Anda di halaman 1dari 52

Main Catalogue

Softstarters
Type PSR
Type PSS
Type PST/PSTB

Catalogue 1SFC132004C0201 December 2006

Supersedes Catalogue 1SFC132001C0201 of May 2005

g
intin
r
p
r
e
d aft -21 and
e
t
s
Adju 2006-12
:
df
Date 02-01 ings in the p3 and 38
,2
ark
2007e yellow m 10, 11, 22
h
e
See t t on pag
rin
p
is
M

(1SFC132198F0001)

Softstarters
News
Torque control

New

The latest version of the PST(B) softstarter


offers a new functionality called Torque
control. With this function enabled the
voltage of the motor is regulated so that
the torque follows a predened torque curve during
start and stop. Torque control is especially useful in
pump applications where a sudden stop can cause
water hammering and pressure surges.

New

Analog output

With the latest version of the PST(B) softstarter it


is possible to have analog output signals from the
softstarter. These signals can then be used as input
to a PLC or an analog meter.

New

Type PSR Softstarter

New

Complete range

The latest addition to the ABB softstarter range is the


compact PSR softstarter. This new softstarter has a
compact, attractive design and is ideal for installation
in places where space is limited and where there is a
demand for easy installation.
With the new PSR softstarter, ABB offers a complete
range of softstarters from 3 to 1810 A. This complete
range consists of the three models PSR, PSS and
PST(B).

ABB Softstarters the complete range


Functionality

PST/PSTB

PSS

Advanced

Flexible

PSR

Compact
45

2
1SFC132004C0201

515

1810 Ampere

Softstarters

Contents
Page
General .
4
The complete range .............................................................................................................. 5
Softstarters, type PSR
Overview ............................................................................................................................... 6
Description ............................................................................................................................ 7
Ordering (incl. accessories) .................................................................................................... 8
Technical data, UL ratings ..................................................................................................... 9
Softstarters, type PSS
Overview ............................................................................................................................. 10
Application and Description ................................................................................................. 12
Ordering .............................................................................................................................. 14
Accessories......................................................................................................................... 18
Technical data ..................................................................................................................... 19
UL ratings ........................................................................................................................... 21
Softstarters, type PST
Overview ............................................................................................................................. 22
Application and Description ................................................................................................. 24
Ordering .............................................................................................................................. 26
Accessories......................................................................................................................... 30
FBP Field Bus Plug.............................................................................................................. 31
Technical data ..................................................................................................................... 37
UL ratings ........................................................................................................................... 41
Wall mounting instruction .................................................................................................... 42
Dimensions ......................................................................................................................... 43
Circuit diagrams .................................................................................................................. 46
Certications and approvals ................................................................................................ 49
Leader in power and automation technologies,
Division Automation Products, Low voltage products .......................................................... 51

Some information about the catalogue:


Ordering details:
When placing an order please give either the Type or the Order
code. Please note that for some of the products you need to ll in
some additional code letters/code numbers to dene the complete
Type/Order code.
Packing:
All softstarters and most of the accessories are delivered in an
individual packing. Some of the accessories are packed together
in batches of n pieces (see ordering Packing pieces). For these
items, please order the total amount corresponding to a multiple
of the number in the packing. Example: If two in the packing, then
please order minimum two, four, six etc.
Note: Each Type or Order code always corresponds to only one
piece.
The products described in this catalogue are subject to change (design,
dimensions, technical data, etc.) without prior notice.

3
1SFC132004C0201

(1SFC132145F0001)

Softstarters
From the moment the rst electrical motors appeared, engineers have been searching a way to avoid electrical and
mechanical problems that occur using Direct-on-Line and
Star-Delta starters. ABB has been producing softstarters
since the beginning of the 1980s. The valuable experience
gained since the early 80s has been incorporated into the
design of todays product ranges. With the latest series
named PST, ABB has taken a signicant step further in soft
starting technology. Matching modern power electronics
with smart circuitry and software, the new PST softstarter
offers superior electronic control of the current and voltage
during motor start-up, in addition to several new design
features.

Motor voltage
V

DoL

Star/Delta

70 %
58 %
30 %

Motor current

AC motors, the workhorse of the industry, that are used to


drive fans, crushers, agitators, pumps, conveyors etc., are
unnecessarily causing unwanted load peaks day in and day
out in production plants all over the world. These violent starts
cause damage in several ways. Among them are:

DoL

Electrical problems due to voltage and current transients


arising from Direct-on-Line or Star-Delta starts. Such transients may overload the local supply network and cause
unacceptable voltage variations that interfere with other
electrical equipment connected to the network.

Mechanical problems that address the entire drive chain,


from motor to driven equipment, to severe stress.

Operational problems, such as pressure surges in pipelines,


damage to products on conveyor belts and uncomfortable
escalator rides.

The nancial consequences are considerable: every technical problem and every breakdown, costs money in terms of
repairs as well as lost production.
The easy solution to all of these problems is to install an ABB
Softstarter type PSR, PSS or PST. With ABB Softstarters, it is
possible to start and stop smoothly while keeping mechanical
and electrical stresses to a minimum.

Adjustable
ramp slope

Time

The solution to both mechanical and electrical problems

Softstart

100 %

I
Star/Delta

Softstart

Motor speed

Torque
T

DoL

Star/Delta

Softstart

Motor speed
Graphs showing the basic differences between direct-on-line starting (DoL), star-delta starting and soft starting in terms of the motor
voltage (V), motor current (I) and motor torque (T).

4
1SFC132004C0201

(1SFC132177F0001)

(1SFC132184F0001)

ABB softstarters The complete range


ABB offers three different ranges of softstarters to cover
every customer need for solutions for small to mediumsized motor applications, from 3 A to 1810 A. The overview
table at the bottom of this page shows the main characteristics of the different types. For more specic technical
details and ordering data, see the following pages.

Compact Range

Type PSR, covers motor currents from 3 to 45 A. It is the latest


addition to the softstarter family and has an attractive, compact
design. Further, the system concept includes MMS and the
softstarters are available for remote control connection using
the FieldBusPlug as an accessory. All sizes include a Run signal
relay, while from sizes 25 A the PSR Softstarters are also provided with an output signal for TOR (Top Of Ramp), i.e. full voltage). With standard performance the PSR Softstarters handle
ten starts per hour. When an auxiliary cooling fan is added, the
starting capacity is increased to 20 starts per hour.
Current ratings 3.9 45 A (1.5 - 22 kW), at 400 V
Motor voltage 208 600 V
Supply voltage 24 V DC or 100-240 V AC
Easy to install and adjust
DIN rail or screw mounting
Integrated by-pass contacts
With their compact design, the PSR Softstarters are ideal for
installation in places where space is limited and where there is a
demand for easy installation.

Flexible Range

Type PSS, covers motor currents from 18 to 300 A and offers


a exible solution with easy installation and setup.
Flexible: With two connection possibilities, either in line with
the motor or inside the motor delta. It can also be equipped
with current limit.
Easy to set up: With just three clearly labeled rotary
switches on the front of the unit it is possible to adjust the
PSS Softstarter for a wide range of applications.
Solid state electrical circuit: This ensures the highest
reliability and reduces maintenance to a minimum,
even in applications with frequent starts and stops.

Advanced Range

Type PST(B), covers motor currents from 30 to 1050 A and


provides advanced functionality, including integrated protections, programmable signal relays, a exible communication

system and an LCD display. Sizes PSTB370 to 1050 A include


a by-pass contactor.
Advanced integrated protections: For the motor; integrated electronic overload relay, phase monitoring relays,
high current and PTC protection. For the Softstarter; advanced thyristor protection.
Flexible bus communication system: By using the ABB
FieldBusPlug (FBP), you can decide at any time which bus
system to select within the ABB FBP range. The interface
between the PST Softstarter and the ABB FBP is always the
same, independent of size and delivery date.
LCD display: With 13 languages, a menu system
similar to your mobile phone, preprogrammed application
settings and automatic status and event logging, it couldnt
be easier to set up and operate!
Programmable signal relays: gives you several possibilities for signalling warnings, faults and other events.
Torque control: allows you to start and stop motors with
a more linear acceleration than when using voltage ramp.
PSR3 ...45
PSS18/30 ...300/515
PST30 ... PSTB1050B
O

1)

Standard
O Optional
Not available

Field bus communication enabled


Real time clock
Programmable fault supervision functions
Programmable warning functions
PTC input for motor protection
High current protection
Phase imbalance /phase reversal protection
Locked rotor protection
Thyristor overtemperature protection
Motor overload protection
Four button keypad (external keypad available)
External keypad
Current limit control
In Line and Inside Delta connection
LED indications
Built-in by-pass contactor (1) On PSTB)
Ramp Start/Stop
Torque control
Analog output

5
1SFC132004C0201

Softstarters

1SFC132137F0001

1SFC132136F0001

Type PSR
Overview

PSR3 ... PSR16

PSR25 ... PSR30

Softstarter, Type
Normal start:
In Line connected
In Line connected

400 V
kW
A
480 V
hp
A

PSR3

PSR6

PSR9

PSR12

PSR16

PSR25

PSR30

1.5
3.9

3
6.8

4
9

5.5
12

7.5
16

11
25

15
30

2
3.4

3
6.1

5
9

7.5
11

10
15.2

15
24.2

20
28

MS116

MS116

MS325

MS450

400V, 40 C
Manual motor starter, Type
If using manual motor starters
type 1 coordination will be
achieved.

MS116

MS116

Fuse protection 400 V, 65 kA, 40 C,

gG Fuse

Using gG fuses type 1


coordination will be achieved.

10 A

25 A

32 A

32 A

50 A

63 A

Suitable switch fuse for the


above gG fuses..

OS32D

OS32D

OS32D

OS32D

OS32D

OS32D

A9

A12

A16

A26

A30

TA25DU

TA25DU

TA25DU

TA25DU

TA25DU

Built-in

Built-in

Built-in

Built-in

Built-in

16 A

MS116

Switch fuse, Type


OS32D

Line contactor, Type


The line contactor is not required
for the softstarter itself but often
used to open if OL trips.

A9

The overload relay is always


required to protect the motor.

TA25DU

A9

Thermal overload relay, Type


TA25DU

By-pass contacs
Built-in

6
1SFC132004C0201

Built-in

Softstarters

Type PSR
Overview and description
Description

1SFC132135F0001

PSR - Compact range, covers motor currents from 3 to 45 A. It is the


latest addition to the softstarter family and has an attractive, compact
design. Further, the system concept includes MMS and the softstarters
are available for remote control connection using the FieldBusPlug as an
accessory. All sizes include a Run signal relay, while from sizes
25 A the PSR Softstarters are also provided with an output signal for
TOR (Top Of Ramp), i.e. full voltage. With standard performance the
PSR Softstarters handle ten starts per hour. When an auxiliary cooling
fan is added, the starting capacity is increased to 20 starts per hour.
Current ratings 3.9 45 A (1.5 - 22 kW), at 400 V
Motor voltage 208 600 V
Supply voltage 24 V DC or 100-240 V AC
Easy to install and adjust
DIN rail or screw mounting
Integrated by-pass contacts

PSR37 ... PSR45


Softstarter, Type
PSR37

PSR45

18.5
37

22
45

25
34

30
46.2

With their compact design, the PSR Softstarters are ideal for installation
in places where space is limited and where there is a demand for easy
installation.

Settings

400V, 40 C
Manual motor starter, Type
MS450

MS450

Fuse protection 400 V, 65 kA, 40 C,


100 A

Switch fuse, Type


OS63D

OS125D

2
3

Line contactor, Type


A40

gG Fuse

125 A

A50

Thermal overload relay, Type


TA42DU

TA75DU

By-pass contacts
Built-in

Built-in

3 U
ini

time
Start

Stop

1 Ramp time START = 1 ... 10 sec


2 Ramp time STOP = 0 ... 20 sec
3 Initial voltage U =40 ... 70 %
ini

(also set end voltage)

7
1SFC132004C0201

Softstarters

Type PSR3 ... PSR45


Ordering details
Motor power

1SFC132137F0001

230 V
Pe
kW

Max rated motor


current, Ie
A

Weight
kg
1 piece

Type

Order code

PSR3-600-70
PSR6-600-70
PSR9-600-70
PSR12-600-70
PSR16-600-70
PSR25-600-70
PSR30-600-70
PSR37-600-70
PSR45-600-70

1SFA 896 103 R7000


1SFA 896 104 R7000
1SFA 896 105 R7000
1SFA 896 106 R7000
1SFA 896 107 R7000
1SFA 896 108 R7000
1SFA 896 109 R7000
1SFA 896 110 R7000
1SFA 896 111 R7000

0.45
0.45
0.45
0.45
0.45
0.65
0.65
1.00
1.00

PSR3-600-81
PSR6-600-81
PSR9-600-81
PSR12-600-81
PSR16-600-81
PSR25-600-81
PSR30-600-81
PSR37-600-81
PSR45-600-81

1SFA 896 103 R8100


1SFA 896 104 R8100
1SFA 896 105 R8100
1SFA 896 106 R8100
1SFA 896 107 R8100
1SFA 896 108 R8100
1SFA 896 109 R8100
1SFA 896 110 R8100
1SFA 896 111 R8100

0.45
0.45
0.45
0.45
0.45
0.65
0.65
1.00
1.00

Description

Type

Order code

Fieldbus Plug Connection Accessory


The same accessory for all sizes

PSR-FBPA

1SFA 896 312 R1001

0.06

Connection kit for PSR3-16 and MS116

PSR16-MS116

1SFA 896 211 R1001

0.03

Connection kit for PSR37-45 and MS450

PSR45-MS450

1SFA 896 213 R1001

0.03

PSR-FAN

1SFA 896 311 R1001

0.01

Supply voltage, Us 100-240 V AC


0.75
1.5
1.5
3
2.2
4
3
5.5
4
7.5
5.5 11
7.5 15
7.5 18.5
11
22

1SFC132136F0001

2.2
4
4
5.5
7.5
15
18.5
22
30

3.9
6.8
9
12
16
25
30
37
45

Supply voltage, Us 24 V DC

1SFC132135F0001

0.75
1.5
1.5
3
2.2
4
3
5.5
4
7.5
5.5 11
7.5 15
7.5 18.5
11
22

PSR37 ... PSR45

2.2
4
4
5.5
7.5
15
18.5
22
30

3.9
6.8
9
12
16
25
30
37
45

1SFC132170F0001

1SFC132168F0001

Accessories

1SFC132169F0001

PSR-FBPA

IEC
500 V
Pe
kW

208 600 V AC

PSR3 ... PSR16

PSR25 ... PSR30

400 V
Pe
kW

PSR16-MS116

Weight
kg
1 piece

PSR45-MS450
1SFC132171F0001

Fan
All sizes can be equipped with auxiliary
cooling fan for increased starting capacity.
Suitable for all sizes.

PSR-FAN

ABB Field Bus Plug


Suitable for all sizes.

