Models G and GB
General Clean Air Light Contaminants
Seismic High Wind Variable Volume
March
2013
Models G and GB
Spun Aluminum Downblast
Model Comparison . . . . . . . . . . . . . . . . . . . . . . 3
GB-071-200HP . . . . . . . . . . . . . . 18-32
Models GB-220-540 . . . . . . . . . . . . . . . . . 33-46
Seismic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SPECIFICATIONS:
High Wind & Hurricane. . . . . . . . . . . . . . . . . . . 7
*UL/cUL is optional
and must be specified
Seismic Certication
Models G and GB
Spun Aluminum Downblast
Model Comparison
9
9
9
9 9
9 9
9
9
6,308
1.75
44,700
3.25
Mixed Flow
Propeller/Axial
Centrifugal
Direct
Belt
High Wind**
Spark Resistant
Contaminated Air
General/Clean Air
9
9
Relative Cost
9
9
Recirculate
Reversible
Supply
Wall
Hanging
Base/Floor
Roof Curb
9
9
Maximum Static
Pressure (in. wg)
GB
9
9
Drive
Type
Application
Maximum Volume
(cfm)
Indoor
Outdoor
Model
Airow
Exhaust
Mounting
Ceiling Mounted
Location
* Smoke Control available on models: 101, 101HP, 121, 131, 141, 141HP, 161, 161HP, 200, 240, 300, 360, 420 and 480.
** High wind limited to sizes 300 and smaller
Direct Drive, G
Use for short and/or low resistance ductwork
Belt Drive, GB
For average length and/or average
resistance ductwork
High volume/average pressure
Construction Features
Models G and GB
Standard Construction Features
1
Wheel
Disconnect
Switch
NEMA-1 switch is factory mounted and wiring is provided from the motor as standard
(other switches are available). All wiring and electrical components comply with the
National Electrical Code (NEC) and are either UL Listed or Recognized.
Fan Shaft
Precisely sized, ground and polished so the first critical speed is at least 25% over
the maximum operating speed. Where the shaft makes contact with bearings, tight
tolerances result in longer bearing life.
Bearings
100% factory tested and designed specifically for air handling applications with a
minimum L10 life in excess of 100,000 hours (L 50 life of 500,000 hours).
Motor
Carefully matched to the fan load and is mounted out of the airstream.
Motor Cover
Constructed of aluminum and attached with fasteners that provide for easy removal and
access to motor compartment and drive assembly.
Motor Cooling
Cooling fins located on top of the fan wheel draw outside air through a large space
between the fan shroud and the motor cover directly into the motor compartment.
Positive motor cooling with fresh air results in maximum motor life.
Lifting Points
Various lifting points are located on the drive frame and bearing plate (on select sizes).
True Vibration
Isolation
Vibration isolators, with no metal-to-metal contact, support the drive assembly and
wheel for long life and quiet operation.
10
Drive Assembly
Belts, pulleys, and keys are oversized 150% of driven horsepower. Machined cast
pulleys are adjustable for final system balancing. Belts are static-free and oil-resistant.
11
Lower Windband
Heavy-gauge aluminum with formed edges for added strength and provides
weather resistance.
12
Curb Cap
Curb cap (with integral deep spun venturi) is constructed of aluminum and is one-piece for
a weather-tight fit.
13
Internal Conduit
Chase
A large diameter conduit for installing electrical wiring through the curb cap into the
motor compartment.
14
Nameplate
Permanent stamped aluminum plate for exact model and serial number identification.
15
Galvanized
Birdscreen
Rigid wire protects the fan discharge from birds and small objects.
16
Fan Shroud
One-piece, heavy-gauge aluminum with a rolled bead for extra strength directs exhaust
air downward.
17
Mounting Holes
Curb cap has prepunched mounting holes to ensure correct attachment to the roof.
18
Internal Supports
Heavy-gauge supports and bracing are added for additional strength to withstand
a load of 75 psf.
19
Reinforced
Wind Band
Roof Curb
(page 10)
High wind-load fans are certified for use with Greenheck model GPFHL, GPFHD, GPF or
equivalent in high wind applications. Roof curbs ship separate for field installation with
attachment details provided.
Construction Features
Models G and GB
6
7
5
15
11
14
12
8
MODEL G
DIRECT DRIVE
DRIVE FRAME
(BELT DRIVE)
6
3
10
4
8
16
2
9
13
18
19
MODEL GB
BELT DRIVE
17
5
Applications
G and GB models
Seismic - G and GB
Seismic
Testing Criteria
All Greenheck seismically certified models have been tested using the most severe seismic event that is
found on the Spectral Response Map per IBC Figures 1613.5 (1-2). Our testing is performed under the
worst case scenario using the highest mapped seismic load, highest level occupancy category, worst
case site class, and highest code mandated importance factor, thereby allowing Greenhecks seismically
certified fans to be used anywhere in the United States under any conditions
California OSHPD
Test Protocols
The California Office of Statewide Health Planning and Development (OSHPD) requires all certified
models be shake table tested in accordance with ICC ES AC-156, in which the fans are physically
subjected to the same or greater forces than they will see during a seismic event. Subjecting
Greenheck model G and GB fans to this type of testing ensures the fans will operate without
problems after a seismic event.
OSHPD Certification
No. 0148-10
The OSHPD certification numbers and supporting documents can be viewed on OSHPDs
website ensuring that the fan has been subjected to and passed rigorous testing standards.
State Licensed
P.E. Calculations
When using the fans in applications which are not covered by California OSHPD standards, Greenheck
models G and GB have been certified by a third party engineering firm to IBC 2009, 2012 and ASCE
7-05 standards. These engineers hold professional engineering (P.E.) licenses in all 50 states, so no
matter where your job is located, you are backed by a P.E. signature for your state.
Certified
Independent
Third-Party Testing
All Greenheck seismically certified fan models have gone through extensive testing procedures.
Greenheck models G and GB have been certified to IBC 2009, 2012, ASCE 7-05 and California OSHPD
standards through both engineering calculations and shake table testing of all models by independent
third party engineering firms.
Applications
G and GB models
U.S. continent
averaged
ed
tornado frequency.
Protocols designed
to protect against wind-borne
debris and severe wind-loads:
Structural
Performance Load
A static load that is 1.5times the design load (91.5 pounds per square foot of pressure) is applied both
positively and negatively to simulate wind force loads in each direction. Structural Performance per
Dade County Protocol TAS-202 (ASTM-E330).
Miami-Dade County
Test Protocols
Greenheck worked with Miami-Dade County to outline a High Velocity Hurricane Zone standard for
rooftop fans. Greenheck model USGF was the first rooftop fan certified and approved by the MiamiDade Building Code Compliance office and Texas Department of Insurance for use in hurricane zones.
Models G and GB have been certified by an independent third party to the ASTM E-330 Static Pressure
Difference Standard, Florida Building Code Test Protocol TAS-201 (large missile impact), 202 (static
pressure difference) and 203 (cyclic pressure) Static Pressure Difference.
Miami-Dade NOA
Numbers
The certifications can be viewed on the Miami-Dade County website under the NOA numbers listed here.
Models G and GB are the first downblast aluminum fans in the industry that have received a Miami-Dade
NOA for high wind and hurricane zones. Miami-Dade NOA 12-0120.13 for models
G and GB.
Florida Product
Approval
Florida Product Approval ensures that products which have been approved can be used anywhere in
the State of Florida which are not governed by the Miami-Dade County high wind regulations. More
information can be found on the Florida Building Code website. Florida Product Approval FL13225.1
for models G and GB
State Licensed
P.E. Calculations
Computational Fluid
Dynamics (CFD)
All Greenheck high wind models have been analyzed using Computational Fluid Dynamics (CFD).
CFD is computer software designed to simulate the flow of high speed winds over the surface of
objects. The software records the force profile exerted on the fan so it can be utilized
in Finite Element Analysis (FEA).
Finite Element
Analysis (FEA)
Utilizing the results from CFD analysis, Greenheck can accurately predict the stress, strain,
and deflection resulting from high wind loads. Greenheck high wind units have been proven
to withstand high winds through Finite Element Analysis utilizing CFD results.
Model G
Features
Motor Information
HP
RPM
1/6
1725
1/4
1725
1/2
1725
3/4
1725
1
1725
2
1725
Extended RPM Motors
1/2
2500
3/4
2200
Voltage
115, 208-240
115, 208-240
115, 208-240
115, 208-240
115, 208-240
208-240
HZ
50/60
50/60
50/60
50/60
50/60
50/60
115
115
50/60
50/60
Benets
Vari-Green Advantages
Initial cost is similar to a belt drive
500
INPUT POWER (WATTS)
50%
75%
100%
600
G-123
with PSC
400
Not recommended
300
EEnergy
S
Savings
GB-123
Single Phase*
200
G-123 with
100
0
0
350
1750
1,750
1,500
1,250
1,000
750
500
250
$0
CUBEGB121
121
CUEG121-A5
123-A5
CUEG121-VG
123-VG
Initial Cost
Maintenance cost over three years
Operating cost over three years
Vari-Green Controls
Transformer - Provides 24V power from the existing
line voltage at the fan to the Vari-Green motor and
controls. Dual voltage primary (120/240V) transformer
provided with the fan.
Remote Dial - Allows for remote, manual airow
adjustments. Wall plate with dial may be mounted in a
standard 2x4 inch electrical junction box.
Two Speed Control with Integral Transformer
Control allows motor rpm to be set at two
independent speeds (high or low). Meets minimum
airow requirements with the ability to bump up
to high speed in an emergency or meet maximum
airow requirements, or reset down to low for energy
conservation.
% of Operation
Time of Day
Series 1
% of Operation
1 2 3 4
Series 2
5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Time of Day
Constant Pressure Control - Indoor - Control VariGreen motor via static (variable volume) or velocity
(constant CFM) pressure on the inlet or outlet side of
the fan. Optional one or two duct or room probes for
use in:
Roof Curbs
10
Birdscreen
Galvanized mesh is standard,
optional aluminum or stainless
steel rigid wire are also available.
Disconnect Switches
A wide selection of NEMA rated
switches are available for positive
electrical shutoff and safety,
including: dust-tight, rainproof,
and corrosion-resistant.
Switches may be internally
or externally mounted.
Dampers
Coatings
Designed to prevent
outside air from entering
back into the building
when fan is off. Includes
gravity and motorized
dampers. Damper sizes
are shown on each
performance data page.
PRIMER
TM
PERMATECTOR
HI-PRO
POLYESTER
11
Typical Installations
Models G and GB
Factory Wired
from Motor to
Disconnect
figure 1
Wiring by
Others
3/4 in.
8 or 12 in.
(19 mm)
Damper
11/4 in.
(32 mm)
Recommended
Duct and
Damper Size
11/4 in.
(32 mm)
Recommended
Roof Opening
figure 2
Wiring by
Others
8 - 24 in.
(203 - 610 mm)
GPF or SD Curb
Damper
11/4 in. (32 mm)
Recommended
Duct and
Damper Size
Recommended
Roof Opening
Wheel Rotation
Direction of rotation is very critical. Rotation in the wrong direction will result in
excessive horsepower, possible motor burnout, and increased noise levels.
