Anda di halaman 1dari 238

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

A single copy of this document is licensed to


IMPERIAL

On
12/11/2015

This is an uncontrolled copy. Ensure use of the


most current version of the document by searching
the Construction Information Service.

Worked Examples to Eurocode 2


25 February 2010
Amended 18 January 2012

Revisions required to Worked Examples to Eurocode 2


due to Amendment 1 to NA to BS EN 1992-1-1:2004 dated Dec 2009.

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Amended 18/1/2012 to illustrate 40K limit on l/d according to Table NA.5 Note 6

Page Where Old text


37/38 3.1.6
Allowable l/d = N u K u F1 u F2 u F3
where
N = 25.6 (U = 0.41%, fck = 30)
K = 1.0
(simply supported)
F1 = 1.0
(beff/bw = 1.0)
F2 = 1.0
(span < 7.0 m)
F3 = 310/Vs 1.5
where
Vs = Vsn (As,req/As,prov) 1/G
where
Vsn | 242 MPa (From Concise
Figure 15.3 and
gk/qk = 1.79, \2 = 0.3, Jg =
1.25)
G = redistribution ratio = 1.0
? Vs | 242 u 594/645 = 222
? F3 = 310/222 = 1.40
? Allowable l/d = 25.6 u 1.40 = 35.8
Actual l/d = 4800/144 = 33.3 ? OK
Use H12 @ 175 B1 (645 mm2/m)
38

3.1.7

By inspection, OK
However, if considered critical:
V = 29.5 kN/m as before
VEd = 29.5 0.14 u 12.3 = 27.8 kN/m
vEd = 27.8 u 103/144 u 103 = 0.19 MPa
vRd,c = 0.53 MPa

Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Revised text
Allowable l/d = N u K u F1 u F2 u F3
where
N = 25.6 (U = 0.41%, fck = 30)
K = 1.0
(simply supported)
F1 = 1.0
(beff/bw = 1.0)
F2 = 1.0
(span < 7.0 m)
F3 = As,prov /As,req 1.50
= 645/ 594 = 1.09
? Allowable l/d = 25.6 u 1.09 = 27.9
Actual l/d = 4800/144 = 33.3
? no good
Try 33.3/27.9 x 654 = 784 mm2/m
i.e. H12@140 (807 mm2/m)
F3 = 807/ 594 = 1.36

? Allowable l/d = 25.6 u 1.36 = 34.8


(which is < 40K = 40)
[Table NA.5 Note 6]
i.e. > 33.3? OK
Use H12 @ 140 B1 (807 mm2/m)
By inspection, OK
However, if considered critical:
V = 29.5 kN/m as before
VEd = 29.5 0.14 u 12.3 = 27.8 kN/m
vEd = 27.8 u 103/144 u 103 = 0.19 MPa
U = 804/1000 x 144 =0.56%
say 50% curtailed use 0.28%
vRd,c = 0.54 MPa

Page 1 of 13

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

42

3.2.6

F3 = As,prov /As,req 1.50


F3 = 310/Vs 1.5
= 645/ 639 = 1.01
where
Allowable l/d = N u K u F1 u F2 u F3
Vs = (fyk/JS) (As,req/As,prov) (SLS
= 23.5 u 1.3 u 1.0 u 1.01
loads/ULS loads) (1/G)
=
30.8
= fyd u (As,req/As,prov) u (gk + \2
Max. span = 30.8 u 144 = 4435 mm,
qk)/(JGgk + JQqk) (1/G)
i.e. < 5795 mm
= (500/1.15) u (639/645) u [(5.9
? No good
+ 0.3 u 3.3)/12.3] u 1.081
= 434.8 u 0.99 u 0.56 u
1.08 = 260 MPa
F3 = 310/260 = 1.19
Note: As,prov/As,req d 1.50
Allowable l/d = N u K u F1 u F2 u F3
= 23.5 u 1.3 u 1.0 u 1.19
= 36.4
Max. span = 36.4 u 144 = 5675 mm, i.e. <
5795 mm
? No good
Try H12 @ 150 B1 (754 mm2/m)
Try H12 @ 125 B1 (904 mm2/m)
Vs = 434.8 u 639/754 u 0.56 u 1.08 =
223
F3 = 310/223 = 1.39
Allowable l/d = 23.5 u 1.3 u 1.0 u 1.39
F3 = 904/639 = 1.41
= 42.5
Allowable l/d = 23.5 u 1.3 u 1.0 u 1.41
Max. span = 42.5 u 144 = 6120 mm,
= 43.1
i.e. > 5795 mm
OK
Max.
span
=
43.1
u 144 = 6206 mm,
? H12 @ 150 B1 (754 mm2/m) OK
i.e. > 5795 mm
OK
? H12 @ 125 B1 (904 mm2/m) OK

43

3.2.7

F3 = As,req/As,prov 1.5
F3 = 310/Vs 1.5
= 502/ 465 = 1.08
where
Vs = fyd u (As,req/As,prov) u (gk + \2 qk)/(JGgk +
JQqk) (1/G)
= (500/1.15) u (465/502) u [ (5.9 + 0.3
u 3.3)/12.3] u 1.03
= 434.8 u 0.93 u 0.56 u 1.03 = 233 MPa
F3 = 310/233 = 1.33
Allowable l/d = N u K u F1 u F2 u F3
= 35.8 u 1.5 u 1.0 u 1.33
Allowable l/d = N u K u F1 u F2 u F3
= 71.4
= 35.8 u 1.5 u 1.0 u 1.08
Max. span = 71.4 u 144 = 10280 mm i.e. >
= 58.0
5795 mm OK
(which is < 40K = 40 x 1.5 =60)
[Table NA.5 Note 6]
Max. span = 58.0 u 144 = 8352 mm
i.e. > 5795 mm
OK

44

3.2.9

In Figure 3.4
H12@150

46

3.2.10a) Crack control


As slab < 200 mm, measures to control
cracking are unnecessary.

In Figure 3.4
H12@125
Crack control
As slab < 200 mm, measures to control
cracking are unnecessary.

The use of Table 15.2 from Concise Eurocode 2implies certain amounts of redistribution, which are defined in Concise
Eurocode 2 Table 15.14.
Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 2 of 13

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

However, as a check on end span:


However, as a check on end span:
Loading is the main cause of cracking,
Loading is the main cause of cracking,
? use Table 7.2N or Table 7.3N for wmax = 0.4 ? use Table 7.2N or Table 7.3N for wmax = 0.4
mm and V = 241 MPa (see deflection check). mm and V = 241 MPa (see deflection check).
Max. bar size = 20 mm
Max. bar size = 20 mm
or max. spacing = 250 mm
or max. spacing = 250 mm
? H12 @ 150 B1 OK.
? H12 @ 125 B1 OK

46

End supports: effects of partial fixity

End supports: effects of partial fixity

Try H12 @ 450 (251 mm2/m) U-bars at


supports

Try H12 @ 500 (226 mm2/m) U-bars at


supports

3.2.10b) End span, bottom reinforcement


Try H12 @ 300 (376 mm2/m) at supports

49

51

End span, bottom reinforcement


Try H12 @ 250 (452 mm2/m) at supports

3.2.10b) Supporrt B bottom steel at support


iii
For convenience use H12 @ 300 B1 (376
mm2/m)

Support B bottom steel at support

3.2.11

See A below

Figure 3.6

57/58 3.3.5b) Span AB: Deflection

For convenience use H12 @250 B1 (452


mm2/m)
Span A
B: Deflection

F3 = 310/Vs 1.5
F3 = 310/Vs 1.5
where
where
Vs = (fyk/JS) (As,req/As,prov) (SLS
Vs = (fyk/JS) (As,req/As,prov) (SLS
loads/ULS loads) (1/G)
loads/ULS loads) (1/G)
= 434.8(523/628) [ (4.30 +
= 434.8(523/628) [ (4.30 + 0.3 u
5.0)/13.38] (65.3/61.7$)
5.0)/13.38] (65.3/61.7$)
= 434.8 u 0.83 u 0.70 u 1.06
= 434.8 u 0.83 u 0.43 u 1.06
= 267 MPa
= 164 MPa
F3 = 310/Vs
F3 = 310/Vs
= 310/267 = 1.16
= 310/164 = 1.89# but 1.50 therefore say
1.50
? Permissible l/d = 22.8 u 1.3 u 0.8 u 0.93 u ? Permissible l/d = 22.8 u 1.3 u 0.8 u 0.93 u
1.16 = 25.6
1.50 = 33.0
Actual
l/d
= 7500/257 = 29.2
Actual l/d = 7500/257 = 29.2
?no good
? OK
Use 2 no. H20/rib (628 mm2/rib) Try 1H25 + 1H20/rib (805 mm2/rib)
d = 254 mm; K = 0.028;
z = 241 mm Asreq = 529 mm2
? Vs = 434.8(529/805) [ (4.30 +
5.0)/13.38] (65.3/61.7$)
= 434.8 u 0.66 u 0.70 u 1.06
= 213 MPa
F3 = 310/213 = 1.45
Permissible l/d
= 22.8 u 1.3 u 0.8 u 0.93 u 1.45
= 32.0
Actual l/d = 7500/254 = 29.5 ? OK
Use 1H25 + 1H20/rib (805 mm2/rib)

Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 3 of 13

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

61

3.3.6b) Span BC
C : Deflection

Span BC
C : Deflection

F3 = 310/VS 1.5
F3 = 310/VS 1.5
where
where
Vs = (fyk/Js) (As,req/As,prov) (SLS loads/ULS
Vs = (fyk/Js) (As,req/As,prov) (SLS loads/ULS
loads) (1/G)
loads) (1/G)
= 434.8 u (474/628) [(4.30 + 0.3 u
= 434.8 u (474/628) [(4.30 + 5.0)
5.0)/13.38](61.1/55.9)
/13.38](61.1/55.9)
= 434.8 u 0.75 u 0.43 u 1.09
= 434.8 u 0.75 u 0.70 u 1.09
= 153 MPa
= 249 MPa
F3 = 310/Vs
F3 = 310/Vs
= 310/153 = 2.03, say = 1.502
= 310/249 = 1.24
? Permissible l/d = 26.8 u 1.5 u 0.8 u 0.77 ? Permissible l/d = 26.8 u 1.5 u 0.8 u 0.77
u 1.50 = 37.1
u 1.24 = 30.7
Actual
l/d
= 9000/257 = 35
Actual l/d = 9000/257 = 35
?
? no good
OK
?Use 2 H20/rib (628 mm2/rib) Try 1H25 + 1H20/rib (805 mm2/rib)
d = 254 mm; K = 0.025;
z = 241 mm Asreq = 480 mm2
? Vs = 434.8(480/805) [ (4.30 +
5.0)/13.38] (61.1/55.9)
= 434.8 u 0.60 u 0.70 u 1.09
= 199 MPa
F3 = 310/199 = 1.56 but 1.50
Permissible l/d
= 26.8 u 1.5 u 0.8 u 0.77 u 1.50
= 37.1
Actual l/d = 9000/254 = 35.4 ? OK
Use 1H25 + 1H20/rib (805 mm2/rib)
65

3.3.10

69

3.3.10b) Support B (and C): bottom steel curtailment


viii
BA and BC To suit prefabrication 2 no.
H20/rib will be curtailed at solid/rib interface,
1000 mm from BA (B towards A) and BC.

Support B (and C): bottom steel curtailment


BA and BC To suit prefabrication 1 H20 +
1H25 /rib will be curtailed at solid/rib
interface, 1000 mm from BA (B towards A)
and BC.

69

3.3.10c) Laps
At AB, check lap 1 no. H20 B to 2 no. H20 B in
rib full tension lap:
l0 = D1 D6 lb,rqd > l0,min
where
D1 = 1.0 (cd = 45 mm, i.e. < 3M)
D6 = 1.5 (as > 50% being lapped)
lb,rqd = (M/4) (Vsd/fbd)
where
M = 20
Vsd = 434.8
= 3.0 MPa as before
fbd

Laps
At AB, check lap 1 no. H20 B to 1 H20 B +
1H25 B in rib full tension lap:
l0 = D1 D6 lb,rqd > l0,min
where
D1 = 1.0 (cd = 45 mm, i.e. < 3M)
D6 = 1.5 (as > 50% being lapped)
lb,rqd = (M/4) (Vsd/fbd)
where
M = 20
Vsd = 434.8 (bar assumed to be fully
stressed)
fbd = 3.0 MPa as before

65

3.3.10d) Figure 3.17

See C below

74

3.4.5b) F3 = 310/Vs 1.5


where

F3 = 310/Vs 1.5
where

Figure 3.15

See B below

Both As,prov/As,req and any adjustment to N obtained from Expression (7.16a) or Expression (7.16b) is restricted to 1.5 by
Note 5 to Table NA.5 in the UK NA.
Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 4 of 13

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Vs = Vsn (As,req/As,prov) 1/G

Vs = Vsn (As,req/As,prov) 1/G


where
where
Vsn = (500/1.15) u (8.5 + 0.3 u 4.0)
Vsn = (500/1.15) u (8.5 + 4.0) /16.6 =
/16.6 = 254 MPa
327 MPa
(or | 253 MPa (From Concise
Figure 15.3 for Gk/Qk = 2.1, \2 = 0.3
and Jg = 1.25)
G = redistribution ratio = 1.03
G = redistribution ratio = 1.03
Vs | 327 u (1324/1570)/1.03 = 267
?
? Vs | 253 u (1324/1570)/1.03 = 207
?
F3
= 310/267 = 1.16
? F3 = 310/207 = 1.50
? Allowable l/d = 20.3 u 1.2 u 1.16 = 28.2
? Allowable l/d = 20.3 u 1.2 u 1.50 = 36.5
Actual l/d = 9500/260 = 36.5 ?no good
Actual l/d = 9500/260 = 36.5 ? OK
Try
H16 @100 (2010 mm2/m) and
Use H20 @ 200 B1 (1570)
F3 = As,prov /As,req 1.50
= 2010/ 1340 = 1.50 1.50
? Allowable l/d = 20.3 u 1.2 u 1.50 = 36.5
Actual l/d = 36.5 ? OK
Use H16@100B1 (2093 mm2/m)
78

3.4.7b) Allowable l/d = N u K u F1 u F2 u F3


Allowable l/d = N u K u F1 u F2 u F3
where
where
N = 26.2 (U = 0.40%, fck = 30)
N = 26.2 (U = 0.40%, fck = 30)
K = 1.2
(flat slab)
K = 1.2
(flat slab)
F1 = 1.0
(beff/bw = 1.0)
F1 = 1.0
(beff/bw = 1.0)
F2 = 1.0
(no brittle partitions)
F2 = 1.0
(no brittle partitions)
F3 = As,prov /As,req 1.50
F3 = 310/Vs
= 1005/ 959 = 1.05 1.50
where
Vs = Vsn (As,req/As,prov) 1/G
where
Vsn | 283 MPa (from Concise
Figure 15.3 and Gk/Qk = 3.6,
\2 = 0.3, Jg = 1.25)
G = redistribution ratio = 1.08
? Vs | 283 u (959/1005)/1.08 = 250
? F3 = 310/250 = 1.24
?Allowable l/d = 26.2 u 1.2 u 1.24 = 39.0
?Allowable l/d = 26.2 u 1.2 u 1.05 = 33.0
Actual l/d = 5900/240 = 24.5 ? OK
Actual l/d = 5900/240 = 24.5 ? OK
Use H16 @ 200 B2 (1005 mm2/m)
Use H16 @ 200 B2 (1005 mm2/m)

90

3.4.13

Spans 12 and 23:


Column strip and middle strip: H20 @ 200 B

Spans 12 and 23:


Column strip and middle strip: H16 @ 100 B1

92

3.4.13

Figure 3.26

See D below

112

4.2.6

F3 = 310/Vs 1.5
where

F3 = As,prov /As,req 1.50


= 4824/4158 = 1.16

Vs in simple situations = (fyk/JS)


(As,req/As,prov) (SLS loads/ULS
loads) (1/G). However in this case
separate analysis at SLS would be
required to determine Vs.
Therefore as a simplification use
the conservative assumption:
310/Vs = (500/fyk) (As,req/As,prov)
= (500/500)u(4824/4158) = 1.16

Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 5 of 13

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

123

4.3.5b) F3 = 310/Vs 1.5


where
Vs=(fyk/JS)(As,req/As,prov)(SLS loads/ULS loads)(1/G)
=434.8u(5835/5892) [(47.8+0.3u45.8)/(1.25 u
47.8 + 1.5 u 45.8)] u (1/0.945)
= 434.8 u 0.99 u 0.48 u 1.06
= 219 MPa

124

4.3.5b)

F3 = As,prov /As,req 1.50


= 5892/5835= 1.01

F3 = 310/Vs 1.5
= 310/219 = 1.41
? Permissible l/d= 17.8u1.3 u0.90u0.95 u1.41 = 27.9 ?Permissible l/d= 17.8u1.3 u0.90u0.95 u1.01 = 20.0
Actual l/d = 7500/252 = 29.8 ? no good Actual l/d = 7500/252 = 29.8 ? no good
Try 12 no. H32 B (9648 mm2)
Try 13 no. H25 B (6383 mm2)
F3 = As,prov /As,req 1.50
F3 = 310/Vs
3
= 9648 /5835 = 1.654 = say 1.50
= 310/219 u 13/12 = 1.53 = say 1.50
? Permissible l/d = 17.8u1.3u0.90u0.95u1.50 = 29.7
? Permissible l/d = 17.8u1.3u0.90u0.95u1.50 = 29.7
Actual leff/d = 7400/252 = 29.8
Actual leff/d = 7400/252 = 29.8
Say OK
Say OK
2
Use 13 no. H25 B (6383 mm2) Use 13 no. H25 B (6383 mm )

124

4.3.6

127

4.3.7d) F3 = 310/Vs 1.5


F3 = As,prov /As,req 1.50
= 3828/3783= 1.01
where
Vs=(fyk/JS)(As,req/As,prov)(SLS loads/ULS loads)(1/G)
=434.8u (3783/3828)[(47.8+0.3u 45.8)/(1.25
u 47.8 + 1.5 u 45.8)] u (1/0.908)
= 434.8 u 0.99 u 0.48 u 1.10
= 227 MPa
F3 = 310/Vs
= 310/227 = 1.37
? Permissible l/d = 44.7 u 1.37 u 0.88 u 0.95
? Permissible l/d
u 1.37 = 70.1
= 44.7 u 1.50 u 0.88 u 0.95 u 1.01 = 56.6
Actual l/d = 7500/252 = 29.8 ? OK
Use 8 no. H25 B (3928 mm2) (which is < 40K = 40 x 1.5 =60)
[Table NA.5 Note 6]

Figure 4.20

See E below

Actual l/d = 7500/252 = 29.8 ? OK


Use 8 no. H25 B (3928 mm2
133

4.3.10

Figures 4.22 and 4.23

See F below

146

5.3

Figure 5.6
300 mm flat slabs All columns 400 mm sq

300 mm flat slabs All columns 500 mm sq

153

5.3.8

2WP]VTa`TS

183

References

183

References

1a National Annex to Eurocode 2- Part 1- 1a National Annex to Eurocode 2- Part 11. BSI 2005
1. Incorporating Amendment No.1 BSI
2009
5 R S NARAYANAN & C H GOODCHILD. 5 R S NARAYANAN & C H GOODCHILD.
The Concrete Centre. Concise Eurocode The Concrete Centre. Concise Eurocode
2, CCIP-005. TCC 2006
2, CCIP-005. TCC 2006 As Amended

Both As,prov/As,req and any adjustment to N obtained from Expression (7.16a) or Expression (7.16b) is restricted to 1.5 by
Note 5 to Table NA.5 in the UK NA.
4
Both As,prov/As,req and any adjustment to N obtained from Expression (7.16a) or Expression (7.16b) is restricted to 1.5 by
Note 5 to Table NA.5 in the UK NA.
Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 6 of 13

190

B1.1

Delete existing text. See G below

2010
New text:
According to Note 5 of Table NA.5 the NA
[1a]
to BS EN 1992-1-1 the modification
factor for service stress used with the l/d
method of checking the SLS state of
deformation (designated factor F3 in TCC
publications) may be determined as either

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

310/Vs using characteristic load


combinations to determine the
service stress, Vs

or
x

(500/fyk)(As,prov /As,req)

In either case the modification factor is


restricted to a maximum of 1.50. In the
UK
fyk = 500 MPa.
Assuming Vs is proportional to Vu, and
using characteristic load combinations to
determine Vs produces values of 310/Vs =
1.00 +3% - 6%. and so is not as attractive
to using As,prov /As,req.
The use of F3 = As,prov /As,req 1.5 is
therefore advocated in checking
deformation using the l/d method.
190
191
191
201
204

B1.2
B1.4
B1.5
C7
C8

See H below
See J below
See K below
See L below
See M below

Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 7 of 13

A Amends to p 51 Figure 3.7

300
250

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

150
125

300
250

B Amends to p 65 Figure 3.15

2H20/rib
1H25 + 1H20/rib
x3

C Amends to p 70 Figure 3.17

2H20/rib
1H25 + 1H20/rib
x2
Note curtailed bat

Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 8 of 13

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

D Amends to p 92 Figure 3.26

H20@200
H16@100

E Amends to p 124 Figure 4.20

25 bar
32 bar

20 bar
20/25 bar

Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 9 of 13

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

F Amends to p133 Figures 4.22 and 4.23

13H25
12H32
x2
T25 in
section
x2

G Amends to p190 B1.1


NewText
According to Note 5 of Table NA.5 the NA to BS EN
1992-1-1[1a] the modification factor for service stress
used with the l/d method of checking the SLS state of
deformation (designated factor F3 in TCC
publications) may be determined as either
x

310/Vs using characteristic load combinations


to determine the service stress, Vs

(500/fyk)(As,prov /As,req)

or

In either case the modification factor is restricted to a


maximum of 1.50. In the UK
fyk = 500 MPa.
Assuming Vs is simply proportional to the ultimate
stress, Vu, produces values of 310/Vs = 1.00 +/- 5%
and so for hand calculations is not as attractive as
using As,prov /As,req.
The use of F3 = As,prov /As,req 1.5 is therefore
advocated in checking deformation using the l/d
method by hand.

Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 10 of 13

H Amends to p190 B1.2


combination values
of actions

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

combination values of actions


taking account of SLS moments,
compression reinforcement,
As,prov /As,req, etc.

[1]
310/Vs

NewText

[1a]

an accurate

J Amends to p191 B1.4

were

Add new text

using the quasi


permanent values of
actions (see B.4)

New para

In the light of the


above disparity and
pending clarification,
the UK NA was revised
and published in
December 2009 as
detailed in B1.1 above.

Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 11 of 13

K Amends to p191 B1.4

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

New paras

Prior to the publication of the


revised UK NA[1a] it was allowable
to calculate the moderation factor
using in l/d verifications of
deformation(F3) by using quasi
permanent loads.
Assuming Vs due to quasi
permanent actions is proportional
to Vu, the method as outlined in C8
may be used to determine Vs in
verifications of crack widths, etc.

L Amends to p201 C7

New text:
either
x

310/Vs using characteristic load


combinations to determine the
service stress, Vs

(500/fyk)(As,prov /As,req)

or

In either case the modification factor is


restricted to a maximum of 1.50.

Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 12 of 13

M Amends to p204 C8

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

below

New text ex p 201:

chg 25 Feb 2010

Amends to Worked Examples to Eurocode 2 - Jan 2012.doc

Page 13 of 13

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

: cement Zg] concrete bg]nlmkr in[eb\Zmbhg

Phkd^]>qZfie^l
mh>nkh\h]^+3Ohenf^*
 ?hkma^]^lb`gh_bg&lbmn\hg\k^m^^e^f^gmlbg_kZf^][nbe]bg`l

mh;L>G*22+&*&*3+))-Zg]bmlNDGZmbhgZe:gg^q3+)).

<A@hh]\abe];L\<>g`F<BH;FBLmkn\m>^mZe

?hk^phk]

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

The introduction of European standards to UK construction is a signicant event as, for the
rst time, all design and construction codes within the EU will be harmonised. The ten design
standards, known as the Eurocodes, will affect all design and construction activities as all current
British Standards for structural design are due to be withdrawn in 2010.
The cement and concrete industry recognised the need to enable UK design professionals to use
Eurocode 2, Design of concrete structures, quickly, effectively, efciently and with condence.
Supported by government, consultants and relevant industry bodies, the Concrete Industry
Eurocode 2 Group (CIEG) was formed in 1999 and this Group has provided the guidance for a
coordinated and collaborative approach to the introduction of Eurocode 2.
As a result, a range of resources are being delivered by the concrete sector (see www.eurocode2.info).
The aim of this publication, Worked Examples to Eurocode 2: Volume 1 is to distil from Eurocode 2,
other Eurocodes and other sources the material that is commonly used in the design of concrete
framed buildings.
These worked examples are published in two parts. Volume 2 will include chapters on Foundations,
Serviceability, Fire and Retaining walls.

:\dghpe^]`^f^gml
The original ideas for this publication emanates from the research project `Eurocode 2: Transition
from UK to European concrete design standards, which was led by the BCA and part funded by
the DTI under their PII scheme and was overseen by a Steering Group and the CIEG. The work has
been brought to fruition by The Concrete Centre from early initial drafts by various authors listed
on the inside back cover. The concrete industry acknowledges and appreciates the support given
by many individuals, companies and organisations in the preparation of this document. These are
listed on the inside back cover.
We gratefully acknowledge the authors of the initial drafts and the help and advice given by Robin
Whittle in checking the text. Thanks are also due to Gillian Bond, Kevin Smith, Sally Huish and the
design team at Michael Burbridge Ltd for their work on the production.
The copyright of British Standards extracts reproduced in this document is held by the British Standards Institution (BSI).
Permission to reproduce extracts from British Standards is granted by BSI under the terms of Licence No: 2009RM010. No other
use of this material is permitted. This publication is not intended to be a replacement for the standard and may not reect the
most up-to-date status of the standard. British Standards can be obtained in PDF or hard copy formats from the BSI online shop:
http://shop.bsigroup.com or by contacting BSI Customer Services for hard copies only:
Tel:+44 (0)20 8996 9001, Email: cservices@bsigroup.com.

In[ebla^][rMa^<hg\k^m^<^gmk^%iZkmh_ma^Fbg^kZeIkh]n\ml:llh\bZmbhg
Kbo^klb]^Ahnl^%-F^Z]hpl;nlbg^llIZkd%LmZmbhg:iikhZ\a%;eZ\dpZm^k%<Zf[^ke^r%Lnkk^r@N*02:;
M^e3$--!)"*+0//)/1))?Zq3$--!)"*+0//)/1)*ppp'\hg\k^m^\^gmk^'\hf
Ma^<hg\k^m^<^gmk^bliZkmh_ma^Fbg^kZeIkh]n\ml:llh\bZmbhg%ma^mkZ]^Zllh\bZmbhg_hkma^Z``k^`Zm^l%
ZliaZem%\^f^gm%\hg\k^m^%ebf^%fhkmZkZg]lbeb\ZlZg]bg]nlmkb^l'ppp'fbg^kZeikh]n\ml'hk`
<^f^gmZg]<hg\k^m^Bg]nlmkrIn[eb\Zmbhgl!<<BI"Zk^ikh]n\^]makhn`aZgbg]nlmkrbgbmbZmbo^mh
in[eblam^\agb\Ze`nb]Zg\^bglniihkmh_\hg\k^m^]^lb`gZg]\hglmkn\mbhg'<<BIin[eb\ZmbhglZk^
ZoZbeZ[e^_khfma^<hg\k^m^;hhdlahiZmppp'\hg\k^m^[hhdlahi'\hfM^e3$--!)"0))-&/)0000
<<BI&)-*
In[ebla^]=^\^f[^k+))2
BL;G201&*&2)-/1*1&1-&0
Ikb\^@khniI
FI:&Ma^<hg\k^m^<^gmk^
All advice or information from MPA - The Concrete Centre is intended only for use in the UK by those who will evaluate the
signicance and limitations of its contents and take responsibility for its use and application. No liability (including that for
negligence) for any loss resulting from such advice or information is accepted by MPA - The Concrete Centre or its subcontractors,
suppliers or advisors. Readers should note that the publications from MPA - The Concrete Centre are subject to revision from time
to time and should therefore ensure that they are in possession of the latest version.
Printed by Michael Burbridge Ltd, Maidenhead, UK.

Phkd^]>qZfie^l
mh>nkh\h]^+3Ohenf^*
Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

<hgm^gml


Lrf[hel

bb

-

;^Zfl

20

-')

@^g^kZe

20

*

Bgmkh]n\mbhg

*

-'*

<hgmbgnhnl[^Zfhgibglniihkml

*'*

:bf

-'+

A^ZoberehZ]^]E&[^Zf

*)-

*'+

>nkh\h]^3;Zlblh_lmkn\mnkZe]^lb`g

-',

<hgmbgnhnlpb]^M&[^Zf

**2

*',

>nkh\h]^*3:\mbhglhglmkn\mnk^l

*'-

>nkh\h]^+3=^lb`gh_\hg\k^m^lmkn\mnk^l

.

<henfgl

*,-

*'.

GZmbhgZe:gg^q^l

.')

@^g^kZe

*,-

*'/

;Zlblh_ma^phkd^]^qZfie^lbgmablin[eb\Zmbhg .

.'*

>]`^\henfg

*,.

*'0

:llnfimbhgl

.'+

I^kbf^m^k\henfg!bgm^kgZe^gobkhgf^gm"

*,2

*'1

FZm^kbZeikhi^kmb^l

.',

Bgm^kgZe\henfg

*-/

*'2

>q^\nmbhg

.'-

+

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml

L fZeei^kbf^m^k\henfgln[c^\m
mhmph&ahnk_bk^k^lblmZg\^

*.0

+'*

F^mah]lh_ZgZerlbl

/

PZeel

*//

+'+

:\mbhgl

/')

@^g^kZe

*//

+',

<aZkZ\m^kblmb\oZen^lh_Z\mbhgl

/'*

La^ZkpZee

*/0

+'-

OZkbZ[e^Z\mbhgl3bfihl^]ehZ]l

+'.

OZkbZ[e^Z\mbhgl3lghpehZ]l

*+

0

K^_^k^g\^lZg]_nkma^kk^Z]bg`

*1,

+'/

OZkbZ[e^Z\mbhgl3pbg]ehZ]l

*,

:ii^g]bq:3 =^kbo^]_hkfneZ^

*1.

+'0

OZkbZ[e^Z\mbhgl3hma^kl

*0

+'1

I^kfZg^gmZ\mbhgl

*1

:ii^g]bq;3 L^kob\^Z[bebmrebfbmlmZm^

*2)

+'2

=^lb`goZen^lh_Z\mbhgl

+*

:ii^g]bq<3 =^lb`gZb]l

*2-

21

+'*) EhZ]ZkkZg`^f^gmh_Z\mbhgl3bgmkh]n\mbhg

+.

+'** E hZ]ZkkZg`^f^gmlZ\\hk]bg`mhma^
NDGZmbhgZe:gg^qmh>nkh\h]^

+.

+'*+ >qZfie^lh_ehZ]bg`

+0

,

LeZ[l

,.

Li^\bZe]^mZbel3lmknmmb^

,')

@^g^kZe

,.

L^kob\^Z[bebmr

,'*

Lbfierlniihkm^]hg^&pZrleZ[

,/

?bk^

,'+

<hgmbgnhnlhg^&pZrlheb]leZ[

-)

K^mZbgbg`pZee

,',

<hgmbgnhnlkb[[^]leZ[

.+

K^_^k^g\^lZg]_nkma^kk^Z]bg`

,'-

?eZmleZ[

0*

:ii^g]bq:3=^kbo^]_hkfneZ^

,'.

LmZbk_eb`am

2.

:ii^g]bq;3=^lb`gZb]l

Ohenf^+!in[ebla^]l^iZkZm^er"
?hng]Zmbhgl

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Symbols and abbreviations used in this publication


Symbol

Definition

:

<khll&l^\mbhgZeZk^Z4:\\b]^gmZeZ\mbhg

:

Lbm^Zembmn]^%f!lghp"

:

:embmn]^h_ma^lbm^bgf^mk^lZ[ho^f^Zgl^Ze^o^e!pbg]"

:%;%<

OZkbZ[e^lnl^]bgma^]^m^kfbgZmbhgh_lebf

:\

<khll&l^\mbhgZeZk^Zh_\hg\k^m^

:]

=^lb`goZen^h_ZgZ\\b]^gmZeZ\mbhg

:>]

=^lb`goZen^h_Zl^blfb\Z\mbhg

:k^_

K^_^k^g\^Zk^Zh_ma^lmkn\mnk^hklmkn\mnkZe^e^f^gm!pbg]"

:l

<khll&l^\mbhgZeZk^Zh_k^bg_hk\^f^gm

:l%fbg

Fbgbfnf\khll&l^\mbhgZeZk^Zh_k^bg_hk\^f^gm

:l%ikho

:k^Zh_lm^^eikhob]^]

:l%k^j

:k^Zh_lm^^ek^jnbk^]

:l*

:k^Zh_k^bg_hk\bg`lm^^ebgeZr^k*

:l+

:k^Zh_\hfik^llbhglm^^e!bgeZr^k+"

:le

:k^Zh_ma^m^glbe^k^bg_hk\^f^gm^qm^g]bg`Zme^Zlme[]$][^rhg]ma^l^\mbhg\hglb]^k^]

:lF!:lG"

M hmZeZk^Zh_k^bg_hk\^f^gmk^jnbk^]bglrff^mkb\Ze%k^\mZg`neZk\henfglmhk^lblmfhf^gm!ZqbZeehZ]"nlbg`
lbfieb_b^]\Ze\neZmbhgf^mah]

:lp

 khll&l^\mbhgZeZk^Zh_la^Zkk^bg_hk\^f^gm4:k^Zh_ing\abg`la^Zkk^bg_hk\^f^gmbghg^i^kbf^m^kZkhng]ma^
<
\henfg

:lp%fbg

 bgbfnf\khll&l^\mbhgZeZk^Zh_la^Zkk^bg_hk\^f^gm4FbgbfnfZk^Zh_ing\abg`la^Zkk^bg_hk\^f^gmbghg^
F
i^kbf^m^kZkhng]ma^\henfg

:m

:k^Zh_m^glbe^k^bg_hk\^f^gmbg_eZmleZ[\henfglmkbil

Z

=blmZg\^%ZeehpZg\^Zmlniihkml

Z

:qbl]blmZg\^_khfma^\hg\k^m^lnk_Z\^mhma^\^gmk^h_ma^[Zk!_bk^"

Z

:g^qihg^gm!bg\hglb]^kbg`[bZqbZe[^g]bg`h_\henfgl"

Z

Ikhc^\mbhgh_ma^_hhmbg`_khfma^_Z\^h_ma^\henfghkpZee

Ze

 blmZg\^[rpab\ama^eh\Zmbhgpa^k^Z[Zkblghehg`^kk^jnbk^]_hk[^g]bg`fhf^gmbl]blieZ\^]mhZeehp_hkma^
=
_hk\^l_khfma^mknllfh]^e_hkla^Zk'!Lab_m]blmZg\^_hk\nkmZbef^gm"

Z*%Z+%

=blmZg\^_khf^]`^h_lniihkmmh\^gmk^h_lniihkm

Z*%[*

=bf^glbhglh_ma^\hgmkhei^kbf^m^kZkhng]Zg^ehg`Zm^]lniihkm!ing\abg`la^Zk"

Z'f'l'e'

:embmn]^Z[ho^f^Zgl^Ze^o^e

[

Ho^kZeepb]mah_Z\khll&l^\mbhg%hk_eZg`^pb]mabgZM&hkE&[^Zf

[

;k^Z]mah_[nbe]bg`!pbg]"

[^

>__^\mbo^pb]mah_Z_eZmleZ[!Z]cZ\^gmmhi^kbf^m^k\henfg"

[^__

>__^\mbo^pb]mah_Z_eZg`^

[^j!a^j"

>jnboZe^gmpb]ma!a^b`am"h_\henfg6[!a"_hkk^\mZg`neZkl^\mbhgl

[fbg

Fbgbfnfpb]mah_p^[hgM&%B&hkE&[^Zfl

[m

F^Zgpb]mah_ma^m^glbhgshg^'?hkZM&[^Zfpbmama^_eZg`^bg\hfik^llbhg%hgerma^pb]mah_ma^p^[blmZd^g
bgmhZ\\hngm

[p

Pb]mah_ma^p^[hgM&%B&hkE&[^Zfl'Fbgbfnfpb]ma[^mp^^gm^glbhgZg]\hfik^llbhg\ahk]l

[*

AZe_h_]blmZg\^[^mp^^gZ]cZ\^gmp^[lh_]hpglmZg][^Zfl

<^

>qihlnk^\h^__b\b^gm!lghp"

<m

Ma^kfZe\h^__b\b^gm!lghp"

<p

La^Zk\^gmk^

ii

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Symbol

Definition

\*%\+

 bf^glbhglh_Zk^\mZg`neZk\henfg'?hk^]`^\henfgl%\*blf^Zlnk^]i^ki^g]b\neZkmhma^_k^^^]`^!ing\abg`
=
la^Zk"

\Zem

:embmn]^_Z\mhk!pbg]"

\]

=rgZfb\_Z\mhk!pbg]"

\]bk

=bk^\mbhgZe_Z\mhk!pbg]"

\^%_eZm

>qihlnk^_Z\mhk!pbg]"

\_

?hk\^\h^__b\b^gm!pbg]"

\fbg

Fbgbfnf\ho^k%!]n^mhma^k^jnbk^f^gml_hk[hg]%\fbg%[hk]nkZ[bebmr\fbg%]nk"

\ghf

GhfbgZe\ho^k'GhfbgZe\ho^klahne]lZmbl_rma^fbgbfnfk^jnbk^f^gmlh_[hg]%]nkZ[bebmrZg]_bk^

\i^

!>qm^kgZe"ik^llnk^\h^__b\b^gm!pbg]"

\i^%*)

!>qm^kgZe"ik^llnk^\h^__b\b^gm_hkZk^Zl7*f+!pbg]"

\ib

Bgm^kgZeik^llnk^\h^__b\b^gm!pbg]"

\ikh[

Ikh[Z[bebmr_Z\mhk!pbg]"

\l^Zlhg

L^Zlhg_Z\mhk!pbg]"

\l

Lbs^_Z\mhk!pbg]"

\r%\q

<henfg]bf^glbhglbgieZg

D\]^o

:eehpZg\^fZ]^bg]^lb`g_hk]^obZmbhg

=

=bZf^m^kh_Z\bk\neZk\henfg4=bZf^m^k

]

>__^\mbo^]^imamhm^glbhglm^^e

]+

>__^\mbo^]^imamh\hfik^llbhglm^^e

]\

>__^\mbo^]^imah_\hg\k^m^bg\hfik^llbhg

>

>__^\mh_Z\mbhg4Bgm^`kbmr!bg_bk^"4>eZlmb\fh]nenl

>\]

=^lb`goZen^h_fh]nenlh_^eZlmb\bmrh_\hg\k^m^

>\f

L^\Zgmfh]nenlh_^eZlmb\bmrh_\hg\k^m^

>I

;^g]bg`lmb__g^ll

>l

=^lb`goZen^h_fh]nenlh_^eZlmb\bmrh_k^bg_hk\bg`lm^^e

>qi'

>qik^llbhg

>JN

LmZmb\^jnbeb[kbnf

^

>\\^gmkb\bmr

^)

Fbgbfnf^\\^gmkb\bmrbg\henfgl

^+

=^_e^\mbhg!nl^]bgZll^llbg`F+bgle^g]^k\henfgl"

^b

>\\^gmkb\bmr]n^mhbfi^k_^\mbhgl

^r%^s

>\\^gmkb\bmr%F>] (O>]Zehg`rZg]sZq^lk^li^\mbo^er!ing\abg`la^Zk"

?*

?Z\mhkmhZ\\hngm_hk_eZg`^]l^\mbhgl!]^_e^\mbhg"

?+

?Z\mhkmhZ\\hngm_hk[kbmme^iZkmbmbhglbgZllh\bZmbhgpbmaehg`liZgl!]^_e^\mbhg"

?,

?Z\mhkmhZ\\hngm_hkl^kob\^lmk^llbgm^glbe^k^bg_hk\^f^gm!]^_e^\mbhg"

?

:\mbhg

?>F

?bq^]^g]fhf^gm

?\!?l"

?hk\^bg\hg\k^m^!lm^^e"

?]

=^lb`goZen^h_ZgZ\mbhg

?>

M^glbe^_hk\^bgk^bg_hk\^f^gmmh[^Zg\ahk^]

?d

<aZkZ\m^kblmb\oZen^h_ZgZ\mbhg

?k^i

K^ik^l^gmZmbo^Z\mbhg!6r?dpa^k^r6_Z\mhkmh\hgo^km\aZkZ\m^kblmb\mhk^ik^l^gmZmbo^Z\mbhg"

?l

M^glbe^_hk\^bgk^bg_hk\^f^gm

?m]

=^lb`goZen^h_ma^m^glbe^_hk\^bgehg`bmn]bgZek^bg_hk\^f^gm

D?m]

:]]bmbhgZem^glbe^_hk\^bgehg`bmn]bgZek^bg_hk\^f^gm]n^mhma^mknllla^Zkfh]^e
iii

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Symbol

Definition

?O%>]

MhmZeo^kmb\ZeehZ]!hg[kZ\^]Zg][kZ\bg`f^f[^kl"

?p

K^lnemZgm\aZkZ\m^kblmb\_hk\^]n^mhpbg]'!L^^l^\mbhg+'/"

_[]

NembfZm^[hg]lmk^ll

_\]

=^lb`goZen^h_\hg\k^m^\hfik^llbo^lmk^g`ma

_\d

<aZkZ\m^kblmb\\hfik^llbo^\rebg]^klmk^g`mah_\hg\k^m^Zm+1]Zrl

_\m%]

=^lb`gm^glbe^lmk^g`mah_\hg\k^m^!a\m _\m%d (g<"

_\m%d

<aZkZ\m^kblmb\ZqbZem^glbe^lmk^g`mah_\hg\k^m^

_\mf

F^ZgoZen^h_ZqbZem^glbe^lmk^g`mah_\hg\k^m^

_l\

<hfik^llbo^lmk^llbg\hfik^llbhgk^bg_hk\^f^gmZmNEL

_r]

=^lb`grb^e]lmk^g`mah_ehg`bmn]bgZek^bg_hk\^f^gm%:le

_rd

<aZkZ\m^kblmb\rb^e]lmk^g`mah_k^bg_hk\^f^gm

_rp]

=^lb`grb^e]lmk^g`mah_ma^la^Zkk^bg_hk\^f^gm

_rp]%^_

>__^\mbo^]^lb`glmk^g`mah_ing\abg`la^Zkk^bg_hk\^f^gm

_rpd

<aZkZ\m^kblmb\rb^e]lmk^g`mah_la^Zkk^bg_hk\^f^gm

@d

<aZkZ\m^kblmb\oZen^h_Zi^kfZg^gmZ\mbhg

@d%lni

Nii^k\aZkZ\m^kblmb\oZen^h_Zi^kfZg^gmZ\mbhg

@d%bg_

Ehp^k\aZkZ\m^kblmb\oZen^h_Zi^kfZg^gmZ\mbhg

`d

<aZkZ\m^kblmb\oZen^h_Zi^kfZg^gmZ\mbhgi^kngbme^g`mahkZk^Z

Ab

AhkbshgmZeZ\mbhgZiieb^]ZmZe^o^e

A

A^b`amh_[nbe]bg`!pbg]"

a

Ho^kZee]^imah_Z\khll&l^\mbhg4A^b`am

aZo^

H[lmkn\mbhga^b`am!pbg]"

a]bl

=blieZ\^f^gma^b`am!pbg]"

a_

=^imah__hhmbg`4Mab\dg^llh__eZg`^

al

=^imah_leZ[

I

L^\hg]fhf^gmh_Zk^Zh_\hg\k^m^l^\mbhg4Bg^kmbZ

I

BglneZmbhg!bg_bk^"

b

KZ]bnlh_`rkZmbhg

D

F>] ([] +_\d':f^Zlnk^h_ma^k^eZmbo^\hfik^llbo^lmk^llbgZf^f[^kbg_e^qnk^

D

?Z\mhkmhZ\\hngm_hklmkn\mnkZelrlm^f!]^_e^\mbhg"

D 

OZen^h_DZ[ho^pab\a\hfik^llbhgk^bg_hk\^f^gmblk^jnbk^]

Do

:\hkk^\mbhg_Z\mhk_hkZqbZeehZ]

Df

:\hkk^\mbhg_Z\mhk_hk\k^^i

d

<h^__b\b^gmhk_Z\mhk

d

K^eZmbo^_e^qb[bebmrhkk^eZmbo^lmb__g^ll

e

<e^Zka^b`amh_\henfg[^mp^^g^g]k^lmkZbgml

e

A^b`amh_ma^lmkn\mnk^bgf^mk^l

e!hkE"

E^g`ma4LiZg

e)

>__^\mbo^e^g`ma!h_\henfgl"

e)