FieldBusPlug

8
1SFC132004C0201

Softstarters

Type PSR3 ... PSR45


Technical data
Rated insulation voltage, Ui

600 V

Rated operational voltage, Ue

208...600 V

Rated supply voltage, Us

100...240 V AC or 24 V DC

Power consumption,
at 100-240 V AC
at 24 V DC

PSR3

PSR6

PSR9

PSR12

PSR16

PSR25

PSR30

PSR37

PSR45

12 VA
5W

12 VA
5W

12 VA
5W

12 VA
5W

12 VA
5W

12 VA
5W

12 VA
5W

10 VA
5W

10 VA
5W

Rated operational current, Ir

PSR3

PSR6

PSR9

PSR12

PSR16

PSR25

PSR30

PSR37

PSR45

3.9 A

6.8 A

9A

12 A

16 A

25 A

30 A

37 A

45 A

Starting capacity at Ir

4 x Ir for 6 sec.

Number of starts per hour,


with aux. fan

standard 10 (4 x Ie during 6 s)
20 (4 x Ie during 6 s)

Service factor

100 %

Ambient temperature

during operation
during storage

Maximum altitude 2)

4000 m

Degree of protection,
main circuit
control circuit
Connectable cable area,
main circuit
control circuit
Signal relays
for Run signal
Resistive load
AC-15 (Contactor)
for Top of Ramp signal
Resistive load
AC-15 (Contactor)
LED for On/Ready
for Run/Top Of Ramp

1)

-25 C to +60 C
-40 C to +70 C
PSR3

PSR6

PSR9

PSR12

PSR16

PSR25

PSR30

PSR37

PSR45

IP20
IP20

IP20
IP20

IP20
IP20

IP20
IP20

IP20
IP20

IP20
IP20

IP20
IP20

IP10
IP20

IP10
IP20

PSR3 - PSR16

PSR25 - PSR30

PSR37 - PSR45

1 x 0.75 - 2.5 mm2


2 x 0.75 - 2.5 mm2
PSR3 - PSR16
1 x 0.75 - 2.5 mm2
2 x 0.75 - 2.5 mm2

1 x 2.5 - 10 mm2
2 x 2.5 - 10 mm2
PSR25 - PSR45
1 x 0.75 - 2.5 mm2
2 x 0.75 - 1.5 mm2

1 x 6 - 35 mm2
2 x 6 - 16 mm2

PSR3 - PSR16

PSR25 - PSR45

240 V, 2 A
240 V, 0.5 A

250 V, 5 A
250 V, 0.5 A

250 V, 2 A
250 V, 0.5 A

Green
Green

Settings
Ramp time during start
Ramp time during stop
Initial- and End Voltage

1-10 sec.
0-20 sec.
40-70%

1)

Above 40 C up to max. 60 C reduce the rated current with 0.8 % per C.

2)

When used at high altitudes above 1000 meters up to 4000 meters you need to derate the rated current using the following formula.

x - 1000]
[ % of Ie = 100 -
150
x = actual altitude for the softstarter

UL ratings
Softstarter

Type

FLA
A

Motor power P (hp) and full load current FLA (A)


Ue
Ue
Ue
208 V
240 V
480 V
hp
hp
hp

PSR3
PSR6
PSR9
PSR12
PSR16
PSR25
PSR30
PSR37
PSR45

3.4
6.1
9
11
15.2
24.2
28
34
46.2

0.5
1
2
3
3
7.5
7.5
10
15

0.75
1.5
2
3
5
7.5
10
10
15

2
3
5
7.5
10
15
20
25
30

Max. fuse
Ue
600V
hp

A, Type

2
5
7.5
10
10
20
25
30
40

40 A J-Type
40 A J-Type
40 A J-Type
40 A J-Type
40 A J-Type
60 A J-Type
70 A J-Type
100 A J-Type
100 A J-Type

9
1SFC132004C0201

Softstarters

1SFT98889-037

1SFT98889-036

Type PSS
Overview

PSS18/30 ... PSS44/76

PSS50 ... PSS72/124

Softstarter, Type
Normal start:
In Line connected
Rated current Ie,
In Line connected
Rated current Ie,

PSS18/30

PSS30/52

PSS37/64

PSS44/76

PSS50/85

PSS60/105

PSS72/124

400 V
kW
A

7.5
18

15
30

18.5
37

22
44

25
50

30
60

37
72

480 V
hp
A

10
18

20
28

25
34

30
40

30
47

40
56

50
67

T2S160

T2S160

T2S160

T2S160

T2S160

400V, 40 C
MCCB (50 kA), Type
If using MCCB only, type 1
coordination will be achieved.

T2S160

T2S160

Fuse protection (65 kA) Bussmann, Type


To achieve a type 2 coordination,
semi-condcutor fuses must be
used.

170M1364

Suitable switch fuse for


recommended semi-conductor
fuses.

OS160RD0380

170M1366

170M1368

170M1369

170M1369

170M1370

170M1371

OS160RD0380

OS160RD0380

OS160RD0380

OS160RD0380

OS160RD0380

A40

A50

A50

A63

A75

TA42DU

TA75DU

TA75DU

TA75DU

TA75DU

A26

A26

A30

A40

A50

PSCT-60
1 turn

PSCT-75
1 turn

PSCT-75
1 turn

PSCT-100
1 turn

Switch fuse, Type


OS160RD0380

Line contactor, Type


The line contactor is not required
for the softstarter itself but often
used to open if OL trips.

A26

The overload relay is always


required to protect the motor.

TA25DU

A30

Thermal overload relay, Type


TA25DU

By-pass contactor, Type


The by-pass contactor can be used
to reduce the power loss of the
softstarter but also to increase the
number of starts/h. All softstarters
can be operated without by-pass.

A9

Must be used if current limit


function is required.

PSCT-60
2 turns

A16

Current transformers, Type


PSCT-40
1 turn

PSCT-50
1 turn

The table above is an overview of possible combinations of devices.


Complete coordination tables are available at www.abb.com/lowvoltage.

10
1SFC132004C0201

Softstarters

1SFT98889-038

1SFT98800-004

Type PSS
Overview

PSS85/147... PSS142/245

PSS175/300... PSS300/515

Softstarter, Type
PSS85/147

PSS105/181

PSS142/245

PSS175/300

PSS250/430

PSS300/515

45
85

55
105

75
142

90
175

132
250

160
300

60
85

75
105

100
125

125
156

150
225

200
248

T3S250

T3S250

T4S320

T5S400

400V, 40 C
MCCB (50 kA), Type
T2S160

T3S250

Fuse protection (65 kA) Bussmann, Type


170M1372

170M3019

170M3020

170M3021

170M5013

170M5015

OESA250R03D80

OESA250R03D80

OESA250R03D80

OESA400R03D80

OESA400R03D80

A145

A185

A260

A300

TA200DU

TA200DU

TA450DU

TA450DU

A95

A145

A145

A210

PSCT-200
1 turn

PSCT-250
1 turn

PSCT-400
1 turn

PSCT-400
1 turn

Switch fuse, Type


OS160RD0380

Line contactor, Type


A95

A110

Thermal overload relay, Type


TA110DU

TA110DU

By-pass contactor, Type


A50

A63

Current transformers, Type


PSCT-125
1 turn

PSCT-150
1 turn

How to select correct size


By using the guide beside, you can
quickly select a suitable softstarter for the
most common applications.
If a more precise selection is required, you
can use Prosoft, a selection software
available at www.abb.com/lowvoltage.

Quick guide for selection


Normal start Class 10

Heavy duty start Class 30

Ordering See page 14 15

Ordering See page 16 17

Typical applications

Typical applications

Bow

thruster
Compressor
Elevator

Centrifugal pump
Conveyor belt (short)
Escalator

Centrifugal fan
Crusher
Mixer

Conveyor belt (long)


Mill
Stirrer

If more than 10 starts /h

Select one size larger than the standard selection.

11
1SFC134001C0201

Softstarters

Type PSS18/30 ... PSS300/515


Application and Description
Application
The softstarter range PSS18/30 ... PSS300/515 is a very exible
solution suitable for most applications and for replacements of StarDelta starters. Since the unit can be connected inside the motor delta
(compare the connection for standard Star-Delta starters), the current
through the softstarter is reduced by 42 %. It will then be possible, for
example, to run a 100 A motor using a 58 A PSS Softstarter.

In-Line

100 A

Inside Delta

58 A
100 A

100 A

In-Line and Inside Delta connection of PSS18/30 PSS300/515

The PSS Softstarter can be selected according to the rated motor


power in normal duty applications like pumps, compressors, elevators, escalators, short conveyor belts and bow thrusters
see page 14-15.
For heavy duty applications like centrifugal fans, crushers, mixers,
mills, stirrers and long conveyor belts, select a softstarter from
page 16-17.

Description

Wide main voltage range 208 - 690 V AC


Supply voltage range 110-120 V AC and 220-240 V AC
Current ratings 18 ... 300 A (In Line) and 30 ... 515 A (Inside Delta)
Same unit can be used for both In Line and Inside Delta connection
Start ramp, Stop ramp and Initial voltage included
Current limit function as option
Solid state electrical circuit
Designed for continuous operation without by-pass
15 % overcurrent capability during continuous run (10 % for PSS300/515)
Accessories for connection and installation available: See the ordering
pages

Built-in signal relays


for fault and by-pass
Transparent lid to
protect the settings

LED indications:
Power supply on
Completed start ramp
General fault (motor side or unit)

Three rotating switches setting:


-Start ramp (130 sec)
-Stop ramp (030 sec)
-Initial voltage (3070 % of Ue)
-Current limit 1.5 4 x Ir
(If used: Initial voltage xed at 40 % of Ue)

External fault
Dip-switch for In Line/
Inside Delta connection

12
1SFC132004C0201

Softstarters

(1SFC132186F0001)

Type PSS18/30 ... PSS300/515

Different sizes of PSS, from left PSS175/300-500L, PSS85/147-500L, PSS50/85-500L and in the front PSS18/30-500L.

Settings
PSS18/30 PSS300/515
U
1

3 U
ini

1SFT 98899-031

time
Start

Stop

1 Ramp time START = 1 ... 30 sec

2 Ramp time STOP = 0 ... 30 sec


3 Initial voltage U =40 ... 70 %, when current limit is
ini

used xed at 40 % (also set end voltage)

13
1SFC132004C0201

Softstarters

Type PSS18/30 ... PSS300/515


Normal starts, class 10 In-Line, Ordering details
PSS18/30 ... PSS300/515
230 500 V
1SFT98889-036

Motor power

1SFT98889-037

PSS18/30-500 ... 44/76-500

PSS50/85-500 ...72/124-500
PSS18/30-690 ... 72/124-690

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type *)

7.5
15
18.5
22
25
30
37
45
55
75
90
132
160

11
18.5
22
25
30
37
45
55
75
90
110
160
200

18
30
37
44
50
60
72
85
105
142
175
250
300

Weight
kg

Order code **)

PSS18/30-500
PSS30/52-500
PSS37/64-500
PSS44/76-500
PSS50/85-500
PSS60/105-500
PSS72/124-500
PSS85/147-500
PSS105/181-500
PSS142/245-500
PSS175/300-500
PSS250/430-500
PSS300/515-500

1SFA 892 001 R00


1SFA 892 002 R00
1SFA 892 003 R00
1SFA 892 004 R00
1SFA 892 005 R00
1SFA 892 006 R00
1SFA 892 007 R00
1SFA 892 008 R00
1SFA 892 009 R00
1SFA 892 010 R00
1SFA 892 011 R00
1SFA 892 013 R00
1SFA 892 014 R00

2.30
2.30
2.30
2.30
3.60
3.80
3.80
8.60
10.40
10.40
20.50
22.00
22.00

400 690 V

1SFT98889-038

Motor power

1SFT98800-004

PSS85/147-500 ...142/245-500
PSS85/147-690 ...142/245-690

PSS175/300-500 ... 300/515-500


PSS175/300-690 ... 300/515-690

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type *)

7.5
15
18.5
22
25
30
37
45
55
75
90
132
160

11
18.5
22
25
30
37
45
55
75
90
110
160
200

15
25
30
37
45
55
59
75
90
132
160
220
257

18
30
37
44
50
60
72
85
105
142
175
250
300

PSS18/30-690
PSS30/52-690
PSS37/64-690
PSS44/76-690
PSS50/85-690
PSS60/105-690
PSS72/124-690
PSS85/147-690
PSS105/181-690
PSS142/245-690
PSS175/300-690
PSS250/430-690
PSS300/515-690
Add code letter in Type for:
Supply voltage, Us
F = 110-120 V, 50/60 Hz
L = 220-240 V, 50/60 Hz
Fault signal relay

no code letter = NO
C = NC

14
1SFC132004C0201

1SFA 893 001 R00


1SFA 893 002 R00
1SFA 893 003 R00
1SFA 893 004 R00
1SFA 893 005 R00
1SFA 893 006 R00
1SFA 893 007 R00
1SFA 893 008 R00
1SFA 893 009 R00
1SFA 893 010 R00
1SFA 893 011 R00
1SFA 893 013 R00
1SFA 893 014 R00

*)

Weight
kg

Order code **)

**)

Add code number in Order code for:


Supply voltage, Us
1 = 110-120 V, 50/60 Hz
2 = 220-240 V, 50/60 Hz
Fault signal relay
1 = NO

2 = NC

2.30
2.30
2.30
2.30
3.60
3.80
3.80
8.60
10.40
10.40
20.50
22.00
22.00

Softstarters

Type PSS18/30 ... PSS300/515


Normal starts, class 10 Inside Delta, Ordering details
PSS18/30 ... PSS300/515
230 500 V
1SFT98889-036

Motor power

1SFT98889-037

PSS18/30-500 ... 44/76-500

PSS50/85-500 ...72/124-500
PSS18/30-690 ... 72/124-690

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type *)

15
25
30
37
45
55
59
75
90
132
160
220
257

18.5
30
37
45
55
75
80
90
110
160
200
295
355

30
52
64
76
85
105
124
147
181
245
300
430
515

690 V
Pe

Rated motor
current, Ie

Weight
kg

Order code **)

PSS18/30-500
PSS30/52-500
PSS37/64-500
PSS44/76-500
PSS50/85-500
PSS60/105-500
PSS72/124-500
PSS85/147-500
PSS105/181-500
PSS142/245-500
PSS175/300-500
PSS250/430-500
PSS300/515-500

1SFA 892 001 R00


1SFA 892 002 R00
1SFA 892 003 R00
1SFA 892 004 R00
1SFA 892 005 R00
1SFA 892 006 R00
1SFA 892 007 R00
1SFA 892 008 R00
1SFA 892 009 R00
1SFA 892 010 R00
1SFA 892 011 R00
1SFA 892 013 R00
1SFA 892 014 R00

