2, APRIL 2013
733
AbstractIt is widely known that controlled switching of transmission lines reduces the transients in power systems. In this paper,
the circuit-breaker (CB) closing time sequence for transmission
lines with various configurations is studied and improved. A theoretical analysis based on modal analysis of traveling waves and
inverse Laplace transform is used to find the actual zero voltage
crossing point of the poles of CB. The transmission-line coupling
effect and its effects on controlled closing sequence are also considered. In addition, the minimum requirement for dielectric strength
and operating time deviation of the CB is extracted for successful
controlled closing. Finally, comprehensive simulation studies are
performed to obtain the optimum closing sequence for various lines
configurations. It is shown that transmission-line overvoltages are
reduced using the proposed controlled closing method.
Index TermsClosing time deviation, controlled closing, optimum closing instant, rate of decrease of dielectric strength
(RDDS), transmission-line switching.
I. INTRODUCTION
CLOSING operation of a transmission line (TL) can produce transient overvoltages whose maximum peaks can
reach up to 3 p.u. It depends on several factors (e.g., the network
configuration on the source side of the breaker and the shunt
compensation level of the transmission line). One of the factors, which has more influence on the maximum voltage peak,
is the instant of closing, which can be different for every pole
of a three-phase breaker [1].
Traditionally, the transient overvoltages due to the switching
of transmission lines are limited through the adoption of preinsertion resistors in the line circuit breakers (CBs) [2]. Although
this is an effective mitigation method, the high cost of implementation and maintenance as well as high failure rates of the
closing resistors have motivated the researchers to study the
concept of accurate modeling of controlled switching relays
(switchsync relays) [3]. Using controlled closing can effectively
limit the overvoltages and eliminate the need for closing resistors [4].
Controlled switching relays offer a closing sequence (i.e., the
pole spread of 1/6 cycle between phases) to energize a transManuscript received February 25, 2012; revised July 31, 2012, September 24,
2012; accepted November 02, 2012. Date of publication January 15, 2013; date
of current version March 21, 2013. This work was supported by the University
of Tehran under Grant 8101064-1-05. Paper no. TPWRD-00194-2012.
The authors are with the School of Electrical and Computer Engineering,
College of Engineering, University of Tehran, Tehran 14395-515, Iran. (e-mail:
m.atefi@ece.ut.ac.ir; msanaye@ut.ac.ir).
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TPWRD.2012.2227831
mission line at zero voltage across the CB contacts [5]. However, these relays do not consider the induced voltage in the
other open phases due to closing of the first pole of CB whereas
this paper focuses on this subject. Although various papers have
studied the transmission-line switching topic, very few studies
are reported about the induced voltage.
The ultimate target for controlled closing is the intended energizing instant which is supervised by the phase angle at which
the CB starts to pre-strike with respect to the selected reference [5]. The elapsed time between the flashover point and the
time when the contacts engage represents the arcing time [6].
In an ideal case, the CB contacts should touch exactly when the
voltage across the contacts is zero. But in reality, the CB operating time may deviate from the intended target. This is usually
caused by variations in the operating conditions, for example,
gradually increasing contact burn-off caused by a high number
of switching operations, change of ambient temperature, and
variations of the auxiliary voltage. The variation in the closing
time of the CB poles is presumed to follow a Gaussian distribution with a standard deviation where a typical value of 0.2 ms
corresponds to a highly stable CB [7].
One of the main causes of deviation in the closing time of a
CB is the variation of the rate of decrease of dielectric strength
(RDDS). For proper operation of CB, the value of RDDS should
exceed the maximum derivative of the applied voltage, and the
statistical variation of RDDS should be low. The variations in
operating times and RDDS are compensated to some extent in
the newly designed switching relays. However, in order to minimize the adverse effect of such statistical variations and due to
the limited speed, the nominal making target is set slightly after
the voltage zero [8]. The maximum prestriking voltage will be
determined according to the statistical scatter of the contacts
closing speed [9]. Some laboratory test results about CB RDDS
and operating time deviations for industrial applications are presented in [10] and [11].
