 2P, 3P, 4P 230 to 240 30 000
1 25865 25667 25723 400 to 415 15 000
2 25866 25668 25724 440 10 000
(1)
4 25867 25670 25726 1-pole breaking capacity with IT isolated neutral
6 25868 25671 25727 system (double fault)

10 25869 25672 25728 v limitation class (IEC 898): 3,


2 4 6 16 25870 25673 25729 v fast closing: increased withstand to the high inrush currents of certain
20 25871 25674 25730 loads,
25 25872 25675 25731 v isolation with positive break indication: opening is indicated by a green
32 25873 25676 25732
strip on the device’s control toggle.
40 25874 25677 25733
This indicates that all poles are open.
50 25875 25679 25735
Tripping curves
c B curve:
63 25876 25680 25736
v magnetic releases operate between 3 and 5 ln.
4P 8 0.5 24908 25174
1 3 5 7
c C curve:
0.75 24909
v magnetic releases operate between 5 and 10 ln.
1 25878 25007 25211
c D curve:
2 25879 25008 25212
v magnetic releases operate between 10 and 14 ln.
4 25880 25010 25214 Mechanical data
6 25881 25011 25215 c Connection by tunnel terminals for the following cables:
10 25882 25012 25216 v 16 mm2 flexible or 25 mm2 rigid for up to 25 A ratings,
2 4 6 8 16 25883 25013 25217 v 25 mm2 flexible or 35 mm2 rigid for 32 to 63 A ratings.
20 25884 25014 25218 c Durability: 20 000 cycles (O-C).
25 25885 25015 25219 c Dimensions (w x h x d mm): 18 x N (number of poles) x 81 x 70.
32 25886 25016 25220 c Weight (g): 1P: 120, 2P: 240, 3P: 360, 4P: 480.
40 25887 25017 25221
50 25888 25018 25222
63 25889 25019 25223
Environment Certification
NF
230 to 400 V AC c Tropicalisation: treatment 2 UTE: NF USE
240 to 415 V AC (relative humidity: 95 % at 55°C).
c Degree of protection:
v of enclosure: IP 40,
M9FP71AEN

v of terminals: IP 20.
c Operating temperature:
-5°C to +60°C.
c Storage temperature:
-40°C to +100°C.

Schneider Electric SA Merlin Gerin As standards. specifications and designs develop from time to This document has been
F-38050 Grenoble cedex 9 time, always ask for confirmation of the information given in printed on ecological paper
tel. +33 (0)4 76 57 60 60 this publication.
telex : merge 320 842 F Published by: Communication BT-S2E
Design and layout by: Sodipe (38)

DIT E D1 97 035 en
ART. 07/00
C60L circuit-breaker
Multi 9 Merlin Gerin

The C60L circuit-breaker is a miniature circuit-breaker used for the


protection of circuits in industry and the tertiary sector.
It ensures the following functions: protection against short-circuit and
overload currents, isolation, protection of persons against indirect contact
with IT and TN earthing systems.

Operation
c 1 to 4-pole circuit-breakers.
c Control and protection:
v B curve: against circuit overcurrents including protection of persons with
IT and TN earthing systems for large longer cables,
v C curve: against the overcurrents of circuits feeding conventional loads,
C60L: 26224 v K curve: against the overcurrents of impedant circuits: motors
(circulation pumps, pumps, ventilators), transformers, auxiliary circuits
(coil, contactor), etc.,
v Z curve: against the overcurrents of electronic circuits (silicon rectifiers,
diodes, thyristors, triacs, etc.).

Advantages
c Conformity with international standards: IEC 947-2.
c Ratings from 0.5 to 63 A.
c Breaking capacity of 25 000 A under 400/415 V.
c Clip-on electrical auxiliaries and add-on accessories.

The range
Remote control C60L circuit-breaker
(M9 FP 37/A .en
product sheet) A1

Vigi C60 module


MERLIN GERIN
MERLIN GERIN
multi 9
multi 9
C60N
Tm C63
A C60 1-2
400Va
a
S
230V
6000
D 10kA IEC 947.2

(M9 FP 73/A .en


auto
A
18310 24182

O - OFF

1P
product sheet)
A2

Auxiliaries
(M9 FP 74/A .en
product sheet)
and/or

2P
MERLIN GERIN
multi 9
C60N
C40
400Va
6000
10kA IEC 947.2

24193

O - OFF
N 1

N 2

O - OFF
+ MERLIN GERIN
multi 9
vigi C60
I∆N 0,030A a
N/1 3

26509
N/2 4
T
T02

test

2P

+ +
MERLIN GERIN
MERLIN GERIN MERLIN GERIN MERLIN GERIN multi 9
OF SD multi 9 multi 9 multi 9 vigi C60
MX OF MN C60N I∆N 0,030A a T02
N/1 3 5
D1 D2 C25 T

Test U< 400Va 1 3 5


110.130V 6000 N/2 4 6
220.415Va 220.415Va 10kA IEC 947.2
reset 26531 test
26924 26927 26946 26960 24217 2 4 6

O - OFF O - OFF O - OFF

3P 3P
OF SD MX + OF MN or
MNs

4P
MERLIN GERIN
multi 9
C60N
C63
400Va
6000
10kA IEC 947.2

23974

O - OFF
1 3 5 7

2 4 6 8

O - OFF O - OFF O - OFF


+ MERLIN GERIN
multi 9
vigi C60
I∆N 0,300A a
N/1 3

26533
5 7
T02

N/2 4
test
6 8
T

4P

C 2

C 2
1 1 1 1 1 1 1 1 1 1 1 1 1

Comb busbars Clip-on markers Padlocking


device

Rotary
handle

Accessories
Terminal shield Screw shield (M9 FP 75/A .en product sheet)

We do more with electricity.