2.30
2.30
2.30
2.30
3.60
3.80
3.80
8.60
10.40
10.40
20.50
22.00
22.00

400 690 V
Motor power

1SFT98889-038

400 V
Pe

1SFT98800-004

PSS85/147-500 ...142/245-500
PSS85/147-690 ...142/245-690

PSS175/300-500 ... 300/515-500


PSS175/300-690 ... 300/515-690

500 V
Pe

Weight
*)

kW

kW

kW

Type

15
25
30
37
45
55
59
75
90
132
160
220
257

18.5
30
37
45
55
75
80
90
110
160
200
295
355

25
45
55
59
75
90
110
132
160
220
257
400
500

30
52
64
76
85
105
124
147
181
245
300
430
515

PSS18/30-690
PSS30/52-690
PSS37/64-690
PSS44/76-690
PSS50/85-690
PSS60/105-690
PSS72/124-690
PSS85/147-690
PSS105/181-690
PSS142/245-690
PSS175/300-690
PSS250/430-690
PSS300/515-690

Order code

Add code letter in Type for:


Supply voltage, Us
F = 110-120 V, 50/60 Hz
L = 220-240 V, 50/60 Hz
Fault signal relay

no code letter = NO
C = NC

kg

1SFA 893 001 R00


1SFA 893 002 R00
1SFA 893 003 R00
1SFA 893 004 R00
1SFA 893 005 R00
1SFA 893 006 R00
1SFA 893 007 R00
1SFA 893 008 R00
1SFA 893 009 R00
1SFA 893 010 R00
1SFA 893 011 R00
1SFA 893 013 R00
1SFA 893 014 R00

*)

**)

2.30
2.30
2.30
2.30
3.60
3.80
3.80
8.60
10.40
10.40
20.50
22.00
22.00

**)

Add code number in Order code for:


Supply voltage, Us
1 = 110-120 V, 50/60 Hz
2 = 220-240 V, 50/60 Hz
Fault signal relay
1 = NO

2 = NC

15
1SFC132004C0201

Softstarters

Type PSS30/52 ... PSS300/515


Heavy duty starts, class 30 In-Line, Ordering details
PSS30/52 ... PSS300/515
230 500 V

Heavy duty

1SFT98889-036

Motor power

1SFT98889-037

PSS30/52-500 ... 44/76-500

PSS50/85-500 ...72/124-500
PSS18/30-690 ... 72/124-690

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type *)

7.5
15
18.5
22
25
30
37
45
55
75
90
132

11
18.5
22
25
30
37
45
55
75
90
110
160

18
30
37
44
50
60
72
85
105
142
175
250

PSS30/52-500
PSS37/64-500
PSS44/76-500
PSS50/85-500
PSS60/105-500
PSS72/124-500
PSS85/147-500
PSS105/181-500
PSS142/245-500
PSS175/300-500
PSS250/430-500
PSS300/515-500

1SFA 892 002 R00


1SFA 892 003 R00
1SFA 892 004 R00
1SFA 892 005 R00
1SFA 892 006 R00
1SFA 892 007 R00
1SFA 892 008 R00
1SFA 892 009 R00
1SFA 892 010 R00
1SFA 892 011 R00
1SFA 892 013 R00
1SFA 892 014 R00

1SFT98889-038

Motor power
400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type *)

7.5
15
18.5
22
25
30
37
45
55
75
90
132

11
18.5
22
25
30
37
45
55
75
90
110
160

15
25
30
37
45
55
59
75
90
132
160
220

18
30
37
44
50
60
72
85
105
142
175
250

1SFA 893 002 R00


1SFA 893 003 R00
1SFA 893 004 R00
1SFA 893 005 R00
1SFA 893 006 R00
1SFA 893 007 R00
1SFA 893 008 R00
1SFA 893 009 R00
1SFA 893 010 R00
1SFA 893 011 R00
1SFA 893 013 R00
1SFA 893 014 R00

1SFT98800-004

PSS175/300-500 ... 300/515-500


PSS175/300-690 ... 300/515-690

Add code letter in Type for:


Supply voltage, Us
F = 110-120 V, 50/60 Hz
L = 220-240 V, 50/60 Hz
Fault signal relay

no code letter = NO
C = NC

Weight
kg

Order code **)

PSS30/52-690
PSS37/64-690
PSS44/76-690
PSS50/85-690
PSS60/105-690
PSS72/124-690
PSS85/147-690
PSS105/181-690
PSS142/245-690
PSS175/300-690
PSS250/430-690
PSS300/515-690
*)

1SFC132004C0201

2.30
2.30
2.30
3.60
3.80
3.80
8.60
10.40
10.40
20.50
22.00
22.00

400 690 V

PSS85/147-500 ...142/245-500
PSS85/147-690 ...142/245-690

16

Weight
kg

Order code **)

**)

Add code number in Order code for:


Supply voltage, Us
1 = 110-120 V, 50/60 Hz
2 = 220-240 V, 50/60 Hz
Fault signal relay
1 = NO

2 = NC

2.30
2.30
2.30
3.60
3.80
3.80
8.60
10.40
10.40
20.50
22.00
22.00

Softstarters

Type PSS30/52 ... PSS300/515


Heavy duty starts, class 30 Inside Delta, Ordering details
PSS30/52 ... PSS300/515
230 500 V

Heavy duty

1SFT98889-036

Motor power

1SFT98889-037

PSS30/52-500 ... 44/76-500

PSS50/85-500 ...72/124-500
PSS18/30-690 ... 72/124-690

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type *)

15
25
30
37
45
55
59
75
90
132
160
220

18.5
30
37
45
55
75
80
90
110
160
200
295

30
52
64
76
85
105
124
147
181
245
300
430

Weight
kg

Order code **)

PSS30/52-500
PSS37/64-500
PSS44/76-500
PSS50/85-500
PSS60/105-500
PSS72/124-500
PSS85/147-500
PSS105/181-500
PSS142/245-500
PSS175/300-500
PSS250/430-500
PSS300/515-500

1SFA 892 002 R00


1SFA 892 003 R00
1SFA 892 004 R00
1SFA 892 005 R00
1SFA 892 006 R00
1SFA 892 007 R00
1SFA 892 008 R00
1SFA 892 009 R00
1SFA 892 010 R00
1SFA 892 011 R00
1SFA 892 013 R00
1SFA 892 014 R00

2.30
2.30
2.30
3.60
3.80
3.80
8.60
10.40
10.40
20.50
22.00
22.00

400 690 V

1SFT98889-038

Motor power

PSS85/147-500 ...142/245-500
PSS85/147-690 ...142/245-690

400 V
Pe

500 V
Pe

690 V
Pe

Rated motor
current, Ie

kW

kW

kW

Type *)

Order code **)

15
25
30
37
45
55
59
75
90
132
160
220

18.5
30
37
45
55
75
80
90
110
160
200
295

25
45
55
59
75
90
110
132
160
220
257
400

30
52
64
76
85
105
124
147
181
245
300
430

PSS30/52-690
PSS37/64-690
PSS44/76-690
PSS50/85-690
PSS60/105-690
PSS72/124-690
PSS85/147-690
PSS105/181-690
PSS142/245-690
PSS175/300-690
PSS250/430-690
PSS300/515-690

1SFA 893 002 R00


1SFA 893 003 R00
1SFA 893 004 R00
1SFA 893 005 R00
1SFA 893 006 R00
1SFA 893 007 R00
1SFA 893 008 R00
1SFA 893 009 R00
1SFA 893 010 R00
1SFA 893 011 R00
1SFA 893 013 R00
1SFA 893 014 R00

Weight

1SFT98800-004

PSS175/300-500 ... 300/515-500


PSS175/300-690 ... 300/515-690

*)

Add code letter in Type for:


Supply voltage, Us
F = 110-120 V, 50/60 Hz
L = 220-240 V, 50/60 Hz
Fault signal relay

no code letter = NO
C = NC

kg

2.30
2.30
2.30
3.60
3.80
3.80
8.60
10.40
10.40
20.50
22.00
22.00

**)

Add code number in Order code for:


Supply voltage, Us
1 = 110-120 V, 50/60 Hz
2 = 220-240 V, 50/60 Hz
Fault signal relay
1 = NO

2 = NC

17
1SFC132004C0201

Softstarters

Accessories for type PSS18/30 ... PSS300/515


Ordering details
Current transformer for current limit function
To be connected to terminals 11 and 12 on the softstarter.
The setting range (1.5 4) corresponds to a multiple of the transformer ratio.
Technical data below shows transformer ratio and number of turns for the primary winding.
You can also use your own current transformer with corresponding transformer ratio and with minimum 1 VA.

PSCT..

For softstarter
type

Transformer ratio,
Number of turns

Type

Order code

Packing
piece

PSS18/30
PSS30/52
PSS37/64
PSS44/76
PSS50/85
PSS60/105
PSS72/124
PSS85/147
PSS105/181
PSS142/245
PSS175/300
PSS250/430
PSS300/515

60/1 2 turns
40/1 1 turn
50/1 1 turn
60/1 1 turn
75/1 1 turn
75/1 1 turn
100/1 1 turn
125/1 1 turn
150/1 1 turn
200/1 1 turn
250/1 1 turn
400/1 1 turn
400/1 1 turn

PSCT-60
PSCT-40
PSCT-50
PSCT-60
PSCT-75
PSCT-75
PSCT-100
PSCT-125
PSCT-150
PSCT-200
PSCT-250
PSCT-400
PSCT-400

1SFA 899 001 R1060


1SFA 899 001 R1040
1SFA 899 001 R1050
1SFA 899 001 R1060
1SFA 899 001 R1075
1SFA 899 001 R1075
1SFA 899 001 R1100
1SFA 899 001 R1125
1SFA 899 001 R1150
1SFA 899 001 R1200
1SFA 899 001 R1250
1SFA 899 001 R1400
1SFA 899 001 R1400

1
1
1
1
1
1
1
1
1
1
1
1
1

Type

Order code

Packing
piece

LZ185-2C/120

1SDA 023 354 R0001


1SFN 074 709 R1000
1SDA 023 368 R0001

3
3
3

Weight
kg
1 piece

0.30
0.30
0.30
0.30
0.30
0.30
0.25
0.25
0.25
0.25
0.25
0.25
0.25

Cable connectors for Cu cables


1SFT98099-011C1

1SFT98099-095C2

For
softstarter
type

Wire
range
mm2

Tightening
torque
max. Nm

PSS85/147142/245 6-185
16
PSS85/147142/245 2x(50-120) 16
PSS175/300300/515 16-240
25

Weight
kg
1 piece

0.20
0.30
0.40

Cable connectors for Al and Cu cables


SB854C2

For
softstarter
type

Wire
range
mm2

PSS85/147142/245 35-95
PSS85/147142/245 25-150
PSS175/300300/515 120-240

1SFT98000-011C3

PSLW-44

1SFC132012F0201

LZ...

LW...

Tightening
torque
max. Nm

Type

Order code

Packing
piece

13.5
31
43

1SDA 023 356 R0001


1SDA 023 357 R0001
1SDA 023 370 R0001

3
3
3

Weight
kg
1 piece

0.10
0.10
0.10

Terminal enlargements
For
softstarter
type

Wire
range
mm2

Type

Order code

Packing
piece

Weight
kg
1 piece

PSS18/30-500 ...44/76-500

1x6...35
2x6...16

PSLW-44

1SFA 899 002 R1044

0.10

PSS50/85-50072/124-500
PSS18/30-690 ... 72/124-690 1x10...50
2x10...25

PSLW-72

1SFA 899 002 R1072

0.15

PSS85/147142/245

LW185

1SFN 074 707 R1000

0.25

PSS175/300300/515

LW300

1SFN 075 107 R1000

0.40

1SFC132010F0201

Terminal nut washer

LT ... -AC

18
1SFC132004C0201

1SFT98099-125

1SFT98099-019C3

LE185

LT ... -AL

For
softstarter
type

Type

Order code

Packing
piece

PSS85/147142/245
PSS175/300300/515

LE185
LE300

1SFN 074 716 R1000


1SFN 075 116 R1000

2
2

Weight
kg
1 piece

0.20
0.30

Terminal shrouds
For
softstarter
type

Suitable for

Type

Order code

Packing
piece

PSS85/147142/245
PSS85/147142/245
PSS175/300300/515
PSS175/300300/515

Cable connectors
Compression lugs
Cable connectors
Compression lugs

LT185-AC
LT185-AL
LT300-AC
LT300-AL

1SFN 124 701 R1000


1SFN 124 703 R1000
1SFN 125 101 R1000
1SFN 125 103 R1000

2
2
2
2

Weight
kg
1 piece

0.10
0.10
0.20
0.20

Softstarters

Type PSS18/30 ... PSS300/515


Technical data
PSS18/30 ... PSS300/515

Rated insulation voltage, Ui

690 V

Rated operational voltage, Ue

208 690 V

Starting capacity
at max. rated current, Ie

4 x Ie for 10 sec

Number of starts per hour

30 3)

Overload capability
Overload class

10

Service factor

PSS18/30 ... 250/430

PSS300/515

115 %

110 %

Ambient temperature
During operation
During storage

-25 to +60 C 1)
-40 to +70 C

Maximum altitud

4000 m

4)

Degree of protection
Main circuit

PSS18/30-500 ... 44/76-500

PSS50/85-500 ...72/124-500

IP 20

IP 10

PSS18/30-690 ... 72/124-690

PSS85/147-690 ...300/515-690

IP 10

IP 00

PSS18/30PSS300/515

Supply and control circuit

IP 20

Settings
Ramp time during start
Ramp time during stop
Initial voltage during start

1 30 sec
0 30 sec
30 70 %

Current limit function

1.5 ... 4 2)

x CT-ratio

Switch for
Inside Delta connection ON/OFF
Signal relays
By-pass signal
Fault signal
Rated operational voltage, Ue
Rated thermal current, Ith
Rated operational current, Ie
at AC-15 (Ue=250 V)
Signal indication LED
Ready to start/stand by
Ramping up/down
Completed start ramp
General fault
External fault
1)
2)
3)
4)

Yes
Yes
Yes (NO or NC)
250V
5A
1.5A

ON
T.O.R

Green

Green
Red
Red

Above 40 C, up to max 60 C, reduce the rated current with 0.8 % per C.


