38ARZ/ARD

Commercial Air-Cooled Split System


Sizes 007 028
With 40RM007-034
6 - 25 Nominal Tons - 60Hz

Product Data
The 38ARZ/ARD condensing units with scroll compressors match Carriers 40RM
indoor-air

handlers for a wide selection of dependable commercial cooling solutions.

Carriers air-cooled split systems:


provide a logical solution for
commercial needs
have a rugged,
dependable
construction

Features/Benefits
These
dependable
split
systems
match
Carriers
indoor-air handlers and directexpansion coils with outdoor
condensing units for a wide
selection
of
commercial
cooling solutions.
Up to 11.0 EER

The high efficiency split commercial split


system combining the 38ARZ/ARD
outdoor condensing unit with 40RM air
handling unit can save 20-27% of energy
consumption.

Constructed for long life

The 38ARZ (single circuit, scroll


compressor) and 38ARD (dual circuit,
scroll compressor) models are designed and
built to last. The copper tube-aluminum fin
outdoor coil construction provides years of
trouble-free operation. Where conditions
require, a range of Enviro-Shield coil
protection options are available. Cabinets
are constructed of prepainted galvanized
steel, delivering unparalleled protection
from the environment. Inside and outside
surfaces are protected to ensure long life,
good looks, and reliable operation. Safety
controls are used for enhanced system
protection
and
reliability.

Efficient operation

Building owners will appreciate the high unit EERs


(Energy Efficiency Ratios) offered by the 38AR units.
These units provide greater efficiency than similar
units in the marketplace, which translates into yearround operating savings.

Controls for performance dependability

The 38AR condensing units offer the building owner


operating controls and components designed for
performance dependability. The highly efficient
compressors are engineered for long life and
durability. The compressors include overload
protection and vibration isolation for quiet operation.
The high pressure switch protects the entire
refrigeration system from abnormally high operating
pressures. A low pressure switch protects the system
from loss of charge.
The 38ARD014-028 units feature 2 compressors and 2
refrigerant circuits that provide continuous air
conditioning and design flexibility.
All units include a crankcase heater to eliminate liquid
slugging at start-up. The latest safety standards for
38AR units are UL, compliant.

Innovative Carrier 40RM packaged air


handlers are custom matched to 38AR
condensing units

The 40RM Series has excellent fan performance,


efficient direct-expansion (DX) coils, a unique
combination of indoor-air quality options, and is easy
to install. Its versatility and state-of-the art features
help to ensure economical performance of the split
system both now and in the future.

Indoor-air quality (IAQ) features


The unique combination of IAQ features in the 40RM
Series air handlers help to ensure that only clean,
fresh, conditioned air is delivered to the occupied
space.
Direct-expansion (DX) cooling coils prevent the buildup of humidity in the room, even during part-load
conditions. Unit sizes of 10 tons and larger feature
dual-circuit coils for improved temperature control.
Standard 1-in. aluminum washable filters remove dust
and airborne particles from the occupied space for
cleaner air.

The pitched, non-corroding drain pan can be adjusted


for a right-hand or left-hand connection to suit many
applications and provide positive drainage and prevent
standing condensate.
Economy The 40RM Series packaged air handlers
have low initial costs, and provide reduced installation
expense and energy-efficient performance.
Quick installation is ensured by the multipoise design.
Units can be installed in either the horizontal or
vertical configuration without modifications. Fan
motors and contactors are prewired and thermostatic
expansion valves (TXVs) are factory-installed on all
40RM models.
High efficiency, precision-balanced fans minimize air
turbulence, surging, and unbalanced operation, cutting
operation expenses.
Rugged dependability The 40RM series units are
made to last. The die-formed galvanized steel panels
ensure structural integrity under all operating
conditions. Galvanized steel fan housings are securely
mounted to a galvanized steel fan deck. Rugged
pillow-block bearings (40RM014-034) are securely
fastened to the solid steel fan shaft with split collets
and clamp locking devices. Smaller unit sizes have
spider-type bearings.
Coil flexibility Model 40RM directexpansion coils
have galvanized steel casings; inlet and outlet
connections are on the same end. The coils are
designed for use with R-22 refrigerant and have 3/8-in.
diameter copper tubes mechanically bonded to
aluminum sine-wave fins.
The coils include matched, factoryinstalled
thermostatic expansion valves (TXVs) with matching
distributor nozzles.
Easier installation and service
The multipoise design and component layout ensures
quick unit installation and operation. Units can be
converted from horizontal to vertical operation by
simply repositioning the unit. Drain pan connections
are duplicated on both sides of the unit. The filters,
motor, drive, TXVs, and coil connections are all easily
accessed by removing side panels.

Model number nomenclature

38AR Z

007

Type
38ARCommercial AirCooled Condenser

--

S - High Ambient
Packaging
1 - Standard

Z-Single Circuit
D- Dual Circuit
Nominal Capacity in-Tons
007 - 6 Tons
008 - 7.5 Tons
012 - 10 Tons
014- 12 Tons
016 - 14 Tons
024 - 20 Tons
028 - 25 Tons
-- - Not Used

Design Series
0 - Original Design

Voltage
2 380360
5 208/230360
6 460360

Fin Type
-- - Standard Bare Fins
C- Cu/Cu Coil
P- Pre-Coated Blue Fins

Table of Contents
38ARZ/ARD

Page.

Features/Benefits.
ModelNumber Nomenclature..
Physical Data.
ARI Capacity ratings 60Hz .
Options and accessories .
Base Unit Dimensions..
Performance data
Electrical Data
Application Data
Typical Wiring Schematic.

1
3

7-9

10-17
18

19
20-26

Model number nomenclature..


Physical Data.
Options and accessories
Base Unit Dimensions..
Selection procedure.
Electrical Data
Typical piping and wiring
Application Data

27

28

29-31

32-41

42-46

47-53

54-57

58-61

Guide Specifications 38ARZ007-012..


Guide specifications 38ARD014-028 ..
Guide specifications 40RM

62,63
64,65
66,67

40RM

Guide Specifications

Physical Data English


UNIT 38AR
NOMINAL CAPACITY (Tons)

007
6

OPERATING WEIGHT (lb)


Aluminium Coils (Standard)
Copper Coils (Optional)
SHIPPING DIMENSIONS (in) (W X H X D)
COMPRESSOR
Qty
Oil Charge (oz)
REFRIGERANT TYPE *
**
Operating Charge, Typical (lb)
Shipping Charge (lb)
FINISH
CONDENSER FAN
QtyRPM
Diameter
Nominal Air Flow (Total CFM)
Watts (Total)
Motor Horsepower,
CONDENSER COIL (Qty)
Face Area (sq ft Total))
RowsFins/in.
Storage Capacity (lb)***
CONTROLS
Pressurerestart Settings (psig)
High Cutout
Cut-in
Low Cutout
Cut-in

300
352

88
12

2850
5400
341
1/8

117
17.3

ARZ
008
7 1/2
383
484
(59.2X45.5X39)
1
90

012
10

014
12 1/2

430
531

676
822

R22

2
217
34.2

23/circuit

28/circuit

3.1

Gray
Propeller Type
21075
26 in
11,000
1460
1/2

21100
22 in
6500
570
1/4
1/4
29.2

024
20

740
764
886
904
(72.6X44.25X41.7)
Scroll
2
60(ea)
85(ea)
110(ea)

110

20 22
2.0

ARD

016
15

028
25
1279
1532
96.54954.3
111 (ea)
17.9 /circuit
3.1

2...1100
30
14500
1500
1
50.4
3... 16
-

29.2
315
48
428 10
320 20
27 4
44 7

428 10
320 20
27 3
44 5
0

DISCHARGE GAS THERMOSTAT ( F)


Cutout
Cut-in
PRESSURE RELIEF
Location
Tempreature
PIPING CONNECTION
QtySuction
QtyLiquid
Hot Gas Stub

---

270 9
190 13
Suction Line
200

11 1/8
1 3/8

11 1/8
1 3/8

11 3/8
1 1/2

*Unit is factory-supplied with holding charge only.


**Typical operating charge with 25 ft of interconnecting piping.
***Storage capacity of condenser coil with coil 80% full of liquid R-22 at 95 F.

--Liquid Line
200
21 3/8
2 1/2
3/8

21 3/8
2 5/8
-

ARI Capacity ratings 60Hz

CONDENSING UNIT

SYSTEM**
EER
IPLV
Net Cap. (Btuh)
AIR
AIR40RM007
HANDLER/
HANDLER/ INDOOR
INDOOR COIL
COIL
N/A
69,000
11.0
Net
Net Cap.
Cap. (Btuh)
(Btuh)
40RM008
71,000
N/A
10.8
40RM007
69,000
69,000
40RM007
11.0
11.0
40RM007
87,000
10.6
N/A
40RM008
40RM008
71,000
71,000
40RM008
90,000
10.6
N/A
87,000
87,000
40RM007
40RM007
10.6
10.6
40RM012
93,000
10.4
N/A
40RM008
40RM008
90,000
90,000
10.6
10.6
40RM012
118,000
N/A
10.3
40RM012
10.4
93,000
40RM012
93,000
10.4
40RM014
123,000
10.4
N/A
40RM012
40RM012
118,000
118,000
10.3
10.3
40RM012
9.9
135,000
9.7
10.4
40RM014
123,000
40RM014
123,000
10.4
40RM014
145,000
10.5
10.9
40RM012
40RM012
135,000
135,000
9.7
9.7
40RM016
10.8
11.0
152,000
10.5
40RM014
145,000
10.5
40RM014
145,000
40RM014
176,000
10.0
10.4
40RM016
40RM016
152,
152,
10.8
10.8
40RM016
187,000
10.2
10.5
40RM014
176,000
10.0
40RM014
176,000
10.0
40RM024
194,000
10.1
10.2
40RM016
40RM016
187,000
187,000
10.2
10.2
222,000
9.5
10.1
40RM016
40RM024
40RM024
194,000
194,000
10.1
10.1
9.8
232,000
9.5
40RM024
40RM016
40RM016
222,000
222,000
9.5
9.5
242,000
40RM028
9.6
9.9
40RM024
232,000
9.5
9.5
40RM024
232,000

N/A
305,000
40RM028
242,000
242,000 9.8
40RM028
40RM028
333,000
10.3 N/A
40RM034

AIR HANDLER/ INDOOR COIL

CONDENSING
CONDENSING UNIT
UNIT
38ARZ007
38ARZ007
38ARZ007
38ARZ008
38ARZ008
38ARZ008
38ARZ012
38ARZ012
38ARZ012
38ARD014
38ARD014
38ARD014
38ARD016
38ARD016
38ARD016
38ARD024
38ARD024
38ARD028

CONDENSING UNIT ONLY***


Net Cap. (Btuh)
EER
IPLV
CONDENSING
CONDENSING UNIT
UNIT ONLY
ONLY
IPLV 72,000
Net Cap. (Btuh)
12.4
N/A IPLV
72,000
72,000
100,000

12.7

12.4
12.4
N/A

100,000
100,000
133,000
12.4

12.7
12.7
N/A

133,000
133,000
12.5
158,000

12.4
12.4
15.1
12.5
12.5

9.9
9.9
10.9
158,000
10.9
158,000
11.0
11.0
204,000
11.9
10.4
10.4
10.5
10.5
204,000
204,000
10.2
10.2
259,000
11.2
10.1
10.1
9.8
9.8
259,000
259,000

318,000
10.1

13.9
11.9

13.1
13.1
N/A

ASHRAE American Society of Heating, Refrigeration and Air Condition Engineers


EER Energy Efficiency Ratio
IPLV Integrated Part Load Value
N/A Not Applicable
SST Saturated Suction Temperature
*Air Conditioning and Refrigeration Institute.
**Ratings in accordance with ARI Standard 360-2000.
***Condensing unit only ratings are at 45 F SST and 95 F entering-air temperature.

UNIT
38AR
Z007
Z008
D014
Z012D014
D014
D016
D024
D028

SOUND
RATING
(60Hz)
dB (A)
80.0
84.0
85.0
86.9
87.5
88.0
94.8

OCTAVE
OCTAVE BANDS
BANDS
OCTAVE BANDS

63

125

250

500

1000

2000

4000

8000

71.5
84.1
88.7

76.8
84.5
85.4
90.9
90.9
90.9
91.4

75.3
80.4
81.7
86.1
86.1
86.1
88.1

74.0
78.6
80.9
83.1
83.4
83.8
85.8

73.9
77.2
82.1
84.0
84.5
84.5
86.4

74.1
76.9
76.2
73.5
76.6
79.2
81.5

73.5
78.8
73.6
71.7
73.2
74.3
75.2

64.0
72.5
67.1
66.7
63.5
65.5
67.4

NOTES:
1. 38ARZ unit is in accordance with ARI 270-95 Sound Rating of Unitary Equipment.
2. Estimated sound power levels, dB re 1 Picowatt. 38ARD014-028 and 38AKS data is based upon a limited amount of actual testing with the estimated sound power
OCTAVE
OCTAVEand
BAND
BAND
CENTER
CENTER
FREQUENCY
FREQUENCY
data being generated from this data in accordance with ARI Standard 370 for large outdoor refrigerating
air-conditioning
equipment.
Since this data is estimated, the
dB(A)
dB(A)
sound power levels should not be guaranteed or certified
as being the actual sound power levels.
3. The acoustic center of the unit is located at the geometric center of the unit.

40RM007
40RM007
40RM008
40RM008
40RM012
40RM012 CFM
UNIT
40RM014
40RM014
40RM007
40RM016
40RM016 2400
40RM008
40RM024
40RM024 3000
40RM012
40RM028
40RM028 4000
40RM014
40RM034
40RM034 5000
40RM016
6000
40RM024
8000
40RM028
10000
40RM034
12000

ESTIMATED SOUND POWER LEVELS (Lw) 40RM007-034

dB(A)
86.3
88.3
91.6
91.1
92.7
96.4
96.2
98.5

63
93.2
95.3
98.6
97.3
98.9
102.6
102.5
104.7

125
89.2
91.3
94.6
93.3
94.9
98.6
98.5
100.7

OCTAVE BAND CENTER FREQUENCY


250
500
1000
85.2
84.2
80.2
87.3
86.3
82.3
90.6
89.6
85.6
89.3
90.3
84.3
90.9
91.9
85.9
94.6
95.6
89.6
94.5
95.5
89.5
96.7
97.7
91.7

2000
78.2
80.3
83.6
82.3
83.9
87.6
87.5
89.7

13.9
13.9

13.1

LEGEND

SOUND LEVELS, dB 38AR UNITS

15.1
15.1

4000
74.2
76.3
79.6
78.3
79.9
83.6
83.5
85.7

Options and accessories


38AR, options

Enviro-Shield condenser options offer pre-coated coils that provide protection in mild coastal
environments. Several options are available to match coil protection to site conditions for optimum durability.
See table below. Consult your Carrier representative for further information.
Non-fused disconnect switch to remove power locally at the condensing unit. This switch also includes a
power lockout capability to protect the service person. This lockout switch saves the service person time and
effort because there is no need to access a distant disconnect switch while servicing the unit.
Carriers line of thermostats provide both programmable and non-programmable capability with the new
Debonair line of commercial programmable thermostats. The Commercial Electronic thermostats provide
7-day programmable capability for economical applications.
PremierLink Controller is a field retrofit split system control compatible with the Carrier Comfort Network
(CCN) and other building automation systems (BAS). This control is designed to allow users the access and
ability to change factory-defined settings thus expanding the function of the standard unit.

CONDENSER COIL OPTIONS


COPPERTUBECOILS
WITHENVIROSHIELDOPTION
AlFins(StandardCoils)
CuFins
WITH ENVIRO
AlFins,PreCoated
Al Fins (Standard Coils)
LEGEND Cu Fins
Al Aluminum
Cu Copper

Standard
X

Standard

ENVIRONMENT
MildCoastal

ModerateCoastal
X
Moderate Coastal

Base Unit Dimensions 38ARZ 007 012


Approximate
Shipping
Weight
Approximate
Shipping
Weight
38AR
38ARZ
Size Size
With Standard Al/Cu Coil With Optional Cu/Cu Coil
KG
LB
KG
LB
007
154
339
178
392
008
192
422
238
524
012
213
467
259
570

Approx.
Shipping
Dimensions
Approx.
Shipping
Dimensions
( Ax xCB) x C )
(AxB
mm
inch
(1504X1157X992)
(59.2X45.5X39)
(1504X1157X992)
(59.2X45.5X39)

Base Unit Dimensions 38ARD 014 024

38ARD Size
014
016
024

Approximate Shipping Weight


With Standard Al/Cu Coil With Optional Cu/Cu Coil
KG
LB
KG
LB
357
785
423
931
386
849
452
994
397
873
461
1014

Approx. Shipping Dimensions


(AxBxC)
mm
inch
(1844X1124X1058)

(72.6X44.25X41.7)

Base Unit Dimensions 38ARD 028

38ARZ
size
028

Approximate shipping weight


With standard Al/Cu Coil With optional Cu/Cu Coil
KG
LB
KG
LB
580
1279
695
1532

Approx. shipping dimensions


(ABC)
mm
Inch
245113801282 96.554.350.5

Performance data
CONDENSING UNIT RATINGS
38ARZ007
SST (F)
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

38ARZ008
SST (F)
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

Air Temperature Entering Condenser (F)


80
85
95
100
105
53.6
52.3
49.4
48.0
46.5
4.24
4.49
5.02
5.31
5.60
101.0
106.0
115.0
120.0
125.0
59.1
57.6
54.6
53.0
51.5
4.33
4.57
5.10
5.39
5.69
102.0
107.0
117.0
122.0
126.0
64.9
63.3
60.1
58.4
56.7
4.42
4.67
5.20
5.49
5.79
104.0
109.0
118.0
123.0
128.0
71.0
69.3
65.8
64.1
62.3
4.53
4.77
5.31
5.60
5.90
106.0
110.0
120.0
125.0
129.0
77.4
75.6
71.9
70.1
68.2
4.65
4.89
5.43
5.72
6.02
107.0
112.0
122.0
126.0
131.0
84.2
82.3
78.4
76.4
74.3
4.78
5.03
5.56
5.86
6.16
109.0
114.0
123.0
128.0
133.0

38ARZ012
115
43.6
6.24
135.0
48.3
6.33
136.0
53.4
6.43
138.0
58.7
6.55
139.0
64.3
6.68
141.0
70.2
6.81
142.0

SST (F)
25
30
35
40
45
50

38ARD014
Air Temperature Entering Condenser (F)
80
85
95
100
105
73.9
71.7
67.0
64.6
62.1
5.81
6.14
6.84
7.21
7.58
98.6
104.0
114.0
118.0
123.0
82.0
79.7
74.9
72.4
69.9
5.88
6.21
6.90
7.28
7.65
99.6
104.0
114.0
119.0
124.0
90.4
88.0
83.0
80.4
77.8
5.98
6.31
7.02
7.40
7.78
101.0
106.0
115.0
120.0
125.0
99.2
96.7
91.4
88.7
85.9
6.09
6.43
7.14
7.53
7.92
103.0
107.0
117.0
122.0
126.0
109.0
106.0
100.0
97.4
94.5
6.22
6.56
7.28
7.68
8.07
104.0
109.0
119.0
123.0
128.0
118.0
116.0
110.0
107.0
104.0
6.36
6.70
7.43
7.83
8.23
106.0
111.0
120.0
125.0
130.0