Check rotation by energizing the unit momentarily. The rotation should be the same
as the rotation decals afxed to the unit and is clockwise when viewed from the top
of the unit.
Clockwise
12
Typical Installations
Models G and GB
Good
Good
Poor
Poor
GB - 240 HP - VG/ 5 / A - X
VG
X = UL 705
F = UL Smoke
= Vari-Green
(Direct Drive only)
Configuration
G - Direct Drive
GB - Belt Drive
Fan Size
060 through 540
Control Systems
Motor HP
6
4
3
5
7
=
=
=
=
=
=
=
=
=
1/6
1/4
1/3
1/2
3/4
10
15
20
30
1
1
2
3
50 = 5
75 = 7
100 = 10
150 = 15
HP - High Pressure
Motor RPM
A = 1725
B = 1140
C = 860
D = 1550
E = 1050
G = 1300
International
(See CAPS for performance)
K = 950 RPM J = 1475 RPM
13
1938
140
(492)
RPM (Direct)
RPM (Vari-Green)
Density 0.075 lb/ft3
0.5
17
06
06
0-
5-
06
5-
06
0-
065
-E
06
0-
DO
0.0
60
120
180
240
300
360
Volume (cfm)
0
100
200
300
400
500
600
Volume (m /hr)
Direct Drive RPM
Direct
Drive
THIS
SYS
TEM
CUR
VE
0.1
20
(432)
VG
VG
40
0.2
5-
0-
134 (44)
60
0.3
06
06
3 (76)
80
0.4
TO
THE
LEF
T OF
(308)
NO
TS
ELE
CT
*12 8
100
1
120
G-1300-RPM
E-1050-RPM
D-1550-RPM
0.05
0.1
0.3
0.375
0.4
CFM
BHP
Sones
CFM
G-1/100 1300 BHP
Sones
CFM
D-1/60 1550 BHP
Sones
CFM
1725 BHP
Sones
138
0.00
1.7
170
0.01
2.9
203
0.01
4.3
226
0.02
5.4
116
0.00
1.7
153
0.01
2.8
188
0.01
3.9
213
0.02
4.9
90
0.01
1.7
135
0.01
2.8
173
0.01
3.8
199
0.02
4.9
73
0.01
1.7
125
0.01
2.7
166
0.01
3.8
193
0.02
4.8
53
0.01
1.7
113
0.01
2.7
158
0.02
3.8
186
0.02
4.8
85
0.01
2.6
140
0.02
3.7
173
0.02
4.8
120
0.02
3.7
155
0.02
4.7
92
0.02
3.6
137
0.02
4.6
101
0.02
4.5
89
0.02
4.4
CFM
BHP
Sones
CFM
1300 BHP
Sones
CFM
1550 BHP
Sones
CFM
1725 BHP
Sones
187
0.01
2.2
231
0.01
3.2
276
0.02
4.9
307
0.03
6.4
161
0.01
2.1
211
0.01
3.1
259
0.02
4.6
292
0.03
5.8
130
0.01
1.9
189
0.01
3
241
0.02
4.5
276
0.03
5.8
110
0.01
1.8
178
0.01
2.9
232
0.02
4.5
268
0.03
5.8
87
0.01
1.7
163
0.01
2.9
223
0.02
4.4
260
0.03
5.8
130
0.01
2.8
201
0.02
4.3
243
0.03
5.8
92
0.01
2.7
176
0.02
4.3
223
0.03
5.7
145
0.02
4.1
201
0.03
5.7
96
0.02
4
160
0.03
5.7
146
0.03
5.7
Motor
HP
Fan
RPM
060
VG1/6
E-1/200 1050
065
VG1/6
E-1/100 1050
G-1/60
D-1/30
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
14
1938
140
RPM (Direct)
0.0
SYS
TEM
CUR
VE
DO
07
5-
07
5-
90
180
270
360
450
540
Volume (cfm)
0
200
400
600
800
Volume (m /hr)
Direct Drive RPM
Motor
HP
D
0-
Direct
Drive
(432)
5-
0-
20
VG
0-
0.1
07
07
17
40
0.2
VG
G
0-
134 (44)
60
0.3
5-
07
3 (76)
80
07
07
(308)
0.4
07
*1218
120
100
RPM (Vari-Green)
Density 0.075 lb/ft3
Density 1.2 kg/m3
0.5
NO
TS
EL
EC
TT
OT
HE
LEF
TO
FT
HIS
(492)
E-1050-RPM
G-1300-RPM
D-1550-RPM
0.05
0.1
0.3
0.375
0.4
CFM
BHP
Sones
CFM
1300 BHP
Sones
CFM
1550 BHP
Sones
CFM
1725 BHP
Sones
253
0.01
2.7
314
0.01
4.1
374
0.02
5.6
416
0.03
6.8
226
0.01
2.1
292
0.01
3.7
356
0.02
5.4
400
0.03
6.7
195
0.01
1.7
269
0.02
3.4
337
0.02
5.2
383
0.03
6.7
179
0.01
1.5
257
0.02
3.3
327
0.03
5.1
375
0.03
6.6
152
0.01
1.2
244
0.02
3.2
317
0.03
5.1
366
0.03
6.6
214
0.02
2.9
297
0.03
4.9
348
0.04
6.5
171
0.02
2.6
274
0.03
4.7
329
0.04
6.3
244
0.03
4.5
309
0.04
6.2
190
0.03
4.1
270
0.04
5.9
253
0.04
5.7
CFM
BHP
Sones
CFM
1300 BHP
Sones
CFM
1550 BHP
Sones
CFM
1725 BHP
Sones
297
0.01
3.6
367
0.02
4.1
438
0.03
6.1
487
0.05
8.0
260
0.01
3.1
338
0.02
3.9
413
0.03
5.8
465
0.05
7.5
222
0.01
2.9
309
0.02
3.7
389
0.03
5.6
443
0.05
7.2
200
0.01
2.8
293
0.02
3.7
377
0.04
5.4
432
0.05
7.1
176
0.01
2.6
277
0.02
3.7
364
0.04
5.3
421
0.05
6.8
241
0.02
3.6
337
0.04
5.1
399
0.05
6.5
195
0.02
3.5
309
0.04
4.9
374
0.05
6.2
277
0.04
4.9
349
0.05
6.1
214
0.03
4.8
306
0.05
6.0
292
0.05
6.0
Fan
RPM
070
VG1/6
E-1/100 1050
G-1/60
D-1/30
075
VG1/6
E-1/80
G-1/50
D-1/25
1050
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
15
134 (44)
120
100
80
60
17
0.6
0.5
0.4
0.3
0.2
(432)
0.1
20
0
0.0
Direct Motor
HP
Drive
085
-VG
0-
VG
08
5-D
08
0-
08
5-G
08
0-
08
5-E
08
0-
DO
40
08
TO
T
4 (102)
140
0.7
(371)
*1458
HE L
EFT
OF T
HIS S
YSTE
M
0.8
180
160
CURV
E
0.9
220
NO
TS
ELE
CT
2134
(552)
100
200
300
400
500
600
Volume (cfm)
0
100
200
300
400
500
600
700
800
900
1000
Volume ( m /hr )
E-1050-RPM
G-1300-RPM
D-1550-RPM
VG-1725-RPM
0.1
0.125
0.3
0.375
0.5
0.625
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
335
0.01
3.8
415
0.02
5.4
495
0.04
7.3
551
0.05
9.1
268
0.02
3.7
361
0.03
5.4
450
0.04
7.3
511
0.06
9.1
249
0.02
3.6
348
0.03
5.4
439
0.04
7.3
501
0.06
9.1
230
0.02
3.7
333
0.03
5.4
427
0.05
7.3
490
0.06
9.1
189
0.02
3.9
303
0.03
5.4
404
0.05
7.3
469
0.06
9
134
0.02
4.2
272
0.03
5.5
379
0.05
7.2
449
0.07
8.9
239
0.03
5.6
354
0.05
7.3
426
0.07
8.9
174
0.03
5.9
314
0.06
7.3
392
0.07
8.9
237
0.06
7.6
332
0.08
9.1
260
0.08
9.4
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
398
0.01
4
493
0.02
5.5
588
0.04
7.6
654
0.05
9.5
326
0.02
3.9
436
0.03
5.3
541
0.04
7.4
612
0.06
9.4
307
0.02
3.9
420
0.03
5.3
528
0.05
7.4
602
0.06
9.4
286
0.02
3.9
405
0.03
5.3
515
0.05
7.4
590
0.06
9.3
240
0.02
4.1
375
0.03
5.3
490
0.05
7.4
567
0.07
9.3
179
0.02
4.3
340
0.04
5.3
464
0.05
7.4
544
0.07
9.3
302
0.04
5.4
439
0.06
7.4
521
0.07
9.3
233
0.04
5.5
394
0.06
7.4
486
0.08
9.3
308
0.06
7.6
419
0.08
9.4
168
0.06
8.1
340
0.09
9.4
Fan
RPM
080
D-1/20 1550
1725
085
D-1/20 1550
1725
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
16
1.0
134 (44)
17
0.4
50
0.2
0.0
RPM
RPM (Vari Green)
3
Density 0.075 lb/ft
Density 1.2 kg/m3
095-VG
090
-VG
095D
090
-D
095G
0-G
09
095
09 -E
0E
DO
(432)
100
0.6
THE L
E
4 (102)
150
NO
T SE
LECT
TO
(371)
0.8
*1458
200
FT OF
THIS S
YSTEM
CURVE
(552)
200
400
600
800
1000
1200
Volume (cfm)
0
500
1000
1500
2000
Volume ( m /hr )
Direct Drive RPM
Direct Motor
HP
Drive
E-1050-RPM
G-1300-RPM
D-1550-RPM
VG-1725-RPM
0.1
0.125
0.3
0.375
0.5
0.625
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
520
0.01
4
644
0.03
5.4
768
0.05
7.6
855
0.06
9.7
441
0.02
3.9
580
0.03
5.4
714
0.05
7.5
806
0.07
9.5
420
0.02
3.9
565
0.04
5.4
701
0.06
7.5
794
0.07
9.5
398
0.02
4
549
0.04
5.4
688
0.06
7.5
782
0.08
9.5
351
0.02
4.1
515
0.04
5.4
662
0.06
7.5
759
0.08
9.5
293
0.02
4.2
478
0.04
5.5
633
0.06
7.4
735
0.08
9.4
440
0.04
5.5
605
0.07
7.4
709
0.09
9.4
373
0.05
5.6
557
0.07
7.4
671
0.09
9.2
473
0.08
7.4
600
0.10
9.1
338
0.07
7.8
522
0.11
9.1
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
717
0.03
5.4
888
0.06
7.6
1059
0.10
9.6
1179
0.13
11.4
606
0.03
4.5
802
0.06
6.8
987
0.10
9.4
1114
0.14
11.4
570
0.04
4.5
780
0.06
6.7
969
0.10
9.3
1098
0.14
11.4
534
0.04
4.5
754
0.06
6.6
950
0.11
9.2
1081
0.14
11.5
468
0.04
4.4
695
0.07
6.5
912
0.11
9
1048
0.15
11.4
389
0.04
4.5
640
0.07
6.4
863
0.11
8.8
1013
0.15
11.2
290
0.03
4.6
586
0.07
6.4
814
0.11
8.7
969
0.15
11
493
0.07
6.4
745
0.12
8.7
903
0.16
10.9
184
0.05
6.8
623
0.12
8.7
800
0.16
11.3
474
0.11
8.7
688
0.16
11.3
Fan
RPM
090
VG- E-1/40
1/6 or
1/4
1050
G-1/25
1300
D-1/15
1550
1725
095
VG- E-1/30
1/6 or
1/4
1050
G-1/12
1300
D-1/8
1550
1725
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
