Anda di halaman 1dari 12

Rectifier Module

R4815N1

Introduction
The R4815N1 is a digital rectifier that converts the 85~300VAC input to 53.5 VDC output and possesses the characters
of high efficiency, walk-in start, hot-plug, complete protection, and low audible noise. The rectifier adopts the latest
power monitoring technology, implements the function of monitoring the states of loads and the rectifier status in real
time. The output voltage of the rectifier can be adjusted through the host.

Feature
Features
High efficiency: >94
Input voltage range: 85~300VAC
Operating temperature range: -40~+75
Voltage/V

Total harmonic distortion(THD): 5


Hot-plug

70
60
50

Digital control

40

Intelligent electric meter

30

Communication over CAN

20

Adjustment of voltage and current

10
0

Meet RoHS requirements

Passing the TUV,CE,CB,UL certifications

10

15

20

25

Current/A

Output feature

%
Power/W

96
94
92

1200

1000

1000

800

800

90
88

600

86
400
84
200

82
80
0%

20%

40%

60%

80%

100%

Load rate

Efficiency curve

0
-40

-20

20

40

60

80

Temperature/

Power derating curve

Specifications
Product

Basic
specifications

R4815N1

Dimension

40.8(H)mm95.5(W)mm208(D)mm

Weight

1.1kg

Cooling

Forced air cooling

Input voltage

85~300VAC

Input mode

220VAC single phase(or 110VAC dual live lines)

Frequency

45~66Hz, rated: 50Hz/60Hz

Maximum input current

6.4A

Power factor

0.99

THD

Output voltage

42~58VDC, default value: 53.5VDC

Output power

1000W(176~300VAC)

Operating temperature

-40~+75

Storage temperature

-40~+70

Relative humidity

5%~95%(non-condensing)

Altitude range

4000m(If the altitude is within the range of 3000m to 4000m, the maximum operating temperature
decreases by 1 as the altitude increases by 200m.)

Input overvoltage
protection

Protection point: >300VAC

Input undervoltage
protection

Protection point: <80VAC

Output overvoltage
protection

58.5~60.5VDC(can be set by PMU)

Output short circuit


protection

A long term short circuit is allowed

Over-temperature
protection

Protection point: 75(167)

MTBF

>500,000hours

Specification

40db(25, full load)

Safety certification

Passes TUV, CE, UL certifications


Catch the CB certificate
Complies with
UL60950-1
IEC60950-1
EN60950-1
CAN/CSA C22.2 No. 60950 -1

EMC

EN55022 Class B
EN55024
EN61000-3-2
EN61000-3-3
ETSI EN300 386
ETSI EN301489
ITU-T K.20

Lightening protection

YD 5098-2005 5KA

Input feature

Output feature

Environmental
specifications

Protection

Reliability
Audible noises

Safety/EMC/
Lightening
protection

Copyright Huawei Technologies Co., Ltd. 2014. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com

Rectifier Module
R4830N2
Introduction
The R4830N2 is a digital rectifier with high efficiency and power density. It converts 85 300 Vac input
voltage to 53.5 Vdc output voltage. The output voltage can be adjusted by the host. It performs
comprehensive protection functions, supports soft start, and produces low noise. With the latest power
monitoring technology, states of the rectifier and load are monitored in real time.

Feature

Features
Efficiency > 94

Input voltage range: 85300 Vac


Operating temperature range: 40 to +75
70

Hot-swappable

60

Voltage/V

Total harmonic distortion(THD): 3.5

Digital control

50
40

Intelligent electric meter

30

Communication over CAN

20
10

Adjustment of voltage and current

0
0

Meet RoHS requirements

10

20

Passing the TUV,CE,CB,UL certifications


Output feature

Disconnect above 320 Vac


Power/W

Efficiency/%

98
94
90
86
82
78
74
0%

20%

40%

60%

Efficiency curve

80%

100%

Load rate

30

40

Current/A

2000
1800
1600
1400
1200
1000
800
600
400
200
0
0

20

40

Power derating curve

60
Temperature/

80

Specifications
Product
Basic
specifications

Input feature

Output feature

Environmental
specifications

Protection

Reliability
Audible noises

R4830N2

Dimension

40.8 (H) 95.5 (W) 208 (D) mm

Weight

1.3 kg

Cooling

Forced air cooling

Input Voltage

85300 Vac

Input Mode

220 Vac singlephase (or 110 Vac duallive wire)

Frequency

45-66 Hz, rated: 50Hz/60Hz

Maximum Input Current

10A

Power Factor

0.99 (full load)