115
57.0
8.36
133.0
64.7
8.46
134.0
72.4
8.59
135.0
80.3
8.74
136.0
88.6
8.91
138.0
97.2
9.09
139.0

SST (F)
20
25
30
35
40
45
50

10

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

Air Temperature Entering Condenser (F)


80
85
95
100
105
102.0
99.3
93.8
90.9
88.1
8.04
8.38
9.13
9.55
9.95
101.0
106.0
116.0
121.0
126.0
112.0
109.0
103.0
99.8
96.7
8.26
8.60
9.31
9.65
10.05
103.0
107.0
117.0
12.02
127.0
122.0
119.0
113.0
109.0
106.0
8.52
8.85
9.55
9.95
10.35
104.0
109.0
118.0
123.0
128.0
133.0
130.0
123.0
119.0
115.0
8.81
9.15
9.85
10.25
10.55
106.0
110.0
120.0
125.0
129.0
144.0
141.0
133.0
130.0
126.0
9.12
9.45
10.15
10.55
10.85
108.0
112.0
122.0
126.0
131.0
156.0
152.0
145.0
141.0
137.0
9.45
9.85
10.55
10.85
11.25
109.0
114.0
123.0
128.0
133.0

115
81.9
10.85
136.0
90.3
10.95
136.0
99.0
11.15
137.0
108.0
11.35
139.0
118.0
11.65
140.0
128.0
12.05
142.0

Air Temperature Entering Condenser (F)


80
85
95
100
105
102.0
99.1
93.2
90.3
87.3
9.04
9.58
10.80
11.40
12.10
103.0
108.0
118.0
123.0
128.0
114.0
111.0
105.0
102.0
98.8
9.09
9.64
10.90
11.50
12.20
103.0
108.0
118.0
123.0
128.0
127.0
124.0
117.0
114.0
110.0
9.14
9.70
10.90
11.50
12.20
103.0
108.0
118.0
123.0
128.0
140.0
137.0
130.0
126.0
123.0
9.19
9.75
11.00
11.60
12.30
103.0
108.0
118.0
123.0
128.0
155.0
151.0
144.0
140.0
136.0
9.81
9.26
11.00
11.70
12.30
108.0
103.0
118.0
123.0
128.0
170.0
166.0
158.0
154.0
150.0
9.37
9.90
11.10
11.70
12.40
103.0
108.0
118.0
123.0
128.0
186.0
182.0
173.0
169.0
164.0
9.55
10.10
11.30
11.90
12.60
104.0
109.0
119.0
124.0
129.0

115
81.1
13.50
138.0
92.2
13.60
138.0
103.0
13.70
138.0
115.0
13.70
138.0
128.0
13.80
138.0
141.0
13.90
138.0
155.0
14.00
139.0

Performance data (cont)


38ARD016
SST (F)
20
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

38ARD024
SST (F)
20
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

Air Temperature Entering Condenser (F)


80
85
95
100
105
141.0
137.0
129.0
124.0
120.0
12.01
12.60
13.70
14.30
14.90
101.0
105.0
115.0
120.0
125.0
156.0
152.0
143.0
138.0
133.0
12.40
12.90
14.00
14.60
15.20
102.0
107.0
116.0
121.0
126.0
171.0
166.0
157.0
152.0
147.0
12.70
13.20
14.30
14.90
15.50
104.0
108.0
118.0
123.0
127.0
187.0
182.0
172.0
166.0
161.0
13.10
13.60
14.70
15.30
15.90
105.0
110.0
119.0
12.04
129.0
203.0
198.0
187.0
181.0
176.0
13.50
14.00
15.10
15.70
16.30
107.0
112.0
121.0
126.0
130.0
221.0
215.0
204.0
198.0
192.0
13.90
14.50
15.60
16.10
16.70
109.0
114.0
123.0
127.0
132.0
239.0
233.0
221.0
215.0
208.0
14.40
14.90
16.10
16.70
17.20
111.0
116.0
125.0
129.0
134.0

115
110.0
16.10
135.0
123.0
16.40
136.0
136.0
16.70
137.0
150.0
17.10
138.0
164.0
17.50
140.0
179.0
17.90
141.0
195.0
18.40
143.0

Air Temperature Entering Condenser (F)


80
85
95
100
105
184.0
179.0
170.0
165.0
160.0
16.20
17.00
18.50
19.40
20.20
105.0
110.0
119.0
124.0
129.0
202.0
197.0
186.0
181.0
176.0
16.80
17.50
19.00
19.80
20.60
107.0
112.0
121.0
126.0
131.0
220.0
214.0
203.0
197.0
191.0
17.30
18.00
19.50
20.30
21.10
109.0
113.0
123.0
127.0
132.0
239.0
233.0
220.0
214.0
208.0
18.00
18.60
20.10
20.80
21.60
111.0
116.0
125.0
129.0
134.0
259.0
253.0
239.0
232.0
225.0
18.70
19.30
20.70
21.50
22.20
113.0
118.0
127.0
131.0
136.0
280.0
273.0
259.0
252.0
244.0
19.40
20.10
21.50
22.20
22.90
116.0
120.0
129.0
134.0
138.0
302.0
295.0
280.0
272.0
264.0
20.20
20.90
22.30
23.00
23.70
118.0
123.0
132.0
136.0
140.0

115
148.0
21.70
139.0
163.0
22.20
140.0
179.0
22.70
141.0
194.0
23.20
143.0
211.0
23.80
145.0
229.0
24.50
147.0
247.0
25.20
149.0

38ARD028
SST (F)
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

Air Temperature Entering Condenser (F)


80
85
95
100
105
186.8
202.7
228.4
244.6
253.2
36.61
33.11
26.87
26.57
25.45
136.4
129.2
122
113
109.4
199.4
217.7
240.5
258.3
267
36.89
33.39
28.625
26.72
25.7
137.3
129.2
122
113.9
110.3
211
232.7
252.6
272
280.8
37.17
33.67
30.38
26.87
25.88
138.2
129.2
122
114.8
111.2
309.8
300.7
280.2
259.2
237.8
26.36
27.31
30.9
34.28
37.82
113
116.6
123.8
131
138.2
262.2
287.4
318
330.8
342
39.34
34.92
31.51
28.39
26.92
140
134.6
125.6
116.6
113
288.8
317.8
341.2
363.7
371.5
40.52
35.55
32.15
29
27.52
141.8
132.8
127.4
118.4
114.8

115
179
38.12
140.9
191.5
38.45
141.8
203.8
38.78
142.7
228
39.545
143.6
254.6
40.65
146.3
278.7
41.575
147.65

LEGEND
kW Compressor Power
SDT Saturated Discharge Temperature at Compressor
(F)
SST Saturated Suction Temperature (F)
TC Gross Cooling Capacity (1000 Btuh)

11

Performance data (cont)

COMBINATION RATINGS

38ARZ007/40RM007
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

1800
57

63.4
63.4
4.40
62.5
62.5
4.67
60.8
60.8
5.22
59.9
59.9
5.53
59.0
59.0
5.84
57.1
57.1
6.46

62

67

66.1
58.4
4.45
65.1
57.9
4.72
62.9
56.8
5.26
61.8
56.3
5.56
60.7
55.7
5.87
58.4
54.6
6.48

71.7
49.0
4.55
70.5
48.5
4.82
68.2
47.5
5.36
67.0
47.0
5.67
65.7
46.5
5.98
63.3
45.5
6.59

72

77.8
39.2
4.66
76.6
38.8
4.93
74.1
37.9
5.48
72.8
37.4
5.79
71.4
36.9
6.10
68.7
35.9
6.72

38ARZ007/40RM008
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2400
57

68.4
68.4
4.49
67.4
67.4
4.76
65.5
65.5
5.31
64.5
64.5
5.62
63.4
63.4
5.93
61.4
61.4
6.55

62

67

69.5
65.8
4.51
68.4
65.2
4.78
66.2
64.0
5.32
65.1
63.3
5.63
63.9
62.5
5.94
61.6
61.1
6.55

74.8
54.8
4.61
73.6
54.3
4.88
71.1
53.3
5.42
69.7
52.8
5.72
68.4
52.2
6.03
65.8
51.2
6.64

72

81.0
42.9
4.72
79.7
42.4
5.00
77.1
41.5
5.54
75.6
41.0
5.85
74.1
40.5
6.16
71.2
39.4
6.78

38ARZ008/40RM007
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

12

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

1800
57

75.3
74.3
5.77
74.2
73.4
6.12
71.8
71.6
6.83
70.6
70.5
7.22
69.4
69.4
7.61
67.0
67.0
8.39

62

81.2
65.8
5.82
79.8
65.2
6.18
77.2
63.8
6.89
75.7
63.1
7.28
74.2
62.4
7.67
71.3
60.9
8.45

67

88.5
56.3
5.91
87.1
55.6
6.27
84.2
54.3
6.98
82.6
53.6
7.38
81.1
53.0
7.78
78.0
51.6
8.59

72

96.1
46.4
6.00
94.6
45.8
6.37
91.6
44.6
7.10
89.9
43.9
7.50
88.3
43.3
7.91
85.0
41.9
8.73

Evaporator Air Cfm


2400
Evaporator Air Ewb (F)
57
62
67
72

69.0
69.0
4.50
68.0
68.0
4.77
66.1
66.1
5.32
65.1
65.1
5.63
64.0
64.0
5.94
61.9
61.9
6.57

69.8
67.2
4.52
68.7
66.6
4.79
66.5
65.2
5.33
65.4
64.4
5.63
64.2
63.7
5.94
61.9
61.9
6.56

74.9
56.0
4.60
73.6
55.5
4.88
71.1
54.6
5.42
69.8
54.0
5.73
68.5
53.5
6.03
65.8
52.4
6.65

81.1
43.6
4.72
79.7
43.1
4.99
77.0
42.2
5.54
75.6
41.7
5.85
74.1
41.2
6.16
71.3
40.2
6.78

Evaporator Air Cfm


3000
Evaporator Air Ewb (F)
57
62
67
72

73.6
73.6
4.58
72.6
72.6
4.86
70.4
70.4
5.40
69.3
69.3
5.71
68.1
68.1
6.03
65.9
65.9
6.65

73.6
73.6
4.58
72.6
72.6
4.86
70.5
70.5
5.40
69.3
69.3
5.72
68.1
68.1
6.03
65.8
65.8
6.65

77.6
63.1
4.65
76.3
62.6
4.93
73.7
61.5
5.47
72.3
60.9
5.78
70.9
60.4
6.08
68.0
59.2
6.70

83.8
48.1
4.77
82.4
47.6
5.05
79.5
46.6
5.59
78.0
46.1
5.90
76.5
45.6
6.21
73.4
44.6
6.83

Evaporator Air Cfm


2400
Evaporator Air Ewb (F)
57
62
67
72

82.5
82.5
5.84
81.3
81.3
6.20
79.0
79.0
6.91
77.7
77.7
7.31
76.4
76.4
7.70
73.8
73.8
8.49

86.4
75.7
5.88
84.9
75.0
6.24
82.0
73.6
6.95
80.4
72.8
7.35
78.8
72.0
7.75
75.6
70.5
8.54

93.6
63.5
5.97
92.0
62.8
6.33
88.8
61.5
7.05
87.1
60.8
7.45
85.4
60.1
7.86
82.0
58.7
8.66

101.0
50.9
6.07
99.5
50.2
6.44
96.2
49.0
7.17
94.4
48.3
7.58
92.6
47.7
7.99
89.0
46.4
8.80

3000
57

72.9
72.9
4.57
71.9
71.9
4.84
69.7
69.7
5.39
68.6
68.6
5.70
67.5
67.5
6.01
65.2
65.2
6.64

62

67

72.9
72.9
4.57
71.9
71.9
4.84
69.8
69.8
5.39
68.6
68.6
5.70
67.5
67.5
6.01
65.2
65.2
6.63

76.9
62.5
4.64
75.6
62.0
4.91
73.1
60.9
5.46
71.7
60.4
5.76
70.3
59.8
6.07
67.4
58.7
6.68

72

83.1
47.6
4.76
81.7
47.2
5.03
78.9
46.2
5.58
77.4
45.7
5.89
75.9
45.2
6.20
72.9
44.2
6.82

3750
57

77.3
77.3
4.65
76.1
76.1
4.92
73.8
73.8
5.47
72.6
72.6
5.78
71.4
71.4
6.10
68.9
68.9
6.72

62

67

77.3
77.3
4.65
76.1
76.1
4.92
73.8
73.8
5.47
72.6
72.6
5.78
71.4
71.4
6.10
68.9
68.9
6.73

79.5
70.4
4.69
78.2
69.8
4.96
75.5
68.7
5.51
74.0
68.0
5.82
72.6
67.3
6.12
69.7
66.0
6.74

72

85.5
52.9
4.81
84.0
52.4
5.08
81.1
51.4
5.62
79.5
50.9
5.93
77.9
50.4
6.24
74.8
49.4
6.86

3000
57

88.0
88.0
5.90
86.7
86.7
6.26
84.1
84.1
6.99
82.7
82.7
7.39
81.3
81.3
7.79
78.5
78.5
8.59

62

89.9
84.1
5.93
88.4
83.3
6.28
85.4
81.7
7.00
83.8
80.7
7.40
82.2
79.8
7.80
78.9
77.9
8.60

67

96.8
70.0
6.01
95.2
69.4
6.38
91.9
68.1
7.10
90.0
67.4
7.51
88.2
66.7
7.91
84.6
65.3
8.71

72

104.0
54.9
6.12
103.0
54.3
6.48
99.2
53.0
7.22
97.3
52.3
7.63
95.4
51.7
8.04
91.7
50.3
8.86

Performance data (cont)


38ARZ008/40RM008
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100

105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2205
57

81.7
81.7
5.83
80.6
80.6
6.19
78.3
78.3
6.90
77.0
77.0
7.30
75.7
75.7
7.69
73.2
73.2
8.48

62

67

85.9
74.2
5.88
84.5
73.5
6.23
81.7
72.1
6.95
80.1
71.3
7.34
78.6
70.6
7.74
75.4
69.0
8.53

93.2
62.4
5.97
91.6
61.7
6.33
88.5
60.4
7.05
86.9
59.8
7.45
85.2
59.1
7.86
81.9
57.7
8.67

72

101.0
50.2
6.07
99.2
49.6
6.43
95.9
48.4
7.17
94.2
47.7
7.57
92.4
47.0
7.98
88.8
45.7
8.79

38ARZ008/40RM012
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000
57

91.6
91.6
5.95
90.2
90.2
6.31
87.5
87.5
7.03
86.0
86.0
7.44
84.6
84.6
7.84
81.6
81.6
8.65

62

67

93.2
87.9
5.97
91.6
87.0
6.33
88.5
85.3
7.05
86.8
84.3
7.45
85.1
83.3
7.86
81.8
81.3
8.66

100.0
73.0
6.06
98.2
72.3
6.42
94.7
70.9
7.14
92.8
70.2
7.55
91.0
69.5
7.96
87.3
68.1
8.77

72

108.0
57.0
6.16
106.0
56.4
6.53
102.0
55.0
7.27
100.0
54.3
7.68
98.3
53.6
8.09
94.3
52.2
8.9

38ARZ012/40RM012
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000
57

110.0
110.0
8.19
108.0
108.0
8.57
105.0
105.0
9.34
104.0
104.0
9.76
102.0
102.0
10.20
98.4
98.4
11.00

62

115.0
99.4
8.32
113.0
98.4
8.70
110.0
96.6
9.45
107.0
95.5
9.86
105.0
94.4
10.30
101.0
92.2
11.10

67

124.0
83.3
8.55
122.0
82.4
8.93
118.0
80.7
9.69
116.0
79.7
10.10
114.0
78.7
10.5
109.0
76.7
11.30

72

134.0
66.8
8.82
132.0
66.0
9.20
127.0
64.3
9.96
125.0
63.4
10.40
122.0
62.4
10.80
117.0
60.5
11.60

Evaporator Air Cfm


3000
Evaporator Air Ewb (F)
57
62
67
72

89.0
89.0
5.92
87.7
87.7
6.28
85.2
85.2
7.00
83.7
83.7
7.40
82.3
82.3
7.80
79.5
79.5
8.61

90.8
85.2
5.94
89.3
84.5
6.30
86.3
82.9
7.02
84.7
81.9
7.42
83.0
80.9
7.82
79.8
79.0
8.61

97.5
70.9
6.02
95.8
70.2
6.39
92.5
69.0
7.11
90.7
68.3
7.52
88.9
67.6
7.92
85.3
66.1
8.73

105.0
55.4
6.12
103.0
54.8
6.49
99.9
53.6
7.23
98.0
52.9
7.64
96.1
52.2
8.05
92.3
50.9
8.87

Evaporator Air Cfm


4000
Evaporator Air Ewb (F)
57
62
67
72

98.4
98.4
6.04
96.9
96.9
6.40
93.9
93.9
7.13
92.3
92.3
7.54
90.7
90.7
7.95
87.4
87.4
8.77

98.4
98.4
6.04
96.9
96.9
6.40
93.9
93.9
7.13
92.3
92.3
7.54
90.7
90.7
7.95
87.4
87.4
8.77

104.0
83.9
6.10
102.0
83.1
6.47
98.1
81.7
7.20
96.1
81.0
7.61
94.2
80.2
8.02
90.3
78.8
8.83

111.0
63.6
6.21
109.0
63.0
6.58
105.0
61.7
7.32
103.0
61.0
7.73
101.0
60.3
8.14
97.1
58.9
8.97

Evaporator Air Cfm


4000
Evaporator Air Ewb (F)
57
62
67
72

119.0
119.0
8.41
117.0
117.0
8.80
114.0
114.0
9.57
112.0
112.0
9.98
110.0
110.0
10.40
106.0
106.0
11.20

121.0
114.0
8.48
119.0
113.0
8.85
115.0
111.0
9.61
113.0
109.0
10.00
111.0
108.0
10.40
106.0
105.0
11.20

130.0
94.6
8.70
128.0
93.7
9.08
123.0
91.9
9.83
121.0
90.9
10.20
118.0
89.9
10.60
113.0
87.8
11.40

139.0
73.6
8.96
137.0
72.8
9.35
132.0
71.1
10.10
130.0
70.2
10.50
127.0
69.2
10.90
122.0
67.3
11.70

3750
57

91.6
91.6
5.95
90.2
90.2
6.31
87.6
87.6
7.04
86.1
86.1
7.44
84.6
84.6
7.84
81.7
81.7
8.65

62

67

92.6
89.4
5.96
91.1
88.4
6.32
88.2
86.4
7.05
86.6
85.2
7.45
85.0
83.9
7.85
81.8
81.4
8.65

98.8
74.7
6.04
97.1
74.1
6.40
93.8
72.8
7.13
91.9
72.1
7.54
90.1
71.4
7.94
86.4
70.0
8.75

72

106.0
57.7
6.14
105.0
57.1
6.51
101.0
55.9
7.25
99.1
55.2
7.66
97.2
54.6
8.07
93.3
53.2
8.89

5000
57

103.0
103.0
6.10
101.0
101.0
6.47
98.3
98.3
7.20
96.5
96.5
7.61
94.8
94.8
8.03
91.3
91.3
8.85

62

103.0
103.0
6.10
101.0
101.0
6.46
98.2
98.2
7.20
96.5
96.5
7.61
94.8
94.8
8.03
91.4
91.4
8.85