17
2438
(619)
HP
300
RPM (Belt)
RPM (Direct)
8
1/
097-A
1.2
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
0.4
50
0.2
0.0
Motor HP
Direct
071
097
Fan
RPM
CFM
720 BHP
VG1/4
790
C-1/8
860
930
1000
1/6
or
1/8
1070
B-1/6
1140
1285
1435
1580
A-1/4
40
1725
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0.125
157
0.01
1.8
172
0.01
2.3
187
0.02
2.8
203
0.02
3.3
218
0.03
3.9
233
0.03
4.6
248
0.04
5.3
280
0.06
6.8
313
0.08
8.0
344
0.10
9.5
376
0.13
11.3
107
0.01
2.0
128
0.01
2.3
148
0.02
2.7
166
0.02
3.4
184
0.03
4.0
202
0.03
4.7
220
0.04
5.4
255
0.06
6.7
292
0.08
8.0
324
0.10
9.5
356
0.13
11.2
86
720
50
100
150
250
200
300
350
400
Volume (cfm)
0
100
200
300
400
500
600
Volume (m /hr)
Direct Drive RPM
Belt
11
097-C
097-B
19
(483)
4H
1/
25
17
100
0.6
35
134 (44)
150
0.8
14
438 (111)
200
HP
(603)
1.0
1/6
*2334
250
C-860-RPM
0.25
70
0.01
2.2
101
0.02
2.7
124
0.02
3.2
146
0.03
3.9
167
0.03
4.5
187
0.04
5.1
228
0.06
6.6
265
0.08
7.9
302
0.10
9.4
339
0.13
11.2
B-1140-RPM
A-1725-RPM
0.875
VG-1725-RPM
1.125
100
0.02
3.6
130
0.03
4.2
152
0.04
4.9
197
0.05
6.3
240
0.08
7.6
281
0.10
9.1
316
0.13
10.8
109
0.03
4.7
166
0.05
6.0
212
0.08
7.3
255
0.10
8.8
297
0.13
10.5
127
0.05
5.9
185
0.07
7.1
230
0.10
8.5
273
0.13
10.2
151
0.07
6.9
205
0.10
8.3
250
0.13
9.9
177
0.09
8.1
227
0.13
9.7
140
0.09
7.9
205
0.12
9.5
171
0.12
9.3
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
18
RPM (Belt)
RPM (Direct)
(619)
RPM (Vari-Green)
HP
438 (111)
YST
EM
CUR
VE
SE
LE
CT
TO
134 (44)
TH
EL
EF
TO
FT
HIS
S
(603)
*2334
19
(483)
DO
NO
Volume (cfm)
Volume (m /hr )
Direct Drive RPM
Belt
Motor HP
Direct
081
098
Fan
RPM
CFM
720 BHP
VG1/4
790
C-1/8
860
930
1000
1/6
1070
B-1/6
1140
1315
1490
1670
1/4
A-1/4
1725
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0.125
361
0.01
3.0
396
0.02
3.5
431
0.02
4.0
466
0.03
4.6
501
0.03
5.3
536
0.04
5.9
571
0.05
6.6
659
0.08
8.3
746
0.11
10.1
836
0.16
12.0
864
0.17
12.7
272
0.01
2.7
315
0.02
3.2
358
0.02
3.7
399
0.03
4.4
439
0.04
5.1
478
0.04
5.8
517
0.05
6.5
612
0.08
8.1
706
0.12
9.9
800
0.16
11.9
829
0.18
12.5
C-860-RPM
0.25
181
0.02
3
261
0.02
3.4
323
0.03
4.0
372
0.04
4.7
416
0.05
5.4
460
0.06
6.1
564
0.08
7.8
663
0.12
9.8
763
0.16
11.7
793
0.18
12.3
B-1140-RPM
A-1725-RPM
0.875
VG-1725-RPM
1.125
259
0.04
4.4
338
0.05
5.0
396
0.06
5.7
513
0.09
7.4
621
0.12
9.3
725
0.17
11.4
756
0.18
12.1
283
0.05
5.5
456
0.09
7.0
574
0.12
8.9
686
0.17
11.0
719
0.19
11.7
362
0.08
6.9
525
0.12
8.6
645
0.17
10.7
679
0.19
11.4
452
0.12
8.5
603
0.17
10.4
640
0.19
11.1
353
0.11
8.4
550
0.18
10.1
592
0.19
10.8
466
0.17
10.0
527
0.19
10.6
377
0.16
9.9
441
0.18
10.5
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
19
(619)
RPM (Vari-Green)
HP
134 (44)
SYS
TEM
CUR
VE
LEF
TO
FT
HIS
438 (111)
TO
TH
E
(603)
*2334
SE
LE
CT
19
O
(483)
DO
Volume (cfm)
Volume (m /hr )
Direct Drive RPM
Belt
Motor HP
Direct
091
099
Fan
RPM
CFM
720 BHP
VG1/4
790
C-1/8
860
930
1000
1/4
1070
B-1/6
1140
1285
1435
1580
A-1/4
1725
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0.125
546
0.02
3.6
599
0.02
4.2
652
0.03
4.9
705
0.04
5.6
758
0.04
6.4
811
0.05
7.3
864
0.07
8.3
974
0.09
9.5
1087
0.13
10.7
1197
0.17
12.1
1307
0.23
13.6
403
0.02
3.5
471
0.02
4.1
536
0.03
4.7
598
0.04
5.5
659
0.05
6.2
718
0.06
7.1
777
0.07
8.1
897
0.10
9.4
1018
0.14
10.6
1135
0.18
12.0
1250
0.23
13.5
C-860-RPM
0.25
291
0.02
3.9
400
0.03
4.5
481
0.04
5.1
552
0.05
5.8
621
0.06
6.7
687
0.07
7.6
819
0.10
9.0
949
0.14
10.4
1072
0.19
11.9
1192
0.24
13.4
B-1140-RPM
A-1725-RPM
0.875
VG-1725-RPM
1.125
414
0.05
5.6
512
0.06
6.3
590
0.07
7.1
736
0.10
8.5
877
0.14
10.0
1009
0.19
11.5
1135
0.24
13.2
457
0.07
6.8
647
0.11
8.2
801
0.15
9.6
941
0.19
11.2
1076
0.25
12.9
526
0.10
7.9
721
0.15
9.3
872
0.20
10.9
1013
0.25
12.6
615
0.15
9.0
799
0.20
10.6
949
0.26
12.3
404
0.12
8.4
707
0.20
10.3
883
0.26
12.0
583
0.19
9.8
806
0.26
11.8
707
0.25
11.5
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
20
(619)
RPM (Vari-Green)
HP
CUR
VE
SYS
TEM
SE
LE
CT
19
50
134 (44)
13
438 (111)
TO
TH
EL
EFT
OF
THI
S
(603)
*2334
(483)
DO
Volume (cfm)
3
Volume (m /hr )
Direct Drive RPM
Belt
Motor HP
Direct
101
Fan
RPM
0.125
610
0.02
3.8
729
0.03
4.6
848
0.05
5.5
966
0.07
6.6
1055
0.10
7.5
1144
0.12
8.5
1229
0.15
9.3
1318
0.19
10.2
1407
0.23
11.4
1462
0.25
12.2
1525
0.29
13.3
477
0.02
2.7
623
0.04
3.7
753
0.05
4.8
883
0.08
6.0
978
0.10
7.0
1073
0.13
8.1
1162
0.16
9.0
1255
0.19
10.0
1348
0.23
11.1
1405
0.26
11.9
1471
0.30
12.8
C-860-RPM
0.25
B-1140-RPM
A-1725-RPM
0.875
VG-1725-RPM
1.25
103
CFM
720 BHP
VG1/4
C-1/8
860
1000
B-1/6
1/4
1140
1245
1350
1450
1555
1660
A-1/4
1725
1/3
1800
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
473
0.04
2.9
654
0.06
4.4
805
0.09
5.7
908
0.11
6.7
1006
0.13
7.8
1099
0.16
8.7
1196
0.20
9.7
1292
0.24
10.7
1351
0.27
11.5
1419
0.30
12.5
507
0.08
4.1
715
0.11
5.7
851
0.14
7.2
965
0.17
8.0
1079
0.22
8.9
1187
0.26
10.1
1250
0.29
10.9
1321
0.33
12.2
731
0.14
6.7
878
0.17
7.5
1005
0.22
8.4
1122
0.26
9.6
1193
0.29
10.3
1270
0.33
11.4
750
0.17
6.9
917
0.22
8.0
1050
0.26
9.1
1126
0.29
10.0
1209
0.33
10.9
791
0.21
7.5
963
0.26
8.7
1052
0.29
9.5
1142
0.33
10.6
841
0.25
8.1
955
0.29
9.0
1065
0.33
10.2
793
0.30
9.3
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
21
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
(603)
438 (111)
134 (44)
URVE
NO
TS
EL
EC
TT
OT
HE
LEF
TO
F TH
IS S
YSTE
MC
*2334
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
19
(483)
Volume (cfm)
3
Volume (m /hr )
Direct Drive RPM
Belt
Motor HP
Direct
101HP
Fan
RPM
0.25
0.5
571
0.06
6.6
635
0.08
8.4
699
0.10
10.4
758
0.13
11.4
826
0.17
12.7
890
0.21
14.2
939
0.25
15.4
979
0.28
15.8
1026
0.33
16.4
1098
0.40
17.8
1120
0.43
18.2
477
0.06
5.7
553
0.09
7.5
626
0.11
9.5
692
0.14
10.7
767
0.18
12.2
836
0.23
13.6
889
0.26
14.8
931
0.30
15.4
981
0.34
16
1056
0.42
17.4
1078
0.44
17.9
342
0.07
5.3
449
0.09
7
537
0.12
9.1
613
0.15
10.6
697
0.19
11.9
772
0.24
13.3
830
0.28
14.4
875
0.31
14.8
928
0.36
15.4
1008
0.43
16.9
1032
0.46
17.4
VG-2550-RPM
1.75
2.25
103HP
CFM
1300 BHP
VG1/2
1445
1590
1/4
A-1/4
1725
1880
2025
2137
1/3
2229
2336
1/2
A-1725 RPM
2500
2550
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
243
0.08
6.3
417
0.12
8.3
521
0.16
10.1
618
0.20
12
702
0.24
13.2
765
0.28
14.2
814
0.32
14.5
871
0.36
14.9
956
0.45
16.7
982
0.47
17.2
364
0.15
10
518
0.20
11.4
622
0.26
12.6
693
0.29
13.4
748
0.33
14.1
809
0.37
14.7
901
0.45
15.8
928
0.47
16.3
337
0.18
11.9
515
0.25
12
607
0.30
13.1
674
0.35
13.7
742
0.39
14
840
0.46
15.5
869
0.49
16.1
313
0.22
11.4
474
0.28
12.1
574
0.33
13.2
661
0.40
14.1
775
0.48
14.8
807
0.51
15.1
406
0.31
12.0
543
0.37
13.5
695
0.48
15.2
735
0.52
15.6
358
0.34
13.6
583
0.46
15.7
639
0.50
16.2
416
0.42
16.6
497
0.47
17.2
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
22
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
438 (111)
CU
RV
E
TH
E
134 (44)
LE