Only if current transformer is connected (accessory).
Valid for 50 % on time and 50 % off time. 3.5 x Ie for 7 sec., if other data is required, contact your sales ofce.
When used at high altitudes above 1000 meters up to 4000 meters you need to derate rated current using
the following formula.
x - 1000
[ % of Ie = 100 - ]
150
x = actual altitude for the softstarter

19
1SFC132004C0201

Softstarters

Type PSS18/30 ... PSS300/515


Technical data
Cross section of connection cables
Type of softstarter
PSS 18/30-500
44/76-500

PSS50/85-500
72/124-500,
18/30-690
72/124-690

PSS85/147-500
142/245-500,
85/147-690
142/245-690

PSS175/300
300/515-500,
175/300
300/515-690

2.5 16
2.5 16

6 50
6 25

See accessories
See accessories

See accessories
See accessories

2.6

4.5

See accessories

See accessories

Main circuit
Connection clamp

Solid/Stranded
Solid/Stranded

1 x mm2
2 x mm2

Tightening torque (recommended)

Nm

20

17.5

Connection bar

mm

Hole diameter

mm

Tightening torque (recommended)

Nm

1 x mm2
2 x mm2

2.5

2.5

2.5

2.5

Nm

0.5

0.5

0.5

0.5

Supply and control circuit


Connection clamp
Solid/Stranded
Solid/Stranded
Tightening torque (recommended)

E1858D

E1859D

Width and thickness

8.5

10.2

18

Fuse ratings and power losses

For
Softstarter
Type

Recommended
ABB Overload protection
Current
range
Type
A

Max 2)
power
loss at
rated /e
W

Max fuse rating - main circuit 1)


Bussman fuses
A
Type
Holder

PSS18/30
PSS30/52
PSS37/64
PSS44/76
PSS50/85
PSS60/105
PSS72/124
PSS85/147
PSS105/181
PSS142/245
PSS175/300
PSS250/430
PSS300/515

TA 25 DU
TA 25 DU
TA 42 DU
TA 75 DU
TA 75 DU
TA 75 DU
TA 75 DU
TA 110 DU
TA 110 DU
TA 200 DU
TA 200 DU
TA 450 DU
TA 450 DU

65
100
120
142
160
190
226
291
351
462
590
815
965

50
80
125
160
160
200
250
315
400
450
500
700
900

1)

618
1030
2237
2944
2950
2960
4572
6585
65105
100142
100175
130250
130300

For the supply circuit 6 A delayed, for MCB use C characteristics.


Calculated power loss at operational current (Iop) without by-pass.
Ptot = 3 x Iop + VA value
Example: PSS 60/105 running at 52A
Ptot = 3 x 52 + 10 = 166W
When using bypass, the powerloss is reduced to the VA value only.
2)

20
1SFC132004C0201

170M1364
170M1366
170M1368
170M1369
170M1369
170M1370
170M1371
170M1372
170M3019
170M3020
170M3021
170M5013
170M5015

170H1007
170H1007
170H1007
170H1007
170H1007
170H1007
170H1007
170H1007
170H3004
170H3004
170H3004
170H3004
170H3004

Ferraz fuses circuit


A
Type
63
100
160
200
200
250
315
400
400
500
530
630
900

6.6 URB 000 D08 V 0063


6.6 URB 000 D08 V 0100
6.6 URB 000 D08 V 0160
6.6 URD 30 D08 A 0200
6.6 URD 30 D08 A 0200
6.6 URD 30 D08 A 0250
6.6 URD 30 D08 A 0315
6.6 URD 30 D08 A 0400
6.6 URD 30 D08 A 0400
6.6 URD 30 D08 A 0500
6.6 URD 30 D08 A 0550
6.6 URD 31 D08 A 0630
6.6 URD 32 D11 A 0900

Power requirements
of supply
VA
9
9
9
9
10
10
10
36
36
36
65
65
65

Softstarters

Type PSS18/30 ... PSS300/515


UL ratings
3-phase motor rating - In Line
Softstarters

Motor power P (hp) and nominal current Ie A

Type

Ue
200V / 208V
hp
A

PSS18/30
PSS30/52
PSS37/64
PSS44/76
PSS50/85
PSS60/105
PSS72/124
PSS85/147
PSS105/181
PSS142/245
PSS175/300
PSS250/430
PSS300/515

5
7.5
10
10
15
15
20
25
30
40
50
75
75

18
28
34
40
47
56
67
85
105
125
156
225
248

Ue
220V / 240V
hp
A
5
10
10
10
15
20
20
30
40
40
60
75
100

18
28
34
40
47
56
67
85
105
125
156
225
248

Ue
440V / 480V
hp
A
10
20
25
30
30
40
50
60
75
100
125
150
200

18
28
34
40
47
56
67
85
105
125
156
225
248

Ue
550V / 600V
hp
A
15
25
30
30
40
50
60
75
100
125
150
200
250

18
28
34
40
47
56
67
85
105
125
156
225
248

3-phase motor rating - Inside Delta


Softstarters

Motor power P (hp) and nominal current Ie A

Type

Ue
200V / 208V
hp
A

PSS18/30
PSS30/52
PSS37/64
PSS44/76
PSS50/85
PSS60/105
PSS72/124
PSS85/147
PSS105/181
PSS142/245
PSS175/300
PSS250/430
PSS300/515

7.5
15
20
20
25
30
40
50
60
75
75
125
150

30
48
58
69
81
96
116
147
181
215
270
389
429

Ue
220V / 240V
hp
A
10
15
20
25
30
30
40
50
60
75
100
150
150

30
48
58
69
81
96
116
147
181
215
270
389
429

Ue
440V / 480V
hp
A
20
30
40
50
60
75
75
100
150
150
200
300
350

30
48
58
69
81
96
116
147
181
215
270
389
429

Ue
550V / 600V
hp
A
25
40
50
60
75
75
100
150
150
200
250
400
400

30
48
58
69
81
96
116
147
181
215
270
389
429

21
1SFC132004C0201

Softstarters

1SFC132173F0001

1SFC132172F0001

Type PST30 ... 300 and PSTB370 ... 1050


Overview

PST85 ... PST142

PST30 ... PST72


Softstarter, Type
Normal start:
In Line connected (400 V)
kW
Rated current Ie,
A

PST30

PST37

PST44

PST50

PST60

PST72

PST85

PST105

PST142

15
30

18.5
37

22
44

25
50

30
60

37
72

45
85

55
105

75
142

In Line connected (480 V)


hp
Rated current Ie,
A

20
28

25
34

30
42

40
54

40
60

50
68

60
80

75
104

100
130

T2S160

T2S160

T2S160

T2S160

T2S160

T3S250

T3S250

If using MCCB only, type 1


coordination will be achieved.

400V, 40 C
MCCB (50 kA), Type
T2S160

T2S160

Fuse protection (65 kA) Bussmann, Type


To achieve a type 2 coordination,
semi-condcutor fuses must be
used.

170M1366 170M1368 170M1369 170M1369 170M1370 170M1371 170M1372 170M1319 170M1320

Suitable switch fuse for


recommended semi-conductor
fuses.

OS160RD0380
OS160RD0380
OS160RD0380
OS160RD0380
OESA250R03D80
OS160RD0380
OS160RD0380
OS160RD0380
OESA250R03D80

Switch fuse, Type

Line contactor, Type


The line contactor is not required
for the softstarter itself but often
used to open if OL trips.

A30

The overload relay is always


required to protect the motor.

Built-in

A40

A50

A50

A63

A75

A95

A110

A145

Built-in

Built-in

Built-in

Built-in

Built-in

Built-in

A30

A40

A50

A50

A63

A95

Integrated

Integrated

Integrated

Integrated

Integrated

Integrated

Thermal overload relay, Type


Built-in

Built-in

By-pass contactor, Type


The by-pass contactor can be used
to reduce the power loss of the
softstarter but also to increase the
number of starts/h. All softstarters
can be operated without by-pass.

A16

A26

A26

Current transformers
Integrated

Integrated

Integrated

The table above is an overview of possible combinations of devices.


Complete coordination tables are available at www.abb.com/lowvoltage.

22
1SFC132004C0201

Softstarters

1SFC132176F0001

1SFC132175F0001

1SFC132174F0001

Type PST30 ... 300 and PSTB370 ... 1050


Overview

PST175... PST300

PSTB370 ... 470

PSTB570 ... 1050

Softstarter, Type
PST175

PST210

PST250

PST300

PSTB370

PSTB470

PSTB570

PSTB720

PSTB840

PSTB1050

90
175

110
210

132
250

160
300

200
370

250
470

315
570

400
720

450
840

560
1050

125
156

150
192

200
248

250
302

300
361

400
480

500
590

600
720

700
840

900
1062

T5S400

T5S400

T5S630

T5S630

S6S630

S6S800

S7S1250

S7S1600

170M5013

170M5015

170M5015

170M5018

170M6018

170M6020 2)

400V, 40 C
MCCB (50 kA), Type
T4S250

T4S250

Fuse protection (65 kA) Bussmann, Type


170M3021

170M5012

170M5013

170M5015

Switch fuse, Type


1)
OESA250R03D80
OESA400R03D80
OESA400R03D80
OESA630R03D80
OESA400R03D80
OESA400R03D80
OESA630R03D80
OESA800R03D80

1)

Line contactor, Type


A185

A210

A260

A300

AF400

AF580

AF580

AF750

AF1350

AF1650

Built-in

Built-in

Built-in

Built-in

Built-in

Built-in

Built-in

A145

A210

Built-in

Built-in

Built-in

Built-in

Built-in

Built-in

Integrated

Integrated

Integrated

Integrated

Integrated

Integrated

Integrated

Integrated

Thermal overload relay, Type


Built-in

Built-in

Built-in

By-pass contactor, Type


A145

A145

Current transformers
Integrated

Integrated

PSTB840 and PSTB1050: Switch fuse not available, use fuseholder, see page 40.
2)
PST1050-690-70 has 170M6019
1)

How to select correct size


By using the guide beside, you can
quickly select a suitable softstarter for the
most common applications.
If a more precise selection is required, you
can use Prosoft, a selection software
available at www.abb.com/lowvoltage.

Quick guide for selection


Normal start Class 10

Heavy duty start Class 30

Ordering See page 26 27

Ordering See page 28 29

Typical applications

Typical applications

Bow

thruster
Compressor
Elevator

Centrifugal pump
Conveyor belt (short)
Escalator

Centrifugal fan
Crusher
Mixer

Conveyor belt (long)


Mill
Stirrer

If more than 10 starts /h

Select one size larger than the standard selection.

23
1SFC132004C0201

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050


Application and description
Application

Description

The PST range is a microprocessor based softstarter designed with the


latest technology for soft start and soft stop of motors. The PST Softstarter has several advanced motor protection features as standard.
The four button keypad and the logic structure of the menu make the
installation, commissioning and operation easy. It is possible to choose
between 13 different languages.

The PST Softstarter can be used with or without a by-pass contactor


except for the larger sizes PSTB370 ... PSTB1050 where the by-pass
contactor is already built-in.
The PST Softstarter can be selected according to the rated motor
power in normal duty applications like pumps, compressors, elevators, escalators, short conveyor belts and bow thrusters.
See page 26-27
For heavy duty applications like centrifugal fans, crushers, mixers,
mills, stirrers and long conveyor belts, select a softstarter from
page 28-29.

In-Line

Inside Delta

100 A

Wide main voltage range 208 - 690 V AC


Wide supply voltage range 100 250 V, 50/60 Hz
Current ratings 30 to 1050 A (In Line) and 52 ... 1810 A (Inside Delta)
Same unit can be used for both In Line and Inside Delta connection
Premium adjustable Softstarter functions like start/stop ramp, kick
start, jog, step down voltage and sequential starts.
Current limit adjustable between 27 x Ie
Thermistor (PTC) supervision of motor winding
Real time clock
Logging of last 20 events with time marking
Prepared for eldbus communication
Motor overload protection with simulated motor temperature from
measured current. Select between 10A, 10, 20 and 30
Locked rotor protection
Motor underload protection
Phase imbalance protection
Phase reversal protection
Torque control
Analog output

58 A
100 A

100 A

In-Line and Inside Delta connection of PST30 PSTB1050

Programmable
signal inputs

Three separate terminals


prepared for external by-pass

Programmable
signal relays

LCD-display with
plain words in
your language

Four button keypad

Symbol for
torque control

Integrated advanced
motor protection
LED indications:
Power on
Fault
Protection

Clear information

Terminals for PTC input


and analogue output

24
1SFC132004C0201

Fieldbus communication

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050


Functional description
LCD display

The display of the PST gives you information presented in plain words
in required language. You can choose between 13 different languages
including English, German, Italian, Chinese, Finnish, Swedish, French,
Spanish, Dutch, Portuguese, Russian, Turkish and Polish. On the
PST display, you get all the information you need to set up, adjust
and trouble-shoot. This makes the PST extremely easy to handle and
reduces the risk of misinterpretations.

Four button keypad

The PST employs the same basic user concept as todays advanced
mobile telephones. Using the four buttons on the keypad, you can easily adjust your own start and stop prole and motor protection
functions for any type of application. There are standard settings for
many common applications including pumps, conveyors, fans, mixers
and compressors for quick and easy set up.
You can also set the advanced warning parameters to allow potential
problems to be identied before real problems occur. A password
protection function is available to prevent unauthorized changes to the
programming.

Starting several motors

You can store as many as three different starting parameter sets for
optimal sequence start of three different motors. You can use this
function for two or three speed motors as well.

Integrated advanced motor protection

Inside the PST Softstarter, you will nd useful features for advanced
motor and softstarter protection, including; programmable overload
protection, high current, underload, phase imbalance, phase reversal,
thyristor overload protection, and bypass monitoring to ensure proper
by-pass operation

Programmable signal relays

All PST units have three programmable signal relays where each relay
can signal Run, Top of Ramp or Event. The Event setting can be used
to signal protections, faults and warnings. The supervisory functions
monitor not only software and critical softstarter functionality but also
phase loss and out of frequency range.

Fieldbus communication

The PST Softstarter has a built-in interface on the front for connection
of the ABB FieldBusPlug used for eldbus communication. Through this
interface it is possible to control the softstarter, achieve status information, up- and down load of parameters. The interface between the softstarter and the FieldBusPlug is always the same. Independently of PST
Softstarter size or delivery date it is possible to connect to any eldbus
protocol later on since this is dened in the FieldBusPlug itself. Avaliable
protocols are AS-Interface, DeviceNet, Probus DP and Modbus-RTU.
To connect the PST Softstarter to a eldbus system you need the accessories described on page 31 to 36 as well as specic software for
PLC set-up, which is available at www.abb.com/lowvoltage on the
Softstarter pages.

Torque control

The default setting is a normal voltage ramp but it


is possible to select torque ramp. With the torque
control function it is possible to start and stop
motors with a more linear acceleration than when
using the normal voltage ramps.
During start this can be used to reduce the wear on the equipment
driven by the motor.
During stop, controlling the torque is especially useful for pump applications where voltage ramps can lead to a sudden torque drop which may
result in water hammering and pressure surges. Torque control will keep
these problems to an absolute minimum.

Torque limit

With the torque limit function enabled, the torque can never exceed a
set value during start. This will minimize stress and wear on the equipment driven by the motor.

Analog output

With the PST(B) softstarter it is possible to have analog output signals to


be used as input to a PLC or an analog meter. The output signals can
be selected to be for instance the current of the motor, main voltage,
active power or the temperature of the motor. The terminals used for
analog output are also used for PTC protection, so only one of these
functions can be used.