67

106.0
93.5
6.14
104.0
92.6
6.50
100.0
91.0
7.24
98.4
90.1
7.65
96.4
89.2
8.05
92.4
87.4
8.87

72

113.0
69.7
6.24
111.0
69.1
6.61
107.0
67.8
7.35
105.0
67.1
7.76
103.0
66.4
8.17
98.7
65.1
9.00

5000
57

126.0
126.0
8.59
124.0
124.0
8.97
120.0
120.0
9.73
118.0
118.0
10.10
116.0
116.0
10.60
111.0
111.0
11.40

62

126.0
125.0
8.60
124.0
123.0
8.98
120.0
120.0
9.74
118.0
118.0
10.10
116.0
116.0
10.60
111.0
111.0
11.40

67

133.0
105.0
8.80
131.0
104.0
9.17
126.0
102.0
9.93
124.0
101.0
10.30
121.0
100.0
10.70
116.0
97.9
11.50

72

143.0
79.9
9.06
140.0
79.0
9.44
135.0
77.3
10.20
132.0
76.4
10.60
130.0
75.5
11.00
124.0
73.6
11.80

13

Performance data (cont)


38ARZ012/40RM014
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57

119.0
119.0
8.42
118.0
118.0
8.80
114.0
114.0
9.57
112.0
112.0
9.98
110.0
110.0
10.40
106.0
106.0
11.20

62

123.0
112.0
8.51
121.0
111.0
8.89
116.0
109.0
9.64
114.0
108.0
10.00
112.0
106.0
10.40
107.0
104.0
11.20

67

132.0
93.2
8.77
130.0
92.3
9.14
125.0
90.4
9.89
123.0
89.3
10.30
120.0
88.2
10.70
115.0
86.1
11.50

72

142.0
73.4
9.05
140.0
72.5
9.43
135.0
70.7
10.20
132.0
69.7
10.60
129.0
68.7
11.00
124.0
66.6
11.80

38ARD014/40RM012
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000
57

119.0
119.0
9.09
118.0
118.0
9.66
115.0
115.0
10.90
113.0
113.0
11.60
111.0
111.0
12.20
108.0
108.0
13.70

62

128.0
106.0
9.15
126.0
105.0
9.72
122.0
103.0
10.90
120.0
102.0
11.60
118.0
101.0
12.30
114.0
99.0
13.70

67

140.0
90.4
9.18
138.0
89.5
9.75
134.0
87.7
11.00
131.0
86.7
11.60
129.0
85.7
12.30
124.0
83.7
13.80

72

153.0
74.3
9.23
151.0
73.4
9.81
146.0
71.7
11.00
144.0
70.8
11.70
141.0
69.8
12.40
136.0
67.8
13.90

38ARD014/40RM014
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

14

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57

130.0
130.0
9.14
129.0
129.0
9.70
125.0
125.0
10.90
123.0
123.0
11.60
122.0
122.0
12.30
118.0
118.0
13.80

62

137.0
120.0
9.18
135.0
119.0
9.73
131.0
117.0
11.00
128.0
115.0
11.60
126.0
114.0
12.30
121.0
112.0
13.80

67

150.0
101.0
9.22
147.0
100.0
9.78
143.0
98.0
11.00
140.0
97.0
11.70
137.0
95.9
12.30
132.0
93.6
13.80

72

163.0
81.6
9.32
161.0
80.7
9.88
156.0
78.7
11.10
153.0
77.7
11.70
150.0
76.7
12.40
144.0
74.5
13.90

Evaporator Air Cfm


5000
Evaporator Air Ewb (F)
57
62
67
72

128.0
128.0
8.66
126.0
126.0
9.05
122.0
122.0
9.81
120.0
120.0
10.20
118.0
118.0
10.60
114.0
114.0
11.40

129.0
127.0
8.68
127.0
126.0
9.06
123.0
122.0
9.81
120.0
120.0
10.20
118.0
118.0
10.60
113.0
113.0
11.40

137.0
106.0
8.90
135.0
105.0
9.28
130.0
103.0
10.00
127.0
102.0
10.40
124.0
101.0
10.80
119.0
99.1
11.60

147.0
81.4
9.18
144.0
80.5
9.56
139.0
78.7
10.30
136.0
77.7
10.70
133.0
76.7
11.10
127.0
74.6
11.90

Evaporator Air Cfm


4000
Evaporator Air Ewb (F)
57
62
67
72

131.0
131.0
9.15
130.0
130.0
9.72
126.0
126.0
10.90
124.0
124.0
11.60
122.0
122.0
12.30
118.0
118.0
13.70

136.0
122.0
9.16
134.0
121.0
9.72
130.0
119.0
10.90
128.0
118.0
11.60
125.0
117.0
12.30
121.0
114.0
13.80

148.0
103.0
9.21
146.0
102.0
9.77
141.0
99.9
11.00
139.0
98.9
11.60
136.0
97.9
12.30
131.0
95.8
13.80

161.0
82.0
9.30
159.0
81.2
9.87
154.0
79.3
11.10
151.0
78.4
11.70
148.0
77.5
12.40
143.0
75.4
13.90

Evaporator Air Cfm


5000
Evaporator Air Ewb (F)
57
62
67
72

143.0
143.0
9.20
141.0
141.0
9.76
137.0
137.0
11.00
135.0
135.0
11.60
132.0
132.0
12.30
128.0
128.0
13.80

145.0
138.0
9.20
143.0
137.0
9.76
138.0
134.0
11.00
136.0
132.0
11.70
133.0
131.0
12.30
128.0
128.0
13.80

157.0
115.0
9.27
154.0
114.0
9.82
149.0
112.0
11.00
146.0
111.0
11.70
144.0
110.0
12.40
138.0
108.0
13.90

171.0
90.5
9.38
168.0
89.5
9.93
162.0
87.5
11.10
160.0
86.5
11.80
157.0
85.4
12.50
150.0
83.3
14.00

6250
57

135.0
135.0
8.84
133.0
133.0
9.22
128.0
128.0
9.99
126.0
126.0
10.40
123.0
123.0
10.80
119.0
119.0
11.60

62

135.0
135.0
8.84
133.0
133.0
9.22
128.0
128.0
9.99
126.0
126.0
10.40
123.0
123.0
10.80
119.0
119.0
11.60

67

140.0
118.0
8.99
138.0
117.0
9.37
133.0
115.0
10.10
130.0
114.0
10.50
127.0
113.0
10.90
121.0
110.0
11.70

72

150.0
88.6
9.27
147.0
87.8
9.65
142.0
86.0
10.40
139.0
85.0
10.80
136.0
84.0
11.20
130.0
81.9
12.00

5000
57

140.0
140.0
9.19
138.0
138.0
9.75
134.0
134.0
11.00
132.0
132.0
11.60
130.0
130.0
12.30
126.0
126.0
13.80

62

142.0
136.0
9.19
140.0
135.0
9.75
136.0
132.0
11.00
133.0
131.0
11.60
131.0
129.0
12.30
126.0
126.0
13.80

67

153.0
114.0
9.25
151.0
113.0
9.80
146.0
111.0
11.00
143.0
110.0
11.70
140.0
109.0
12.40
135.0
107.0
13.80

72

166.0
89.0
9.33
164.0
88.1
9.89
158.0
86.3
11.10
156.0
85.3
11.80
153.0
84.3
12.40
147.0
82.3
13.90

6250
57

151.0
151.0
9.24
149.0
149.0
9.79
145.0
145.0
11.00
143.0
143.0
11.70
140.0
140.0
12.30
135.0
135.0
13.80

62

151.0
151.0
9.23
149.0
149.0
9.79
145.0
145.0
11.00
143.0
143.0
11.70
140.0
140.0
12.40
135.0
135.0
13.80

67

162.0
128.0
9.30
159.0
127.0
9.85
154.0
125.0
11.10
151.0
124.0
11.70
148.0
123.0
12.40
142.0
120.0
13.90

72

176.0
98.5
9.43
173.0
97.5
9.98
167.0
95.6
11.20
164.0
94.5
11.80
161.0
93.5
12.50
154.0
91.3
14.00

Performance data (cont)


38ARD014/40RM016
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4500
57

143.0
143.0
9.19
141.0
141.0
9.75
137.0
137.0
11.00
135.0
135.0
11.60
133.0
133.0
12.30
129.0
129.0
13.80

62

147.0
136.0
9.22
145.0
134.0
9.77
140.0
132.0
11.00
138.0
131.0
11.60
135.0
129.0
12.30
130.0
126.0
13.80

67

160.0
113.0
9.28
157.0
112.0
9.85
152.0
110.0
11.10
149.0
109.0
11.70
146.0
108.0
12.40
140.0
106.0
13.90

72

174.0
89.9
9.42
171.0
89.0
9.98
165.0
86.9
11.20
162.0
85.8
11.80
159.0
84.7
12.50
153.0
82.5
14.00

38ARD016/40RM014
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57

154.0
152.0
12.40
152.0
150.0
12.90
147.0
146.0
14.10
144.0
144.0
14.80
141.0
141.0
15.40
136.0
136.0
16.80

62

166.0
134.0
12.60
163.0
133.0
13.20
157.0
130.0
14.40
154.0
128.0
15.00
151.0
127.0
15.60
144.0
124.0
16.90

67

181.0
115.0
13.00
178.0
113.0
13.50
171.0
111.0
14.70
168.0
109.0
15.30
164.0
107.0
16.00
157.0
104.0
17.30

72

196.0
94.7
13.30
193.0
93.4
13.90
186.0
90.6
15.10
182.0
89.1
15.70
179.0
87.6
16.40
170.0
84.4
17.70

38ARD016/40RM016
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4500
57

169.0
169.0
12.70
167.0
167.0
13.30
161.0
161.0
14.50
159.0
159.0
15.10
156.0
156.0
15.70
150.0
150.0
17.10

62

180.0
152.0
12.90
177.0
151.0
13.50
170.0
147.0
14.70
166.0
145.0
15.30
163.0
144.0
15.90
155.0
140.0
17.20

67

195.0
128.0
13.30
192.0
127.0
13.90
184.0
124.0
15.10
181.0
122.0
15.70
177.0
120.0
16.30
168.0
117.0
17.60

72

211.0
104.0
13.70
208.0
103.0
14.30
200.0
99.8
15.50
196.0
98.2
16.10
192.0
96.6
16.80
183.0
93.2
18.10

Evaporator Air Cfm


6000
Evaporator Air Ewb (F)
57
62
67
72

155.0
155.0
9.27
153.0
153.0
9.82
149.0
149.0
11.00
146.0
146.0
11.70
144.0
144.0
12.40
139.0
139.0
13.90

156.0
155.0
9.26
153.0
153.0
9.82
149.0
149.0
11.00
146.0
146.0
11.70
144.0
144.0
12.40
139.0
139.0
13.90

166.0
130.0
9.34
164.0
129.0
9.90
158.0
127.0
11.10
155.0
126.0
11.80
152.0
125.0
12.50
146.0
122.0
13.90

180.0
100.0
9.49
178.0
99.5
10.00
172.0
97.4
11.20
168.0
96.3
11.90
165.0
95.2
12.60
158.0
92.9
14.10

Evaporator Air Cfm


5000
Evaporator Air Ewb (F)
57
62
67
72

168.0
168.0
12.70
166.0
166.0
13.20
160.0
160.0
14.40
158.0
158.0
15.10
155.0
155.0
15.70
149.0
149.0
17.10

176.0
154.0
12.90
173.0
153.0
13.40
167.0
149.0
14.60
163.0
148.0
15.20
160.0
146.0
15.80
152.0
142.0
17.20

191.0
129.0
13.20
188.0
128.0
13.80
180.0
125.0
15.00
177.0
123.0
15.60
173.0
122.0
16.20
165.0
118.0
17.50

206.0
104.0
13.60
203.0
102.0
14.20
196.0
99.7
15.40
191.0
98.1
16.00
187.0
96.5
16.60
178.0
93.3
17.90

Evaporator Air Cfm


6000
Evaporator Air Ewb (F)
57
62
67
72

185.0
185.0
13.10
182.0
182.0
13.60
176.0
176.0
14.80
173.0
173.0
15.50
169.0
169.0
16.10
163.0
163.0
17.50

190.0
175.0
13.20
186.0
173.0
13.70
179.0
169.0
14.90
176.0
167.0
15.50
172.0
165.0
16.20
164.0
160.0
17.50

204.0
146.0
13.50
201.0
144.0
14.10
193.0
141.0
15.30
189.0
139.0
15.90
185.0
138.0
16.50
175.0
134.0
17.80

221.0
115.0
13.90
217.0
113.0
14.50
209.0
111.0
15.70
204.0
109.0
16.40
200.0
107.0
17.00
190.0
104.0
18.30

7500
57

164.0
164.0
9.31
162.0
162.0
9.87
157.0
157.0
11.10
154.0
154.0
11.70
152.0
152.0
12.40
146.0
146.0
13.90

62

164.0
164.0
9.33
162.0
162.0
9.89
157.0
157.0
11.10
154.0
154.0
11.80
152.0
152.0
12.50
146.0
146.0
13.90

67

171.0
146.0
9.37
168.0
144.0
9.93
162.0
142.0
11.10
159.0
141.0
11.80
156.0
139.0
12.50
150.0
137.0
13.90

72

185.0
110.0
9.54
182.0
109.0
10.10
175.0
107.0
11.30
172.0
106.0
11.90
169.0
105.0
12.60
162.0
103.0
14.10

6250
57

179.0
179.0
12.90
176.0
176.0
13.50
171.0
171.0
14.70
167.0
167.0
15.30
164.0
164.0
16.00
158.0
158.0
17.30

62

183.0
171.0
13.00
180.0
169.0
13.60
173.0
166.0
14.80
170.0
163.0
15.40
166.0
161.0
16.00
159.0
156.0
17.30

67

197.0
143.0
13.40
194.0
141.0
13.90
187.0
138.0
15.10
182.0
137.0
15.70
178.0
135.0
16.40
170.0
132.0
17.70

72

213.0
112.0
13.70
210.0
111.0
14.30
202.0
108.0
15.50
197.0
106.0
16.20
193.0
105.0
16.80
183.0
101.0
18.10

7500
57

196.0
196.0
13.30
193.0
193.0
13.90
186.0
186.0
15.10
183.0
183.0
15.70
179.0
179.0
16.40
172.0
172.0
17.70

62

197.0
193.0
13.30
194.0
191.0
13.90
187.0
186.0
15.10
183.0
183.0
15.70
179.0
179.0
16.40
172.0
172.0
17.70

67

211.0
162.0
13.70
207.0
160.0
14.30
199.0
157.0
15.50
194.0
155.0
16.10
190.0
153.0
16.70
180.0
150.0
18.00

72

227.0
125.0
14.10
223.0
123.0
14.70
215.0
120.0
15.90
210.0
119.0
16.50
205.0
117.0
17.20
195.0
114.0
18.50

15

Performance data (cont)


38ARD016/40RM024
Temp (F) Air
Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

80
85
95
100
105
115

6,000
57

190.0
190.0
13.20
187.0
187.0
13.80
181.0
181.0
15.00
178.0
178.0
15.60
174.0
174.0
16.20
167.0
167.0
17.60

62

194.0
181.0
13.30
191.0
179.0
13.90
184.0
175.0
15.00
180.0
173.0
15.70
176.0
171.0
16.30
168.0
166.0
17.60

67

209.0
150.0
13.60
205.0
149.0
14.20
197.0
146.0
15.40
193.0
144.0
16.00
188.0
142.0
16.60
179.0
138.0
18.00

72

226.0
118.0
14.00
222.0
117.0
14.60
213.0
114.0
15.90
209.0
112.0
16.50
204.0
110.0
17.10
194.0
107.0
18.40

38ARD024/40RM016
Temp (F) Air
Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

80
85
95
100
105
115

4500
57

196.0
190.0
16.70
193.0
188.0
17.40
187.0
184.0
19.00
184.0
182.0
19.90
180.0
179.0
20.80
173.0
173.0
22.60

62

211.0
168.0
17.10
207.0
166.0
17.80
200.0
162.0
19.40
197.0
161.0
20.30
193.0
159.0
21.10
185.0
155.0
22.90

67

229.0
144.0
17.70
225.0
142.0
18.40
217.0
138.0
20.00
213.0
136.0
20.80
209.0
135.0
21.70
200.0
131.0
23.50

72

248.0
119.0
18.30
244.0
117.0
19.00
235.0
114.0
20.60
231.0
112.0
21.40
226.0
110.0
22.30
216.0
106.0
24.00

38ARD024/40RM024
Temp (F) Air
Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

80
85
95
100
105
115

16

6,000
57

219.0
219.0
17.30
216.0
216.0
18.10
209.0
209.0
19.70
206.0
206.0
20.60
202.0
202.0
21.40
195.0
195.0
23.30

62

229.0
199.0
17.70
226.0
197.0
18.40
217.0
192.0
20.00
213.0
190.0
20.80
209.0
188.0
21.70
200.0
184.0
23.40

67

248.0
167.0
18.30
243.0
165.0
19.00
234.0
161.0
20.60
230.0
159.0
21.40
225.0
157.0
22.20
215.0
153.0
24.00

72

267.0
134.0
19.00
263.0
132.0
19.70
253.0
128.0
21.30
248.0
126.0
22.10
242.0
124.0
22.90
232.0
120.0
24.60

Evaporator Air Cfm


8,000
Evaporator Air Ewb (F)
57
62
67
72

205.0
205.0
13.50
202.0
202.0
14.10
195.0
195.0
15.30
191.0
191.0
16.00
187.0
187.0
16.60
179.0
179.0
17.90

205.0
204.0
13.50
202.0
201.0
14.10
195.0
195.0
15.30
191.0
191.0
16.00
187.0
187.0
16.60
179.0
179.0
17.90

217.0
173.0
13.80
213.0
171.0
14.40
204.0
168.0
15.60
200.0
166.0
16.20
195.0
164.0
16.90
185.0
160.0
18.10

233.0
132.0
14.20
229.0
131.0
14.80
220.0
128.0
16.10
216.0
126.0
16.70
210.0
124.0
17.30
200.0
121.0
18.60

Evaporator Air Cfm


6000
Evaporator Air Ewb (F)
57
62
67
72

212.0
212.0
17.10
209.0
209.0
17.90
203.0
203.0
19.50
200.0
200.0
20.40
196.0
196.0
21.20
189.0
189.0
23.10

224.0
192.0
17.50
220.0
190.0
18.20
212.0
186.0
19.80
208.0
184.0
20.60
204.0
182.0
21.50
195.0
178.0
23.30

242.0
161.0
18.10
238.0
160.0
18.80
229.0
156.0
20.40
224.0
154.0
21.20
220.0
152.0
22.00
210.0
148.0
23.80

261.0
130.0
18.80
257.0
128.0
19.50
247.0
125.0
21.10
242.0
123.0
21.90
237.0
121.0
22.70
226.0
117.0
24.40

Evaporator Air Cfm


8,000
Evaporator Air Ewb (F)
57
62
67
72

237.0
237.0
17.90
234.0
234.0
18.70
226.0
226.0
20.30
222.0
222.0
21.10
218.0
218.0
22.00
210.0
210.0
23.80

241.0
228.0
18.10
237.0
226.0
18.80
228.0
221.0
20.40
224.0
218.0
21.20
219.0
215.0
22.00
210.0
209.0
23.80