FT
OF
TH
IS
SY
ST
EM
(603)
*2334
TO
19
(483)
DO
T
NO
CT
LE
SE
Volume (cfm)
3
Volume (m /hr )
Direct Drive RPM
Belt
Motor HP
Direct
121
Fan
RPM
0.125
704
0.02
3.2
873
0.03
4.2
1043
0.05
5.4
1213
0.08
6.7
1383
0.12
8.4
1535
0.16
10.2
1692
0.21
12.5
1789
0.25
13.5
1880
0.29
14.6
1983
0.34
15.9
2093
0.40
17.4
515
0.02
3.3
735
0.04
4.3
932
0.06
5.5
1119
0.09
6.8
1300
0.13
8.4
1460
0.17
10.1
1625
0.23
12.4
1726
0.27
13.4
1820
0.31
14.5
1926
0.36
15.8
2038
0.42
17.2
C-860-RPM
0.25
B-1140-RPM
A-1725-RPM
VG-1725-RPM
1.25
1.5
123
CFM
580 BHP
VG1/2
720
C-1/8
1/4
860
1000
B-1/6
1140
1265
1395
1475
1/3
1550
1635
1/2
A-1/2
1725
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
523
0.04
4.1
796
0.06
5.2
1013
0.09
6.7
1213
0.14
8.4
1384
0.18
10.1
1557
0.24
12.3
1661
0.28
13.3
1759
0.32
14.3
1868
0.37
15.6
1984
0.44
17.0
694
0.09
6.4
993
0.14
7.9
1204
0.19
9.7
1404
0.26
12.0
1521
0.30
13.0
1629
0.34
14.0
1747
0.40
15.3
1871
0.46
16.7
831
0.14
7.8
1093
0.20
9.6
1315
0.26
11.7
1441
0.31
12.7
1555
0.35
13.8
1680
0.41
15.0
1810
0.47
16.4
950
0.19
9.4
1214
0.26
11.5
1356
0.31
12.4
1475
0.36
13.5
1608
0.42
14.8
1743
0.48
16.2
907
0.24
11.3
1132
0.31
12.0
1289
0.36
12.9
1446
0.43
13.9
1600
0.50
15.5
974
0.33
12.4
1231
0.41
13.4
1426
0.50
14.9
1180
0.47
14.0
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
23
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
134 (44)
CU
RV
E
SY
ST
EM
TH
IS
TH
E
19
OF
4 (102)
(483)
DO
NO
T
EC
EL
TS
TO
Volume (cfm)
3
Volume (m /hr )
Direct Drive RPM
Belt
131
Motor HP
Direct
Fan
RPM
0.125
823
0.02
4.5
1022
0.04
5.4
1221
0.06
6.6
1419
0.10
8.1
1618
0.15
10.0
1774
0.19
12.0
1866
0.22
13.2
2044
0.29
15.0
2271
0.40
16.2
2391
0.47
16.9
2448
0.50
17.4
626
0.02
4.5
879
0.04
5.4
1106
0.07
6.5
1323
0.11
8.0
1535
0.16
9.8
1698
0.2
11.7
1794
0.23
12.8
1978
0.31
15.0
2212
0.42
16.0
2335
0.48
16.6
2393
0.52
17.0
C-860-RPM
0.25
B-1140-RPM
A-1725-RPM
VG-1725-RPM
1.25
1.5
133
CFM
580 BHP
VG3/4
720
C-1/8
1/4
860
1000
B-1/6
1140
1250
1315
1/3
1440
1600
1/2
1685
3/4
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
LE
FT
(603)
*2334
A-1/2
1725
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
650
0.04
5.2
962
0.07
6.3
1213
0.11
7.7
1444
0.16
9.6
1617
0.21
11.3
1718
0.24
12.5
1911
0.32
15.1
2152
0.43
15.8
2279
0.50
16.3
2338
0.53
16.7
867
0.11
7.0
1211
0.17
8.8
1426
0.23
10.5
1545
0.26
11.7
1759
0.34
14.5
2023
0.45
15.3
2158
0.52
15.7
2220
0.56
15.9
1031
0.17
8.5
1133
0.22
9.7
1435
0.26
11.2
1674
0.34
13.9
1873
0.47
14.6
2093
0.54
15.1
2159
0.57
15.6
1305
0.26
10.9
1571
0.35
13.4
1783
0.47
14.2
2020
0.55
14.8
2089
0.58
15.4
1299
0.34
12.5
1686
0.48
13.9
1857
0.56
14.5
1935
0.59
14.9
1425
0.47
13.2
1654
0.56
13.9
1746
0.60
14.3
1312
0.52
13.5
1474
0.58
13.8
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
24
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
(603)
4 (102)
134 (44)
22
SE
LE
CT
(559)
TO
*2334
TH
EL
EF
TO
FT
HIS
SY
STE
MC
URV
E
DO
NO
Volume (cfm)
3
Volume (m /hr )
Direct Drive RPM
Belt
141
Motor HP
Direct
Fan
RPM
CFM
VG3/4
1/4
720
C-1/8
860
950
1075
1/3
B-1/3
1140
1265
1/2
1360
1450
VG-1
1550
0.125
1076
0.04
4.7
1336
0.07
5.8
1595
0.12
7.1
1762
0.16
8.1
1994
0.24
10.0
2115
0.28
11.0
2347
0.39
12.9
2523
0.48
14.6
2690
0.58
16.2
2875
0.71
17.7
3200
0.98
20.0
855
0.04
4.7
1169
0.08
5.9
1457
0.13
7.0
1636
0.17
8.0
1882
0.25
9.9
2008
0.30
10.9
2250
0.40
12.7
2433
0.50
14.3
2606
0.60
15.9
2797
0.73
18.0
3129
1.00
21.0
0.25
A-1725-RPM
1.25
VG-1725-RPM
1.5
1.75
143
580 BHP
3/4
B-1140-RPM
C-860-RPM
A-1
1725
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
938
0.08
5.2
1304
0.13
6.6
1506
0.18
7.6
1771
0.26
9.4
1905
0.31
10.4
2158
0.41
12.3
2347
0.51
13.9
2524
0.61
15.6
2719
0.74
17.4
3059
1.02
20.0
1085
0.17
6.5
1490
0.26
8.4
1660
0.31
9.4
1955
0.42
11.4
2166
0.52
13.1
2358
0.63
14.7
2566
0.77
16.8
2923
1.05
19.6
1233
0.29
8.2
1677
0.42
10.4
1943
0.53
12.2
2165
0.64
13.8
2396
0.78
15.0
2782
1.07
18.5
1048
0.35
8.8
1602
0.51
11.0
1905
0.63
12.9
2191
0.79
14.8
2619
1.07
17.2
1501
0.59
11.7
1910
0.76
14.8
2427
1.09
17.0
1297
0.65
14.9
2184
1.06
16.8
1815
1.00
16.7
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
25
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
*2334
(603)
4 (102)
134 (44)
TO
TH
EL
EFT
OF
THI
SS
YST
EM
CUR
VE
00
SE
LE
CT
22
22
(559)
DO
NO
Damper Size = 16 x 16
Roof Opening = 18 x 18 (470 x 470)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight G/GB = 75/83 lbs. (34/38 kg)
Volume (cfm)
3
Volume (m /hr )
Belt
Motor HP
Direct
141HP
Fan
RPM
.5
CFM
VG3/4
B-1/4
1140
1320
1500
1/3
1655
A-1/2
1/2
A-1725-RPM
VG-2200-RPM
2.25
2.5
2.75
143HP
1020 BHP
1/4
.75
B-1140-RPM
1725
1812
1900
2050
3/4
2170
2200
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
488
0.08
6.3
645
0.11
7.7
837
0.17
10.3
1009
0.24
13.1
1151
0.32
15.0
1213
0.36
16.2
1289
0.41
17.8
1366
0.47
19.0
1495
0.58
21.0
1598
0.68
22.0
1623
0.71
23.0
413
0.11
7.6
700
0.18
9.8
903
0.26
12.3
1064
0.34
14.1
1132
0.38
15.4
1213
0.43
17.2
1294
0.49
18.4
1430
0.61
20.0
1536
0.71
22.0
1562
0.74
22.0
592
0.25
12.4
833
0.35
13.1
932
0.39
14.2
1030
0.46
15.8
1127
0.53
17.4
1285
0.65
19.3
1407
0.76
21.0
1436
0.78
22.0
668
0.34
13.6
784
0.39
14.3
911
0.45
15.6
1033
0.53
16.8
1200
0.66
18.8
1328
0.77
21.0
1360
0.80
21.0
588
0.37
14.9
763
0.45
15.9
901
0.52
16.7
1113
0.66
18.6
1248
0.78
21.0
1281
0.82
21.0
545
0.41
16.6
753
0.51
17.0
991
0.66
18.3
1163
0.79
21.0
1200
0.82
21.0
857
0.65
18.3
1045
0.78
20.0
1088
0.81
21.0
672
0.61
18.6
919
0.77
19.7
968
0.80
20.0
757
0.74
19.8
834
0.79
20.0
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
26
163-A
600
HP
2.5
RPM (Belt)
HP
1.5
(619)
RPM (Direct)
RPM (Vari-Green)
HP
P
1H
TH
EL
EF
TO
FT
HIS
SY
ST
EM
CU
RV
E
TO
SE
LE
CT
NO
T
75
50
25
17
15
75
12
40
1000
2000
3000
4000
5000
Volume (cfm)
0
2000
4000
6000
8000
Volume (m /hr)
Direct Drive RPM
Fan
RPM
0.0
11
94
86
DO
13
161
HP
0.5
100
Damper Size = 16 x 16
Roof Opening = 18 x 18 (470 x 470)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight G/GB = 101/88 lbs. (46/40 kg)
Motor HP
Direct
163-B
1.0
163-C
(559)
Belt
HP
3/4
200
22
1.5
4
1/
1 4 (44)
3
300
HP
1/3
4 (102)
400
(603)
2.0
H
1/2
*2334
500
B-1140-RPM
C-860-RPM
0.125
0.25
1713
0.07
5.8
2127
0.14
7.8
2540
0.23
10.5
2791
0.31
12.6
3249
0.48
15.3
3367
0.54
15.9
3545
0.63
17.0
3692
0.71
17.9
4062
0.95
21
4652
1.42
26
5095
1.87
30
1417
0.08
5.6
1893
0.15
7.5
2344
0.24
10.0
2612
0.32
12.0
3095
0.50
14.7
3219
0.56
15.4
3403
0.65
16.5
3557
0.73
17.4
3938
0.97
20
4545
1.45
25
4997
1.89
30
970
0.07
5.3
1632
0.15
7.2
2145
0.25
9.6
2434
0.33
11.5
2943
0.52
14.1
3072
0.57
14.9
3263
0.66
16.0
3422
0.75
17.0
3815
0.99
19.6
4437
1.47
25
4899
1.92
30
A-1725-RPM
1.25
1.5
163
CFM
580 BHP
VG-1
1/4
720
C-1/4
860
1/3
945
1/2
1100
B-1/2
1140
1200
3/4
1250
1375
VG-2
1 2
1575
A-2
1725
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
1243
0.14
6.8
1913
0.26
9.3
2236
0.34
11.2
2787
