TM221CE24R
Characteristics
Main
Modicon M221
Logic controller
100...240 V AC
10 relay
5...125 V DC
5...250 V AC
2A
Theinformationprovidedinthisdocumentationcontainsgeneraldescriptionsand/ortechnicalcharacteristicsoftheperformanceoftheproductscontainedherein.
Thisdocumentationisnotintendedasasubstituteforandisnottobeusedfordeterminingsuitabilityorreliabilityoftheseproductsforspecificuserapplications.
Itisthedutyofanysuchuserorintegratortoperformtheappropriateandcompleteriskanalysis,evaluationandtestingoftheproductswithrespecttotherelevantspecificapplicationorusethereof.
NeitherSchneiderElectricIndustriesSASnoranyofitsaffiliatesorsubsidiariesshallberesponsibleorliableformisuseoftheinformationcontainedherein.
Range of product
Complementary
Discrete I/O number
24
85...264 V
Network frequency
50/60 Hz
Inrush current
<= 40 A
Power consumption in VA
24 V
DC
10 bits
LSB value
10 mV
Conversion time
Input impedance
Response time
0 ms for input
12 ms for input
3 ms for input
1/9
125 V DC
277 V AC
4 A at COM 2 termnal
4 A at COM 2 termnal
7 A at COM 0 termnal
7 A at COM 1 termnal
Electrical durability
Switching frequency
Mechanical durability
Minimum load
Protection type
Without protection at 5 A
Reset time
1s
Memory capacity
256 kB for user application and data RAM with 10000 instructions
256 kB for internal variables RAM
Data backed up
2 GB SD card optional
Battery type
Backup time
0.2 s Boolean
60 s response time
Realtime clock
With
Clock drift
<= 30 s/month at 25 C
Regulation loop
4 fast input (HSC mode) (counting frequency: 100 kHz), counting capacity: 32 bits
A/B
Pulse/direction
Single phase
Supply
Transmission rate
Port Ethernet
Communication service
DHCP client
Ethernet/IP adapter
Modbus TCP server
2/9
Electrical connection
Cable length
Insulation
Marking
CE
Mounting support
Height
70 mm
Depth
70 mm
Width
110 mm
Product weight
0.395 kg
Environment
standards
EN/IEC 60664-1
EN/IEC 61131-2
EN/IEC 61010-2-201
product certifications
CSA
CULus
LR
IACS E10
RCM
EAC
DNV-GL
environmental characteristic
surge withstand
3/9
Conducted emissions conforming to EN/IEC 55011 power lines (AC), 0.15...0.5 MHz :
79 dBV/m QP/66 dBV/m AV
Conducted emissions conforming to EN/IEC 55011 power lines (AC), 0.5...300 MHz :
73 dBV/m QP/60 dBV/m AV
Conducted emissions conforming to EN/IEC 55011 power lines, 10...150 kHz :
120...69 dBV/m QP
Conducted emissions conforming to EN/IEC 55011 power lines, 150 kHz...1.5 MHz :
79...63 dBV/m QP
Conducted emissions conforming to EN/IEC 55011 power lines, 1.5...30 MHz : 63
dBV/m QP
Radiated emissions conforming to EN/IEC 55011 class A 10 m, 30...230 MHz : 40
dBV/m QP
Radiated emissions conforming to EN/IEC 55011 class A 10 m, 200 MHz...1 GHz : 47
dBV/m QP
immunity to microbreaks
10 ms
-25...70 C
relative humidity
IP degree of protection
pollution degree
<= 2
operating altitude
0...2000 m
storage altitude
0...3000 m
vibration resistance
shock resistance
Offer Sustainability
Sustainable offer status
REACh
Available
Available
Dimensions
Mounting on a Rail
4/9
(1)
Mounting
Correct Mounting Position
5/9
Clearance
Digital Inputs
Wiring Diagram (Positive Logic)
(*)
Type T fuse
(*)
Type T fuse
Relay Outputs
Negative Logic (Sink)
6/9
(*)
Type T fuse
(1)
The COM0, COM1 and COM2 terminals are not connected internally.
(2)
To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling
diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load
(*)
Type T fuse
(1)
The COM0, COM1 and COM2 terminals are not connected internally.
(2)
To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling
diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load
Analog Inputs
Wire Color
0V
Black
AN1
Red
0V
Black
AN0
Red
Ethernet Connection
Pin N Signal
1
TD+
7/9
TD-
RD+
RD-
SL1 Connection
SL1
N
RS 232
RS 485
RxD
N.C.
TxD
N.C.
RTS
N.C.
N.C.
D1
N.C.
D0
CTS
N.C.
N.C*.
5 Vdc
Common Common
8/9
Derating Curves
Embedded Digital Inputs (No Cartridge)
X:
Ambient temperature
Y:
X:
Ambient temperature
Y:
9/9