The purpose of this paper is to achieve minimum overvoltage
of the transmission line with minimization of prestriking voltage
and arcing time during the closure of a transmission line. The
newly developed switching relays function is in good agreement
with this goal but their function requires improvement. Because
after closing the first pole, the voltage of the second and third
poles of CB at the instant of closing (i.e., at 1/6 and 1/3 cycles) are not zero due to the coupling effect between phases of a
transmission line. Therefore, in this paper, a theoretical analysis
based on traveling waves, modal analysis, and Laplace transform is presented to find the optimum instant for closing the
poles of a CB, in order to reduce the prestriking voltage and
arcing time.
734
In general, the frequency dependence of the modal transformation matrix is small for overhead lines, but may be significant in the case of underground cables and untransposed vertical twin-circuit overhead lines [12]. In the next section, the
frequency dependence of the lines parameters is ignored to
simplify solving the modal domain equations in the analytical
studies. However, this dependency is considered in the simulation studies. Due to complexity and the time-consuming nature
of the theoretical analysis, only some cases are discussed using
the proposed analytical method, to validate the results obtained
by simulation studies.
The skin effect is considered in the PSCAD simulation, although its effect is negligible for frequencies below 5 kHz [1]
that is the concern of this paper. The corona effect is important if
the conductor voltage exceeds the corona inception voltage and
for fast front transients [1]. The steepness of the voltage wave
during line closing is not high, especially for the ZVC closing of
the first pole. The second and third pole voltages are also fairly
less than 1 p.u. just before energizing them. Therefore, taking
the corona effect into account will not change the paper results
considerably.
Considering the TL coupling effect and Gaussian distribution functions for closing time and RDDS of CB, the real value
of overvoltages, prestriking voltage, and arcing time are obtained, and the minimum requirements for RDDS are extracted.
Finally, the optimum sequence of closing, considering the operating time deviation of the CB, is proposed to be used in the
switchsync relay for various transmission-line configurations.
and current,
and , the matrices of modal voltage and current vectors
and
are related to phase matrices.
Using modal transformation matrices, the modal traveling-wave
equations can be written as follows [13]:
(3)
(4)
The eigenvalue analysis should be used to find the matrices
and
that diagonalize the
and
, respectively.
Laplace transform is used in this paper to solve the modal traveling waves equations.
It is assumed that all lines parameters have constant values,
and the line is lossless. Since the impedance and admittance
matrices per unit length of line are
and
and the
and
matrices are ignored in favor of
simplification of the theoretical analysis, the
and , which
make the
and
matrices diagonal, should be found. For
a simple case, if the line is completely transposed, the
and
are equal and so the
and
are equal consequently.
With and , as the self-inductance and self-capacitance perunit length of each phase of line and
and
as the mutual
ones, the surge impedance and velocity of wave in each of the
zero, positive, and negative modes are as follows [13]:
(5)
conditions,
and
are zero. Considering
and
for the sending and receiving ends, respectively, the
boundary condition for which the current at
is zero leads
to
(8)
where
is the mode traveling time constant which is calculated by dividing the line length by the velocity of the wave in
each mode. The boundary condition at
yields
735
(9)
Also from (8) and (9) and using
results in
(16)
(10)
, substituting
Using the KVL equation for phase A at
in (6) and expressing the voltage of phase A in the form
of mode voltages and using (10) results in
(11)
where
is
(12)
Finally, the induced voltages at line side of the next poles are
and mode voltages, i.e.,
extracted by using
(13)
where
and
The voltage at the end of the line for other phases can be
calculated in a similar way.
For a double-circuit transmission line, all matrices of
and are 6 6 and the modal transformation matrices
and
are 6 6 as well. Therefore, equations of the single-circuit
TL can be extended for this case too.
For theoretical confirmation of the simulation results, a
MATLAB program is developed based on the proposed modal
analysis and Laplace transform. Various cases are studied and
some of them are presented as sample cases.
are as follows:
(14)
Equations (12)(14), which are developed in this paper, are
used for calculating the optimum closing instants. Induced
voltage for an ideally transposed line is a particular situation in
which
(15)
736
Fig. 2. Simulated induced voltage on other phases after closing phase A for
a 400-kV flat tower TL. (a) Untransposed. (b) Transposed.
Fig. 3. Induced voltages on other phases after closing phase for a 400-kV
double-circuit line: (a) untransposed and (b) separately transposed.