0.53
13.8
2922
0.58
14.5
3123
0.68
15.6
3289
0.76
16.6
3694
1.01
19.2
4330
1.49
24
4800
1.94
29
2198
0.52
12.5
2382
0.59
13.3
2641
0.69
14.6
2838
0.79
15.6
3304
1.04
18.4
4007
1.54
24
4510
2.01
28
1900
0.50
12.0
2125
0.57
12.9
2429
0.68
14.1
2658
0.78
15.2
3161
1.05
18.0
3894
1.56
23
4409
2.03
28
1808
0.54
12.1
2167
0.66
13.7
2444
0.76
14.9
3007
1.04
17.6
3769
1.56
23
4308
2.04
28
2609
1.01
17.2
3512
1.57
22
4082
2.06
27
2073
0.93
15.4
3198
1.54
22
3845
2.06
26
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
27
Exhaust
Roof Downblast - Belt
Drive
Belt Drive
Size: GB H-GB
GB-161HP
2838
RPM (Belt)
(721)
HP
*2334
(603)
4 (102)
134 (44)
SE
LE
CT
TO
THE
LEF
TO
F TH
IS S
YST
EM C
URV
E
22
NO
T
(559)
D
Volume (cfm)
Volume (m /hr)
Motor
HP
Fan
RPM
0.5
0.625
0.75
1.75
2.25
2.5
161HP
825
1/4
960
1095
1/3
1210
1270
1/2
1330
1390
1485
3/4
1580
1660
1
1740
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
702
0.11
6.5
1093
0.18
7.7
1380
0.26
9.0
1606
0.34
10.6
1718
0.39
11.4
1829
0.44
12.3
1938
0.50
13.3
2109
0.60
14.9
2275
0.72
16.7
2414
0.82
18.3
2551
0.94
20
919
0.17
7.6
1271
0.26
9.0
1514
0.35
10.3
1636
0.40
11.2
1753
0.45
12.1
1865
0.51
13.0
2041
0.61
14.7
2214
0.73
16.7
2357
0.84
18.8
2497
0.96
21
585
0.15
8.0
1139
0.26
8.9
1416
0.35
10.4
1545
0.40
11.1
1668
0.46
11.9
1789
0.52
12.8
1973
0.63
14.4
2150
0.75
16.4
2297
0.85
18.3
2442
0.97
21
949
0.37
11.4
1204
0.45
12.0
1399
0.53
12.7
1654
0.65
13.7
1868
0.77
14.7
2037
0.89
16.2
2200
1.03
17.5
1032
0.48
13.1
1416
0.63
14.0
1704
0.791
14.8
1887
0.91
15.8
2066
1.03
17.2
1012
0.57
14.7
1447
0.75
15.4
1702
0.90
15.8
1917
1.05
16.8
1034
0.67
16.6
1441
0.86
17.1
1714
1.03
17.2
996
0.75
20
1452
0.98
19.2
987
0.85
28
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
28
2.5
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
600
HP
1H
HP
1.5
(902)
60
14
TO
SE
LE
CT
55
NO
T
35
85
10
DO
13
11
40
183-C
11
HP
HP
1.0
0.5
(762)
H
3/4
183-B
3
1/
30
134 (44)
200
1.5
4
1/
512 (140)
400
H
1/2
*28
(711)
2.0
94
8
81 60
0
73
0
49
180
Motor HP
Direct
Fan
RPM
CFM
730 BHP
VG-1
1/3
810
C-1/2
860
1/2
940
1000
3/4
1055
B-1
1140
VG-2
1185
112
1000
2000
3000
4000
5000
6000
2000
4000
6000
8000
10000
Volume (m /hr)
Direct Drive RPM
C-860-RPM
0.125
0.25
2839
0.21
7.4
3150
0.29
8.8
3344
0.35
10.1
3655
0.46
12.7
3888
0.55
15.2
4102
0.65
16.2
4433
0.81
17.9
4608
0.91
19.0
5191
1.31
22
5444
1.51
24
5677
1.71
26
2668
0.23
8.7
2997
0.31
9.9
3202
0.36
10.8
3527
0.47
12.8
3769
0.57
14.7
3990
0.67
15.7
4329
0.84
17.4
4508
0.94
18.4
5102
1.33
22
5359
1.54
23
5596
1.74
25
2469
0.25
7.2
2832
0.33
8.7
3049
0.39
9.8
3388
0.49
12.0
3638
0.58
13.7
3867
0.68
14.9
4216
0.85
16.8
4401
0.96
17.8
5010
1.36
21
5273
1.56
23
5514
1.77
24
B-1140-RPM
1.5
1.75
183
1/4
Volume (cfm)
Belt
0.0
1335
1400
2
1460
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
1882
0.25
6.7
2375
0.35
8.2
2647
0.42
9.1
3052
0.54
11.1
3339
0.64
13.0
3596
0.74
14.0
3980
0.93
16.0
4179
1.03
17.1
4814
1.41
21
5086
1.61
22
5336
1.81
24
2387
0.63
11.1
2811
0.77
12.4
3328
0.98
14.3
3575
1.1
15.4
4344
1.54
19.2
4655
1.75
21
4938
1.97
23
2856
0.95
13.6
3178
1.09
14.7
4052
1.57
18.7
4401
1.81
21
4699
2.03
22
2499
0.99
13.7
3713
1.56
18.2
4097
1.81
20
4426
2.05
22
3262
1.51
17.6
3747
1.79
19.7
4123
2.05
22
3253
1.71
19.2
3765
2.02
21
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
29
(902)
HP
Density 0.075 lb/ft3
134 (44)
CU
RVE
SY
ST
EM
FT
HIS
EF
TO
512 (140)
TH
EL
*28
(711)
TO
30
LE
CT
(762)
DO
T
NO
SE
Volume (cfm)
Volume (m /hr )
Motor
HP
Fan
RPM
0.5
0.75
2.25
2.5
2.75
180HP
795
1/4
845
1/3
935
1/2
1075
1150
3/4
1225
1350
1445
112
1540
1620
2
1700
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
1547
0.22
8.6
1759
0.26
9.1
2114
0.35
10.3
2601
0.51
12.9
2847
0.61
14.6
3088
0.73
16.3
3485
0.96
19.5
3782
1.16
22
4076
1.39
25
4319
1.60
27
4560
1.84
30
1920
0.52
11.6
2298
0.65
12.6
2610
0.78
13.9
3095
1.04
16.4
3428
1.25
18.8
3744
1.49
21
4005
1.71
24
4263
1.96
26
1811
0.62
12.3
2277
0.78
13.3
2840
1.05
15.8
3213
1.28
17.8
3576
1.53
20
3848
1.76
23
4114
2.01
25
1711
0.72
13.2
2540
1.05
15.0
2969
1.29
17.3
3353
1.55
19.6
3663
1.79
22
3964
2.06
24
2059
0.99
15.1
2670
1.28
16.4
3119
1.56
18.9
3450
1.81
21
3764
2.08
23
2216
1.21
16.6
2827
1.55
18.1
3223
1.82
20
3560
2.10
22
2407
1.48
18.3
2923
1.80
19.7
3340
2.11
22
2512
1.72
19.8
3037
2.07
21
2642
1.99
21
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
30
(902)
RPM (Direct)
HP
Density 0.075 lb/ft3
CUR
VE
TO
134 (44)
TH
EL
EF
TO
FT
HIS
SYS
TEM
512 (140)
*28
(711)
SE
LE
CT
30
(762)
DO
NO
Volume (cfm)
Volume (m /hr )
Direct Drive RPM
Motor HP
Belt
Direct
200
Fan
RPM
0.125
2435
0.1
6.5
3320
0.25
8.5
3680
0.34
9.6
3973
0.43
10.8
4261
0.52
12.1
4759
0.73
14.1
5340
1.03
16.7
5689
1.25
18.5
6032
1.49
20
6308
1.7
22
6640
1.99
24
1976
0.1
5.8
2984
0.26
7.9
3378
0.34
9
3700
0.43
10
4013
0.53
11
4548
0.74
13.3
5158
1.04
16
5517
1.26
17.8
5870
1.5
19.6
6154
1.71
21
6494
2
23
0.25
B-1140-RPM
1.0
1.25
1.5
1.75
203
440
1/4
600
1/3
665
718
1/2
770
3/4
C-860-RPM
C-3/4
860
965
1028
112
1090
B-2
1140
2
1200
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
2637
0.26
7.3
3085
0.35
8.5
3422
0.45
9.6
3744
0.55
10.7
4289
0.75
12.9
4927
1.05
15.4
5309
1.27
17.2
5682
1.51
18.9
5980
1.72
21
6336
2.01
23
2089
0.25
6.1
2706
0.35
7.7
3109
0.45
9
3477
0.55
10.2
4068
0.77
12.4
4720
1.08
15
5101
1.29
16.8
5473
1.52
18.4
5779
1.74
20
6145
2.02
22
3085
0.74
11.1
4015
1.08
13.7
4488
1.32
15.6
4925
1.56
17.5
5267
1.79
19.1
5651
2.09
21
3240
1.02
13
3911
1.28
14.7
4450
1.56
16.8
4832
1.79
18.5
5274
2.09
21
2941
1.14
14.6
3751
1.48
15.8
4287
1.75
17.5
4829
2.08
19.9
3439
1.61
16.5
4177
1.99
18.6
3077
1.69
16.7
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
31
(902)
HP
Density 0.075 lb/ft3
134 (44)
30
URV
E
IS S
YST
EM
C
L EF
TO
F TH
512 (140)
TO
TH
E
*28
(711)
N
OT
SE
LE
CT
(762)
DO
Volume (cfm)
3
Motor
HP
Fan
RPM
0.5
0.75
1.25
2.75
3.25
200HP
740
1/2
895
958
3/4
1020
1125
1205
1 2
1
1285
1350
2
1415
1520
3
1625
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
1961
0.30
8.7
2809
0.52
11.4
3116
0.63
12.8
3409
0.75
14.1
3885
0.99
16.9
4229
1.19
18.8
4569
1.43
21
4843
1.65
23
5114
1.88
24
5550
2.31
27
5982
2.80
32
2331
0.53
10.9
2715
0.65
12.1
3050
0.77
13.6
3584
1.02
16.4
3967
1.24
17.9
4343
1.49
20
4638
1.71
22
4919
1.95
24
5368
2.38
27
5812
2.88
31
1424
0.45
10.3
2153
0.63
11.6
2602
0.78
13.1
3243
1.04
15.5
3663
1.27
17.2
4070
1.52
19.1
4384
1.75
21
4692
2.00
23
5182
2.45
27
5642
2.95
31
1857
0.71
12.6
2804
1.04
15.3
3314
1.29
16.5
3770
1.55
18.1
4109
1.78
19.8
4442
2.04
22
4952
2.50
26
5448
3.02
29
2136
0.97
15.2
2884
1.27
16.4
3416
1.57
17.8
3811
1.81
19.3
4169
2.07
21
4713
2.53
24
5233
3.06
28
2278
1.40
18.9
2996
1.76
19.1
3492
2.07
19.7
4166
2.58
23
4767
3.13
27
2250
1.78
23
3458
2.53
22
4196
3.16
25
2850
2.38
22
3859
3.12
24
2046
2.06
22
3377
3.01
23
2725
2.76
22