THD

3.5 (full load)


5% (load 50% )

Output Voltage

4258 Vdc, default value: 53.5 Vdc

Output Power

1740 W (176300 Vac);


755 W (85175 Vac decreased linearly)

Operating Temperature

40 to +75 (non-derating under 55)

Storage Temperature

40 to +75

Relative Humidity

5% 95% (non-condensing)

Altitude Range

4000 m (If the altitude is within the range of 3000 m to 4000 m, the maximum
operating temperature decreases by 1 as the altitude increases by 200m)

Input Overvoltage Protection

Protection point: > 300 Vac

Input Undervoltage Protection

Protection point: < 80 Vac

Output Overvoltage Protection

5660Vdc (can be set by PMU)

Output Short Circuit


Protection

A long term short circuit is allowed

Over-temperature Protection

Protection function is available

MTBF

> 500,000 hours

Specification

45dB (25, full load)

Safety Certification

Passes TUV, CE, UL certifications


Catch the CB certificate
UL60950-1
IEC60950-1
EN60950-1
CAN/CSA C22.2 No. 60950 -1

EMC

EN55022 Class B
EN55024
EN61000-3-2
EN61000-3-3
ETSI EN300 386
ETSI EN301489
ITU-T K.20

Lightening Protection

5KA

Safety/EMC/
Lightening
protection

Copyright Huawei Technologies Co., Ltd. 2015. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com

Rectifier Module
R4850G2

Introduction
The R4850G2 is a digital rectifier that converts the 85~300VAC to 53.5 VDC and possesses the characters of high
efficiency, high power density, walk-in start, hot-plug, complete protection, and low noise. The rectifier adopts the
latest power monitoring technology, implements the function of monitoring the states of loads and the rectifier status in
real time. The output voltage of the rectifier can be adjusted through the host.

Feature
Features
High efficiency: >96
Input voltage range: 85~300VAC
Operating temperature range: -40~75

Voltage/V

Total harmonic distortion(THD): 5


Hot-plug
Digital control

60
50
40

Intelligent electric meter

30

Communication over CAN

20

Adjustment of voltage and current

10

Meet RoHS requirements


0
0

Passing the TUV,CE,CB,UL certifications

10

20

30

40

50

Output feature
%
Power/W

98
96
94
92

60

70

Current/A

3500
3000

3000

2500

90

2100

2000

88
86

1500

84

1000

82
80

500
0%

20%

40%

60%

80%

100%

Load rate

Efficiency curve

-40

-20

20

40

60

80

Temperature/

Power derating curve

Specifications
Product

Basic
specifications

R4850G2

Dimension

40.8(H)105(W )281(D)mm

W eight

2kg

Cooling

Forced air cooling

Input voltage

85~300VAC

Input mode

220VAC single phase(or 110VAC dual live lines)

Frequency

45~66Hz, rated: 50Hz/60Hz

Rated input current

<17A

Power factor

0.99

THD

Output voltage

42~58VDC, default value: 53.5VDC

Output power

3000W(176~300VAC)

Operating temperature

-40~+75(non-derating under 55)

Storage temperature

-40~+75

Relative humidity

5%~95%(non-condensing)

Altitude range

4000m(If the altitude is within the range of 3000m to 4000m, the maximum operating temperature
decreases by 1 as the altitude increases by 200m.)

Input overvoltage
protection

Protection point: >300VAC

Input undervoltage
protection

Protection point: <80VAC

Output overvoltage
protection

58.5~60.5VDC(can be set by PMU)

Output short circuit


protection

A long term short circuit is allowed.

Over-temperature
protection

Protection point: 75(167)

MTBF

>500,000hours

Specification

55dB(40, full load)

Safety certification

Passes TUV, CE, UL certifications


Catch the CB certificate
Complies with
UL60950-1
IEC60950-1
EN60950-1
CAN/CSA C22.2 No. 60950 -1

EMC

EN55022 Class B
EN55024
EN61000-3-2
EN61000-3-3
ETSI EN300 386
ETSI EN301489
ITU-T K.20

Lightening protection

YD 5098-2005 5KA

Input feature

Output feature

Environmental
specifications

Protection

Reliability
Audible noises

Safety/EMC/
Lightening
protection

Copyright Huawei Technologies Co., Ltd. 2014. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com

Rectifier Module
R4850N2

Introduction
The R4850N2 is a digital rectifier that converts the 85~300VAC to 53.5 VDC and possesses the characters of high
efficiency, high power density, walk-in start, hot-plug, complete protection, and low noise. The rectifier adopts the
latest power monitoring technology, implements the function of monitoring the states of loads and the rectifier
status in real time. The output voltage of the rectifier can be adjusted through the host.