According to the analytical results shown in Fig. 3, the optimum closing instant of phase is 2.73 and 2.6 ms for the
untransposed and separately transposed double-circuit lines, respectively. Moreover, the optimum instant of closing is 2.7 ms
for the double-circuit line where both circuits are transposed together. The PSCAD simulation results are quite similar to the
aforementioned results.
737
Fig. 4. Absolute value of the contact voltage and minimum and maximum prestriking voltages.
AND
According to (19), one can conclude that by having a determined operating time variation, the nominal RDDS of a CB
should be higher than a minimum value to achieve successful
controlled closing. On the other hand, one can realize from
Fig. 4 that the actual value of maximum prestriking voltage and
arcing time is increased and the minimum prestriking voltage
is not zero when the coupling voltage is not considered. To
minimize the prestriking voltage and, consequently, the adverse
effects on overvoltages, the actual value of ZVC should be
considered.
In order to illustrate this concept, the peak value of the
per-unit induced voltage at the line side of the CB second pole
is assumed
. Therefore, the maximum prestriking voltage
after occurrence of ZVC, considering the time delay of
is
, where
is obtained
by solving the following equations for the conventional and
proposed controlled closing algorithms, respectively:
(20)
For example, for
1.2 p.u.,
ms, and
0.25
p.u., the prestriking voltage for both methods is calculated by
solving (20). Especially in the case that
is about 0.9 ms, the
maximum prestriking voltage is about 0.29 p.u. for the conventional method. While considering the actual value of ZVC in
the proposed method, the maximum prestriking voltage is decreased to 0.13 p.u.
Following the aforementioned analytical results in the next
section, comprehensive simulation studies are performed to find
the minimum requirements of RDDS and CB operating time
deviation and optimum instants for closing the CB next poles
for various line configurations based on the actual value of ZVC.
The analytical results obtained in this paper are used to validate
the simulation results of the next section.
V. SIMULATION RESULTS
In this section, at first, the requirements for successful
controlled closing are obtained using simulation results of
Section III and the proposed equations are given in Section IV.
Then transmission-line closing simulation results for several
cases are presented. Finally, the improved sequence of contact
closing considering the operating time deviation of CB is
proposed to be used in switchsync relays for various transmission-line configurations.
738
Fig. 5. Minimum requirement for the RDDS versus arcing time for various
.
Fig. 7. Comparison of the prestriking voltages for the conventional and proposed methods.
Fig. 8. Overvoltages at the end of the line for phase C using the conventional
and proposed closing methods.
Fig. 7, for the extreme case in which is 0.9 ms, the maximum
prestriking voltage for the proposed controlled closing method
is decreased by about 0.15 p.u. in comparison to the conventional method. Therefore, arcing time is also decreased using
the proposed actual ZVC point.
To show the advantage of the proposed method more clearly,
phase C overvoltage levels for the TL of Fig. 10 using the
conventional and proposed closing methods for transposed and
untransposed cases are shown in Fig. 8. It should be noted that
phase B is closer to phase A in the line conductors configuration and, consequently, the coupling voltage in phase C for
the untransposed line is less than that for the transposed line.
Therefore, the advantage of the proposed method is more for
the transposed line. Fig. 8 clearly shows that the overvoltages
are reduced using the proposed method.
B. Single-Circuit Transmission Line
1) Uncompensated Flat Tower Transmission Line: A
400-kV, 400-km uncompensated flat tower transmission line,
similar to the one studied in Section III, is simulated. The
optimum closing instants considering the coupling effect for
different lengths of line and for the transposed and untransposed lines are analyzed. There is no significant difference
between the ZVC values of the third pole for transposed and
untransposed lines. Meanwhile, for the second pole, the ZVC
for the transposed line occurs about 0.10.15 ms earlier than
739
TABLE I
PROPOSED CLOSING INSTANTS FOR A STANDARD DEVIATION OF 0.2 ms
TABLE II
PROPOSED CLOSING TIME SEQUENCE FOR A 400-kV FLAT TOWER TL
Fig. 9. Optimum instants of closing for the transposed transmission line. (a)
Second pole. (b) Third pole.
740
TABLE III
PROPOSED CLOSING TIME-SEQUENCE ALGORITHM FOR SIMULTANEOUS
CLOSING BOTH LINES OF A 400-kV DOUBLE-CIRCUIT LINE
one is energized and closing both de-energized lines simultaneously). For these cases, a 400-kV widely used concentric
tower shown in Fig. 11. in the Appendix is simulated with
or without shunt compensation on both lines. Based on the
simulation studies, the results for the case of closing one line
when the other one is de-energized is similar to the results of
single-circuit line closing and, therefore, these results are not
presented in this section.