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
32
RPM (Belt)
HP
534 (146)
134 (44)
YS
TE
MC
UR
VE
(800)
TH
EL
EF
TO
FT
HIS
S
*3112
LE
CT
TO
34
(864)
DO
NO
SE
Motor
HP
Fan
RPM
0.125
0.25
3230
0.14
7.4
3533
0.18
8.1
3799
0.23
8.8
4179
0.30
10.0
4863
0.48
13.0
5395
0.65
15.0
5737
0.79
15.7
6079
0.93
16.6
6444
1.11
17.8
6801
1.31
19.4
7485
1.74
23
2879
0.16
7.2
3219
0.20
7.8
3512
0.25
8.4
3924
0.32
9.6
4654
0.50
12.8
5206
0.68
14.9
5559
0.82
15.6
5911
0.97
16.4
6286
1.15
17.5
6651
1.34
19.1
7349
1.78
23
2296
0.16
6.9
2758
0.21
7.4
3132
0.26
7.9
3629
0.34
8.9
4403
0.53
12.1
4990
0.71
14.4
5362
0.84
15.2
5732
1.00
16.1
6122
1.18
17.2
6501
1.38
18.8
7212
1.82
23
1.25
1.5
220
425
1/4
465
500
1/3
550
1/2
640
3/4
710
755
1
800
848
112
895
985
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
1951
0.19
7.0
2542
0.26
7.5
3158
0.35
8.4
4120
0.54
11.2
4762
0.73
13.6
5148
0.87
14.6
5530
1.02
15.6
5932
1.21
16.9
6323
1.41
18.5
7062
1.86
22
2526
0.33
8.0
3702
0.55
10.5
4459
0.74
12.8
4920
0.89
14.0
5326
1.05
15.2
5741
1.23
16.5
6142
1.44
18.2
6898
1.89
22
3208
0.54
9.7
4077
0.75
12.1
4579
0.90
13.4
5049
1.06
14.6
5540
1.26
16.2
5960
1.47
18.0
6734
1.92
22
3633
0.74
11.2
4206
0.90
12.7
4716
1.07
14.2
5236
1.27
15.7
5723
1.49
17.6
6568
1.95
22
3095
0.82
11.2
3929
1.05
12.5
4566
1.27
14.5
5122
1.50
16.9
6107
1.99
21
3542
1.17
13.4
4401
1.47
15.5
5548
2.00
20
4883
1.96
19.0
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
33
YST
EM
CUR
VE
SE
LE
CT
TO
134 (44)
FT
HIS
S
534 (146)
TH
EL
EF
TO
(800)
*3112
RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
34
(864)
DO
NO
Motor
HP
Fan
RPM
0.5
0.625
0.75
2952
0.47
8.9
3215
0.53
9.4
3614
0.65
10.6
3973
0.77
12.0
4532
1.00
15.0
4975
1.22
16.7
5400
1.46
18.7
5740
1.68
21
6076
1.93
23
6422
2.20
24
7100
2.82
28
2555
0.46
8.5
2871
0.53
9.2
3312
0.65
10.3
3719
0.79
11.5
4317
1.02
13.8
4791
1.25
16.0
5245
1.50
18.2
5591
1.72
20
5935
1.97
22
6289
2.24
24
6981
2.87
27
1892
0.42
8.3
2440
0.52
8.9
2974
0.65
9.9
3424
0.79
11.1
4083
1.04
13.5
4590
1.27
15.3
5060
1.53
17.5
5432
1.76
19.4
5794
2.01
21
6154
2.29
23
6858
2.92
27
2.25
2.5
220HP
650
1/2
680
728
3/4
775
850
913
112
975
1025
2
1075
1127
3
1230
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
2643
0.75
10.5
3536
1.03
12.7
4119
1.29
14.4
4660
1.57
16.3
5075
1.81
18.2
5459
2.06
20
5852
2.36
22
6611
3.01
27
2648
0.95
12.0
3545
1.27
13.5
4185
1.56
15.4
4643
1.82
17.1
5082
2.10
18.7
5520
2.41
21
6316
3.08
25
2557
1.13
13.0
3602
1.53
14.8
4157
1.804
16.4
4649
2.10
18.3
5124
2.42
20
6009
3.14
25
3492
1.74
15.6
4136
2.07
17.7
4703
2.41
19.3
5649
3.15
23
3346
1.93
16.4
4173
2.37
18.6
5263
3.14
22
3299
2.17
17.7
4812
3.10
22
4265
3.02
22
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
34
134 (44)
EFT
OF
THI
S SY
STE
MC
URV
E
534 (146)
TT
OT
HE
L
(800)
*3112
RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
SE
LE
C
34
OT
(864)
DO
Motor
HP
Fan
RPM
0.125
0.25
3902
0.19
5.9
4223
0.24
6.7
4637
0.32
7.8
5371
0.50
10.3
5720
0.60
11.7
6060
0.71
13.1
6702
0.96
15.8
7143
1.16
17.7
7575
1.39
19.7
7988
1.63
22
8355
1.86
24
3422
0.21
5.9
3785
0.26
6.6
4242
0.35
7.5
5031
0.53
9.7
5400
0.64
11.0
5757
0.75
12.4
6428
1.01
15.0
6886
1.21
16.6
7332
1.44
18.6
7757
1.68
21
8135
1.92
23
2691
0.20
4.7
3188
0.27
5.7
3761
0.35
6.9
4666
0.54
9.1
5069
0.65
10.4
5449
0.78
11.8
6158
1.05
14.3
6632
1.26
15.9
7092
1.49
17.7
7529
1.73
19.6
7916
1.97
21
1.25
1.5
240
425
1/4
460
1/3
505
1/2
585
623
3/4
660
730
778
112
825
870
2
910
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
2036
0.22
4.2
3060
0.34
6.1
4195
0.55
8.8
4660
0.66
10.0
5094
0.79
11.3
5861
1.05
13.8
6363
1.27
15.4
6844
1.51
17.2
7300
1.77
19.1
7700
2.02
21
3562
0.53
8.2
4131
0.65
9.6
4636
0.78
11.0
5507
1.06
13.4
6058
1.28
15.0
6574
1.52
16.8
7055
1.78
18.7
7467
2.03
21
2112
0.41
7.2
3428
0.61
9.1
4073
0.76
10.6
5077
1.06
13.1
5700
1.29
14.7
6261
1.54
16.4
6775
1.80
18.3
7215
2.05
20
3217
0.69
10.4
4568
1.03
12.9
5266
1.28
14.4
5901
1.53
16.2
6457
1.80
17.9
6933
2.06
19.6
4145
1.18
13.2
5002
1.48
14.8
5680
1.77
16.9
6240
2.05
19.2
7757
1.68
21
5388
1.97
16.7
3707
1.66
13.6
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
35
RPM (Belt)
HP
534 (146)
CU
RVE
TO
134 (44)
HIS
SY
ST
EM
(800)
TH
EL
EF
TO
FT
*3112
EL
EC
T
34
(864)
DO
NO
Motor
HP
Fan
RPM
0.5
0.625
3035
0.42
8.0
3475
0.53
9.4
3877
0.64
11.0
4247
0.76
12.7
4860
0.99
15.9
5310
1.20
18.5
5751
1.43
22
6114
1.65
24
6474
1.89
27
6853
2.16
29
7610
2.80
31
2586
0.41
7.6
3147
0.53
8.8
3603
0.65
10.3
4005
0.77
11.9
4654
1.02
15.2
5118
1.23
17.4
5574
1.47
19.9
5948
1.69
23
6315
1.92
26
6702
2.20
27
7471
2.84
30
0.75
2.25
2.5
240HP
635
1/2
685
733
3/4
780
860
920
1 2
1
980
1030
2
1080
1133
3
1240
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
2693
0.51
8.4
3272
0.65
9.7
3740
0.78
11.3
4434
1.04
14.3
4925
1.25
16.6
5392
1.49
19.1
5776
1.72
21
6154
1.96
24
6550
2.24
26
7333
2.89
29
2964
0.75
10.3
3915
1.05
13.2
4496
1.29
15.0
5010
1.54
17.2
5428
1.77
19.6
5826
2.02
23
6237
2.31
24
7053
2.97
28
3105
0.99
12.2
3944
1.27
13.8
4562
1.55
15.6
5039
1.80
17.6
5468
2.06
20
5914
2.36
22
6767
3.04
27
3958
1.52
14.8
4560
1.80
16.3
5062
2.08
18.2
5560
2.40
21
6469
3.10
25
3896
1.73
15.7
4555
2.05
17.3
5133
2.39
19.3
6146
3.14
24
3763
1.93
16.7
4588
2.35
18.7
5775
3.14
23
5364
3.13
23
4776
3.04
22
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
36
RPM (Belt)
HP
Density 0.075 lb/ft3
*36
(914)
814 (210)
OT
HE
LEF
TO
F TH
IS S
YST
EM C
URV
E
TS
EL
EC
TT
134 (44)
40
NO
(1016)
DO
Motor
HP
Fan
RPM
0.125
0.25
3875
0.12
8.0
4714
0.22
9.2
5231
0.30
10.4
6005
0.45
11.4
6716
0.63
12.9
7491
0.88
14.4
8588
1.33
16.7
9041
1.55
17.8
9493
1.79
18.9
10138
2.18
21
10784
2.62
23
3121
0.14
7.1
4130
0.25
8.8
4716
0.33
10.3
5570
0.50
10.9
6324
0.68
12.1
7137
0.93
13.7
8278
1.39
16.2
8746
1.61
17.4
9212
1.86
18.6
9875
2.26
20
10537
2.70
23
1727
0.12
7.4
3393
0.26
8.6
4095
0.35
10.3
5063
0.52
10.4
5898
0.72
11.3
6775
0.98
13.0
7979
1.44
15.8
8460
1.67
17.0
8938
1.92
18.3
9617
2.33
20
10292
2.78
22
0.5
1.5
1.75
260
300
1/4
365
1/3
405
1/2
465
3/4
520
580
112
665
700
2
735
785
3
835
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
3745
0.53
9.6
4869
0.75
10.3
5912
1.04
12.2
7274
1.53
15.0
7811
1.77
16.2
8335
2.03
17.6
9069
2.44
19.7
9794
2.91
22
3008
0.64
9.4
4826
1.03
11.0
6474
1.57
14.2
7068
1.82
15.5
7649
2.10
16.8
8452
2.53
18.9
9225
3.02
21
5465
1.55
13.3
6227
1.83
14.8
6878
2.13
16.2
7769
2.58
18.2
8606
3.08
20
3608
1.29
12.8
4912
1.71
13.8
5916
2.09
15.6
7006
2.59
17.9
7932
3.12
19.9
4236
1.80
14.9
5949
2.49
17.1
7157
3.10
19.7
4189
2.11
16.7
6024
2.93
18.7
4294
2.49
18.6
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
37
134 (44)
FT
HIS
SYS
TEM
TH
EL
EF
TO
814 (210)
SE
LE
CT
TO
*36
(914)
CUR
VE
RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
40
(1016)
DO
NO
Motor
HP
Fan
RPM
0.125
4859
0.18
9.3
5912
0.33
9.2
6803
0.50
9.6
7694
0.72
11.4
8585
1.00
13.4