Integrated by-pass contactor

On the larger sizes (PSTB 370 ... PSTB1050), there is an ABB AF


contactor integrated. This gives you advantages in terms of costsaving, space saving and last but not least energy saving. With a
by-pass contactor you can reduce the power losses during normal run
by 90 % or more.
The smaller units, PST30 up to PST300, which are not equipped with a
built-in by-pass contactor, have an extra set of three terminals on the line
side. The terminals are marked B1, B2 and B3 and shall be used when
connecting an external by-pass contactor. This will enable the integrated
protection functions also when the softstarter is by-passed.

External keypad (option)

An external keypad is available as


option. The keypad can be mounted on a
panel door for example to view/control the
softstarter without opening the door. The
keypad can also be used to copy parameters between different softstarters.
PSTB570 with integrated by-pass contactor.

25
1SFC132004C0201

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050


Normal starts, class 10 In-Line, Ordering details
PST30 ... PST300
1SFC132172F0001

230 600 V

1SFC132173F0001

PST30 ... PST72

PST85 ... PST142

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power
400 V 500 V
Pe
Pe
kW
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

15
18.5
22
25
30
37
45
55
75
90
110
132
160

30
37
44
50
60
72
85
105
142
175
210
250
300

18.5
22
25
30
37
45
55
75
90
110
132
160
200

400 690 V

1SFC132174F0001

1SFA 894 002 R7000


1SFA 894 003 R7000
1SFA 894 004 R7000
1SFA 894 005 R7000
1SFA 894 006 R7000
1SFA 894 007 R7000
1SFA 894 008 R7000
1SFA 894 009 R7000
1SFA 894 010 R7000
1SFA 894 011 R7000
1SFA 894 012 R7000
1SFA 894 013 R7000
1SFA 894 014 R7000

Weight
kg

4.8
4.8
4.8
4.8
5.0
5.0
11.2
13.0
13.0
21.5
21.5
23.0
23.0

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PST175 ... PST300

PST30-600-70
PST37-600-70
PST44-600-70
PST50-600-70
PST60-600-70
PST72-600-70
PST85-600-70
PST105-600-70
PST142-600-70
PST175-600-70
PST210-600-70
PST250-600-70
PST300-600-70

Order code

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

15
18.5
22
25
30
37
45
55
75
90
110
132
160

18.5
22
25
30
37
45
55
75
90
110
132
160
200

25
30
37
45
55
59
75
90
132
160
184
220
257

30
37
44
50
60
72
85
105
142
175
210
250
300

PST30-690-70
PST37-690-70
PST44-690-70
PST50-690-70
PST60-690-70
PST72-690-70
PST85-690-70
PST105-690-70
PST142-690-70
PST175-690-70
PST210-690-70
PST250-690-70
PST300-690-70

Order code

1SFA 895 002 R7000


1SFA 895 003 R7000
1SFA 895 004 R7000
1SFA 895 005 R7000
1SFA 895 006 R7000
1SFA 895 007 R7000
1SFA 895 008 R7000
1SFA 895 009 R7000
1SFA 895 010 R7000
1SFA 895 011 R7000
1SFA 895 012 R7000
1SFA 895 013 R7000
1SFA 895 014 R7000

Weight
kg

4.8
4.8
4.8
4.8
5.0
5.0
11.2
13.0
13.0
21.5
21.5
23.0
23.0

PSTB370 ... PSTB1050 with integrated by-pass


1SFC132175F0001

230 600 V

PSTB370 ... PSTB470

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power
400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

200
250
315
400
450
560

257
315
400
500
600
730

370
470
570
720
840
1050

400 690 V

1SFC132176F0001

26
1SFC132004C0201

1SFA 894 015 R7000


1SFA 894 016 R7000
1SFA 894 017 R7000
1SFA 894 018 R7000
1SFA 894 019 R7000
1SFA 894 020 R7000

Weight
kg

31.0
31.0
52.0
55.0
60.0
60.0

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PSTB570 ... PSTB1050

PSTB370-600-70
PSTB470-600-70
PSTB570-600-70
PSTB720-600-70
PSTB840-600-70
PSTB1050-600-70

Order code

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

200
250
315
400
450
560

257
315
400
500
600
730

355
450
560
710
800
1000

370
470
570
720
840
1050

PSTB370-690-70
PSTB470-690-70
PSTB570-690-70
PSTB720-690-70
PSTB840-690-70
PSTB1050-690-70

Order code

1SFA 895 015 R7000


1SFA 895 016 R7000
1SFA 895 017 R7000
1SFA 895 018 R7000
1SFA 895 019 R7000
1SFA 895 020 R7000

Weight
kg

31.0
31.0
52.0
55.0
60.0
60.0

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050


Normal starts, class 10 Inside Delta, Ordering details
PST30 ... PST300
230 600 V

Supply voltage, Us 100...250 V, 50/60 Hz

1SFC132172F0001

Motor power

1SFC132173F0001

PST30 ... PST72

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

25
30
37
45
55
59
75
90
132
160
184
220
257

30
37
45
55
75
80
90
110
160
200
250
295
355

52
64
76
85
105
124
147
181
245
300
360
430
515

400 690 V

PST85 ... PST142

1SFC132174F0001

1SFA 894 002 R7000


1SFA 894 003 R7000
1SFA 894 004 R7000
1SFA 894 005 R7000
1SFA 894 006 R7000
1SFA 894 007 R7000
1SFA 894 008 R7000
1SFA 894 009 R7000
1SFA 894 010 R7000
1SFA 894 011 R7000
1SFA 894 012 R7000
1SFA 894 013 R7000
1SFA 894 014 R7000

Weight
kg

4.8
4.8
4.8
4.8
5.0
5.0
11.2
13.0
13.0
21.5
21.5
23.0
23.0

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PST175 ... PST300

PST30-600-70
PST37-600-70
PST44-600-70
PST50-600-70
PST60-600-70
PST72-600-70
PST85-600-70
PST105-600-70
PST142-600-70
PST175-600-70
PST210-600-70
PST250-600-70
PST300-600-70

Order code

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

25
30
37
45
55
59
75
90
132
160
184
220
257

30
37
45
55
75
80
90
110
160
200
250
295
355

45
55
59
75
90
110
132
160
220
257
315
400
500

52
64
76
85
105
124
147
181
245
300
360
430
515

PST30-690-70
PST37-690-70
PST44-690-70
PST50-690-70
PST60-690-70
PST72-690-70
PST85-690-70
PST105-690-70
PST142-690-70
PST175-690-70
PST210-690-70
PST250-690-70
PST300-690-70

Order code

1SFA 895 002 R7000


1SFA 895 003 R7000
1SFA 895 004 R7000
1SFA 895 005 R7000
1SFA 895 006 R7000
1SFA 895 007 R7000
1SFA 895 008 R7000
1SFA 895 009 R7000
1SFA 895 010 R7000
1SFA 895 011 R7000
1SFA 895 012 R7000
1SFA 895 013 R7000
1SFA 895 014 R7000

Weight
kg

4.8
4.8
4.8
4.8
5.0
5.0
11.2
13.0
13.0
21.5
21.5
23.0
23.0

PSTB370...PSTB1050 with integrated by-pass


1SFC132175F0001

230 600 V

PSTB370 ... PSTB470

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power
400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

355
450
540
710
800
1000

450
600
700
880
1000
1250

640
814
987
1247
1455
1810

400 690 V

1SFC132176F0001

1SFA 894 015 R7000


1SFA 894 016 R7000
1SFA 894 017 R7000
1SFA 894 018 R7000
1SFA 894 019 R7000
1SFA 894 020 R7000

Weight
kg

31.0
31.0
52.0
55.0
60.0
60.0

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PSTB570 ... PSTB1050

PSTB370-600-70
PSTB470-600-70
PSTB570-600-70
PSTB720-600-70
PSTB840-600-70
PSTB1050-600-70

Order code

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

355
450
540
710
800
1000

450
600
700
880
1000
1250

600
800
960
1200
1400
1700

640
814
987
1247
1455
1810

PSTB370-690-70
PSTB470-690-70
PSTB570-690-70
PSTB720-690-70
PSTB840-690-70
PSTB1050-690-70

Order code

1SFA 895 015 R7000


1SFA 895 016 R7000
1SFA 895 017 R7000
1SFA 895 018 R7000
1SFA 895 019 R7000
1SFA 895 020 R7000

Weight
kg

31.0
31.0
52.0
55.0
60.0
60.0

27
1SFC132004C0201

Softstarters

Type PST37 ... 300 and PSTB370 ... 1050


Heavy duty starts, class 30 In-Line, Ordering details
PST37 ... PST300
230 600 V

Supply voltage, Us 100...250 V, 50/60 Hz

1SFC132172F0001

Motor power

1SFC132173F0001

PST30 ... PST72

PST85 ... PST142

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

15
18.5
22
25
30
37
45
55
75
90
110
132

18.5
22
25
30
37
45
55
75
90
110
132
160

30
37
44
50
60
72
85
105
142
175
210
250

400 690 V

1SFC132174F0001

1SFA 894 003 R7000


1SFA 894 004 R7000
1SFA 894 005 R7000
1SFA 894 006 R7000
1SFA 894 007 R7000
1SFA 894 008 R7000
1SFA 894 009 R7000
1SFA 894 010 R7000
1SFA 894 011 R7000
1SFA 894 012 R7000
1SFA 894 013 R7000
1SFA 894 014 R7000

Weight
kg

4.8
4.8
4.8
5.0
5.0
11.2
13.0
13.0
21.5
21.5
23.0
23.0

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PST175 ... PST300

PST37-600-70
PST44-600-70
PST50-600-70
PST60-600-70
PST72-600-70
PST85-600-70
PST105-600-70
PST142-600-70
PST175-600-70
PST210-600-70
PST250-600-70
PST300-600-70

Order code

Heavy duty

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

15
18.5
22
25
30
37
45
55
75
90
110
132

18.5
22
25
30
37
45
55
75
90
110
132
160

25
30
37
45
55
59
75
90
132
160
184
220

30
37
44
50
60
72
85
105
142
175
210
250

PST37-690-70
PST44-690-70
PST50-690-70
PST60-690-70
PST72-690-70
PST85-690-70
PST105-690-70
PST142-690-70
PST175-690-70
PST210-690-70
PST250-690-70
PST300-690-70

Order code

1SFA 895 003 R7000


1SFA 895 004 R7000
1SFA 895 005 R7000
1SFA 895 006 R7000
1SFA 895 007 R7000
1SFA 895 008 R7000
1SFA 895 009 R7000
1SFA 895 010 R7000
1SFA 895 011 R7000
1SFA 895 012 R7000
1SFA 895 013 R7000
1SFA 895 014 R7000

Weight
kg

4.8
4.8
4.8
5.0
5.0
11.2
13.0
13.0
21.5
21.5
23.0
23.0

PSTB370 ... PSTB1050 with integrated by-pass


230 600 V

Supply voltage, Us 100...250 V, 50/60 Hz

1SFC132175F0001

Motor power

PSTB370 ... PSTB470

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

160
200
250
315
400
450

200
257
315
400
500
600

300
370
470
570
720
840

400 690 V

1SFC132176F0001

28
1SFC132004C0201

1SFA 894 015 R7000


1SFA 894 016 R7000
1SFA 894 017 R7000
1SFA 894 018 R7000
1SFA 894 019 R7000
1SFA 894 020 R7000

Weight
kg

31.0
31.0
52.0
55.0
60.0
60.0

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PSTB570...PSTB1050

PSTB370-600-70
PSTB470-600-70
PSTB570-600-70
PSTB720-600-70
PSTB840-600-70
PSTB1050-600-70

Order code

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

160
200
250
315
400
450

200
257
315
400
500
600

257
355
450
560
710
800

300
370
470
570
720
840

PSTB370-690-70
PSTB470-690-70
PSTB570-690-70
PSTB720-690-70
PSTB840-690-70
PSTB1050-690-70

Order code

1SFA 895 015 R7000


1SFA 895 016 R7000
1SFA 895 017 R7000
1SFA 895 018 R7000
1SFA 895 019 R7000
1SFA 895 020 R7000

Weight
kg

31.0
31.0
52.0
55.0
60.0
60.0

Softstarters

Type PST37 ... 300 and PSTB370 ... 1050


Heavy duty starts, class 30 Inside Delta, Ordering details
PST37 ... PST300
230 600 V

Supply voltage, Us 100...250 V, 50/60 Hz

1SFC132172F0001

Motor power

1SFC132173F0001

PST30 ... PST72

PST85 ... PST142

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

25
30
37
45
55
59
75
90
132
160
184
220

30
37
45
55
75
80
90
110
160
200
250
295

52
64
76
85
105
124
147
181
245
300
360
430

400 690 V

1SFC132174F0001

1SFA 894 003 R7000


1SFA 894 004 R7000
1SFA 894 005 R7000
1SFA 894 006 R7000
1SFA 894 007 R7000
1SFA 894 008 R7000
1SFA 894 009 R7000
1SFA 894 010 R7000
1SFA 894 011 R7000
1SFA 894 012 R7000
1SFA 894 013 R7000
1SFA 894 014 R7000

Weight
kg

4.8
4.8
4.8
5.0
5.0
11.2
13.0
13.0
21.5
21.5
23.0
23.0

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PST175 ... PST300

PST37-600-70
PST44-600-70
PST50-600-70
PST60-600-70
PST72-600-70
PST85-600-70
PST105-600-70
PST142-600-70
PST175-600-70
PST210-600-70
PST250-600-70
PST300-600-70

Order code

Heavy duty

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

25
30
37
45
55
59
75
90
132
160
184
220

30
37
45
55
75
80
90
110
160
200
250
295

45
55
59
75
90
110
132
160
220
257
315
400

52
64
76
90
105
124
147
181
245
300
360
430

PST37-690-70
PST44-690-70
PST50-690-70
PST60-690-70
PST72-690-70
PST85-690-70
PST105-690-70
PST142-690-70
PST175-690-70
PST210-690-70
PST250-690-70
PST300-690-70

Order code

1SFA 895 003 R7000


1SFA 895 004 R7000
1SFA 895 005 R7000
1SFA 895 006 R7000
1SFA 895 007 R7000
1SFA 895 008 R7000
1SFA 895 009 R7000
1SFA 895 010 R7000
1SFA 895 011 R7000
1SFA 895 012 R7000
1SFA 895 013 R7000
1SFA 895 014 R7000

Weight
kg

4.8
4.8
4.8
5.0
5.0
11.2
13.0
13.0
21.5
21.5
23.0
23.0

PSTB370...PSTB1050 with integrated by-pass


230 600 V

Supply voltage, Us 100...250 V, 50/60 Hz

1SFC132175F0001

Motor power

PSTB370 ... PSTB470

400 V
Pe
kW

500 V
Pe
kW

690 V
Pe
kW

Rated motor
current, Ie
A
Type

257
355
450
540
710
800

355
450
600
700
880
1000

515
640
814
987
1247
1455

400 690 V

1SFA 894 015 R7000


1SFA 894 016 R7000
1SFA 894 017 R7000
1SFA 894 018 R7000
1SFA 894 019 R7000
1SFA 894 020 R7000

Weight
kg,

31.0
31.0
52.0
55.0
60.0
60.0

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

1SFC132176F0001

PSTB370-600-70
PSTB470-600-70
PSTB570-600-70
PSTB720-600-70
PSTB840-600-70
PSTB1050-600-70

Order code

400 V
Pe

500 V
Pe

690 V
Pe

Rated motor
current, Ie

kW

kW

kW

Type

Order code

257
355
450
540
710
800

355
450
600
700
880
1000

500
600
800
960
1200
1400

515
640
814
987
1247
1455

PSTB370-690-70
PSTB470-690-70
PSTB570-690-70
PSTB720-690-70
PSTB840-690-70
PSTB1050-690-70

1SFA 895 015 R7000


1SFA 895 016 R7000
1SFA 895 017 R7000
1SFA 895 018 R7000
1SFA 895 019 R7000
1SFA 895 020 R7000

Weight
kg

31.0
31.0
52.0
55.0
60.0
60.0

PSTB570 ... PSTB1050

29
1SFC132004C0201

Softstarters

Accessories for type PST30 ... 300 and PSTB370 ... 1050
Ordering details
Cable connectors for Cu cables
1SFT98099-011C1

1SFT98099-095C2

For PST85...300 you need 9 pieces if also using the terminals B1, B2, B3 for external by-pass contactor.
For
softstarter
type

Wire
range
mm2

Tightening
torque
max. Nm

PST85 142
PST85 142
PST175 300

6-185
16
2 x (50-120) 16
16-240
25

Type

Order code

Packing
piece

LZ185-2C/120

1SDA 023 354 R0001


1SFN 074 709 R1000
1SDA 023 368 R0001

3
3
3

Weight
kg
1 piece

0.20
0.30
0.40

SB8054C2

Cable connectors for Al and Cu cables


For PST85...300 you need 9 pieces if also using the terminals B1, B2, B3 for external by-pass contactor.

