GAS DIFFUSER NOZZLE FOR RAISED FLOOR OR SUSPENDED CEILING


PROTECTION
DN: ISO7 Rp 3/8" to 1"
PMS: 60 bar
* P min: 10 bar
Temperature: 20 C to + 50 C

Code: See table


Reference: BFFP 3/8" to 1"
Use: HFC227ea*/Fk5-1-12*/IG100/CO2/CDT (IG100, IG01)

Legend
1 BFFP 3/8"
2 BFFP 1/2" to 1"
A Drilled holes

Code

Reference

D inlet

B
L
(mm) (mm)

Mass
(kg)

Maximum flow rate


IG100
(kg/min)

Chimical
(kg/s)

Maximum hole diameters


2 holes at 180 4 holes at 90 or
(mm)
50 (mm)

FR2:LB707830008

BFFP 3/8"

ISO7 Rp 3/8"

26

48

0.12

5.6

FR2:LB707970008

BFFP 1/2"

ISO7 Rp 1/2"

35

40

0.19

18

10.2

7.2

FR2:LB707820008

BFFP 3/4"

ISO7 Rp 3/4"

45

41

0.32

35

3.3

13.7

9.7

FR2:LB707840008

BFFP 1"

ISO7 Rp 1"

55

48

0.51

70

5.6

15.5

11

Material

Marking

Brass

Reference

Ni15 Bright nickel plating

Code
Revision
SS/AA
VdS
G 398006

Certification
VdS*

VdS 2344 G398006

Document No.

FTEX 80 20 20

Revision

05-2009

Building Technologies

Activity FIS

Operation
These nozzles are designed to discharge the extinguishing gas into the raised floors or suspended ceilings in which they are installed. The drilled holes
are perpendicular to the pipe inlet (horizontal jet).
The drilled hole diameters are calculated from the following formula:
M = hom A hom
where

with

G
1
------------ = -----L- + ----- hom
L G

M*:

Total flow (kg/s)

A: Nozzle opening area (m)

Velocity (m/s)

k : Density of phase k (kg/m3)

hom:

Homogeneous

k : Weight fraction of phase k

Installation
This discharge nozzle is mounted directly onto a threaded pipe wrapped with Tflon tape. It is tightened using an adjustable spanner. Particular care must
be paid to the orientation of the nozzle openings in order to optimize the diffusion of the gas into the protected volume. The rules governing the layout of
this type of nozzle are defined in the application instructions of the relevant extinguishing system.

Storage
In the original packaging, protected against shock.

Maintenance/servicing
A visual inspection must be made of the nozzle once every six months. During this inspection, check that the exit holes are not blocked (e.g: by nascent
corrosion or excessive dust) and that the nozzle holes comply with the installation drawings.

SIEMENS standard additional equipment


Not applicable.

Spare parts
Not applicable.

Documentation
Not applicable.

Precautions
This product is exclusively intended for use by specialised installers with experience in the design, installation and maintenance of automatic extinguishing
systems. They must ensure that this product is correctly used according to the specified conditions, that there is no danger for themselves or others, and
that the SIEMENS instructions are followed (assembly instructions, technical instructions, commissioning instructions, installation manuals). Checks shall
also be made to ensure that the product is installed in accordance with the accident prevention regulations and national regulations in force. The installers
shall also ensure that users have read and understood the information relating to this product.

Siemens SAS
Building Technologies
ZI BP 20 617, rue Fourny
78531 BUC Cedex FRANCE
Tel. +33 1 - 30 84 66 00
Fax +33 1 - 39 56 42 08
www.siemens.fr/buildingtechnologies
Document No.
Revision

FTEX 80 20 20
05-2009

2009 Copyright by Siemens SAS


Subject to change and availability without notice