Cancellation
Seyed Hossein Hosseini1, Tohid Nouri2 and Mehran Sabahi2
1
1. Introduction
Three-phase four-wire power distribution systems are widely
used to supply nonlinear loads. The existence of nonlinear loads
in the utility has been increasing at an unprecedented pace in
recent years. Industries have adopted adjustable speed drives, dc
power supplies to improve efficiency and productivity. Most of
the equipments use a rectifier front end to convert ac power
from the source to dc power. The rectifier front ends inject
harmonic current into utility due to their nonlinear nature and
cause many problems, such as overheating of utility
transformers, harmonic resonances in the utility and increased
losses. The third harmonic is most serious when nonlinear loads
are single phase that will cause zero sequence current flows
through neutral current which may damage neutral conductor.
Traditionally, LC tuned passive filters have been used to
absorb harmonic currents generated by nonlinear loads. Their
main advantages are high reliability and low cost. However they
have several drawbacks [1, 3]:
1) Mistuning occurs due to component tolerances of the
inductors and capacitors.
2) The LC tuned passive filter may form series and parallel
resonances with the utility.
3) The filter frequency is fixed, and not easy to adjust.
In recent years active power filters have been proposed which
can overcome above problems of passive filters but their
capability is limited by switching device and are not cost
effective due to their large rating and high frequency switching
requirement of PWM inverter [4, 6]. Hybrid active filters are
developed to solve the active power filter as well as passive
I-244
LS
Lac
Non
Linear
Load
Qc 3 CV s2
(3)
1
(2 f .m ) 2C fm
(4)
Cdc
3. Compensation principle
The principle of compensation for current harmonic and
reactive power is explained with the help of two single phase
equivalent circuits shown in Fig. 3.
(a)
V AFH = KI SH
(1)
(b)
I SH
Zf
=
I LH K + Z f + Z S
(2)
I-245
5. Simulation results
The efficiency of the proposed hybrid active filter has been
examined by computer simulation using MATLAB and
associated toolbox SIMULINK and Power System Blockset.
The main parameters of the system are given in Table 1. The
loads used in the following simulations are three single-phase
rectifier loads which are connected between every phase and
neutral. Fig. 5 shows the simulation results of the nonlinear load
currents.
Table 1. Main parameters of the system
50
phase a( A )
-50
0.52
320 V (peak), 50 Hz
(10 mH, 88.8 f), (16 mH, 25 f)
120 V , 9800 f, 10KHz
-100
0.52
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.6
phase b ( A )
0.57
0.58
0.59
0.6
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.6
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.6
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.6
50
-50
-100
0.52
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.6
phase c ( A)
100
-5
-10
0.52
50
T i m e ( s )
-50
-100
0.52
10
cur r ent ( A)
Sour ce Neut r al
0.56
-50
0.52
100
0.55
50
phase c( A)
phase a ( A)
-50
0.54
-50
0.52
100
50
0.53
50
phase b( A)
Vsa , fs
(L3 , C3), (L5 , C5)
Vdc , Cdc, fpwm
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.6
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.6
cur r nt ( A)
Load Neut r al
100
50
0
-50
-100
0.52
T i m e ( s )
I-246
300
DC l i nk
v ol t age ( V)
DC l i n k
v o l t a g e ( V)
300
250
200
150
100
50
0
0.52
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0
0.5
Hy b r i d f i l t e r
cur r ent
p h a s e a ( A)
100
0.6
50
-50
0.52
200
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.6
0.65
0.7
0.75
0.8
0.85
0.9
0.95
100
0
-100
-200
0.5
0.6
0.55
200
0.55
0.6
0.65
0.7
0.75
0.8
0.85
0.9
0.95
0.55
0.6
0.65
0.7
0.75
0.8
0.85
0.9
0.95
0.55
0.6
0.65
0.7
0.75
0.8
0.85
0.9
0.95
-50
0.52
Hy br i d f i l t er
cur r ent
pha s e c( A)
So ur c e c u r r e nt
p h a s e a ( A)
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.6
50
-50
0.52
150
100
50
0
-50
-100
-150
0.5
Lo ad Neu t r al
cu r r e nt ( A)
Hy b r i d f i l t e r
cur r ent
ph ase b( A)
50
0.53
0.54
0.55
0.56
0.57
0.58
0.59
100
50
0
-50
-100
0.5
0.6
Ti me(s)
Time(s)
Fig. 11. Simulation results under the transient response of stepon load
Re a c t i v e
p o we r ( VAR)
3000
2000
7. References
1000
0
-1000
-3000
-4000
0
-2000
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
[2]
[3]
[4]
[5]
6. Conclusions
In this paper a new three-phase four-wire hybrid active filter
is proposed. The main feature of its structure is that it uses a
single capacitor at DC link and neutral wire is connected
directly to the positive terminal of DC link and thus avoiding
split capacitors. On the other hand it saves two power switches
and solves the problems of conventional structures. The
proposed structure uses an LC tuned coupling circuit, which
blocks the source voltage thus reducing the DC link voltage and
consequently active power filter rating. A simple control method