Installation manual of

indoor units
TVR Series Variable Refrigerant
System

MVRC028 ~ MVRC140
MVRD022 ~ MVRD140
MVRH100 ~ MVRH140
MVRX028 ~ MVRX140
MVRS022 ~ MVRS071
MVRF175 ~ MVRF600

VRF-SVN02A-EN
2000-6298-02

Contents
Safety precautions 1
Preparing works before installation 1
Precautions for installation 1
Precautions for test running 1

Dimension of indoor units 2


Dimension of MVRC 2
Dimension of MVRD 2
Dimension of MVRH 3
Dimension of MVRX3
Dimension of MVRF4
Dimension of MVRS5

Indoor unit installation 6


Installation of MVRC 6
Installation of MVRX 8
Installation of MVRD/MVRS/MVRH 9
Installation of MVRF 12
Installation of EXV Box of indoor unit 14

Refrigerant pipe installation 15


Three principles for installation 15
Connecting refrigerant pipe with flared joint 15
Welding of refrigerant pipe 16
Blow wash on pipes 17
Leakage test and thermal insulation on refrigerant pipe 17

Drainpipe installation 19
Sustention of drainpipe 19
Connection of drainpipe 19
Centralized draining 20
Draining test and thermal insulation of drainpipe 21

Installation of power supply and communication cable 22


Specification for power supply cable

22

Specification for communication cable 22


Installation of power supply cable 23
Installation of communication cable 23

Installation of communication cable for wired controller 24


Installation of communication cable 24
Fasten 24

Installation of communication cable for centralized controller 25


Installation of communication cable 25
Fasten 25

Code setting of indoor units 26


Direction on failures 28

Safety precautions

Caution Carefully read this directory before installation and


usingit is important
This production obeys standards below
GB/T 18837-2002

JB 8655-1997

GB 4706.1-2005

This manual is for Trane Variable Refrigerant System Indoor unit. The
contents will change with the improvement of this equipmentwe will not
remind you again then.

Preparing works before installation

Installation and maintenance must

caustic gas (eg.:SO 2, H 2S). In

install, repair or transport the

such environment, equipments

equipments.

might be rusted and then

All electric works should be done

leakage will be caused.


(3) Locations with dust, vapor,

Improper installation will cause

lampblack or special spray,

water leakage, electric shock, fire

such as kitchen.

water to appear.

Perform leakage test after


installation to find out any leaking
point.

Precautions for test running

Do not operate wired controller


wireless remote controllercard
controller or centralized controller

Make sure that all ground wires

with wet hands. Do not let water

Make sure that the capacity of

have been linked to ground. Do not

get into them.

wires meets requirement, and the

link ground wires to lightning

wires are not loosen or damaged.

rod, telephone lines, gas pipes

When the location of installation is

or water pipes.

of refrigerant to exceed limitation in

case of a leakage of the refrigerant.


Ensure that the location of
installation is strong enough.

Do not strain or bend the cable of


wired controller or centralized
controller. Do not press buttons of

Do not strain power supply cables


or communication cables too tight.

must be kept to avoid the thickness

the controllers with sharp objects.

Do not put fingers or sticks into air

This system needs an independent

inlet or outlet when the system is

power supply.

running.

Install cables securely and avoid

Do not touch the refrigerant pipe

pressure on terminal board.

when the unit is running or stopped

Otherwise, equipment falling will

Otherwise, a power leakage or fire

minutes ago. It will cause

be caused.

accident might be caused.

unnecessary hurt because the pipe

Electric parts should be placed

might be too hot or too cold.

Precautions for installation

insulation to avoid condensation

technicians. Users should not

a small room, a good ventilation

might be caused.
(2) Locations with acid, alkali and

accident etc.

drainage. Pay attention to thermal

be performed only by licensed

by licensed electricians.

In these locations, an explosion

away from water and moisture. Do

Locations which do not suit for


installation:
(1) Locations with a possible
leakage of combustible gas
or materials which easily
evaporate , such as gasoline.

Do not switch off the power

not install wired controller or

supply immediately after the

centralized controller in locations

units stop running. Wait 5

with combustible or corrosive gas.

minutes before shutting off the

Follow this directory to install

power supply.Otherwise, water

drainpipe to insure a smooth

leakage might happen.