1) Closing One Line When the Other Line Is Energized: A
de-energized line in close proximity to an energized line has a
voltage induced on it through capacitive coupling. This voltage
depends drastically on tower configuration and in practical circumstances, the magnitude of induced voltage can be as high as
30% of the energized line voltage [17]. If the line is transposed,
the induced voltage is negligible. For untransposed delta or concentric towers, the induced voltage is less than 0.1 p.u. and can
be ignored as well. In these cases, the coupling voltage due to
first phase closing is much more than the coupling voltage of the
second line. Therefore, the results obtained for the single-circuit transmission line are applicable in this case as well. However, for vertical and especially flat towers and lines with a high
number of bundles, the induced voltage is considerable and can
be as high as 0.3 p.u.
The phase conductor arrangement of double-circuit lines is
an important factor for the electric- and magnetic-field levels
around them. The optimum phase arrangement of double-circuit lines for the electric- and magnetic-field minimization is
investigated in [18]. A double-circuit line with a flat configuration has the highest coupling effect for which symmetrical and
optimum arrangements are shown in Fig. 12.
For the symmetrical arrangement of Fig. 12(a), the voltages
of two sides of the de-energized line CB second pole have a
phase difference of about 10 and the line length does not affect
transients by preventing the CB prestrike. At first, the analytical method using modal transformation and inverse Laplace
transform is presented. Then, several simulations are performed
for transposed and untransposed lines and single- and doublecircuit lines with or without shunt compensation. The method
works very well for untransposed and transposed transmission
lines while the advantage of the proposed method is more for
the transposed lines. Some of the results are confirmed by comparing them with the analytical studies results. Moreover, the
minimum requirements for operating time deviation and the
RDDS of a CB are presented in order to have successful controlled closing.
Some of the obtained results are summarized as follows.
In order to reduce transmission-line closing overvoltages,
the coupling effect should be considered.
If the conventional method is used similarly for all TL configurations, it could result in up to 30% of TL extra overvoltages.
Proper instant for CB closing depends on TL configuration,
compensation level, transposition, and line length.
For successful controlled closing, the actual zero voltage
crossing point should be used.
It is proposed to adjust the closing instant of the CB second
pole earlier than the 1/6 cycle of the conventional-controlled switching method.
Required RDDS is assumed to be 1 p.u. in the conventional
method, whereas considering the coupling effect, it should
be more than 1.2 p.u. for some cases.
For a given operating time deviation of the CB and TL
configuration, the RDDS shall be higher than a specified
value to achieve the minimum prestriking voltages.
The overvoltages at the far end of the line are decreased
using the suggested method. Also, insulators with smaller
dimensions can be selected. Moreover, the proposed
method decreases the prestriking voltage and the CB
arcing time and, therefore, positively affects CB aging.
The second pole for the transposed line should be closed
earlier in comparison to the untransposed line.
The coupling effect for the transposed line is more in comparison to the untransposed line.
The coupling effect for the double-circuit line is more in
comparison to the single-circuit line.
For all types of uncompensated lines, the ZVC of the third
pole does not differ so much from 6.7 ms.
The shunt compensation does not affect
considerably,
whereas
may be more than 0.4 ms for the compensated
line.
At the most adverse situation,
could reach up to 1 ms.
This method is useful to be applied for aging transmission
lines and CBs to decrease the overvoltages on the aging
networks and to prevent prestriking and failure of the CB.
APPENDIX
The configuration of the transmission lines studied in this
paper are shown in Figs. 1012.
741
REFERENCES
[1] J. A. Martinez-Velasco, Power System Transients, Parameter Determination. Boca Raton, FL: CRC, Taylor & Francis Group, 2010.
[2] P. Mestas and M. C. Tavares, Comparative analysis of control
switching transient techniques in transmission lines energization
maneuver, presented at the Int. Conf. Power Syst. Transients, Lyon,
France, Jun. 47, 2007.
[3] M. Sanaye-Pasand, M. R. Dadashzadeh, and M. Khodayar, Limitation of transmission line switching overvoltages using switchsync relays, presented at the Int. Conf. Power Syst. Transients, Montreal, QC,
Canada, Jun. 1923, 2005.
