Product

Data

50DJ,DK,DW,DY
WeathermakerT II
Rooftop Units
Cooling with
Optional Electric Heat
20 to 27 Nominal Tons

Single-Package Rooftop Products


Designed to Meet Commercial and
Industrial Application Requirements
dedicated vertical supply/return
units
dedicated horizontal supply/return
units
variable air volume controls
constant volume controls

Features/Benefits
Design flexibility
Dedicated vertical supply/return unit
(Model 50DJ,DK) is ideal for new construction. The low unit profile is
maintained when the unit is installed
on the accessory roof curb, which
is approved by the National Roofing
Contractors Association (NRCA). The
roof curb is made watertight by the
roofer.
The ducts are attached directly to
the roof curb to allow all ductwork
to be completed before the unit is
positioned.
Dedicated horizontal unit (Model
50DW,DY) is ideal for replacement or
special applications such as thru-thewall jobs or jobs where sound must be
attenuated before the duct penetrates
the roof. Ducts connect directly to
unit, using factory-supplied flanges.
Horizontal units may be curb mounted
or slab mounted.

Unit efficiency
Dual serviceable, semi-hermetic compressors on intertwined evaporator
coil ensures excellent full and part-load
efficiency with EERs (Energy Efficiency Ratio) to 9.7. Dual refrigerant
circuits provide standby capability
should one circuit require service.
Copyright 1992 Carrier Corporation

Form 50DJ,DK-5PD

Reliable 06D Carlyle compressors are


proven performers.
Variable air volume (VAV) units have
a minimum of 5 stages of unloading.
Constant volumes have 2 stages of
capacity with field-installed accessory
unloaders available to provide 5-stage
operation.
Optional hot gas bypass valve permits low-load operation of the refrigeration system.
Optional integrated economizer permits free cooling and utilizes a solidstate enthalpy control. The economizer
operates in conjunction with mechanical cooling when required and is
factory installed for either vertical or
horizontal operation. A field-installed
differential enthalpy sensor is available
as an accessory for even greater energy savings. The use of differential enthalpy allows the unit control to
compare the enthalpy difference between return air and outside air to
determine which is more economical
to condition for enhanced energy
savings. Field-installed rainhood/filter
assembly prevents moisture or objects from entering the unit. Also
available is an accessory manual outdoor air damper that allows intake
of up to 25% nominal cfm.
Exhaust air relief is available for
economizer units:
barometric relief (CV or VAV)
power exhaust (CV)
100% modulating power exhaust
(VAV)
Power exhaust relieves up to 100%
of nominal cfm. Field-adjustable set
points on modulating power exhaust
prevent space pressurization problems. Factory-installed relief options
are unit mounted on downflow units.
Accessories can be duct mounted
on horizontal applications.
Single supply fan design reduces
noise and vibration, and avoids problems related to parallel fan designs.
Inlet guide vanes (option) are available on VAV units for fan modulation. All associated controls are factory
installed.
Alternate size motors provide
application flexibility. Optional highefficiency motors increase unit
efficiency.

Installation/serviceability
Small footprint requires less roof area
and makes unit easier to rig. Low
2

unit profile allows units to be mounted


closer to edge of building while remaining out of public view. Up to
60% smaller volume than comparable
units.
Single-point electric connections are
standard on all units, regardless of
voltage or optional heater size. Electrical service access can be made
through roof curb or side of unit.
Hinged access panels are located
so as to make it easy to reach
standard serviceable components for
maintenance. No fasteners need to be
removed, which reduces servicing
time and prevents roof leaks caused
by discarded screws puncturing the
roof.

Unit controls
Constant volume units (Model
50DJ,DW) utilize a solid-state relay
board that interfaces with any 2-stage
heat/2-stage cool thermostat. Economizer units utilize a mixed air thermistor with a field-adjustable set point.
Variable volume units (Model
50DK,DY) utilize a self-diagnostic
microprocessor based control. The
microprocessor monitors stages of
cooling, morning warm-up cycle and
unit safety controls. At start-up, the
self-diagnostic test verifies component
operation and calibration. Fault codes
reduce service troubleshooting time
and difficulty.

Accessory space temperature reset


(VAV only) prevents overcooling the
space and maintains higher airflow to
ensure adequate ventilation air to
the space. It automatically resets the
discharge air temperature up when
space temperature reaches the field
adjustable set point. Discharge air
temperature resets up 3.3 F for every
degree below set point in the space.
Unit design is ETL (Electrical Testing
Laboratory) and CSA (Canadian
Standards Association) certified.
When installed with the economizer
and power exhaust option or accessory and field-supplied switches and
wiring, units can be run in the building
pressurization mode or the smoke
purge mode. In the event of a fire or
smoke condition, a zone can be
pressurized to prevent smoke from
entering the zone, or smoke can
be exhausted from a zone. On constant volume (CV) units, a set of terminals is provided for a switch or relay
to disable the unit; all other connections must be made directly to the
appropriate device. On the VAV
units, terminals are provided for most
of the necessary connections. (Refer
to page 27 of this book.)
Terminals are provided for a fieldinstalled 115-v convenience outlet
to be used during servicing when unit
is not operating. Terminals can also
be used to power field-installed smoke
detectors.

Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
EER (Energy Efficiency Ratio) and IPLV
(Integrated Part-Load Value) Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,9
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10,11
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-18
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-24
Typical Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-27
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29,30
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-36

Model number nomenclature

Physical data
CONSTANT VOLUME UNITS
BASE UNIT 50
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)*
COMPRESSORS (2 each unit)
Capacity Steps (%) Standard
Accessory
REFRIGERANT
Operating Charge (lb), Sys 1/Sys 2
CONDENSER COILS
Face Area (sq ft)
Fins Per Inch (Al)
(Cu)
EVAPORATOR COILS
Face Area (sq ft)
Fins Per Inch
OUTDOOR AIR FANS (2 each unit)
Nominal Cfm
Nominal Hp
Watts Input (Total)
INDOOR AIR FANS (1 each unit)
Nominal Cfm
Maximum Allowable Cfm
Maximum Allowable Rpm
Standard Motor and Drive
Motor Hp
Full Load Efficiency (%)
Standard
High
Motor Frame Size
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
Belts
Quantity
Length (in.)
Optional Motor and Drive
Motor Hp
Full Load Efficiency (%)
Standard
High
Motor Frame Size
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
Belts
Quantity
Length (in.)
Optional Power Exhaust**
Motors...Hp
Fans...Diameter (in.)
Filters (Quantity...L x W x D)
20% Standard Efficiency
Disposable

DJ024
20
2440

DW024
DJ028
DW028
DJ030
DW030
20
25
25
27
27
2650
2900
3100
2930
3140
Semi-Hermetic, 06D Type, 1750 Rpm
62, 100
60, 100
55, 100
21, 42, 62, 80, 100
20, 40, 60, 80, 100
18, 37, 55, 100
R-22, Controlled by Thermostatic Expansion Valve
23.1/18.1
22.6/16.3
22.3/18.3
3-Row, 38-in. Tube Diameter
24.75
17.0
19.0
19.0
15.7
17.5
17.5
4-Row, 12-in. Tube Diameter
20.1
23.4
23.4
15
15
15
Propeller Type, 30-in. Diameter, 1140 Rpm
10,000
13,000
15,000
34 (208/230, 460 v); 1 (575 v)
1
1
1700
2400
2900
Centrifugal Type, 18 x 15-in.
8,000
10,000
10,800
10,000
12,500
12,500
1,200
1,200
1,200
1.438-in. Fan Pulley Bore, Service Factor 1.15
5
712
10
84.3
86.5
184T
10.6
4.75
780
2
56
712

84.8
88.5
213T
8.0
4.12
900
2
2
2
85
47
85
1.438-in. Fan Pulley Bore, Service Factor 1.15
10

84.8
88.5
213T
8.0
4.12
900

3
47

2
47

2
80

1...1
1...24

NA
2...18 x 24 x 2
4...24 x 24 x 2

3
3
47
85
Propeller Type, 1140 Rpm
1...1
NA
1...30
2...18 x 24 x 2
6...20 x 24 x 2

296

3
85
15

87.4
89.5
215T
8.0
4.50
980

*Weights do not include economizer. See page 6 for weights of options and accessories.
Standard fan motor is supplied with standard fan drive and belts. Optional fan motor is supplied with
optional fan drive, pulleys, and belts. Other combinations are field supplied.
**Optional unit-mounted power exhaust not available (NA) on Models 50DW. Accessory constant volume power exhaust may be duct mounted on 50DW installation.

87.4
89.5
215T
8.0
4.50
980

85.7
90.0
254T
8.0
5.00
1090
3
50

3
85

1...1
1...30

NA

2...18 x 24 x 2
6...20 x 24 x 2

VARIABLE AIR VOLUME UNITS

BASE UNIT 50
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)*
COMPRESSORS (2 each unit)
Capacity Steps (%) Standard
REFRIGERANT
Operating Charge (lb), Sys 1/Sys2
CONDENSER COILS
Face Area (sq ft)
Fins Per Inch (Al)
(Cu)
EVAPORATOR COILS
Face Area (sq ft)
Fins Per Inch
OUTDOOR AIR FANS (2 each unit)
Nominal Cfm
Nominal Hp
Watts Input (Total)
INDOOR AIR FANS (1 each unit)
Nominal Cfm
Maximum Allowable Cfm
Maximum Allowable Rpm
Standard Motor and Drive
Motor Hp
Full Load Efficiency (%)
Standard
High
Motor Frame Size
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
Belt (No Inlet Guide Vanes)
Quantity
Length (in.)
Belts (Inlet Guide Vanes)
Quantity
Length (in.)
Optional Motor and Drive
Motor Hp
Full Load Efficiency (%)
Standard
High
Motor Frame Size
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
Belts (No Inlet Guide Vanes)
Quantity
Length (in.)
Belts (Inlet Guide Vanes)
Quantity
Length (in.)
Optional Power Exhaust**
Motors...Hp
Fans...Diameter (in.)
Filters (Quantity...L x W x D)
20% Standard Efficiency
Disposable

DK024
20
2440

DY024
DK028
DY028
DK030
DY030
20
25
25
27
27
2650
2900
3100
2930
3140
Semi-Hermetic, 06D Type, 1750 Rpm
21, 42, 62, 80, 100
20, 40, 60, 80, 100
18, 37, 55, 100
R-22, Controlled by Thermostatic Expansion Valve
25.2/18.1
24.6/16.3
24.3/18.3
3-Row, 38-in. Tube Diameter
24.75
17.0
19.0
19.0
15.7
17.5
17.5
4-Row, 12-in. Tube Diameter
20.1
23.4
23.4
15
15
15
Propeller Type, 30-in. Diameter, 1140 Rpm
10,000
13,000
15,000
34 (208/230, 460 v); 1 (575 v)
1
1
1700
2400
2900
Centrifugal Type, 18 x 15-in.
8,000
10,000
10,800
10,000
12,500
12,500
1,200
1,200
1,200
1.438-in.Fan Pulley Bore, Service Factor 1.15
5
712
10
84.3
86.5
184T
10.6
4.75
780

84.8
88.5
213T
8.0
4.12
900

2
56

2
85

2
53
712

2
47

87.4
89.5
215T
8.0
4.50
980
2
85

2
2
2
95
45
90
1.438-in. Fan Pulley Bore, Service Factor 1.15
10

84.8
88.5
213T
8.0
4.12
900

3
47

3
85

2
53

2
100
15

87.4
89.5
215T
8.0
4.50
980

2
47

2
80

2
45

2
90

1...1
1...24

NA
2...18 x 24 x 2
4...24 x 24 x 2

3
47

85.7
90.0
254T
8.0
5.00
1090
3
85

3
50

3
85

2
2
53
100
Propeller Type, 1140 Rpm
1...1
NA
1...30

3
45

3
95

1...1
1...30

NA

2...18 x 24 x 2
6...20 x 24 x 2

2...18 x 24 x 2
6...20 x 24 x 2

*Weights do not include economizer. See page 6 for weights of options and accessories.
Standard fan motor is supplied with standard fan drive and belts. Optional fan motor is supplied with
optional fan drive, pulleys, and belts. Other combinations are field supplied.
**Optional unit-mounted power exhaust not available (NA) on Models 50DY. Accessory modulating
power exhaust may be duct mounted on 50DY installations.

296

Physical data (cont)


OPERATING WEIGHTS OF OPTIONS
AND ACCESSORIES

WEIGHT DISTRIBUTION AND CENTER OF GRAVITY

UNIT

50DJ,DK

50DW,DY

024
028
030
024
028
030

1
749
883
891
791
910
921

WEIGHT OF
CORNER (lb)
2
3
4
491
531
809
579
625
953
585
632
962
520
586
893
613
691
1026
620
700
1039

OPTION OR ACCESSORY
ROOFCURB
Vertical Supply/Return (50DJ,DK)
Horizontal Supply/Return (50DW,DY)
ECONOMIZER
ECONOMIZER RAINHOOD
25% OUTDOOR AIR HOOD
POWER EXHAUST
CV
VAV
HOOD FOR POWER EXHAUST OR
BAROMETRIC RELIEF
CV
VAV
HAIL GUARD
ELECTRIC HEAT (kW)
18
36
72
90
108
ALTERNATE MOTOR AND DRIVE
Size 024
028
030
COPPER CONDENSER
Size 024
028,030
INLET GUIDE VANES (VAV Only)

DIM
(ft-in.)
A
B
4-1
3-8
4-5
3-8
4-5
3-8
5-1
3-7
5-6
3-7
5-6
3-7

NOTE: Weights include economizer, but not economizer rainhood.


