LABORATORIO N 8
MEDIDAS DE VALORES MEDIOS Y EFICACES EN CIRCUITOS MONOFASICOS
GRUPO NMERO 3
LABORATORIO
INTEGRANTES
CIRCUITOS ELECTRICOS II
:
LIMA 2008
NDICE
OBJETIVOS
(3)
MATERIALES UTILIZADOS
(3)
PROCEDIMIENTO
(5)
CUESTIONARIO
(11)
CONCLUSIONES Y RECOMENDACIONES
(27)
BIBLIOGRAFA
(28)
I.
OBJETIVOS
II.
ELEMENTOS A UTILIZAR
Figura 1 Autotransformador.
1 Diodo de 5A.
Juego de Conductores
CIRCUITOS A UTILIZAR
IV.
PROCEDIMIENTO
1. Se arm el circuito N1, y regulamos los valores de ambas resistencias
R1 y R2 en su mximo valor.
, y se vari
Vac (V)
12.65
13.02
14.61
16.15
17.81
Vdb (V)
11.97
11.62
10.02
8.43
6.72
I (mA)
61.1
62.2
70
77.7
85.3
Luego tenemos:
Tabla 2
Reostato
Osciloscopi
o
Multimetro
Vacmax(V
)
Vdbmax(V)
R1()
R2()
Vac(V)
Vdb(V)
206
75.4
6.5
4.7
13.4
9.8
206
112.1
5.75
6.4
11.8
13.2
206
133.1
5.2
7.2
10.5
14.8
206
154.2
5.1
7.8
10.4
16.2
206
178
5.45
5.42
11.2
18.4
Reostato
Osciloscopi
o
Multimetro
Vacmax(V
)
Vdbmax(V)
R1()
R2()
Vac(V)
Vdb(V)
206
75.4
6.5
4.7
13.4
9.8
206
112.1
5.75
6.4
11.8
13.2
206
133.1
5.2
7.2
10.5
14.8
206
154.2
5.1
7.8
10.4
16.2
206
178
5.45
5.42
11.2
18.4
Reostato
Multimetro
Osciloscopio
10
Vdbmax(V
Vacmax(V)
)
R1()
R2()
Vac(V)
Vdb(V)
206
178.1
5.12
11.5
14.2
16.8
206
168.4
5.16
11
13.22
15.9
206
159.1
7.78
10.7
13.82
15.5
206
145
7.87
10.1
14.23
14.8
206
134.6
6.98
9.69
14.15
14.2
11
VabM (V)
147.6
28.6
137.5
fab
VdbM (V)
VacM (V)
fac (Hz)
59.95
12.2
59.99
16.8
60.6
28.4
59.77
13
60.02
15.2
59.92
122.5
28.6
59.8
13.4
59.95
14
59.95
115
28.4
59.8
13.8
59.84
14
59.92
105.5
28.6
59.81
14.8
59.77
13.2
59.77
(Hz)
pico-pico
fdb (Hz)
12
V.
CUESTIONARIO
13
14
Generador elctrico
Un generador elctrico es todo dispositivo capaz de mantener una diferencia de potencial
elctrico entre dos de sus puntos, llamados polos, terminales o bornes. Los generadores
elctricos son mquinas destinadas a transformar la energa mecnica en elctrica. Esta
transformacin se consigue por la accin de un campo magntico sobre los conductores
elctricos dispuestos sobre una armadura (denominada tambin estator). Si
mecnicamente se produce un movimiento relativo entre los conductores y el campo, se
generara una fuerza electromotriz (F.E.M.).
Se clasifican en dos tipos fundamentales: primarios y secundarios. Son generadores
primarios los que convierten en energa elctrica la energa de otra naturaleza que reciben
o de la que disponen inicialmente, mientras que los secundarios entregan una parte de la
energa elctrica que han recibido previamente.
16
17
De atraccin magntica.
De repulsin magntica
En ambos tipos de medidores la corriente que se quiere medir pasa a travs de una bobina
de hilo dando lugar a la generacin de un campo magntico cuya fuerza es proporcional a
la intensidad I que pasa por la bobina.
18
Con el instrumento tipo atraccin, el campo de bobina atrae un disco de hierro dulce que
pivota. El par resultante de esta atraccin es proporcional al cuadrado de la corriente a
travs de la bobina.
Donde:
k: Es una constante que depende de los materiales del medidor.
I: Corriente a travs de la bobina.
A este par se opone otro desarrollado por los muelles, el cual es proporcional al ngulo
de giro del disco y la aguja indicadora.
Donde
Ks: Constante de los muelles.
: Es el ngulo de giro del disco.
Para existir un equilibrio, se igualan los momentos
medidas bajas, con la ventaja de que puede ser utilizado en las medidas de corriente
alterna y continua. En corriente alterna la corriente que se mide es proporcional a su valor
eficaz.
Instrumento digital
En contra posicin con los instrumentos de medicin analgica, los instrumentos digitales
indican los valores de medida en cifras numricas. Esto es ms ventajoso para la
observacin visual, as de este modo se puede prescindir de la lectura de rayas y de la
interpolacin de valores intermedios. Esto evita agregar un error de visualizacin a los
errores propios del instrumento.