Selection table Implementation
type width in rating curves c Designed for installation in modular enclosures and switchboards.
mod. of (A) ref. c Easy mounting on symmetrical rail.
9 mm B C K Z c Easy connection using serrated tunnel terminals with flap.
1P 2 0.5 25406 c Captive screws with mixed +/- indent.
1 1 25392 25460 26133
c Simplified clip-on combination of circuit-breaker with auxiliaries.
1.6 25461 26134
2 25393 25462 26135
c Use of comb busbars to simplify circuit-breaker connection.
3 25394 25463 26136
4 25395 25464 26137
6 25331 25396 25465 26139
10 25332 25397 25467 26141 C 2

2 16 25333 25398 25468 26142


C 2

20 25334 25399 25469 26143


25 25335 25400 25470 26145
32 25336 25401 25471 26146 OF
MERLIN GERIN
multi 9
C60N
C25
MERLIN GERIN
multi 9
C60N
C25
400Va 1 3

40 25337 25402 25472 26147


400Va 1 3
Test 6000
6000
10kA IEC 947.2
10kA IEC 947.2 MERLIN GERIN MERLIN GERIN
24204 2 4
26924
24204 2 4 multi 9 multi 9
O - OFF O - OFF MN C60N O - OFF O - OFF

50 25338 25403 25473 D1 D2


U<

220.415Va
C25
400Va
6000
10kA IEC 947.2

24204
1 3

26960 2 4

63 25339 25404 25474 O - OFF O - OFF

2P 4 0.5 25407
1 3 1 25418 25478
1.6 25479 26154
2 25419 25480 26155 Example: upstream comb busbar connection
3 25420 25481 26157
4 25421 25482 26158
6 25357 25422 25483 26159
10 25358 25423 25485 26161
2 4 16 25359 25424 25486 26163
Technical data
20 25360 25425 25487 26164 Electrical data
25 25361 25426 25488 26165 c Power circuit:
32 25362 25427 25489 26166 v voltage rating: 440 V AC,
40 25363 25428 25490 26167 v ratings from 0.5 to 63 A set at 40°C,
50 25364 25429 25491
v breaking capacity:
63 25365 25430 25492
3P 6 0.5 25408
- as in IEC 947-2 (Icu)
1 3 5 1 25431 25496 rating number voltage breaking
1.6 25497 26174 (A) of poles (V) capacity (A)
2 25432 25498 26176 0.5 à 25 1P 230 to 240 25 000
3 25433 25499 26177 415 6 000 (1)
4 25434 25500 26178 2P, 3P, 4P 230 to 240 50 000
6 25370 25435 25501 26180 400 to 415 25 000
10 25371 25436 25503 26182 440 20 000
2 4 6 16 25372 25437 25504 26184 32 à 40 1P 230 to 240 20 000
20 25373 25438 25505 26185 415 5 000 (1)
25 25374 25439 25506 26224 2P, 3P, 4P 230 to 240 40 000
32 25375 25440 25507 26225 400 to 415 20 000
40 25376 25441 25508 26226 440 15 000
50 25377 25442 25509 50 à 63 1P 230 to 240 15 000
63 25378 25443 25510 415 4 000 (1)
4P 8 0.5 25409 2P, 3P, 4P 230 to 240 30 000
1 3 5 7 1 25444 25514 400 to 415 15 000
1.6 25515 26232 440 10 000
(1)
2 25445 25516 26234 1-pole breaking capacity with IT isolated neutral system (double fault)
3 25446 25517 26236 v limitation class (EN 60 898): 3,
4 25447 25518 26237
6 25383 25448 25519 26239
v fast closing: increased withstand to the high inrush currents of certain
10 25384 25449 25521 26241 loads,
2 4 6 8 16 25385 25450 25522 26242 v isolation with positive break indication: opening is indicated by a green
20 25386 25451 25523 26243 strip on the device’s control toggle.
25 25387 25452 25524 26244 This indicates that all poles are open.
32 25388 25453 25525 26245 Tripping curves
40 25389 25454 25526 26246 c B curve:
50 25390 25455 25527
v magnetic releases operate between 3.2 and 4.8 ln.
63 25391 25456 25528
c C curve:
v magnetic releases operate between 7 and 10 ln.
c K curve:
Environment v magnetic releases operate between 10 and 14 ln.
c Tropicalisation: treatment 2 c Z curve:
(relative humidity: 95 % at 55°C) v magnetic releases operate between 2.4 and 3.6 ln.
c Degree of protection: Mechanical data
v of enclosure: IP 40, c Connection by tunnel terminals for the following cables:
v of terminals: IP 20. v 16 mm2 flexible or 25 mm2 rigid for up to 25 A ratings,
c Operating temperature: v 25 mm2 flexible or 35 mm2 rigid for 32 to 63 A ratings.
M9FP72AEN

-5°C to +60°C. c Durability: 20 000 cycles (O-C).


c Storage temperature: c Dimensions (w x h x d mm): 18 x N (number of poles) x 81 x 70.
-40°C to +100°C. c Weight (g): 1P: 120, 2P: 240, 3P: 360, 4P: 480.

Schneider Electric SA Merlin Gerin As standards. specifications and designs develop from time to This document has been
F-38050 Grenoble cedex 9 time, always ask for confirmation of the information given in printed on ecological paper
tel. +33 (0)4 76 57 60 60 this publication.
telex : merge 320 842 F Published by: Communication BT-S2E
Design and layout by: Sodipe (38)

DIT E D1 97 036 en