Feature
Features
High efficiency: >94
Input voltage range: 85~300VAC
Operating temperature range: -40~75
Voltage/V

Total harmonic distortion(THD): 5


Hot-plug
Digital control

60
50
40

Intelligent electric meter


30

Supports CAN communication


20

Adjustment of voltage and current


10

Meet RoHS requirements


0

Passing the TUV,CE,CB,UL certifications

10

20

30

40

50

60

70

Current/A

Output feature
%
Power/W

95
93

3500
3000

3000

2500

91

2400

2000
89
1500
87

1200
1000

85

500

83

0
0%

20%

40%

60%

80%

100%

Load rate

Efficiency curve

-40

-20

20

40

60

80

Temperature/

Power derating curve

Specifications
Product

Basic
specifications

Input feature

R4850N2

Dimension

40.8(H)105(W)281(D)mm

Weight

2kg

Cooling

Forced air cooling

Input voltage

85~300VAC

Input mode

220VAC single phase


(or 110VAC dual live lines)

Frequency

45~66Hz, rated: 50Hz/60Hz

Maximum input current

19A

Power factor

0.99

THD

Output voltage

42~58VDC, default value: 53.5VDC

Output power

3000W(176~300VAC)

Operating temperature

-40~+75(non-derating under 50)

Storage temperature

-40~+75

Relative humidity

5%~95%(non-condensing)

Altitude range

4000m(If the altitude is within the range of 3000m to 4000m, the maximum operating temperature
decreases by 1 as the altitude increases by 200m.)

Input overvoltage
protection

Protection point: >300VAC

Input undervoltage
protection

Protection point: <80VAC

Output overvoltage
protection

58.5~60.5VDC(can be set by PMU)

Output short circuit


protection

A long term short circuit is allowed.

Over-temperature
protection

Protection point: 75(167)

MTBF

>500,000hours

Specification

55dB(40, full load)

Safety certification

Passes TUV, CE, UL certifications


Catch the CB certificate
Complies with
UL60950-1
IEC60950-1
EN60950-1
CAN/CSA C22.2 No. 60950 -1

EMC

EN55022 Class B
EN55024
EN61000-3-2
EN61000-3-3
ETSI EN300 386
ETSI EN301489
ITU-T K.20

Lightening protection

YD 5098-2005 5KA

Output feature

Environmental
specifications

Protection

Reliability
Audible noises

Safety/EMC/
Lightening
protection

Copyright Huawei Technologies Co., Ltd. 2014. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com

Rectifier Module
R4850S1
Introduction
The R4850S1 is a digital rectifier that converts 85-300V AC to 53.5 V DC and has the highest efficiency in industry. It also
possesses the characters of high power density, walk-in start, hot-swappable, complete protection, and low noise, etc. The
rectifier adopts the latest power monitoring technology, implements the function of monitoring the status of the load and
rectifier in real time. The output voltage of the rectifier can be adjusted through the host.

Feature
Super high efficiency: 98%, the highest in industry
Wide input voltage range: 85-300V AC
Wide operating temperature range: -40 0C-75 0C
Low total harmonic distortion(THD): 5%
Voltage/V

Hot-swappable
Digital control
Intelligent electric meter
CAN communication
LED alarm presentation
Voltage and current adjustable, current sharing
320V AC offline function

Current/A

Power/W

Efficiency/%

Output feature

100%

98%
96%
94%
92%
90%
88%
86%
84%
0%

20%

40%

60%

80%

100%
Load rate

Efficiency curve

Temperature/ 0C

Power derating curve

Specifications
Product

Basic
specifications

Input

Output

Environment

Protection

Reliability
Audible noise

R4850S1

Dimension

40.8(H)105(W)281(D)mm

Weight

2.5kg

Cooling

Forced air cooling

Input voltage

85-300V AC

Input mode

220V AC single phase (or 110V AC dual live lines)

Frequency

45-66Hz, rated: 50Hz/60Hz

Rated input current

<17A

Power factor

0.99 (load rate 50%)

THD

5% (load rate 50%)

Output voltage

42-58V DC, default value: 53.5V DC

Output power

3000W (176-300V AC)