259.0
190.0
18.70
254.0
188.0
19.40
244.0
184.0
20.90
239.0
182.0
21.70
233.0
180.0
22.60
223.0
175.0
24.30

278.0
148.0
19.40
273.0
146.0
20.10
263.0
142.0
21.70
257.0
140.0
22.50
251.0
138.0
23.30
239.0
134.0
25.00

10,000
57

215.0
215.0
13.80
211.0
211.0
14.40
204.0
204.0
15.60
200.0
200.0
16.20
196.0
196.0
16.90
187.0
187.0
18.20

62

215.0
215.0
13.80
211.0
211.0
14.40
204.0
204.0
15.60
200.0
200.0
16.20
196.0
196.0
16.90
187.0
187.0
18.20

67

222.0
193.0
14.00
218.0
191.0
14.50
209.0
187.0
15.80
205.0
185.0
16.40
200.0
183.0
17.00
190.0
178.0
18.30

72

238.0
145.0
14.40
234.0
144.0
15.00
225.0
141.0
16.20
220.0
139.0
16.80
215.0
137.0
17.50
203.0
133.0
18.70

7500
57

226.0
226.0
17.60
223.0
223.0
18.30
216.0
216.0
19.90
212.0
212.0
20.80
208.0
208.0
21.60
200.0
200.0
23.50

62

233.0
213.0
17.80
229.0
211.0
18.50
220.0
207.0
20.10
216.0
204.0
20.90
211.0
202.0
21.70
202.0
197.0
23.50

67

250.0
178.0
18.40
246.0
176.0
19.10
236.0
172.0
20.70
231.0
170.0
21.50
226.0
168.0
22.30
216.0
164.0
24.00

72

270.0
140.0
19.10
265.0
138.0
19.80
255.0
135.0
21.40
249.0
133.0
22.20
244.0
131.0
23.00
233.0
127.0
24.70

10,000
57

250.0
250.0
18.40
246.0
246.0
19.10
238.0
238.0
20.70
234.0
234.0
21.50
229.0
229.0
22.40
220.0
220.0
24.20

62

251.0
250.0
18.40
247.0
246.0
19.10
238.0
238.0
20.70
234.0
234.0
21.50
229.0
229.0
22.40
220.0
220.0
24.20

67

265.0
211.0
18.90
261.0
209.0
19.70
250.0
205.0
21.20
245.0
202.0
22.00
239.0
200.0
22.80
228.0
196.0
24.50

72

285.0
161.0
19.60
280.0
159.0
20.40
269.0
155.0
21.90
263.0
153.0
22.70
257.0
151.0
23.50
244.0
147.0
25.20

Performance data (cont)


38ARD024/40RM028
Temp (F) Air
Entering
Condenser
(Edb)
57
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

7,500
62

236.0
236.0
17.90
233.0
233.0
18.70
225.0
225.0
20.30
221.0
221.0
21.10
217.0
217.0
22.00
209.0
209.0
23.80

242.0
223.0
18.10
238.0
221.0
18.80
229.0
216.0
20.40
225.0
214.0
21.20
220.0
211.0
22.10
211.0
206.0
23.80

67

260.0
185.0
18.70
256.0
184.0
19.50
246.0
179.0
21.00
241.0
178.0
21.80
236.0
175.0
22.60
225.0
171.0
24.40

72

280.0
146.0
19.50
275.0
144.0
20.20
265.0
140.0
21.80
260.0
138.0
22.50
254.0
136.0
23.40
242.0
132.0
25.10

38ARD028/40RM028
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115
122

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

7,500
62

67

302
256
26.7
296
253
27.7
285
248
30.0
280
243
31.3
274
239
32.5
268
235
35.1
259
229
37.8

322
213
27.5
317
211
28.6
304
207
30.9
297
204
32.1
290
202
33.2
283
189
35.8
271
186
38.4

8,000
72

347
166
28.6
341
164
29.7
328
159
32.0
320
158
33.1
313
155
34.3
304
150
36.8
291
148
39.4

62

305
264
26.9
299
260
27.9
288
253
30.2
284
249
31.5
278
244
32.7
272
239
35.3
263
231
38.2

67

323
220
27.7
318
219
28.8
305
214
31.1
298
211
32.2
291
209
33.4
284
196
35.9
272
190
38.5

38ARD028/40RM034
Temp (F) Air
Entering
Condenser
(Edb)
80
85
95
100
105
115
122

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

9,000
62

319
286
27.7
313
282
28.8
301
275
31.2
296
271
32.5
290
267
33.8
283
263
36.5
273
256
39.3

67

340
238
28.6
335
236
29.7
321
231
32.1
314
228
33.3
306
225
34.5
299
211
37.2
287
208
39.9

72

367
185
29.7
360
184
30.8
346
178
33.2
338
177
34.4
331
174
35.6
321
168
38.2
308
165
41.0

62

334
313
28.4
329
309
29.5
316
298
31.8
311
293
33.1
305
288
34.4
298
281
37.1
287
271
40.0

Evaporator Air Cfm


10,000
Evaporator Air Ewb (F)
57
62
67
72

254.0
254.0
18.50
250.0
250.0
19.30
242.0
242.0
20.90
237.0
237.0
21.70
233.0
233.0
22.50
223.0
223.0
24.30

254.0
252.0
18.50
250.0
249.0
19.30
242.0
242.0
20.90
237.0
237.0
21.70
233.0
233.0
22.50
223.0
223.0
24.30

269.0
212.0
19.10
265.0
210.0
19.80
255.0
206.0
21.40
249.0
204.0
22.10
243.0
202.0
23.00
232.0
197.0
24.60

290.0
162.0
19.80
285.0
161.0
20.60
273.0
157.0
22.10
268.0
155.0
22.90
262.0
153.0
23.70
249.0
148.0
25.40

Evaporator Air - CFM


9,000
Evaporator Air - EWB (F)
72
62
67
72
62

348
169
28.8
342
168
29.9
328
163
32.2
321
162
33.2
314
159
34.5
304
154
36.9
291
152
39.6

311
271
27.2
306
267
28.3
295
259
30.6
290
254
31.8
284
249
33.0
278
244
35.6
268
235
38.4

327
233
27.9
321
231
29.0
309
226
31.2
301
224
32.3
294
221
33.6
287
207
36.0
275
204
38.7

351
177
28.9
345
176
30.0
331
171
32.3
324
170
33.4
316
167
34.6
307
162
37.1
294
159
39.7

318
279
27.6
314
275
28.6
302
265
30.9
296
260
32.2
291
255
33.4
284
249
35.9
273
240
38.7

Evaporator Air - CFM


10,000
12,000
Evaporator Air - EWB (F)
67
72
62
67
351
269
29.1
344
267
30.2
333
263
32.5
323
258
33.7
316
255
35.0
307
239
37.6
295
235
40.3

376
204
30.1
370
203
31.3
355
197
33.7
348
196
34.8
339
193
36.1
329
187
38.7
315
184
41.3

347
342
28.8
342
338
29.9
330
326
32.3
324
320
33.6
318
313
34.9
310
306
37.5
298
294
40.4

361
303
29.4
355
300
30.5
341
294
32.7
333
290
34.0
325
287
35.3
316
268
37.8
303
263
40.6

12,500
57

266.0
266.0
18.90
262.0
262.0
19.70
253.0
253.0
21.30
248.0
248.0
22.10
243.0
243.0
22.90
233.0
233.0
24.70

62

67

266.0
266.0
18.90
262.0
262.0
19.70
253.0
253.0
21.30
248.0
248.0
22.10
243.0
243.0
22.90
233.0
233.0
24.70

276.0
236.0
19.30
271.0
234.0
20.00
260.0
230.0
21.60
255.0
227.0
22.40
249.0
225.0
23.20
237.0
219.0
24.90

10,000
67

331
246
28.1
325
244
29.2
312
239
31.3
305
236
32.5
298
234
33.8
289
218
36.2
278
214
38.9

72

296.0
178.0
20.00
290.0
176.0
20.80
279.0
172.0
22.30
273.0
170.0
23.10
266.0
168.0
23.90
253.0
164.0
25.60

12,500
72

355
185
29.0
349
184
30.2
335
179
32.5
328
178
33.6
319
175
34.8
310
170
37.3
297
167
39.8

62

67

334
293
28.4
329
289
29.5
317
278
31.9
311
273
33.1
305
268
34.4
298
261
36.9
287
252
39.9

347
259
28.9
341
256
30.0
328
251
32.2
320
248
33.5
313
246
34.8
304
229
37.3
292
225
40.0

72

372
195
29.8
366
193
31.1
352
188
33.5
344
187
34.6
335
184
35.9
325
179
38.4
311
175
41.0

15,000
72

387
228
30.3
381
226
31.6
366
220
34.0
358
219
35.1
349
216
36.4
338
209
39.0
324
205
41.5

62

357
357
29.7
353
353
30.8
340
340
33.3
334
334
34.6
327
327
35.9
319
319
38.6
307
307
41.6

67

372
316
30.2
365
313
31.4
351
306
33.7
343
303
35.0
335
300
36.3
326
280
39.0
312
275
41.8

72

399
238
31.2
393
236
32.5
377
230
35.0
369
228
36.1
359
225
37.5
348
218
40.1
334
214
42.8

17

Electrical data
UNIT
SIZE
38AR
Z007

Z008

Z012

D014

D016

D024

D028

VOLTAGE
RANGE*

COMPRESSOR 1

MIN

MAX

RLA

LRA

RLA

LRA

208/230-3-60
460-3-60
380-3-60
400-3-50
208/230-3-60
460-3-60
380-3-60
400-3-50
208/230-3-60
460-3-60
380-3-60
400-3-50
208/230-3-60
460-3-60
380-3-60
400-3-50
208/230-3-60
460-3-60
380-3-60
400-3-50
208/230-3-60
460-3-60
380-3-60
400-3-50
208/230-3-60
460-3-60
380-3-60

187
418
342
360
187
418
342
360
187
418
342
360
187
418
342
360
187
418
342
360
187
418
342
360
187
418
342

254
506
418
440
254
506
418
440
254
506
418
440
254
506
418
440
254
506
418
440
254
506
418
440
254
506
418

22.4
9.51
9.51
9.43
25.6
13.5
16
13.5
35.7
20.7
21.4
20.7
22.4
9.51
9.51
9.43
25.6
13.5
16
13.5
35.7
20.7
21.4
20.7
45.7
22.9
27.1

170
80
80
80
190
95
135
95
237
130
160
130
170
80
80
80
190
95
135
95
237
130
160
130
255
145
155

------------22.4
9.51
9.51
9.43
25.6
13.5
16
13.5
35.7
20.7
21.4
20.7
45.7
22.9
27.1

------------170
80
80
80
190
95
135
95
237
130
160
130
255
145
155

LEGEND
FLA Full Load Amps
kW Total Fan Motor Input (kilowatts)
LRA Locked Rotor Amps
MCA Minimum Circuit Amps per NEC, Section 430-24
MOCP Maximum Overcurrent Protection (amps)
RLA Rated Load Amps (compressor)
*Units are suitable for use on electrical systems where
voltage supplied to the unit terminals is not below or
above the listed limits.

18

COMPRESSOR 2

NOMINAL
VOLTAGE
V-Ph-Hz

FAN MOTORS
(Qty 2)
FLA
LRA
(ea)
(ea)
0.9
1.6
0.5
0.9
0.9
1.6
0.5
0.9
1.5
3.1
0.8
1.6
1.5
3.1
0.8
1.6
1.5
3.1
0.8
1.6
1.5
3.1
0.8
1.6
3.6
7.5
1.9
-3.6
7.5
1.7
-3.6
7.5
1.9
-3.6
7.5
1.7
-3.6
7.5
1.9
-3.6
-1.7
7.5
5.5
2.8
3.9
-

POWER SUPPLY
MCA

MOCP

29.125
12.5
13
12.4
33.9
17.9
21.9
17.9
46.5
26.9
28.6
26.9
65
28.5
32.8
27.8
73
38.5
49
38
98.3
56.5
62
56
125.3
62.9
75.6

51.3
20
20
20
55
30
30
30
80
45
45
45
70
35
35
30
80
45
55
45
125
70
70
70
150
80
90

NOTES:
1. The MCA and MOCP values are calculated in
accordance with theNational Electrical Code (NEC),
Article 440.
2. Motor RLA and LRA values are established in
accordance with Underwriters Laboratories (UL),
Standard 1995.

Application data
Operating limits

LIQUID LINE DATA 38ARD014-024 UNITS

Maximum Outdoor
Temperature
Minimum Outdoor Ambient

Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge
Temperature
Minimum Discharge Superheat

115 F
See Minimum Outdoor-Air
Operating Temperature
table below.
55 F

295 F
60 F

UNIT
38ARZ007
38ARZ008
38ARZ012
38ARD014
38ARD016
38ARD024
38A RD028

REFRIGERANT PIPING SIZES


LINEAR LENGTH OF PIPING FT
0-25

UNIT
38AR

MAXIMUM REFRIGERANT CHARGE

38ARZ007-012
38ARD014-024
38ARD028

For refrigerant lines longer than 75 lineal ft, a


liquid line solenoid valve installed at the indoor
unit and a suction accumulator are required. Refer
to the Refrigerant Specialties
Part Numbers table.

For applications with liquid lift greater than 20 ft,


use 1/2-in. liquid line where 3/8 in. is shown; use 5/8in. liquid line where 1/2 in. is shown. The
maximum liquid lift is 60 ft.
R-22 (lb)
17.3
34.2
34.2
(2)17.3
(2)34.2
(2)34.2
(2)27.5

COND
TEMP
(F)

MINIMUM OUTDOOR TEMP (F)

90

50

90

59

Std

60

It is recommended that the refrigerant piping for all


commercial split systems include a liquid line
solenoid valve, a liquid line filter drier and a sight
glass.

Liquid line

UNIT 38AR

38ARZ007-012
38ARD014-028

LIQUID LINE
Max Allow.
Max Allow.
Pressure
Temp Loss
Drop (psi)
(F)

IMPORTANT: Do not bury refrigerant piping


underground.

25 to 55 F

MINIMUM OUTDOOR-AIR OPERATING


TEMPERATURE

MAX
ALLOW.
LIFT (ft)

Refrigerant piping

95 F

NOTES:
1. Select air handler at no less than 300 cfm/ton (nominal
condensing unit capacity).
2. Total combined draw of the field-supplied liquid line
solenoid valve and air handler fan contactor must not exceed 22
va. If the specified va must be exceeded, use a remote relay to
control the load.

UNIT 38AR
Z007
Z008
Z012
D014
D016
D024
D028

UNIT 38AR

25-50

50-75

75-100

Line Size (in. OD)


L

Z007

3/8

11/8

3/8

11/8

3/8

11/8

3/8

11/8

Z008

3/8

11/8

1/2

11/8

1/2

11/8

1/2

13/8

Z012

1/2

13/8

1/2

13/8

1/2

13/8

1/2

13/8

D014
D016

1/2
1/2

1 1/8
13/8

1/2
1/2

1 1/8
13/8

1/2
1/2

1 1/8 1/2
13/8 5/8

1 1/8
13/8

D024

1/2

13/8

1/2

13/8

5/8

13/8

3/8

UNIT
38AR
D028

04 (0-13.1 )
L
5 /8

S
1 3 /8

5/8

LINEAR LENGTH OF PIPING M (FT)


4-10 (13.1-32.8 )
10-22 (32.8-72.2)
2230.5(72.2-100)
Line Size (in. OD)
L
S
L
S
L
S
5/8
13/8
7/8
7/8
15/8
15/8
13/8
7/8
15/8
7/8
15/8

LEGEND
L Liquid Line S Suction Line
NOTES:
1. Pipe sizes are based on a 2 F loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length, shown for
each column, plus a 50% allowance for fittings.
3. Charge units with R-22 refrigerant in accordance with unit
installation instructions.
4. 38ARD has two independent refrigerant circuits and ref pipe sizes
for 38ARD series are given for each circuit

REFRIGERANT SPECIALTIES PART NUMBERS

LIQUID
LINE SIZE
(in.)

LIQUID LINE
SOLENOID VALVE
(LLSV)

LLSV COIL

SIGHT GLASS

FILTER DRIER

SUCTION LINE
ACCUMULATOR

200RB5T4M
200RB5T4M
200RB5T4M
200RB6T4M

AMG-24/50-60
AMG-24/50-60
AMG-24/50-60
AMG-24/50-60

AMI1TT3
AMI1TT3
AMI1TT4
AMI1TT4

P502-8304S
P502-8304S
P502-8304S
P502-8307S

S-7063S
S-7063S
S-7063S
S-7063

1/2
1/2

200RB5T4M Qty 2
200RB5T4M Qty 2

AMG-24/50-60 Qty 2
AMG-24/50-60 Qty 2

AMI1TT4 Qty 2
AMI1TT4 Qty 2

P502-8304S Qty 2
P502-8304S Qty 2

S-7063S Qty 2
S-7063S Qty 2

5/8

200RB5T5M Qty 2

AMG-24/50-60 Qty 2

AMI1TT5 Qty 2

P502-8304S Qty 2

S-7063S Qty 2

1/2

200RB6T4M Qty 2
200RB6T5M Qty 2

AMG-24/50-60 Qty 2
AMG-24/50-60 Qty 2

AMI1TT5 Qty 2
AMI1TT5 Qty 2

P502-8307S* Qty 2
P502-8307S* Qty 2

S-7063S Qty 2
S-7063S Qty 2

200RB6T5M Qty 2

AMG-24/50-60 Qty 2

AMI1TT5 Qty 2

P502-8307S* Qty 2

S-7063S Qty 2

3/8
3/8
1/2
1/2

5/8
5/8

19

Typical wiring schematic


38ARZ 230V/460V

20

Typical wiring schematic


38ARZ 380V

21

Typical wiring schematic


38ARD 230V/460V- (14-24)

22

Typical wiring schematic


38ARD 380V - (14-24)

23

Typical wiring schematic

38ARD (14-24)

24

Typical wiring schematic


38ARD028 230V,380V, 460V

25

Typical wiring schematic


38ARD028 230V,380V, 460V (cont.)

26

40RM007-034
6-25 Nominal Tons 60 Hz

Model number nomenclature - 40RM


4 0RM -

40RM.

016

SD

Commercial Packaged
Air Handler

Cooling Coil
-

E D

Factory-Installed Options

ED

Painted, Standard Motor and


Standard Drive

FD

Painted, Standard Motor and


Medium-Static Drive (Not available
for 028 size for 60 Hz units.

RD

Painted, Alternate Motor and


Medium-Static Drive (Available for
60 Hz sizes 028 only

WD

Painted, Alternate Motor and


High-Static Drive

Direct Expansion

Nominal Capacity
007
6 (21)
008
7-1/2 (26)
012
10 (35)
014
12-1/2 (43)

Tons (kW)
016
15 (52)
024
20 (70)
028
25 (87)
034
30 (105)

S: SAMCO
D: Double Skin
Expansion Device

B
Thermostatic Expansion Valves (40RM )

Voltage Designation (V-Ph-Hz)


3
5
6

8
9

208/230-1-60 (007-010 sizes only)


208/230-3-60
208/230/460-3-60 (all sizes 007-014; size 016
except YC and WD options)

460-3-60 (sizes 016 with YC or WD options and

all size 024-034 units)

230-3-50
400-3-50

Packaging
1
Standard Domestic
3
Export

Revision Number
0
Original Model
RD and WD option codes for all 034 size units and 008, 010 units with 208/230-1-60 power designate
standard motor and high-static drive.
NOTE: See the following table for the sizes available for each unit.