=blmZg\^[^mp^^gihbgmlh_s^khfhf^gm

e)

=^lb`geZie^g`ma

e)%_b

>__^\mbo^e^g`mang]^k_bk^\hg]bmbhgl

e[

;Zlb\Zg\ahkZ`^e^g`ma

e[]

=^lb`gZg\ahkZ`^e^g`ma

e[%^j

>jnboZe^gmZg\ahkZ`^e^g`ma

e[%fbg

FbgbfnfZg\ahkZ`^e^g`ma

iv

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Symbol

Definition

e[%kj]

;Zlb\Zg\ahkZ`^e^g`ma

e^__

>__^\mbo^liZg

eg

<e^ZkliZg

er%es

LiZglh_Zmph&pZrleZ[bgma^rZg]s]bk^\mbhgl

F

;^g]bg`fhf^gm'Fhf^gm_khf_bklmhk]^kZgZerlbl

F

Fhf^gm\ZiZ\bmrh_Zlbg`erk^bg_hk\^]l^\mbhg!Z[ho^pab\a\hfik^llbhgk^bg_hk\^f^gmblk^jnbk^]"

F)%>ji

?bklmhk]^k[^g]bg`fhf^gmbgjnZlbi^kfZg^gmehZ]\hf[bgZmbhg!LEL"

F)*%F)+

?bklmhk]^k^g]fhf^gmlZmNELbg\en]bg`ZeehpZg\^l_hkbfi^k_^\mbhgl

F)>]

>jnboZe^gm_bklmhk]^kfhf^gmbg\en]bg`ma^^__^\mh_bfi^k_^\mbhgl!ZmZ[hnmfb]a^b`am"

F)>]%_b

?bklmhk]^kfhf^gmng]^k_bk^\hg]bmbhgl

F+

GhfbgZel^\hg]hk]^kfhf^gmbgle^g]^k\henfgl

F>]

=^lb`goZen^h_ma^Ziieb^]bgm^kgZe[^g]bg`fhf^gm

F>]r%F>]s

=^lb`gfhf^gmbgma^k^li^\mbo^]bk^\mbhg

FK]r%FK]s

Fhf^gmk^lblmZg\^bgma^k^li^\mbo^]bk^\mbhg

Fm

=^lb`gmkZgl_^kfhf^gmmh\henfg_khfZ_eZmleZ[

f

Gnf[^kh_o^kmb\Zef^f[^kl\hgmkb[nmbg`mhZg^__^\m

f

FZll

G

:qbZe_hk\^

G

;Zlb\liZg&mh&^__^\mbo^&]^imakZmbh%e(]%_hkD6*')

G)>]%_b

:qbZeehZ]ng]^k_bk^\hg]bmbhgl

G:

GZmbhgZe:gg^q

GZ%G[

Ehg`bmn]bgZe_hk\^l\hgmkb[nmbg`mhAb

G>]

=^lb`goZen^h_ma^Ziieb^]ZqbZe_hk\^!m^glbhghk\hfik^llbhg"ZmNEL

G=I

GZmbhgZeer=^m^kfbg^]IZkZf^m^k!l"Zlin[ebla^]bgZ\hngmkrlGZmbhgZe:gg^q

g

EhZ]e^o^eZmghkfZem^fi^kZmnk^l'<hgl^koZmbo^erg6)'0!_bk^"

g

:qbZelmk^llZmNEL

g

NembfZm^Z\mbhg!ehZ]"i^kngbme^g`ma!hkZk^Z"

g

K^eZmbo^ZqbZe_hk\^G>] (!:\ _\]"

g[Ze

Ma^oZen^h_gZmfZqbfnffhf^gmk^lblmZg\^

g)%gl

Gnf[^kh_lmhk^rl

Jd

<aZkZ\m^kblmb\oZen^h_ZoZkbZ[e^Z\mbhg

Jd*!Jdb"

<aZkZ\m^kblmb\oZen^h_Ze^Z]bg`oZkbZ[e^Z\mbhg!<aZkZ\m^kblmb\oZen^h_ZgZ\\hfiZgrbg`oZkbZ[e^Z\mbhg"

jd

<aZkZ\m^kblmb\oZen^h_ZoZkbZ[e^Z\mbhgi^kngbme^g`mahkZk^Z

j[

;Zlb\pbg]ik^llnk^

ji

I^Zdpbg]ik^llnk^

ji!s^"

I^Zdo^eh\bmrik^llnk^Zmk^_^k^g\^a^b`ams^%!pbg]"

K

K^lblmZg\^4F^\aZgb\Zek^lblmZg\^!bg_bk^"

K:

K^Z\mbhgZmlniihkm:

K;

K^Z\mbhgZmlniihkm;

K]

=^lb`goZen^h_ma^k^lblmZg\^mhZgZ\mbhg

k

KZ]bnl

kf

KZmbhh__bklmhk]^k^g]fhf^gmlbg\henfglZmNEL

LEL

L ^kob\^Z[bebmrebfbmlmZm^!l"\hkk^lihg]bg`mh\hg]bmbhgl[^rhg]pab\ali^\b_b^]l^kob\^k^jnbk^f^gmlZk^gh
ehg`^kf^m

l

LiZ\bg`

l

LghpehZ]hgZkhh_
v

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Symbol

Definition

ld

<aZkZ\m^kblmb\`khng]lghpehZ]

lk

KZ]bZeliZ\bg`h_i^kbf^m^klh_la^Zkk^bg_hk\^f^gm

lm

MZg`^gmbZeliZ\bg`la^Zkk^bg_hk\^f^gmZehg`i^kbf^m^klh_la^Zkk^bg_hk\^f^gm

m

Mab\dg^ll4Mbf^[^bg`\hglb]^k^]4;k^Z]mah_lniihkm

m)

Ma^Z`^h_\hg\k^m^Zmma^mbf^h_ehZ]bg`

NEL

NembfZm^ebfbmlmZm^!l"Zllh\bZm^]pbma\heeZil^hkhma^k_hkflh_lmkn\mnkZe_Zbenk^

n

I^kbf^m^kh_\hg\k^m^\khll&l^\mbhg%aZobg`Zk^Z:\

n

I^kbf^m^kh_maZmiZkmpab\abl^qihl^]mh]krbg`

n

<bk\nf_^k^g\^h_hnm^k^]`^h_^__^\mbo^\khll&l^\mbhg!mhklbhg"

n)

I^kbf^m^kZ]cZ\^gmmh\henfgl!ing\abg`la^Zk"

n*

;Zlb\\hgmkhei^kbf^m^k!Zm+]_khf_Z\^h_ehZ]"!ing\abg`la^Zk"

n*#

K^]n\^]\hgmkhei^kbf^m^kZmi^kbf^m^k\henfgl!Zm+]_khf_Z\^h_ehZ]"!ing\abg`la^Zk"

nb

E^g`mah_ma^\hgmkhei^kbf^m^kng]^k\hglb]^kZmbhg!ing\abg`la^Zk"

nhnm

I^kbf^m^kZmpab\ala^Zkk^bg_hk\^f^gmblghehg`^kk^jnbk^]

O

La^Zk_hk\^

O>]

=^lb`goZen^h_ma^Ziieb^]la^Zk_hk\^

OK]%\

La^Zkk^lblmZg\^h_Zf^f[^kpbmahnmla^Zkk^bg_hk\^f^gm

OK]%fZq

La^Zkk^lblmZg\^h_Zf^f[^kebfbm^][rma^\knlabg`h_\hfik^llbhglmknml

OK]%\fbg

Fbgbfnfla^Zkk^lblmZg\^h_f^f[^k\hglb]^kbg`\hg\k^m^Zehg^

OK]%l

La^Zkk^lblmZg\^h_Zf^f[^k`ho^kg^][rma^rb^e]bg`h_la^Zkk^bg_hk\^f^gm

o[

;Zlb\pbg]o^eh\bmr

o[%)

M a^_ng]Zf^gmZe[Zlb\pbg]o^eh\bmr[^bg`ma^\aZkZ\m^kblmb\*)fbgnm^pbg]o^eh\bmrZm*)fZ[ho^`khng]e^o^ebg
hi^g\hngmkr

o[%fZi

?ng]Zf^gmZe[Zlb\pbg]o^eh\bmr_khf?b`nk^G:'*f(l

o>]

Ing\abg`la^Zklmk^ll

o>]

La^Zklmk^ll_hkl^\mbhglpbmahnmla^Zkk^bg_hk\^f^gm!6O>] ([p]"

o>]%s

La^Zklmk^ll_hkl^\mbhglpbmala^Zkk^bg_hk\^f^gm!6O>] ([ps6O>] ([p)'2]"

oK]%\

=^lb`gla^Zkk^lblmZg\^h_\hg\k^m^pbmahnmla^Zkk^bg_hk\^f^gm^qik^ll^]ZlZlmk^ll

oK]%fZq

<ZiZ\bmrh_\hg\k^m^lmknml^qik^ll^]ZlZlmk^ll

P*

?Z\mhk\hkk^lihg]bg`mhZ]blmkb[nmbhgh_la^Zk!ing\abg`la^Zk"

P^

I^Zd^qm^kgZepbg]ehZ]

Pd

 aZkZ\m^kblmb\oZen^h_pbg]Z\mbhg!G;ghmbgma^>nkh\h]^lZg]lahne][^k^`Zk]^]ZlZ_hkfh_Jd%
<
\aZkZ\m^kblmb\oZen^h_ZoZkbZ[e^Z\mbhg"

pd

<aZkZ\m^kblmb\ngbmpbg]ehZ]'

pd

<kZ\dpb]ma

pfZq

Ebfbmbg`\Ze\neZm^]\kZ\dpb]ma

Q)%Q:%Q< <hg\k^m^^qihlnk^\eZll^l
Q=%Q?%QL
q

G^nmkZeZqbl]^ima

q

=blmZg\^[^mp^^g[nbe]bg`l!pbg]"

q

=blmZg\^h_ma^l^\mbhg[^bg`\hglb]^k^]_khfma^\^gmk^ebg^h_ma^lniihkm

q%r%s

<h&hk]bgZm^l4IeZg^lng]^k\hglb]^kZmbhg

qn

=^imah_ma^g^nmkZeZqblZmma^nembfZm^ebfbmlmZm^Z_m^kk^]blmkb[nmbhg

S

Shg^gnf[^kh[mZbg^]_khffZi!lghp"

s

E^o^kZkfh_bgm^kgZe_hk\^l

vi

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Symbol

Definition

s

K^_^k^g\^a^b`am!pbg]"

s^

K^_^k^g\^a^b`am_hkpbg]pZk]pZeelh_k^\mZg`neZk[nbe]bg`l!pbg]"

a

:g`e^4:g`e^h_la^Zkebgdlmhma^ehg`bmn]bgZeZqbl4KZmbh

a:

:\h^__b\b^gm_hknl^pbmaZk^ik^l^gmZmbo^oZkbZ[e^Z\mbhgmZdbg`bgmhZ\\hngmZk^Zlniihkm^]

a*%a+%a,
a-%a.%a/

?Z\mhkl]^Zebg`pbmaZg\ahkZ`^Zg]eZilh_[Zkl

a\\!a\m"

:\h^__b\b^gmmZdbg`bgmhZ\\hngmehg`m^kf^__^\mlh_\hfik^llbo^!m^glbe^"ehZ]Zg]ma^pZrehZ]blZiieb^]

a^

Fh]neZkkZmbh6>l (>\]

ag

:\h^__b\b^gm_hknl^pbmaZk^ik^l^gmZmbo^oZkbZ[e^Z\mbhgmZdbg`bgmhZ\\hngmgnf[^kh_lmhk^rllniihkm^]

b

:g`e^4KZmbh4<h^__b\b^gm

b

?Z\mhk]^Zebg`pbma^\\^gmkb\bmr!ing\abg`la^Zk"

g

IZkmbZe_Z\mhk

g<

IZkmbZe_Z\mhk_hk\hg\k^m^

g?

IZkmbZe_Z\mhk_hkZ\mbhgl%?

g@

IZkmbZe_Z\mhk_hki^kfZg^gmZ\mbhgl%@

g@d%lni

IZkmbZe_Z\mhkmh[^Ziieb^]mh@d%bg_

g@d%bg_

IZkmbZe_Z\mhkmh[^Ziieb^]mh@d%lni

gJ

IZkmbZe_Z\mhk_hkoZkbZ[e^Z\mbhgl%J

gF

IZkmbZe_Z\mhk_hkfZm^kbZe!nlnZeerg<hkgL"

gL

IZkmbZe_Z\mhk_hkk^bg_hk\bg`lm^^e

d

K^]blmkb[nmbhgkZmbh^jnZelkZmbhh_ma^k^]blmkb[nm^]fhf^gmmhma^^eZlmb\[^g]bg`fhf^gm!*k^]blmkb[nmbhg"

e\n

NembfZm^\hfik^llbo^lmkZbgbgma^\hg\k^m^

e\n+

NembfZm^\hfik^llbo^lmkZbgebfbmbg\hg\k^m^pab\ablghm_neerbgink^ZqbZe\hfik^llbhgZllnfbg`nl^h_ma^
iZkZ[heb\k^\mZg`neZklmk^lllmkZbgk^eZmbhglabi!gnf^kb\Zeere\n+6e\n,"

e\n,

 embfZm^\hfik^llbo^lmkZbgebfbmbg\hg\k^m^pab\ablghm_neerbgink^ZqbZe\hfik^llbhgZllnfbg`nl^h_ma^
N
[bebg^Zklmk^lllmkZbgk^eZmbhglabi

el\

<hfik^llbo^lmkZbgbgk^bg_hk\^f^gm

elm

M^glbe^lmkZbgbgk^bg_hk\^f^gm

n

?Z\mhk]^_bgbg`^__^\mbo^lmk^g`ma!6*_hk<.)(/)"

n*

<h^__b\b^gm_hk[hg]\hg]bmbhgl

n+

<h^__b\b^gm_hk[Zk]bZf^m^k

y

:g`e^4:g`e^h_\hfik^llbhglmknml!la^Zk"

yb

Bg\ebgZmbhgnl^]mhk^ik^l^gmbfi^k_^\mbhgl

l

Le^g]^kg^llkZmbh

l

?Z\mhk]^_bgbg`ma^a^b`amh_ma^\hfik^llbhgshg^!6)'1_hk<.)(/)"

l_b

Le^g]^kg^llbg_bk^

lebf

Ebfbmbg`le^g]^kg^llkZmbh!h_\henfgl"

mb%m*%m+

LghpehZ]laZi^_Z\mhkl

m_b

 Zmbhh_ma^]^lb`gZqbZeehZ]ng]^k_bk^\hg]bmbhglmhma^]^lb`gk^lblmZg\^h_ma^\henfgZmghkfZem^fi^kZmnk^
K
[nmpbmaZg^\\^gmkb\bmrZiieb\Z[e^mh_bk^\hg]bmbhgl

v

Lmk^g`mak^]n\mbhg_Z\mhk_hk\hg\k^m^\kZ\d^]bgla^Zk

j

K^]n\mbhg_Z\mhk(]blmkb[nmbhg\h^__b\b^gm'?Z\mhkZiieb^]mh@dbg;L>G*22)>qi'!/'*)["

r

K^jnbk^]m^glbhgk^bg_hk\^f^gmkZmbh

r

=^glbmrh_Zbk!pbg]"

r

K^bg_hk\^f^gmkZmbh_hkk^jnbk^]\hfik^llbhgk^bg_hk\^f^gm%:l+([]

vii

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Symbol

Definition

r*

I^k\^gmZ`^h_k^bg_hk\^f^gmeZii^]pbmabg)'/.e)_khfma^\^gmk^ebg^h_ma^eZi[^bg`\hglb]^k^]

re

K^bg_hk\^f^gmkZmbh_hkehg`bmn]bgZek^bg_hk\^f^gm

rer%res

K^bg_hk\^f^gmkZmbhh_[hg]^]lm^^ebgma^rZg]s]bk^\mbhg

r)

K^_^k^g\^k^bg_hk\^f^gmkZmbh_\d)'.*),

s`]

=^lb`goZen^h_ma^`khng]ik^llnk^

sl

Lmk^llbgk^bg_hk\^f^gmZmLEL

sl

:[lhenm^oZen^h_ma^fZqbfnflmk^lli^kfbmm^]bgma^k^bg_hk\^f^gmbff^]bZm^erZ_m^kma^_hkfZmbhgh_ma^\kZ\d

sl\!slm"

Lmk^llbg\hfik^llbhg!Zg]m^glbhg"k^bg_hk\^f^gm

sl]

=^lb`glmk^llbgma^[ZkZmma^nembfZm^ebfbmlmZm^

sln

Ngfh]b_b^]l^kob\^lmk^llbgk^bg_hk\^f^gm]^m^kfbg^]_khfNELehZ]l!L^^?b`nk^<,"

h!e%m)"

?bgZeoZen^h_\k^^i\h^__b\b^gm

h^_

>__^\mbo^\k^^i_Z\mhk

f

;Zk]bZf^m^k

c

?Z\mhkl]^_bgbg`k^ik^l^gmZmbo^oZen^lh_oZkbZ[e^Z\mbhgl

c)

<hf[bgZmbhgoZen^h_ZoZkbZ[e^Z\mbhg!^'`'nl^]pa^g\hglb]^kbg`NEL"

c*

?k^jn^gmoZen^h_ZoZkbZ[e^Z\mbhg!^'`'nl^]pa^g\hglb]^kbg`pa^ma^kl^\mbhgpbeeaZo^\kZ\d^]hkghm"

c+

JnZlb&i^kfZg^gmoZen^h_ZoZkbZ[e^Z\mbhg!^'`'nl^]pa^g\hglb]^kbg`]^_hkfZmbhg"

w

F^\aZgb\Zek^bg_hk\^f^gmkZmbh6:l_r] (:\_\]*

viii

Bgmkh]n\mbhg

* Introduction

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

*'* Aim
Ma^Zbfh_mablin[eb\ZmbhgblmhbeenlmkZm^makhn`aphkd^]^qZfie^lahp;L>G*22+**T*V
!>nkh\h]^+"fZr[^nl^]bgikZ\mb\^mh]^lb`gbg&lbmn\hg\k^m^[nbe]bg`lmkn\mnk^l'Bmblbgm^g]^]
maZm ma^l^ phkd^] ^qZfie^l pbee ^qieZbg ahp \Ze\neZmbhgl mh >nkh\h]^ + fZr [^ i^k_hkf^]'
>nkh\h]^+lmkb\mer\hglblmlh__hnkiZkml!IZkml**%*+%+Zg],"T*&-V[nm_hkma^inkihl^lh_
mablin[eb\Zmbhg%>nkh\h]^+k^_^klmhiZkm**hger%nge^lljnZeb^]'Ma^phkd^]^qZfie^lpbee
[^\Zkkb^]hnmpbmabgma^^gobkhgf^gmh_hma^kk^e^oZgmin[eb\Zmbhgleblm^][^ehp%Zg]beenlmkZm^]
bg?b`nk^*'*3
N Ma^hma^kmak^^iZkmlh_>nkh\h]^+'
N Hma^k>nkh\h]^l'
N FZm^kbZeZg]^q^\nmbhglmZg]Zk]l'
N In[eb\Zmbhgl[rma^\hg\k^m^bg]nlmkrZg]hma^kl'

Ma^k^ Zk^% ma^k^_hk^% fZgr k^_^k^g\^l mh hma^k ]h\nf^gml Zg] pabe^ bm bl bgm^g]^] maZm mabl
in[eb\Zmbhg%k^_^kk^]mhZlPhkd^]^qZfie^l%\ZglmZg]Zehg^%bmblZgmb\biZm^]maZmnl^klfZr
k^jnbk^ l^o^kZe h_ ma^ hma^k k^_^k^g\^l mh aZg]% bg iZkmb\neZk% <hg\bl^ >nkh\h]^ +T.V% pab\a
lnffZkbl^l ma^ kne^l Zg] ikbg\bie^l maZm pbee [^ \hffhger nl^] bg ma^ ]^lb`g h_ k^bg_hk\^]
\hg\k^m^_kZf^][nbe]bg`lmh>nkh\h]^+'

WORKED
EXAMPLES

STANDARDS

CONCRETE INDUSTRY
PUBLICATIONS

PUBLICATIONS
BY OTHERS

NA
CONCISE
EUROCODE
2

BS EN 1990
BASIS OF
DESIGN

MANUALS

VOL 2
NA
BS EN 19912
NA
BS EN 199111
2 NA
NA
3
NA
ACTIONS
4
NA
6

WORKED EXAMPLES
TO EUROCODE 2
VOL 1

HOW TO
DESIGN
CONCRETE
STRUCTURES
DETAILERS
HANDBOOK

Densities and
imposed loads
Fire
Snow
Wind
Execution

www.
Eurocode2
.info
DESIGN
GUIDES

PD6687
NA

NA
BS EN 199211 12 NA
NA
DESIGN OF
2
CONCRETE
3
STRUCTURES
General
Fire
Bridges
Liquid retaining

RC SPREAD
SHEETS

BS EN 13670
EXECUTION
OF
CONCRETE
STRUCTURES

PRECAST
DESIGN
MANUAL

PRECAST
WORKED
EXAMPLES

Ghm^
Ma^m^kfLmZg]Zk]l^g\hfiZll^l;kbmblaLmZg]Zk]l%>nkh\h]^l%GZmbhgZe:gg^q^l!G:"Zg]In[ebla^]=h\nf^gml
?b`nk^*'*
Phkd^]^qZfie^lbg\hgm^qm

Ma^]^lb`glZk^bgZ\\hk]Zg\^pbma;L>G*22+**T*V%Zlfh]b^][rma^NDGZmbhgZe:gg^qT*ZV
Zg]^qieZbg^]bgI=//10T/V'
1

@^g^kZeer% ma^ \Ze\neZmbhgl Zk^ \khll&k^_^k^g\^] mh ma^ k^e^oZgm \eZnl^l bg Zee _hnk iZkml h_
>nkh\h]^ +T*-V Zg]% pa^k^ ZiikhikbZm^% mh hma^k ]h\nf^gml' L^^ ?b`nk^ *'+ _hk Z `nb]^ mh
ik^l^gmZmbhg'K^_^k^g\^lmh;L1**)T0Vk^_^kmhIZkm*nge^llhma^kpbl^lmZm^]'