1250W (85V AC, 175-85V AC derating linearly)

Operating temperature

-40 0C-+75 0C (full rated output below 55 0C)

Storage temperature

-40 0C-+75 0C

Relative humidity

5%-95% (non-condensing)

Altitude range

4000m (If the altitude is within the range of 3000m to 4000m, the maximum operating temperature
decreases by 10C as the altitude increases by 200m)

Input overvoltage
protection

>300V AC

Input undervoltage
protection

<80V AC

Output overvoltage
protection

56 ~ 60V DC (Adjustable)

Output short circuit


protection

A long term short circuit is allowed

Over-temperature
protection

Protection point: >75 0C (167 0F)

MTBF

>500,000hours

Specification

55dB (40 0C, full load)

Electrical Safety

TUV, CE, UL, FCC, RCM certifications


CB certificate
UL60950-1
IEC60950-1
EN60950-1
CAN/CSA C22.2 No. 60950 -1
EN60950-1

EMC

EN55022 Class B
EN55024
EN61000-3-2
EN61000-3-3
ETSI EN300 386
ETSI EN301489
ITU-T K.20
FCC CFR47 Part 15 Subpart B
AS/NZS CISPR22

Lightening protection

YD 5098-2005 5KA

Design
standards

Copyright Huawei Technologies Co., Ltd. 2015. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

General Disclaimer
The information in this document may contain predictive statements including, without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com

Rectifier Module
R48100G1

Introduction
The R48100G1 is a digital control 3-phase rectifier with the maximum output power being 6000W. It converts 260~530VAC
input voltage to 53.5VDC output voltage. The output voltage can be adjusted by the host. It performs comprehensive
protection functions, supports soft start, and produces low noise. With the latest power monitoring technology, states of the
rectifier and load are monitored in real time. Multiple rectifiers can be paralleled.

Feature
Features
Efficiency over 96%, saving huge energy
Wide range of AC input voltage:260~530VAC
Wide range of operating temperature:-40 to +75
Voltage/V

Total harmonic distortion (THD) 5%


Digital control mode
Hot swap

60
50
40

Supports intelligent electric meter

30

Supports CAN communication

20

Supports LED display

10

Supports voltage and current adjustment

0
0

20

40

60

80

100

120

Current/A

Passes the TUV,CE,UL certifications and gets the CB

Output feature

certificate

Power/W

%
98
96
94

7000

6000

6000
5000

4800

4000

92

3200

3000

90
88

2000

86

1000
0

84
0%

20%

40%

60%

80%

100%

Load rate

Efficiency curve

-40

-20

20

40

60

80

Temperature/

Power derating curve

Specifications
Product

Basic
specifications

R48100G1

Dimension

43mm(H) 238mm(W) 378mm(D)

Weight

< 6kg

Cooling

Forced cooling

Input voltage

260~530VAC

Input mode

380V, three phase three line

Frequency

45~66Hz, rated 50Hz/60Hz

Maximum input current

13A(Vin: 308VAC,100% load)

Power factor

0.99

THD

5%

Output voltage

42~58VDC,rated 53.5VDC

Output power

6000W(304~530VAC)

Operating temperature

-40 to +75 (output derating above 45)

Storage temperature

-40 to +75

Relative humidity

5%~95% (non-condensing)

Altitude range

4000m (If the altitude is within the range of 2000m to 4000m, the maximum operating temperature
decreases by 1 as the altitude increases by 200m)

Input overvoltage
protection

Protection point: >530VAC, <550VAC

Input undervoltage
protection

Protection point: <260VAC

Output overvoltage
protection

58.5~60.5VDC(can be set by PMU)

Output short circuit


protection

A long term short circuit is allowed. After the fault is rectified, the rectifier is restored to a healthy state
automatically.

Over-temperature
protection

Protection point: 75

MTBF

540,000 hours

Specification

45dB(25, full load)

Safety certification

Passes TUV, CE, UL certifications


Catch the CB certificate
Complies with
UL60950-1
IEC60950-1
EN60950-1
CAN/CSA C22.2 No. 60950-1

EMC

EN55022 Class B
EN55024
EN61000-3-2
EN61000-3-3
ETSI EN300 386
ITU-T K.20

Lightening protection

5KA

Input feature

Output feature

Environmental
specifications

Protection

Reliability

Audible noises

Safety/EMC/
Lightening
protection

Copyright Huawei Technologies Co., Ltd. 2014. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com

Anda mungkin juga menyukai