Quality Assurance

27

Physical data
40RM -

ENGLISH

UNIT 40RM
007SD
008SD
012SD
014SD
016SD
024SD
028SD
034SD
NOMINAL CAPACITY (Tons)
6

71/2
10

121/2
15

20

25

30

OPERATING WEIGHT (lb)


Base Unit (Double skin) with TXV
448

452

472

804

819

824

1188

1198

Plenum
97

97

97

140

140

140

180

180

FANS
Qty...Diam. (in.)
1...15

1...15

1...15

2...15

2...15

2...15

2...18

2...18

Nominal Airflow (cfm)


2400

3000

4000

5000

6000

8000

10,000
12,000
Airflow Range (cfm)
1800-3000
2250-3750
3000-5000
3750-6250
4500-7500
6000-10,000 7500-12,500 9000-15,000
Nominal Motor Hp (Standard Motor)*
208/230-1-60
1.3
2.4
208/230-3-60 and 460-3-60
2.4
2.4
2.4
2.9
3.7
5.0
7.5
10.0
575-3-60
1.0
2.0
2.0
3.0
3.0
5.0
7.5
10.0
230-3-50, 400-3-50
2.4
2.4
2.9
2.9
2.9
5.0
7.5
10.0
Motor Speed (rpm)
208/230-1-60
1725

1725

208/230-3-60 and 460-3-60


1725

1725

1725

1725

1725

1745

1745

1745

575-3-60
1725

1725

1725

1725

1725

1745

1755

1755

230-3-50, 400-3-50
1425

REFRIGERANT
R-22

Operating charge (lb)


3.0
2.0/2.0
2.5/2.5
3.5/3.5
4.5/4.5
5.0/5.0
3.0
1.5/1.5
(approx per circuit)
DIRECT-EXPANSION COIL
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig)
435

Face Area (sq ft)


6.67
8.33
10.0
13.25
17.67
19.88
24.86
29.83
No. of Splits
1

Split Type...Percentage
Face...50/50
No. of Circuits per Split
12

15

12

13

15

18

Rows...Fins/in.
3...15

3...15

3...17

3...15

3...15

3...17

3...15

3...15

STEAM COIL**
Max Working Pressure (psig at 400 F)
175

Total Face Area (sq ft)


6.67
6.67
6.67
13.33
13.33
13.33
15.0
15.0
Rows...Fins/in.
1...9

1...9

1...9

1...10

1...10

1...10

1...10

1...10

HOT WATER COIL**


Max Working Pressure (psig)
150

Total Face Area (sq ft)


6.67
6.67
6.67
13.33
13.33
13.33
15.0
15.0
Rows...Fins/in.
2...8.5

2...8.5

2...8.5

2...8.5

2...8.5

2...8.5

2...12.5

2...12.5

Water Volume
(gal)
8.3
13.9
14.3
(ft3)
1.1
1.85
1.90
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil - Suction (ODF)
1...11/8
1...11/8
2...11/8
2...11/8
2...11/8
2...11/8
2...13/8
2...13/8
DX Coil - Liquid Refrigerant (ODF)
1...5/8
2...5/8
Steam Coil, In (MPT)
1...21/2
1...21/2
Steam Coil, Out (MPT)
1...11/2
1...11/2
Hot Water Coil, In (MPT)
1...11/2
1...11/2
1...2

Hot Water Coil, Out (MPT)


1...11/2
1...11/2
1...2

1/4
Condensate (PVC)
1...1 ODM/1 IDF
FILTERS
Washable - Factory Supplied
4...16 x 20 x 1
4...20 x 24 x 1

Quantity...Size (in.)
4...16 x 24 x 1

4...16 x 24 x 1
4...20 x 25 x 1

Access Location
Front
LEGEND
DX - Direct Expansion
TXV - Thermostatic Expansion Valve
*Refer to alternate Fan Motor Data table, pages 54 and 55, for alternate motor data.
Units are shipped without refrigerant charge.
**Please contact your local Carrier sales office for availability.
Please contact your local Carrier sales office for the weights of single skin units.

28

Options and accessories


Factory-installed

options

Alternate fan motors and drives are available to pro

vide the widest possiblerange of performance.

Field-installed accessories

Two-row hot water coils have copper tubes mechani

cally bonded to aluminum plate fins and non-ferrous

headers.

One-row steam coil has copper tubes and aluminum fins.

The Inner Distributing Tube (IDT) design provides uniform

temperaturesacrossthecoil face.The steam coil hasa broad

operating pressure range; up to 175 psig (1207 kPag) at

400 F (204.4 C) and up to 300 psig (2069 kPag)at 300 F

(148.9 C). The IDT steam coils are especiallysuited to ap


plications where sub-freezingair enters the unit.
Electric r esistance heat coils have an open-wire design
and are mounted in a rigid frame. Safety cutouts for high
temperature conditions are standard. Terminal block for
single-point power connection is included.
Economizer (enthalpy contr olled) provides ventilation
air and ``free'' cooling if outside ambient temperature and
humidity are suitable. Can also be used with CO2 sensors
to help meet indoor air quality requirements.
Discharge plenum directs the air discharge directly into
the occupied space;integral horizontal and vertical louvers
enable redirection of airflow. Accessory is available un
painted or painted. Field assemblyrequired.
Standard units available from the factory are in

Double skin.

Return-air grille provides a protective barrier over the


return-air opening and givesa finished appearanceto units
installed in the occupied space. Accessory is availableun
painted or painted.
Subbase provides a stable, raised platform and room for
condensatedrain trap connection for verticalfloor-mounted
units. Accessoryis availableunpainted or painted.
Over head suspension package includes necessary brack
ets to support units in horizontal ceiling installations.
CO 2 sensors can be used in conjunction with the econ
omizer accessoryto help meet indoor air quality require
ments. The sensor signals the economizer to open when
the CO2 level in the spaceexceedsthe set point. A Carrier
Comfort Systemprogrammable thermostat can be usedto
override the sensorif the outsideair temperature is too high
or too low.
Carrier's line of ther mostats provide both program
mable and non-programmable capability with the new
Debonair line of commercial programmable thermostats,
the TEMP System controls offer communication capabil
ity with stagedheating and cooling, the Commercial Elec
tronic thermostats provide 7-day programmable capability
for economicalapplications,while the Non-Programmable
thermostatsoffer a multitude of stagedheating and cooling
subbaseoptions.
Condensate drain trap includesan overflow shutoff switch
that can be wired to turn off the unit if the trap becomes
plugged. Kit also includesa wire harnessthat can be con
nected to an alarm if desired. The transparent trap is de
signed for easy serviceand maintenance.

29

CARRIER THERMOSTATS
DEBONAIR COMMERCIAL PROGRAMMABLE
THERMOSTAT

COMMERCIAL ELECTRONIC
THERMOSTAT

Pm

AUTO

COOL
HEAT

TEMP SYSTEM THERMOSTAT

NON-PROGRAMMABLE THERMOSTAT
H

30

Options and accessories (cont)

40RM WITH DISCHARGE PLENUM,


RETURN-AIR GRILLE AND SUBBASE

40RM WITH HOT WATER OR STEAM COIL


HOT WATER OR
STEAM COIL

DISCHARGE
PLENUM

RETURN-AIR
GRILLE

SUBBASE
FAN
COIL
UNIT

40RM WITH ECONOMIZER

FAN COIL
UNIT

40RM WITH CONDENSATE TRAP

ECONOMIZER

31

Dimensions
40RM007SD-012SD
UNIT

40RM007SD
40RM008SD
40RM012SD

UNIT WEIGHT
lb (kg)
448 (203)
452 (205)
472 (214)

All the above mentioned weights


are for double skin units.

TXV -

Thermostatic Expansion
Valve

NOTES:
1. Dimensions in [
millimeters.
2.

] are in

Direction of airow .

3. Recommended clearance:
Rear: 39(76.2 mm) (28-69[762 mm]
with electric heat accessory)
Front: 28-69 (762 mm)
Right side: 28-69 (762 mm)
Left Side: 28-69 (762 mm)
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied and
field installed.

32

Dimensions (cont)
40RM014SD-024SD

TXV -

Thermostatic Expansion
Valve

NOTES:
1. Dimensions in [ ] are in
millimeters.
2.
Direction of airflow.
UNIT

3. Recommended clearance:
Rear: 39 (76.2 mm) (28-69
[762 mm] with electric heat
accessory)
Front: 28-69 (762 mm)
Right side: 28-69 (762 mm)
Left Side: 28-69 (762 mm)
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied
and field installed.
UNIT
40RM014SD
40RM016SD
40RM024SD

UNITWEIGHT
lb (kg)
804 (364)
819 (371)
824 (373)

All the weights men


tioned in the table
are for double skin
units.

33

Dimensions (cont)
40RM028SD,034SD

TXV -

Thermostatic Expansion
Valve

NOTES:
1. Dimensions in [ ] are in
millimeters.
2.
Direction of airflow.
3. Recommended clearance:
Rear: 39 (76.2 mm)
Front: 28-69 (762 mm)
Right side: 28-69 (762 mm)
Left Side: 28-69 (762 mm)
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied
and field installed.
UNIT
40RM028SD
40RM034SD

UNIT WEIGHT
lb (kg)
1188 (538)
1198 (542)

All the above mentioned weights are for


double skin units.

34

Dimensions (cont)

OVERHEAD SUSPENSION ACCESSORY


UNIT SIZES 007-012

UNIT SIZES 014-024

UNIT SIZES 028,034

NOTE: Dimensions in [

] are millimeters.

35

PLENUM, RETURN-AIR GRILLE, AND SUBBASE ACCESSORIES

UNIT SIZES 007-012

UNIT SIZES 014-024

NOTE: Dimensions in [

36

] are millimeters.

Dimensions (cont)

PLENUM, RETURN-AIR GRILLE, AND SUBBASE ACCESSORIES (cont)


UNIT SIZES 028,034

NOTE: Dimensions in [

] are millimeters.

37

HOT WATER AND STEAM COIL ACCESSORIES

UNIT SIZES 007-012

NOTE: Dimensions in [

] are millimeters.

DIMENSION
A
B
C
D
E
F
G

HOT WATER COIL


112 MPT [38.1]
112 MPT [38.1]
[60.3]
238
[123.8]
478
[54.0]
218
1-1114 [590.6]
3- 4 [1016.0]

STEAM COIL
112 MPT [38.1]
212 MPT [63.5]
318
[79.4]
318
[79.4]
4916
[115.8]
1-9
[584.2]
3-4 [1016.0]

DIMENSION
A
B
C
D
E
F
G

HOT WATER COIL


2 MPT [50.8]
2 MPT [50.8]
[60.3]
238
[123.8]
478
[54.0]
218
1-1114 [590.6]
6- 8 [2032.0]

STEAM COIL
112 MPT [38.1]
212 MPT [63.5]
318
[79.4]
318
[79.4]
4916
[115.8]
1-9
[584.2]
6-8 [2032.0]

UNIT SIZES 014-024

NOTE : Dimensions in [

38

] are millimeters.

40RM028SD,034SD

TXV -

Thermostatic Expansion
Valve

NOTES:
1. Dimensions in [ ] are in
millimeters.
2.
Direction of airflow.
3. Recommended clearance:
Rear: 39 (76.2 mm)
Front: 28-69 (762 mm)
Right side: 28-69 (762 mm)
Left Side: 28-69 (762 mm)
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied
and field installed.
UNIT
40RM028SD
40RM034SD

UNIT WEIGHT
lb (kg)
1188 (538)
1198 (542)

All the above mentioned weights are for


double skin units.

39

ECONOMIZER ACCESSORY

UNIT SIZES 007-012

UNIT SIZES 014-024

UNIT SIZES 028,034

NOTES:
1. For horizontal unit applications, economizer can be attached to end of unit opposite duct connections.
2. Dimensions in [ ] are millimeters.

40

Dimensions (cont)

ELECTRIC HEAT ACCESSORY

UNIT SIZES 007-012

UNIT SIZES 014-034

UNIT SIZE
014-024
028,034

A
1-314
[387.4]
1-338
[390.5]

B
4-638
[1381.1]
5-4716
[1636.8]

C
2516
[58.7]
2116
[26.9]

D
2-114
[641.4]
2-6316
[766.8]

E
1058
[269.9]
1-14
[311.2]

F
1-4
[406.4]
1-7
[482.6]

G
1-4516
[414.3]
1-4516
[414.0]

H
1-634
[476.3]
1-10
[558.8]

J
1-78
[327.0]
1-4716
[417.1]

NOTE: Dimensions in [ ] are millimeters.

41

Selection procedure (with example)

English (60 Hz)


Cooling (DX)
I Determine the cooling load and temperature and
quantity of air entering the evaporator.
Given:
Total Capacity . . . . . . . . . . . . . . . . . . . . 200,000 Btuh
Sensible Heat Capacity . . . . . . . . . . . . . 130,000 Btuh
Air Temperature Entering Indoor
Coil . . . . . . . . . . . . . . . . . . . . . . . . 80 F db, 67 F wb

Air Quantity Entering Indoor Coil . . . . . . . 6000 cfm

Ductwork Static Pressure Loss . . . . . . . . . . 0.8 in. wg

Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . 230-3-60

II Determine unit selection and coil refrigerant


temperature.
Enter the Cooling Capacities table at 6000 cfm. Se
lect a 40RM016 unit which has a total capacity of
207,000 and 174,000 Btuh at 40 and 45 F coil re
frigerant temperature, respectively. By interpolation,
coil refrigerant temperature of 41.1 F is needed to give
a total capacity of 200,000 Btuh. Sensible capacity is
approximately 149,000 Btuh. Cooling load is
satised.

42

Fan
I Determine fan speed and brake horsepower:
From the Accessory Pressure Drop table, read a loss
of 0.23 in. wg for a hot water coil at 6000 cfm.
External static pressure = 0.80 + 0.23
= 1.03 in. wg
Enter 40RM016 Fan Performance table at 6000 cfm
and 1.03 in. wg. Interpolate and determine fan speed
of 866 rpm and 2.7 bhp.
II Determine motor and drive.
Enter the fan motor data tables on page 54, and nd
that the 230 v standard motor for a 40RM016 unit is
rated at 3.7 Hp. Since the bhp required is 2.7, a stand
ard motor satises the requirement and should be used.
Next, nd the type of drive that satises the 866 rpm
requirement in the Drive Data tables on pages 59,60 .
For a 40RM016 unit, the Medium-Static Drive table
on page 59 shows an rpm range of 742 to 943. Since
the rpm required is 866, the medium-static drive sat
ises the requirement and should be used. Select the
standard motor and medium-static drive combination
(option code HC or FD).
To select an outdoor unit for this 40RM016 indoor
section, refer to the Combination Rating sheets for
Carrier condensing units in the condensing unit Prod
uct Data Digest, or consult the Carrier Electronic
Catalog.

Performance data (cont)


FAN PERFORMANCE DATA 0.0-1.2 in. wg ESP 60 Hz, ENGLISH

Bhp

EXTERNAL STATIC PRESSURE (in. wg)


0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp

442
483
526
570
616

0.32
0.42
0.53
0.67
0.82

534
569
606
646
687

0.42
0.53
0.64
0.78
0.94

611
642
676
712
750

0.52
0.63
0.75
0.89
1.05

678
708
739
773
808

0.61
0.73
0.86
1.00
1.16

0.32
0.45
0.62
0.82
1.03

472
516
569
624
673

0.44
0.57
0.75
0.95
1.17

560
599
645
695
740

0.55
0.68
0.86
1.08
1.29

634
669
712
758
800

0.65
0.79
0.98
1.20
1.42

700
732
773
815
855

444
518
592
666
740

0.58
0.82
1.11
1.44
1.83

541
604
669
735
803

0.71
0.95
1.25
1.59
1.98

621
677
736
797
861

0.83
1.08
1.38
1.72
2.12

691
742
797
854
914

0.94
1.20
1.51
1.86
2.26

40RM
014

3,750
4,300
5,000
5,700
6,250

363
416
484
552
605

0.37
0.53
0.81
1.17
1.51

475
517
573
631
678

0.58
0.78
1.08
1.47
1.83

566
601
650
702
744

0.80
1.02
1.35
1.76
2.15

645
676
719
766
805

40RM
016

4,500
5,300
6,000
6,800
7,500

391
460
521
590
651

0.51
0.80
1.13
1.60
2.10

495
551
602
663
718

0.75
1.08
1.43
1.93
2.45

581
629
675
730
779

1.00
1.35
1.73
2.26
2.81

40RM
024

6,000
7,000
8,000
9,000
10,000

503
586
670
754
838

1.07
1.64
2.37
3.28
4.39

587
660
735
812
891

1.37
1.98
2.74
3.69
4.83

661
726
795
867
941

40RM
028

7,500
8,750
10,000
11,250
12,500

412
481
549
618
687

1.15
1.76
2.55
3.52
4.71

492
550
610
672
735

1.53
2.17
2.99
4.00
5.22

40RM
034

9,000
10,500
12,000
13,500
15,000

471
550
628
707
785

1.78
2.72
3.93
5.44
7.27

539
608
679
752
826

2.17
3.15
4.40
5.94
7.81

UNIT

AIRFLOW
(Cfm)

40RM
007

1,800
2,100
2,400
2,700
3,000

Bhp

Rpm

320
373
427
480
533

0.22
0.31
0.42
0.54
0.69

2,250
2,600
3,000
3,400
3,750

359
415
478
542
598

40RM
012

3,000
3,500
4,000
4,500
5,000

40RM
008

Rpm

0.0

0.2

Rpm

1.0

1.2

Bhp

Rpm

739
767
796
828
862

0.70
0.82
0.96
1.11
1.28

795
821
849
880
912

Bhp
0.80
0.92
1.06
1.21
1.39

0.75
0.90
1.09
1.31
1.60

759
790
828
869
906

0.86
1.01
1.20
1.43
1.66

814
843
879
918
954

0.96
1.11
1.32
1.55
1.78

753
801
853
907
964

1.05
1.32
1.63
1.99
2.39

809
855
904
956
1010

1.17
1.44
1.75
2.12
2.53

862
906
953
1003
1055

1.28
1.56
1.88
2.24
2.66

1.02
1.26
1.62
2.06
2.47

715
743
782
826
862

1.24
1.50
1.89
2.36
2.79

779
805
841
881
915

1.47
1.74
2.16
2.66
3.11

839
862
896
934
966

1.69
1.99
2.44
2.96
3.43

657
700
741
791
837

1.25
1.63
2.04
2.59
3.16

725
764
801
847
890

1.50
1.91
2.34
2.92
3.52

787
823
858
901
941

1.76
2.20
2.65
3.26
3.88

845
878
911
951
990

2.02
2.48
2.96
3.60
4.24

1.67
2.31
3.12
4.09
5.27

727
787
851
918
988

1.97
2.65
3.49
4.50
5.70

789
844
904
967
1034

2.28
2.99
3.86
4.90
6.14

846
898
954
1014
1077

2.59
3.33
4.23
5.31
6.85

900
948
1001
1059
1120

2.90
3.67
4.61
5.72
7.02

568
616
669
725
783

2.00
2.66
3.50
4.53
5.78

640
680
726
777
830

2.56
3.22
4.07
5.12
6.38

710
742
782
827
876

3.22
3.86
4.70
5.76
7.04

776
802
836
876
922

3.98
4.58
5.40
6.45
7.74

840
860
889
925
966

4.83
5.38
6.17
7.21
8.49

604
665
730
797
867

2.63
3.64
4.92
6.49
8.39

667
720
779
841
907

3.17
4.18
5.48
7.08
9.01

728
774
827
885
947

3.78
4.79
6.09
7.71
9.66

788
827
874
928
986

4.46
5.45
6.76
8.38
10.35

845
878
921
970
1024

5.22
6.18
7.47
9.10
11.07

See Legend and Notes on page 4 0 .