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

@^g^kZeer%ma^lbfie^^qZfie^l]^i^g]hg^jnZmbhglZg]]^lb`gZb]l]^kbo^]_khf>nkh\h]^+'
Ma^]^kbo^]^jnZmbhglZk^`bo^gbg:ii^g]bq:Zg]ma^]^lb`gZb]l_khfL^\mbhg*.h_<hg\bl^
>nkh\h]^+T.VZk^k^i^Zm^]bg:ii^g]bq;'
Ma^^qZfie^lZk^bgm^g]^]mh[^ZiikhikbZm^_hkma^bkinkihl^%pab\ablmhbeenlmkZm^ma^nl^h_
>nkh\h]^+_hkbg&lbmn\hg\k^m^[nbe]bg`lmkn\mnk^l'Ma^k^Zk^lbfie^^qZfie^lmhbeenlmkZm^ahp
mrib\ZeaZg]\Ze\neZmbhglfb`am[^]hg^nlbg`ZoZbeZ[e^\aZkmlZg]mZ[e^l]^kbo^]_khfma^<h]^'
Ma^l^Zk^_heehp^][rfhk^]^mZbe^]^qZfie^lbeenlmkZmbg`ma^]^mZbe^]phkdbg`lh_ma^<h]^l'
Bghk]^kmh^qieZbgma^nl^h_>nkh\h]^+%l^o^kZeh_ma^\Ze\neZmbhglZk^ik^l^gm^]bg]^mZbe_Zk
bg^q\^llh_maZmg^\^llZkrbg]^lb`g\Ze\neZmbhglhg\^nl^klZk^_ZfbebZkpbmama^<h]^'MhZg
^qm^gm%ma^]^lb`glZk^\hgmkbo^]mhlahpoZeb]f^mah]lh_]^lb`gbg`^e^f^gml%mh`bo^bglb`am
Zg]mha^eibgoZeb]Zmbg`\hfinm^kf^mah]l'Ma^rZk^ghmg^\^llZkberma^fhlmZiikhikbZm^%ma^
fhlm^\hghfb\hkma^hgerf^mah]lh_]^lb`gbg`ma^f^f[^klbeenlmkZm^]'
Sections 1 and 2

Worked examples

Cl. 6.4.4

K^e^oZgm\eZnl^lhk_b`nk^gnf[^kl_khf;L>G
*22+**!b_ma^k^_^k^g\^blmhhma^kiZkml%hma^k
>nkh\h]^lhkhma^k]h\nf^gmlmablpbee[^bg]b\Zm^]"

Cl. 6.4.4

NA

?khfma^k^e^oZgmNDGZmbhgZe:gg^q!`^g^kZeermh
;L>G*22+**"

NA

Cl. 6.4.4 & NA

?khf[hma;L>G*22+**Zg]NDGZmbhgZe:gg^q

Cl. 6.4.4 & NA

Fig. 2.1
Section 5.2

K^e^oZgmiZkmlh_mablin[eb\Zmbhg

Fig. 2.1
Section 5.2

EC1-1-1: 6.4.3

?khfhma^k>nkh\h]^l3;L>G*22)%;L>G*22*%
;L>G*22+*+%^m\

EC1-1-1: 6.4.3

PD 6687[6]

;Z\d`khng]iZi^kmhNDGZmbhgZe:gg^q^l
;L>G*22+*

PD 6687[6]

Concise

<hg\bl^>nkh\h]^+T.V

Concise

How to: Floors [8]

Ahpmh]^lb`g\hg\k^m^lmkn\mnk^lnlbg`
>nkh\h]^+T1V3?ehhkl

How to:
Floors[8]

Grey shaded tables

Bg:ii^g]b\^l%]^kbo^]\hgm^gmbgmZ[e^lghm_khf
>nkh\h]^+

?b`nk^*'+
@nb]^mhik^l^gmZmbhg

:llhf^h_ma^]^mZbebg`kne^lbg>nkh\h]^+Zk^`^g^kZeerfhk^bgoheo^]maZgmahl^mh;L1**)%
lhf^ h_ ma^ ]^lb`gl ik^l^gm^] bg mabl in[eb\Zmbhg aZo^ [^^g ^qm^g]^] bgmh Zk^Zl maZm aZo^
mkZ]bmbhgZeer[^^gma^k^lihglb[bebmrh_]^mZbe^kl'Ma^l^^qm^g]^]\Ze\neZmbhglZk^ghmg^\^llZkber
iZkm h_ghkfZe ]^lb`g [nm Zk^ bg\en]^] Zm ma^ ^g] h_ lhf^ \Ze\neZmbhgl' Bm bl Zllnf^] maZm
ma^]^lb`g^kpbee]bl\nllZg]Z`k^^pbmama^]^mZbe^kZk^Zlh_k^lihglb[bebmrZg]ma^]^`k^^h_
kZmbhgZeblZmbhg% ma^ ^qm^gm h_ ]^lb`gbg` ]^mZbel% Zll^llf^gm h_ \nkmZbef^gm Zg] hma^k Zli^\ml
maZmma^]^mZbe^klahne]ng]^kmZd^'Bmblk^\h`gbl^]maZmbgma^oZlmfZchkbmrh_\Zl^l%ma^kne^l
`bo^gbg]^mZbebg`fZgnZelT1%2Vpbee[^nl^]'Ahp^o^k%ma^^qZfie^lZk^bgm^g]^]mha^eipa^g
\nkmZbef^gm%Zg\ahkZ`^Zg]eZie^g`malg^^]mh[^]^m^kfbg^]'

Bgmkh]n\mbhg
*'+ Eurocode: Basis of structural design

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Bg ma^ >nkh\h]^ lrlm^f ;L >G *22)% >nkh\h]^3 ;Zlbl h_ lmkn\mnkZe ]^lb`gT*)V ho^kZk\a^l Zee ma^
hma^k>nkh\h]^l%;L>G*22*mh;L>G*222';L>G*22)]^g^lma^^__^\mlh_Z\mbhgl%bg\en]bg`
`^hm^\agb\Ze Zg] l^blfb\ Z\mbhgl% Zg] Ziieb^l mh Zee lmkn\mnk^l bkk^li^\mbo^ h_ ma^ fZm^kbZe h_
\hglmkn\mbhg'Ma^fZm^kbZe>nkh\h]^l]^g^ahpma^^__^\mlh_Z\mbhglZk^k^lblm^][r`bobg`kne^l_hk
]^lb`gZg]]^mZbebg`h_\hg\k^m^%lm^^e%\hfihlbm^%mbf[^k%fZlhgkrZg]Zenfbgbnf'!l^^?b`nk^*',"'
BS EN 1990, Eurocode:
Basis of structural design

Structural safety,
serviceability and durability

BS EN 1991, Eurocode 1:
Actions on structures

Actions on structures

BS EN 1992, Eurocode 2: Concrete


BS EN 1993, Eurocode 3: Steel
BS EN 1994, Eurocode 4: Composite
BS EN 1995, Eurocode 5: Timber
BS EN 1996, Eurocode 6: Masonry
BS EN 1999, Eurocode 9: Aluminium
BS EN 1997, Eurocode 7:
Geotechnical design

Design and detailing

BS EN 1998, Eurocode 8:
Seismic design

Geotechnical
and seismic
design

?b`nk^*',
Ma^>nkh\h]^ab^kZk\ar

;L>G*22)ikhob]^lma^g^\^llZkrbg_hkfZmbhg_hkma^ZgZerlblh_lmkn\mnk^lbg\en]bg`iZkmbZe
Zg]hma^k_Z\mhklmh[^Ziieb^]mhma^Z\mbhgl_khf>nkh\h]^*'Bm^lmZ[ebla^lma^ikbg\bie^lZg]
k^jnbk^f^gml_hkma^lZ_^mr%l^kob\^Z[bebmrZg]]nkZ[bebmrh_lmkn\mnk^l'Bm]^l\kb[^lma^[Zlbl_hk
]^lb`gZl_heehpl3

EC0: 2.1

:lmkn\mnk^laZee[^]^lb`g^]Zg]^q^\nm^]!\hglmkn\m^]"bgln\aZpZrmaZmbmpbee%]nkbg`bml
bgm^g]^]eb_^%pbmaZiikhikbZm^]^`k^^lh_k^ebZ[bebmrZg]bgZg^\hghfb\ZepZr3
N LnlmZbgZeeZ\mbhglZg]bg_en^g\^lebd^ermhh\\nk]nkbg`^q^\nmbhgZg]nl^'
N K^fZbg_bm_hkma^nl^_hkpab\abmblk^jnbk^]'

Bghma^kphk]l%bmlaZee[^]^lb`g^]nlbg`ebfbmlmZm^likbg\bie^lmhaZo^Z]^jnZm^3
N LmZ[bebmr'
N Lmkn\mnkZek^lblmZg\^!bg\en]bg`lmkn\mnkZek^lblmZg\^bg_bk^"'
N L^kob\^Z[bebmr'
N =nkZ[bebmr'

?hk[nbe]bg`lmkn\mnk^l%Z]^lb`gphkdbg`eb_^h_.)r^Zklblbfieb^]'
;L>G*22)lmZm^lmaZmebfbmlmZm^llahne][^o^kb^]bgZeek^e^oZgm]^lb`glbmnZmbhgl3i^klblm^gm%
mkZglb^gmhkZ\\b]^gmZe'Ghk^e^oZgmebfbmlmZm^laZee[^^q\^^]^]pa^g]^lb`goZen^l_hkZ\mbhgl
Zg]k^lblmZg\^lZk^nl^]bg]^lb`g'Ma^ebfbmlmZm^lZk^3
N NembfZm^ebfbmlmZm^l!NEL"%pab\aZk^Zllh\bZm^]pbma\heeZil^hkhma^k_hkflh_lmkn\mnkZe

_Zbenk^'
N L^kob\^Z[bebmrebfbmlmZm^l!LEL"%pab\a\hkk^lihg]mh\hg]bmbhgl[^rhg]pab\ali^\b_b^]

l^kob\^k^jnbk^f^gmlZk^ghehg`^kf^m'
:eeZ\mbhglZk^Zllnf^]mhoZkrbgmbf^Zg]liZ\^'LmZmblmb\Zeikbg\bie^lZk^Ziieb^]mhZkkbo^Zmma^
fZ`gbmn]^h_ma^iZkmbZeehZ]_Z\mhklmh[^nl^]bg]^lb`gmhZ\ab^o^ma^k^jnbk^]k^ebZ[bebmrbg]^q
!e^o^eh_lZ_^mr"'Ma^k^blZgng]^kerbg`ZllnfimbhgmaZmma^Z\mbhglma^fl^eo^lZk^]^l\kb[^]bg
lmZmblmb\Zem^kfl'
3

*', Eurocode 1: Actions on structures

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

:\mbhglZk^]^g^]bgma^*)iZkmlh_;L>G*22*>nkh\h]^*3:\mbhglhglmkn\mnk^lT**V3
;L>G*22***3+))+3=^glbmb^l%l^e_&p^b`am%bfihl^]ehZ]l_hk[nbe]bg`l
;L>G*22**+3+))+3:\mbhglhglmkn\mnk^l^qihl^]mhk^
;L>G*22**,3+)),3LghpehZ]l
;L>G*22**-3+)).3Pbg]Z\mbhgl
;L>G*22**.3+)),3Ma^kfZeZ\mbhgl
;L>G*22**/3+)).3:\mbhgl]nkbg`^q^\nmbhg
;L>G*22**03+))/3:\\b]^gmZeZ\mbhgl
;L>G*22*+3+)),3:\mbhglhglmkn\mnk^l'MkZ_\ehZ]lhg[kb]`^l
;L>G*22*,3+))/3<kZg^lZg]fZ\abg^kr
;L>G*22*-3+))/3LbehlZg]mZgdl
Mabl in[eb\Zmbhg bl fZbger \hg\^kg^] pbma ]^lb`gbg` _hk ma^ Z\mbhgl ]^g^] [r IZkm**3
=^glbmb^l%l^e_&p^b`am%bfihl^]ehZ]l_hk[nbe]bg`l'
=^lb`goZen^lh_Z\mbhglZg]ehZ]ZkkZg`^f^gmlZk^\ho^k^]bgL^\mbhg+'

*'- Eurocode 2: Design of concrete structures


>nkh\h]^+3=^lb`gh_\hg\k^m^lmkn\mnk^lT*-Vhi^kZm^lpbmabgZg^gobkhgf^gmh_hma^k>nkhi^Zg
Zg];kbmblalmZg]Zk]l!l^^?b`nk^*',"'Bmbl`ho^kg^][r;L>G*22)T*)VZg]ln[c^\mmhma^Z\mbhgl
]^g^]bg>nkh\h]^l*T**V%0T*+VZg]1T*,V'Bm]^i^g]lhgoZkbhnlfZm^kbZelZg]^q^\nmbhglmZg]Zk]l
Zg] bl nl^] Zl ma^ [Zlbl h_ hma^k lmZg]Zk]l' IZkm +% ;kb]`^lT,V% Zg] IZkm ,% Ebjnb]k^mZbgbg`Zg]
\hgmZbgf^gmlmkn\mnk^lT-V%phkd[r^q\^imbhgmhIZkm**Zg]*+%maZmbl%\eZnl^lbgIZkml+Zg],
\hgkf%fh]b_rhkk^ieZ\^\eZnl^lbgIZkm**'

BS EN 1990
EUROCODE
Basis of Structural Design
BS EN 1997
EUROCODE 7
Geotechnical Design

BS EN 1998
EUROCODE 8
Seismic Design
BS EN 1991
EUROCODE 1
Basis of Structural Design

BS 4449
Reinforcing
Steels

BS 8500
Specifying
Concrete

BS EN 206
Concrete

BS EN 13670
Execution of
Structures

BS EN 1995
EUROCODE 5
Design of
Composite
Structures

BS EN 1992
EUROCODE 2
Design of concrete structures
Part 11: General Rules for
Structures
Part 12: Structural Fire Design

BS EN 1992
EUROCODE 2
Part 2:
Bridges

BS EN 1992
EUROCODE 2
Part 3:
Liquid Retaining
Structures

Ghm^
?hk\eZkbmrGZmbhgZe:gg^q^lZg]^qieZgZmhkr]h\nf^gml!^'`'I=//10%Zg]
Ghg&<hgmkZ]b\mhkr<hfie^f^gmZkrBg_hkfZmbhgG<<B"Zk^ghmlahpg'
?b`nk^*'>nkh\h]^+bg\hgm^qm

BS EN 10080
Reinforcing
Steels

BS EN 13369
Precast
Concrete

Bgmkh]n\mbhg

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

*'. National Annexes


Bmblma^ik^kh`Zmbo^h_^Z\a<>GF^f[^kLmZm^mh\hgmkhee^o^elh_lZ_^mrbgmaZm\hngmkr':lZ
k^lnem%lhf^lZ_^mr_Z\mhklZg]hma^kiZkZf^m^klbgma^>nkh\h]^l%ln\aZl\ebfZmb\\hg]bmbhgl%
]nkZ[bebmr\eZll^lZg]]^lb`gf^mah]l%Zk^ln[c^\mmh\hgkfZmbhghkl^e^\mbhgZmZgZmbhgZee^o^e'
Ma^]^\blbhglfZ]^[rma^gZmbhgZe[h]b^l[^\hf^GZmbhgZeer=^m^kfbg^]IZkZf^m^kl!G=Il"
pab\a Zk^ in[ebla^] bg Z GZmbhgZe:gg^q !G:" _hk ^Z\a iZkm h_ ^Z\a >nkh\h]^'Ma^ GZmbhgZe
:gg^q fZr Zelh bg\en]^ k^_^k^g\^ mh ghg&\hgmkZ]b\mhkr \hfie^f^gmZkr bg_hkfZmbhg !G<<B"%
ln\aZlgZmbhgZelmZg]Zk]lhk`nb]Zg\^]h\nf^gml'
Mablin[eb\Zmbhgbg\en]^lk^_^k^g\^lmhma^k^e^oZgmGZmbhgZe:gg^q^lZlZiikhikbZm^'

*'/ Basis of the worked examples in this publication













































Ma^]^lb`g\Ze\neZmbhglbgmablin[eb\ZmbhgZk^bgZ\\hk]Zg\^pbma3
N ;L>G*22)%>nkh\h]^3;Zlblh_lmkn\mnkZe]^lb`gT*)VZg]bmlNDGZmbhgZe:gg^qT*)ZV'
N ;L>G*22*%>nkh\h]^*3:\mbhglhglmkn\mnk^lbg*)iZkmlT**VZg]ma^bkNDGZmbhgZe

:gg^q^lT**ZV'
N ;L>G*22+**%>nkh\h]^+IZkm**3=^lb`gh_\hg\k^m^lmkn\mnk^l@^g^kZekne^lZg]

kne^l_hk[nbe]bg`lT*VZg]bmlNDGZmbhgZe:gg^qT*ZV'
N ;L>G*22+*+%>nkh\h]^+IZkm*+3=^lb`gh_\hg\k^m^lmkn\mnk^l@^g^kZekne^l

Lmkn\mnkZe_bk^]^lb`gT+VZg]bmlNDGZmbhgZe:gg^qT+ZV'
N I=//10%;Z\d`khng]iZi^kmhma^NDGZmbhgZe:gg^q^lT/V'
N ;L>G*220%>nkh\h]^03@^hm^\agb\Ze]^lb`gIZkm*'@^g^kZekne^lT*+VZg]bmlNDGZmbhgZe

:gg^qT*+ZV'
Ma^rnl^fZm^kbZel\hg_hkfbg`mh3
N ;L1.))*3<hg\k^m^<hfie^f^gmZkr;kbmblaLmZg]Zk]mh;L>G+)/*3F^mah]h_li^\b_rbg`

Zg]`nb]Zg\^mhma^li^\b_b^kT*-V'
N ;L---23Lm^^e_hkma^k^bg_hk\^f^gmh_\hg\k^m^P^e]Z[e^k^bg_hk\bg`lm^^e;Zk%\hbeZg]

]^\hbe^]ikh]n\mLi^\b_b\ZmbhgT*.V'
Ma^rfZd^k^_^k^g\^mhl^o^kZein[eb\Zmbhgl%fhlmghmZ[er3

N <hg\bl^>nkh\h]^+_hkma^]^lb`gh_bg&lbmn\hg\k^m^_kZf^][nbe]bg`lmh;L>G*22+**3
+))-Zg]bmlNDGZmbhgZe:gg^q3+)).T.V'
T1V'

N Ahpmh]^lb`g\hg\k^m^lmkn\mnk^lnlbg`>nkh\h]^+

Ma^^q^\nmbhgh_ma^phkdlblZllnf^]mh\hg_hkfmh3
N I=//10;Z\d`khng]iZi^kmhma^NDGZmbhgZe:gg^q^l;L>G*22+*'T/V
N GL<L%GZmbhgZelmkn\mnkZe\hg\k^m^li^\b_b\Zmbhg_hk[nbe]bg`\hglmkn\mbhg%,k]^]bmbhgT*/VFZr

+))-'
Hk%pa^gZoZbeZ[e^
N ;L>G*,/0)3>q^\nmbhgh_\hg\k^m^lmkn\mnk^l'=n^+)*)T*0V':lbfie^f^gm^][r

li^\b_b\Zmbhglln\aZl3
N GL<L%GZmbhgZelmkn\mnkZe\hg\k^m^li^\b_b\Zmbhg_hk[nbe]bg`\hglmkn\mbhg%-ma^]bmbhgT*1V

<<BI&).)%]n^+)*)'

*'0 Assumptions
*'0'* Eurocode 2

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Cl. 1.3

PD 6687[6]

 >nkh\h]^+Zllnf^lmaZm3
 N =^lb`gZg]\hglmkn\mbhgpbee[^ng]^kmZd^g[rZiikhikbZm^erjnZeb_b^]Zg]^qi^kb^g\^]i^klhgg^e'
 N :]^jnZm^lni^koblbhgZg]jnZebmr\hgmkhepbee[^ikhob]^]'
 N FZm^kbZelZg]ikh]n\mlpbee[^nl^]Zlli^\b_b^]'

 N Ma^lmkn\mnk^pbee[^Z]^jnZm^erfZbgmZbg^]Zg]pbee[^nl^]bgZ\\hk]Zg\^pbmama^]^lb`g[kb^_'
 N Ma^k^jnbk^f^gml_hk^q^\nmbhgZg]phkdfZglabi`bo^gbg>G*,/0)Zk^\hfieb^]pbma'

*'0'+ The worked examples
Nge^llghm^]hma^kpbl^%ma^\Ze\neZmbhglbgmablin[eb\ZmbhgZllnf^3

EC0: Table 2.1

N :]^lb`geb_^h_.)r^Zkl'

Table 3.1

N Ma^nl^h_<,)(,0\hg\k^m^'

BS 4449

N Ma^nl^h_@kZ]^:%;hk<k^bg_hk\^f^gm%]^lb`gZm^]AbgZ\\hk]Zg\^pbma;L1///T*2V'

Table 4.1,
BS 8500: Table A.1

N >qihlnk^\eZllQ<*'

Building Regs[20,21]

N *ahnk_bk^k^lblmZg\^'

@^g^kZeer^Z\a\Ze\neZmbhgblkhng]^]Zg]bmblma^khng]^]oZen^maZmblnl^]bgZgr_nkma^k\Ze\neZmbhg'

*'1 Material properties


FZm^kbZeikhi^kmb^lZk^li^\b^]bgm^kflh_ma^bk\aZkZ\m^kblmb\oZen^l'MablnlnZeer\hkk^lihg]l
mhma^ehp^k._kZ\mbe^h_ZgZllnf^]lmZmblmb\Ze]blmkb[nmbhgh_ma^ikhi^kmr\hglb]^k^]'
Ma^oZen^lh_g<Zg]gL%iZkmbZe_Z\mhkl_hkfZm^kbZel%Zk^bg]b\Zm^]bgMZ[e^*'*'
Table 2.1 & NA

MZ[e^*'*
IZkmbZe_Z\mhkl_hkfZm^kbZel
=^lb`glbmnZmbhg

g<\hg\k^m^

gLk^bg_hk\bg`lm^^e

ULS persistent and transient

*'.)

*'*.