LZ...

For
softstarter
type

Wire
range
mm2

Tightening
torque
max. Nm

Type

Order code

Packing
piece

PST85 142
PST85 142
PST175 300

35-95
25-150
120-240

13.5
31
43

1SDA 023 356 R0001


1SDA 023 357 R0001
1SDA 023 370 R0001

3
3
3

1SFT98000-012C3

Terminal extensions

LX...

For
softstarter
type

Dimensions
hole
bar
mm2
mm

Type

Order code

Packing
pieces

PST85142
PST175300
PSTB370...470
PSTB570...1050

8.5
10.5
10.5
13

LX185
LX300
LX460
LX750

1SFN 074 710 R1000


1SFN 075 110 R1000
1SFN 075 710 R1000
1SFN 076 110 R1000

1
1
1
1

17.5 x 5
20 x 5
25 x 5
40 x 6

Weight
kg
1 piece

0.10
0.10
0.10
Weight
kg
1 piece

0.250
0.350
0.500
0.850

1SFT98000-011C3

Terminal enlargements

LW...

For
softstarter
type

Dimensions
hole
bar
mm2
mm

Type

Order code

Packing
pieces

PST3072
PST85142
PST175...300
PSTB370...470
PSTB570...1050

6.5
10.5
10.5
10.5
13

LW110
LW185
LW300
LW460
LW750

1SFN 074 307 R1000


1SFN 074 707 R1000
1SFN 075 107 R1000
1SFN 075 707 R1000
1SFN 076 107 R1000

1
1
1
1
1

15 x 3
17.5 x 5
20 x 5
25 x 5
40 x 6

Weight
kg
1 piece

0.100
0.250
0.450
0.730
1.230

1SFC132010F0201

Terminal nut washer

LE185

For
softstarter
type

Type

Order code

Packing
piece

PST85...142
PST175...300

LE185
LE300

1SFN 074 716 R1000


1SFN 075 116 R1000

2
2

1SFT98099-125

1SFT98099-019C3

1SFC132113F0201

LT ... -AL

PSTM-2

30
1SFC132004C0201

1SFC132189F0001

PSTEK

0.20
0.30

Terminal shrouds
For
softstarter
type

LT ... -AC

Weight
kg
1 piece

PST85142
PST85142
PST175...300
PST175...300
PSTB370...470
PSTB370...470
PSTB570...1050
PSTB570...1050

Req. qty

Type

Order code

Packing
pieces

1 pcs and
1 pcs
1 pcs and
1 pcs
3 pcs
3 pcs
2 pcs
2 pcs
2 pcs
2 pcs

LT185-AC
LT460-AC
LT185-AL
LT460-AL
LT300-AC
LT300-AL
LT460-AC
LT460-AL
LT750-AC
LT750-AL

1SFN 124 701 R1000


1SFN 125 701 R1000
1SFN 124 703 R1000
1SFN 125 703 R1000
1SFN 125 101 R1000
1SFN 125 103 R1000
1SFN 125 701 R1000
1SFN 125 703 R1000
1SFN 126 101 R1000
1SFN 126 103 R1000

2
2
2
2
2
2
2
2
2
2

Type

Order code

Packing
piece

PSTEK

1SFA 899 003 R1000

Weight
kg
1 piece

0.050
0.100
0.220
0.800
0.070
0.280
0.100
0.800
0.120
0.825

External keypad including a 3m cable


For
softstarter
type

PST30...300
PSTB370...1050

Weight
kg
1 piece

0.400

Marine Kit
For
softstarter
type

Type

Order code

Packing
piece

PST85142

PSTM-2

1SFA 899 004 R1000

Weight
kg
1 piece

0.24

Softstarters

Orange cable

FBP FieldBusPlug
AS-Interface Fieldbus Connectors
AS-Interface FieldBusPlug Direct

Ready-made AS-Interface slave eldbus interface with various cable lengths.


Applicable on all MSD11-FBP and terminal devices with max. 2 input and 1 output signals.
Degree of protection IP65, diagnostic LED
Designation
FieldBusPlug

Cable
length

Type

Order code

AS-Interafce FBP Direct

0.25 m
0.50 m
1.00 m
5.00 m

ASD11-FBP.025
ASD11-FBP.050
ASD11-FBP.100
ASD11-FBP.500

1SAJ 210 000 R0003


1SAJ 210 000 R0005
1SAJ 210 000 R0010
1SAJ 210 000 R0050

AS-Interafce FBP Direct


AS-Interafce FBP Direct
AS-Interafce FBP Direct

Packing

Weight
kg

pieces
1
1
1
1

1 piece
0.09
0.10
0.13
0.36

AS-Interface FieldBusPlug Performance

Ready-made AS-Interface slave eldbus interface with various cable lengths.


Applicable on all FBP motor starters and devices with max. 4 input signals and 3 output signals
Degree of protection IP65, diagnostic LED

ASD11-FBP
ASP22-FBP

Packing

Weight
kg

1SAJ 220 000 R0003

pieces
1

1 piece
0.09

ASP22-FBP.050

1SAJ 220 000 R0005

0.10

1.00 m

ASP22-FBP.100

1SAJ 220 000 R0010

0.13

5.00 m

ASP22-FBP.500

1SAJ 220 000 R0050

0.36

Designation
FieldBusPlug

Cable
length

Type

Order code

AS-Interafce FBP
Performance

0.25 m

ASP22-FBP.025

AS-Interafce FBP
Performance

0.50 m

AS-Interafce FBP
Performance
AS-Interafce FBP
Performance

31
1SFC132004C0201

Softstarters

FBP FieldBusPlug
AS-Interface Fieldbus Accessories

Orange cable

Accessories for AS-Interface Bus Connection

AS-Interface Round Cable for Bus Junctions


Ready-made bus cable with an M12 connector and an open cable end.
Application on bus junctions such as e.g. AS-Interface couplers or devices with an integrated AS-Interface

Designation

Cable
length

AS-Interface Round Cable


with female connector
0.30 m
AS-Interface Round Cable
with male connector
0.30 m

Packing

Weight
kg

1 piece

Type

Order code

pieces

ASF11-FBP.030

1SAJ 922 002 R0003

0.04

ASM11-FBP.030

1SAJ 922 003 R0003

0.04

ASF11-FBP, ASM11-FBP

AS-Interface Round Cable for Bus Extension


Ready-made bus cable with M12 male and female connectors

Designation

Type

Order code

Packing
pieces

AS-Interface Extension
Cable

1.00 m

ASX11-FBP.100

1SAJ 922 001 R0010

0.08

3.00 m

ASX11-FBP.300

1SAJ 922 001 R0030

0.20

5.00 m

ASX11-FBP.500

1SAJ 922 001 R0050

0.31

100 m

ASC11-FBP.999

1SAJ 922 004 R1000

5.60

AS-Interface Extension
Cable

AS-Interface Extension
Cable

AS-Interface Extension
ASX11-FBP

Weight
kg
1 piece

Cable
length

Cable

AS-Interface Round Cable and Accessories for Bus Extension


Bus cable and coupling accessories

Designation

ASM11-FBP.0, ASF11-FBP.0

AS-Interface Round Cable,


male conn.
AS-Interface Round Cable,
female conn.
AS-Interface Flat-Cable
Branch Circuit
with M12 socket

Weight
kg
1 piece

Type

Order code

Packing
pieces

ASM11-FBP.0

1SAJ 922 005 R0001

0.15

ASF11-FBP.0

1SAJ 922 006 R0001

0.15

AST11-FBP.0

1SAJ 922 007 R0001

0.15

AS-Interface Addressing Device, Power Unit, miscellaneous accessories

AST11-FBP.0

32
1SFC132004C0201

Designation
FieldBusPlug

Type

Order code

Packing
pieces

AS-Interface Addr. Device, including


plug-in power unit
Address Signs for FieldBusPlug

ASA21-FBP.0
CAL11-FBP.0

1SAJ 922 010 R0001


1SAJ 929 005 R0001

1
400

Weight
kg
1 piece

0.56
0.15

Softstarters

FBP FieldBusPlug/DeviceNet and


MODBUS-RTU Fieldbus Connectors

Black cable

DeviceNet FieldBusPlug
Ready-made DeviceNet eldbus interface with various cable lengths.
Applicable on all FBP motor starters and other devices
Degree of protection IP65, diagnostic LED

Designation

Cable
length

Type

Order code

Packing
pieces

DeviceNet-FBP
DeviceNet-FBP
DeviceNet-FBP
DeviceNet-FBP

0.25 m
0.50 m
1.00 m
5.00 m

DNP21-FBP.025
DNP21-FBP.050
DNP21-FBP.100
DNP21-FBP.500

1SAJ 230 000 R0003


1SAJ 230 000 R0005
1SAJ 230 000 R0010
1SAJ 230 000 R0050

1
1
1
1

Weight
kg
1 piece

0.09
0.10
0.13
0.36

MODBUS-RTU FieldBusPlug
Ready-made MODBUS-RTU eldbus interface with various cable lengths.
Applicable on all FBP motor starters and other devices
Degree of protection IP65, diagnostic LED

DNP21-FBP
MRP21-FBP

Designation

Cable
length

Type

Order code

Packing
pieces

MODBUS-RTU-FBP
MODBUS-RTU-FBP
MODBUS-RTU-FBP
MODBUS-RTU-FBP

0.25 m
0.50 m
1.00 m
5.00 m

MRP21-FBP.025
MRP21-FBP.050
MRP21-FBP.100
MRP21-FBP.500

1SAJ 250 000 R0003


1SAJ 250 000 R0005
1SAJ 250 000 R0010
1SAJ 250 000 R0050

1
1
1
1

Weight
kg
1 piece

0.09
0.10
0.13
0.36

To connect the PST Softstarter to a DeviceNet eldbus system...


you need specic software for PLC set-up, (EDS le) which is available at www.abb.com/lowvoltage
on the Softstarter pages. Look under the documentation-link named Software. If you need help or advice,
please contact your local ABB ofce.

33
1SFC132004C0201

Softstarters

FBP FieldBusPlug/DeviceNet and


MODBUS-RTU Fieldbus Accessories

Black cable

Accessories for the DeviceNet and MODBUS-RTU Bus Connector


DeviceNet and MODBUS-RTU round cable for bus junctions
Ready-made bus cable with an M12 connector and an open cable end.
Designation

Round Cable
with female connector
Round Cable
with male connector

Weight
kg
1 piece

Cable
length

Type

Order code

Packing
pieces

0.50 m

DNF11-FBP.050

1SAJ 923 002 R0005

0.04

0.50 m

DNM11-FBP.050

1SAJ 923 003 R0005

0.04

DNF-11FBP.050

DeviceNet and MODBUS-RTU Round Cable for Bus Extension


Ready-made bus cable with M12 male and female connectors

DNM-11FBP.050

DNX11-FDP

Designation

Type

Order code

Packing
pieces

Extension Cable

1.00 m

DNX11-FBP.100

1SAJ 923 001 R0010

0.08

Extension Cable

3.00 m

DNX11-FBP.300

1SAJ 923 001 R0030

0.20

Extension Cable

5.00 m

DNX11-FBP.500

1SAJ 923 001 R0050

0.31

Round Cable

100 m

DNC11-FBP.999

1SAJ 923 004 R0001

5.6

DeviceNet and MODBUS-RTU Round Cable and Accessories for Bus Extension
Bus cable and coupling accessories
Designation

DNM11-FBP.0

Cable
length

Round Cable
Male Connector
Device Net Round Cable
Female Connector

Weight
kg
1 piece

Type

Order code

Packing
pieces

DNM11-FBP.0

1SAJ 923 005 R0001

0.15

DNF11-FBP.0

1SAJ 923 006 R0001

0.15

DeviceNet and MODBUS-RTU, Termination Resistor, Miscellaneous Accessories


DNF11-FBP.0

Weight
kg
1 piece

Cable
length

Designation

Type

Order code

Packing
pieces

Termination Resistor, 120 Ohm

DNR11-FBP.120

1SAJ 923 007 R0001

Weight
kg
1 piece

0.02

DNR11-FBP.120

To connect the PST Softstarter to a DeviceNet eldbus system...


you need specic software for PLC set-up, (EDS le) which is available at www.abb.com/lowvoltage
on the Softstarter pages. Look under the documentation-link named Software. If you need help or advice,
please contact your local ABB ofce.