Dimension of indoor units


Dimension of MVRC

950mm

4-7.515

A 880
signal receiver

950mm

discharge
grill

790

B 880

suction grille

720
A/B dimension of installation hole on roof

width
840X840

drainpipe(25)

Model

MVRC028/036/045/056/071/090 MVRC100/112/125/140

240mm

285mm

Dimension of MVRD
D(length of air return plenum)

175

Model

A
B
C
D
(mm) (mm) (mm) (mm)

MVRD022/025/028/032/036 895

684

714

722

MVRD040/045/050/056

1110

894

924

932

MVRD063/071

1435 1187 1219 1227

MVRD080/090

1635 1284 1314 1322

C(distance between hanging holes)

MVRD100/112

1635 1393 1414 1422

A(total length)

MVRD125/140

1835 1563 1592 1600

4-10.515

B(length of airway)

depth 492
20
height
250

240
drainpipe
19.05

25 155

Dimension of indoor units


Dimension of MVRH
length of return airway 936

4-1240

distance between
hanging holes 570

length of airway 953


distance between hanging holes 1150
total length 1230
depth 750

58

319

252

height 400

40

25
drainpipe

Dimension of MVRX

280mm

673mm

4-12

25
drainpipe
243mm

distance between hanging holes K


width W

W idth W
(m m )

K
(m m )

905

800

M VRX071/090

1288

1185

M VRX112/125/140

1672

1568

M odel
M VRX028/036/056

Dimension of indoor units


Dimension of MVRF
MVRF175, MVRF210, MVRF250, MVRF300
depth 820

height 500

58

312

400

40

25
drainpipe

length of return airway 1035


4-1240

1215

lenght of airway 600


distance between hanging holes 1260
total lenght 1340

MVRF 400
58

gas pipe

height 680

depth 848

582

313

40

liquid pipe
25
drainpipe
length of return airway 1315

4-15

distance between
hanging holes 648

length of box 1514

length of airway 940


distance between hanging holes 1625
total length 1690

distance between
hanging holes 640

Dimension of indoor units

MVRF500MVRF600
depth 848

gas pipe

height 682

58

582

313

40

liquid pipe

25
drainpipe
4-15

length of return airway 1667

distance between
hanging holes 648

length of box 1864

length of airway 1062


distance between hanging holes 1976
total length 2043

Dimension of MVRS
A

(mm)

(mm)

(mm)

(mm)

MVRS022/028/036

955

687

715

725

MVRS045/056

1380

1112

1140

1150

MVRS071

1660

1392

1420

1430

D (length of air return box )

Model

4- 1018

190

262

B(length of airway)
C(distance between hanging holes)
A(total length)

10

depth 475

127

height 192
19
drainpipe

25

height of air
return box 187

Indoor unit installation

There are some fundamental


requirements of installation below:

Make sure that the ventilation is

Installation of MVRC
Schematic diagram for location of installation.

the indoor unit can reach all


Make sure that there is no
impediment around the air inlet

girder

girder

3.5m

1.0m

0.5m

0.5m

corners of the room.

0.3m

good enough, and air blew from

indoor unit

impediment

and outlet to insure a good


floor

ventilation.

securely.

Install in the limitation shown in the schematic diagram above. Or the

Make sure that the drainpipes work


Make sure that the location of
installation is strong enough to
withstand the weight of the indoor

efficiency of air conditioning will be influenced.

Unit hanging

hanging stick.

unit . Otherwise, damage and


injury will be caused.

Make sure that all hanging sticks


in use are strong enough to

Make sure that the distance between hanging sticks is 790 mm720 mm.
Hang the indoor unit onto the hanging sticks with nut, flat mat and elastic mat.
Ensure that the unit is installed horizontally. Then screw down the nuts of the
hanging sticks to avoid falling or vibration.

withstand the weight of the unit.

Measure the ceiling and mark the location. Perforate in the ceiling and set the

Choose a location which needs


hanging stick

shortest pipe and least work to


make piping connection more

nut

convenient.

indoor unit

elastic mat

flat mat

flat mat

nut

Decoration panel installation

Make sure that the indoor unit body is in the very center of the hole in the ceiling.
Remove the suction grille from the decoration panel:
1) Push the suction grille lever inward and lift up the lever side .Shown as
picture below.

Indoor unit installation


2) Detach the suction grille from the

the hooks on the sides of the indoor unit body. Shown as in the picture below:

decoration panel by lifting the

Not to let the louver motor lead wire get caught in the sealing material.

grille up approximately 45

4) Screw all 4 hex head screws(located directly beneath the latches) ,panel

Shown as picture below:

will rise. Shown as in the picture below:


5) Adjust the decoration panel by turning it to the arrowed direction, shown as
in the picture below, so that the ceiling opening is completely covered.