43

FAN PERFORMANCE DATA 1.4-2.4 in. wg ESP 60 Hz, ENGLISH


UNIT

AIRFLOW
(Cfm)

40RM
007

1,800
2,100
2,400
2,700
3,000

Rpm

1.4

1.6

EXTERNAL STATIC PRESSURE (in. wg)


1.8
2.0
2.2
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp

Rpm

847
872
899
928
959

0.89
1.02
1.16
1.32
1.49

896
920
946
974
1004

0.98
1.11
1.26
1.42
1.60

942
965
990
1018
1046

1.07
1.21
1.36
1.52
1.71

986
1008
1033
1059
1087

1.16
1.30
1.46
1.63
1.81

1027
1050
1073
1099
1126

1.25
1.40
1.55
1.73
1.92

40RM
008

2,250
2,600
3,000
3,400
3,750

865
893
928
965
1000

1.06
1.22
1.43
1.66
1.90

913
940
973
1010
1043

1.16
1.33
1.54
1.78
2.02

958
984
1017
1052
1084

1.27
1.43
1.65
1.89
2.13

1001
1027
1058
1092
1124

1.37
1.54
1.76
2.00
2.25

1042
1067
1098
1131
1162

1.47
1.65
1.87
2.12
2.37

40RM
012

3,000
3,500
4,000
4,500
5,000

911
953
999
1047
1097

1.39
1.67
2.00
2.37
2.79

958
998
1042
1089
1138

1.50
1.79
2.12
2.50
2.92

1002
1041
1084
1129
1177

1.61
1.90
2.24
2.62
3.05

1044
1082
1124
1168

1.72
2.02
2.36
2.74

1084
1122
1162

1.83
2.13
2.48

1123
1159
1199

1.94
2.25
2.60

40RM
014

3,750
4,300
5,000
5,700
6,250

894
916
948
984
1014

1.91
2.23
2.71
3.25
3.75

947
967
997
1031
1060

2.14
2.48
2.98
3.55
4.07

996
1016
1044
1076
1104

2.37
2.73
3.26
3.86
4.39

1044
1062
1089
1120
1147

2.60
2.98
3.53
4.16
4.71

1089

1107
1133
1162
1188

2.83

3.24
3.81
4.46
5.03

40RM
016

4,500
5,300
6,000
6,800
7,500

899
930
961
999
1036

2.29
2.78
3.28
3.94
4.60

951
980
1009
1045
1080

2.56
3.08
3.60
4.28
4.97

999
1027
1055
1089
1123

2.84
3.38
3.92
4.63
5.34

1046
1072
1098
1132
1164

3.12
3.68
4.24
4.98
5.71

40RM
024

6,000
7,000
8,000
9,000
10,000

950
996
1047
1102
1160

3.21
4.02
4.99
6.13
7.46

999
1042
1091
1143
1200

3.53
4.37
5.37
6.54
7.91

1045
1086
1133
1183

3.85
4.72
5.75
6.96

1089
1129
1173

4.17
5.07
6.13

1091
1116
1141
1173

1131
1169

3.41
3.99
4.57
5.33

4.50
5.43

1133
1157
1181

1172

3.70
4.30
4.91

4.83

40RM
028

7,500
8,750
10,000
11,250
12,500

903
917
941
972
1010

5.79
6.26
7.01
8.02
9.29

963
972
991
1019
1053

6.83
7.22
7.91
8.89
10.15

1021
1025
1040
1064
1095

7.98
8.26
8.89
9.83
11.05

1078
1078
1089

9.21
9.38
9.93

40RM
034

9,000
10,500
12,000
13,500
15,000

901
928
966
1011
1062

6.07
6.98
8.24
9.86
11.84

955
978
1011
1052

6.98
7.84
9.07
10.67

1008
1026
1055
1092

7.98
8.76
9.95
11.52

1060
1073
1098

9.05
9.74
10.88

See Legend and Notes on page 40.

44

Rpm

2.4

Bhp

Bhp

Performance data (cont)


FACTOR Y-SUPPLIED FILTER PRESSURE DROP
- ENGLISH

40RM
007

AIRFLOW
(Cfm)
1,800
2,400
3,000

PRESSURE DROP
(in. wg)
0.05
0.08
0.11

40RM
008

2,250
3,000
3,750

0.07
0.11
0.15

40RM
012

3,000
4,000
5,000

0.11
0.17
0.23

40RM
014

3,750
5,000
6,250

0.06
0.10
0.13

40RM
016

4,500
6,000
7,500

0.08
0.12
0.17

40RM
024

6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40

UNIT

40RM
028
40RM
034

LEGEND
Bhp ESP -

Brake Horsepower Input to Fan


External Static Pressure

Bold indicates field supplied drive is required.

Plain type indicates standard motor and standard drive.

Underline indicates a different motor and drive combination other than

the standard motor and standard drive combination is required. Refer to

fan motor and drive tables, pages 54-60, to complete selection.


NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 1-in.
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. For 60 Hz units, the medium-static drive and standard motor combi
nation is not available for 028 size.

ACCESSORY PLENUM AIR THROW DATA ENGLISH


(Ft)
VANE DEFLECTION
Straight
2112
45

UNIT

AIRFLOW
(Cfm)

40RM
007

2,400

39

33

24

40RM
008

3,000

45

38

28

40RM
012

4,000

55

46

33

40RM
014

5,000

45

38

28

40RM
016

6,000

50

43

31

40RM
024

8,000

60

51

37

40RM
028

10,000

76

65

47

40RM
034

12,000

85

72

52

NOTE: Throw distances shown are for 75 fpm terminal velocity. Use
the following multipliers to determine throw values for other terminal
velocities.
TERMINAL VELOCITY
(Fpm)
50
100
150

THROW FACTOR
X 1.50
X 0.75
X 0.50

45

ACCESSORY PRESSURE DROP ENGLISH


(in. wg)
HEATING COILS
Steam
0.10
0.16
0.23

UNIT

AIRFLOW
(Cfm)

DISCHARGE
PLENUM

RETURN AIR
GRILLE

40RM
007

1,800
2,400
3,000

0.06
0.10
0.14

0.01
0.01
0.02

Hot Water
0.10
0.16
0.23

40RM
008

2,250
3,000
3,750

0.09
0.14
0.21

0.01
0.02
0.03

0.15
0.23
0.35

0.15
0.23
0.35

0.06
0.10
0.15

0.06
0.09
0.15

40RM
012

3,000
4,000
5,000

0.14
0.22
0.32

0.02
0.04
0.06

0.23
0.37
0.53

0.23
0.37
0.53

0.10
0.17
0.26

0.09
0.17
0.28

40RM
014

3,750
5,000
6,250

0.07
0.12
0.17

0.01
0.02
0.02

0.11
0.17
0.25

0.11
0.17
0.25

0.04
0.07
0.11

0.05
0.07
0.11

40RM
016

4,500
6,000
7,500

0.10
0.16
0.23

0.01
0.02
0.03

0.15
0.23
0.33

0.15
0.23
0.33

0.06
0.10
0.15

0.06
0.09
0.15

6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

0.16
0.26
0.37
0.15
0.24
0.34
0.20
0.32
0.46

0.02
0.04
0.06
0.02
0.03
0.05
0.03
0.05
0.07

0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85

0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85

0.10
0.17
0.26
0.09
0.16
0.24
0.13
0.22
0.34

0.09
0.17
0.28
0.06
0.09
0.14
0.08
0.14
0.21

40RM
024
40RM
028
40RM
034

46

Electric
0.04
0.06
0.10

ECONOMIZER
0.05
0.07
0.09

Electrical data

STANDARD MOTORS
UNIT

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

V*-PH-Hz

VOLTAGE
LIMITS

208/230-1-60
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-1-60
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50

FAN MOTOR
Hp (kW)

FLA

187-253
187-253
414-506
518-632
207-253
360-440
187-253
187-253
414-506
518-632
207-253
360-440

1.3
2.4
2.4
1.0
2.4
2.4
2.4
2.4
2.4
2.0
2.4
2.4

7.6
5.2
2.6
1.4
5.2
2.6
11.0
5.2
2.6
2.3
5.2
2.6

187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440

2.4 (1.79)
2.4 (1.79)
2.0 (1.49)
2.9 (2.16)
2.9 (2.16)
2.9 (2.16)
2.9 (2.16)
3.0 (2.24)
2.9 (2.16)
2.9 (2.16)
3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
2.9 (2.16)
2.9 (2.16)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)

(0.97)
(1.79)
(1.79)
(0.75)
(1.79)
(1.79)
(1.79)
(1.79)
(1.79)
(1.49)
(1.79)
(1.79)

5.2
2.6
2.3
7.5
3.4
7.5
3.4
3.8
7.5
3.4
10.2
4.8
3.8
7.5
3.4
15.3/12.8
6.4
5.1
15.2
7.6
22.4/19.4
9.7
7.8
22.8
11.4
29.3/26.8
13.4
10.3
32.2
16.1

POWER SUPPLY
Minimum
Circuit
MOCP
Amps
9.5
15
6.5
15
3.3
15
8.0
15
6.5
15
3.3
15
13.8
20
6.5
15
3.3
15
2.9
15
6.5
15
3.3
15
6.5
3.3
2.9
9.4
4.3
9.4
4.3
4.8
9.4
4.3
12.8
6.0
4.8
9.4
4.3
19.1/16.0
8.0
6.4
19.0
9.5
28.0/24.3
12.1
9.8
28.5
14.3
36.6/33.5
16.8
12.9
40.3
20.1

20
15
15
15
15
15
15
15
15
15
20
15
15
15
15
30/25
15
15
30
15
50/40
20
15
50
25
60/60
30
20
70
30

See Legend and Notes on page 43.

47

ALTERNATE MOTORS
UNIT

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

V*-PH-Hz

VOLTAGE
LIMITS

208/230-1-60
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-1-60
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50
208/230-3-60
460-3-60
575-3-60
230-3-50
400-3-50

Hp (kW)

FLA

187-253
187-253
414-506
518-632
207-253
360-440
187-253
187-253
414-506
518-632
207-253
360-440

2.4
2.9
2.9
2.0
2.4
2.4
2.4
2.9
2.9
3.0
2.9
2.9

11.0
7.5
3.4
2.3
5.2
2.6
11.0
7.5
3.4
3.8
7.5
3.4

187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440
187-253
414-506
518-632
207-253
360-440

3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
5.0 (3.73)
5.0 (3.73)
3.7 (2.76)
3.7 (2.76)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)

LEGEND
FLA
Full Load Amps
MOCP Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal voltages
shown. Voltages should not exceed the limits shown in the Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in accordance
with NEC (National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percentage of voltage
imbalance.
% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 400-3-50.

AB = 393 v

BC = 403 v

AC = 396 v

393 + 403 + 396


Average Voltage =
3
1192
=
3
= 397

48

FAN MOTOR

(1.79)
(2.16)
(2.16)
(1.49)
(1.79)
(1.79)
(1.79)
(2.16)
(2.16)
(2.24)
(2.16)
(2.16)

10.2
4.8
3.8
15.2
7.6
10.2
4.8
5.1
15.2
7.6
15.3/12.8
6.4
5.1
15.2
7.6
22.4/19.4
9.7
7.8
22.8
11.4
29.3/26.8
13.4
10.3
32.2
16.1

POWER SUPPLY
Minimum
Circuit
MOCP
Amps
13.8
20
9.4
15
4.3
15
2.9
15
6.5
15
3.3
15
13.8
15
9.4
15
4.3
15
4.8
15
9.4
15
4.3
15
12.8
6.0
4.8
19.0
9.5
12.7
6.0
6.4
19.0
9.5
19.1/16.0
8.0
6.4
19.0
9.5
28.0/24.3
12.1
9.8
28.5
14.3
36.6/33.5
16.8
12.9
40.3
20.1

20
15
15
30
15
20
15
15
30
15
30/25
15
15
30
15
50/40
20
15
50
25
60/60
30
20
60
30

Determine maximum deviation from average voltage.


(AB) 397 393 = 4 v
(BC) 403 397 = 6 v
(AC) 397 396 = 1 v
Maximum deviation is 6 v.
Determine percent voltage imbalance.
6
397

% Voltage Imbalance = 100 x


= 1.5%

This amount of phase imbalance is satisfactory because it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

Electrical data (cont)


ELECTRIC HEATER DATA
HEATER
PART NO.

UNIT

V-PH-Hz

208-3-60

CAELHEAT001A00

240-3-60

240-3-50
480-3-60
CAELHEAT002A00
400-3-50
CAELHEAT003A00

575-3-60

208-3-60

CAELHEAT004A00

240-3-60
40RM007-012

240-3-50
480-3-60

CAELHEAT005A00
400-3-50
CAELHEAT006A00

575-3-60

208-3-60

CAELHEAT007A00

240-3-60

240-3-50
480-3-60
CAELHEAT008A00
400-3-50
CAELHEAT009A00

575-3-60

FAN MOTOR
Hp
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
2.4
2.9
5.0
2.4
2.9
3.7
2.4
2.9
5.0
1.0
2.0
3.0
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
2.4
2.9
5.0
2.4
2.9
3.7
2.4
2.9
5.0
1.0
2.0
3.0
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
2.4
2.9
5.0
2.4
2.9
3.7
2.4
2.9
5.0
1.0
2.0
3.0

kW
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
3.73
1.79
2.16
2.76
1.79
2.16
3.73
0.75
1.49
2.24
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
3.73
1.79
2.16
2.76
1.79
2.16
3.73
0.75
1.49
2.24
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
3.73
1.79
2.16
2.76
1.79
2.16
3.73
0.75
1.49
2.24

FLA
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
5.2
7.5
15.2
2.6
3.4
4.8
2.6
3.4
7.6
1.4
2.3
3.8
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
5.2
7.5
15.2
2.6
3.4
4.8
2.6
3.4
7.6
1.4
2.3
3.8
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
5.2
7.5
15.2
2.6
3.4
4.8
2.6
3.4
7.6
1.4
2.3
3.8

Nominal
Capacity (kW)
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1
Stage 2
Total
3.8

3.8
3.8

3.8
3.8

3.8
3.8

3.8
3.8

3.8
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
5.0

5.0
3.5

3.5
3.5

3.5
3.5

3.5
5.0

5.0
5.0

5.0
5.0

5.0
7.5

7.5
7.5

7.5
7.5

7.5
7.5

7.5
7.5

7.5
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
6.9

6.9
6.9

6.9
6.9

6.9
10.0

10.0
10.0

10.0
10.0

10.0
11.3

11.3
11.3

11.3
11.3

11.3
11.3

11.3
11.3

11.3
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
10.4

10.4
10.4

10.4
10.4

10.4
15.0

15.0
15.0

15.0
15.0

15.0

FLA
10.4
10.4
10.4
10.4
10.4
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
6.00
6.00
6.00
5.00
5.00
5.00
5.00
5.00
5.00
20.8
20.8
20.8
20.8
20.8
24.1
24.1
24.1
24.1
24.1
24.1
24.1
24.1
12.0
12.0
12.0
10.0
10.0
10.0
10.0
10.0
10.0
31.3
31.3
31.3
31.3
31.3
36.1
36.1
36.1
36.1
36.1
36.1
36.1
36.1
18.0
18.0
18.0
15.0
15.0
15.0
15.1
15.1
15.1

MCA*

MOCP*

22.5
26.8
19.5
22.4
25.8
24.5
28.8
21.5
24.4
27.8
21.5
24.4
34.0
10.8
11.8
13.5
9.5
10.5
15.8
8.0
9.2
11.0
35.6
39.8
32.6
35.4
38.8
39.6
43.8
36.6
39.4
42.8
36.6
39.4
49.1
18.3
19.3
21.0
15.8
16.8
22.0
14.3
15.4
17.3
48.6
52.9
45.6
48.5
51.9
54.6
58.9
51.6
54.5
57.9
51.6
54.5
64.1
25.8
26.8
28.6
22.0
23.0
28.3
20.6
21.7
23.6

25
35
20
25
30
25
35
25
25
30
25
25
40
15
15
15
15
15
20
15
15
15
40
40
35
40
40
40
50
40
40
50
40
40
50
20
20
25
20
20
25
15
20
20
50
60
50
50
60
60
60
60
60
60
60
60
70
30
30
30
25
25
30
25
25
25

49

ELECTRIC HEATER DATA (cont)


HEATER
PART NO.

UNIT

V-PH-Hz

208-3-60

CAELHEAT010A00

240-3-60
40RM007-012

240-3-50
480-3-60

CAELHEAT011A00
400-3-50
CAELHEAT012A00

575-3-60

208-3-60

CAELHEAT013A00

240-3-60
40RM008,012

240-3-50
480-3-60

CAELHEAT014A00
400-3-50
CAELHEAT015A00

FLA
Hp
MCA
MOCP

575-3-60

FAN MOTOR
Hp
1.3
2.4
2.4
2.9
3.7
1.3
2.4
2.4
2.9
3.7
2.4
2.9
5.0
2.4
2.9
3.7
2.4
2.9
5.0
1.0
2.0
3.0
2.4
2.4
2.9
3.7
2.4
2.4
2.9
3.7
2.4
2.9
5.0
2.4
2.9
3.7
2.4
2.9
5.0
2.0
3.0

kW
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
3.73
1.79
2.16
2.76
1.79
2.16
3.73
0.75
1.49
2.24
1.79
1.79
2.16
2.76
1.79
1.79
2.16
2.76
1.79
2.16
3.73
1.79
2.16
2.76
1.79
2.16
3.73
1.49
2.24

FLA
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
5.2
7.5
15.2
2.6
3.4
4.8
2.6
3.4
7.6
1.4
2.3
3.8
11.0
5.2
7.5
10.2
11.0
5.2
7.5
10.2
5.2
7.5
15.2
2.6
3.4
4.8
2.6
3.4
7.6
2.3
3.8

LEGEND
Full Load Amps
Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection (Amps)

*Values shown are for single-point connection of electric heat accessory and air
handler.
Single-phase motors. All other motors are 3-phase.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine
heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v capacity (kW) by the factor shown in the table below for the unit voltage.
HEATER
ACTUAL HEATER VOLTAGE
RATING
VOLTAGE 200 208 230 240 400 440 460 480 550
240
0.694 0.751 0.918 1

480

0.694 0.84 0.918 1

575

0.915

50

575 600

1 1.089

Nominal
Capacity (kW)
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1
Stage 2
Total
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
10.4
6.9
17.4
10.4
6.9
17.4
10.4
6.9
17.4
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
11.3
26.3
15.0
11.3
26.3
15.0
11.3
26.3
15.0
11.3
26.3
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
13.9
10.4
24.3
13.9
10.4
24.3
13.9
10.4
24.3
20.0
15.0
35.0
20.0
15.0
35.0

FLA
52.1
52.1
52.1
52.1
52.1
60.1
60.1
60.1
60.1
60.1
60.1
60.1
60.1
30.1
30.1
30.1
25.1
25.1
25.1
25.1
25.1
25.1
73.0
73.0
73.0
73.0
84.2
84.2
84.2
84.2
84.2
84.2
84.2
42.1
42.1
42.1
35.1
35.1
35.1
35.1
35.1

MCA*

MOCP*

74.7
78.9
71.7
74.5
77.9
84.7
88.9
81.7
84.6
87.9
81.7
84.6
94.2
40.8
41.8
43.6
34.6
35.6
40.8
33.1
34.3
36.1
105.0
97.7
100.6
104.0
119.0
111.7
114.6
118.0
111.7
114.6
124.2
55.9
56.9
58.6
47.1
48.1
53.4
46.8
48.7

80
80
80
80
80
90
90
90
90
90
90
90
100
50
50
50
25
40
50
35
35
40
110
100
110
110
125
125
125
125
125
125
125
60
60
60
50
50
60
50
50

2. The following equation converts kW of heat energy to Btuh:


kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total external static
pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied
motors.

