Equipment
Generating Unit Size selection
Selection of type of Turbine
Main Inlet valve
Governor Performance Requirement
Pressure Oil system equipment
Materials
Rated Voltage
Reactive Power Capacity
Temperature Rise Limit
Damper winding
Flywheel Effect
Online condition monitoring
Field Flashing and Excitation Requirement
GSU Transformer
DC Supply System
Grounding System
Control and Protection
Protection System
EOT Crane
Fire Protection System
HVAC System
Compressed Air System
Powerhouse Lift
Page
No.
2
2
2
2
2
2
2
2
2
2
3
3
3
3
4
4
4
4
4
4
4
5
5
N.
O.
P.
GSU Transformer
Secondary Voltage should be specified considering impedance voltage drop.
Tap Changer Normal Range - + 5%. For 400 KV, Range - -21/2% to 71/2%.
Fire Protection System for Transformer
Mulsifyre Fire Protection System.
Fire Wall if space between transformers < 15m.
Rating of firewall For 3 Hours and capable of withstanding exploding
bushing and surge arrestors.
Wall shall extend 0.31m above top of Tank/ oil conservator and 0.61m
beyond cooling radiators.
Diaphragm type oil sealing in conservator.
Diaphragm shall be able to withstand the vacuum during installation / maintenance
period.
Online Monitoring System
Onload Tap changer Monitoring To monitor temperature / timing
sequence / tap position, Motor Load and current.
DGA / EGA To monitor H2 and CO.
Online Spectroscopy To monitor Methane/ Ethylene/ Ethane.
Bushing Monitor To monitor bushing charging current.
Partial discharge Monitor
DC Supply System
In general Lead Acid Batteries are used.
Normally 10% Design Margin and 25% Aging factor for batteries.
Degree of Protection for enclosure of DCDB: IP-44.
Grounding System
Powerhouse Max. resistance to ground as 1.0ohm.
3
SWITCHYARD EQUIPMENT
X. HV Switchyard
Cost, Space & Security are deciding factors for selection of GIS or AIS.
Location decided considering
Topographical features, accessibility, public safety, audible noise, electric and
magnetic field effects on human health, soil resistivity& switchyard grounding,
Impact of weather and environmental pollution, convenience of Tower
loactions.
Y. Switching Schemes
Switching Scheme must ensure:
Short circuit capacity, flexible operation, high reliability, Isolation of Bus,
isolation of CBs, Isolation of Bus faults.
Z. Circuit Breakers
For voltage<245KV, common 3-Pole operating mechanism is adopted.
Breakers with surge suppression resistors preferred for voltage > 400KV.
AA.
Isolating Switches