Remove the service cover on the


corner. Slide the service cover
outward to remove. Shown as
picture below:

Install the decoration panel


1) Set the decoration panel to the
indoor unit body by matching the

6) Tighten the screws until the thickness of the sealing material between the

position of the louver motor of the

decoration panel and the indoor unit body reduces to 3/16-5/16 inches.

decoration panel to the piping

Shown as picture below:

position of the indoor unit ,as in


the right picture.
2) Install the decoration panel to
the indoor unit body by hanging
the latch on the opposite side of
the louver motor and the latch
near the louver motor to the
hook of

indoor unit body.

Shown as in the right


picture:

Connect the wire of remote light and louver motor to the indoor controller.
Shown as picture below:

3) Hang the remaining 2 latches to

Indoor unit installation

A1B1A2B2

wire of the
remote light

louver motor
lead wire

MOTOR

REMOTE

indoor
controller

Suction grille installation

Make sure that the filter is set in the suction grille correctly and is not flexible.
Make sure that it is convenient to open the Suction grille, and then set it into
the panel.

Installation of MVRX
This type of indoor unit has two installation modesinstall on the ceiling and
install on the floor.

When installing on the ceiling

Make sure that, around the equipment, there is enough space for repairing,
70

as shown in the picture below:

500

500

500

500

300

Fix the hanging sticks. Make sure that they are securely installed.
Remove the suction grille, frame and hung board.
Install hung board to the nuts of hanging sticks.
Hang the equipment to the hung board and screw down the nuts. After
installation of refrigerant pipe and drainpipe, put the removed suction grille
and frame back.

Indoor unit installation

hung board

nut

hanging stick

flat mat

frame

hung board
flat mat

Suction grille

nut

When installing on the floor

Remove suction grille, frame.


Connect the refrigerant pipes and drainpipe.
Put the suction grille and frame back.

Installation of MVRD/MVRS/MVRH
0

50

15

00

RS
MV VRD
M
RH
MV

15

00

50

space around the epuipment

Installation of MVRD/MVRS

Make sure that, around the equipment, there is enough space for repairing.
As shown in the picture above.

Fix hanging sticks, and then hang the tache of the unit onto the hanging sticks.
Make sure that the hanging sticks are exactly connected to the unit, and the
tache of the unit are reliable.

Make a lean on the direction of draining. Then screw down the nuts of the
hanging sticks.

Installation of MVRH
Cautions

The unit should be installed in a place where the filter is easy to clean and
detachment
9

Indoor unit installation

If the length of hanging stick is more than 3m, it is necessary to take


precautions against shake.

Make sure that, around the equipment, there is enough space for repairing.

Unit hanging

hanging stick

are securely installed

nut1
flat mat
unit

Choose a location for hang, fix the hanging sticks and make sure that they

tache
nut2
nut3

Make sure that the tache of the unit are reliable


Hang the tache of the unit onto the hanging sticks between nut 1and 2
Use nut 2 to adjust the height of the unit;
Ensure that the unit is installed horizontally;
Screw down nut 1 and 3 of the hanging sticks to avoid falling or vibration.

Installation of air duct (for MVRD/MVRS/ MVRH)


Cautions

When designing air duct, make sure that the resistance of air duct equals to
static pressure outside the unit, otherwise the air volume would be too large
or too small;

Proper design of air duct can avoid noise efficiently;


Make the resistance of air duct equals to static pressure outside the
indoor unit by changing the speed of the units fan or adjust the resistance
of air duct.

Set heat insulation layer around the duct in order to cut down energy waste
and to prevent vapor from condensing;

Air duct should be steadily sustained by the iron hanging sticks. All joints
should be enveloped by airproof tape;

Keep the inlet of the units heat exchanger and the air return window more
than 1m.

The distance between the edge of air duct and the wall should be no less
than 150mm.

Installation of air return duct (for MVRD/MVRS)

When use bottom return, buy or make a folded canvas air duct as a connection
of air return plenum and air return window. It can be adjusted to the height of
the ceiling. When the unit is running, canvas air duct can prevent the jar of the
ceiling.