Electrical data (cont)


ELECTRIC HEATER DATA (cont)
HEATER
PART NO.

UNIT

208-3-60

CAELHEAT016A00

240-3-60

240-3-50

480-3-60
CAELHEAT017A00
400-3-50
CAELHEAT018A00

575-3-60

208-3-60

CAELHEAT019A00

240-3-60

40RM014-024

240-3-50

480-3-60
CAELHEAT020A00
400-3-50
CAELHEAT021A00

575-3-60

208-3-60

CAELHEAT022A00

240-3-60

240-3-50

480-3-60
CAELHEAT023A00
400-3-50
CAELHEAT024A00

FAN MOTOR

V-PH-Hz

575-3-60

Hp
2.9
3.7
5.0
7.5
2.9
3.7
5.0
7.5
2.9
5.0
7.5
2.9
3.7
5.0
7.5
2.9
5.0
7.5
3.0
5.0
7.5
2.9
3.7
5.0
7.5
2.9
3.7
5.0
7.5
2.9
5.0
7.5
2.9
3.7
5.0
7.5
2.9
5.0
7.5
3.0
5.0
7.5
2.9
3.7
5.0
7.5
2.9
3.7
5.0
7.5
2.9
5.0
7.5
2.9
3.7
5.0
7.5
2.9
5.0
7.5
3.0
5.0
7.5

kW
2.16
2.76
3.73
5.59
2.16
2.76
3.73
5.59
2.16
3.73
5.59
2.16
2.76
3.73
5.59
2.16
3.73
5.59
2.24
3.73
5.59
2.16
2.76
3.73
5.59
2.16
2.76
3.73
5.59
2.16
3.73
5.59
2.16
2.76
3.73
5.59
2.16
3.73
5.59
2.24
3.73
5.59
2.16
2.76
3.73
5.59
2.16
2.76
3.73
5.59
2.16
3.73
5.59
2.16
2.76
3.73
5.59
2.16
3.73
5.59
2.24
3.73
5.59

FLA
7.5
10.2
15.3
22.4
7.5
10.2
12.8
19.4
7.5
15.2
22.8
3.4
4.8
6.4
9.7
3.4
7.6
11.4
3.8
5.1
7.8
7.5
10.2
15.3
22.4
7.5
10.2
12.8
19.4
7.5
15.2
22.8
3.4
4.8
6.4
9.7
3.4
7.6
11.4
3.8
5.1
7.8
7.5
10.2
15.3
22.4
7.5
10.2
12.8
19.4
7.5
15.2
22.8
3.4
4.8
6.4
9.7
3.4
7.6
11.4
3.8
5.1
7.8

Nominal
Capacity (kW)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1
Stage 2
Total
7.5

7.5
7.5

7.5
7.5

7.5
7.5

7.5
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
10.0

10.0
6.9

6.9
6.9

6.9
6.9

6.9
10.0

10.0
10.0

10.0
10.0

10.0
15.0

15.0
15.0

15.0
15.0

15.0
15.0

15.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
13.9

13.9
13.9

13.9
13.9

13.9
20.0

20.0
20.0

20.0
20.0

20.0
15.0
7.5
22.5
15.0
7.5
22.5
15.0
7.5
22.5
15.0
7.5
22.5
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
13.9
6.9
20.8
13.9
7.9
20.8
13.9
7.9
20.8
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0

FLA
20.8
20.8
20.8
20.8
24.1
24.1
24.1
24.1
24.1
24.1
24.1
12.0
12.0
12.0
12.0
10.0
10.0
10.0
10.0
10.0
10.0
41.7
41.7
41.7
41.7
48.1
48.1
48.1
48.1
48.1
48.1
48.1
24.1
24.1
24.1
24.1
20.0
20.0
20.0
20.1
20.1
20.1
62.5
62.5
62.5
62.5
72.2
72.2
72.2
72.2
72.2
72.2
72.2
36.1
36.1
36.1
36.1
30.1
30.1
30.1
30.1
30.1
30.1

MCA*

MOCP*

35.4
38.8
45.1
54.4
39.4
42.8
46.1
54.4
39.4
49.1
58.6
19.3
21.0
23.0
27.2
16.8
22.0
26.8
17.3
19.6
22.1
61.5
65.4
71.1
79.6
69.5
73.4
76.1
84.4
69.5
79.1
86.4
34.3
36.1
39.1
43.2
29.3
45.1
49.2
29.9
31.5
34.9
87.5
90.9
97.2
106.2
99.6
103.0
106.2
114.5
99.6
109.2
118.7
49.4
51.1
53.1
57.2
41.8
47.1
51.8
42.4
44.0
47.4

40
40
50
70
40
50
50
70
40
50
70
20
25
25
30
20
25
35
20
20
25
70
70
80
90
70
80
80
90
70
80
90
35
40
40
50
30
50
50
30
35
35
90
100
100
110
100
110
110
125
100
110
125
50
60
60
60
50
50
60
50
50
50

51

ELECTRIC HEATER DATA (cont)


HEATER
PART NO.

UNIT

V-PH-Hz
208-3-60

CAELHEAT025A00

240-3-60

40RM016,024

240-3-50
480-3-60

CAELHEAT026A00
400-3-50
CAELHEAT027A00

575-3-60
208-3-60

CAELHEAT028A00

240-3-60
240-3-50
480-3-60

CAELHEAT029A00
CAELHEAT030A00

400-3-50
40RM028,034

575-3-60
208-3-60

CAELHEAT031A00

240-3-60
240-3-50

CAELHEAT032A00
CAELHEAT033A00

FLA
Hp
MCA
MOCP

480-3-60
400-3-50
575-3-60

FAN MOTOR
Hp
3.7
5.0
7.5
3.7
5.0
7.5
2.9
5.0
7.5
3.7
5.0
7.5
2.9
5.0
7.5
3.0
5.0
7.5
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0

kW
2.76
3.73
5.59
2.76
3.73
5.59
2.16
3.73
5.59
2.76
3.73
5.59
2.16
3.73
5.59
2.24
3.73
5.59
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46

FLA
10.2
15.3
22.4
10.2
12.8
19.4
7.5
15.2
22.8
4.8
6.4
9.7
3.4
7.6
11.4
3.8
5.1
7.8
22.4
29.3
19.4
26.8
22.8
32.2
9.7
13.4
11.4
16.1
7.8
10.3
22.4
29.3
19.4
26.8
22.8
32.2
9.7
13.4
11.4
16.1
7.8
10.3

LEGEND
Full Load Amps
Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection (Amps)

*Values shown are for single-point connection of electric heat accessory and air
handler.
Single-phase motors. All other motors are 3-phase.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine
heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v capacity (kW) by the factor shown in the table below for the unit voltage.
HEATER
ACTUAL HEATER VOLTAGE
RATING
VOLTAGE 200 208 230 240 400 440 460 480 550
240
0.694 0.751 0.918 1

480

0.694 0.84 0.918 1

575

0.915

52

575 600

1 1.089

Nominal
Capacity (kW)
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
20
20
20
20
20
20
20
20
20
20
20
20
40
40
40
40
40
40
40
40
40
40
40
40

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1
Stage 2
Total
22.6
15.0
37.6
22.6
15.0
37.6
22.6
15.0
37.6
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
20.8
13.9
34.7
20.8
13.9
34.7
20.8
13.9
34.7
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
15.0

15.0
15.0

15.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
20.0

20.0
13.9

13.9
13.9

13.9
20.0

20.0
20.0

20.0
15.0
15.0
30.0
15.0
15.0
30.0
20.0
20.0
40.0
20.0
20.0
40.0
20.0
20.0
40.0
20.0
20.0
40.0
20.0
20.0
40.0
20.0
20.0
40.0
13.9
13.9
27.8
13.9
13.9
27.8
20.0
20.0
40.0
20.0
20.0
40.0

FLA
104.3
104.3
104.3
120.3
120.3
120.3
120.3
120.3
120.3
60.1
60.1
60.1
50.1
50.1
50.1
50.2
50.2
50.2
41.7
41.7
48.1
48.1
48.1
48.1
24.1
24.1
20.0
20.0
20.1
20.1
83.4
83.4
96.2
96.2
96.2
96.2
48.1
48.1
40.1
40.1
40.2
40.2

MCA*

MOCP*

143.1
149.5
158.4
163.1
166.4
174.6
159.7
169.4
178.9
81.2
83.2
87.3
66.9
72.1
76.9
67.5
69.1
72.5
80.1
88.7
84.3
94.0
88.6
100.4
42.2
46.8
39.3
45.2
34.9
38.0
132.2
140.9
144.5
153.8
148.8
160.5
72.3
76.9
64.4
70.2
60.0
63.1

150
150
175
175
175
200
175
175
200
90
90
90
70
80
80
70
70
80
90
100
90
110
90
110
50
50
40
50
35
40
150
150
150
175
150
175
80
80
70
80
60
70

2. The following equation converts kW of heat energy to Btuh:


kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total external static
pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied
motors.

Electrical data (cont)

ELECTRIC HEATER DATA (cont)


HEATER
PART NO.

UNIT

V-PH-Hz
208-3-60

CAELHEAT034A00

240-3-60
240-3-50
480-3-60

CAELHEAT035A00
CAELHEAT036A00

400-3-50
40RM028,034

575-3-60
208-3-60

CAELHEAT037A00

240-3-60
240-3-50

CAELHEAT038A00
CAELHEAT039A00

FLA
Hp
MCA
MOCP

480-3-60
400-3-50
575-3-60

FAN MOTOR
Hp
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0

kW
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46

FLA
22.4
29.3
19.4
26.8
22.8
32.2
9.7
13.4
11.4
16.1
7.8
10.3
22.4
29.3
19.4
26.8
22.8
32.2
9.7
13.4
11.4
16.1
7.8
10.3

LEGEND
Full Load Amps
Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection (Amps)

*Values shown are for single-point connection of electric heat accessory and air
handler.
Single-phase motors. All other motors are 3-phase.

Nominal
Capacity (kW)
50
50
50
50
50
50
50
50
50
50
50
50
70
70
70
70
70
70
70
70
70
70
70
70

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1
Stage 2
Total
22.6
15.0
37.6
22.6
15.0
37.6
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
20.8
13.9
34.7
20.8
13.9
34.7
30.0
20.0
50.0
30.0
20.0
50.0
30.0
22.6
52.6
30.0
22.6
52.6
40.0
30.0
70.0
40.0
30.0
70.0
40.0
30.0
70.0
40.0
30.0
70.0
40.0
30.0
70.0
40.0
30.0
70.0
27.8
20.8
48.6
27.8
20.8
48.6
40.0
30.0
70.0
40.0
30.0
70.0

FLA
104.3
104.3
120.3
120.3
120.3
120.3
60.1
60.1
50.1
50.1
50.2
50.2
145.9
145.9
168.4
168.4
168.4
168.4
84.2
84.2
70.2
70.2
70.3
70.3

MCA*

MOCP*

158.3
166.9
174.6
183.9
178.9
190.6
87.3
91.9
76.9
82.8
72.5
75.6
173.9
182.6
192.6
201.9
196.9
208.6
96.3
100.9
84.4
90.3
80.0
83.2

175
175
200
200
200
200
90
100
80
90
80
80
175
200
200
225
200
225
100
110
90
100
90
90

2. The following equation converts kW of heat energy to Btuh:


kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total external static
pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied
motors.

NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine
heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v capacity (kW) by the factor shown in the table below for the unit voltage.
HEATER
ACTUAL HEATER VOLTAGE
RATING
VOLTAGE 200 208 230 240 400 440 460 480 550 575 600
240
0.694 0.751 0.918 1
480
- 0.694 0.84 0.918 1
575
- 0.915 1 1.089

53

Typical piping and wiring


VERTICAL INST ALLA TION - 40RM (TYPICAL)

NEC TXV -

LEGEND
National Electrical Code
Thermostatic Expansion Valve
Piping

*Field supplied.
Double riser may be required. Consult condensing unit product data catalog for
details.

54

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design
Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended
for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant
migration to the compressor.
5. Internal factory-supplied TXVs not shown.

Typical piping and wiring (cont)


HORIZONT AL INST ALLA TION -

LEGEND
NEC - National Electrical Code
TXV - Thermostatic Expansion Valve
*Accessory item.
Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniqes. Refer
to Carrier System Design Manual for details.

40RM (TYPICAL)

2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include all details for, a spe
cific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended
to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

55

WIRE ROUTING, BASE UNIT -

40RM,

WIRE ROUTING, UNIT WITH ELECTRIC HEAT -

NEC -

National Electrical Code

56

40RM,

Typical piping and wiring (cont)


CONTROL WIRING SCHEMA TIC -

TYPICAL

EQUIP
GND
HC
HTR
IFC
IFM
TB

LEGEND
Equipment
Ground
Heater Contactor
Heater Element
Indoor Fan Contactor
Indoor Fan Motor
Terminal Block
Factory Wiring
Field Wiring

57

Application data
Operating limits
Maximum fan speed . . . . . . . . . . . . . . . . 1200 rpm (20 r/s)
40RM007-024
40RM028,034 . . . . . . . . . . . . . . . . 1100 rpm (18.3 r/s)

General
Select equipment to match or to be slightly lessthan peak
load. This providesbetter humidity control, lessunit cycling,
and lesspart-load operation. Equipment should be selected
to perform at no lessthan 300 cfm/ton (40 L/s per kW).

The air handler fan must always be operating when the


condensingunit is operating.
Ductwork should be sized according to unit size, not
building load. For larger units with two fans, a split duct
transition is recommendedat the fan outlets, but a plenum
can be usedwith slight reduction in external static pressure
capability.
For variable air volume (VAV) systems with supply-to
return air recycling, usethe equipment room as a return air
plenum.

FACTOR Y-INST ALLED NOZZLE AND DISTRIBUTOR DATA


UNIT

40RM007
40RM008
40RM012
40RM014
40RM016
40RM024
40RM028
40RM034

TXV
Qty...Part No.*

DISTRIBUTOR
Qty...Part No.*

1...XVE-5
1...SVE-8
2...XVE-4
2...XVE-5
2...XVE-8
2...XVE-10
2...EBSVE-11
2...SVE-15

1...1116
1...1126
2...1115
2...1115
2...1116
2...1116
2...1126
2...1126

*Sporlan Valve Co. part numbers shown.

58

FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
12...1/4
15...1/4
9...1/4
9...1/4
12...1/4
13...1/4
15...1/4
18...1/4

NOZZLE
Qty...Part No.
1...E5
1...C6
2...E4
2...E5
2...E6
2...E8
2...C10
2...C12

Application data (cont)


FAN MOTOR DATA
STANDARD MOTOR 40RM
007

40RM
008

Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

1725
1.3
56Y

1725
2.4
56Y

Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

1725
2.4
56Y

Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

1725
1.0
56
5/8

7/8

Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

1425
2.4
56Y

1425
2.4
56Y

5/8

5/8

UNIT

NEMA -

5/8

5/8

40RM
014

40RM
012

5/8

5/8

575-3-60
1725
2.0
56HZ

1725
2.0
56HZ

7/8

40RM
028

1725
3.7
56Y

7/8

7/8

1725
3.0
56HZ

1725
3.0
56HZ

7/8

7/8

230-3-50 and 400-3-50


1425
1425
2.9
2.9
56Y
56Y
7/8

40RM
024

40RM
016

208/230-1-60
5/8
208/230-3-60 and 460-3-60
1725
1725
1725
2.4
2.4
2.9
56Y
56Y
56Y

1425
2.9
56Y

7/8

7/8

40RM
034

1745
5.0
S184T
11/8

1745
7.5
S213T
13/8

1745
10.0
S215T
13/8

1745
5.0
184T
11/8

1755
7.5
S213T
13/8

1755
10.0
D215T
13/8

1425
5.0
184T
11/8

1425
7.5
S213T
13/8

1425
10.0
S215T
13/8

National Electrical Manufacturers Association (U.S.A.)

ALTERNA TE MOTOR -

UNIT

40RM
007

40RM
008

Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

1725
2.4
56Y

1725
2.4
56Y

Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

1725
2.9
56Y

Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

1725
2.0
56HZ

1725
3.0
56HZ

7/8

7/8

Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

1425
2.4
56Y

NEMA -

ENGLISH

5/8

7/8

7/8

ENGLISH

40RM
012

208/230-1-60
7/8
208/230-3-60 and 460-3-60
1725
1725
2.9
3.7
56Y
Y56Y
7/8

7/8

575-3-60
1725
3.0
56HZ
7/8

230-3-50 and 400-3-50


1425
1425
2.9
5.0
56Y
S184T
7/8

7/8

1725
3.7
Y56Y

40RM
024

40RM
016

40RM
014

40RM
028

1725
5.0
S184T
11/8

1745
7.5
S213T
13/8

1745
10.0
S215T
13/8

1745
5.0
184T
11/8

1745
5.0
184T
11/8

1755
7.5
S213T
13/8

1750
10.0
D215T
13/8

1425
5.0
S184T
11/8

1425
5.0
S184T
11/8

1425
7.5
S213T
13/8

1425
10.0
S215T
13/8

7/8

National Electrical Manufacturers Association (U.S.A.)