See Operating Weights of Options and Accessories table, at right.

WEIGHT (lb)
250
280
140
140
40
50
70
100
110
40
75
85
110
110
110
45
25
45
104
143
100

CV Constant Volume
VAV Variable Air Volume

EER and IPLV ratings


UNIT 50
DJ024
DK024
DW024
DY024
DJ028
DK028
DW028
DY028
DJ030
DK030
DW030
DY030

EER*
9.7
9.7
9.6
9.6
9.0
9.0
8.8
8.8
8.6
8.6
8.5
8.5

The integrated part load value (IPLV) is a calculated value


to compare unit part load operation. The IPLV between CV
and VAV units should not be compared, as the reduction in
indoor fan power at part load is not reflected in the VAV
units IPLV ratings. Refer to ARI 360-D1 (Air Conditioning
and Refrigeration Institute) for additional information.

IPLV*
11.2
10.0
10.9
9.8
10.2
8.9
9.6
8.4
9.5
8.4
9.0
8.0

EER Energy Efficiency Ratio


IPLV Integrated Part-Load Values

024 units only.

Part load operation


For efficient part load operation, the Weathermakert II units
utilize 2 semi-hermetic compressors, each on its own refrigerant circuit. Additional capacity steps allow the unit to
match the cooling load without cycling compressors or artificially loading the unit with hot gas bypass.
Constant volume units have 2 stages of cooling capacity
as standard. Accessory suction pressure unloaders are available for installation on the lead compressor. Accessory unloaders are NOT required on the lag compressor and should
NOT be installed. Capacity reduction is handled by the lead
compressor.
6

To provide the maximum capacity steps available, VAV


units are supplied with electric unloaders as standard.
See table below for capacity steps per unit.
CAPACITY STEPS
UNIT
SIZE

296

024
028
030

CONSTANT VOLUME (DJ,DW)


With One
With 2
Unloader
Unloaders
62,100
21,62,100
21,42,62,80,100
60,100
20,60,100
20,40,60,80,100
55,100
37,55,100
18,37,55,100

Standard

VARIABLE AIR
VOLUME
(DK,DY)
21,42,62,80,100
20,40,60,80,100
18,37,55,65,83,100

Options and Accessories


ITEM
Integrated Economizer
Inlet Guide Vanes (VAV Only)
Electric Heat
Copper/Copper Condenser Coil
High-Efficiency Supply
Fan Motors**
Alternate Supply Fan Motors
Barometric Relief
Power Exhaust (CV Only)
100% Modulating Power Exhaust
(VAV Only)
Hot Gas Bypass
Roof Curb
Time GuardT II Compressor Cycle
Delay
Condenser Hail Guard
Thermostat and Subbase (CV Only)
Compressor Unloaders (CV Only)
Head Pressure Control Package
Temperature Reset Package
(VAV Only)
Two-Step Demand Limit
Control (VAV Only)
Outdoor Air Thermostat (CV Only)
Differential Enthalpy Sensor
25% Manual Outdoor Air Damper

OPTION*
X
X
X
X

ACCESSORY

TIME GUARDt II DEVICE

X
X
X
X

X
X

X
X
X
X
X
X
X
X
X
X
X
X

LEGEND
CV Constant Volume
VAV Variable Air Volume
*Factory installed
Field installed
**Not available on 575-v units
Unit mounted on downflow units; duct mounted on horizontal units.

Accessory solid-state Time Guard II device prevents compressor short cycling


by providing a 5-minute delay before restarting the compressor after shutdown.
The use of Time Guard II devices (one per compressor) ensure proper oil return and protects motor windings from overheating.

ELECTRIC HEATER

POWER EXHAUST

Heaters are available in a wide range of capacities for factory or field installation. Most heater packages are wired for 2-stage heat. On VAV units, electric
heat is used for morning warm-up only, and is wired only for single-stage heat.

VAV MICROPROCESSOR CONTROLS


DISPLAY/SET POINT BOARD
When combined with the economizer, the power exhaust can exhaust up to 100%
of the return air and eliminate overpressurization of the building.

SET POINT
POTENTIOMETER

DISPLAY

DISPLAY
BUTTON

ECONOMIZER
DISPLAY

20
10
0
10
20

30
40

10

30

0
10

20

50
60

C
F

20

70

COLD TEMP SETPOINT

Integrated economizer saves energy by using low temperature outside air to provide cooling. The electronic control logic located in the economizer motor integrates economizer cooling with mechanical cooling. If the conditioned space requires more cooling, mechanical cooling will be brought on to satisfy the cooling
need. Solid-state enthalpy control senses both dry- and wet-bulb of the outdoor air
to provide an accurate enthalpy reading. Differential enthalpy sensor compares
outdoor temperature and humidity to return air temperature and humidity and determines the most economic mixture of air. Spring return damper motor automatically closes the outdoor air dampers in the event of a power failure.

Microprocessor-based VAV control system constantly monitors more than a


dozen system operating condition indicators throughout the unit, analyzes these
inputs, and adjusts unit operation to maintain accurate temperature control
with minimal energy consumption throughout all operating modes and loading
conditions.
By displaying any of 35 different numerical codes, the control system instantly detects and locates component problems in the unit.

Base unit dimensions 50DJ,DK


NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Center of gravity.
3. Allow 128-09 (3658) at top and 68-09 (1829) on sides
for service and operational clearance.
4. On multiunit applications allow 128-09 (3658) between adjacent condensers and economizers.
5. For smaller service and operational clear-ances, contact Carrier Application Engineering Department.
6. Bottom ducts designed to be attached to accessory
roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as
done on the accessory roof curb.
7. Always line up condenser end of unit tight against
the roof curb.
8. Units with bottom return and power exhaust require
a 90 elbow in return air duct.
9. Units with bottom supply and electric heat require a
90 elbow in supply air duct.
10. When unit is slab mounted, locate the condensate
drain as low as possible on vertical face of base rail
at the same location as the standard condensate drain
using factory supplied fitting. Plug factory drilled condensate hole.

UNIT
SIZE

WEIGHT
Lbs
Kg

A
mm

50DJ024
2580 1172.7 1244.6
50DK024
50DJ028
3040 1381.8
50DK028
1346.2
50DJ030
3070 1395.5
50DK030

B
ft-in.

mm

C
ft-in.

mm

D
ft-in.

mm

E
ft-in.

mm

F
ft-in.

4-1

1680.0 5-618 3141.0 10-31116 525.5 1-81116 807.0 2-734

4-5

1956.0

*Weights include economizer, but not rainhood.

6-5

3397.0 11-134

382.5 1-3116

mm

ft-in.

2048.0 6- 858

935.0 3-01316 2131.0 6-1178

Base unit dimensions 50DW,DY


NOTES:
1. Dimensions in [
2.

] are in millimeters.

Center of gravity.

3. Allow 128-09 (3658) at top and 68-09 (1829) on sides for service
and operational clearance.
4. On multiunit applications allow 128-09 (3658) between adjacent
condensers and economizers.
5. For smaller service and operational clearances, contact Carrier
Application Engineering Department.
6. Always line up condenser end of unit tight against the roof curb.
7. When unit is slab mounted, locate the condensate drain as low
as possible on vertical face of base rail at the same location as
the standard condensate drain using factory supplied fitting. Plug
factory drilled condensate hole.

UNIT
SIZE

WEGHT*
lbs
kgs

A
mm

50DW024
2790 1268.2 1549.4
50DY024
50DW028
3240 1472.7
50DY028
1676.4
50DW030
3280 1490.9
50DY030

B
ft-in.

mm

C
ft-in.

mm

D
ft-in.

5-1

2182.0 7-1

5-6

2470.0 8-114 810.0 2-778 4165.0

78

682.0 2-2

mm

78

E
ft-in.

3909.0 12-9

78

13-8

mm

ft-in.

533.5

1-9

379.5 1-21516

*Weight includes economizer, but not rainhood.

296

Accessory dimensions 50DJ,DK


ROOF CURB

UNIT LEVELING TOLERANCES


*From edge of unit to horizontal.
NOTE: To prevent the hazard of stagnant water build-up in the drain pan
of the indoor section, unit can only be pitched as shown.

NOTES:
1. Roof curb accessory 50DJ900391 is shipped
disassembled.
2. Dimensions in ( ) are millimeters.
3. Roof curb: 16 gage (VA03-56) steel.
4. The 028 and 030 units overhang the roof curbs
on supply air/return air end.

10

DIMENSIONS (degrees and inches)


UNIT
50DJ,DK

B
Deg
1.00

C
in.
3.25

Deg
.50

D
in.
.75

Deg
.50

in.
.75

Accessory dimensions 50DW,DY


ROOF CURB

UNIT LEVELING TOLERANCES


*From edge of unit to horizontal.
NOTE: To prevent the hazard of stagnant water build-up in the drain pan of
the indoor section, unit can only be pitched as shown.

NOTES:
1. Roof curb accessory 50DJ900401 is shipped
disassembled.
2. Dimensions in ( ) are millimeters.
3. Roof curb: 16 gage (VA03-56) steel.
4. The 028 and 030 units overhang the roof curbs
on the return air end.

DIMENSIONS (degrees and inches)


UNIT
50DW,DY

B
Deg
1.38

C
in.
4.00

Deg
.50

D
in.
.75

Deg
.50

in.
.75

11

Selection procedure (with example)


I Determine cooling and heating requirements at
design conditions.
Given:
Required Cooling Capacity (TC) . . . . . 230,000 Btuh
Sensible Heat Capacity (SHC) . . . . . . 170,000 Btuh
Required Heating Capacity . . . . . . . . . . 60,000 Btuh
Condenser Entering Air Temperature . . . . . . . . 95 F
Indoor Air Temperature . . . . . . . 80 F edb, 67 F ewb
Evaporator Air Quantity . . . . . . . . . . . . . . . 7,000 cfm
External Static Pressure . . . . . . . . . . . . . . 1.50 in. wg
Electrical Characteristics (V-Ph-Hz) . . . . . . . 460-3-60
Integrated Economizer Required.
Ewb Entering Wet Bulb
Edb Entering Dry Bulb
II Select unit based on required cooling capacity.
Enter Cooling Capacities table at condenser entering
temperature of 95 F. Unit 50DJ024 at 7,000 cfm and
67 F ewb will provide a total capacity of 233,000 Btuh
and a SHC of 174,000 Btuh. Calculate SHC correction, if required, using notes under cooling capacities
tables.
III Select unit that corresponds to power source
available.

The Electrical Data table shows that a 460-3-60 unit


is available.
IV Select heating capacity of unit to provide design
condition requirement.
Using the formula found in the notes following the Heating Capacities table, calculate unit heating capacity. Unit
50DJ024 with 18 kW will provide 61,434 Btuh (18
kW x 3413 Btuh/kW).
V Determine fan speed and power requirements
at design conditions.
Tabulated fan performance includes 2-in. disposable
filters and wet evaporator coil. Refer to Component
Pressure Drops table for economizer pressure drop (.2
in. wg) and 18 kW heater pressure drop (.11 in. wg).
Add these pressure drops to the specified external static
pressure of 1.5 in. wg:
1.50 + .20 + .11 = 1.81 in. wg
Find fan rpm and bhp at 1.8 in. wg and 7,000 cfm on
Fan Performance table. Note that the fan speed is 930
rpm and the power required is 5.2 bhp. The standard
5.0 hp motor is required.