34
1SFC132004C0201

Softstarters

FBP FieldBusPlug/Probus DP/V0, DP/V1 Fieldbus


Connectors

Purple cable

Probus DP/V0 FieldBusPlug


Ready-made Probus DP/V0 eldbus interface with various cable lengths.
Applicable on all FBP motor starters and other devices
Degree of protection IP65, diagnostic LED

Designation

Cable
length

Type

Order code

Packing
pieces

Probus DP/V0-FBP
Probus DP/V0-FBP
Probus DP/V0-FBP
Probus DP/V0-FBP

0.25 m
0.50 m
1.00 m
5.00 m

PDP21-FBP.025
PDP21-FBP.050
PDP21-FBP.100
PDP21-FBP.500

1SAJ 240 000 R0003


1SAJ 240 000 R0005
1SAJ 240 000 R0010
1SAJ 240 000 R0050

1
1
1
1

Weight
kg
1 piece

0.09
0.10
0.13
0.36

Probus DP/V1 FieldBusPlug


Ready-made Probus DP/V1 eldbus interface with various cable lengths.
Applicable on all FBP motor starters and other devices
Degree of protection IP65, diagnostic LED

PDP21-FBP
PDP22-FBP

Designation

Cable
length

Type

Order code

Packing
pieces

Probus DP/V1-FBP
Probus DP/V1-FBP
Probus DP/V1-FBP
Probus DP/V1-FBP

0.25 m
0.50 m
1.00 m
5.00 m

PDP22-FBP.025
PDP22-FBP.050
PDP22-FBP.100
PDP22-FBP.500

1SAJ 240 100 R0003


1SAJ 240 100 R0005
1SAJ 240 100 R0010
1SAJ 240 100 R0050

1
1
1
1

Weight
kg
1 piece

0.09
0.10
0.13
0.36

To connect the PST Softstarter to a Probus DP eldbus system...


you need specic software for PLC set-up, (GSD le) which is available at www.abb.com/lowvoltage
on the Softstarter pages. Look under the documentation-link named Software. If you need help or advice,
please contact your local ABB ofce.

35
1SFC132004C0201

Softstarters

FBP FieldBusPlug/Probus DP/V0, DP/V1 Fieldbus


Accessories

Purple cable

Accessories for the Probus DP/V0. DP/V1 Bus Connector


Probus DP/V0, DP/V1 Round Cable for Bus Junctions
Ready-made bus cable with an M12 connector and an open cable end.
Application on bus junctions such as e.g. Probus DB couplers or devices with an integrated Probus DB
interface

PDF11-FBP.50

Weight
kg
1 piece

Designation

Cable
length

Type

Order code

Packing
pieces

Round Cable
with female connector

0.50 m

PDF11-FBP.050

1SAJ 924 002 R0005

0.04

Round Cable
with male connector

0.50 m

PDM11-FBP.050

1SAJ 924 003 R0005

0.04

Probus DP/V0, DP/V1 Round Cable for Bus Extension


Ready-made bus cable with M12 male and female connectors

PDM11-FBP.50

Weight
kg
1 piece

Designation

Cable
length

Type

Order code

Packing
pieces

Extension Cable

1.00 m

PDX11-FBP.100

1SAJ 924 001 R0010

0.08

Extension Cable

3.00 m

PDX11-FBP.300

1SAJ 924 001 R0030

0.20

Extension Cable

5.00 m

PDX11-FBP.500

1SAJ 924 001 R0050

0.31

Round Cable

100 m

PDC11-FBP.999

1SAJ 924 004 R1000

5.60

Probus DP/V0, DP/V1 Accessories for Bus Extension

PDX11-FBP

Weight
kg
1 piece

Designation

Type

Order code

Packing
pieces

Male Connector

PDM11-FBP.0

1SAJ 924 005 R0001

0.03

Female Connector

PDF11-FBP.0

1SAJ 924 006 R0001

0.03

Probus DP/V0, DP/V1 Termination Resistor, Miscellaneous Accessories

PDM11-FBP.0

Weight
kg
1 piece

Designation

Type

Order code

Packing
pieces

Termination resistor, 150 ohm


Feeding connector 24V DC
Code B-A
Feeding connector 24V DC
Code A-A
Adaptor M12-Dsub9-M12
Cable lenth 0.50m
Adaptor M12-Dsub9-M12
Cable lenth 2 x 0.50m

PDR11-FBP.150
PDV11-FBP.0

1SAJ 924 007 R0001


1SAJ 924 008 R0001

1
1

0.03
0.04

PDV12-FBP.0

1SAJ 924 011 R0001

0.04

PDA11-FBP.050

1SAJ 924 009 R0001

0.04

PDA12-FBP.050

1SAJ 924 010 R0001

0.04

PDF11-FBP.0

To connect the PST Softstarter to a Probus DP eldbus system...


you need specic software for PLC set-up, (GSD le) which is available at www.abb.com/lowvoltage
on the Softstarter pages. Look under the documentation-link named Software. If you need help or advice,
please contact your local ABB ofce.

36
1SFC132004C0201

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050


Technical data
PST30 300

PSTB370 ... 1050

Rated insulation voltage Ui

690 V

690 V

Rated operational voltage Ue

208 ... 690 V

208 ... 690 V

Starting capacity
at max rated current Ir

3 x Ir for 15 sec. 3 x Ir for 15 sec

Number of starts per hour

30 1)

10 1)

Overload capability,
Overload Class
Service factor

10
115 %

10
115 %
100 %

0 +50 C 2)
-25 +70 C

0 +50 C 2)
-25 +70 C

Altitude
Maximum altitude

4000 m

4000 m

Degree of protection
Main circuit
Supply and Control circuit
Main circuit
Built in By-pass contactor
Cooling system - Fan cooled
(thermostat controlled)

Supply circuit
Supply voltage one range

HMI for settings


(Human Machine Interface)
20 segment display
Keypad with two selection
keys and two navigating keys
Plain text in 13 languages
(English, German, Italian,
Dutch, Chinese, Finnish,
Swedish, French, Spanish,
Russian, Portuguese,
Turkish and Polish)
Signal relays
Number of programmable
signal relays (Each relay can
be programmed to be Run,
By-pass or Event signal)
K4 Default as Run signal
K5 Default as By-pass signal
K6 Default as Event signal
Rated operational voltage Ue
Rated thermal current Ith
Rated operational current Ie
at AC-15 (Ue = 250 V)
Analog output
Output signal reference
Type of output signal

(Each input can be programmed


to be either; Non, Reset, Enable,
Jog, DOL- On, Start motor 2 or
Start motor 3, FB-Dis ).

IP10 (PST30 ... 72) IP00 (all)


IP00 ( PST85 ... 300)
IP20
IP20
No

Yes

Yes

Yes

100 ... 250 V,


50/60 Hz
+10 %/-15 %

100 ... 250 V


50/60 Hz
+10 %/-15 %

Yes

Yes

Yes

Yes

Yes

Yes

3
Yes
Yes
Yes
250 V
5A

3
Yes
Yes
Yes
250 V
5A

1.5 A

1.5 A

Yes
Yes
Yes

Yes
Yes
Yes

Yes

Yes

Yes

Yes

Yes
Yes
Yes
Yes
Yes
Yes
Yes

Yes
Yes
Yes
Yes
Yes
Yes
Yes

Yes
Yes
Yes
Yes

Yes
Yes
Yes
Yes

Start of several motors


Possible to set up and start
three different motors

Yes

Yes

Field bus connection


Connection for
ABB FieldBusPlug

Yes

Yes

PTC input
Switch off resistance
Switch on resistance

2825 ohm + 20% 2825 ohm + 20%


1200 ohm + 20% 1200 ohm + 20%

External keypad
Display
Ambient temperature
During operation
During storage
Degree of protection
1)

0 ... 10 V, 0 ...20 mA, 4 ... 20 mA


I Amp, U Volt, P kW, P hp, Q kVAr,
S kVA, TmpMot, TmpSCR, cosPhi

Yes
Yes

Yes

Protections
Electronic overload
Adjustable tripping classes Class 10 A, 10, 20 and 30
Dual overload (separate overload
function for start and run)
PTC connection
Locked rotor protection
Underload protection
Phase imbalance
High current (8 x Ie)
Phase reversal protection
Warnings (pre-warning)
High current
Low current (underload)
Overload trip
Overtemp. thyristors (SCR)

3)

PSTB370 ... 1050

Yes

Signal indication LEDs


Power on Green
Fault - Red
Protection - Yellow

(PSTB370...
PSTB840)
(PSTB1050)

Ambient temperature
During operation
During storage

3)

PST30 300

Control circuit /Hardware inputs


Internal 24 V DC (10 mA closed) Yes
Start / Stop inputs
Yes
Two extra programmable inputs

LCD type
+ 0+50 oC
-25+70 oC
IP66

Valid for 50 % on time and 50 % off time, with 3.5 x Ie for 7 seconds. If other
data is required, please contact your sales ofce

2)

Above 40 C up to max. 50 C reduce the rated current with 0.8 % per C.

3)

When used at high altitudes above 1000 meters up to 4000 meters you need
to derate rated current using the following formula.

x - 1000
[ % of Ie = 100 - ]
150
x = actual altitude for the softstarter

PSTB Integrated by-pass ratings


Softstarter

Type

PSTB370

PSTB470

PSTB570

PSTB720

PSTB840

PSTB1050

Contactor
AC-3 rating

Type
A

AF300
305

AF300
305

AF460
460

AF580
580

AF750
750

AF750
750

37
1SFC132004C0201

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050


Technical data/Settings
Major possible settings and the displayed text and the set default values
Description

Text on display
(Eng)

Values on display

Default value

Setting current for overload, locked rotor etc.


Time for start ramp
Time for stop ramp
Initial voltage for start ramp
End voltage for stop ramp
Step down voltage
Level of the current limit.
Selection of Kick start
Level of Kick start if selected
Time for Kick start if selected

Setting Ie
Start Ramp
Stop Ramp
Init Volt
End Volt
Step Down
Current Lim
Kick Start
Kick Level
Kick Time

9,0 ...1207 A divided into 19 overlapping ranges.


1 ... 30 s, 1 ... 120 s (Range depends on Start Range)
0 ... 30 s, 0 ... 120 s (Range depends on Stop Range)
30 ... 70 %
30 ... 70 %
30 ...100 %
2.0 ... 7.0 x Ie
Yes, No
50 ... 100 %
0.1 ... 1.5 s

See table, page 40


10 s
0s
30 %
30 %
100 %
4.0 x Ie
No
50 %
0.2

Selectable range for start ramp


Selectable range for stop ramp
Overload protection
Overload Class
Overload Class, Dual type, Start Class
Overload Class, Dual type, Run Class
Type of operation for overload protection
Locked rotor protection
Trip level for locked rotor protection
Trip time for locked rotor protection
Type of operation for locked rotor protection
Underload protection
Trip level for Underload protection
Trip time for Underload protection
Type of operation for Underload protection
Phase imbalance protection
Trip level for phase imbalance protection
Type of operation for phase imbalance protection
High current protection
Type of operation for high current protection
Phase reversal protection
Type of operation for phase reversal protection
PTC protection
Type of operation for PTC protection
An external Bypass contactor is used
High current warning
Trip level for high current warning
Low current warning
Trip level for low current warning
Overload warning
Trip level for overload warning
Thyristor overload warning
Type of operation for phase loss fault
Type of operation for by-pass doesnt close
Type of operation for by-pass doesnt open
Type of operation for eldbus fault
Type of operation for frequency fault
Type of operation for heat sink over temperature fault
Type of operation for thyristor short circuit fault
Function of programmable input In_0
Function of programmable input In_1
Function of programmable relay output K4
Function of programmable relay output K5
Function of programmable relay output K6
Control of the softstarter with eldbus
Number of sequences for sequence start.
Language to use on display
Password for display
Start mode
Stop mode
Torque limit
Analog output
Analog output, reference
Analog output, type of value

Start Range
Stop Range
Overload
OL Class
OL Class S
OL Class R
OL Op
Locked Rotor
Lock R Lev
Lock R Time
Lock R Op
Underload
Underl Lev
Underl Time
Underl Op
Phase Imb
Ph Imb Lev
Ph Imb Op
High I
High I Op
Phase Rev
Ph Rev Op
PTC
PTC Op
Ext ByPass
Warn I=High
Wa I=H Lev
Warn I=Low
Wa I=L Lev
Warn OL
Wa OL Lev
Warn SCR OL
Ph Loss Op
BP open Op
BP closed Op
FB Fault Op
Freq F Op
HS Temp Op
SCR SC Op
In0
In1
Relay K4
Relay K5
Relay K6
Fieldb Ctrl
No of Seq
Language
Password
Start Mode
Stop Mode
Torque limit
Analogue Out
Anl Ref
Anl Type

1 ... 30 s, 1...120 s
0 ... 30 s, 0 ... 120 s
No, Normal, Dual
10 A, 10, 20, 30
10A, 10, 20, 30
10A, 10, 20, 30
Stop-M, Stop-A, Ind
Yes, No
0.5 ... 8.0 x Ie
0.2 ... 10 s
Stop-M, Stop-A, Ind
Yes, No
0.4 ... 0.8 x Ie
1 ... 30 s
Stop-M, Stop-A, Ind
Yes, No
10 ... 80 %
Stop-M, Stop-A, Ind
Yes, No
Stop-M, Stop-A, Ind
Yes, No
Stop-M, Stop-A, Ind
Yes, No
Stop-M, Stop-A
Yes, No
Yes, No
0.5 ... 5.0 x Ie
Yes, No
0.4 ...1.0 x Ie
Yes, No
40 ... 99 %
Yes, No
Stop-M, Stop-A
Stop-M, Stop-A
Stop-M, Stop-A
Stop-M, Stop-A
Stop-M, Stop-A
Stop-M, Stop-A
Stop-M, Stop-A
None, Reset, Enable, Jog, DOL, Start 2, FB-Dis
None, Reset, Enable, Jog, DOL, Start 3, FB-Dis
Run, TOR, Event
Run, TOR, Event
Run, TOR, Event
Yes, No
No, 2, 3
US/UK, FI, SE, PT, NL, IT, FR, ES, DE, CN, RU, TR, PL
No, 1 ... 255
Volt, Torque
Volt, Torque
20 ... 200 %
Yes, No
0 ...10 V, 0 ... 20 mA, 4 ... 20 mA
I Amp, U Volt, P kW, P hp, Q kVAr, S kVA, TmpMot, TmpSCR, cosPhi

1 ... 30 s
0 ... 30 s
Normal
10
10
10
Stop-M
No
4,0 x Ie
1.0 s
Stop-M
No
0.5 x Ie
10 s
Stop-M
No
80 %
Stop-M
No
Stop-M
No
Stop-M
No
Stop-M
No
No
1.2 x Ie
No
0.8 x Ie
No
90 %
No
Stop-M
Stop-M
Stop-M
Stop-M
Stop-M
Stop-M
Stop-M
Reset
Reset
Run
TOR
Event
No
No
US/UK

38
1SFC132004C0201

Volt
Volt
150 %
No
4 ...20 mA
I Amp

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050


Technical data/Settings
Tripping curves for the integrated electronic overload protection
All units have an integrated electronic overload protection possible to set on four different tripping classes.
Below you nd a curve for each tripping class in cold state.