La medicin digital requiere una cuantificacin de los valores de medida, que en general se
presentan en forma analgica. En consecuencia, un medidor digital cuenta la cantidad de
valores discretos que representan al valor analgico, siendo la indicacin siempre insegura
en + 1 unidad (error de cuantificacin). El error de cuantificacin se puede disminuir
mediante una subdivisin correspondientemente fina y aumentar la exactitud de la medida,
pero esta est limitada por la exactitud de los elementos de medida empleados y de sus
componentes.
En la cuantificacin se detectan y cuentan los valores instantneos de la magnitud a medir
en intervalos de tiempo constante t. Cada valor de medida as determinado se indica y
conserva hasta que aparece el siguiente.
Restato
Multimetro
Osciloscopio
Vabmax( Vacmax( Vdbmax(
V)
V)
V)
R1()
R2()
Vab(V)
Vac(V)
Vdb(V)
206
188,2
24,74
12,65
11,97
35,6
18,2
17,2
206
178
24,71
13,02
11,62
35,9
19
16,8
20
206
137,1
24,69
14,61
10,02
35,3
20,8
14,3
206
103,1
24,65
16,15
8,43
35,4
23,2
12,1
206
75,4
24,67
17,81
6,72
35,75
25,6
9,945
Vmax/
Vaceficaz(
V)
ErrorVab(
%)
Error
ErrorVac(
%)
Vdbeficaz(
V)
ErrorVdb(
%)
25.17
12.86
12.16
-1.73
-1.66
-1.58
25.38
13.43
11.87
-1.96
-1.52
-2.19
24,96
14.7
10.11
-1.12
1.20
-2.12
25.03
16.4
8.55
-1.53
1.59
-2.15
25.27
Para R2=152.5
18.1
7.03
-1.32
1.95
-2.2
Restato
Multimetro
R1()
R2()
Vab(V)
Vac(V)
Vdb(V)
I(mA)
206
188.2
19.76
12.65
11.97
61.1
206
178
20.11
13.02
11,62
62.2
206
137.1
20.08
14.61
10.02
70
206
103.1
20
16.15
8.43
77.7
206
75.4
20.04
17.81
6.72
85.3
Analiticamente
Error
ErrorVac(
ErrorVdb(
%)
%)
Vab(V
)
Vac(V)
Vdb(V)
I(mA)
ErrorVab(
%)
ErrorI(mA
)
24,74
12.92
11.81
62.76
-4.03
--2.13
1.32
-2.71
24,71
13.14
11.76
62.5
0.54
-1.82
-2.05
-4.24
24,69
15.1
10.15
70.3
0.39
-0.01
0.01
-3.33
21
24,65
16.4
8.56
77.9
0.87
-0.75
-4.37
24,67
17.95
6.81
85.6
0.19
0.47
-0.77
-3.65
Para R2=188.2
I(mA) = 24.74/(R1+R2)*1000 = 24.74/(206+188.2)*1000 = 62.76
Vdb(V) = I(mA) * R2 / 1000 = 62.76 * 188.2 / 1000 =11.81
Vac(V) = I(mA) * R1 / 1000 = 62.76 * 206/ 1000 =12.92
ErrorVab(%) = 100*(24.73 24.74)/ 24.73 = -4.03
ErrorVac(%) = 100*(12.65 12.92)/ 12.65 = -2.13
ErrorVdb(%) = 100*(11.97- 11.81)/ 11.97 = 1.33
ErrorI(mA) = 100*(61.1- 62.76)/ 61.1 = -2.71
CIRCUITO 2
Reostato
Osciloscopi
o
Multimetro
Vacmax(V
)
Vdbmax(V)
R1()
R2()
Vac(V)
Vdb(V)
206
75.4
6.5
4.7
13.4
9.8
206
112.1
5.75
6.4
11.8
13.2
206
133.1
5.2
7.2
10.5
14.8
206
154.2
5.1
7.8
10.4
16.2
206
178
5.45
5.42
11.2
18.4
Error
ErrorVdb(
%)
6.7
4.9
-3.07
-4.25
5.9
6.6
-2.6
-3.125
5.25
7.4
-0.96
-2.77
5.2
8.1
-1.96
-3.84
5,6
5.6
-2.75
-3.32
Para R2=75.4
22
Multimetro
R1()
R2()
Vac(V)
Vdb(V)
I(mA)
206
75.4
6.5
4.7
46
206
112.1
5.75
6.4
40.7
206
133.1
5.2
7.2
38.2
206
154.2
5.1
7.8
35.8
206
178
5.45
5.42
32
Analiticamente
Error
ErrorVac(% ErrorVdb(% ErrorI(mA
)
)
)
Vac(V)
Vdb(V)
I(mA)
6.72
4.9
45.5
-3.38
-4.25
1.08
5.84
6.7
41.2
-3.76
-3.77
1.65
5.43
7.5
38.5
-2.56
-2.88
0.93
5.33
8.1
36.1
-1.89
-0.95
3.11
5.62
Para R2=145.9
5.55
32.6
-1.65
-2.14
4.12
I(mA) = 26.8 *
/(R1+R2)*1000 / 2 = = 45.5 mA
Multimetro
R1()
R2()
Vac(V)
Vdb(V)
206
178.1
5.12
11.5
Osciloscopio
Vdbmax(V
Vacmax(V)
)
14.2
16.8
23
206
168.4
5.16
11
13.22
15.9
206
159.1
7.78
10.7
13.82
15.5
206
145
7.87
10.1
14.23
14.8
206
134.6
6.98
9.69
14.15
14.2
Transformando a
valores eficaces
Vab
Vdb
eficaz(V)
eficaz(V)
Error
Error
Vdb(%)
5.02
11.87
-3.295
4.67
11.24
-2.2
4.88
10.96
-2.429
5.03
10.46
-3.613
5.00
10.04
-3.3
Para R2=147.6