Performance data
COOLING CAPACITIES
50DJ,DK,DW,DY024
Temp (F)
Air Entering
Condenser

85

95

100

105

115

120

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4000/0.02
72
239
114
17.1
229
110
18.5
223
108
19.2
217
106
19.9
207
101
21.3
201
99
21.9

67
220
138
16.5
210
134
17.8
205
131
18.4
200
129
19.1
190
125
20.3
185
123
21.0

62
201
161
15.8
192
156
17.0
188
154
17.6
183
151
18.2
174
147
19.5
170
145
20.0

72
247
123
17.4
235
118
18.8
230
116
19.5
224
114
20.2
212
109
21.6
207
107
22.2

Evaporator Air Quantity Cfm/BF


5000/0.03
6000/0.04
Evaporator Air Ewb (F)
67
62
72
67
228
210
255
237
152
179
131
165
16.8
16.2
17.6
17.1
218
200
243
225
147
173
126
160
18.1
17.4
19.1
18.4
212
196
237
219
145
171
124
158
18.7
17.9
19.8
19.0
207
191
231
214
142
168
122
156
19.4
18.6
20.5
19.7
196
181
218
202
138
163
117
151
20.7
19.8
21.9
21.0
191
176
213
197
135
160
115
148
21.3
20.4
22.6
21.6

7000/0.04
62
218
197
16.5
208
191
17.7
203
188
18.4
199
185
19.0
189
178
20.3
184
175
20.9

50DJ,DK,DW,DY024
Temp (F)
Air Entering
Condenser

85

95

100

105

115

120

12

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

8000/0.05
72
266
146
18.1
254
142
19.5
247
139
20.3
241
137
21.0
227
132
22.4
221
130
23.0

67
249
191
17.5
237
186
18.9
230
183
19.5
224
181
20.2
212
175
21.6
205
172
22.2

62
232
230
16.9
222
221
18.2
217
216
19.0
212
212
19.6
202
202
20.9
197
197
21.7

Evaporator Air Quantity Cfm/BF


9000/0.06
Evaporator Air Ewb (F)
72
67
62
269
252
238
153
202
237
18.2
17.6
17.1
256
239
228
148
197
227
19.7
19.0
18.5
249
233
222
146
194
222
20.3
19.7
19.2
243
227
217
144
192
217
21.1
20.3
19.8
229
215
206
139
185
206
22.5
21.6
21.2
222
208
201
136
183
201
23.2
22.4
21.9

10,000/0.06
72
271
160
18.3
259
155
19.7
252
153
20.5
245
150
21.2
231
145
22.6
224
143
23.3

67
255
213
17.7
242
208
19.0
236
205
19.8
230
202
20.5
216
196
21.8
210
193
22.5

62
244
244
17.4
233
233
18.7
228
228
19.5
223
223
20.1
211
211
21.5
206
206
22.2

72
263
139
17.9
250
134
19.4
244
132
20.1
238
130
20.8
224
125
22.2
218
123
22.9

67
245
179
17.4
233
174
18.7
227
171
19.4
220
169
20.0
209
164
21.4
202
161
22.0

62
227
214
16.8
216
209
18.1
211
205
18.7
206
202
19.3
195
194
20.6
190
190
21.3

COOLING CAPACITIES (cont)


50DJ,DK,DW,DY028
Temp (F)
Air Entering
Condenser

85

95

100

105

115

120

5000/0.02
72
314
150
25.1
300
144
27.1
293
141
28.0
286
138
28.9
272
133
30.9
266
130
31.8

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

67
290
180
24.1
277
174
25.9
270
171
26.7
265
169
27.7
252
162
29.4
245
160
30.4

62
266
209
23.0
254
202
24.7
249
199
25.5
242
197
26.3
231
191
28.0
226
188
28.8

72
324
160
25.6
309
154
27.6
302
151
28.5
294
148
29.5
279
143
31.4
272
140
32.3

Evaporator Air Quantity Cfm/BF


6250/0.02
7500/0.03
Evaporator Air Ewb (F)
67
62
72
67
300
276
335
311
197
231
170
214
24.6
23.5
26.0
25.0
287
265
319
296
191
225
164
207
26.4
25.2
28.0
26.9
280
258
311
289
188
222
161
204
27.3
26.0
29.0
27.8
273
252
303
282
185
218
158
202
28.2
26.9
30.0
28.7
260
240
287
268
179
212
152
195
29.9
28.7
31.8
30.6
253
234
279
260
176
209
149
192
30.9
29.5
32.8
31.5

8750/0.04
62
288
255
24.0
275
247
25.7
268
244
26.7
262
241
27.5
249
233
29.3
242
229
30.1

72
345
180
26.5
328
174
28.5
319
172
29.5
311
169
30.5
294
162
32.4
286
159
33.4

67
322
231
25.5
306
225
27.4
298
221
28.3
290
218
29.3
275
212
31.1
268
208
32.0

62
299
277
24.5
285
271
26.2
278
266
27.2
272
263
28.1
258
254
29.9
252
249
30.8

50DJ,DK,DW,DY028
Temp (F)
Air Entering
Condenser

85

95

100

105

115

120

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

10,000/0.04
72
350
190
26.8
333
183
28.8
324
181
29.8
316
178
30.7
298
172
32.7
289
168
33.7

67
328
247
25.8
311
240
27.6
303
237
28.6
295
234
29.5
279
227
31.3
271
224
32.3

62
306
298
24.7
291
287
26.6
285
282
27.6
278
277
28.4
265
264
30.4
258
258
31.4

Evaporator Air Quantity Cfm/BF


11,250/0.05
Evaporator Air Ewb (F)
72
67
62
353
331
312
199
261
309
26.9
25.9
25.0
336
315
299
193
255
296
28.9
27.8
27.0
327
306
291
189
250
290
29.9
28.8
27.9
319
298
285
186
247
284
30.9
29.7
28.9
301
283
271
180
240
271
32.9
31.6
30.8
291
274
265
176
237
265
33.7
32.5
31.8

VAV Units Only (50DK,DY)


BF
Ewb
kW
SHC
TC

Bypass Factor
Entering Wet-Bulb
Compressor Motor Power Input
Sensible Heat Cap. (1000 Btuh)
Total Cap. (1000 Btuh) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
tldb = t edb

sensible capacity (Btuh)

1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (hlwb ).
hlwb = hewb

total capacity (Btuh)

4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil.

12,500/0.06
72
356
208
27.0
339
201
29.0
331
199
30.0
322
195
31.0
303
189
33.0
294
185
33.9

67
335
276
26.1
318
269
28.0
310
265
29.0
302
261
30.0
286
254
31.8
278
251
32.8

62
318
318
25.3
305
305
27.4
299
299
28.3
291
291
29.3
278
278
31.3
271
271
32.3

3. SHC is based on 80 F edb temperature of air entering evaporator coil.


Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

BF

79
81

.05
.10
.20

1.04
.98
.87

ENTERING AIR DRY-BULB TEMP (F)


78
77
76
75
under 75
82
83
84
85
over 85
Correction Factor
2.07
3.11
4.14
5.18
Use formula
1.96
2.94
3.92
4.91
shown below.
1.74
2.62
3.49
4.36

Interpolation is permissible.
Correction Factor = 1.10 x (1 - BF) x (edb - 80).
4. Cooling capacities are gross and do not include deduction for indoor fan motor
heat.

13

Performance data (cont)


COOLING CAPACITIES (cont)
50DJ,DK,DW,DY030
Temp (F)
Air Entering
Condenser

85

95

100

105

115

5400/0.02

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

72
336
161
26.6
323
155
28.7
316
152
29.8
308
149
30.8
294
143
32.9

67
310
193
25.5
297
187
27.4
291
184
28.4
284
180
29.4
272
175
31.2

62
283
223
24.2
273
218
26.2
267
214
27.1
261
211
27.9
249
206
29.7

72
352
172
27.3
338
167
29.5
331
164
30.6
323
161
31.6
306
154
33.6

Evaporator Air Quantity Cfm/BF


6750/0.03
8100/0.04
Evaporator Air Ewb (F)
67
62
72
67
326
300
363
337
212
250
184
230
26.1
25.0
27.8
26.6
312
288
348
323
206
244
178
224
28.2
26.9
30.0
28.7
305
281
339
314
202
240
175
221
29.2
27.9
31.1
29.7
298
274
332
307
200
237
171
218
30.1
28.7
32.1
30.6
284
261
314
292
194
231
165
211
32.1
30.5
34.1
32.6

9450/0.05
62
312
275
25.6
298
268
27.5
291
264
28.4
284
260
29.4
270
253
31.2

72
372
194
28.2
355
188
30.3
347
185
31.5
338
182
32.5
320
175
34.6

67
346
247
27.1
330
241
29.0
323
238
30.2
313
235
31.1
297
228
33.0

62
321
297
26.0
307
290
27.9
299
285
28.8
292
282
29.9
277
272
31.7

50DJ,DK,DW,DY030
Temp (F)
Air Entering
Condenser

85

95

100

105

115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

72
378
204
28.4
360
198
30.6
352
195
31.7
342
192
32.8
325
185
34.9

Evaporator Air Quantity Cfm/BF


10,800/0.05
12,150/0.06
Evaporator Air Ewb (F)
67
62
72
67
353
328
382
357
264
316
214
280
27.4
26.3
28.6
27.5
335
314
364
340
257
307
207
273
29.3
28.2
30.8
29.6
327
306
356
331
254
303
204
269
30.4
29.2
31.9
30.6
319
299
346
324
250
297
201
267
31.4
30.3
33.0
31.7
302
285
330
307
243
285
195
259
33.4
32.2
35.2
33.7

VAV units only (50DK,DY)


BF
Ewb
kW
SHC
TC

Bypass Factor
Entering Wet-Bulb
Compressor Motor Power Input
Sensible Heat Cap. (1000 Btuh)
Total Cap. (1000 Btuh) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
tldb = t edb

sensible capacity (Btuh)

1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h lwb ).
hlwb = hewb

14

total capacity (Btuh)


4.5 x cfm

62
335
331
26.6
320
320
28.6
314
314
29.7
306
306
30.6
293
243
32.8

Where: h ewb = Enthalpy of air entering evaporator coil.


3. SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

BF

79
81

.05
.10
.20

1.04
.98
.87

ENTERING AIR DRY-BULB TEMP (F)


78
77
76
75
under 75
82
83
84
85
over 85
Correction Factor
2.07
3.11
4.14
5.18
Use formula
1.96
2.94
3.92
4.91
shown below.
1.74
2.62
3.49
4.36

Interpolation is permissible.
Correction Factor = 1.10 x (1 - BF) x (edb - 80).
4. Cooling capacities are gross and do not include deduction for indoor fan motor
heat.

ELECTRIC HEATER CAPACITIES


CONSTANT VOLUME UNITS
UNIT 50

VOLTAGE

LOW (kW)
Single Stage

208
230
460
575
208
230
460
575
208
230
460
575

15
18
18
N/A
15
18
18
N/A
15
18
18
N/A

DJ
024,028,030

DW
024

DW
028,030

MED (kW)
Two Stages
1st
1st and 2nd
15
29
18
36
18
36
18
36
15
29
18
36
18
36
18
36
15
29
18
36
18
36
18
36

HIGH (kW)
Two Stages
1st
1st and 2nd
29
59
36
72
54
90
54
72
45
74
54
90
54
90
54
90
45
74
54
90
72
108
72
108

VARIABLE AIR VOLUME UNITS


UNIT 50

VOLTAGE

DK,DY
024,028,030

208
230, 460
575

LOW (kW)
Single Stage
15
18
N/A

MED (kW)
Single Stage
29
36
36

N/A Not applicable


NOTES:
1. High heat not available on VAV units.
2. Btuh = kW x 3413 Btuh/kW

FAN PERFORMANCE 50DJ UNITS AND 50DK UNITS WITHOUT INLET GUIDE VANES
UNIT
50DJ,DK

AIRFLOW
(Cfm)

024

6,000
7,000
8,000
9,000
10,000

UNIT
50DJ,DK

AIRFLOW
(Cfm)

024
(cont)

6,000
7,000
8,000
9,000
10,000

UNIT
50DJ,DK

AIRFLOW
(Cfm)

028,030

7,000
8,000
9,000
10,000
11,000
12,000
12,500

UNIT
50DJ,DK

AIRFLOW
(Cfm)

028,030
(cont)

7,000
8,000
9,000
10,000
11,000
12,000
12,500

0.2
Rpm Bhp
570
1.8
630
2.7
690
3.8
760
5.2
830
6.7

0.4
Rpm Bhp
620
2.2
670
2.9
730
4.2
800
5.4
860
7.2

0.6
Rpm Bhp
660
2.4
710
3.3
770
4.5
830
5.8
890
7.6

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)


0.8
1.0
1.2
1.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
690
2.6
730
2.9
770
3.3
820 3.6
750
3.5
790
3.8
830
4.2
860 4.5
800
4.7
830
5.0
860
5.5
900 5.7
860
6.2
890
6.5
930
7.0
960 7.6
920
8.0
950
8.6
980
9.1 1010 9.6

1.6
Rpm Bhp
850
3.8
890
4.7
930
6.2
990
8.1
1040 10.1

1.8
Rpm Bhp
880
4.0
930
5.2
960
6.6
1020
8.6
1060 10.5

2.0
Rpm Bhp
920
4.3
960
5.6
1000
7.2
1040
8.9
1090 10.8

2.2
Rpm Bhp
950
4.7
990
6.2
1030
7.6
1070
9.4
1120 11.1

2.4
Rpm Bhp
980
5.2
1030
6.6
1060
8.0
1100
9.7
1150 11.6

2.6
Rpm Bhp
1020
5.7
1060
6.9
1080
8.3
1130 10.2
1170 12.0

AVAILABLE
2.8
Rpm Bhp
1050
5.9
1080
7.2
1120
8.7
1160 10.6
1190 12.4

EXTERNAL STATIC PRESSURE (in. wg)


3.0
3.2
3.4
Rpm Bhp Rpm Bhp Rpm Bhp
1080
6.2 1110
6.7 1130
7.0
1110
7.6 1140
8.0 1160
8.4
1140
9.0 1170
9.5 1190 10.0
1180 10.9 1200 11.3

3.6
Rpm Bhp
1150 7.3
1180 8.8

3.8
Rpm Bhp
1180 7.7

4.0
Rpm Bhp
1200 8.0

0.2
Rpm Bhp
550
2.3
590
3.1
640
4.4
710
5.7
770
7.0
850
9.2
870 10.0

0.4
Rpm Bhp
590
2.5
630
3.5
690
4.6
750
5.9
820
7.5
870
9.5
910 11.0

0.6
Rpm Bhp
630
2.8
670
3.8
730
4.9
800
6.3
850
8.0
910 10.4
940 11.5

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)


0.8
1.0
1.2
1.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
670
3.0 710
3.3
750
3.5
800
3.9
720
4.1 760
4.5
800
4.7
830
5.0
770
5.2 810
5.6
840
5.9
870
6.2
830
6.8 860
7.2
900
7.7
940
8.4
880
8.6 910
9.0
940
9.6
970 10.0
940 10.9 960 11.2
990 11.7 1020 12.2
960 11.9 980 12.3 1010 12.7 1040 13.2

1.6
Rpm Bhp
830
4.3
860
5.3
900
6.6
980
9.2
1000 10.6
1050 12.7
1070 13.7

1.8
Rpm Bhp
870
4.6
900
5.7
940
7.2
1010
9.6
1030 11.1
1070 13.2
1100 14.5

2.0
Rpm Bhp
900
4.9
930
6.1
970
7.8
1030
9.9
1060 11.5
1100 13.7
1120 14.8

2.2
Rpm Bhp
930
5.2
960
6.6
1000
8.4
1060 10.2
1080 12.0
1130 14.3
1150 15.4

2.4
Rpm Bhp
970
5.7
1000
7.2
1030
8.7
1090 10.8
1110 12.5
1160 14.8
1170 15.8

2.6
Rpm Bhp
1000
6.3
1030
7.6
1060
9.2
1120 11.1
1130 12.8
1180 15.3
1200 16.5

AVAILABLE
2.8
Rpm Bhp
1030
6.7
1060
8.0
1090
9.5
1140 11.4
1160 13.1
1200 15.6

3.6
Rpm Bhp
1140
7.9
1170
9.5
1190 11.1

3.8
Rpm Bhp
1170 8.2
1190 9.9

4.0
Rpm Bhp
1190 8.8

Bhp Brake Horsepower


Boldface Special order motor required.
NOTES:
1. Fan performance is based on wet coils, clean 2-in. filters and roof curb.
2. See Component Pressure Drops table, page 18, before using fan performance
tables.
3. Conversion Bhp to Watts
Bhp x 746
Watts =
motor efficiency

EXTERNAL STATIC PRESSURE (in. wg)


3.0
3.2
3.4
Rpm Bhp Rpm Bhp Rpm Bhp
1060
6.9 1080
7.2 1110
7.5
1080
8.3 1110
8.6 1140
9.0
1120 10.0 1140 10.3 1170 10.7
1170 11.9 1190 12.4

1180 13.6 1200 14.0

See Physical Data table, pages 4 and 5, for motor efficiencies.