When use rear return, air return duct should be made. Connect air
10

Indoor unit installation


return duct to canvas air duct with rivet and connect the other end to air return
plenum. As shown in the picture below .
rear return:

bottom return:
rivet

rea air teturn plenum

bottom air return plenum


air
return
duct

air return window

canvas duct

canvas duct

rivet

air return window

Installation of air outlet duct (for MVRD/MVRS)

Air outlet duct usually has a section of rectangle or circle;


If the section is rectangle, the duct can be directly connected with the airway
of indoor unit with rivet;

If the section is circle, an additional transiting air duct should be set between
the air outlet duct and the airway of the indoor unit. The other side of the air
duct can be connected to air window directly. Shown as below:
hanging
stick
the indoor
transiting
unit
air duct
air return duct
canvas duct
air inlet window

air outlet duct


filter screen
air outlet window

Installation of air duct (for MVRH)

air outlet duct

static pressure box

11

indoor unit

air return duct

Indoor unit installation


Installtion of MVRF
Cautions

Please attach heat insulation material on the unit if the temperature inside the
ceiling higher than 30 and humidity higher than 80%.

An outdoor unit must match with only one MVRF unit, and the MVRF unit can
not share the outdoor unit with other kinds if indoor units.

Because of high noise, the installation should avoid noise and jar.
The unit need a special air outlet window, and this air outlet must keep away
from other unitsair inlet to avoid the veracity of the temperature sensor.

Make sure that there is enough space for maintenance


The unit should be installed in a place where the filter is easy to clean and
detachment.
800

tache (4)

air inlet

50
500

check hole
600600

Make sure that


around the
equipment, there is
enough space for
repairing

50

MVRF

2500

300

the service
space

air outlet

500

floor
the service space

Hannging the unit

Choose a location for hanging, fix the hanging sticks and make sure that they
are securely installed;

Make sure that the tache is reliable;


Hang the tache of the unit onto the hanging sticks between nut 1and 2;
Use nut 2 to adjust the height of the unit;
Ensure that the unit is installed horizontally;
Screw down nut 1 and 3 of the hanging sticks to avoid falling or vibration.

12

Indoor unit installation

hanging stick

unit

nut1
flat mat
tache

unit

nut1/2/3

nut2

hanging stick

nut3
MVRF175MVRF300

hole for
install
flat mat
MVRF400MVRF600

Cautions: keep the drainpipe and air inlet in a lower placeotherwise there
might be a leakage of water. Shown as below.

drainpipe

drainpipe

air inlet

air inlet

Installation of the duct (for MVRF)

Connect the air duct and the inlet/outlet flange of the unit with screw;
Airproof the flange of inlet and outlet with aluminum adhesive tape to avoid
air leakage.
insulation board

flange of outlet

flange of inlet

rd)

ownwa
air duct (d

air
inlet

MVRF

air
outlet

lid
canvas duct
wall

Cautions:
(1) Make the air inlet duct lean down to avoid seeper.
(2) Ensure that the air inlet can breathe in fresh air, otherwise the unit may
malfunction.
(3) Set heat insulation layer around the air duct in order to cut down energy
waste and to prevent vapor from condensing( thickness25mm).
13

Indoor unit installation


Installation of EXV Box of indoor unit
Cautions:

Follow the instruction on indoor unitEXV Box Application identification.


EXV Box must be placed vertically;
After EXV Box placed correctly, connect its inlet to the liquid pipe from the
outdoor unit and its outlet to the liquid pipe of the indoor unit.

It is suggested that the length of the pipe between EXV Box and the indoor
unit should be no more than 10m. 20m is the limitation.

Set heat insulation layer around EXV Box to prevent vapor from condensing.
Communication cable of the EXV Box should be connected to the indoor
controller.

Dimension of EXV Box:

distance between the 2 taches 245

width 75

communication cableconnected to
the indoor controller
outlet of EXV Box,
connected to indoor unit

height 165

inlet of EXV Box


connected to liquid pipe from outdoor unit

Schematic picture for installation of EXV Box:

A1 B1A2 B2

EXV Box

RESET

ON

S1

DIP

1 2 3 4 5 6 7 8

ON

S2

DIP

1 2 3 4 5 6

ON

to liquid
pipe of
outdoor
unit

NoteMVRF175~MVRF600 do not have an EXV Box.