[4] K. M. C. Dantas, D. Jr. Fernandes, W. L. A. Neves, B. A. Souza, and L.
C. A. Fonseca, Mitigation of switching overvoltages in transmission
lines via controlled switching, presented at the IEEE Power Energy
Soc. Gen. Meeting, Pittsburgh, PA, Jul. 2024, 2008.
[5] Control Switching Buyers Guide, 3rd ed. Ludvika, Sweden: ABB,
2009.
[6] C. H. Flurscheim, Power Circuit Breaker Theory and Design. Stevenage, U.K.: Peregrinus, 1985.
[7] U. Samitz, H. Siguerdidjane, F. Boudaoud, P. Bastard, J. P. Dupraz, M.
Collet, J. Martin, and T. Jung, On controlled switching of high voltage
unloaded transmission lines, in Proc. Elektrotech. Inf., Paris, France,
Aug. 2002, vol. 119, no. 12, pp. 415421.
[8] Y. Gual, G. Xu, W. Liu, X. Zheng, and N. Du, Controlling strategy and
implementation for synchronously closing 550 kV parallel capacitor,
in Proc. IEEE Conf. Mechatron. Autom., Changchun, Jilin, China, Aug.
912, 2009, pp. 50025007.
[9] K. Frohlish, C. Hoelzl, M. Stanek, A. C. Carvalho, W. Hofbauer, P.
Hoegg, B. L. Avent, D. F. Peelo, and J. H. Sawada, Controlled closing
on shunt reactor compensated transmission lines part I: Closing control device development, IEEE Trans. Power Del., vol. 12, no. 2, pp.
734740, Apr. 1997.
[10] U. Kriisi and K. J. Frohlich, Controlled switching-suitability check for
already-installed HVAC circuit breakers, in Proc. IEEE/PES Transm.
Distrib. Conf. Exhibit., Oct. 610, 2002, vol. 2, pp. 813817.
[11] H. Hamada et al., RDDS (rate of decrease of dielectric strength)
measurement for gas circuit breaker, in Proc. IEEE/Power Eng.
Soc. Transm. Distrib. Conf. Exhibit., Oct. 610, 2002, vol. 3, pp.
17551759.
[12] A. B. Fernandes and W. L. A. Neves, Phase-domain transmission
line models considering frequency-dependent transformation matrix,
IEEE Trans. Power Del., vol. 19, no. 2, pp. 708714, Apr. 2004.
[13] J. D. Glover, M. S. Sarma, and T. J. Overbye, Power System Analysis
and Design, 4th ed. Stamford, CT: Cengage Learning, 2007.
[14] A. El Hakimi, H. Le-Huy, and P. Viarouge, Semi-analytical method
for overhead transmission line transients simulation: Model for use in
real-time, in Proc. IEEE Conf. Elect. Comput. Eng., Montreal, QC,
Canada, Sep. 1995, vol. 1, pp. 4043.
[15] Y. Hase, Handbook of Power System Engineering. Hoboken, NJ:
Wiley, 2007.
[16] Transmission Line Reference Book: 345 kV and Above, 2nd ed. Palo
Alto, CA: Elect. Power Res. Inst., 1987.
[17] Transmission and Distribution Committee of the IEEE Power and Energy Society, IEEE Standard 524a-1993, 1993.
[18] G. Filippopoulos, D. Tsanakas, G. Kouvarakis, and J. Voyatzakis, Optimum conductor arrangement of compact lines for electric and magnetic field minimizationcalculation and measurement, The Power
Connection PFISTERER on-line publication list, May 9, 2010.
M. A. Atefi received the B.Sc. and the M.Sc. degrees in electrical engineering
from The University of Tehran, Tehran, Iran, in 2005 and 2007, respectively,
where he is currently pursuing the Ph.D. degree.
His research interests include power system protection and the study and simulation of electromagnetic transients in power systems and apparatus.
M. Sanaye-Pasand (M98SM05) received the Ph.D. degree from The University of Calgary, Calgary, AB, Canada, in 1998.
Currently, he is a Professor with the School of Electrical and Computer Engineering, University of Tehran, Tehran, Iran. His research interests include power
system protection, control, and transients.