Accidental non-fire

*'+)

*'))

Accidental fire

*'))

*'))

SLS

*'))

*'))

*'2 Execution
Bgma^ND%==>GO*,/0)T++Vbl\nkk^gmerZoZbeZ[e^[nmpbmahnmbmlGZmbhgZe:iieb\Zmbhg=h\nf^gm'
?hk[nbe]bg`lmkn\mnk^lbgma^ND%ma^[Z\d`khng]]h\nf^gmI=//10T/V\hglb]^klma^ikhoblbhglh_
ma^GZmbhgZeLmkn\mnkZe<hg\k^m^Li^\b\Zmbhg!GL<L"T*/Vmh[^^jnboZe^gmmhmahl^bg>G*,/0)_hk
mhe^kZg\^\eZll*'Pa^gin[ebla^]%;L>G*,/0)T*0VZg]%b_ZiikhikbZm^%ma^\hkk^lihg]bg`GZmbhgZe
:iieb\Zmbhg=h\nf^gmpbeemZd^ik^\^]^g\^'

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml

+ Analysis, actions and load arrangements


+'* Methods of analysis

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

+'*'* ULS
:mma^nembfZm^ebfbmlmZm^!NEL"ma^mri^h_ZgZerlbllahne][^ZiikhikbZm^mhma^ikh[e^f[^bg`
\hglb]^k^]'Ma^_heehpbg`Zk^\hffhgernl^]3
N Ebg^Zk^eZlmb\ZgZerlbl'

Cl. 5.1.1(7)

N Ebg^Zk^eZlmb\ZgZerlblpbmaebfbm^]k^]blmkb[nmbhg'
N IeZlmb\ZgZerlbl'

?hk NEL% ma^ fhf^gml ]^kbo^] _khf ^eZlmb\ ZgZerlbl fZr [^ k^]blmkb[nm^] ikhob]^] maZm ma^
k^lnembg`]blmkb[nmbhgh_fhf^gmlk^fZbglbg^jnbeb[kbnfpbmama^Ziieb^]Z\mbhgl'Bg\hgmbgnhnl
[^ZflhkleZ[lpbma_\d.)FIZma^fbgbfnfZeehpZ[e^kZmbhh_ma^k^]blmkb[nm^]fhf^gmmh
ma^fhf^gmbgma^ebg^ZkZgZerlbl%d%bl)'0)pa^k^<eZll;hk<eZll<k^bg_hk\^f^gmblnl^]hk
)'1)pa^k^<eZll:k^bg_hk\^f^gmblnl^]'
Pbmabgma^ebfbmll^m%\h^_\b^gml_hkfhf^gmZg]la^Zk]^kbo^]_khf^eZlmb\ZgZerlblfZr[^
nl^]mh]^m^kfbg^_hk\^lbgk^`neZklmkn\mnk^l!l^^:ii^g]bq;"'Ma^]^lb`gh_\henfgllahne][^
[Zl^]hg^eZlmb\fhf^gmlpbmahnmk^]blmkb[nmbhg'
IeZlmb\ZgZerlblfZr[^nl^]_hk]^lb`gZmNELikhob]^]maZmma^k^jnbk^]]n\mbebmr\Zg[^Zllnk^]%
_hk^qZfie^3[rebfbmbg`qn (]!mh)'+._hk\hg\k^m^lmk^g`ma\eZll^l<.)(/)"4nlbg`<eZll;
hk<k^bg_hk\^f^gm4hk^glnkbg`ma^kZmbhh_fhf^gmlZmbgm^kf^]bZm^lniihkmlmhfhf^gmlbg
liZglbl[^mp^^g)'.Zg]+')'

Cl. 5.5.4 & NA

Cl. 5.1.1

Cl. 5.6.2

+'*'+ SLS
:mma^l^kob\^Z[bebmrebfbmlmZm^!LEL"ebg^Zk^eZlmb\ZgZerlblfZr[^nl^]'Ebg^Zk^eZlmb\ZgZerlbl
fZr[^\Zkkb^]hnmZllnfbg`3
N <khll&l^\mbhglZk^ng\kZ\d^]Zg]k^fZbgieZg^!b'^'ZgZerlblfZr[^[Zl^]hg\hg\k^m^

`khlll^\mbhgl"'

Cl. 5.4(1)

N Ebg^Zklmk^lllmkZbgk^eZmbhglabil'
N Ma^nl^h_f^ZgoZen^lh_^eZlmb\fh]nenl'

+'+ Actions



:\mbhglk^_^kmhehZ]lZiieb^]mhma^lmkn\mnk^Zl]^g^][^ehp3
N I^kfZg^gmZ\mbhglZk^Z\mbhgl_hkpab\ama^oZkbZmbhgbgfZ`gbmn]^pbmambf^blg^`eb`b[e^'

EC1-1-1: 2.1

N OZkbZ[e^Z\mbhglZk^Z\mbhgl_hkpab\ama^oZkbZmbhgbgfZ`gbmn]^pbmambf^blghmg^`eb`b[e^'

EC1-1-1:
2.2, 3.3.1(2)

N :\\b]^gmZeZ\mbhglZk^Z\mbhglh_lahkm]nkZmbhg[nmh_lb`gb_b\ZgmfZ`gbmn]^maZmZk^

ngebd^ermhh\\nkhgZ`bo^glmkn\mnk^]nkbg`ma^]^lb`gphkdbg`eb_^'

 Bfihl^]]^_hkfZmbhglZk^ghm\hglb]^k^]bgmablin[eb\Zmbhg'

EC1-1-7

+', Characteristic values of actions







Ma^oZen^lh_Z\mbhgl`bo^gbgma^oZkbhnliZkmlh_>nkh\h]^*3:\mbhglhglmkn\mnk^lT**VZk^mZd^g
Zl\aZkZ\m^kblmb\oZen^l'Ma^\aZkZ\m^kblmb\oZen^h_ZgZ\mbhgbl]^g^][rhg^h_ma^_heehpbg`
mak^^Zem^kgZmbo^l3
N Bmlf^ZgoZen^`^g^kZeernl^]_hki^kfZg^gmZ\mbhgl'

EC0: 4.1.2



N :gnii^koZen^pbmaZgbgm^g]^]ikh[Z[bebmrh_ghm[^bg`^q\^^]^]hkehp^koZen^pbmaZg

bgm^g]^]ikh[Z[bebmrh_[^bg`Z\ab^o^]ghkfZeernl^]_hkoZkbZ[e^Z\mbhglpbmadghpg
lmZmblmb\Ze]blmkb[nmbhgl%ln\aZlpbg]hklghp'
N :ghfbgZeoZen^nl^]_hklhf^oZkbZ[e^Zg]Z\\b]^gmZeZ\mbhgl'

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

+'- Variable actions: imposed loads


+'-'* General
Bfihl^]ehZ]lhg[nbe]bg`lZk^]bob]^]bgmh\Zm^`hkb^l'Mahl^fhlm_k^jn^gmernl^]bg\hg\k^m^
]^lb`gZk^lahpgbgMZ[e^+'*'
<Zm^`hkr =^l\kbimbhg
EC1-1-1:
Tables 6.1, 6.7, 6.9
& NA

A
B
C
D
E
F
G
H
I
K
MZ[e^+'*
<Zm^`hkb^lh_
bfihl^]ehZ]l

:k^Zl_hk]hf^lmb\Zg]k^lb]^gmbZeZ\mbobmb^l
H__b\^Zk^Zl
:k^Zlh_\hg`k^`Zmbhg
Lahiibg`Zk^Zl
LmhkZ`^Zk^ZlZg]bg]nlmkbZenl^!bg\en]bg`Z\\^llZk^Zl"
MkZ__b\Zg]iZkdbg`Zk^Zl!o^ab\e^l5,)dG"
MkZ__b\Zg]iZkdbg`Zk^Zl!o^ab\e^l7,)dG"
Khh_l!bgZ\\^llb[e^^q\^im_hkfZbgm^gZg\^Zg]k^iZbk"
Khh_l!Z\\^llb[e^pbmah\\niZg\r\Zm^`hkb^l:="
Khh_l!Z\\^llb[e^_hkli^\bZel^kob\^l%^'`'_hka^eb\him^keZg]bg`Zk^Zl"

Ghm^l
1<Zm^`hkrCblghmnl^]'
2?hk_hkdeb_mehZ]bg`k^_^kmh;L>G*22***<e'/'+','

+'-'+ Characteristic values of imposed loads


<aZkZ\m^kblmb\oZen^l_hk\hffhgernl^]bfihl^]ehZ]lZk^`bo^gbgMZ[e^l+'+mh+'1'
EC1-1-1:
Tables 6.1, 6.2
& NA.3

MZ[e^+'+
:3]hf^lmb\Zg]k^lb]^gmbZe
Ln[&
\Zm^`hkr

>qZfie^

Bfihl^]ehZ]l

A1

:eenlZ`^lpbmabgl^e_&\hgmZbg^]]p^eebg`ngbml'<hffngZe
Zk^Zl!bg\en]bg`dbm\a^gl"bglfZeeZ[eh\dlh__eZml

*'.

+')

A2

;^]khhflZg]]hkfbmhkb^l%^q\^immahl^bgl^e_&\hgmZbg^]
lbg`e^_Zfber]p^eebg`ngbmlZg]bgahm^elZg]fhm^el

*'.

+')

jd!dG(f+" Jd!dG"

A3

;^]khhflbgahm^elZg]fhm^el4ahlibmZepZk]l4mhbe^mZk^Zl

+')

+')

A4

;beebZk](lghhd^kkhhfl

+')

+'0

A5

;Ze\hgb^lbglbg`e^&_Zfber]p^eebg`ngbmlZg]\hffngZeZk^Zl
bglfZeeZ[eh\dlh__eZml

+'.

+')

A6

;Ze\hgb^lbgahlm^el%`n^lmahnl^l%k^lb]^gmbZe\en[l'<hffngZe
Zk^ZlbgeZk`^kZ[eh\dlh__eZml

Fbg',')[

Fbg'+')\

A7

;Ze\hgb^lbgahm^elZg]fhm^el

Fbg'-')[

Fbg'+')\

Ghm^l
aLfZee[eh\dlh__eZmlZk^mahl^pbma,lmhk^rlZg]-_eZmli^k_ehhk(lmZbk\Zl^'Hma^kpbl^ma^rZk^
\hglb]^k^]mh[^eZk`^k[eh\dlh__eZml
bLZf^Zlma^khhflmhpab\ama^r`bo^Z\\^ll%[nmpbmaZfbgbfnfh_,')dG(f+hk-')dG(f+
c<hg\^gmkZm^]Zmma^hnm^k^]`^

EC1-1-1:
Tables 6.1, 6.2
& NA.3

MZ[e^+',
;3h__b\^l
Ln[&
\Zm^`hkr

>qZfie^

Bfihl^]ehZ]l

B1

@^g^kZenl^hma^kmaZgbg;+

+'.

+'0

B2

:mhk[^ehp`khng]_ehhke^o^e

,')

+'0

jd!dG(f+" Jd!dG"

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

MZ[e^+'-
<3Zk^Zlh_\hg`k^`Zmbhg

EC1-1-1:
Tables 6.1, 6.2
& NA.3

Ln[&
\Zm^`hkr

>qZfie^

Bfihl^]ehZ]l

<*

:k^ZlpbmamZ[e^l

C11

In[eb\%bglmbmnmbhgZeZg]\hffngZe]bgbg`khhflZg]
ehng`^l%\Z_^lZg]k^lmZnkZgml!Ghm^3nl^<-hk<.b_
ZiikhikbZm^"

C12

K^Z]bg`khhflpbmagh[hhdlmhkZ`^

+'.

-')

C13

<eZllkhhfl

,')

,')

<+

:k^Zlpbma_bq^]l^Zml

C21

:ll^f[erZk^Zlpbma_bq^]l^Zmbg`a

-')

,'/

C22

IeZ\^lh_phklabi

,')

+'0

<,

:k^Zlpbmahnmh[lmZ\e^l_hkfhobg`i^hie^

C31

<hkkb]hkl%aZeepZrl%Zble^lbgbglmbmnmbhgZemri^[nbe]bg`l%
ahlm^el%`n^lmahnl^l%k^lb]^gmbZe\en[lZg]\hffngZe
Zk^ZlbgeZk`^kb[eh\dlh__eZml

,')

-'.

C32

LmZbkl%eZg]bg`lbgbglmbmnmbhgZemri^[nbe]bg`l%ahlm^el%
`n^lmahnl^l%k^lb]^gmbZe\en[lZg]\hffngZeZk^Zlbg
eZk`^kb[eh\dlh__eZml

,')

-')

C33

<hkkb]hkl%aZeepZrl%Zble^lbghma^kc[nbe]bg`l

-')

-'.

C34

<hkkb]hkl%aZeepZrl%Zble^lbghma^kc[nbe]bg`lln[c^\m^]mh
pa^^e^]o^ab\e^l%bg\en]bg`mkhee^rl

.')

-'.

C35

LmZbkl%eZg]bg`lbghma^kc[nbe]bg`lln[c^\m^]mh\khp]l

-')

-')

C36

PZedpZrlEb`am]nmr!Z\\^lllnbmZ[e^_hkhg^i^klhg%
pZedpZrpb]maZiikhq/))ff"

,')

+')

C37

PZedpZrl@^g^kZe]nmr!k^`neZkmph&pZri^]^lmkbZg
mkZ__b\"

.')

,'/

C38

PZedpZrlA^Zor]nmr!ab`a&]^glbmri^]^lmkbZgmkZ__b\
bg\en]bg`^l\Zi^khnm^l"

0'.

-'.

C39

Fnl^nf_ehhklZg]Zkm`Zee^kb^l_hk^qab[bmbhginkihl^l

-')

-'.

<-

:k^Zlpbmaihllb[e^iarlb\ZeZ\mbobmb^l

j d

Jd

+')

,')

C41

=Zg\^aZeelZg]lmn]bhl%`rfgZlbZ%lmZ`^ld

.')

,'/

C42

=kbeeaZeelZg]]kbeekhhfld

.')

0')

<.

:k^Zlln[c^\m^]mheZk`^\khp]l

C51

:ll^f[erZk^Zlpbmahnm_bq^]l^Zmbg`%\hg\^kmaZeel%[Zkl
Zg]ieZ\^lh_phklabid,e

.')

,'/

C52

LmZ`^lbgin[eb\Zll^f[erZk^Zld

0'.

-'.

D^r
a?bq^]l^Zmbg`bll^Zmbg`pa^k^bmlk^fhoZeZg]ma^nl^h_ma^liZ\^_hkhma^kinkihl^lblbfikh[Z[e^

bLfZee[eh\dlh__eZmlZk^mahl^pbma,lmhk^rlZg]-_eZmli^k_ehhk(lmZbk\Zl^'Hma^kpbl^ma^rZk^
\hglb]^k^]mh[^eZk`^k[eh\dlh__eZml

cHma^k[nbe]bg`lbg\en]^mahl^ghm\ho^k^][r<,*Zg]<,+%Zg]bg\en]^ahm^elZg]fhm^elZg]
bglmbmnmbhgZe[nbe]bg`lln[c^\m^]mh\khp]l

d?hklmkn\mnk^lmaZmfb`am[^lnl\^imb[e^mhk^lhgZg\^^__^\ml%k^_^k^g\^lahne][^fZ]^mhG:'+'*
e?hk`kZg]lmZg]lZg]lmZ]bZ%k^_^k^g\^lahne][^fZ]^mhma^k^jnbk^f^gmlh_ma^ZiikhikbZm^
\^kmb_rbg`Znmahkbmr

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

EC1-1-1:
Tables 6.1, 6.2
& NA.3

EC1-1-1:
Tables 6.3, 6.4
& NA.4, NA.5

MZ[e^+'.
=3lahiibg`Zk^Zl
Ln[&
\Zm^`hkr

>qZfie^

Bfihl^]ehZ]l

Lahiibg`Zk^Zl

D1

:k^Zlbg`^g^kZek^mZbelahil

-')

,'/

D2

:k^Zlbg]^iZkmf^gmlmhk^l

-')

,'/

jd!dG(f+"

Jd!dG"

MZ[e^+'/
>3lmhkZ`^Zk^ZlZg]bg]nlmkbZenl^!bg\en]bg`Z\\^llZk^Zl"
Ln[&
\Zm^`hkr

>qZfie^

Bfihl^]ehZ]l

>*

:k^Zllnl\^imb[e^mhZ\\nfneZmbhgh_`hh]lbg\en]bg`Z\\^llZk^Zl

E11

@^g^kZeZk^Zl_hklmZmb\^jnbif^gmghmli^\b_b^]
^el^pa^k^!bglmbmnmbhgZeZg]in[eb\[nbe]bg`l"

E12
E13

jd!dG(f+"

Jd!dG"

+')

*'1

K^Z]bg`khhflpbma[hhdlmhkZ`^%^'`'eb[kZkb^l

-')

-'.

@^g^kZelmhkZ`^hma^kmaZgmahl^li^\b_b^]Z

+'-(f

0')

E14

?be^khhfl%_bebg`Zg]lmhkZ`^liZ\^!h__b\^l"

.')

-'.

E15

LmZ\dkhhfl![hhdl"

+'-(fa^b`am
!fbg'/'."

0')

E16

IZi^klmhkZ`^Zg]lmZmbhg^krlmhk^l

-')(fa^b`am

2')

E17

=^gl^fh[be^lmZ\dbg`![hhdl"hgfh[be^mkhee^rlbg
in[eb\Zg]bglmbmnmbhgZe[nbe]bg`l

-'1(fa^b`am

0')

E18

=^gl^fh[be^lmZ\dbg`![hhdl"hgfh[be^mkn\dlbg
pZk^ahnl^l

-'1(fa^b`am
!fbg'*.')"

0')

E19

<he]lmhkZ`^

.')(fa^b`am
!fbg'*.')"

2')

Bg]nlmkbZenl^

L^^;L>G*22***3
MZ[e^l/'./'/

>+

?hkdeb_ml<eZll^l?E*mh?E/
D^r

aEhp^k[hng]oZen^`bo^g'Fhk^li^\b_b\ehZ]oZen^llahne][^Z`k^^]pbma\eb^gm

MZ[e^+'0
?Zg]@3mkZ__b\Zg]iZkdbg`Zk^Zl
Ln[&
\Zm^`hkr

>qZfie^

MkZ__b\Zg]iZkdbg`Zk^Zl!o^ab\e^l5,)dG"
MkZ__b\Zg]iZkdbg`Zk^Zl!o^ab\e^l5,)dG"

jd!dG(f+"

Jd!dG"

+'.

.')

.')

Mh[^
]^m^kfbg^]_hk
li^\b_b\nl^

MkZ__b\Zg]iZkdbg`Zk^Zl!o^ab\e^l7,)dG"
MkZ__b\Zg]iZkdbg`Zk^Zl!o^ab\e^l7,)dG"

10

Bfihl^]ehZ]l

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
MZ[e^+'1
A%BZg]D3khh_l
Ln[&
\Zm^`hkr

>qZfie^

Khh_l!bgZ\\^llb[e^^q\^im_hkfZbgm^gZg\^Zg]k^iZbk"

jd!dG(f+"

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Khh_lehi^%a

EC1-1-1:
6.3.4.1(2), Tables 6.9,
6.10, 6.11 & NA.7

Bfihl^]ehZ]l

5,)

)'/

,)5a5/)

)'/!/)a"(,)

5/)

Jd!dG"

)'2

Khh_l!Z\\^llb[e^pbmah\\niZg\r\Zm^`hkb^l:="
<Zm^`hkb^l:=

:lMZ[e^l+'+mh+'.Z\\hk]bg`mh
li^\b_b\nl^

Khh_l!Z\\^llb[e^_hkli^\bZel^kob\^l%^'`'_hka^eb\him^keZg]bg`Zk^Zl"
A^eb\him^k\eZllA<*!5+)dG"!ln[c^\mmh
]rgZfb\_Z\mhkf 6*'-"

+)

A^eb\him^k\eZllA<+!5/)dG"

/)

Ghm^l
1Khh_lZk^\Zm^`hkbs^]Z\\hk]bg`mhma^bkZ\\^llb[bebmr'Bfihl^]ehZ]l_hkkhh_lmaZmZk^ghkfZeer
Z\\^llb[e^Zk^`^g^kZeerma^lZf^Zl_hkma^li^\b_b\nl^Zg]\Zm^`hkrh_ma^Z]cZ\^gmZk^Z'Bfihl^]
ehZ]l_hkkhh_lpbmahnmZ\\^llZk^`bo^gZ[ho^'

EC1-1-1:
6.3.4 & NA

2Ma^k^blgh\Zm^`hkrC'

Movable partitions
Ma^l^e_&p^b`amh_fhoZ[e^iZkmbmbhglfZr[^mZd^gbgmhZ\\hngm[rZngb_hkfer]blmkb[nm^]ehZ]%
jd%pab\alahne][^Z]]^]mhma^bfihl^]ehZ]lh_hhklZl_heehpl3

EC1-1-1:
6.3.1.2 (8) & NA

N ?hkfhoZ[e^iZkmbmbhglpbmaZl^e_&p^b`amh_*')dG(fpZeee^g`ma3

jd6)'.dG(f+'
N ?hkfhoZ[e^iZkmbmbhglpbmaZl^e_&p^b`amh_+')dG(fpZeee^g`ma3

jd6)'1dG(f+'
N ?hkfhoZ[e^iZkmbmbhglpbmaZl^e_&p^b`amh_,')dG(fpZeee^g`ma3

jd6*'+dG(f+'
A^Zob^kiZkmbmbhgllahne][^\hglb]^k^]l^iZkZm^er'

+'-', Reduction factors


General
Khh_l ]h ghm jnZeb_r _hk ehZ] k^]n\mbhgl' Ma^ f^mah] `bo^g [^ehp \hfieb^l pbma ma^ ND
GZmbhgZe:gg^q[nm]b__^kl_khfmaZm`bo^gbgma^>nkh\h]^'

EC1-1-1:
6.3.1.2 (10)
6.3.1.2(11) & NA

Area
: k^]n\mbhg _Z\mhk _hk bfihl^] ehZ]l _hk Zk^Z% a:% fZr [^ nl^] Zg] lahne] [^ ]^m^kfbg^]
nlbg`3
a:6*'):(*))))'0.

EC1-1-1:
6.3.1.2 (10)
& NA Exp. (NA.1)

pa^k^


:blma^Zk^Z!f+"lniihkm^]pbmaehZ]ljnZeb_rbg`_hkk^]n\mbhg!b'^'\Zm^`hkb^l:mh>Zl
eblm^]bgMZ[e^+'*"'

11

EC1-1-1:
6.3.1.2 (11)
& NA Exp. ( NA.2)

Number of storeys
:k^]n\mbhg_Z\mhk_hkgnf[^kh_lmhk^rl%ag%fZr[^nl^]Zg]lahne][^]^m^kfbg^]nlbg`3
ag6*'*g(*)
ag6)'/
ag6)'.
pa^k^

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.