14

S3

DIP

1 2 3 4 5 6 7 8

SLM

EXV

to gas
pipe of
outdoor
unit

communication cable of the


EXV Box(connected to the
indoor controller)

indoor
controller

Refrigerant pipe installation


Three principles of installation:
Reason

Dry

Rain water, etc. get into


the pipe

Countermeasure

Condensing water get into

Blow with N 2 vacuum drying

the pipe

Clean

Oxide formed when welding Replace O2 with N2 when welding


Dust from outside get into
the pipe

Not completely welded

Blow with N 2
Use proper welding rod and copper pipe
Follow basic operation rules of flared
joint.

Airproof

Air leakage at joint of 2


pipes

Exactly follow basic operation rules of


welding.
Exactly follow basic rules of pipe
connecting

Connecting refrigerant pipe with flared joint

Use pipe cutter to cut pipes. If the diameter of the pipe is too large, metal saw
can be used. Make sure that the sawdust will not get into the pipe;

Install the nut onto pipe before flaring;


Ensure that the flared pipe is concentric. Make sure that there is no damage
on the surface of flared end. Do not make any flaws such as burr, crack,
drape, etc.

Lubricate the surface of flared joint with grease in order to let nut go smoothly
through. It can avoid a pipe distortion

Screw down nuts with proper torsion. Do not break nuts because of screwing
too hardUse two wrenches to hold the pipe; Shown as below:

15

Refrigerant pipe installation

ared end A
(mm)

45
2
902

Dorsion

(mm)

14.2~17.2 N m

6.35

(144~176 Kgf cm)


32.7~39.9 N m

9.52
torsion wrench

Dimension of

Dimension

R 0.4 ~0.8

(333~407 Kgf cm)

8.7~9.1

12.8~13.2

normal wrench
49.5~60.3 N m

12.70

(504~616 Kgf cm)


61.8~75.4 N m

15.88

pipe joint in the indoor unit


nut of flared joint

(630~770 Kgf cm)


92.7~118.6 N m

19.05

(990~1210 Kgf cm)

16.2~16.6

19.3~19.7

23.1~23.7

Welding of refrigerant pipe

Weld on the horizontal line or a level below. Do not weld on a level above if
not necessary.
welding area

hand valve

N2
plug
pressure adjuster

pressure
hose

N2 pot

Pay attention to the direction and angle of liquid and gas pipe to avoid
refrigerant short circuit or oil cumulation.

When welding, fill the pipe with 0.20.5 Kgf/cm 2 N 2 .After welding, leave
the pipe naturally cooling or cool it with N2. Do not sprinkle cold water onto
pipe because it will cause crack by sudden cold.

Bend the pipe as less as possible, if the pipe must be bended, choose a large
bending radius;

Standard for distance between sustentions of horizontal pipe is shown in the


table below:
Diameter(mm)

< 20

25~40

50

Maximum distance (m)

1.0

1.5

2.0

16

Refrigerant pipe installation


Blow wash on pipes
Pipes must be blew by N2 after installation because during installation, there
must be some dust and moisture getting into pipes.
pressure adjuster

outdoor unit

A
gas pipe
liquid pipe

B indoor unit

leave the joints unconnected temporarily,


cover them with adhesive tape

Use N 2 to blow. There must be a pressure adjuster on N 2 pot.


Connect pressure adjuster and inlet of liquid pipe of outdoor unit with
pressure hose.

Block all the joints of liquid pipe except indoor unit A with the plugs.
Open N2 pot and set the pressure to 5Kgf/cm2.
Make sure that N2 goes through the liquid pipe which is connected to indoor
unit A. (Joints on the other side of indoor unit should be covered by adhesive
tape to avoid dust to be blown in.)

Blow wash
a. Block the liquid pipe of indoor unit A with some insulant in hand.
b. Remove the insulant quickly when the pressure is hard to resist and let
N2 eject out of the pipe( first blow wash).
c. Perform step a and b again (second blow wash).
d. Place a piece of clean cloth at the outlet, after N 2 ejects onto the cloth,
some dirt will be found on the cloth. If the cloth becomes wet, it means that
there is water in the pipe. Blow again until there is no dirt found on the cloth
and the cloth no longer becomes wet.

Redo steps above on indoor unit B.


After blow wash on liquid pipe, perform it again on gas pipe.