4. Minimum airflow shown is minimum recommended design cfm. Minimum airflow shown is minimum heating cfm for units equipped with electric heater.
5. VAV units can operate down to 70 cfm/nominal ton in cooling mode.

15

Performance data (cont)


FAN PERFORMANCE 50DW UNITS AND 50DY UNITS WITHOUT INLET GUIDE VANES
UNIT
50DW,DY

AIRFLOW
(Cfm)

024

6,000
7,000
8,000
9,000
10,000

UNIT
50DW,DY

AIRFLOW
(Cfm)

024
(cont)

6,000
7,000
8,000
9,000
10,000

UNIT
50DW,DY

AIRFLOW
(Cfm)

028,030

7,000
8,000
9,000
10,000
11,000
12,000
12,500

UNIT
50DW,DY

AIRFLOW
(Cfm)

028,030
(cont)

7,000
8,000
9,000
10,000
11,000
12,000
12,500

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)


0.8
1.0
1.2
1.4
1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
710
2.8
760
3.1
790 3.3
830
3.6
870
3.9
770
3.8
810
4.1
840 4.4
870
4.7
920
5.1
830
5.0
860
5.3
900 5.7
930
6.1
960
6.5
900
6.7
930
7.2
960 7.6
990
8.1 1020
8.5
960
8.7
990
9.3 1020 9.7 1050 10.1 1080 10.5

0.2
Rpm Bhp
570
1.9
650
2.9
720
4.1
800
5.4
870
7.2

0.4
Rpm Bhp
620
2.1
690
3.1
760
4.4
830
5.8
900
7.7

0.6
Rpm Bhp
670
2.5
730
3.5
790
4.7
870
6.2
930
8.3

2.2
Rpm Bhp
970
5.0
1020
6.5
1060
7.9
1110
9.8
1160 11.8

2.4
Rpm Bhp
1010
5.5
1050
6.8
1090
8.2
1140 10.4
1180 12.1

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)


2.6
2.8
3.0
3.2
3.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1040
5.9 1070
6.2 1100 6.5 1130
7.0 1160 7.5
1080
7.2 1110
7.5 1140 8.0 1160
8.3 1190 8.8
1120
8.7 1150
9.2 1170 9.6 1200 10.1

1170 10.7 1190 11.1

1200 12.5

0.2
Rpm Bhp
630
2.7
670
3.7
740
5.0
810
6.4
870
8.4
950 11.0
980 12.2

0.4
Rpm Bhp
680
3.0
720
4.0
780
5.2
840
6.9
910
9.1
980 11.6
1020 12.9

0.6
Rpm Bhp
720
3.3
760
4.3
810
5.5
870
7.4
940
9.5
1010 12.1
1040 13.3

2.2
Rpm Bhp
1000
6.3
1030
7.7
1070
9.3
1120 11.1
1170 13.3

2.4
Rpm Bhp
1030
6.7
1060
8.1
1100
9.6
1150 11.5
1200 13.9

AVAILABLE
2.6
Rpm Bhp
1060
7.0
1090
8.4
1130 10.2
1170 12.0

AVAILABLE
0.8
Rpm Bhp
760
3.6
790
4.6
840
6.0
910
7.9
970 10.0
1040 12.6
1070 13.9

2.0
Rpm Bhp
940
4.6
980
6.0
1020
7.4
1080
9.4
1130 11.4

1.8
Rpm Bhp
930
5.3
960
6.7
1020
8.5
1070 10.5
1120 12.4
1170 15.0
1190 16.2

2.0
Rpm Bhp
970
5.8
1000
7.2
1040
8.9
1090 10.8
1150 13.0
1200 15.5

1.8
Rpm Bhp
940
5.3
990
6.9
1030
8.5
1090 10.3
1140 12.5

2.0
Rpm Bhp
970
5.6
1020
7.3
1060
8.9
1120 10.7
1170 13.0

3.6
Rpm Bhp
1190 7.9

EXTERNAL STATIC PRESSURE (in. wg)


1.0
1.2
1.4
1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
800
3.9
830
4.3
860
4.6
900
4.9
820
4.9
860
5.3
900
5.7
930
6.2
880
6.4
920
6.9
950
7.5
980
8.1
950
8.5
980
9.1 1010
9.6 1040 10.0
1010 10.7 1040 11.2 1070 11.6 1090 12.0
1070 13.2 1090 13.6 1120 14.0 1150 14.6
1090 14.4 1120 14.8 1140 15.2 1170 15.7

EXTERNAL STATIC PRESSURE (in. wg)


2.8
3.0
3.2
3.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1090
7.3 1120
7.6 1140
8.0 1170
8.4
1120
8.7 1140
9.1 1160
9.5 1190 10.0
1160 10.6 1180 11.0 1200 11.3

1200 12.5

1.8
Rpm Bhp
910
4.3
950
5.5
990
7.0
1050
8.9
1100 10.9

3.6
Rpm Bhp
1190 8.8

FAN PERFORMANCE 50DK UNITS WITH INLET GUIDE VANES


UNIT
50DK

AIRFLOW
(Cfm)

024

6,000
7,000
8,000
9,000
10,000

UNIT
50DK

AIRFLOW
(Cfm)

024
(cont)

6,000
7,000
8,000
9,000
10,000

0.2
Rpm Bhp
640
2.6
710
3.8
770
5.0
850
6.7
920
8.7

0.4
Rpm Bhp
680
2.9
750
4.1
810
5.5
880
7.0
960
9.4

0.6
Rpm Bhp
730
3.3
790
4.5
840
5.8
910
7.5
990 10.1

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)


0.8
1.0
1.2
1.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
770
3.7
810
4.1
840
4.4
870
4.7
820
4.8
860
5.1
890
5.4
930
5.9
870
6.1
910
6.6
940
7.0
970
7.5
940
8.0
970
8.5 1000
9.0 1030
9.5
1020 10.6 1040 11.0 1070 11.4 1090 11.7

1.6
Rpm Bhp
910
5.0
960
6.4
1000
8.0
1060
9.9
1120 12.1

2.2
Rpm Bhp
1010
6.0
1050
7.6
1090
9.3
1150 11.2
1200 13.5

2.4
Rpm Bhp
1040
6.5
1080
8.0
1120
9.7
1170 11.7

AVAILABLE
2.6
Rpm Bhp
1070
7.0
1110
8.5
1150 10.1
1200 12.3

EXTERNAL STATIC PRSSURE (in. wg)


2.8
3.0
3.2
Rpm Bhp Rpm Bhp Rpm Bhp
1090
7.3 1120
7.6 1150
8.1
1140
9.0 1160
9.4 1190
9.8
1170 10.6 1200 11.1

3.6
Rpm Bhp
1200 8.8

Bhp Brake Horsepower

16

3.4
Rpm Bhp
1170
8.4

FAN PERFORMANCE 50DK UNITS WITH INLET GUIDE VANES (cont)


UNIT
50DK

AIRFLOW
(Cfm)

028,030

7,000
8,000
9,000
10,000
11,000
12,000
12,500

UNIT
50DK

AIRFLOW
(Cfm)

028,030
(cont)

7,000
8,000
9,000
10,000
11,000
12,000
12,500

0.2
Rpm Bhp
630
3.2
690
4.3
750
5.7
830
7.3
900
9.7
960 12.1
990 13.4

0.4
Rpm Bhp
660
3.4
730
4.7
790
6.0
860
7.8
930 10.2
990 12.7
1020 13.9

0.6
Rpm Bhp
700
3.6
770
5.0
830
6.4
890
8.3
960 10.8
1020 13.3
1050 14.6

2.2
Rpm Bhp
990
6.9
1040
8.6
1070 10.0
1130 12.3
1170 14.8

2.4
Rpm Bhp
1020
7.3
1070
9.0
1100 10.4
1160 12.8
1200 15.3

AVAILABLE
2.6
Rpm Bhp
1050
7.6
1100
9.4
1130 10.9
1180 13.4

AVAILABLE
0.8
Rpm Bhp
740
4.0
810
5.5
860
6.8
920
8.8
990 11.4
1050 14.0
1070 15.2

EXTERNAL STATIC PRESSURE (in. wg)


1.0
1.2
1.4
Rpm Bhp Rpm Bhp Rpm Bhp
780
4.4
830
4.8
860
5.2
850
5.9
880
6.3
920
6.7
900
7.3
930
7.9
960
8.3
950
9.3
980
9.9 1010 10.5
1010 11.8 1040 12.3 1070 12.8
1080 14.6 1100 15.0 1130 15.5
1100 15.7 1130 16.2 1160 16.9

EXTERNAL STATIC PRESSURE (in. wg)


2.8
3.0
3.2
Rpm Bhp Rpm Bhp Rpm Bhp
1080
8.0 1100
8.3 1130
8.7
1120
9.7 1140 10.0 1160 10.3
1150 11.3 1180 11.9 1200 12.3
1200 13.7

3.4
Rpm Bhp
1160
9.2
1190 10.9

1.6
Rpm Bhp
890
5.5
950
7.2
990
8.8
1040 10.9
1100 13.3
1160 16.0

1.8
Rpm Bhp
920
5.8
980
7.9
1020
9.3
1070 11.3
1120 13.7
1180 16.6

2.0
Rpm Bhp
960
6.4
1010
8.3
1050
9.7
1100 11.7
1150 14.2
1200 17.0

1.6
Rpm Bhp
900
4.9
950
6.2
1010
8.2
1080 10.2
1140 12.6

1.8
Rpm Bhp
940
5.3
990
6.7
1040
8.5
1110 10.6
1160 13.0

2.0
Rpm Bhp
970
5.7
1020
7.2
1070
8.9
1130 11.0
1190 13.4

1.6
Rpm Bhp
910
5.7
980
7.7
1040
9.6
1110 12.0
1170 14.7

1.8
Rpm Bhp
940
6.1
1010
8.2
1070 10.0
1130 12.4
1200 15.3

2.0
Rpm Bhp
970
6.6
1040
8.6
1100 10.4
1160 12.8

3.6
Rpm Bhp
1190 9.7

FAN PERFORMANCE 50DY UNITS WITH INLET GUIDE VANES


UNIT
50DY

AIRFLOW
(Cfm)

024

6,000
7,000
8,000
9,000
10,000

UNIT
50DY

AIRFLOW
(Cfm)

024
(cont)

6,000
7,000
8,000
9,000
10,000

UNIT
50DY

AIRFLOW
(Cfm)

028,030

7,000
8,000
9,000
10,000
11,000
12,000
12,500

UNIT
50DY

AIRFLOW
(Cfm)

028,030
(cont)

7,000
8,000
9,000
10,000
11,000
12,000
12,500

0.6
Rpm Bhp
710
3.2
780
4.4
850
5.9
930
7.9
1000 10.2

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)


0.8
1.0
1.2
1.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
750
3.5
790
3.8
830
4.2
870
4.6
810
4.8
850
5.1
890
5.4
920
5.7
880
6.3
910
6.6
950
7.1
980
7.7
960
8.3
990
8.8 1020
9.3 1050
9.7
1030 10.8 1060 11.2 1090 11.6 1120 12.2

0.2
Rpm Bhp
620
2.5
700
3.7
780
5.2
860
6.7
940
9.2

0.4
Rpm Bhp
670
2.9
740
4.0
810
5.6
900
7.3
970
9.6

2.2
Rpm Bhp
1010
6.2
1050
7.6
1100
9.3
1160 11.5

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)


2.4
2.6
2.8
3.0
3.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1040
6.6 1070
7.0 1000
7.4 1130
7.8
1160
8.3
1080
8.0 1110
8.5 1140
8.9 1170 9.5 1200 10.0
1130
9.8 1160 10.2 1190 10.8

1190 12.0

0.6
Rpm Bhp
740
4.1
820
5.6
880
7.1
960
9.5
1030 12.0
1100 14.9
1130 16.5

AVAILABLE
0.8
Rpm Bhp
780
4.4
860
5.9
910
7.5
990 10.1
1060 12.5
1130 15.6
1160 16.9

EXTERNAL STATIC PRESSURE (in. wg)


1.0
1.2
1.4
Rpm Bhp Rpm Bhp Rpm Bhp
810
4.7
840
5.0
880
5.3
890
6.3
920
6.7
950
7.2
940
8.0
980
8.6 1010
9.2
1020 10.6 1050 11.0 1180 11.5
1090 13.1 1120 13.6 1140 14.2
1160 16.1 1180 16.5 1200 17.0

0.2
Rpm Bhp
660
3.5
740
4.7
820
6.3
900
8.5
970 11.1
1050 13.9
1070 14.8

0.4
Rpm Bhp
700
3.8
780
5.2
850
6.7
930
9.0
1000 11.6
1080 14.5
1100 15.7

2.2
Rpm Bhp
1000
7.0
1070
8.9
1130 11.0
1190 13.5

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)


2.4
2.6
2.8
3.0
3.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1030
7.4 1060
7.8 1100
8.3 1130
8.8 1160
9.3
1100
9.3 1130
9.8 1160 10.2 1180 10.7 1200 11.2
1150 11.4 1170 11.8 1200 12.3

Bhp Brake Horsepower


Boldface Special order motor required.
NOTES:
1. Fan performance is based on wet coils, clean 2-in. filters and roof curb.
2. See Component Pressure Drops table, page 18, before using fan performance
tables.
3. Conversion Bhp to Watts
Bhp x 746
Watts =
motor efficiency
See Physical Data table, pages 4 and 5, for motor efficiencies.