EC1-1-1:
6.3.1.2 (11) & NA

_hk*g.
_hk.5g*)
_hkg7*)

g6gnf[^kh_lmhk^rlpbmaehZ]ljnZeb_rbg`_hkk^]n\mbhg!b'^'\Zm^`hkb^l:mh=Zleblm^]bg
MZ[e^+'*"'

Use
:\\hk]bg`mhma^NDG:%a:Zg]agfZrghm[^nl^]mh`^ma^k'

+'. Variable actions: snow loads


EC1-1-3:
5.2(3)

EC1-1-3:
5.3.1, 5.3.2 & NA

Bgi^klblm^gmhkmkZglb^gmlbmnZmbhgl%lghpehZ]hgZkhh_%l%bl]^g^]Zl[^bg`3
l6mb<^<mld
pa^k^

mb 6

 

 

 


lghpehZ]laZi^_Z\mhk%%^bma^km*hkm+
m*6ng]kb_m^]lghplaZi^_Z\mhk
m+6]kb_m^]lghplaZi^_Z\mhk
?hkZmkhh_l%)6a!pbmaghab`a^klmkn\mnk^l\ehl^hkZ[nmmbg`"%
m*6m+6)'1
  ?hklaZeehpfhghibm\akhh_l%)5a5,)!pbmaghab`a^klmkn\mnk^l\ehl^hk
Z[nmmbg`"%m*6)'1%m+6)'1!*$a(,)"?hkhma^k_hkflh_khh_Zg]eh\Ze^__^\ml
k^_^kmh;L>G*22**,L^\mbhgl.',Zg]/

EC1-1-3:
5.2(7) &Table 5.1






<^ 6
 
 
 

^qihlnk^\h^_\b^gm
?hkpbg]lp^immhih`kZiar<^6)'1
?hkghkfZemhih`kZiar<^6*')
?hkla^em^k^]mhih`kZiar<^6*'+

EC1-1-3:
5.2(8)

<m 6 ma^kfZe\h^_\b^gm%<m6*')hma^kmaZg_hklhf^`eZll&\ho^k^]khh_l%hklbfbeZk

EC1-1-3:
& NA 2.8




ld 6 \aZkZ\m^kblmb\`khng]lghpehZ]dG(f+
 6 )
 '*.!)'*S$)')."$!:$*))"(.+.





pa^k^
S 6 shg^gnf[^kh[mZbg^]_khfma^fZibg;L>G*22**,G:?b`nk^G:'*
: 6 lbm^Zembmn]^%f

? b`nk^G:'*h_ma^G:mh;L>G*22**,Zelh`bo^l`nk^l_hkldZm*))fZ'f'l'e'
Zllh\bZm^]pbmama^shg^l'

? hkma^fZchkbmrh_ma^Lhnma>Zlm%ma^Fb]eZg]l%Ghkma^kgBk^eZg]Zg]ma^ghkmah_
>g`eZg]ZiZkm_khfab`a`khng]%ld6)'.)dG(f+'

? hkma^P^lm<hngmkr%P^lmPZe^lZg]Bk^eZg]ma^`nk^ble^ll'?hkfhlmh_L\hmeZg]
Zg]iZkmlh_ma^^Zlm\hZlmh_>g`eZg]%ma^`nk^blfhk^'L^^?b`nk^+'*'

LghpehZ]bl\eZllb^]ZlZoZkbZ[e^q^]Z\mbhg'>q\^imbhgZe\bk\nflmZg\^lfZr[^mk^Zm^]Zl
Z\\b]^gmZeZ\mbhglbgpab\a\Zl^k^_^k^g\^lahne][^fZ]^mh;L>G*22**,'

12

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml

5
5
55

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

3
4

3
2

1
2
3
4
5

2
4
4

1
1

1
2

2
1
2

Zone 1 = 0.25 kN/m2 at 100 m a.m.s.l.


Zone 1 = 0.40 kN/m2 at 100 m a.m.s.l.
Zone 1 = 0.50 kN/m2 at 100 m a.m.s.l.
Zone 1 = 0.60 kN/m2 at 100 m a.m.s.l.
Zone 1 = 0.70 kN/m2 at 100 m a.m.s.l.

EC1-1-3: NA Fig.
NA.1

4
2 3
4 2

1
?b`nk^+'*
<aZkZ\m^kblmb\`khng]lghpehZ]fZi!`khng]lghpehZ]Zm*))fZ'f'l'e'!dG(f+"

+'/ Variable actions: wind loads


Mabl L^\mbhg ik^l^gml Z o^kr lbfie^ bgm^kik^mZmbhg h_ >nkh\h]^ *T**% **ZV Zg] bl  bgm^g]^] mh
ikhob]^ Z [Zlb\ ng]^klmZg]bg` pbma k^li^\m mh k^\mZg`neZk&ieZg [nbe]bg`l pbma Zm khh_l' Bg
`^g^kZe%fZqbfnfoZen^lZk^`bo^g3pbmafhk^bg_hkfZmbhgZehp^koZen^fb`am[^nl^]'Ma^
nl^klahne][^\Zk^_nemh^glnk^maZmZgrbg_hkfZmbhgnl^]blpbmabgma^l\hi^h_ma^Ziieb\Zmbhg
^goblZ`^]'Ma^ nl^k bl k^_^kk^] mh fhk^ li^\bZeblm `nb]Zg\^T+,% +-V hk ;L >G *22**-T+.V Zg]
bmlNDGZmbhgZe:gg^qT+.ZV'Ma^GZmbhgZe:gg^qbg\en]^l\e^ZkZg]\hg\bl^hp\aZkml_hkma^
]^m^kfbgZmbhgh_i^Zdo^eh\bmrik^llnk^%ji'
Bg^ll^g\^\aZkZ\m^kblmb\pbg]ehZ]\Zg[^^qik^ll^]Zl3
pd6\_ji!s"
pa^k^

\_ 6 _hk\^\h^_\b^gm%pab\aoZkb^l%[nmblZfZq'h_*',_hkho^kZeeehZ]

ji!s"6 \^!s"\^Mj[












pa^k^
\^!s" 6 ^qihlnk^_Z\mhk_khf?b`nk^+',
\^M 6 mhpgm^kkZbg_Z\mhk_khf?b`nk^+'-
j[ 6 )'))/o[+dG(f+
pa^k^
o[ 6 o[%fZi\Zem
pa^k^
o[%fZi6 _ng]Zf^gmZe[Zlb\pbg]o^eh\bmr_khf?b`nk^+'+
\Zem 6 Z embmn]^_Z\mhk%\hgl^koZmbo^er%\Zem6*$)'))*:
pa^k^
:6Zembmn]^Z'f'l'e

EC1-1-4:
Figs NA.7, NA.8

EC1-1-4:
Fig. NA.1

Lrf[hel Z[[k^obZmbhgl Zg] lhf^ h_ ma^ \Zo^Zml Zk^ ^qieZbg^] bg ma^ l^\mbhgl [^ehp% pab\a
mh`^ma^kikhob]^Zikh\^]nk^_hk]^m^kfbgbg`pbg]ehZ]mh;L>G*22**-'

13

+'/'* Determine basic wind velocity, vb


o[6\]bk\l^Zlhg\ikh[o[%)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

EC1-1-4:
4.2(1) Note 2
& NA 2.4, 2.5

pa^k^

\]bk

EC1-1-4:
4.2(2) Note 3
& NA 2.7: Fig. NA.2

EC1-1-4:
4.2(1) Notes 4 & 5
& NA 2.8

EC1-1-4:
4.2(1) Note 2
& NA 2.4: Fig. NA.1

EC1-1-4:
4.2(2) Note 1
& NA 2.5





6 ]bk^\mbhgZe_Z\mhk
<hgl^koZmbo^er%\]bk6*')
!\]bkblZfbgbfnfh_)'0,hk)'0-_hkpbg]bgZg^Zlm^ker]bk^\mbhg%
,)mh*+)"
\l^Zlhg 6 l^Zlhg_Z\mhk
?hkZ/fhgmak^mnkgi^kbh]%bg\en]bg`pbgm^k%hk`k^Zm^k%
\l^Zlhg6*'))
\ikh[ 6 ikh[Z[bebmr_Z\mhk

6 *'))_hkk^mnkgi^kbh]h_.)r^Zkl
o[%) 6 o[%fZi\Zem
pa^k^
o[%fZi 6 _ng]Zf^gmZe[Zlb\pbg]o^eh\bmr_khf?b`nk^+'+
\Zem

6 Z embmn]^_Z\mhk
<hgl^koZmbo^er%\Zem6*$)'))*:

pa^k^

:6Zembmn]^h_ma^lbm^bgf^mk^lZ'f'l'e'
Pa^k^hkh`kZiarbllb`gb\Zgm!b'^'ma^lbm^bl\ehl^mhZlehi^
lm^^i^kmaZg)')."%k^_^kmhG:+'.

+'/'+ Calculate basic wind pressure, qb


j[6)'.r o[+
EC1-1-4: 4.5(1)
Note 2 & NA 2.18

pa^k^

o[ 6 ZlZ[ho^

r 6 ]^glbmrh_Zbk

 6 *'++/d`(f,!6*+')G(f,"_hkND

+'/', Calculate peak wind pressure, qp(z)


EC1-1-4: 4.5(1)
Note 1 & NA 2.17

ji!s"6\^!s"j[_hk\hngmkreh\Zmbhgl

6\^!s"\^Mj[_hkmhpgeh\Zmbhgl
pa^k^

EC1-1-4: 4.5(1)
Note 1, NA 2.17
& Fig. A.NA.1

j[  6 ZlZ[ho^

EC1-1-4: 4.5(1)
Note 1 & NA 2.17:
Fig. NA.7

\^!s" 6 ^qihlnk^_Z\mhk]^kbo^]_khf?b`nk^+',Zma^b`ams!l^^[^ehp"

EC1-1-4: 4.5(1)
Note 1 & NA 2.17:
Fig. NA.8

\^%M 6 ^qihlnk^\hkk^\mbhg_Z\mhk_hkmhpgm^kkZbg]^kbo^]_khf?b`nk^+'-









s




EC1-1-4: 7.2.2(1),
Note & NA 2.26



14

 6




ma^a^b`amZmpab\ajibllhn`am
?hkZpbg]pZk]pZeeZg]pa^ga[%jibl\Ze\neZm^]Zmma^k^_^k^g\^a^b`am
s^6a'?hkhma^kZli^\mkZmbhla3[h_ma^pbg]pZk]pZee%ji%bl\Ze\neZm^]Zm
]b__^k^gmk^_^k^g\^a^b`aml_hk^Z\aiZkm!l^^;L>G*22**-"'
pa^k^
a 6 a^b`amh_[nbe]bg`
[ 6 [k^Z]mah_[nbe]bg`
?hke^^pZk]Zg]lb]^pZeel%
s6a^b`amh_[nbe]bg`

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
200

200
Use 1.0 in this area

31
30

4.0

100
90
80
70
60
50

29
28
27
26

3.5

40

30

25

20

30

3.0

z -hdis(m)

z -hdis(m)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

40

100
90
80
70
60
50

10
20

0.9

23

10
9
8
7
6
5

22
24

2.5

2.0

3
2
0.1

10
9
8
7
6
5

0.8

4
0.7

3
1.5
1
10
100
Distance upwind to shoreline (km)

2
0.1

1
10 20
Distance inside town terrain (km)

Ghm^
Ln[c^\mmhZembmn]^\hkk^\mbhg'

Ghm^
@^g^kZeera]bl6)'?hkm^kkZbg\Zm^`hkrBO!mhpgl^m\'"l^^;L>G*22**-3:'.'

?b`nk^+'+
FZih__ng]Zf^gmZe[Zlb\pbg]
o^eh\bmr%o[%fZi%!f(l"

?b`nk^+',
>qihlnk^_Z\mhk\^!s"_hklbm^lbg\hngmkr
hkmhpgm^kkZbg

EC1-1-4: 4.2(1)
Note 2 & NA 2.4: Fig. NA.1

EC1-1-4: 4.5(1)
Note 1 & NA 2.17: Fig. NA.7

?b`nk^+'-
Fnembieb^k_hk^qihlnk^\hkk^\mbhg_hk
lbm^lbgmhpgm^kkZbg
EC1-1-4: 4.5(1)
Note 1 & NA 2.17: Fig. NA.8

+'/'- Calculate characteristic wind load, wk


pd6ji!s"\_
pa^k^

ji!s"

\ _







6
6

6

ZlZ[ho^
_hk\^\h^_\b^gm_hkma^lmkn\mnk^hklmkn\mnkZe^e^f^gm
@^g^kZeer
\i^$\ib

pa^k^
\i^6 ! ^qm^kgZe"ik^llnk^\h^_\b^gm]^i^g]^gmhglbs^h_Zk^Z\hglb]^k^]Zg]shg^'
?hkZk^ZlZ[ho^*f+%\i^%*)lahne][^nl^]'

EC1-1-4:
7, 8 & NA

EC1-1-4:
7.2.1(1) Note 2 &
NA. 2.25




Overall loads
?hkma^pZeelh_k^\mZg`neZk&ieZg[nbe]bg`l%\i^%*)fZr[^]^m^kfbg^]_khf
MZ[e^0'*h_;L>G*22**-'

EC1-1-4:
7.2.2(2) Note 1 &
NA.2.27

 hp^o^k%_hkma^]^m^kfbgZmbhgh_ho^kZeeehZ]lhg[nbe]bg`l%ma^g^mik^llnk^
A
\h^_\b^gml`bo^gbgMZ[e^+'2fZr[^nl^]'Bgmabl\Zl^bmpbee[^ngg^\^llZkr
mh]^m^kfbg^bgm^kgZepbg]ik^llnk^\h^_\b^gml'

EC1-1-4:
7.2.2(2) Note 1 &
NA.2.27, Table NA.4

Cladding loads
?hkZk^ZlZ[ho^*f+%\i^%*)lahne][^nl^]'\i^%*)fZr[^]^m^kfbg^]_khf
MZ[e^0'*h_;L>G*22**-'L^^MZ[e^+'*)'

EC1-1-4:
7.2.2(2) Note 1 &
NA.2.27

15




Flat roofs
?hkZmkhh_l%Z\\hk]bg`mhma^:]oblhkrGhm^bgma^G:lhf^h_ma^oZen^l
h_\i^%*)bgMZ[e^0'+h_;L>G*22**-!l^^MZ[e^+'**"Zk^lb`gb\Zgmer
]b__^k^gm_khf\nkk^gmikZ\mb\^bgma^ND'Bmk^\hff^g]lmaZm]^lb`g^kllahne]
\hglb]^knlbg`ma^oZen^lbg;L/,223+mhfZbgmZbgma^\nkk^gme^o^elh_lZ_^mr
Zg]^\hghfr'L^^MZ[e^+'*+'

EC1-1-4:
NA.2.28 & NA
advisory note




? hkhma^k_hkflh_khh_k^_^kmh;L>G*22**-Zg]ma^NDG:'
BmpbeeZelh[^g^\^llZkrmh]^m^kfbg^bgm^kgZepbg]ik^llnk^\h^_\b^gml_hk
ma^]^lb`gh_\eZ]]bg`'

EC1-1-4:
7.2.9(6) Note 2




EC1-1-4:
NA 2.27, Table NA.4

MZ[e^+'2
G^mik^llnk^\h^__b\b^gm%\i^%*)%_hkpZeelh_k^\mZg`neZkieZg[nbe]bg`l#

EC1-1-4:
7.2.3, NA.2.28 & NA
advisory note

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

BS 6399:
Table 8 & Fig. 18

\ib 6 bgm^kgZeik^llnk^\h^_\b^gm'
  ?hkgh]hfbgZgmhi^gbg`l\ibfZr[^mZd^gZlma^fhk^hg^khnlh_$)'+Zg])',

a(]
5
1
0.25

G^mik^llnk^\h^__b\b^gm%\i^%*)
*',
*'*
)'1

Ghm^l
*#bg^__^\mma^l^oZen^lZk^_hk\^\h^__b\b^gml_hk]^m^kfbgbg`ho^kZeeehZ]lhg[nbe]bg`l'
+a6a^b`amh_[nbe]bg`'
,[6[k^Z]mah_[nbe]bg`!i^ki^g]b\neZkmhpbg]"'
-]6]^imah_[nbe]bg`!iZkZee^emhpbg]"'
.OZen^lfZr[^bgm^kiheZm^]'
/>q\en]^l_ngg^eebg`'

EC1-1-4:
7.2.2(2) Table 7.1,
Note 1 & NA 2.27:
Tables NA.4a , NA.4b

MZ[e^+'*)
>qm^kgZeik^llnk^\h^__b\b^gm%\i^%*)%_hkpZeelh_k^\mZg`neZk&ieZg[nbe]bg`l
=^l\kbimbhg

Zone A

?hkpZeeliZkZee^emhma^pbg]]bk^\mbhg%Zk^Zlpbmabg
)'+fbgT[4+aVh_pbg]pZk]^]`^

*'+

Zone B

?hkpZeeliZkZee^emhma^pbg]]bk^\mbhg%Zk^Zlpbmabg
)'+fbgT[4+aVh_pbg]pZk]^]`^

)'1

Zone C

?hkpZeeliZkZee^emhma^pbg]]bk^\mbhg%Zk^Zl_khf
)'+fbgT[4+aVmhfbgT[4+aVh_pbg]pZk]^]`^

Zone D

Pbg]pZk]pZee

$)'1

Zone E

E^^pZk]pZee

FZq'

Zones D
G^m
and E
Ghm^l
*a6a^b`amh_[nbe]bg`'
+[6[k^Z]mah_[nbe]bg`!i^ki^g]b\neZkmhpbg]"'
EC1-1-4:
7.2, Table 7.2 & NA

\i^%*)

Shg^

)'.

)'0
$*',

MZ[e^+'**
>qm^kgZeik^llnk^\h^__b\b^gm%\i^%*)_hk_eZmkhh_l#
Shg^

=^l\kbimbhg

\i^%*)
LaZki^]`^
Zm^Zo^l

16

Fbg'

PbmaiZkZi^m

Zone F

Pbmabg)'*fbgT[4+aVh_pbg]pZk]^]`^Zg]pbmabg
*'1
)'+fbgT[4+aVh_k^mnkg^]`^!iZkZee^emhpbg]]bk^\mbhg"

*'/

Zone G

Pbmabg)'*fbgT[4+aVh_pbg]pZk]^]`^Zg]hnmpbma
*'+
)'+fbgT[4+aVh_k^mnkg^]`^!iZkZee^emhpbg]]bk^\mbhg"

*'*

Zone H

Khh_[^mp^^g)'*fbgT[4+aVZg])'.fbgT[4+aV_khf
pbg]pZk]^]`^

)'0

)'0

Zone I
K^fZbg]^k[^mp^^g)'.fbgT[4+aVZg]e^^pZk]^]`^
)'+
)'+
Ghm^l
*#:\\hk]bg`mhG:mh;L>G*22*&*&-%mablmZ[e^blghmk^\hff^g]^]_hknl^bgma^ND'
+a6a^b`amh_[nbe]bg`'
,[6[k^Z]mah_[nbe]bg`!i^ki^g]b\neZkmhpbg]"'

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
MZ[e^+'*+
>qm^kgZeik^llnk^\h^__b\b^gm%\i^%_hk_eZmkhh_l

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Shg^

=^l\kbimbhg

EC1-1-4:
7.2.3, NA.2.28 &
NA advisory note.

\i^
LaZki^]`^
Zm^Zo^l

PbmaiZkZi^m

Zone A

Pbmabg)'*fbgT[4+aVh_pbg]pZk]^]`^Zg]pbmabg
)'+.fbgT[4+aVh_k^mnkg^]`^!iZkZee^emhpbg]]bk^\mbhg"

+')

*'2

Zone B

Pbmabg)'*fbgT[4+aVh_pbg]pZk]^]`^Zg]hnmpbma
)'+.fbgT[4+aVh_k^mnkg^]`^!iZkZee^emhpbg]]bk^\mbhg"

*'-

*',

Zone C

Khh_[^mp^^g)'*fbgT[4+aVZg])'.fbgT[4+aV_khf
pbg]pZk]^]`^

)'0

)'0

Zone D

K^fZbg]^k[^mp^^g)'.fbgT[4+aVZg]e^^pZk]^]`^

)'+

)'+

BS 6399:
Table 8 & Fig. 18

Ghm^l
*a6a^b`amh_[nbe]bg`'
+[6[k^Z]mah_[nbe]bg`!i^ki^g]b\neZkmhpbg]"'

+'/'. Calculate the overall wind force, Fw


?p6\l\]Spd :k^_
pa^k^

EC1-1-4:
5.3.2, Exp. (5.4)
& NA

pd 6 ZlZ[ho^

EC1-1-4:
6.2(1) a), 6.2(1) c)





\l\] 6 lmkn\mnkZe_Z\mhk%\hgl^koZmbo^er
 6 *')
  hkfZr[^]^kbo^]
pa^k^
\l 6 lbs^_Z\mhk
  \lfZr[^]^kbo^]_khf>qi'!/'+"hkmZ[e^G:','=^i^g]bg`hgoZen^lh_
![$a"Zg]!sa]bl"Zg]]bob]bg`bgmhShg^:%;hk<%ZoZen^h_\l
!Z_Z\mhk5*'))"fZr[^_hng]'








\]6 ]rgZfb\_Z\mhk
  \]fZr[^]^kbo^]_khf>qi'!/',"hk`nk^G:'2'=^i^g]bg`hgoZen^lh_dl
!eh`Zkbmafb\]^\k^f^gmh_lmkn\mnkZe]Zfibg`"Zg]a([%ZoZen^h_\]!Z_Z\mhk7
*'))"fZr[^_hng]'

  \ ]fZr[^mZd^gZl*')_hk_kZf^][nbe]bg`lpbmalmkn\mnkZepZeelZg]fZlhgkr
bgm^kgZepZeel%Zg]_hk\eZ]]bg`iZg^elZg]^e^f^gml

:k^_6k^_^k^g\^Zk^Zh_ma^lmkn\mnk^hklmkn\mnkZe^e^f^gm

+'0 Variable actions: others


:\mbhgl]n^mh\hglmkn\mbhg%mkZ_\%k^%ma^kfZeZ\mbhgl%nl^Zllbehlhk_khf\kZg^lZk^hnmlb]^
ma^l\hi^h_mablin[eb\ZmbhgZg]k^_^k^g\^lahne][^fZ]^mhli^\bZeblmebm^kZmnk^'

EC1-1-4:
6.2(1) e) & NA.2.20

EC1-1-4:
6.3(1), Exp. (6.2) &
NA.2.20, Table NA3

EC1-1-4:
6.3(1), Exp. (6.3) &
NA.2.20: Fig. NA9
EC1-1-4:
5.3.2, Exp. (5.4)
& NA

EC1-1-6, EC1-2,
EC1-1-2, EC1-1-5,
EC1-3 & EC1-4

17

+'1 Permanent actions


Ma^ ]^glbmb^l Zg] Zk^Z ehZ]l h_ \hffhger nl^] fZm^kbZel% la^^m fZm^kbZel Zg] _hkfl h_
\hglmkn\mbhgZk^`bo^gbgMZ[e^l+'*,mh+'*.'