Leakage test and thermal insulation on refrigerant pipe

Step1:Perform leakage test on the indoor unit and the pipe after installation.
Charge the system with N 2 from liquid and gas pipe to stated pressure( unit
for R2228Kgf/cm 2 , unit for R410A38Kgf/cm 2 . step2:Maintain the
pressure for 24 hours, and then check whether the pressure goes down.
Make sure that the whole system is airtight;
17

Refrigerant pipe installation

Caution: If temperature of the air changes in the two steps, pressure shall be
justified with the equation below:
actual pressure pressure of step1 air temperature of step1
air temperature of step20.1Kgf/cm 2

Perform thermal insulation on gas and liquid pipe respectively after no


leakage on the pipe.
WRONG

CORRECT

Gas pipe and liquid


pipe must be insulated
respectively
liquid pipe

Insulate only gas pipe


(Cooling Only Model)
gas pipe
liquid pipe

gas pipe
control
cable

insulation

insulation

tie band

Pipe joint must be


insulated also

Insulate both gas and


liquid pipe
insulation

control gas
cable pipe

tie band

tie band

Support of insulate
material & pipe

insulation
liquid
pipe
control
cable

cuprum pipe

the joint
hast be
insulated

insulation

metal
support
arc washer

18

Drainpipe installation
Sustention of drainpipe

The diameter of drainpipe should be adapted to the capacity of the indoor


unit.

Make the drainpipe as short as possible and a lean must be set;


Maintain a steady lean to prevent water from flowing back;

Do not force on the joint when connecting drainpipe to indoor unit;


Space for sustention of horizontal pipe:
Type

Pipe diameter

Distance

Hard PVC pipe

25~40mm

<1.5m

Connection of drainpipe
Without water pump:

Horizontal drainpipe must have a lean no less than 1/100, and be supported
by hanging sticks

For MVRF/ MVRH, install a U trap at the end of drainpipe to prevent smelly
gas from getting into indoor unit

Do not install drainpipe from low to high, otherwise, water will flow back to the
indoor unit.

MVRS/MVRD
hanging stick
indoor unit

1~1.5m
horizontal drain
pipe(slope>1/100)

ceiling

MVRH/MVRF

1~1.5m

indoor unit

H50mm
clear terminal
of drainpipe
ceiling

H/2
U trap

19

hanging stick

horizontal drain
pipe(slope>1/100)

Drainpipe installation

With water pump:

Height of the drainpipe outside the indoor unit should be less than 500mm, or
there might be a leakage of water;

Horizontal drainpipe must have a lean no less than 1/100, and be supported
by hanging sticks
300mm

1~1.5m

hanging stick

20mm
500mm

horizontal drain pipe


(slope>1/100)

indoor unit
ceiling

centralized draining
Without water pump:
MVRS/MVRD

indoor unit

100

indoor unit

indoor unit

central drainpipe slope1/100

ceiling

MVRH/MVRF

indoor unit

100

indoor unit

indoor unit

central drainpipe slope1/100

ceiling

With water pump:

If more than 3 indoor units, please install the main exhaust pipe in front of the
indoor unit which is farthest away from the main drainpipe.

20

Drainpipe installation

1~1.5m

main exhaust pipe

hanging
stick

500
indoor unit

indoor unit
main drainpipe

indoor unit

central draipipe
slope1/100

ceiling

Draining test and thermal insulation of drainpipe

Perform draining test after drainpipe installation: Inject 2L water into the
indoor unit and make sure that the water flows out from drainpipe

If the indoor unit has a water pump, run the unit in cooling mode and check its
draining

Make sure that there is no water leakage


Perform thermal insulation to drainpipe after draining test.
MVRS/MVRD

MVRH/MVRF

drainpipe

21

drainpipe

Installation of power supply and


communication cable

Choose power supply cable and


communication cable under local

cable to communication port!

Communication cables must

or national rules;

be installed. Total length of

Protect all wires with wire tube;

communication cables should be

Use specified wires and make sure

less than 1000m.

that they are steadily connected.

Do not force on terminal block.

Do not connect communication


cables when power is on. Do not
pull out communication cables
when power is on. Do that after the

Specifications for

power is off.

power supply cable

signal, communication cables must

cable of indoor unit are shown as

be screened by STP.

below:

Choose STP which has a tighter


screen layer, as shown in the

voltage

power
ground
V supply cable wire

220V/50H Z 242/198

1.5mm2

1.5mm2

When total power is over


1700W ( e.g. units with electric
heater ), diameter of the
power supply cable should be
enlarged.

To avoid the interference of strong

Specifications for power supply

power supply

Distribution box should have

picture below.

Do not connect signal A with signal


B, as shown in the picture below.

When power supply and communication


cables are parallel,maintain a
necessary distance between
power supply and communication
cables.

a fuse and switch for each


indoor unit, considering the
capacity of each.