Time (s)
10 000

1000

100

Class 30
Class 20
Class 10
Class 10A

10

Tripping curves for electronic overload protection (Cold)

8
Current (x Ie)

1SFC132134F0201

ABB FieldBusPlug
Controlling possibilities when using different eld buses
AS-Interface

DeviceNet

Probus DP V0

Probus DP V1

Modbus-RTU

Simple control
(start/stop etc)

Complete control

Simple status information

Detailed status information

Possibilities to write parameters

Possibilities to read parameters

For more detailed information, please see the Installation and Commissioning manual available at
www.abb.com/lowvoltage on the Softstarter pages.

39
1SFC132004C0201

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050


Technical data/Settings
Cross section of connectable cables
Type of softstarter
PST30 ... 72

PST85 ... 142

PST175 ... 300

PSTB370 ... 470

PSTB570 ... 1050

L1, L2, L3
T1, T2, T3

Yes
Yes

Yes
Yes

Yes
Yes

Yes
Yes

Yes
Yes

B1, B2, B3

Yes

Yes

Yes

No

No

10 ... 95
6 ... 35

See accessories
See accessories

See accessories
See accessories

Tightening torque (recommended), Nm

6.0

See accessories

See accessories

Connection bar

No

Main circuit
Available terminals:
(For external by-pass):
Connection clamp

Tightening torque (recommended), Nm

Supply and control circuit


Connection clamp

22.5
E1859D

mm
mm

40

E1858D

Width and thickness


Hole diameter

25

20

17.5

8.5

6.5

10.2

22.5

6.5 12.5

10.5

18

E1861D

1 x mm2
2 x mm2

E1860D

Solid/Stranded
Solid/Stranded

40

49

Yes

Yes

Yes

Yes

Yes

2.5

2.5

2.5

2.5

2.5

2 x mm2

1.5

1.5

1.5

1.5

1.5

Tightening torque (recommended), Nm

0.5

0.5

0.5

0.5

0.5

Solid/Stranded

1 x mm2

Solid/Stranded

Fuse ratings and power losses


For
softstarter
Type

PST

PST30
PST37
PST44
PST50
PST60
PST72
PST85
PST105
PST142
PST175
PST210
PST250
PST300

PSTB 600 V
PSTB370
PSTB470
PSTB570
PSTB720
PSTB840
PSTB1050

PSTB 690 V
PSTB370
PSTB470
PSTB570
PSTB720
PSTB840
PSTB1050
1)
2)

Recommended
ABB Overload protection
Current
range
Type
A

Max 2)
power
loss at
rated Ie
W

Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated

9...35
11...43
13...51
15...58
18...69
22...83
25...98
32...120
43...163
53...201
63...241
75...288
90...345

100
120
140
160
190
230
270
325
435
540
645
765
920

80
125
160
160
200
250
315
400
450
500
630
700
900

170M1366
170M1368
170M1369
170M1369
170M1370
170M1371
170M1372
170M3019
170M3020
170M3021
170M5012
170M5013
170M5015

170H1007
170H1007
170H1007
170H1007
170H1007
170H1007
170H1007
170H3004
170H3004
170H3004
170H3004
170H3004
170H3004

100
160
200
200
250
315
400
400
500
550
630
630
900

Integrated
Integrated
Integrated
Integrated
Integrated
Integrated

111...425
141...540
171...655
216...828
252...966
315...1207

90
110
105
110
170
170

700
900
900
1250
1500
1800

170M5013
170M5015
170M5015
170M5018
170M6018
170M6020

170H3004
170H3004
170H3004
170H3004
170H3004
170H3004

Integrated
Integrated
Integrated
Integrated
Integrated
Integrated

111...425
141...540
171...655
216...828
252...966
315...1207

90
110
105
110
170
170

700
900
900
1250
1500
1600

170M5013
170M5015
170M5015
170M5018
170M6018
170M6019

170H3004
170H3004
170H3004
170H3004
170H3004
170H3004

Maximum fuse ratings - main circuit 1)


Bussmann fuses
A
Type
Holder

For the supply circuit 6A delayed, for MCB use C characteristics.


See PSS page 20

40
1SFC132004C0201

Power
requirements
supply
circuit
VA/VA pull in

Ferraz fuses
A
Type
6,6 URB 000 D08V 0100
6,6 URB 000 D08V 0160
6,6 URD 30 D08A 0200
6,6 URD 30 D08A 0200
6,6 URD 30 D08A 0250
6,6 URD 30 D08A 0315
6,6 URD 30 D08A 0400
6,6 URD 30 D08A 0400
6,6 URD 30 D08A 0500
6,6 URD 30 D08A 0550
6,6 URD 31 D08A 0630
6,6 URD 31 D08A 0630
6,6 URD 32 D11A 0900

5
5
5
5
5
5
10
10
10
15
15
15
15

630
900
900
1250
1600
2000

6,6 URD 31
6,6 URD 32
6,6 URD 32
6,6 URD 33
6,6 URD 33
6,6 URD 33

D08A 0630
D11A 0900
D11A 0900
D11A 1250
D11A 1250
PLAF 2000

20/480
20/480
25/900
25/860
25/860
25/860

630
900
900
1250
1600
1600

6,6 URD 31
6,6 URD 31
6,6 URD 31
6,6 URD 33
6,6 URD 33
6,6 URD 33

D08A 0630
D11A 0900
D11A 0900
D11A 1250
TTFA 1600
TTFA 1600

20/480
20/480
25/900
25/860
25/860
25/860

Softstarters

Type PST30...300, PSTB370...1050


UL ratings
3-phase motor rating - In Line
Softstarters

Motor power, P (hp), and nominal current, Ie A

Type

Ue
200V / 208V
hp
A

Ue
220V / 240V
hp
A

Ue
440V / 480V
hp
A

Ue
550V / 600V
hp
A

PST30
PST37
PST44
PST50
PST60
PST72
PST85
PST105
PST142
PST175
PST210
PST250
PST300
PSTB370
PSTB470
PSTB570
PSTB720
PSTB840
PSTB1050

7.5
10
10
15
20
20
25
30
40
50
60
75
100
125
150
200
250
300
400

10
10
15
20
20
25
30
40
50
60
75
100
100
150
200
250
300
350
450

20
25
30
40
40
50
60
75
100
125
150
200
250
300
400
500
600
700
900

25
30
40
50
50
60
75
100
125
150
200
250
300
350
500
600
700
800
1000

28
34
42
54
60
68
80
104
130
156
192
248
302
361
480
590
720
840
1062

28
34
42
54
60
68
80
104
130
156
192
248
302
361
480
590
720
840
1062

28
34
42
54
60
68
80
104
130
156
192
248
302
361
480
590
720
840
1062

28
34
42
54
60
68
80
104
130
156
192
248
302
361
480
590
720
840
1062

3-phase motor rating - Inside Delta


Softstarters

Motor power, P (hp), and nominal current, Ie A

Type

Ue
200V / 208V
hp
A

Ue
220V / 240V
hp
A

Ue
440V / 480V
hp
A

Ue
550V / 600V
hp
A

PST30
PST37
PST44
PST50
PST60
PST72
PST85
PST105
PST142
PST175
PST210
PST250
PST300
PSTB370
PSTB470
PSTB570
PSTB720
PSTB840
PSTB1050

10
15
20
25
30
30
40
50
60
75
100
125
150
200
250
300
400
500
600

15
20
25
30
40
40
50
60
75
100
100
150
200
250
300
350
500
600
700

30
40
50
60
75
75
100
125
150
200
250
300
400
500
600
700
1000
1200
1500

40
50
60
75
100
100
125
150
200
250
300
350
500
600
700
800
1200
1500
1800

42
54
72
80
104
104
130
156
192
248
302
361
480
590
720
840
1247
1454
1839

42
54
72
80
104
104
130
156
192
248
302
361
480
590
720
840
1247
1454
1839

42
54
72
80
104
104
130
156
192
248
302
361
480
590
720
840
1247
1454
1839

42
54
72
80
104
104
130
156
192
248
302
361
480
590
720
840
1247
1454
1839

41
1SFC132004C0201

Softstarters

Type PSR, PSS, PST and PSTB


Wall mounting instruction, dimensions
Minimum distance to wall/front

Dimensions
Softstarter, type

25
25
25

0
0
0

0
0
0

45
45
54

140
160
187

114
128
153

PSS18/30 ... 44/76


PSS50/85 ... 72/124
PSS85/147 ... 142/245
PSS175/300 ... 300/515

20
20
20
20

10
10
10
10

100
100
100
100

120
140
181
356

200
250
340
340

163
163
265
265

PSS ... -690 for 690 V


PSS18/30 ... 72/124
PSS85/147 ... 142/245
PSS175/300 ... 300/515

20
20
20

10
10
10

100
100
100

140
181
356

250
340
340

163
265
265

PST - all
PST30 ... 72
PST85 ... 142
PST175 ... 300

20
20
20

10
10
10

100
100
100

160
186
360

260
390
420

196
270
270

PSTB - all
PSTB370 ... 470
PSTB570 ... 1050

20
20

15
15

150
150

365
435

460
515

361
381

PSR3 ... PSR45


PSR3 ... 16
PSR25 ... 30
PSR37 ... 45
PSS ... -500 for 500 V

Dimensions
PSTEK

138

135
107
53.5

53.5

4.8

9.5

28

22.5

Dotted line denotes area


covered by external keypad

Dimensions in mm
42
1SFC132004C0201

1SFC132118F0201

118
138

14

1SFC132117F0201

23

135

Softstarters

Type PSR3 ... PSR45


Dimensions
PSR37 45

54 mm (2.13)

187 mm (7.36)

5 mm (0.20)

179 mm (7.05)

44 mm (1.73)

172 mm (6.77)

4 mm (0.16)

PSR25 30

3.5 mm (0.14)

PSR3 16

Dimensions in mm (and inches)

43
1SFC132004C0201

Softstarters

Type PSS18/30 ... PSS300/515


Dimensions

162

162
10

10

120

105

1SFC132124F0201

PSS50/85-500 72/124-500
PSS18/30-690 72/124-690

1SFC132122F0201

PSS18/30-500 44/76-500

7,5

140

132,5

17,5
20

1SFC132128F0201

264,5

PSS 175/300-500 300/515-500


PSS 175/300-690 300/515-690

1SFC132126F0201

265

132,5

PSS85/147-500 142/245-500
PSS85/147-690 142/245-690

(4x

,5

1SFC132125F0201

(4x

234

1SFC132123F0201

200

184

,5

250

7,5

125

35 35
43,75

43,75

181

11,5

1SFC132129F0201

7 (4x)
10

Dimensions in mm
44
1SFC132004C0201

340

320

340
1SFC132127F0201

)
4x

10

(
7

356
333

11,5

320

158

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050


Dimensions
PST85 ...142

PST85 ...142 with marine kit

155

262

PSTB370 ... 470

PSTB570 ... 1050

460

PST175 ... 300

46,5

1SFC132131F0201

46,5

52,5

390

251

64,5

12

1SFC132130F0201

270

PST30 ... 72

Dimensions in mm
45
1SFC132004C0201

Softstarters

Type PSR3 ... PSR45


Diagrams
PSR3 ...16
C) With fuses, contactor and O.L.

1SFB536105G1002

1SFB536105G1003

B) With MMS and auxiliary contact

1SFB536105G1001

A) With MMS

PSR25 ... 45

46
1SFC132004C0201

1SFB536105G1006

F) With fuses, contactor and O.L.

1SFB536105G1005

E) With MMS and auxiliary contact

1SFB536105G1004

D) With MMS

Softstarters

Type PSS18/30 ... PSS300/515


Diagrams
PSS18/30300/515

F6

Temperature monitor

K5

Relay, actuated at full


voltage (Ue = 100%)

K6

Relay, fault signal

T1

Control transformer

T2

Current transformer

V1-V6 Thyristor

47
1SFC132004C0201

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050


Diagrams
PST30...300

PSTB370...1050

48
1SFC132004C0201

Softstarters

Type PSR, PSS, PST and PSTB


Certications and Approvals
The table below shows the approvals and certications for different softstarters.
For approvals and/or certicates not listed below, please contact your local ABB sales ofce.
Certications and approvals

Abbreviation
Approved in

Certications

Approvals:
ship classication
societies

CE
EU

UL
USA

cULus
USA

CSA
Canada

CCC
China

GOST
Russia

ANCE
Mexico

C-tick
Australia

LRS
Gr.Britain

Germany

GL

PSR3

PSR6

PSR9

PSR12

PSR16

PSR25

PSR30

PSR37

PSR45

PSS18/30

PSS30/52

PSS37/64

PSS44/76

PSS50/85

PSS60/105

PSS72/124

PSS85/147

PSS105/181

PSS142/245

PSS175/300

PSS250/420

PSS300/515

PST30

PST37

PST44

PST50

PST60

PST72

PST85

PST105

PST142

PST175

PST210

PST250

PST300

PSTB370

PSTB470

PSTB570

PSTB720

PSTB840
PSTB1050

PSR3 ... PSR45

PSS18/30...300/215

PST30...PSTB1050

Standard design approved, the company labels bear the certication mark when this is required.

49
1SFC132004C0201

Notes

50
1SFC132004C0201

Notes

Leader in power and automation technologies


ABB (www.abb.com) is a leader in power and automation technologies that enable utility and industry customers to improve performance while lowering environmental impact. The ABB Group of
companies operates in around 100 countries and employs about
107 000 people.

Division Automation Products

The division Automation Products serves customers in the automotive, chemicals, consumer, electronics, life sciences, manufacturing,
marine, metals, minerals, paper, petroleum, turbochargers and utility
industries.
Besides strong domain knowledge of the industries we serve, our
offer includes measurement, control, communication, instrumentation, drives, motors, power electronics, software and a broad range of
low-voltage products. Much of this is sold through external channel
partners such as distributors, system integrators, contractors and
original equipment manufacturers.

Low voltage products

Due to ABBs broad program of product standardization, components of today are the building blocks of system solutions,
incorporating functionalities that will allow seamless integration in
real-time automation and information systems.
At the product level, all the low voltage products can operate together perfectly.
To create a system solution every product included has to be
equipped with the tools necessary to install, operate and maintain it
efciently throughout the product life cycle.
The range of low voltage product is supported by technical documentation. This together with design and compact unit makes it
easier than ever to incorporate our products in your system.
Our customers can nd all product related documentation such as
brochures, catalogues, selection program, certicates, drawings and
other information directly at: www.abb.com/lowvoltage.

51
1SFC132004C0201

Catalogue 1SFC132004C0201 Printed in December 2006


Prod. ABB Automation Technologies AB/Division Automation Products, Cewe-Control/XM

ABB Automation Technologies AB


Division Automation Products/Cewe-Control
SE-721 61 Vsters, Sweden
Telephone +46 21 32 07 00
Telefax +46 121 12 60 01
http://www.abb.com/lowvoltage