3.4
Rpm Bhp
1190 8.8

3.4
Rpm Bhp
1190 9.8

4. Minimum airflow shown is minimum recommended design cfm. Minimum


airflow shown is minimum heating cfm for units equipped with electric heater.
5. VAV units can operate down to 70 cfm/nominal ton in cooling mode.

17

Performance data (cont)


COMPONENT PRESSURE DROPS (in. wg)
COMPONENT
ECONOMIZER
All Units
LOW ELECTRIC HEAT
208/230 and 460 V
50DJ,DK
50DW,DY
MED ELECTRIC HEAT
208/230, 460 and 575 V
50DJ,DK
50DW,DY
HIGH ELECTRIC HEAT
208/230 V
50DJ
50DW
460 and 575 V
50DJ
50DW024
50DW028,030

6000

7000

8000

CFM
9000
10,000

0.18

0.20

0.25

0.28

0.03
0.03

0.11
0.10

0.15
0.14

0.20
0.09

0.24
0.13

0.28
0.12
0.26
0.11
0.11

50DJ,DK,DW,DY024
POWER EXHAUST FAN PERFORMANCE

18

11,000

12,000

0.32

0.36

0.40

0.16
0.14

0.18
0.15

0.18
0.17

0.19
0.20

0.29
0.14

0.35
0.16

0.41
0.21

0.48
0.25

0.56
0.30

0.33
0.16

0.39
0.18

0.47
0.20

0.58
0.23

0.68
0.30

0.80
0.32

0.33
0.16
0.16

0.41
0.19
0.19

0.49
0.21
0.24

0.58
0.23
0.26

0.68
0.30
0.35

0.80
0.32
0.40

50DJ,DK,DW,DY028,030
POWER EXHAUST FAN PERFORMANCE

Electrical data
UNIT 50DJ,DW024
NOMINAL
V-PH-HZ

208/230-3-60

460-3-60

575-3-60

FLA
Hp
IFM
LRA

VOLTAGE
RANGE
Min

187

414

518

Max

254

508

632

Full Load Amps


Nominal Horsepower
Indoor Fan Motor
Locked Rotor Amps

COMPR
NO. 1
RLA

43.3

22.1

17.9

COMPR
NO. 2

LRA

228

114

91

MCA
MOCP
OFM
RLA

RLA

31.5

15.7

12.6

LRA

160

80

64

OFM
Total
FLA

POWER EXHAUST
FAN MOTOR**

IFM
Hp

FLA

5.0*

15.2

7.5*

22.0

5.0

12.4

7.5

19.6

5.0*

7.2

7.5*

10.5

5.0

6.2

7.5

9.8

5.0*

5.6

7.5*

8.6

6.4

3.2

4.8

Minimum Circuit Amps (for wire sizing)


Maximum Overcurrent Protection
Outdoor Fan Motor
Rated Load Amps

ELECTRIC
HEAT

POWER SUPPLY

FLA

kW

FLA

MCA

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

2.4

2.4

2.4

2.4

2.4

2.4

15-18
15-18
29-36
29-36
59-72**
59-72**
74-90

15-18
15-18
29-36
29-36
59-72**
59-72**
74-90

15-18
15-18
29-36
29-36
59-72**
59-72**
74-90

15-18
15-18
29-36
29-36
59-72**
59-72**
74-90

18
18
36
36
90
90

18
18
36
36
90
90

18
18
36
36
90
90

18
18
36
36
90
90

36
36
72**
72**
90

36
36
72**
72**
90

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

22.6
22.6
45.2
45.2
113.0
113.0

22.6
22.6
45.2
45.2
113.0
113.0

22.6
22.6
45.2
45.2
113.0
113.0

22.6
22.6
45.2
45.2
113.0
113.0

36.1
36.1
72.3
72.3
90.4

36.1
36.1
72.3
72.3
90.4

108.5-108.5
115.1-114.5
108.5-108.5
115.1-114.5
121.2-132.0
121.2-132.0
223.5-245.2
223.5-245.2
274.6-301.4
115.3-115.3
121.9-121.3
115.3-115.3
121.9-121.3
129.8-140.5
129.8-140.5
232.0-253.8
283.1-309.9
232.0-253.8
105.7-105.7
112.3-111.7
105.7-105.7
112.3-111.7
117.7-128.5
117.7-128.5
220.0-241.7
220.0-241.7
271.1-297.9
112.9-112.9
119.5-118.9
112.9-112.9
119.5-118.9
126.7-137.5
126.7-137.5
229.0-250.7
229.0-250.7
280.1-306.9
53.7
56.7
53.7
56.7
65.5
65.5
150.2
150.2
57.0
60.0
57.0
60.0
69.6
69.6
154.4
154.4
52.7
55.7
52.7
55.7
64.2
64.2
149.0
149.0
56.3
59.3
56.3
59.3
68.7
68.7
153.5
153.5
45.4
47.8
52.1
52.1
97.4
97.4
120.0
48.4
50.8
55.9
55.9
101.1
101.1
123.7

MOCP
Fuse Only
150-150
150-150
150-150
150-150
150-150
150-150
225-250
225-250
300-350
150-150
150-150
150-150
150-150
150-175
150-175
250-300
300-350
250-300
125-125
150-150
125-125
150-150
125-125
150-150
225-250
225-250
300-300
150-150
150-150
150-150
150-150
150-150
150-150
250-300
250-300
300-350
70
70
70
70
70
70
175
175
70
80
70
80
80
80
175
175
70
70
70
70
70
70
150
150
70
80
70
80
80
80
175
175
60
60
60
60
125
125
125
60
60
70
70
125
125
125

*Standard efficiency
High efficiency
**DJ units only
DW units only

(208/230, 460 v only)

19

Electrical data (cont)


UNIT 50DJ,DW028
NOMINAL
V-PH-HZ

208/230-3-60

460-3-60

575-3-60

20

VOLTAGE
RANGE
Min

187

414

518

Max

254

508

632

COMPR
NO. 1
RLA

63.6

28.6

22.9

LRA

266

120

96

COMPR
NO. 2
RLA

39.7

19.9

15.9

LRA

198

99

79

OFM
Total
FLA

POWER EXHAUST
FAN MOTOR**

IFM
Hp

FLA

7.5*

22.0

10.0*

26.4

7.5

19.6

10.0

24.2

7.5*

10.5

10.0*

12.5

7.5

9.8

10.0

12.2

7.5*

8.6

10.0*

11.6

10.8

5.4

4.8

ELECTRIC
HEAT

POWER SUPPLY

FLA

kW

FLA

MCA

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0*

6.6-6.0*

6.6-6.0*

6.6-6.0*

6.6-6.0*

6.6-6.0*

6.6-6.0*

6.6-6.0*

6.6-6.0*

6.6-6.0*

6.6-6.0*

6.6-6.0*

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

2.4

2.4

2.4

2.4

2.4

2.4

15-18
15-18
29-36
29-36
59-72**
59-72**
74-90

15-18
15-18
29-36
29-36
59-72**
59-72**
74-90

15-18
15-18
29-36
29-36
59-72**
59-72**
74-90

15-18
15-18
29-36
29-36
59-72**
59-72**
74-90

18
18
36
36
90**
90**
108

18
18
36
36
90**
90**
108

18
18
36
36
90**
90**
108

18
18
36
36
90**
90**
108

36
36
72**
72**
108

36
36
72**
72**
108

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

22.6
22.6
45.2
45.2
113.0
113.0
135.6

22.6
22.6
45.2
45.2
113.0
113.0
135.6

22.6
22.6
45.2
45.2
113.0
113.0
135.6

22.6
22.6
45.2
45.2
113.0
113.0
135.6

36.1
36.1
72.3
72.3
108.4

36.1
36.1
72.3
72.3
108.4

152.0-152.0
158.6-158.0
152.0-152.0
158.6-158.0
152.0-152.0
158.6-158.0
232.0-253.8
232.0-253.8
283.1-309.9
156.4-156.4
163.0-162.4
156.4-156.4
163.0-162.4
156.4-156.4
163.0-162.4
237.5-259.2
237.5-259.2
288.6-315.4
149.6-149.6
156.2-155.6
149.6-149.6
156.2-155.6
149.6-149.6
156.2-155.6
229.0-250.7
229.0-250.7
280.1-306.9
154.2-154.2
160.8-160.2
154.2-154.2
160.8-160.2
154.2-154.2
160.8-160.2
234.7-256.5
234.7-256.5
285.9-312.6
71.5
74.5
71.5
74.5
71.5
74.5
154.4
154.4
182.6
73.5
76.5
73.5
76.5
73.5
76.5
156.9
156.9
185.1
70.8
73.8
70.8
73.8
70.8
73.8
153.5
153.5
181.7
73.2
76.2
73.2
76.2
73.2
76.2
156.5
156.5
184.7
57.9
60.3
57.9
60.3
101.1
101.1
146.2
60.9
63.3
60.9
63.3
104.9
104.9
150.0

MOCP
Fuse Only
200-200
200-200
200-200
200-200
200-200
200-200
250-300
250-300
300-350
200-200
225-225
200-200
225-225
200-200
225-225
250-300
250-300
300-350
200-200
200-200
200-200
200-200
200-200
200-200
250-300
250-300
300-350
200-200
200-200
200-200
200-200
200-200
200-200
250-300
250-300
300-350
100
100
100
100
100
100
175
175
200
100
100
100
100
100
100
175
175
200
90
100
90
100
90
100
175
175
200
100
100
100
100
100
100
175
175
200
80
80
80
80
125
125
150
80
80
80
80
150
150
150

UNIT 50DJ,DW030
NOMINAL
V-PH-HZ

208/230-3-60

460-3-60

575-3-60

FLA
Hp
IFM
LRA

VOLTAGE
RANGE
Min

187

414

518

Max

254

508

632

Full Load Amps


Nominal Horsepower
Indoor Fan Motor
Locked Rotor Amps

COMPR
NO. 1
RLA

63.6

30.0

22.9

COMPR
NO. 2

LRA

266

120

96

MCA
MOCP
OFM
RLA

RLA

44.3

22.1

17.9

LRA

228

114

91

OFM
Total
FLA

POWER EXHAUST
FAN MOTOR**

IFM
Hp

FLA

10.0*

26.4

15.0*

42.0

10.0

24.2

15.0

36.6

10.0*

12.5

15.0*

20.0

10.0

12.2

15.0

18.3

10*

11.6

15*

15.4

10.8

5.4

4.8

Minimum Circuit Amps (for wire sizing)


Maximum Overcurrent Protection
Outdoor Fan Motor
Rated Load Amps

ELECTRIC
HEAT

POWER SUPPLY

FLA

kW

FLA

MCA

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-5.0

6.6-6.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

2.4

2.4

2.4

2.4

2.4

2.4

15
15
29
29
59**
59**
74

15
15
29
29
59**
59**
74

15
15
29
29
59**
59**
74

15
15
29
29
59**
59**
74

18
18
36
36
90**
90**
108

18
18
36
36
90**
90**
108

18
18
36
36
90**
90**
108

18
18
36
36
90**
90**
108

36
36
72**
72**
108

36
36
72**
72**
108

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

40.9- 45.2
40.9- 45.2
81.8- 90.4
81.8- 90.4
163.6-181.0
163.6-181.0
204.5-225.9

22.6
22.6
45.2
45.2
113.0
113.0
135.6

22.6
22.6
45.2
45.2
113.0
113.0
135.6

22.6
22.6
45.2
45.2
113.0
113.0
135.6

22.6
22.6
45.2
45.2
113.0
113.0
135.6

36.1
36.1
72.3
72.3
108.4

36.1
36.1
72.3
72.3
108.4

161.0-161.0
167.6-167.0
161.0-161.0
167.6-167.0
161.0-161.0
167.6-167.0
237.5-259.2
237.5-259.2
288.6-315.4
176.6-176.6
183.2-182.6
176.6-176.6
183.2-182.6
176.6-176.6
183.2-182.6
257.0-278.8
257.0-278.8
308.1-334.9
158.8-158.8
165.4-164.8
158.8-158.8
165.4-164.8
158.8-158.8
165.4-164.8
234.7-256.5
234.7-256.5
285.9-312.6
171.2-171.2
177.8-177.2
171.2-171.2
177.8-177.2
171.2-171.2
177.8-177.2
250.2-272.0
250.2-272.0
301.4-328.1
77.5
80.5
77.5
80.5
77.5
80.5
156.9
156.9
185.1
85.0
88.0
85.0
88.0
85.0
88.0
166.2
166.2
194.5
77.2
80.2
77.2
80.2
77.2
80.2
156.5
156.5
184.7
83.3
86.3
83.3
86.3
83.3
86.3
164.1
164.1
192.4
62.9
65.3
62.9
65.3
104.9
104.9
150.0
66.7
69.1
66.7
69.1
109.6
109.6
154.7