ErrorVdb(%) = 100*(11.87 11.5) / 11.87 = -3.295
Reostato
Multimetro
R1()
R2()
Vac(V)
Vdb(V)
I(mA)
206
178.1
5.12
11.5
60
206
168.4
5.16
11
61.6
206
159.1
7.78
10.7
63
206
145
7.87
10.1
66.1
206
134.6
6.98
9.69
67.5
Analiticamente
Error
ErrorVac(% ErrorVdb(% ErrorI(mA
)
)
)
Vab(V
)
Vac(V)
Vdb(V)
I(mA)
24.62
5.22
11.9
61.2
1.9
1.72
1.96
24.62
5.25
11.4
62.44
2.54
2.1
2.33
24.62
7.87
11.23
63.9
1.2
1.6
1.43
24.62
7.98
11.1
66.8
2.68
3.75
1.68
7.32
10.12
68.4
3.12
-19.47
2.67
24.62
Para R2=178.1
24
) = 11.9
5. OBSERVACIONES
Para el caso 1 donde tericamente el valor medio debe ser cero, el osciloscopio
marca valores de hasta 50 mV entre positivo y negativo.
Existe una cada de potencial en los diodos comerciales, pero en nuestro caso no ha
convenido expresar los clculos tericos por ser innecesario en esta prctica, por lo
que las tablas 4.5, 4.6 y 4.8 se vern resultados de errores tomando como
referencia al valor pico-pico.
Para los casos 2 y 3 el borne a-c es decir la resistencia R 1 o voltaje V1 esta antes
que el diodo rectificador de media onda para el caso 2 y tambin esta antes del
puente de diodos en el caso 3, la diferencia entre ambos es que solo en el caso 2;
25
6. CONCLUSIONES
Para el circuito 1, las tablas 4.2 y 4.3 muestran errores, respecto al terico,
pequeas desviaciones de 0.076% el ms pequeo y 2.909% el ms grande lo que
quiere decir que, aunque suene muy obvio, la onda es alterna del tipo sinusoidal ya
que los valores del osciloscopio lo revelan as, es decir recibimos seal del tipo
alterna sinusoidal y no de otra manera y los parmetros que lo justifican son el valor
medio, el valor eficaz y el valor pico-pico en conclusin estas determinaran las
caractersticas de una onda. Por otro lado el valor medio para el caso 1 no era cero,
como debera ser tericamente, sino que tena valores de, por ejemplo 8.93 mV o
-49.6mV, lo que revela que el osciloscopio no ilustra una seal de voltaje
completamente sinusoidal.
Para el circuito 2, con un diodo, la onda toma otra forma, y ya no es alterna, sino
que es positiva en el primer semiperiodo y cero el otro semiperiodo, por lo que su
valor medio y eficaz cambian, como muestran las tablas 4.1 y 4.4, el valor eficaz del
circuito 1 es mayor que el valor eficaz del circuito 2 para sus respectivas
resistencias, adems el valor medio se hace positivo, desde este punto de vista la
26
onda sinusoidal alterna es mejor que la rectificacin de media onda para cargas
monofsicas. Adems de que un rectificador de media onda slo entrega la mitad
de la energa disponible en una onda AC
Para el circuito 2, es interesante destacar que la tensin en la carga es
unidireccional (positiva) pero no continua. Esta forma de onda no es la deseable
para
generalmente
requieren
una
alimentacin constante.
Para el circuito 3, con el puente de diodos, como se ve en respectivas imgenes, la
onda no es alterna, ms bien es una onda positiva, adems el periodo se reduce a
la mitad, por lo que la frecuencia se duplica a 120Hz, como se muestran en las
figuras. El clculo del valor eficaz es de la misma forma que para una onda alterna
sinusoidal, pero su voltaje pico-pico es menor y por ende su valor eficaz tambin es
menor. Los errores para este circuito tambin tienen desviaciones pequeas.
7. REFERENCIAS
Manual de Laboratorio de Circuitos Elctricos II FIM-UNI
Fundamentos De Circuitos Elctricos ; Charles K. Alexander & Matthew N.O.Sadiku;
3ra.Edicin; McGraw Hill
Introduccin al Anlisis de Circuitos, Boylestad, 10 edicin, Pearson
27