DATA SHEET OF 415 V VVVF DRIVE FOR MOTORS

P.O No :2300024123/109 DATED 28/04/2010


CUSTOMER :TATA STEEL LTD ,Jamshedpur
Expansion Project

3MTPA

CONSULTANT :M.N DASTUR & CO (P) LTD

JOB NAME:
GAS MIXING & BOOSTING STATION FOR TSCR & LCP #8 & #9

DOC. NO.: BSL-TSL-GMBS-DS-97, R:1

Sl No

VVVFD DESCRIPTION

DATA TO BE CONFIRMED BY
VENDOR

PARAMETERS

Input Supply

415 V with +- 10 % Variation

Input Frequency

50 +/-4%

Fundamental Power Factor

0.95 to 0.98 (at nominal load)

Output Voltage

3Ph symmetrical, U, at the field weakening point

Output Frequency

0-500Hz

Frequency Resolution

0.01Hz

Overload Capacity

110% for 1min Every 5mins for Fan/Pump Load ,


min Every 5mins for Heavy Duty Application

Peak Overload Capacity

Imax (400VAC and 500VAC) (atleast 10secs at start)

Field Weakening Point

8 to 500Hz

10

Switching

4KHz (average)

11

Acceleration Time

0-1800 Sec

12

Deceleration Time

0-1800 Sec

13

Efficiency

98% at Nominal Power Level without Encoder feedback

14

Ambient Temp

40 Deg C. above 40C the maximum output current is de-rated 1%


forevery additional 1C (up to 50C (122F) maximum limit

15

Relative Humidity

5-95%

16

Inrush Current

Less than rated i/p Current

17

Motor Control

DIRECT TORQUE CONTROL

18

Torque Control

Torque Step Rise Time :


Open Loop : <5ms with Nominal Torque
Closed Loop : <5ms with nominal Torque
Non - Lenearity :
Open Loop :

+/- 4% with nominal torque

Closed Loop : .+/-3% with Nominal torque


19

Speed Control

Static Accuracy :
Open Loop : 10% of motor slip
Closed Loop : 0.01% of nominal speed
Dynamic Accuracy :
Open Loop : 0.3 to 0.4% /Sec with 100% torque step
Closed Loop : 0.1 to 0.2% / Sec with 100% torque step

20

Analog I/P

3 (Atleast 2 programmable Differential Current I/P

21

Analog O/P

2 programmable Differential Current O/P

22

Digital I/P

23

Digital O/P

3 relay O/P

24

Single Phase Protection

Required (I/P & O/P)

25

Overvoltage Trip Limit

1.3 * Vmax

26

Undervoltage Trip Limit

0.65 * Vmin

Page 1 of 4

150% for 1

DATA SHEET OF 415 V VVVF DRIVE FOR MOTORS


P.O No :2300024123/109 DATED 28/04/2010
CUSTOMER :TATA STEEL LTD ,Jamshedpur
Expansion Project

3MTPA

CONSULTANT :M.N DASTUR & CO (P) LTD

JOB NAME:
GAS MIXING & BOOSTING STATION FOR TSCR & LCP #8 & #9

DOC. NO.: BSL-TSL-GMBS-DS-97, R:1

Sl No

VVVFD DESCRIPTION

DATA TO BE CONFIRMED BY
VENDOR

PARAMETERS

27

Over Temperature

140 deg C (284 Deg F)

28

Auxiliary Voltage

Short Ckt Protected

29

Ground Fault

required

30

Microprocessor Fault

required

31

Motor Stall Protection

required

32

Motor Over-temperature Protection (I2t)