59

Application data (cont)


STANDARD DRIVE DATA, 6 0 Hz UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. - Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

ENGLISH

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

2.4-3.4

2.8-3.8

3.4-4.4

2.8-3.8

2.8-3.8

3.7-4.7

4.3-5.3

4.3-5.3

2.5

2.5

2.5

2.5

2.5

3.0

3.0

3.0

8.8
1
1-A

8.8
1
1-A

8.8
1
1-A

9.0
1 7/16
1-A

9.0
1 7/16
1-A

9.4
1 7/16
2-B

40.3

41.3

42.3

42.3

42.3

41.8

11.0
1 15/16
2-B*
(2) 42.8
(2) 43.8

11.0
1 15/16
2-B*
(2) 42.8
(2) 43.8

568
470-666
1200

647
549-745
1200

764
666-863
1200

632
537-728
1200

632
537-728
1200

771
679-863
1200

752
682-841
1100

752
674-831
1100

19.6

19.6

19.7

19.1

19.1

15.3

13.1

13.1

10.44
12.32

10.44
12.32

10.44
12.32

10.44
12.32

10.44
12.32

9.12
10.99

6.67
9.43

6.67
9.43

*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

MEDIUM-ST ATIC DRIVE DATA, 6 0 Hz UNIT


MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. - Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

3.4-4.4

3.4-4.4

3.4-4.4

3.4-4.4

3.7-4.7

4.3-5.3

4.3-5.3

4.3-5.3

2.5

2.5

2.5

2.5

3.0

3.0

3.0

3.0

8.8
1
1-A

8.0
1
1-A

8.0
1
1-A

8.2
1 7/16
1-A

8.6
1 7/16
1-B

9.4
1 7/16
2-B

42.3

40.3

40.3

41.3

41.8

41.8

9.4
1 15/16
2-B*
(2) 38.8
(2) 39.8

9.4
1 15/16
2-B*
(2) 38.8
(2) 39.8

764
666-863
1200

841
733-949
1200

841
733-949
1200

820
715-926
1200

842
742-943
1200

881
798-984
1200

881
798-984
1100

881
798-984
1100

19.7

21.6

21.6

21.1

16.7

15.3

15.3

15.3

10.44
12.32

10.44
12.32

10.44
12.32

10.44
12.32

10.44
12.32

9.16
10.99

6.67
9.43

6.67
9.43

*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

60

ENGLISH

HIGH-ST ATIC DRIVE DATA, 6 0 Hz UNIT


MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. - Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

ENGLISH

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

3.4-4.4

3.4-4.4

3.4-4.4

3.7-4.7

4.3-5.3

4.3-5.3

4.3-5.3

4.3-5.3

2.5

2.5

2.5

3.0

3.0

3.0

3.0

3.0

7.0
1
1-A
41.3

6.0*
1
1-A
37.3

6.0
1
1-A
37.3

7.4
1 7/16
1-B
39.8

7.9
1 7/16
1-B
39.8

7.4
1 7/16
2-B
36.8

8.6
1 15/16
2-B
37.8

8.6
1 15/16
2-B
37.8

961
838
1084
1200

1121
978
1200*
1200

1121
978
1200
1200

979
873
1096
1200

1060
950
1171
1200

1118
1014
1200
1200

1024
873
1075
1100

1024
873
1075
1100

24.6

28.7

28.7

19.4

18.4

19.4

16.7

16.7

10.44
12.32

10.44
12.32

10.44
12.32

10.44
12.32**

9.16
10.99

8.16
10.02

6.67
9.43

6.67
9.43

*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in.
and resulting fan speed is 837-1096 rpm.
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.
**575-v unit has a center distance of 9.16-10.99.

61

Guide Specifications 38ARZ007-012


Commercial Air-Cooled Condensing Units
HVAC Guide Specifications

Size Range: 6 to 10 Tons, Nominal


Carrier Model Numbers: 38ARZ, Sizes 007-012
Part 1 General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit
suitable for on-the-ground or rooftop installation.
Unit shall consist of a reciprocating or scroll airconditioning compressor assembly, an air-cooled
coil, propeller- type condenser fans, and a control
box. Unit shall discharge supply air upward as
shown on contract drawings. Unit shall be used in
a refrigeration circuit matched with a packaged airhandling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI
Standard 360-2000.
B. Unit construction shall comply with
ANSI/ASHRAE 15 safety code latest revision and
comply with NEC.
C. Unit shall be constructed in accordance with UL
1995 standard.
D. Unit cabinet shall be capable of withstanding
500-hour salt spray exposure per ASTM B117
(scribed specimen).
E. Air-cooled condenser coils for (38ARZ) shall be
leak tested at 200 psig, and pressure tested at 428
psig.
F. Unit shall be manufactured in a facility
registered to ISO 9001:2000 manufacturing quality
standard.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled according to unit
manufacturers recommendations.
1.04 WARRANTY (FOR
SPECIFYING ENGINEER.)

INCLUSION

BY

Part 2 Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled
condensing unit. Contained within the unit
enclosure shall be all factory wiring, piping,
controls, compressor, holding charge (R-22), and
special features required prior to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized
steel, bonderized and coated with a prepainted
baked enamel finish.

62

2. A heavy-gage roll-formed perimeter base rail


with forklift slots and lifting holes shall be
provided to facilitate rigging.
C. Fans:
1. Condenser fans shall be direct driven, propeller
type, discharging air vertically upward.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC-coated steel wire safety
guards.
4. Condenser fan and motor shaft shall be
corrosion resistant.
D. Compressor:
1. Compressor shall be of the hermetic scroll type
2. Compressor shall be mounted on rubber
grommets.
3. Compressors shall include overload protection.
4. Compressors shall be equipped with a crankcase
heater.
5. Compressor shall be equipped with internal high
discharge temperature protection (38ARZ007 and
012 only).
E. Condenser Coil:
1. Condenser coil shall be air-cooled and circuited
for integral subcooler.
2. Coil shall be constructed of aluminum fins
(copper fins optional) mechanically bonded to
internally grooved seamless copper tubes which
are then cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include
liquid line service valve, suction line service valve,
a full charge of compressor oil, and a holding
charge of refrigerant.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
2. Minimum safety devices which are equipped
with automatic reset (after resetting first at
thermostat), shall include:
a. High discharge pressure cutout.
b. Low pressure cutout.
c. High discharge temperature cutout (38ARZ008
only).
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed _____ Btuh at a suction temperature of

_____ F. The power consumption at full load shall


not exceed _____ kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
cooling capacity of _____ Btuh or greater at
conditions of _____ cfm entering-air temperature
at the evaporator at _____ F wet bulb and
_____ F dry bulb, and air entering the condensing
unit at _____F.
3. The system shall have an EER of _____ Btuh/
Watt or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
_____ v, 3-ph, 60 Hz. The unit shall be capable of
satisfactory operation within voltage limits of ____
v to _____ v.
2. Unit electrical power shall be single-point
connection.
3. Unit control circuit shall contain a 24-v
transformer for unit control.
J. Special Features:
1. Low-Ambient Temperature Control:
A low-ambient temperature control shall be
available as a field-installed accessory. This lowambient control shall regulate speed of the
condenser-fan motors in response to the saturated
condensing temperature of the unit. The control
shall maintain correct condensing pressure at
outdoor temperatures down to 20 F.
2. Gage Panel Package:
Gage panel package shall include a suction and
discharge pressure gage.
3. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Coils shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive coastal

environments. Coating shall be applied to the


aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Copper-Fin Coils:
Coils shall be constructed of copper-fins
mechanically bonded to copper-tubes and copper
tube sheets. A polymer strip shall prevent coil
assembly from contacting sheet metal coil pan to
minimize potential for galvanic corrosion between
the coil and pan. All copper construction shall
provide
protection
in
moderate
coastal
environments.
4. Thermostat Controls:
a. Programmable multi-stage thermostat shall have
7-day clock, holiday scheduling, large backlit
display, remote sensor capability, and Title 24
compliance.
b. Commercial Electronic Thermostat shall have 7day timeclock, auto-changeover, multi-stage
capability, and large LCD (liquid crystal display)
temperature display.
c. Carrier PremierLink Controller:
This control will function with CCN (Carrier
Comfort Network) and ComfortVIEW
software. It shall also be compatible with
ComfortLink controllers. It shall be ASHRAE
62-99 compliant and Internet ready. It shall accept
a CO2 sensor in the conditioned space and be
Demand Control Ventilation (DCV) ready. The
communication rate must be 38.4K or faster. It
shall include an integrated economizer controller.

63

Guide specifications 38ARD014-028

Commercial Air-Cooled Condensing Units


HVAC Guide Specifications

Size Range: 12 to 20 Tons, Nominal


Carrier Model Number: 38ARD, Sizes 014-028
Part 1 General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit
suitable for on-the-ground or rooftop installation.
Unit shall have 2 independent refrigeration
circuits. Unit shall consist of dual scroll
compressors, an aircooled coil, propeller-type
condenser fans, and a control box. Unit shall
discharge supply air upward as shown on contract
drawings. Unit shall be used in a refrigeration
circuit matched with a packaged airhandling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI
Standard 360-2000, and shall be certified and listed
in the latest ARI directory.
B. Unit construction shall comply with
ANSI/ASHRAE safety code, latest revision, and
comply with NEC.
C. Unit shall be constructed in accordance with UL
1995 standard and shall carry the UL and UL,
Canada label.
D. Unit cabinet shall be capable of withstanding
500-hour salt spray exposure per ASTM B117
(scribed specimen).
E. Air-cooled condenser coils shall be leak tested
at 150 psig, and pressure tested at 480 psig.
F. Unit shall be manufactured in a facility
registered to ISO 9001:2000 manufacturing quality
standard.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled according to unit
manufacturers recommendations.
1.04 WARRANTY (FOR INCLUSION BY
SPECIFYING ENGINEER.)
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled
condensing unit. Contained within the unit
enclosure shall be all factory wiring, piping,
controls, compressor, holding charge (R-22), and
special features required prior to field start-up.
B. Unit Cabinet:
Unit cabinet shall be constructed of G-90
galvanized steel, bonderized and coated with a
prepainted baked enamel finish.
C. Fans:
1. Condenser fans shall be direct driven,
propellertype, discharging air vertically upward.
2. Fan blades shall be balanced.

64

3. Condenser fan discharge openings shall be


equipped with PVC-coated steel wire safety
guards.
4. Condenser fan and motor shaft shall be
corrosion resistant.
D. Compressor:
1. Compressors shall be of the hermetic scroll type.
2. Compressors shall be mounted on rubber
grommets.
3. Compressors shall include overload protection.
4. Compressors shall be equipped with a crankcase
heater.
5. Compressors shall be equipped with internal
high discharge temperature protection (38ARD016
and 028 only).
E. Condenser Coil:
1. Condenser coil shall be air-cooled and circuited
for integral subcooler.
2. Coil shall be constructed of aluminum fins
(copper fins optional) mechanically bonded to
internally grooved seamless copper tubes which
are then cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include high
side pressure relief device, liquid line service
valve, suction line service valve, a full charge of
compressor oil, and a holding charge of refrigerant.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
c. Recycle time delay of five minutes to prevent
compressor short cycling.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at thermostat):
a. High discharge pressure cutout.
b. Loss-of-charge cutout.
c. Condenser fan motors to be protected against
overload condition by internal overloads.
Manual reset at the unit:
Electrical overload protection through the use of
define-purpose contactors and calibrated, ambient
compensated, magnetic trip circuit breakers.
Circuit breakers shall open all three phases in the
event of an overload in any one of the phases or a
single phase condition.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed _____ Btuh at a suction temperature of
_____ F. The power consumption at full load shall
not exceed _____ kW.

2. The combination of the condensing unit and the


evaporator or fan coil unit shall have a total net
cooling capacity of _____ Btuh or greater at
conditions of _____ cfm entering-air temperature
at the evaporator at _____ F wet bulb and _____ F
dry bulb, and air entering the condensing unit at
_____ F.
3. The system shall have an EER of _____ Btuh/
Watt or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
_____ v, 3-ph, 60 Hz. The unit shall be capable of
satisfactory operation within voltage limits of
_____ v to _____ v.
2. Unit electrical power shall be single-point
connection.
3. Unit control circuit shall contain a 24-v
transformer for unit control.
J. Special Features:
1. Low-Ambient Temperature Control:
A low-ambient temperature control shall be
available as a factory-installed option or as a fieldinstalled accessory. This low-ambient control shall
regulate speed of the condenser-fan motors in
response to the saturated condensing temperature
of the unit. The control shall maintain correct
condensing pressure at outdoor temperatures down
to 20 F.
2. Gage Panel Package:
Gage panel package shall include a suction and
discharge pressure gage.
3. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Coils shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive coastal

environments. Coating shall be applied to the


aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Copper-Fin Coils:
Coils shall be constructed of copper-fins
mechanically bonded to copper-tubes and copper
tube sheets. A polymer strip shall prevent coil
assembly from contacting sheet metal coil pan to
minimize potential for galvanic corrosion between
the coil and pan. All copper construction shall
provide
protection
in
moderate
coastal
environments.
4. Thermostat Controls:
a. Programmable multi-stage thermostat with 7-day
clock, holiday scheduling, large backlit display,
remote sensor capability, and Title 24 compliance.
b. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multistage capability,
and large LCD (liquid crystal display) temperature
display.
c. Carrier PremierLink Controller:
This control will function with Carrier Comfort
Network (CCN) and ComfortVIEW software.
It shall also be compatible with ComfortLink
controllers. It shall be ASHRAE 62-99 compliant
and Internet ready. It shall accept a CO2 sensor in
the conditioned space and be Demand Control
Ventilation (DCV) ready. The communication rate
must be 38.4K or faster. It shall include an
integrated
economizer
controller.

65

Guide specifications 40RM


Commercial Packaged Air-Handling Unit
HVAC Guide Specifications
SizeRange: 2,400 to 12,000 CFM (1150 to 5650 L/s),
Nominal Airflow 6 t o 3 0 Tons (21 to
105 kW), Nominal Cooling
Carrier Model Numbers: 40RM (Direct-Expansion Coil)
Part 1 - GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commer
cial split systems.Unit shall have a multiposition de
sign and shall be capable of horizontal or vertical
installation on a floor or in a ceiling, with or without
ductwork. (Only vertical units are to be applied with
out ductwork.)
B. Unit with direct-expansioncoil shall be used in a re
frigerant circuit with a matching air-cooled con
densing unit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed & tested in accordance with
ASHRAE 15 Safety Code for Mechanical Refrigera
tion (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL
(U.S.A.) and ETL, Canada, standardsand shall carry
the ETL and ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with
NFPA-90A (U.S.A.)requirements for flame spread
and smoke generation.
D. Unit shall be manufactured in a facility registered to
the ISO 9002 manufacturing quality standard.
E. Direct-expansionand chilled water coils shallbe burst
and leak tested at 435 psi (2999 kPa).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer's
recommendations.
Par t 2 - Products
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit
that can be used in a suspended horizontal configu
ration or a vertical configuration. Unit shall consistof
forward-curved belt-driven centrifugal fan(s), motor &
drive assembly,prewired fan motor contactor, factory
installedrefrigerant metering devices(direct-expansion
coil units), cooling coil, 1-in. (25.4-mm) washable air
filters, and condensate drain pans for vertical or hori
zontal configurations.

66

A. Base Unit (Painted):


1. Cabinetshall be constructed of zinc coated steel
and polyester powder painted to protect them
from corrosion in the harsh Middle Eastern climate
and also to increase the colour life in high ultra
violet (UV) radiation regions.
2. Cabinet panels shall be fully insulated with 1/2 in.
(12.7-mm) fire-retardant material.
3. Unit shall contain PVC condensate drain pans for
both vertical and horizontal applications. Drain
pans shallhave connectionson right and left sides
of unit to facilitate field connection. Drain pans
shall have the ability to be sloped toward the right
or left side of the unit to prevent standing water
from accumulatingin pans.
4. Unit shall have factory-supplied 1-in. (25.4 mm)
washable-type filters installed upstream from the
cooling coil. Filter access shall be from the front
of the unit.
B. Coils:
Coils shall consist of 3 rows (40RM, 40RMS), of
coppertubes with sine-wave aluminum fins bonded
to the tubes by mechanical expansion. Suction and
liquid line connectionsor supply and discharge con
nections shallbe made on the same side of the coil.
1. Direct-expansioncoilsshallfeaturefactory-installed
thermostatic expansion valves (TXVs) for refrig
erant control. The TXVs shall be capable of ex
ternal adjustment. Direct-expansion heat pump
coils shall have a factory-installedbypassline and
check valve assemblyaround the TXVs to allow
liquid flow from the coil to the outdoor unit during
the heating mode. Coil tubing shall be internally
rifled to maximize heat transfer.
C. Operating Characteristics:
Unit shall be capable of providing
cfm (L/s)
airflow at an external static pressureof
in. wg
(kPag).
D. Motor:
Fan motor of the size and electrical characteristics
specifiedon the equipment scheduleshall be factory
supplied and installed.
Motors rated at 1.3 through 3.7 hp (0.97 through
2.76 kW) shall have internal thermal overload pro
tection. Motors rated at 5, 7 1/2 , and 10 hp (3.73,
5.60, and 7.46 kW) shall be protected by a circuit
breaker.

E. Factory-InstalledOptions:
1. Alternate Motor and Drive:
An alternate motor and/or medium- or high-static
drive shall be available to meet the airflow and
external static pressure requirements specified
on the equipment schedule.
F. Field-InstalledAccessories (ordered from NAO):
1. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt,
3-phase, 60 Hz; and 240, 400-volt, 3 phase,
50 Hz power supply shallbe factory-suppliedfor
field installationasshown on the equipmentdraw
ings. Electricheat assemblyshallbe ETL (U.S.A.)
and ETL, Canada, agency approved, and shall
have single-point power wiring. Heater assem
bly shallincludecontactorswith 24-V coils, power
wiring, 24-v control wiring terminal blocks, and
a hinged accesspanel. Electric heaters shall not
be used with air discharge plenum.
2. Air Discharge Plenum:
Plenum shall be factory supplied to provide free
blow air distribution for vertical floor-mounted
units. A grille with moveable vanes for hori
zontal or vertical airflow adjustment shall be
included. Plenum shall be field-assembledand
field-installedon the unit's fan deck for blow-thru
air distribution. Plenum shall not be used with
electric heaters.
3. Return Air Grille:
Grille shall be factory supplied for field installa
tion on the unit's return air opening.

6. Thermostat Controls:
a. Debonair programmablemulti-stagethermo
statwith 7-dayclock, holiday scheduling,large
Thermoglow display, remote sensorcapa
bility, and Title 24 compliance.
b. TEMP System programmable communicat
ing multi-stage thermostat with fan switch,
time clock, LCD display,F/C capability,and
CCN compatiblity.
c. CommercialElectronicThermostatwith 7-day
time clock, auto-changeover, multi-stageca
pability, and large LCD temperature display.
d. Non-programmablethermostatwith fan switch
subbase.
7. Overhead SuspensionPackage:
Package shall include necessary brackets to
support units in a horizontal ceiling installation.
8. CO2 Sensor:
Sensorshallprovide the ability to signalthe econo
mizer to open when the spaceCO2 levelexceeds
the predetermined set point. Sensor shall have
the capability of being connected to Comfort
System relay pack or to economizer using field
supplied and -installed Honeywell dc adapter
no. Q769C1004.
9. CondensateDrain Trap:
Trap shall have transparent, serviceabledesign
for easycleaning. Kit shallinclude overflow shut
off switch and wiring harnessfor connection to
an alarm if desired.

4. Unit Subbase:
Subbaseassemblyshall be factory supplied for
field installation. Subbase shall elevate floormounted vertical units to provide access for
correct condensate drain connection.
5. Economizer:
Economizerfor ventilation or ``free'' cooling shall
be factory provided for field installation on either
return air opening of air handler. For free cool
ing applications, economizershallbe compatible
with separate thermostat; economizer dampers
shall open when outdoor air enthalpy is suitable
for free cooling. Economizershall be compatible
with separate CO2 sensor accessory; economizer
dampersshall open when indoor CO2 level rises
abovepredetermined setpoint. Economizershall
include enthalpy control and damper actuator.

67

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations
38AR-04 PD 60HZ
2015