9719
1.45
15.9
10772
1.97
18.8
11549
2.43
21
12311
2.94
23
13363
3.76
25
14416
4.73
28
3976
0.19
5.3
5222
0.35
6.2
6222
0.52
8.0
7197
0.75
10.6
8150
1.04
12.9
9334
1.49
15.4
10425
2.02
18.2
11226
2.48
20
12007
3.00
22
13084
3.82
25
14157
4.79
28
0.25
0.5
1.5
1.75
300
300
1/3
365
1/2
420
3/4
475
530
112
600
665
713
3
760
825
5
890
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
4340
0.35
5.7
5537
0.53
7.0
6616
0.77
9.6
7640
1.06
12.2
8907
1.53
14.9
10060
2.06
17.7
10901
2.53
19.6
11704
3.05
21
12804
3.88
24
13898
4.85
28
5095
0.74
8.1
6456
1.07
10.7
7952
1.55
13.8
9228
2.11
16.8
10129
2.59
18.9
10997
3.13
21
12175
3.97
24
13335
4.96
27
4195
0.91
9.4
6721
1.52
12.2
8269
2.11
15.7
9297
2.61
18.0
10242
3.16
19.8
11501
4.02
23
12716
5.03
26
7025
2.03
13.7
8283
2.57
16.4
9369
3.15
18.6
10770
4.05
22
12073
5.06
25
6691
2.38
13.7
8293
3.06
16.8
9909
4.01
20
11379
5.09
24
6437
2.76
14.0
8885
3.90
18.7
10536
5.02
22
7128
3.56
16.1
9568
4.89
21
7963
4.54
18.7
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
38
814 (210)
134 (44)
*36
(914)
TH
EL
EF
TO
FT
HIS
SY
ST
EM
CU
RVE
RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
LE
CT
TO
40
(1016)
N
DO
OT
SE
Motor
HP
Fan
RPM
0.5
0.75
1.25
2.25
2.5
2.75
300HP
460
1/2
495
3/4
565
620
112
710
748
2
785
840
3
895
980
5
1065
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
2912
0.41
9.7
3602
0.53
10.3
4662
0.77
11.8
5398
1.01
13.4
6542
1.48
17.2
7013
1.71
18.8
7460
1.96
20
8107
2.37
23
8746
2.84
25
9722
3.68
32
10688
4.67
44
3309
0.94
10.6
5269
1.55
15.3
5889
1.81
17.0
6402
2.08
18.5
7146
2.52
21
7870
3.03
23
8951
3.90
29
10006
4.94
37
4221
1.47
13.4
5027
1.78
15.7
5737
2.10
17.9
6636
2.57
21
7394
3.07
23
8531
3.99
28
9621
5.04
37
4800
2.00
16.2
5922
2.56
19.7
6892
3.11
23
8094
4.03
27
9233
5.12
36
4992
2.43
18.0
6150
3.08
22
7657
4.08
26
8831
5.17
35
5245
2.92
19.8
7029
4.09
25
8429
5.23
33
6264
3.95
24
7903
5.24
31
5222
3.69
23
7255
5.17
30
6543
5.01
29
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
39
RPM (Belt)
HP
878 (225)
TO
134 (44)
CU
RVE
(978)
TH
EL
EF
TO
FT
HIS
SY
STE
M
*3812
EL
EC
T
46
(1168)
DO
T
NO
Motor
HP
Fan
RPM
0.125
0.25
6159
0.22
5.2
6643
0.28
5.9
7850
0.46
8.5
8937
0.68
10.2
10024
0.95
12.6
11232
1.34
15.1
12319
1.77
17.7
13285
2.22
19.6
14251
2.74
22
15580
3.57
24
16908
4.57
28
5043
0.25
4.9
5633
0.31
5.5
7029
0.50
8.3
8232
0.73
9.8
9401
1.01
11.9
10683
1.40
14.6
11824
1.84
17.2
12828
2.29
19.2
13825
2.82
21
15190
3.66
24
16549
4.66
27
3236
0.22
4.8
4308
0.31
5.2
6036
0.52
7.4
7410
0.76
9.2
8713
1.06
11.3
10087
1.46
14.0
11294
1.91
16.6
12340
2.37
18.7
13376
2.90
21
14786
3.75
24
16185
4.761
27
1.25
1.5
1.75
330
255
1/3
275
1/2
325
3/4
370
415
112
465
510
550
3
590
645
5
700
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
5257
0.72
8.3
7050
1.07
10.0
8706
1.51
12.8
10085
1.98
15.6
11266
2.47
17.7
12408
3.03
19.8
13922
3.91
23
15408
4.95
27
6966
1.46
11.7
8696
1.99
14.4
10041
2.51
16.7
11307
3.09
18.8
12958
4.00
22
14564
5.08
26
6472
1.79
13.9
8616
2.46
15.7
10081
3.08
17.7
11912
4.04
21
13624
5.14
25
8536
2.95
17.1
10749
4.01
20
12640
5.17
24
9292
3.85
19.4
11538
5.12
23
10184
4.94
22
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
40
RPM (Belt)
HP
SY
ST
EM
TO
134 (44)
LE
FT
OF
TH
IS
878 (225)
TH
E
(978)
*3812
CU
RV
E
EC
T
46
(1168)
DO
NO
L
SE
Motor
HP
Fan
RPM
0.125
0.25
8024
0.40
7.6
8693
0.51
8.7
9763
0.72
10.8
10966
1.02
13.7
12304
1.45
15.9
12919
1.67
17.0
13507
1.91
18.1
14524
2.38
20
15513
2.90
22
16931
3.77
26
18322
4.77
30
7070
0.43
6.6
7830
0.54
7.7
9024
0.76
10.0
10330
1.07
13.3
11737
1.50
15.6
12379
1.73
16.7
12991
1.97
17.8
14043
2.44
19.8
15064
2.96
22
16519
3.84
25
17941
4.85
30
5804
0.44
5.6
6756
0.56
6.8
8109
0.79
8.9
9558
1.11
11.9
11085
1.55
14.8
11776
1.78
16.1
12431
2.02
17.3
13551
2.5
19.4
14614
3.03
22
16107
3.91
25
17560
4.93
29
1.25
1.5
360
300
1/2
325
3/4
365
410
112
460
483
2
505
543
3
580
633
5
685
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
5001
0.51
5.6
7013
0.78
7.9
8686
1.12
10.9
10360
1.58
14.1
11109
1.82
15.5
11795
2.07
16.8
12959
2.55
18.9
14077
3.09
21
15654
3.98
24
17179
5.01
29
7641
1.11
9.6
9568
1.59
13.1
10355
1.83
14.8
11096
2.09
16.5
12350
2.59
18.6
13523
3.14
21
15146
4.04
24
16711
5.07
28
8607
1.56
12.1
9517
1.83
13.7
10368
2.10
15.5
11679
2.60
17.8
12917
3.17
20
14639
4.10
23
16243
5.14
28
7096
1.46
10.9
8488
1.78
12.9
9473
2.07
14.7
10965
2.60
16.9
12289
3.18
19.1
14072
4.12
23
15774
5.20
26
8917
2.46
15.6
10813
3.13
17.6
12892
4.13
21
14710
5.23
24
11465
4.05
19.7
13535
5.21
23
12119
5.10
22
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
41
RPM (Belt)
HP
Density 0.075 lb/ft3
878 (225)
TO
134 (44)
TH
EL
EF
TO
FT
HIS
S
(978)
*3812
YST
EM
CUR
VE
SE
LE
CT
46
(1168)
DO
NO
Motor
HP
Fan
RPM
0.5
0.75
1.25
2.5
2.75
360HP
420
1
435
112
500
525
2
550
590
3
630
690
5
750
803
712
855
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
6097
0.91
10.4
6576
1.02
10.8
8432
1.56
13.4
9061
1.79
14.7
9681
2.05
16.0
10657
2.50
18.0
11616
3.01
20
13062
3.93
24
14487
5.02
27
15728
6.13
31
16918
7.37
35
5650
1.61
12.7
6998
1.98
14.2
8495
2.52
15.7
9767
3.10
17.6
11464
4.11
21
13002
5.22
24
14309
6.33
28
15568
7.58
33
6528
2.32
14.9
8525
3.04
16.9
10468
4.05
20
12220
5.26
24
13647
6.46
27
14946
7.71
31
6006
2.63
15.7
9335
3.99
19.2
11282
5.20
23
12863
6.44
26
14315
7.82
29
7159
3.60
18.1
10239
5.13
22
11960
6.37
25
13544
7.76
29
8513
4.83
21
10986
6.30
24
12676
7.69
27
9445
6.01
23
11761
7.61
27
10368
7.32
26
8273
6.63
25
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
42
RPM (Belt)
HP
Density 0.075 lb/ft3
CU
RV
E
TH
E
134 (44)
OF
TH
IS
SY
ST
EM
934 (248)
LE
FT
*44
(1118)
52
(1321)
DO
NO
CT
LE
SE
Motor
HP
Fan
RPM
0.125
8242
0.27
3.1
9890
0.46
4.6
11332
0.69
6.2
12568
0.95
8.0
14217
1.37
11.7
15659
1.83
14.4
17925
2.74
19.0
19574
3.57
22
21222
4.55
24
22994
5.79
27
24725
7.20
30
6454
0.29
2.9
8573
0.50
5.0
10219
0.75
6.8
11579
1.01
8.4
13357
1.45
11.3
14892
1.92
13.8
17264
2.86
18.4
18968
3.69
21
20663
4.68
24
22478
5.93
27
24245
7.35
30
0.25
1.00
1.25
1.5
420
200
1/2
240
3/4
275
305
112
345
380
435
475
5
515
558
7 2
1
600
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
6365
0.48
4.9
8698
0.76
5.6
10320
1.03
7.5
12411
1.49
10.8
14043
1.97
13.3
16540
2.93
17.8
18320
3.78
20
20081
4.80
23
21957
6.07
26
23765
7.51
30
8672
1.01
7.2
11102
1.50
10.1
12983
2.00
12.7
15792
2.97
17.3
17640
3.84
19.8
19459
4.87
22
21383
6.15
25
23243
7.61
29
9463
1.45
9.6
11787
2.00
12.3
14790
2.99
16.6
16887
3.88
19.3
18826
4.92
21
20805
6.22
24
22709
7.70
27
10108
1.91
12.0
13764
3.00
16.4
15929
3.90
18.6
18046
4.95
21
20219
6.28
24
22166
7.76
27
12502
2.95
16.5
14994
3.91
18.3
17162
4.98
20
19446
6.31
23
21621
7.81
26
12315
3.69
18.3
15254
4.92
19.4
17835
6.34
23
20104
7.87
26
12312
4.56
19.1
15908
6.21
22
18585
7.86
26
16590
7.64
26
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
43