If a breaker is connected to more


than one indoor unit, the breaker
should have a larger capacity;

Specifications for
communication cable

AOutside protecting layer (PVC)


BScreen layer
CInsulation material
DConductorcopper

Indoor controller 1

Indoor controller 2

communication port

communication port

A1

B1

A1

Use 0.75-1.25 mm 2 polythene STP


as communication cable between
indoor and outdoor units;

Do not connect power supply


22

Connect A with B,wrong

B1

Installation of power supply and


communication cable
Installation of power supply cable
power supply
L1 L2 L3 N

L1 L2 L3 N
switch

L1 L2 L3 N
switch

fuse

fuse
RST N

RST N

switch

switch

switch
fuse

fuse

fuse

indoor unit 1

indoor unit 2

......

indoor unit i

Installation of communication cable


screen layer must be grounded with outdoor unit .

to central
control
devices
(optional)

Main outdoor controller

A1 B1 A2 B2 A B

Indoor controller 1

Indoor controller 2

communication port
A1
B1

communication port
A1
B1

Indoor controller i

communication port
J15
A1
B1

communication cable

Slave outdoor
controller 1
communication port
A2
B2

Slave outdoor
controller 2
communication port
A2
B2
communication cable should
be layed as bus structure.

communication cable

23

J15 of last
unit on main
bus should be
on

Installation of communication cable


for wired controller

A1B1A2B2

Installation of communication cable:


RESET

ON

S1

DIP

1 2 3 4 5 6 7 8

ON

S2

DIP

1 2 3 4 5 6

ON

S3

DIP

Indoor controller

S U N M O N T U E W E D T H U F RI STA

PM

ON/OFF

SLM

1 2 3 4 5 6 7 8

communication cable for


wired controller

Some communication cable for wired controller is offered with the indoor unit.
If not enough for installation, it can be bought from the franchiser.

Fasten

After the indoor unit is installed, educe communication cable from indoor unit;
Remove backboard from wired controller;
Fasten dead plate and backboard on the wall with tapping screw. The height
should be above 1.5m to prevent the controller from being reset by kids;

Connect indoor controller with wired controller by communication cable through


backboard;

Aim the cover of wired controller at the backboard. Push it, you will hear a
click, it means wired controller is steadily fixed on the wall.
(The dead plate is offered with wired controller)

communication cable

backboard tapping screw


dead plate
cover of wired controller
wall

24

Installation for centralized


controller

Installation of communication cable:


method 1:

transformer
input220VAC
output7.5VDC

power supply:
220V ~

communication cable
of centralized
controller
A1 B1 A2 B2 A B

centralized
controller

A1 B1 GND +
communication cable
of the indoor and
outdoor unit
A1 B1
the indoor
unit 1

A1 B1

A1 B1

the indoor
unit 2

the indoor
unit i

method 2:

A1 B1 A2 B2 A B
communication cable
of centralized
controller

power supply:
220V ~

communication cable
of the indoor and
outdoor unit
A1 B1

A1 B1

the indoor
unit 1

the indoor
unit 2

A1 B1

A1 B1 GND +

transformer
input220VAC
output7.5VDC

centralized
controller

the indoor
unit i

Fasten

Fix the centralized controller to the wall with tapping screw. Just as the installation of wired controller.
There is no communication cable with the centralized controller. Communication cable can be bought from franchiser.

25

Code setting of indoor unit


Instruction on code setting

IP address of indoor unit will be distributed by outdoor controller, so it is not


necessary to set it.

Capacity and model code was set when the production left factory, make sure
that they are correct.
A1 B1 A2 B2

RESET

S1
ON

S2
DIP

1 2 3 4 5 6 7 8

ON

DIP

1 2 3 4 5 6

capacity
code

S3
ON

DIP

Indoor controller

SLM

1 2 3 4 5 6 7 8

function
code

model
code

S1: Capacity code of indoor unit


Capacity

S1
1

MVR*022

MVR*025

MVR*028

MVR*032

MVR*036

MVR*040

MVR*045

MVR*050

MVR*056

MVR*063

MVR*071

MVR*080

MVR*090

MVR*100

MVR*112

MVR*125

MVR*140

26

Code setting of indoor unit


ExampleIf the unit is MVR*022then S1 is 00001000shown as below

S1
S3Model and function code
Number

Function

2
S3

Electric heater 2

Without electric
heater 2

With electric
heater 2

Electric heater 1

Without electric
heater 1

With electric
heater 1

S3

Model

MVRD

MVRS

MVRH

MVRC

MVRX

MVRH

MVRF

Example: MVRX, with 1 electric heater, then S3 is 00010100shown as below:

S3

27

Direction on failures
Solution of easy problems
Failure
The fan of the indoor unit
does not work.