required

33

Degree of Protection

IP 40

Page 2 of 4

DATA SHEET OF 6.6 KV SWITCHBOARD


JOB NAME:
GAS MIXING & BOOSTING STATION FOR TSCR & LCP #8 &
#9

2300024123/109 DATED 28/04/2010


DOC. NO.: BSL-TSL-GMBS-DS-52, R:0

Sl No

Description

PARAMETERS

Equipment

6.6 kV Switchgear

1.4.1

Type

Horizontal isolation, horizontal drawout,vaccum /SF6 circuit -breaker

1.4.2

Rating of circuit breaker

6.6 kV,1250 A, ,40 kA for 3 Secs

1.4.3

Type of Operating Mechanism

240 V AC Motorised Spring Charged ( Supply to be obtained from substation


A.C.D.B /Auxilliary /Control Transformer

1.4.4

Closing Coil Voltage

110 V D.C.-Supply to be obltained from substation D.C.D.B

1.4.5

Trip Coil Voltage

110 V D.C

1.4.6

Accessories

1.4

-TNC Switch
-Alarm accept push -button
-CB auxilliary NO & NC swicthes (2 NO & 2 NC) spare in service position to be left
wired up to terminal strips for Purchaser's use )
-Anti - pumping contactor
- MCBs for spring charging motors and auxiliary transformer
-HRC control circuit fuses and liks
-240 V A.C space heaters with thermostat and switch and 240 V switch socket outlet
for each panel
-Stud Type terminal strips to which all contacts shall be wired to.
-Painted mimic
- All other fittings & accessories as required

1.4.7

Current Transformers

1.4.8

Relays

-Cast resin CTs ,40 kA /1 Sec


-As required and as per SLD
-One number single element high burden 110 DC master trip relays ,type VAJH -13
(Typical)

1.4.9
1.4.10 Meters

As per single line digram (minimum)/as required

1.4.11 Indication lamps (110 AC Cluster LED for All Lamps)

-CB "ON" "OFF", "AUTO TRIP","SPRING CHARGED","TRIP CIRUIT HEALTY"

1.4.12 6.6 kV switch board panels

-Additional panel of identical dimensions and paint shades to the above panels shall
be if the relays and meters as specified cannot be accomodated as proposed

1.4.13

For the specified arrangement of switchboard arrnagement of switchboard and cable termination ,dummy panels ,bus riser ,if required
,shall be provided as required.

1.4.14

Automatic Bus Transfer (ABT) scheme shall be incorporated in 6.6 kV switchboard ,generally confirming to with synchronism check
provision and with timer to allow paralleling for restoration of normal power supply to prevent asynchronous closing.Auto /manual
selection shall be provided for ABT .Provision shall also be provided to prevent closing of incoming & bus coupler circuit -breakers on
BUS FAULT conditions.

1.4.15

Protection ,control & supervision relays shall be numerical type. All metering relays,controls ,Alarm and annunciation system ,indication
lamps shall be mounted on the hinged door of the metering chamber in front of the switchboard.

1.4.16

Communicable type numericl and microprocessor based protection ,control and supervison relay shall be provided for .6 kV incoming
and outgoing feeders.

Page 3 of 4

DATA SHEET OF 6.6 KV SWITCHBOARD


JOB NAME:
GAS MIXING & BOOSTING STATION FOR TSCR & LCP #8 &
#9

2300024123/109 DATED 28/04/2010


DOC. NO.: BSL-TSL-GMBS-DS-52, R:0

1.4.17

General requirement of the communicable type numerical relay Instantaneous & IDMTL over current protection of setting range 8% to
800 % of CT primary current for instantaneous element with delay 0-10 seconds and 8% to 200 % of CT primary current for IDMTL
element and instantaneous & IDMTL earth fault protection of setting range 8% to 100 % of the CT primary current with time delay 0-10
seconds for instantaneous element . For incomers, numerical relays shall have O/C facilities.

1.4.18

Digital type Kwh meters of SATEC make shall be provided for the 6.6 kV incomers of 6.6 kV switchboard with facility of data
transmission ,in future ,having pulse output for data acquisition.

1.4.19

Static annunciation system with provision for alarm (audio & visual)and adequate channel with test /accept /reset acknowledge Pbs for
indication 6.6 kV Incoming & outgoing CB status, 415 V incoming /buscoupler ACBs status ,D.C supply availability ,ventilation system
failure & battery charger disturbance etc and transformers fault & trip status .A common push button for testing all lamps shall be
provided .

1.4.20 Each Bus section shall indicate bus voltage through individual bus PT provided in each bus section
1.4.21 Swicth board shall have base frame.
1.4.22 Switch board shall have continuos 50 X 6 copper earth bus at the bottom of the panel.
1.4.23 Pilot wire protection relays shall be accompanied with current injection unit.

Page 4 of 4