MOCP
Fuse Only
200-200
225-225
200-200
225-225
200-200
225-225
250-300
250-300
300-350
225-225
225-225
225-225
225-225
225-250
225-250
300-300
300-300
350-350
200-200
225-225
200-200
225-225
200-200
225-225
250-300
250-300
300-350
225-225
225-225
225-225
225-225
225-225
225-225
300-300
300-300
350-350
100
110
100
110
100
110
175
175
200
110
110
110
110
125
125
175
175
200
100
110
100
110
100
110
175
175
200
110
110
110
110
110
110
175
175
200
80
80
80
80
150
150
150
80
90
90
90
125
125
175

*Standard efficiency
High efficiency
**DJ units only
DW units only

(208/230, 460 v only)

21

Electrical data (cont)


UNIT 50DK,DY024
NOMINAL
V-PH-HZ

208/230-3-60

460-3-60

575-3-60

22

VOLTAGE
RANGE
Min

187

414

518

Max

254

508

632

COMPR
NO. 1
RLA

43.3

22.1

17.9

LRA

228

114

91

COMPR
NO. 2
RLA

31.5

15.7

12.6

LRA

160

80

64

OFM
Total
FLA

POWER EXHAUST
FAN MOTOR**

IFM
Hp

FLA

5.0*

15.2

7.5*

22.0

5.0

12.4

7.5

19.6

5.0*

7.2

7.5*

10.5

5.0

6.2

7.5

9.8

5.0*

5.6

7.5*

8.6

6.4

3.2

4.8

ELECTRIC
HEAT

POWER SUPPLY

FLA

kW

FLA

MCA

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

2.4

2.4

2.4

2.4

15-18
15-18
29-36
29-36

15-18
15-18
29-36
29-36

15-18
15-18
29-36
29-36

15-18
15-18
29-36
29-36

18
18
36
36

18
18
36
36

18
18
36
36

18
18
36
36

36
36

36
36

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

22.6
22.6
45.2
45.2

22.6
22.6
45.2
45.2

22.6
22.6
45.2
45.2

22.6
22.6
45.2
45.2

36.1
36.1

36.1
36.1

108.5-108.5
115.1-114.5
108.5-108.5
115.1-114.5
121.2-132.0
121.2-132.0
115.3-115.3
121.9-121.3
115.3-115.3
121.9-121.3
129.8-140.5
129.8-140.5
105.7-105.7
112.3-111.7
105.7-105.7
112.3-111.7
117.7-128.5
117.7-128.5
112.9-112.9
119.5-118.9
112.9-112.9
119.5-118.9
126.7-137.5
126.7-137.5
53.7
56.7
53.7
56.7
65.5
65.5
57.0
60.0
57.0
60.0
69.6
69.6
52.7
55.7
52.7
55.7
64.2
64.2
56.3
59.3
56.3
59.3
68.7
68.7
45.4
47.8
52.1
52.1
48.4
50.8
55.9
55.9

MOCP
Fuse Only
150-150
150-150
150-150
150-150
150-150
150-150
150-150
150-150
150-150
150-150
150-175
150-175
125-125
150-150
125-125
150-150
125-125
150-150
150-150
150-150
150-150
150-150
150-150
150-150
70
70
70
70
70
70
70
80
70
80
80
80
70
70
70
70
70
70
70
80
70
80
80
80
60
60
60
60
60
60
70
70

UNIT 50DK,DY028
NOMINAL
V-PH-HZ

208/230-3-60

460-3-60

575-3-60

FLA
Hp
IFM
LRA

VOLTAGE
RANGE
Min

187

414

518

Max

254

508

632

Full Load Amps


Nominal Horsepower
Indoor Fan Motor
Locked Rotor Amps

COMPR
NO. 1
RLA

63.6

28.6

COMPR
NO. 2

LRA

266

120

22.9

MCA
MOCP
OFM
RLA

96

RLA

39.7

19.9

15.9

LRA

198

99

79

OFM
Total
FLA

POWER EXHAUST
FAN MOTOR**

IFM
Hp

FLA

7.5*

22.0

10.0*

26.4

7.5

19.6

10.0

24.2

7.5*

10.5

10.0*

12.5

7.5

9.8

10.0

12.2

7.5*

8.6

10.0*

11.6

10.8

5.4

4.8

Minimum Circuit Amps (for wire sizing)


Maximum Overcurrent Protection
Outdoor Fan Motor
Rated Load Amps

ELECTRIC
HEAT

POWER SUPPLY

FLA

kW

FLA

MCA

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

2.4

2.4

2.4

2.4

15-18
15-18
29-36
29-36

15-18
15-18
29-36
29-36

15-18
15-18
29-36
29-36

15-18
15-18
29-36
29-36

18
18
36
36

18
18
36
36

18
18
36
36

18
18
36
36

36
36

36
36

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

22.6
22.6
45.2
45.2

22.6
22.6
45.2
45.2

22.6
22.6
45.2
45.2

22.6
22.6
45.2
45.2

36.1
36.1

36.1
36.1

152.0-152.0
158.6-158.0
152.0-152.0
158.6-158.0
152.0-152.0
158.6-158.0
156.4-156.4
163.0-162.4
156.4-156.4
163.0-162.4
156.4-156.4
163.0-162.4
149.6-149.6
156.2-155.6
149.6-149.6
156.2-155.6
149.6-149.6
156.2-155.6
154.2-154.2
160.8-160.2
154.2-154.2
160.8-160.2
154.2-154.2
160.8-160.2
71.5
74.5
71.5
74.5
71.5
74.5
73.5
76.5
73.5
76.5
73.5
76.5
70.8
73.8
70.8
73.8
70.8
73.8
73.2
76.2
73.2
76.2
73.2
76.2
57.9
60.3
57.9
60.3
60.9
63.3
60.9
63.3

MOCP
Fuse Only
200-200
200-200
200-200
200-200
200-200
200-200
200-200
225-225
200-200
225-225
200-200
225-225
200-200
200-200
200-200
200-200
200-200
200-200
200-200
200-200
200-200
200-200
200-200
200-200
100
100
100
100
100
100
100
100
100
100
100
100
90
100
90
100
90
100
100
100
100
100
100
100
80
80
80
80
80
80
80
80

*Standard efficiency
High efficiency
**DJ units only
DW units only

(208/230, 460 v only)

23

Electrical data (cont)


UNIT 50DK,DY030
NOMINAL
V-PH-HZ

208/230-3-60

460-3-60

575-3-60

FLA
Hp
IFM
LRA

VOLTAGE
RANGE
Min

187

414

518

Max

254

508

632

Full Load Amps


Nominal Horsepower
Indoor Fan Motor
Locked Rotor Amps

COMPR
NO. 1
RLA

63.6

30.0

COMPR
NO. 2

LRA

266

120

22.9

MCA
MOCP
OFM
RLA

96

RLA

44.3

22.1

17.9

LRA

228

114

91

OFM
Total
FLA

POWER EXHAUST
FAN MOTOR**

IFM
Hp

FLA

10.0*

26.4

15.0*

42.0

10.0

24.2

15.0

36.6

10.0*

12.5

15.0*

20.0

10.0

12.2

15.0

18.3

10*

11.6

15*

15.4

10.8

5.4

4.8

Minimum Circuit Amps (for wire sizing)


Maximum Overcurrent Protection
Outdoor Fan Motor
Rated Load Amps

ELECTRIC
HEAT

POWER SUPPLY

FLA

kW

FLA

MCA

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

6.6-6.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

2.4

2.4

2.4

2.4

15-18
15-18
29-36
29-36

15-18
15-18
29-36
29-36

15-18
15-18
29-36
29-36

15-18
15-18
29-36
29-36

18
18
36
36

18
18
36
36

18
18
36
36

18
18
36
36

36
36

36
36

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

40.9-45.2
40.9-45.2
81.8-90.4
81.8-90.4

22.6
22.6
45.2
45.2

22.6
22.6
45.2
45.2

22.6
22.6
45.2
45.2

22.6
22.6
45.2
45.2

36.1
36.1

36.1
36.1

161.0-161.0
167.6-167.0
161.0-161.0
167.6-167.0
161.0-161.0
167.6-167.0
176.6-176.6
183.2-182.6
176.6-176.6
183.2-182.6
176.6-176.6
183.2-182.6
158.8-158.8
165.4-164.8
158.8-158.8
165.4-164.8
158.8-158.8
165.4-164.8
171.2-171.2
177.8-177.2
171.2-171.2
177.8-177.2
171.2-171.2
177.8-177.2
77.5
80.5
77.5
80.5
77.5
80.5
85.0
88.0
85.0
88.0
85.0
88.0
77.2
80.2
77.2
80.2
77.2
80.2
83.3
86.3
83.3
86.3
83.3
86.3
62.9
65.3
62.9
65.3
66.7
69.1
66.7
69.1

*Standard efficiency
High efficiency
**DK units only

(208/230, 460 v only)

24

MOCP
Fuse Only
200-200
225-225
200-200
225-225
200-200
225-225
225-225
225-225
225-225
225-225
225-250
225-250
200-200
225-225
200-200
225-225
200-200
225-225
225-225
225-225
225-225
225-225
225-225
225-225
100
110
100
110
100
110
110
110
110
110
125
125
100
110
100
110
100
110
110
110
110
110
110
110
80
80
80
80
80
90
90
90

Typical wiring schematics


FIELD POWER WIRING CONNECTIONS

TIME GUARDt II DEVICE WIRING


UNITS WITH ECONOMIZER

LEGEND
EQUIP Equipment
GND
Ground
NEC
National Electrical Code

TIME GUARDt II DEVICE WIRING


UNITS WITHOUT ECONOMIZER

25

Typical wiring schematics (cont)


FIELD CONTROL THERMOSTAT WIRING,
CONSTANT VOLUME UNITS

FIELD CONTROL WIRING,


VARIABLE AIR VOLUME UNITS

LEGEND
HIR Heating Interlock Relay
NOTES:
1. SW1 Field-Supplied Switch (or Time Clock) used to move unit
in and out of the occupied mode.
2. If unit has heat, field must wire between terminals 8 and 9 or 8
and 15 and supply power source to drive room terminals wide
open during heating.
3. Night Thermostat Field-supplied thermostat which can be used
to keep building from becoming too hot or too cold when unit is in
the unoccupied mode.
4. Single-step demand limit consists of a field-supplied 5-20 K-ohm
potentiometer wired to TB2 as shown.
5. If temperature reset is used, thermistor T10 must be wired in series with potentiometer P7 (located on the reset board) and wired
to TB2 as shown. T10 and the reset board are included in accessory package 50DJ900021.
6.

Factory Wiring

Field Wiring
7. Contact ratings for HIR relay (HN61KL013) 125 va pilot duty
at 125/250 volt.

26

FIELD WIRING FOR BUILDING PRESSURIZATION AND SMOKE PURGE


CONSTANT VOLUME UNITS

BUILDING PRESSURIZATION
Switch 1
Switch 2
Switch 3 (if unit equipped with power exhaust)
Switch 5
Switch 6

VARIABLE AIR VOLUME UNITS

SMOKE PURGE
Switch 1
Switch 3
Switch 4
Switch 5
Switch 6

Switch 1 Firestat or smoke detector normally closed.


Switch 2 Building pressurization switch (energize indoor fan motor)
normally open.
Switch 3 Switch to isolate indoor fan motor from power exhaust motor
normally closed.
Switch 4 Smoke purge switch (energize power exhaust motor) normally open.
Switch 5 Switch to provide 24 volts to economizer motor normally
open.
Switch 6 Switch to drive economizer outside air damper full open
normally closed. Remove jumper wire.
Switch 7 Switch to isolate indoor fan motor from economizer motor/CV
board normally closed.

LEGEND
DPS
ECR
HIR
IFC
MPE

(for CV and VAV units)


Differential Pressure Switch
OMR
Economizer Relay
PEC
Heating Interlock Relay
Indoor Fan Contactor
Sw

Modulating Power Exhaust


TB

Occupied Mode Relay


Power Exhaust
Contactor Coil
Switch
Terminal Block

NOTES (for CV and VAV units):


1. Switch 1 and 1a are for time clock and night thermostat (VAV units only)
and are not part of building pressurization or smoke purge.
2. Power exhaust option can be unit mounted on bottom supply/return units
only; accessory can be duct mounted on side supply/return units.
3.
is field wiring.
4.
is factory wiring.
5. All switches are field supplied.
6. For building pressurization, field-supplied power source must drive room
terminals wide open.