RPM (Belt)
1114 (286)
CU
RV
E
TH
E
134 (44)
LE
FT
OF
TH
IS
SY
ST
EM
*4714
(1200)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
TO
58
(1473)
DO
OT
C
LE
SE
Motor
HP
Fan
RPM
0.125
0.25
12020
0.51
7.3
13522
0.73
8.3
15025
1.00
9.5
17129
1.48
11.8
18631
1.90
14.0
21636
2.98
17.6
23619
3.87
20
24942
4.56
22
25542
4.90
23
27345
6.01
27
29149
7.28
31
10059
0.55
6.6
11811
0.77
8.0
13516
1.05
9.5
15830
1.54
11.2
17437
1.97
13.0
20608
3.06
17.0
22678
3.66
19.9
24050
4.65
22
24672
4.99
23
26532
6.11
27
28386
7.39
31
6529
0.48
7.3
9500
0.76
7.6
11662
1.06
8.6
14379
1.58
10.7
16135
2.02
12.2
19548
3.13
16.4
21736
4.05
19.5
23158
4.75
22
23801
5.09
23
25719
6.22
27
27623
7.50
31
0.875
1.25
480
1/2
200
3/4
225
250
112
285
310
360
393
415
425
455
712
485
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
9587
1.42
9.1
12656
1.97
11.5
17010
3.17
15.5
19605
4.14
18.3
21181
4.85
21
21883
5.20
22
23966
6.36
26
26016
7.67
30
15420
3.21
15.0
18254
4.12
18.0
20012
4.86
20
20799
5.22
21
23046
6.41
25
25153
7.72
29
13507
3.00
14.2
16764
4.06
17.5
18733
4.84
20
19550
5.20
21
21953
6.41
25
24290
7.78
29
15086
3.94
16.7
17211
4.74
19.1
18156
5.13
20
20786
6.38
24
23201
7.75
28
15486
4.58
18.1
16604
5.00
19.3
19471
6.30
24
22106
7.73
28
15870
5.85
21
19517
7.49
26
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
44
RPM (Belt)
HP
Density 0.075 lb/ft3
CU
RV
E
EM
TH
IS
SY
ST
OF
TH
E
134 (44)
LE
FT
1412 (368)
*5034
(1289)
64
(1626)
DO
NO
T
EC
EL
S
T
Motor
HP
Fan
RPM
0.125
14102
0.50
6.7
16117
0.75
8.4
17245
0.92
9.5
19743
1.38
11.9
21677
1.83
14.0
24820
2.74
17.7
27157
3.59
19.9
29494
4.60
22
33764
6.90
27
35457
8.00
30
37068
9.14
32
11123
0.57
6.5
13588
0.85
8.0
14939
1.04
9.1
17749
1.54
11.5
19873
2.02
13.8
23263
3.00
17.4
25739
3.89
19.5
28188
4.92
22
32624
7.27
27
34371
8.38
29
36030
9.54
32
0.25
0.875
1.25
500
175
200
214
112
245
269
308
337
5
366
712
419
440
10
460
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
10593
0.83
7.7
12242
1.04
8.7
15481
1.57
11.0
17857
2.06
13.2
21627
3.09
16.9
24253
4.01
19.1
26834
5.10
21
31467
7.57
27
33279
8.74
29
34991
9.94
32
12983
1.53
10.7
15752
2.08
12.7
19752
3.11
16.2
22614
4.06
18.5
25429
5.20
21
30265
7.70
26
32134
8.87
29
33900
10.10
32
17903
3.11
15.8
20937
4.08
17.9
23831
5.20
20
29015
7.80
26
30989
9.01
29
32805
10.24
32
15284
2.96
15.6
19206
4.06
17.6
22310
5.24
19.8
27607
7.80
25
29679
9.03
28
31625
10.32
31
16671
3.88
17.4
20688
5.19
19.5
26276
7.84
24
28373
9.05
27
30342
10.32
30
18366
4.99
19.4
24940
7.88
24
27107
9.10
26
29127
10.36
29
23486
7.78
23
25801
9.09
26
27917
10.41
28
22407
8.73
25
25310
10.26
27
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
45
RPM (Belt)
CU
RV
E
LE
FT
1412 (368)
OF
TH
IS
SY
ST
EM
*5034
(1289)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
TH
E
134 (44)
O
64
(1626)
DO
NO
T
EC
EL
TS
Motor
HP
Fan
RPM
0.125
15488
0.61
6.9
17258
0.85
7.8
18143
0.99
8.3
20798
1.49
10.1
22922
1.99
12.3
26197
2.97
16.2
31064
4.96
21
35578
7.45
27
39118
9.90
32
41950
12.21
36
44694
14.77
40
1250
0.65
6.3
14674
0.90
7.5
15724
1.04
8.2
18814
1.57
10.4
21228
2.09
12.1
24874
3.11
15.6
30005
5.13
21
34653
7.65
26
38277
10.12
32
41165
12.45
36
43957
15.02
40
0.25
1.25
1.5
1.75
540
175
195
205
112
235
259
296
351
712
402
10
442
474
15
505
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
11068
0.87
7.2
12632
1.03
8.1
16229
1.56
10.5
18963
2.11
11.9
22870
3.14
15.3
28492
5.21
19.9
33552
7.80
26
37435
10.34
32
40381
12.68
37
43221
15.27
40
12673
1.50
10.6
16439
2.08
11.6
20831
3.13
15.0
26810
5.24
19.3
32075
7.84
25
36109
10.39
32
39287
12.80
36
42332
15.45
40
18610
3.10
14.3
25115
5.23
18.7
30612
7.87
24
34766
10.44
32
38034
12.85
35
41157
15.51
39
21376
5.15
17.4
27519
7.82
23
32131
10.46
28
35558
12.90
33
38813
15.60
38
24274
7.73
21
29134
10.36
27
32927
12.84
31
36503
15.60
36
26111
10.24
26
30151
12.73
30
33869
15.48
35
26271
12.42
28
31293
15.36
32
26758
14.84
30
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.
46
Specifications
Vari-Green
Vari-Green Control Indoor Air Quality
Temperature / Humidity
Control to be a packaged indoor air quality control
designed to regulate fan speed based on level of
temperature and/or relative humidity in a space.
Control shall include a Proportional Integral Derivative
(PID) feedback loop and shall have labeled terminal
strips for easy wiring. Fan shall be direct drive
including an electronic commutation (EC) Vari-Green
Motor. Control package shall be Vari-Green Indoor Air
Quality Temperature / Humidity Control.
Vari-Green Motor
Motor to be an electronic commutation (EC)
motor specifically designed for fan applications.
AC induction type motors are not acceptable.
Examples of unacceptable motors are: Shaded
Pole, Permanent Split Capacitor (PSC), Split
Phase, Capacitor Start and 3phase induction type
motors. Motors shall be permanently lubricated
with heavy-duty ball bearings to match the fan load
and prewired to the specific voltage and phase.
Internal motor circuitry shall convert AC power
supplied to the fan to DC power to operate the
motor. Motor shall be speed controllable down to
20% of full speed (80% turndown). Speed shall be
controlled by either a potentiometer dial mounted
on the motor or by a 0-10 VDC signal. Motor shall
be a minimum of 85% efficient at all speeds.
LEED information
Greenheck became one of the rst manufacturers
in the Air Movement and Control industry to join
the LEED/green movement when they joined the
United States Green Building Council (USGBC) in
2005. Greenheck has been actively researching
qualication requirements for our products to meet
LEED credits and prerequisites.
47
48
49
50
Anywhere. Anytime.
Regional warehouses are nearby
and fully stocked.
U.S.
California
Florida
North Carolina
Texas
Wisconsin
WORLDWIDE
Mexico
MANUFACTURING LOCATIONS
California
Kentucky
North Carolina
Wisconsin
China
Mexico
1 HOUR
LOCAL STOCK
CUSTOMER
PICK UP
QD STOCK
SAME-DAY
OR NEXT DAY
SHIPMENTS
1-DAY
CUSTOM-BUILT
PRODUCTS
SHIPPED IN
ONE DAY
3-5-10-DAYS
CUSTOM-BUILT
PRODUCTS
SHIPPED IN 3, 5
OR 10 DAYS
Model G
Number
060-095
097-098
099-103
103HP
123
133
143
143HP
163
183
203
QD-1-3-5-10
1-3-5-10
QD-1-3-5-10
1-3-5-10
QD-1-3-5-10
QD-1-3-5-10
QD-1-3-5-10
1-3-5-10
QD-1-3-5-10
1-3-5-10
1-3-5-10
Size
Model GB
Number
071-091
101
101HP
121
131
141
141HP
161
161HP
180
180HP
200
200HP
220
220HP
240
240HP
260
300
300HP
330
360
360HP
420
480
500
540
QD-1-3-5-10
QD-1-3-5-10
1-3-5-10
QD-1-3-5-10
QD-1-3-5-10
QD-1-3-5-10
1-3-5-10
QD-1-3-5-10
1-3-5-10
QD-1-3-5-10
1-3-5-10
QD-1-3-5-10
1-3-5-10
1-3-5-10
1-3-5-10
QD-1-3-5-10
1-3-5-10
1-3-5-10
QD-1-3-5-10
1-3-5-10
1-3-5-10
1-3-5-10
1-3-5-10
1-3-5-10
1-3-5-10
1-3-5-10
1-3-5-10
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and
in the Library under Warranties.
Prepared to Support
Green Building Efforts
00.F&V.1000 R8 3-2013 SP
Copyright 2013 Greenheck Fan Corp.