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

:\mbhglZkblbg`_khfl^mme^f^gm%]^_hkfZmbhgZg]\k^^iZk^hnmlb]^ma^l\hi^h_mabl]h\nf^gm
[nm `^g^kZeer Zk^ mh [^ \hglb]^k^] Zl i^kfZg^gm Z\mbhgl' Pa^k^ \kbmb\Ze% k^_^k mh li^\bZeblm
ebm^kZmnk^'
MZ[e^+'*,
;ned]^glbmb^l_hklhbelZg]fZm^kbZelT**%+/V
dG(f,

;ned]^glbmb^l

<eZrlmb__

*2++

<hg\k^m^k^bg_hk\^]

 +.')

<eZrlh_m

*/*2

<hg\k^m^p^mk^bg_hk\^]

 +/')

;ned]^glbmb^l
Lhbel

FZm^kbZel

@kZgneZkehhl^

*/*1

@eZll

 +.'/

@kZgneZk]^gl^

*2+*

@kZgbm^

 +0',

Lbemr\eZr%lZg]r\eZr

*/+)

AZk]\hk^

 *2')

Ebf^lmhg^!IhkmeZg]lmhg^f^]'p^b`am"  ++')

FZm^kbZel

18

dG(f,

:liaZem

++'.

;eh\dlZ^kZm^]\hg\k^m^!fbg'"

.')

Ebf^lmhg^!fZk[e^a^Zorp^b`am"

 +/'0

FZ\Z]ZfiZobg`

 +*')

;eh\dlZ^kZm^]\hg\k^m^!fZq'"

2')

;eh\dl]^gl^Z``k^`Zm^

+)')

;eh\dleb`amp^b`am

*-')

;hhdl[nedlmhkZ`^

 1**

LZg]lmhg^

 +,'.

;kb\dphkd[en^

+-')

L\k^^]lZg](\^f^gm

 ++')

;kb\dphkd^g`bg^^kbg`

++')

Lm^^e(bkhg

 00')

;kb\dphkd_e^mmhg

*1')

M^kkZ\hmmZ

 +)'0

;kb\dphkdEhg]hglmh\d

*2')

Mbf[^k=hn`eZl_bk

 .'+

;kb\dphkdlZg]ebf^

+*')

Mbf[^k>nkhi^Zg[^^\a(hZd

 0'*

<abi[hZk]

/'2

Mbf[^k@kZ]^<*/

 ,'/

<hg\k^m^Z^kZm^]

*)')

Mbf[^k@kZ]^<+-

 -'*

Mbf[^kBkhdh(m^Zd

 /'-

<hg\k^m^eb`amp^b`am

*1')

<hg\k^m^ieZbg

+-')

F=?

 1')

IeZlm^k

 *-'*

Ierphh]

 /',

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
MZ[e^+'*-
Mrib\ZeZk^ZehZ]l_hk\hg\k^m^leZ[lZg]la^^mfZm^kbZelT**%+/V
Mrib\ZeZk^ZehZ]l

dG(f+

<hg\k^m^leZ[l

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Ik^\Zlm\hg\k^m^lheb]ngbml!*))ff"

Mrib\ZeZk^ZehZ]l

dG(f+

La^^mfZm^kbZel
+'.)

IeZlm^kldbf\hZm

)').

Ik^\Zlm\hg\k^m^aheehp\hk^ngbmlZ!*.)ff" +'-)

IeZlm^k[hZk]!*+'.ff"

)')2

Ik^\Zlm\hg\k^m^aheehp\hk^ngbmlZ!+))ff" +'10

IeZlm^k[hZk]!*2ff"

)'*.

Ik^\Zlm\hg\k^m^'aheehp\hk^ngbmlZ!,))ff" -')0

Ierphh]!*+'.ff"

)')1

Ik^\Zlm\hg\k^m^aheehp\hk^ngbmlZ!-))ff"

-'1-

Ierphh]!*2ff"

)'*+

Kb[[^]leZ[[!+.)ff"

-'))

JnZkkrmbe^lbg\en]bg`fhkmZk[^]]bg`

)',+

Kb[[^]leZ[[!,))ff"

-',)

KZbl^]_ehhka^Zor]nmr

)'.)

Kb[[^]leZ[[!,.)ff"

-'0)

KZbl^]_ehhkf^]bnfp^b`am

)'-)

PZ__e^leZ[\lmZg]Zk]fhne]l!,+.ff" /'))

KZbl^]_ehhkeb`amp^b`am

)',)

PZ__e^leZ[\lmZg]Zk]fhne]l!-+.ff" 0',)

K^g]^k!*,ff"

)',)

PZ__e^leZ[\lmZg]Zk]fhne]l!.+.ff" 1'/)

L\k^^].)ff

*'*.

La^^mfZm^kbZel

L\k^^]eb`amp^b`am!+.ff"

)'-.

:liaZem!+)ff"

)'-/

LmZbge^lllm^^ekhh_bg`!)'-ff"

)').

<Zki^mZg]ng]^keZr

)').

Lnli^g]^]\^bebg`lm^^e

)'*)

<abi[hZk]!*1ff"

)'*+

Lnli^g]^]_b[k^[hZk]mbe^l

)').

=krebgbg`hglmn]!+)ff"

)'*.

M@[hZk]l!*.'.ff"

)')2

?Zel^\^bebg`lm^^e_kZfbg`

)'*)

M@[hZk]l!++ff"

)'*+

?^em!,eZr^k"Zg]\abiibg`l

)',.

Mbe^l\^kZfb\_ehhkhg[^]]bg`

*'))

@eZll]hn[e^`eZsbg`

)'.+

;Zmm^gl_hkleZmbg`Zg]mbebg`

)'),

@eZlllbg`e^`eZsbg`

)',)

Mbe^l\eZrkhh_!fZq"

)'/0

BglneZmbhg`eZll_b[k^!*.)ff"

)'),

Mbe^lgZmnkZeleZm^!mab\d"

)'/.

IZobg`lmhg^l!.)ff"

*'+)

Mbe^lbgm^keh\dbg`\hg\k^m^

)'..

IeZlm^kmph\hZm`rilnf!*+ff"

)'+*

Mbe^lieZbg\hg\k^m^

)'0.

D^r
ZAheehp\hk^_b`nk^lZllnf^ghmhiibg`!.)fflmkn\mnkZemhiibg`:*'+.dG(f+"
[Kb[[^]leZ[l3*.)p^[90.)\^gmk^lpbma*))ffmab\d_eZg`^(leZ['P^[lehi^*3*)
\PZ__e^leZ[l3*.)kb[l92))\^gmk^lpbma*))ffmab\d_eZg`^(leZ['P^[lehi^*3*)

19

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

MZ[e^+'*.
EhZ]l_hkmrib\Ze_hkflh_\hglmkn\mbhgT+/V
<ZobmrpZee

!dG(f+"

K^lb]^gmbZe_ehhk

;kb\dphkd*)+'.ff

+'-)

<Zki^m

)').

BglneZmbhg.)ff

)')+

?ehZmbg`_ehhk

)'*.
/'+.

;eh\dphkd*))ff

*'-)

L^e_&p^b`amh_+.)fflheb]leZ[

)'+*

Lnli^g]^]\^bebg`

)'+)

MhmZe

-')

)'*)

Eb`amp^b`am\eZ]]bg`

!dG(f+"

L^kob\^l

BglneZm^]iZg^e

)'+)

Inkebgl

)').

=krebgbg`hglmn]

)'*.

MhmZe

)'-)

MhmZe

/'0.

L\ahhe_ehhk

!dG(f+"

<Zki^m(_ehhkbg`

)').

L^e_&p^b`amh_+.)fflheb]leZ[

/'+.
)'*.

<nkmZbgpZeebg`

!dG(f+"

Lnli^g]^]\^bebg`

:eehp

*'))

L^kob\^l

)'+)

Ik^\Zlm\hg\k^m^\eZ]]bg`

!dG(f+"

MhmZe

/'/)

?Z\bg`

*'))

AhlibmZe_ehhk

!dG(f+"

Ik^\ZlmiZg^e!*))ff"

+'-)

?ehhkbg`

)').

BglneZmbhg

)').

L^e_&p^b`amh_+.)fflheb]leZ[

/'+.

=krebgbg`hglmn]

)'*.

L\k^^]

+'+)
)'*.

MhmZe

,'/)

Lnli^g]^]\^bebg`

=krebgbg`

!dG(f+"

L^kob\^l![nm\Zg[^`k^Zm^k"

)').

F^mZelmn]l

)').

MhmZe

1'0)

?eZmkhh_(^qm^kgZem^kkZ\^

!dG(f+"

IZobg`hk`kZo^e%Zeehp

+'+)

IeZlm^k[hZk]Zg]ldbf+

)'-)

MhmZe

)'-.

Mbf[^klmn]pZee

!dG(f+"

Mbf[^klmn]l

)'*)

PZm^kikhh_bg`

)'.)

BglneZmbhg

)'*)

IeZlm^k[hZk]Zg]ldbf+

)'-)

MhmZe

)'.)

L^e_&p^b`amh_+.)fflheb]leZ[\^bebg`

/'+.

H__b\^_ehhk

!dG(f+"

Lnli^g]^]\^bebg`

)'*.

<Zki^m

)'),

L^kob\^l

)',)

KZbl^]_ehhk

)',)

MhmZe

2'.)

L^e_&p^b`amh_+.)fflheb]leZ[

/'+.

Mbf[^kibm\a^]khh_

!dG(f+"

Lnli^g]^]\^bebg`

)'*.

Mbe^l!kZg`^)'.))'0."

)'0.

L^kob\^l

)',)

;Zmm^gl

)').

MhmZe

0'),

?^em

)').

H__b\^\hk^Zk^Z

!dG(f+"

KZ_m^kl

)'*.

Mbe^lZg][^]]bg`%Zeehp

*'))

BglneZmbhg

)').

L\k^^]

+'+)

IeZlm^k[hZk]ldbf

)'*.

L^e_&p^b`amh_+.)fflheb]leZ[

/'+.

L^kob\^l

)'*)

Lnli^g]^]\^bebg`

)'*.

L^kob\^l

)',)

MhmZe

2'2)

LmZbkl

!dG(f+"

*.)ffpZblm! z *0.9+.dG(f,"

-'-)

Mk^Z]l)'*.)'+.-(+9+.dG(f,

*'11

<^bebg`chblml

)'*.

MhmZei^ki^g]b\neZkmhkhh_

*'-.

MhmZehgieZgZllnfbg`,)ibm\a

*'/)

F^mZe]^\dbg`khh_

!dG(f+"

BglneZm^]iZg^e

)'+)

*'*)

Inkebgl

)'*)
)',)

)'+*

Lm^^ephkd

?bgbla3mbe^l[^]]bg`

*'))

L^kob\^l

)'*)

MhmZe

1'/)

MhmZe

)'0)

IeZlm^k

20

!dG(f+"

IeZlm^k

L\k^^])').9++dG(f,

+'.\EhZ]l_hkmrib\Ze_hkflh_\hglmkn\mbhg
MZ[e^+'*-
+'.\EhZ]l_hkmrib\Ze_hkflh_\hglmkn\mbhg

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
+'2 Design values of actions
+'2'* General case
Ma^]^lb`goZen^h_ZgZ\mbhg%?] %maZmh\\nklbgZehZ]\Zl^bl

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

?]6g?c ?d
pa^k^
 g? 6iZkmbZe_Z\mhk_hkma^Z\mbhgZ\\hk]bg`mhma^ebfbmlmZm^ng]^k\hglb]^kZmbhg'MZ[e^
+'*/bg]b\Zm^lma^iZkmbZe_Z\mhklmh[^nl^]bgma^ND_hkma^\hf[bgZmbhglh_
k^ik^l^gmZmbo^Z\mbhglbg[nbe]bg`lmkn\mnk^l'
 c ?d fZr[^\hglb]^k^]Zlma^k^ik^l^gmZmbo^Z\mbhg%?k^i%ZiikhikbZm^mhma^ebfbmlmZm^
[^bg`\hglb]^k^]



pa^k^
c 6 Z_Z\mhkmaZm\hgo^kmlma^\aZkZ\m^kblmb\oZen^h_ZgZ\mbhgbgmhZk^ik^l^gmZmbo^
oZen^'BmZ]cnlmlma^oZen^h_ma^Z\mbhgmhZ\\hngm_hkma^gZmnk^h_ma^ebfbm
lmZm^ng]^k\hglb]^kZmbhgZg]ma^chbgmikh[Z[bebmrh_ma^Z\mbhglh\\nkkbg`
lbfnemZg^hnler'Bm\ZgZllnf^ma^oZen^h_*')_hkZi^kfZg^gmZ\mbhghkc)
hkc*hkc+_hkZoZkbZ[e^Z\mbhg'MZ[e^+'*0lahplahp\aZkZ\m^kblmb\oZen^lh_
oZkbZ[e^Z\mbhglZk^\hgo^km^]bgmhk^ik^l^gmZmbo^oZen^l'MablmZ[e^bl]^kbo^]
_khf;L>G*22)T*)VZg]bmlGZmbhgZe:gg^qT*)ZV'
?d 6 \aZkZ\m^kblmb\oZen^h_ZgZ\mbhgZl]^g^]bgL^\mbhgl+'+Zg]+','

MZ[e^+'*/
IZkmbZe_Z\mhkl!g?"_hknl^bgo^kb_b\Zmbhgh_ebfbmlmZm^lbgi^klblm^gmZg]mkZglb^gm]^lb`glbmnZmbhgl
EbfbmlmZm^

I^kfZg^gmZ\mbhgl
!@d"

E^Z]bg`oZkbZ[e^Z\mbhg :\\hfiZgrbg`oZkbZ[e^
!Jd%*"
Z\mbhgl!Jd%b"]

*'*)!)'2"Z

*'.)!)')"Z

EC0:
Tables A1.2(A), A1.2(B),
A1.2(C), A1.4 & NA

Z">jnbeb[kbnf!>JN"
c)%b*'.)!)')"Z

["Lmk^g`maZmNEL!LMK(@>H"ghmbgoheobg``^hm^\agb\ZeZ\mbhgl
Either
>qi'!/'*)"

*',.!*')"Z

*'.

c)*'.

*',.!*')"Z

c)*'.

c)*'.

*'+.!*')"Z

*'.

c)*'.

or the worst case of


 >qi'!/'*)Z"
 and
 >qi'!/'*)["

\"Lmk^g`maZmNEL!LMK(@>H"pbma`^hm^\agb\ZeZ\mbhgl
Worst case of
 L^m;

*',.!*')"Z

*'.!)')"Z

*')

*',

 and
 L^m<
]"L^kob\^Z[bebmr
<aZkZ\m^kblmb\

*'))

*'))

c)%b*'))

?k^jn^gm

*'))

c*%**'))

c+%b*'))

JnZlb&i^kfZg^gm

*'))

c+%**'))

c+%b*'))

*')

:][

c*%b!fZbg"
c+%b!hma^kl"

*')

:>]\

c+%b

^":\\b]^gmZe]^lb`glbmnZmbhgl
>qi'!/'**Z"
_"L^blfb\
>qi'!/'*+Z(["

D^r
Z OZen^b__ZohnkZ[e^!lahpgbg[kZ\d^ml"
[ E^Z]bg`Z\\b]^gmZeZ\mbhg%:]%blng_Z\mhk^]
\ L^blfb\Z\mbhg%:>]
] K^_^kmh;L>G*22)3:*'+'+G:

Ghm^l
* Ma^oZen^lh_cZk^`bo^gbgMZ[e^+'*0'
+ @^hm^\agb\ZeZ\mbhgl`bo^gbgma^mZ[e^
Zk^[Zl^]hg=^lb`g:iikhZ\a*bg
<eZnl^:*','*!."h_;L>G*22)%pab\abl
k^\hff^g]^]bgbmlGZmbhgZe:gg^q'

21

+'2'+ Design values at ULS


?hkma^NELh_lmk^g`ma!LMK"%ma^]^lb`g^kfZr\ahhl^[^mp^^gnlbg`>qik^llbhg!/'*)"hkma^
phklm\Zl^h_>qik^llbhg!/'*)Z"hk>qik^llbhg!/'*)["'

EC0: 6.4.3.2(3)

Single variable action


:mNEL%ma^]^lb`goZen^h_Z\mbhglbl

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

^bma^k
 >qi'!/'*)" *',.@d$*'.Jd%*
hkma^phklm\Zl^h_3
 >qi'!/'*)Z" *',.@d$c)%**'.Jd%*
Zg]
 >qi'!/'*)[" *'+.@d$*'.Jd%*
pa^k^

@d 6 i^kfZg^gmZ\mbhg

Jd%*6 lbg`e^oZkbZ[e^Z\mbhg

c)%*6 \hf[bgZmbhg_Z\mhk_hkZlbg`e^oZkbZ[e^ehZ]!l^^MZ[e^+'*0"
MZ[e^+'*0
OZen^lh_c_Z\mhkl
EC0: A1.2.2
& NA

EC1-1-1: 3.3.2

:\mbhg

c)

c*

c+

Bfihl^]ehZ]lbg[nbe]bg`l

Category A: domestic, residential areas

)'0

)'.

)',

Category B: office areas

)'0

)'.

)',

Category C: congregation areas

)'0

)'0

)'/

Category D: shopping areas

)'0

)'0

)'/

Category E: storage areas

*')

)'2

)'1

Category F: traffic area (vehicle weight 30 kN)

)'0

)'0

)'/

Category G: traffic area (30 kN < vehicle weight 160 kN)

)'0

)'.

)',

Category H: roofsZ

)'0

)')

)')

Snow loads where altitude 1000 m a.m.s.l.Z

)'.

)'+

)')

Wind loadsZ

)'.

)'+

)')

Temperature effects (non-fire)Z

)'/

)'.

)')

D^r
a Hgkhh_l%bfihl^]ehZ]l%lghpehZ]lZg]pbg]ehZ]llahne]ghm[^Ziieb^]mh`^ma^k'
Ghm^l
1 Ma^gnf^kb\ZeoZen^l`bo^gZ[ho^Zk^bgZ\\hk]Zg\^pbma;L>G*22)Zg]bmlNDGZmbhgZe:gg^q'
2 <Zm^`hkb^lDZg]EZk^Zllnf^]mh[^Zl_hk<Zm^`hkrA

>qik^llbhg!/'*)"e^Z]lmhma^nl^h_g?6g@6*',._hki^kfZg^gmZ\mbhglZg]g?6gJ6*'.)_hk
oZkbZ[e^Z\mbhgl!g@_hki^kfZg^gmZ\mbhglblbgm^g]^]mh[^\hglmZgmZ\khllZeeliZgl"'
>qik^llbhg!/'*)"blZepZrl^jnZemhhkfhk^\hgl^koZmbo^maZgma^e^ll_ZohnkZ[e^h_>qik^llbhgl
!/'*)Z"Zg]!/'*)["'>qik^llbhg!/'*)["pbeeghkfZeerZiierpa^gma^i^kfZg^gmZ\mbhglZk^ghm
`k^Zm^kmaZg-'.mbf^lma^oZkbZ[e^Z\mbhgl!^q\^im_hklmhkZ`^ehZ]l%\Zm^`hkr>bgMZ[e^+'*0%
pa^k^>qik^llbhg!/'*)Z"ZepZrlZiieb^l"'
Ma^k^_hk^%^q\^imbgma^\Zl^h_\hg\k^m^lmkn\mnk^llniihkmbg`lmhkZ`^ehZ]lpa^k^c)6*')%
hk_hkfbq^]nl^%>qik^llbhg!/'*)["pbeenlnZeerZiier'Manl%_hkf^f[^kllniihkmbg`o^kmb\Ze
Z\mbhglZmNEL%*'+.@d$*'.Jdpbee[^ZiikhikbZm^_hkfhlmlbmnZmbhglZg]Ziieb\Z[e^mhfhlm
\hg\k^m^lmkn\mnk^l!l^^?b`nk^+'."'
<hfiZk^]pbmama^nl^h_>qik^llbhg!/'*)"%ma^nl^h_^bma^k>qik^llbhg!/'*)Z"hk!/'*)["e^Z]l
mh Z fhk^ \hglblm^gm k^ebZ[bebmr bg]^q Z\khll eb`amp^b`am Zg] a^Zorp^b`am fZm^kbZel'

22

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
50

gk kN/m (or kN/m2)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

40

Use Exp. (6.10a)

30
Ghm^
:llnfbg`c)6)'0
b'^'Ziieb\Z[e^mhZeeZk^Zl
^q\^imlmhkZ`^'

20
Use Exp. (6.10b)

10
0

10

q k kN/m (or kN/m2)


?b`nk^+'.
Pa^gmhnl^>qi'!/'*)Z"hk>qi'!/'*)["

Accompanying variable actions


:`Zbg ma^ ]^lb`g^k fZr \ahhl^ [^mp^^g nlbg` >qik^llbhg !/'*)" hk ma^ e^ll _ZohnkZ[e^ h_
>qik^llbhgl!/'*)Z"hk!/'*)["'

EC0:
6.4.3.2(3)

>bma^k
>qi'!/'*)" *',.@d$*'.Jd%*$S!c)%b*'.Jd%b "
hkma^phklm\Zl^h_3
>qi'!/'*)Z" *',.@d$c)%**'.Jd%*$S!c)%b*'.Jd%b"
Zg]
>qi'!/'*)[" *'+.@d$*'.Jd%*$S!c)%b*'.Jd%b"
pa^k^
 @d 6 i^kfZg^gmZ\mbhg
 Jd%*6 *lmoZkbZ[e^Z\mbhg
 Jd%b 6 bmaoZkbZ[e^Z\mbhg
 c)%*6 \aZkZ\m^kblmb\\hf[bgZmbhg_Z\mhk_hk*lmoZkbZ[e^ehZ]!l^^MZ[e^+'*0"
 c)%b 6 \aZkZ\m^kblmb\\hf[bgZmbhg_Z\mhk_hkbmaoZkbZ[e^ehZ]!l^^MZ[e^+'*0"
Bgma^Z[ho^%Jd%*!Zg]c)%b "k^_^klmhma^e^Z]bg`oZkbZ[e^Z\mbhgZg]Jd%b!Zg]c)%b "k^_^klmh
Z\\hfiZgrbg`bg]^i^g]^gmoZkbZ[e^Z\mbhgl'Bg`^g^kZe%ma^]blmbg\mbhg[^mp^^gma^mphmri^lh_
Z\mbhglpbee[^h[obhnl!l^^?b`nk^+'/"4pa^k^bmblghm%^Z\aehZ]lahne]bgmnkg[^mk^Zm^]Zlma^
e^Z]bg`Z\mbhg':elh%ma^gnf^kb\ZeoZen^l_hkiZkmbZe_Z\mhkl`bo^gbgma^NDGZmbhgZe:gg^qT*)ZV
Zk^nl^]bgma^^jnZmbhglZ[ho^'Ma^oZen^h_c)]^i^g]lhgma^nl^h_ma^[nbe]bg`Zg]lahne]
[^h[mZbg^]_khfma^NDGZmbhgZe:gg^q_hk;L>G*22)!l^^MZ[e^+'*0"'