Smoke control recommendations


It is common practice to use the rooftop unit for building
pressurization and smoke purge functions in the event of a
building fire. These functions are enhanced when multiple
rooftop units are used to zone a building.
The intent of building pressurization is to keep smoke out
of a zone. This is accomplished by:
opening the economizer (option)
running the supply fan (optional inlet guide vanes open)
closing the modulating power exhaust dampers if installed (option on VAV units)
shutting off the power exhaust fan (if installed)
This allows the space to be overpressurized and smoke
will not enter the space.
The smoke purge function allows the rooftop unit to remove smoke from the space. Required unit functions for
smoke purge are:

BUILDING PRESSURIZATION
Switch 2
Switch 3
Switch 6
Switch 7
Switch 8
Switch 9
Switch 11
Switch 11a

SMOKE PURGE
Switch 2
Switch 4
Switch 6
Switch 7
Switch 8
Switch 10
Switch 11
Switch 11a

Switch 1 and 1a Field-supplied ON-OFF switch (time clock) and night


thermostat (see Note 1).
Switch 2
Firestat or smoke detector normally closed.
Switch 3
Building pressurization switch (energize indoor fan
motor) normally open.
Switch 4
Smoke purge switch (energize power exhaust motor)
normally open.
Switch 6
Switch to drive economizer outside air damper fully
open normally open.
Switch 7
Switch to isolate indoor fan motor from power exhaust
motor normally closed.
Switch 8
Switch to provide 24-volt power to inlet guide vane
motor and modulating power exhaust damper motor
normally open.
Switch 9
Switch to drive inlet guide vanes fully open normally
open.
Switch 10
Switch to drive modulating power exhaust dampers
fully open normally open.
Switch 11a
Switch to energize field-supplied power source which
drives room terminals fully open normally open.
Switch 11
Switch to deenergize field-supplied power source which
drives room terminals fully open normally closed.

economizer opens
exhaust fan running
exhaust dampers are open
supply fan is not running
The above wiring information shows what electrical connections and switches are required to enable smoke purge
and building pressurization. Note that the optional economizer is required for both functions and the power exhaust
is required for smoke purge.
There are 115-v terminals (TB3 Terminals 4 and 8 VAV,
TB2 Terminals 4 and 5 CV) available for powering field installed smoke detectors. The maximum available va during
smoke detector standby mode is 10 va, and 45 va during
alarm mode.
Note that is is possible to remotely energize the power
exhaust fan using the power exhaust contacts. This would
allow smoke removal to occur without a fireman having to
climb onto the roof before structural integrity can be
verified.
27

Controls
Operating sequences, constant volume units
(50DJ,DW)
Cooling, units without economizer Unit power ON,
system selector switch at COOL or AUTO., fan switch at
AUTO.; thermostat at setting below room temperature:
Y1 on the thermostat subbase closes, energizing compressor no. 1 as first stage of cooling. (Compressor no. 1 is
always the larger of the 2 unit compressors.) If cooling load
cannot be satisfied with only first-stage cooling, Y2 on the
thermostat will close, energizing compressor no. 2.
Condenser fans are energized with compressor no. 1.
The no. 1 fan runs continuously while the unit is on mechanical cooling; the no. 2 fan is cycled on and off for head
pressure control. Check cooling effects at a setting above
room temperature. Compressors will shut off.
Heating, units without economizer Unit power ON,
system selector switch at HEAT, fan switch at AUTO.; thermostat at setting above room temperature:
When W1 on the thermostat closes, the first stage of electric heat is energized. On a further drop in room temperature, W2 on the thermostat closes, energizing the second
stage of electric heat.
NOTE: Units equipped with low electric heat option have
only one stage. Reset thermostat to a setting below room
temperature. Unit should shut off.
Cooling, units with economizer With subbase switch
set at COOL and fan switch set at AUTO., indoor fan is
energized when Y1 on thermostat closes. If enthalpy is below setting on enthalpy switch, the economizer outside air
dampers will modulate open to satisfy the cooling requirement. If outside air alone will not meet the cooling requirements, Y2 on the thermostat will close, energizing compressor no. 1 to work in conjunction with the modulating
economizer to meet the cooling requirement. While the unit
is operating using outside air, compressor no. 2 cannot be
energized. If enthalpy is above setting on enthalpy switch,
the economizer outside air dampers move to the minimum
(ventilation) position, and condenser fans numbers 1 and 2
cycle on and off as described in Cooling, units without economizer.
NOTE: If fan switch is ON and the room thermostat is
satisfied, the outside air dampers move to the minimum
position.
Heating, units with economizer Operation is the same
as described in Heating, units without economizer, except
that the outside air dampers move to the minimum position.

Operating sequences, variable air volume


units
(50DK,DY)
Cooling When field-supplied switch or time clock places
unit in the occupied mode, microprocessor goes through a
3-minute initialization period (assuming that the control ONOFF switch is in ON position) during which display will continuously show 20 .

28

During initialization period, effective range of economizer potentiometer P2 is established and is used to sense
position of economizer dampers. For approximately 60 seconds of initialization period, dampers are driven fully open
and full open resistance of potentiometer is recorded by
microprocessor. The dampers are then driven to fully closed
position and this potentiometer resistance is also recorded
by microprocessor. These 2 readings establish effective range
of the economizer potentiometer.
Upon completion of initialization mode, the control operates unit to try to maintain the temperature at setting of
the cold temperature set point (mounted on the display
board). This is potentiometer P1. The control will always
try to useeconomizer as first stage of cooling, enthalpy permitting. Enthalpy permitting, control will open economizer
dampers and try to maintain leaving air temperature at the
cold temperature set point minus 2. If economizer dampers become fully open and still cannot maintain desired leaving air temperature, control will begin to cycle on compressors and condenser fans. Once mechanical cooling begins,
control strives to maintain leaving air temperature at cold
temperature set point rather than at the cold temperature
set point minus 2.
The microprocessor determines how rapidly capacity steps
are added or subtracted based on deviation from leaving air
set point and rate of change of leaving air temperature.
If enthalpy is such that economizer cannot be used for
cooling, dampers will go to their minimum position as set
by potentiometer P5 (located on accessory board). The control will then use mechanical cooling to meet the cooling
load.
Units with morning warm-up heat (optional electric
heat), heating When in heating mode, room terminals
must be wide open.
Dip switch 4 (located on the processor board) must be in
ON position.
If return-air temperature (T2) is 5 below warm-up temperature set point P6 (located on the accessory board), heating relay will be energized and heat will be brought on and
will run until return-air temperature is above 2 below setting on P6. During heating, economizer dampers will be
fully closed. The unit can go in and out of heating until
return-air temperature rises above the setting on P6. After
the return-air temperature rises above the warm-up set point,
unit cannot go back into heating mode until unit re-enters
occupied mode.
Units equipped with space temperature reset Unit
operates exactly like a unit without reset until reset is used.
When unit is operating in reset mode, a code of 21 will
appear on display when display button is pushed; this means
that control is controlling to a leaving air set point different
than that set using P1.
Units equipped with demand limit Unit operates exactly like standard VAV units until demand limiting takes effect and limits amount of compression that will be allowed
to be brought on.

Typical piping and wiring

50DW

Application data
Condensate removal
When units are mounted on roof curbs, use the factoryprovided condensate drain connections provided in the unit
base rail. Condensate drain openings are provided on the
air-handling end of the unit to allow proper drainage. When
units are mounted on concrete slabs, condensate drain openings must be drilled in the vertical face of the baserail, as

low as possible, at the same location as the factory drilled


holes. The factory supplied couplings can then be used to
connect the condensate trap. It is important to provide space
for the 4-in. trap on slab-mount installations. This can usually be accomplished by installing the trap at the edge of
the concrete slab.

29

Application data (cont)


Temperature sensors
Variable air volume applications that require averaging multiple space temperature sensors to determine when to modify
the discharge air temperature can be satisfied using either
4 or 9 sensors as shown below.

NOTE: Only Carrier sensors may be used (part number


HH79NZ014). Sensors must be used in multiples of 1, 4
and 9 only, with total sensor wiring not to exceed
1000 feet.

SPACE TEMPERATURE RESET 4 SENSOR APPLICATION

Factory Wiring
Field Wiring

SPACE TEMPERATURE RESET 9 SENSOR APPLICATION

Factory Wiring
Field Wiring

30

Guide specifications
50DJ,DW constant volume units
Packaged Rooftop Cooling Unit
With Electric Heat Constant Volume
Application
HVAC Guide Specifications
Size Range: 20 to 27 Tons, Nominal
Carrier Model Number: 50DJ (Downflow)
50DW (Horizontal)
NOTE: Items throughout the specification which apply only
to With Electric Heat are indicated by single brackets [i.e.].
Part 1 General
1.01 SYSTEM DESCRIPTION
A. Outdoor rooftop mounted, electronically controlled
cooling unit with heating option utilizing semi-hermetic
type reciprocating compressors for cooling duty and
[electric resistance] for heating duty. Unit shall discharge supply air downward or horizontally as shown
on contract drawings.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards
360 and 270.
B. Unit shall be designed to conform to UL Standards 465.
C. Unit shall be ETL listed and CSA certified as a total
package for safety requirements.
D. Roof curb shall be designed to conform to NRCA
Standards.
E. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
F. Unit casing shall be capable of withstanding Federal
test method Standard No. 141 (Method 6061) 500
hour salt spray test.
G. Evaporator and condenser coils shall be leak tested
at 150 psig (1034 kPa) and pressure tested at 450
psig (3103 kPa).
1.03 DELIVERY, STORAGE AND HANDLING
A. Unit shall be stored and handled per manufacturers
recommendations.
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single-piece, cooling unit with heating option. Contained within the unit enclosure shall
be all factory wiring, piping, controls, refrigerant charge
(R-22), and special features required prior to field
start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a baked enamel
finish.
2. Cabinet panels shall be hinged for easy servicing.
3. Lifting lugs shall be factory installed to facilitate
overhead rigging.
4. Unit shall be equipped with factory-supplied condensate drain connection for evaporator coil.

C. Fans:
1. The single indoor blower (evaporator fan) shall be
of the forward curved centrifugal belt driven type
only, with fixed pitch pulley drive.
2. Outdoor (condensing) fans shall discharge air vertically upward and shall have permanently lubricated bearings.
3. Outdoor (condensing) fans shall be of the direct
driven propeller type only and be protected by a
coated steel wire guard.
4. Indoor blower (evaporator fan) shaft bearings
shall be of the ball bearing type with lubrication
provisions.
D. Compressors:
1. Two semi-hermetic type with unloading
capability.
2. Factory mounted on spring vibration isolators.
3. Equipped with a factory-installed crankcase heater
to minimize liquid refrigerant accumulation in compressor during shutdown and prevent refrigerant
dilution of oil.
E. Coils:
1. Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
copper tubes with all joints brazed.
2. Tube sheet openings to be belled to prevent tube
wear.
3. Evaporator coil shall be of the full face active
design.
4. Coils shall be intertwined circuited to provide 2
independent refrigeration systems.
F. Heating Section:
1. Factory-installed electric resistance heater(s) of the
characteristics shown in the equipment schedule.
2. Heater elements shall be open wire type,
adequately supported and insulated with ceramic
bushings.
G. Refrigerant Components:
Refrigerant circuit components shall include: filter driers, liquid line sight glasses, compressor discharge
valves, liquid line service valves and thermal expansion valves.
H. Filter Section:
1. Standard filter section shall consist of low velocity
disposable 2-in. thick fiberglass filters in commercially available sizes.
2. Filter face velocity shall not exceed 400 fpm at
nominal airflows.
I. Controls and Safeties:
1. Unit Controls:
a. Unit shall be complete with self-contained,
demand-oriented solid state control system.
b. Unit staging shall be minimum 2-cool, 2-heat
(one-heat on low heat package only).
c. Unit shall perform in response to a variable
space temperature signal.
31

Guide specifications
50DJ,DW constant volume units (cont)
d.

J.

K.

L.

M.

32

In the event of a power failure, unit control


system shall sequence the unit to restart beginning with the first stage of cooling or
heating.
e. Thermostats shall be of the dual set point type
for heating and cooling.
f. Set points must have adjustable dead band
between heat and cool.
2. Safeties:
a. Thermistors shall be located within the unit.
b. Compressors shall be provided with the following minimum protection:
1) Overcurrent (manual reset circuit breaker).
2) Overtemperature.
3) Low-pressure switch.
4) High-pressure switch.
Operating Characteristics:
1. Unit shall be capable of starting and running at
115 F ambient outdoor temperature per maximum load criteria of ARI Standard 360.
2. Compressor with standard controls shall be capable of operation down to 45 F ambient outdoor
temperature.
3. Cooling capacity control shall be accomplished
through the use of unloaders and/or compressor
staging.
Electrical Requirements:
All unit power wiring shall enter unit cabinet at a
single location, either through side of bottom (curb
opening).
Motors:
1. Compressor motors shall be cooled by suction gas
passing through motor windings and shall have internal thermal overload protection.
2. Indoor blower poly-phase motor bearings shall be
of the ball bearing type.
3. Outdoor totally enclosed motors shall have permanently lubricated sealed ball bearings and inherent automatic reset thermal overload protection.
4. Each poly-phase compressor and indoor fan motor shall be protected against overcurrent and single
phasing conditions. Protection devices shall be
manual reset type.
Special Features:
Certain standard features are not applicable when the
features designated * are specified. For assistance in
amending the specifications, your local Carrier Sales
Office should be contacted.
1. Integrated Economizer:
a. Integrated modulating type capable of simultaneous economizer and compressor operation; with spring return motor to close outside dampers on shutdown or power failure.
b. Includes all hardware and controls to provide
cooling with outside air.