The unit does not work.

Cool or warm wind is not


adequate.

Reason

Solution

Room temperature is higher (when heating) or lower


(when cooling) than set temperature.

Reset temperature of the room

When start running in heating mode, fan of indoor unit


Wait 4 minutes
does not work at first. System is avoiding to blow cold air in.
Power supply is off

Check and open power supply

timer on function is set.

Cancel the function or wait

Fuse of the circuit is burnt.

Change a new fuse

Filter is too dirty.

Clean or change the filter

Ventilation of the indoor unit is not good

Remove the blockage

Ventilation of outdoor unit is not good.


Voltage of battery is not adequate

Change battery

Battery is not correctly installed.

Reinstall correctly

Wireless remote controller is too far away from the unit.


(over 6 meters)

Get closer to the unit

Electric appliance such as fluorescent lamp is turning


on or off

Wait a second

Condensing water appears


on the panel of indoor unit.

Air moisture is too great.

Dehumidify

The indoor unit might stop


when the system is running
in heating mode.

System is defrosting.

Wait until defrosting is over

Fan stops working when


dehumidifying.

Do fan and compressor run or not when dehumidifying is Wait until system works normally
controlled by program. This phenomenon is normal.
again.

Wireless remote controller


does not display clearly or
does not work.

Solution of failure

If users cannot solve the problem, please contact with local repair department and record the failure code displayed
on wired controller or wireless remote controller:

If failure happens when wireless remote controller is being used, the defrost light of remote signal receiver on the indoor
unit will glitter (once per second, 2.5 seconds between groups):

Glitter times

Failure

Glitter times

Failure

Failure on indoor temperature sensor

Failure on temperature sensor at inlet

Failure on temperature sensor at middle of the heat


exchanger

Failure on temperature sensor at outlet

Failure on communication between indoor and


outdoor unit

Conflict between running modes

28

Direction on failures

If failure happens when wired controller is being used, failure codes will display on wired controller. Failure codes
are shown as below:
Failure code
Indoor unit

Master unit

Failure
00

Failure on communication between indoor and outdoor unit

01

Failure on sensor of indoor unit

02

Conflict between running modes

10

Fire alarm

11

Failure on sensor of outdoor unit

12

Compressor or fan overloading

13

Compressor contactor conglutination

14

Failure on parameter overtop the set area

15

General failure

16

System failure

Note: When failure happens on the 1# slave unit, the failure code will display 2 on wired controller. When failure
happens on the 2# slave unit, the failure code will display 3 on wired controller. For example: 33 is the failure of
compressor contactor conglutination which happens on the 2# slave unit.

If failure happens when centralized controller is being used, failure code will display on centralized controller.
Failure code is shown as below:
Code

Meaning

Code

Meaning

High pressure exceeds limitation

20

Overloading of compressor 3

Overloading of fan

21

Failure on sensor of low pressure

22

Failure on sensor of high pressure

Fire alarm

23

24

Conglutination on contactor 1

25

Conglutination on contactor 2

26

Conglutination on contactor 3

27

Slave unit 1 failure in communication

TH1 failure

28

Slave unit 2 failure in communication

TH2 failure

29

Slave unit 3 failure in communication

10

TH3 failure

30

11

TH4 failure

31

Memory failure

12

TH5 failure

32

Refrigerant leakage

13

TH6 failure

33

Four-way valve failure

14

TH7 failure

34

Little superheat

15

TH8 failure

35

Low pressure exceeds limitation

16

Failure on sensor 1 of fan

36

Exhaust temperature exceeds limitation

17

Failure on sensor 2 of fan

37

Environment temperature exceeds limitation

18

Overloading of compressor 1

38

No communication

19

39
System error
Overloading of compressor 2
Failure
on
communication
between
indoor
and
outdoor
unit.132
means
Failure
on
communication between 32#
101~164 indoor unit and the outdoor unit.
29

Trane
www.trane.com
For more information, contact your local district
office

Literature Order Number

VRF-SVN02A-EN

Date

Sep 2008

Supersedes

New

Stocking Location

China

TRANE has a policy of continuous product data and product improvement and reserves the right to
change design and specifications without Note.