2.

3.

4.

5.

6.

7.

8.

9.

c. Equipped with low leakage dampers not to


exceed 1% leakage at 1.0 in. wg pressure
differential.
d. Capable of introducing up to 100% outside
air.
e. Utilizes a solid state enthalpy control to sense
both dry- and wet-bulb of the outdoor air.
Roof Curb:
Formed 16 gage galvanized steel with wood nailer
strip and capable of supporting entire unit.
Head Pressure Control Package:
a. Package shall consist of solid-state control
panel, condensing temperature sensor(s) and
variable speed outdoor fan motor.
b. Package shall be capable of modulating outdoor fan speed to maintain condensing temperature between 90 F and 110 F at outdoor
ambient temperatures down to 20 F.
c. Requires change to approved condenser fan
motor for application.
Unloader:
Suction pressure unloader shall be field-installed
on the lead compressor for capacity control on
multi-compressor units.
Power Exhaust Package:
a. Packages shall be for use on downflow units
with economizer package only.
b. Package shall include integral propeller type
exhaust fan complete with fan drive and
damper.
c. Power exhaust shall be permitted to operate
only in conjunction with unit economizer to
assure proper building pressurization.
Barometric Relief Damper Package:
a. Package shall relieve excess internal pressure and consist of damper assembly, hoods,
damper screen, seal strip and required hardware.
b. Damper assembly shall close due to gravity
upon unit shutoff.
c. Unit mounted on downflow applications; can
be duct mounted on horizontal-supply
applications.
Optional Condenser Coil Material:
Unit shall be factory equipped with condenser
coil made from copper tubes and copper fins.
Optional high efficiency indoor fan motors
shall be factory supplied to reduce electric
consumption.
Condenser Coil (Hail) Guards:
Expanded metal grille complete with support retainers and fasteners shall be provided for the
protection of the condensing coil.

10. [Electric Resistance Heaters:]


a. Open wire nichrome elements with all necessary safety and operating controls.
b. ETL listed and indicated on basic unit informative plate.
c. Multiple heat capacities available.
11. [Outdoor Air Thermostat:]
Thermostat shall allow for additional stages of
electric heat based on outdoor temperatures.
12. Thermostat and Subbase Assembly:
Provides staged cooling and heating, automatic
(or manual) changeover and fan control.
13. Accessory Skid:
Provides lifting slots for fork truck handling.
14. Differential Enthalpy Control:
Sensor shall be capable of comparing heat content (temperature and humidity) of outdoor air
and return air and controlling economizer cut-in
point at the most economical level.

15. Optional Compressor Cycle Delay:


Compressor shall be prevented from restarting
for a minimum of 5 minutes after shutdown.
16. 25% Manual Outdoor Air Damper:
Provides up to 25% outdoor air.
17. High-Efficiency Supply Fan Motors:
High-efficiency motors shall be factory-supplied
to reduce electric consumption.
18. Alternate motor and drive shall be provided for
higher static applications.
19. Hot gas bypass valve shall be provided for low
load operation of the refrigeration system.

33

Guide specifications
50DK,DY variable air volume units
Packaged Rooftop Cooling Unit
With Electric Heat Variable Volume
Application

C.

HVAC Guide Specifications


Size Range: 20 to 27 Tons, Nominal
Carrier Model Number: 50DK (Downflow)
50DY (Horizontal)
NOTE: Items throughout the specification which apply only
to With Electric Heat are indicated by single brackets [i.e.].
Part 1 General
1.01 SYSTEM DESCRIPTION
A. Outdoor rooftop mounted, electronically controlled
cooling unit with heating option utilizing semi-hermetic
type reciprocating compressors for cooling duty and
[electric resistance] for heating duty. Unit shall discharge supply air downward or horizontally as shown
on contract drawings.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards
360 and 270.
B. Unit shall be designed to conform to UL Standards
465.
C. Unit shall be ETL listed and CSA certified as a total
package for safety requirements.
D. Roof curb shall be designed to conform to NRCA
Standards.
E. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
F. Unit casing shall be capable of withstanding Federal
test method Standard No. 141 (Method 6061) 500
hour salt spray test.
G. Evaporator and condenser coils shall be leak tested
at 150 psig (1034 kPa) and pressure tested at 450
psig (3103 kPa).
1.03 DELIVERY, STORAGE AND HANDLING
A. Unit shall be stored and handled per manufacturers
recommendations.
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single-piece, cooling unit with heating option. Contained within the unit enclosure shall
be all factory wiring, piping, controls, refrigerant charge
(R-22), and special features required prior to field
start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a baked enamel
finish.
2. Cabinet panels shall be hinged for easy servicing.
3. Lifting lugs shall be factory installed to facilitate
overhead rigging.

34

D.

E.

F.

G.

H.

4. Unit shall be equipped with factory-supplied condensate drain connection for evaporator coil.
Fans:
1. The single indoor blower (evaporator fan) shall be
of the forward curved centrifugal belt driven type
only, with fixed pitch pulley drive (with optional
factory-installed inlet guide vanes and controls).
2. Outdoor (condensing) fans shall discharge air vertically upward and shall have permanently lubricated bearings.
3. Outdoor (condensing) fans shall be of the direct
driven propeller type only and be protected by a
coated steel wire guard.
4. Indoor blower (evaporator fan) shaft bearings shall
be of the ball bearing type with lubrication
provisions.
Compressors:
1. Two semi-hermetic type with unloading capability.
2. Factory mounted on spring vibration isolators.
3. Equipped with a factory-installed crankcase heater
to minimize liquid refrigerant accumulation in compressor during shutdown and prevent refrigerant
dilution of oil.
Coils:
1. Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
copper tubes with all joints brazed.
2. Tube sheet openings to be belled to prevent tube
wear.
3. Evaporator coil shall be of the full face active
design.
4. Coils shall be intertwined circuited to provide 2
independent refrigeration systems.
[Heating Section:]
1. Factory-installed electric resistance heater(s) of the
characteristics shown in the equipment schedule.
2. Heater elements shall be open wire type, adequately
supported
and
insulated
with
ceramic
bushings.
3. Heater is single stage for morning warm-up only.
Refrigerant Components:
Refrigerant circuit components shall include: filter driers, liquid line sight glasses, compressor discharge
valves, liquid line service valves and thermal expansion valves.
Filter Section:
1. Standard filter section shall consist of low-velocity,
disposable 2-in. thick fiberglass filters in commercially available sizes.
2. Filter face velocity shall not exceed 400 fpm at
nominal airflows.

I. Controls, Safeties and Diagnostics:


1. Controls:
a. Control shall be accomplished through the
use of a factory-installed, microprocessorbased control system and associated electronic and electrical hardware. Control system shall determine control sequences through
monitoring the following operational variables:
1) Evaporator leaving air temperature.
2) Evaporator entering air temperature.
3) Saturated condensing temperature.
4) Economizer position.
5) Minimum economizer set point.
6) Morning warm-up set point.
b. Controls shall be capable of performing the
following functions:
1) Capacity control based on discharge air
temperature and compensated by rate of
change of return air temperature. Capacity control shall be accomplished through
the use of an unloading device and compressor staging.
2) Perform a quick test to check the status
of all input and output signals to the control system using diagnostic display module.
3) Control of integrated economizer operation.
4) Single step demand limit control.
5) Condenser fan cycling to maintain correct
head pressure.
6) [Morning warm-up.]
2. Safeties:
Unit components shall be equipped with the following protections:
a. Compressors:
1) Overtemperature (shuts down compressor).
2) Overcurrent (shuts down individual
compressor).
3) Crankcase heaters.
4) Ground fault (shuts down individual
compressor).
5) High-pressure switch (shuts down individual compressor).
6) Low-pressure switch (shuts down compressor, automatic reset type).
b. [Heating Section:]
1) Automatic reset high temperature limit
switches.
2) Heat limiters (fusible links).
3) Overcurrent protection.
4) Branch circuit protection.

J.

K.

L.

M.

3. Diagnostics:
a. Diagnostic display module shall be capable of
indicating a safety lockout condition through
displaying a 2-digit code for which a legend
shall be provided in the control panel.
b. Diagnostic module must also be capable of
displaying outputs of microprocessor controlled run test to verify operating of every
switch, thermistor, potentiometer, fan and
compressor before unit is started.
Operating Characteristics:
1. Unit shall be capable of starting and running at
115 F ambient outdoor temperature per maximum load criteria of ARI Standard 360.
2. Compressor with standard controls shall be capable of operation down to 45 F ambient outdoor
temperature.
3. Provides multi-stage mechanical cooling capability.
4. Unit shall be factory equipped with hot gas bypass
valve, shutoff valve and tubing to maintain capacity control at minimum cooling loads.
Electrical Requirements:
All unit power wiring shall enter unit cabinet at a
single location, either through side or bottom (curb
opening).
Motors:
1. Compressor motors shall be cooled by suction gas
passing through motor windings and shall have internal thermal overload protection.
2. Indoor blower poly-phase motor bearings shall be
of the ball bearing type.
3. Outdoor totally enclosed motors shall have permanently lubricated sealed ball bearings and inherent automatic reset thermal overload protection.
4. Each poly-phase compressor and indoor fan motor shall be protected against overcurrent and single
phasing conditions. Protection devices shall be
manual reset type.
Special Features:
Certain standard features are not applicable when the
features designated * are specified. For assistance in
amending the specifications, your local Carrier Sales
Office should be contacted.
1. Integrated Economizer:
Enthalpy controlled integrated type consisting of
dampers, motors and linkages, and potentiometer in conjunction with control system to provide primary cooling using outdoor air, enthalpy
permitting, supplemented with mechanical cooling when necessary.
a. Dampers shall be low leakage type, not to
exceed 1% leakage at 1.0 in. wg pressure
differential when fully closed.
b. Linkages shall have a spring return feature
which shuts dampers upon a power interruption or unit shutdown.
35

Guide specifications
50DK,DY variable air volume units (cont)

2.

3.

4.

5.

6.

7.

c. Capable of introducing up to 100% outside


air.
d. Utilizes a solid state enthalpy control to sense
both dry- and wet-bulb of the outdoor air.
Roof Curb:
a. Formed 16 gage galvanized steel with wood
nailer strip and capable of supporting entire
unit.
Head Pressure Control Package:
a. Package shall consist of solid-state control
panel, condensing temperature sensor(s) and
variable speed outdoor fan motor.
b. Package shall be capable of modulating outdoor fan speed to maintain condensing temperature between 90 F and 110 F at outdoor
ambient temperatures down to 20 F.
c. Requires change to approved condenser fan
motor for application.
Modulating Power Exhaust Package:
a. Package is unit mounted on downflow with
economizer package only.
b. Package shall include integral propeller type
exhaust fan complete with fan drive, field adjustable differential pressure switch and gage.
Field-installed rainhood includes 100% modulating damper package and actuator.
c. Power exhaust is microprocessor controlled
to operate in conjunction with economizer to
maintain a field calibrated interior pressure.
Barometric Relief Damper Package:
a. Package shall relieve excess internal pressure and consist of damper assembly, hoods,
damper screen, seal strip and required hardware.
b. Damper assembly shall close due to gravity
upon unit shutoff.
c. Unit mounted on downflow units only; can
be duct mounted on horizontal supply applications.
Optional Condenser Coil Material:
Unit shall be factory equipped with condenser
coil made from copper tubes and copper fins.
Optional high-efficiency indoor fan motors
shall be factory supplied to reduce electric
consumption.

Carrier Corporation Syracuse, New York 13221

296

8. Condenser Coil (Hail) Guards:


Expanded metal grille complete with support retainers and fasteners shall be provided for the
protection of the condensing coil.
9. [Electric Resistance Heaters:]
a. Open wire nichrome elements with all necessary safety and operating controls.
b. ETL listed and indicated on basic unit informative plate.
c. Multiple heat capacities available.
10. Space Temperature Reset Package:
Temperature reset package consisting of a reset
board and a thermistor. Package shall be capable
of resetting leaving discharge air temperature to
prevent overcooling of the conditioned space.
11. Two-Step Demand Limit Control:
Package shall allow external demand limit control device to limit the capacity of the unit to some
pre-selected set points which are percentages of
the unit capacity stages.
12. Optional inlet guide vanes and controls shall be
factory installed.
13. Accessory Skid:
Provides lifting slots for fork truck handling.
14. Differential Enthalpy Control:
Sensor shall be capable of comparing heat content (temperature and humidity) of outdoor air
and return air and controlling economizer cut-in
point at the most economical level.
15. Optional Compressor Cycle Delay:
Compressor shall be prevented from restarting
for a minimum of 5 minutes after shutdown.
16. 25% Manual Outdoor Air Damper:
Package shall provide up to 25% outdoor air.
17. High-Efficiency Supply Fan Motors:
High-efficiency motors shall be factory-supplied
to reduce energy consumption.
18. Alternate motor and drive shall be provided for
higher static applications.
19. Hot gas bypass valve shall be provided for low
load operation of refrigeration system.

3-92

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Tab 1b

Page 36

Catalog No. 525-057

Printed in U.S.A.

PC 111