EC0:
A1.2.2, A1.3.1 & NA

qk2
gk2
qk1
gk1
qk1
gk1

qk3 = wk

qk1
gk1
qk1
gk1
A
?b`nk^+'/
Bg]^i^g]^gmoZkbZ[e^Z\mbhgl

Ghm^
@^g^kZeerma^oZkbZ[e^
Z\mbhglhgZmrib\Zeh__b\^
[eh\dphne][^\hglb]^k^]
Zl[^bg`mak^^l^mlh_
bg]^i^g]^gmoZkbZ[e^
Z\mbhgl3
*' Bfihl^]h__b\^ehZ]l
hgma^h__b\^_ehhkl'
+' Khh_bfihl^]ehZ]'
,' Pbg]ehZ]'

23

Ma^^qik^llbhglmZd^bgmhZ\\hngmma^ikh[Z[bebmrh_chbgmh\\nkk^g\^h_ehZ]l[rZiierbg`ma^
c)%b_Z\mhkmhma^Z\\hfiZgrbg`oZkbZ[e^Z\mbhg'Ma^ikh[Z[bebmrmaZmma^l^\hf[bg^]Z\mbhglpbee
[^^q\^^]^]bl]^^f^]mh[^lbfbeZkmhma^ikh[Z[bebmrh_Zlbg`e^Z\mbhg[^bg`^q\^^]^]'
B_ma^mphbg]^i^g]^gmoZkbZ[e^Z\mbhglJd%*Zg]Jd%+Zk^Zllh\bZm^]pbma]b__^k^gmliZglZg]ma^
nl^h_>qik^llbhg!/'*)["blZiikhikbZm^%ma^gbghg^l^mh_ZgZerl^lZiier
*'+.@d$*'.Jd%*mhma^Jd%*liZgl

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Zg]*'+.@d$c)'b*'.Jd%*mhma^Jd%+liZgl'
BgZllh\bZm^]ZgZerl^lZiier
*'+.@d$c)%b*'.Jd%*mhma^Jd%*liZgl
Zg]*'+.@d$*'+.Jd%+mhma^Jd%+liZgl'
L^^>qZfie^+'**'+!mphoZkbZ[e^Z\mbhgl"'

+'2', Design values at SLS


EC0: 6.5 & Table A1.4

Ma^k^Zk^mak^^\hf[bgZmbhglh_Z\mbhglZmLEL!hkehZ]\hf[bgZmbhgZmLEL"'Ma^l^Zk^`bo^gbg
MZ[e^+'*1'Ma^\hf[bgZmbhgZg]oZen^mh[^nl^]]^i^g]lhgma^gZmnk^h_ma^ebfbmlmZm^[^bg`
\a^\d^]' JnZlb&i^kfZg^gm \hf[bgZmbhgl Zk^ Zllh\bZm^] pbma ]^_hkfZmbhg% \kZ\d pb]mal Zg]
\kZ\d\hgmkhe'?k^jn^gm\hf[bgZmbhglfZr[^nl^]mh]^m^kfbg^pa^ma^kZl^\mbhgbl\kZ\d^]hk
ghm'Ma^gnf^kb\oZen^lh_c)%c*Zg]c+Zk^`bo^gbgMZ[e^+'*0'
<heehjnbZeer
c)aZl[^\hf^dghpgZlma^\aZkZ\m^kblmb\oZen^
c*aZl[^\hf^dghpgZlma^_k^jn^gmoZen^
c+aZl[^\hf^dghpgZlma^jnZlb&i^kfZg^gmoZen^

EC0: Table A1.4

MZ[e^+'*1
IZkmbZe_Z\mhklmh[^Ziieb^]bgma^o^kb_b\Zmbhgh_ma^LEL
Permanent actions Gk

Variable actions Qk

Unfavourablea

Favourablea

Leadingb

Othersb

Characteristic

@d%lni

@d%bg_

Jd%*

c)%bJd%b

Frequent

@d%lni

@d%bg_

c*%*Jd%*

c+%bJd%b

Quasi-permanent

@d%lni

@d%bg_

c+%*Jd%*

c+%bJd%b

Combination

D^r
a @^g^kZeer@d%lniZg]@d%bg_fZr[^mZd^gZl@d'L^^L^\mbhg+'2'.
b c_Z\mhklZk^`bo^gbgMZ[e^+'*0

+'2'- Design values for other limit states


EhZ]\hf[bgZmbhglZk^`bo^gbgMZ[e^+'*/_hk
Z">jnbeb[kbnf!>JN"%
["Lmk^g`maZmNELghmbgoheobg``^hm^\agb\ZeZ\mbhgl%
\"Lmk^g`maZmNELpbma`^hm^\agb\ZeZ\mbhgl%
]"L^kob\^Z[bebmr%
^":\\b]^gmZeZg]
_"L^blfb\]^lb`glbmnZmbhgl'

24

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
+'2'. Variations in permanent actions

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Pa^gma^oZkbZmbhgh_Zi^kfZg^gmZ\mbhgblghmlfZeema^gma^nii^k!@dc%lni"Zg]ma^ehp^k
!@dc%bg_"\aZkZ\m^kblmb\oZen^l!ma^2.Zg]._kZ\mbe^oZen^lk^li^\mbo^er"lahne][^^lmZ[ebla^]'
Mablikh\^]nk^blg^\^llZkrhgerpa^gma^\h^_\b^gmh_oZkbZmbhg!6*))tlmZg]Zk]]^obZmbhg(
f^Zg"bl`k^Zm^kmaZg*)'Bgm^kflh_i^kfZg^gmZ\mbhgl%oZkbZmbhglbgma^l^e_&p^b`amh_\hg\k^m^
bg\hg\k^m^_kZf^lZk^\hglb]^k^]lfZee'

EC0: 4.1.2, 4.1.2 (3)

PD 6687[6]: 2.8.4

:m NEL pa^k^ ma^ oZkbZmbhg bl ghm lfZee% g@d%lni lahne] [^ nl^] pbma @dc%lni Zg] g@d%bg_ pbma
@dc%bg_'LbfbeZker%pa^k^ma^oZkbZmbhgblghmlfZee%ZmLEL@dc%lnilahne][^nl^]pa^k^Z\mbhglZk^
ng_ZohnkZ[e^Zg]@dc%bg_nl^]pa^k^_ZohnkZ[e^'
Pa^k^\a^\dl%ghmZ[er\a^\dlhglmZmb\^jnbeb[kbnf!>JN"%Zk^o^krl^glbmbo^mhoZkbZmbhgh_ma^
fZ`gbmn]^h_Zi^kfZg^gmZ\mbhg_khfhg^ieZ\^mhZghma^k%ma^_ZohnkZ[e^Zg]ng_ZohnkZ[e^
iZkmlh_mablZ\mbhglahne][^\hglb]^k^]Zlbg]bob]nZeZ\mbhgl'Bgln\ao^krl^glbmbo^o^kb\Zmbhgl
g@%lniZg]g@%bg_lahne][^nl^]'

EC0: 6.4.3 (4)

+'*) Load arrangements of actions: introduction


Ma^ikh\^llh_]^lb`gbg`\hg\k^m^lmkn\mnk^lbgoheo^lb]^gmb_rbg`k^e^oZgm]^lb`glbmnZmbhglZg]
ebfbmlmZm^l'Ma^l^bg\en]^i^klblm^gm%mkZglb^gmhkZ\\b]^gmZelbmnZmbhgl'Bg^Z\a]^lb`glbmnZmbhg
ma^lmkn\mnk^lahne][^o^kb^]Zmma^k^e^oZgmebfbmlmZm^l'

EC0: 3.2

Bg ma^ ZgZerlbl h_ ma^ lmkn\mnk^ Zm ma^ ebfbm lmZm^ [^bg` \hglb]^k^]% ma^ fZqbfnf ^__^\m h_
Z\mbhgl lahne] [^ h[mZbg^] nlbg` Z k^Zeblmb\ ZkkZg`^f^gm h_ ehZ]l'@^g^kZeer oZkbZ[e^ Z\mbhgl
lahne][^ZkkZg`^]mhikh]n\^ma^fhlmng_ZohnkZ[e^^__^\m%_hk^qZfie^mhikh]n\^fZqbfnf
ho^kmnkgbg`fhf^gmlbgliZglhkfZqbfnf[^g]bg`fhf^gmlbglniihkml'
?hk [nbe]bg` lmkn\mnk^l% ]^lb`g \hg\^gmkZm^l fZbger hg ma^ NEL% ma^ nembfZm^ ebfbm lmZm^ h_
lmk^g`ma!LMK"%Zg]LEL%ma^l^kob\^Z[bebmrebfbmlmZm^'Ahp^o^k%bmbl^ll^gmbZemaZmZeeebfbmlmZm^l
Zk^\hglb]^k^]'Ma^ebfbmlmZm^lh_^jnbeb[kbnf!>JN"%lmk^g`maZmNELpbma`^hm^\agb\ZeZ\mbhgl
!LMK(@>H"Zg]Z\\b]^gmZelbmnZmbhglfnlm[^mZd^gbgmhZ\\hngmZlZiikhikbZm^'

EC0: 3.3, 3.4, 6.4, 6.5

+'** Load arrangements according to the UK National


Annex to Eurocode
Bg[nbe]bg`lmkn\mnk^l%Zgrh_ma^_heehpbg`l^mlh_lbfieb^]ehZ]ZkkZg`^f^gmlfZr[^nl^]Zm
NELZg]LEL!L^^?b`nk^+'0"'

Cl. 5.1.3 & NA

N Ma^fhk^\kbmb\Zeh_3

 Z"Zem^kgZm^liZgl\Zkkrbg`g@@d$gJJdpbmahma^kliZglehZ]^]pbmag@@d4Zg]
 ["ZgrmphZ]cZ\^gmliZgl\Zkkrbg`g@@d$gJJdpbmahma^kliZglehZ]^]pbmag@@d'
N Hkma^fhk^\kbmb\Zeh_3

 Z"Zem^kgZm^liZgl\Zkkrbg`g@@d$gJJd4pbmahma^kliZglehZ]^]pbmag@@d4Zg]
 ["ZeeliZgl\Zkkrbg`g@@d$gJJd'
N Hk%_hkleZ[lhger%ZeeliZgl\Zkkrbg`g@@d$g@@d%ikhob]^]ma^_heehpbg`\hg]bmbhglZk^f^m3
L BgZhg^&pZrliZggbg`leZ[ma^Zk^Zh_^Z\a[Zr^q\^^]l,)f+!Z[Zrbl]^_bg^]ZlZ

lmkbiZ\khllma^_neepb]mah_Zlmkn\mnk^[hng]^]hgma^hma^klb]^l[rebg^lh_lniihkm"'
L M
 a^kZmbhh_ma^oZkbZ[e^Z\mbhg%Jd%mhma^i^kfZg^gmZ\mbhg%@d%]h^lghm^q\^^]*'+.'
L Ma^fZ`gbmn]^h_ma^oZkbZ[e^Z\mbhg^q\en]bg`iZkmbmbhgl]h^lghm^q\^^].dG(f+'

Pa^k^ZgZerlblbl\Zkkb^]hnm_hkma^lbg`e^ehZ]\Zl^h_ZeeliZglehZ]^]%ma^k^lnembg`fhf^gml%
^q\^im mahl^ Zm \Zgmbe^o^kl% lahne] [^ k^]n\^] [r +)% pbma Z \hgl^jn^gmbZe bg\k^Zl^ bg ma^
liZgfhf^gml'

25

g JJ d
g JJ d

g @@ d

g JJ d g @
@ d

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

g JJ d

a) Alternate spans loaded

b) Adjacent spans loaded

g @@ d

c) All spans loaded

Ghm^
Pabelmma^nl^h_>qi'!/'*)"blbg]b\Zm^]%ma^l^ZkkZg`^f^gmlfZr^jnZeer[^nl^]pbma>qi'!/'*)Z"
hk!/'*)["'
?b`nk^+'0
EhZ]ZkkZg`^f^gml_hk[^ZflZg]leZ[lZ\\hk]bg`mhNDG:mh>nkh\h]^

26

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
+'*+ Examples of loading
Ikhc^\m]^mZbel

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

chg

Ch[gh'

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

<Ze\neZm^][r

Continuous beam in a domestic


structure

CCIP 041
1
Oct 09

2.12.1 Continuous beam in a domestic structure


Determine the appropriate load combination and ultimate load
for a continuous beam of four 6 m spans in a domestic structure
supporting a 175 mm slab at 6 m centres.
qk
gk
A

6000 mm

6000 mm

6000 mm

6000 mm

Figure 2.8 Continuous beam in a domestic structure


a) Actions
Permanent action, gk
Self-weight, 175 mm thick slabs : 0.17 x 25 x 6.0
E/o self-weight downstand 800 225 : 0.80 x 0.225 x 25
50 mm screed @ 22 kN/m3 : 0.05 x 22 x 6.0
Finishes and services : 0.50 x 6.0
Dividing wall 2.40 4.42 (200 mm dense blockwork with
plaster both sides)
Total
gk
Variable action, qk
Imposed, dwelling @ 1.5 kN/m2 : 1.5 x 6.0
Total

= 26.3
= 4.5
= 6.6
= 3.0
= 10.6
= 51.0

=
qk =

Ultimate load, n
Assuming use of Exp. (6.10), n = 1.35 51 + 1.5 9.0 =
Assuming use of worst case of Exp. (6.10a) or Exp. (6.10b)
Exp. (6.10a): n = 1.35 51 + 0.7 1.5 9.0 =
Exp. (6.10b): n = 1.25 51 + 1.5 9.0 =
In this case Exp. (6.10a) would be critical
=ultimate load

kN/m

9.0
9.0

= 82.4
= 78.3
= 77.3
= 78.3

This could also be determined from Figure 2.5 or by determining that gk > 4.5qk

27

Ikhc^\m]^mZbel

Continuous beam in mixed use


structure

<Ze\neZm^][r

chg

Ch[gh'

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

2.12.2 Continuous beam in mixed use structure


Determine the worst case arrangements of actions for ULS design of a
continuous beam supporting a 175 mm slab @ 6 m centres. Note that
the variable actions are from two sources as dened in Figure 2.9.:
qk1 = 15 kN/m

qk2 = 24 kN/m
gk = 51 kN/m

6000 mm

6000 mm

6000 mm

6000 mm

Office use @ 2.5 kN/m2

Shopping use @ 4.0 kN/m2

c0 = 0.7

c0 = 0.7

Figure 2.9 Continuous beam in mixed-use structure

a) Load combination
Load combination Exp. (6.10a) or Exp. (6.10b) will be used, as either
will produce a smaller total load than Exp. (6.10). It is necessary to
decide which expression governs.
i) Actions
Permanent action
As before, Example 2.12.1
Variable action
Ofce @ 2.5 kN/m2
Shopping @ 4.0 kN/m2
Ultimate load, n
For ofce use:
Exp. (6.10a): n = 1.35 51 + 0.7 1.5 15.0
Exp. (6.10b): n = 1.25 51 + 1.5 15.0
For shopping use:
Exp. (6.10a): n = 1.35 51 + 1.5 0.7 24.0
Exp. (6.10b): n = 1.25 51 + 1.5 24.0
By inspection Exp. (6.10b) governs in both cases

kN/m
gk

= 51.0

qk1
qk2

= 15.0
= 24.0

= 84.6
= 86.3
= 94.1
= 99.8

b) Arrangement of ultimate loads


As the variable actions arise from different sources, one is a leading
variable action and the other is an accompanying variable action. The
unit loads to be used in the various arrangements are:
This could also be determined from Figure 2.5 or by determining that g > 4.5q
k
k

28

CCIP 041
1
Oct 09

EC1-1-1:
6.3.1.1 & NA,
EC0:
A.1.2.2. & NA

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
i) Actions
Permanent
1.25 51.0
Variable
Ofce use
as leading action, gQQk = 1.5 15
as accompanying action,
c0gQQk = 0.7
1.5 15
Shopping use
as leading action, gQQk = 1.5 24
as accompanying action,
c0gQQk = 0.7
1.5 24

kN/m
= 63.8

= 22.5
= 15.75

= 36.0
= 25.2

ii) For maximum bending moment in span AB

The arrangement and magnitude of actions of loads are shown


in Figure 2.10. The variable load in span AB assumes the value as
leading action and that in span CD takes the value as an
accompanying action.
Leading
variable action
gQ q k1 = 22.5 kN/m

Accompanying
Permanent
variable action
action
c Q g Q q k2 = 25.2 kN/m gG g k = 63.8 kN/m

Figure 2.10 For maximum bending moment in span


p AB

iii) For maximum bending moment in span CD


The load arrangement is similar to that in Figure 2.10, but now
the variable load in span AB takes its value as an accompanying
action
(i.e. 15.75 kN/m) and that in span CD assumes the value as
leading action (36 kN/m).
Accompanying
variable action
c Qg Qq k1 = 15.8 kN/m

Leading
variable action
g Qq k2 = 36.0 kN/m

Permanent
action
gG,inf g k = 63.8 kN/m

Figure 2.11 For maximum bending moment in span


p CD

29

iv) For maximum bending moment at support B

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

The arrangement of loads is shown in Figure 2.12. As both spans AB


and BC receive load from the same source, no reduction is possible
(
(other
than that for large
g area).
).
Leading
variable action
gQ q k1 = 22.5 kN/m

EC1-1-1:
6.3.1.1 (10)
& NA

Permanent
action
gG g k = 63.8 kN/m

Figure 2.12 For maximum bending moment at support


pp
B
v) For maximum bending moment at support D
The relevant arrangement of loads is shown in Figure 2.13. Comments
made in d) also apply here.
Leading
variable action
gQ q k2 = 36 kN/m

Permanent
action
gG g k = 63.8 kN/m

Figure 2.13 For maximum bending moment at support


pp
D
vi) For critical curtailment and hogging in span CD
The relevant arrangement of loads is shown in Figure 2.14.
Accompanying
p
variable action
c 0gQ q k1 = 15.8 kN/m

Leading
variable action
g Q q k2 = 36.0 kN/m
Permanent actionn
gG,in f g k = 51 kN/m
m
D

Figure 2.14 For curtailment and hogging in span


p CD
Eurocode 2 requires that all spans should be loaded with either gG,sup or gG,inff (as
per Table 2.16). As illustrated in Figure 2.14, using gG,inff = 1.0 might be critical for
curtailment and hogging in spans.
spans

Variable actions may be subjected to reduction factors: a , according to the


A

area supported
pp
((m2), aA = 1.0 A/1000 0.75.

30

Cl. 2.4.3(2)

EC1-1-1:
6.3.1.2 (10)
& NA

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
Ikhc^\m]^mZbel

<Ze\neZm^][r

chg

Ch[gh'

Propped cantilever

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

2.12.3 Propped cantilever


Determine the Equilibrium, ULS and SLS (deformation) load
combinations for the propped cantilever shown in Figure 2.15. The
action P at the end of the cantilever arises from the permanent
action of a wall.
gk

qk

CCIP 041
1
Oct 09

EC0:
Table 1.2(B),
Note 3

C
A

Figure 2.15 Propped


pp cantilever beam and loading
For the purposes of this example, the permanent action P is considered
to be from a separate source than the self-weight of the structure so
both gG,sup and gG,inf need to be considered.

a) Equilibrium limit state (EQU) for maximum uplift at A


0.0qk = 0
gGinf gk= 0.9gk

gGk,sup P= 1.1P

1.5qk

C
gGk,sup gk= 1.1gk

EC0:
Table A1.2 (A)
& NA
EC0:
6.4.3.1 (4),
Table A1.2 (A)
& NA

b) Ultimate limit state (ULS)


i) For maximum moment at B and anchorage of top reinforcement BA
gGk,sup gk= 1.35gk

gQ qk= 1.5qk gGk,sup P= 1.35P

EC0: Tables A1.1,


A1.2 (B) & NA

C
A

Figure 2.17 ULS: maximum moment at B


Notes
gGk,inf gk = 1.0 gk may be critical in terms of curtailment of top bars BA.

31

ii) For maximum sagging moment AB


gGk,sup P=
P 1.1P

gQqk= 1.5qk
gGk,sup gk= 1.35gk

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

C
A

EC0:
Table A1.1,
A1.2 (B) & NA

Figure 2.18 ULS: maximum span


p moment AB
Notes
1 Depending on the magnitude of gk, qk length AB and BC, gGk,inf gk (= 1.0 gk) may be more
critical for span moment.
2 The magnitude of the load combination indicated are those for Exp. (6.10) of BS EN
1990. The worst case of Exp. (6.10a) and Exp. (6.10b) may also have been used.
3 Presuming supports A and B were columns then the critical load combination for Column
A would be as Figure 2.18. For column B the critical load combination might be either as
Figure 2.17 or 2.18.

c) Serviceability limit state (SLS) of deformation:


(quasi-permanent loads)
i) For maximum deformation at C
1.0c
c2qk= 0.3*qk

1.0gk

1.0P

EC0:
Tables A1.1,
A1.2.2, A1.4 &
NA

C
A

*Assuming office area

Figure 2.19 SLS: maximum deformation at C

ii) For maximum deformation AB


1.0c
c2qk= 0.3*qk

1.0P

1.0gk
C
A

* Assuming office area

Figure 2.20 SLS: maximum deformation AB


Notes
Quasi-permanent load combinations may also be used for calculations of crack widths or
controlling cracking, i.e. the same load combinations as shown in Figures 2.19 and 2.20 may
be used to determine SLS moment to determine stress in reinforcement. The characteristic
and/or frequent combinations may be appropriate for other SLS limit states: for example, it
is recommended that the frequent combination is used to determine whether a member has
cracked or not.

32

:gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
Ikhc^\m]^mZbel

<Ze\neZm^][r

chg

Ch[gh'

Overall stability

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP-041
1
Oct 09

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

2.12.4 Overall stability (EQU)


For the frame shown in Figure 2.21, identify the various load
arrangements to check overall stability (EQU) against overturning.
Assume that the structure is an ofce block and that the loads qk2
and qk3 may be treated as arising from one source.
qk1
gk1
qk2
gk2
wk

qk3
gk3

Figure 2.21 Frame configuration

a) EQU Treating the floorr imposed load as the leading variable


action
Permanent action,
P
favourable
0.9gk1

Accompanying
variable action
= gQk co wk
= 1.5 x 0.5 x wk

Accompanying variable actioon


on = gQkco qk1 = 1.05qk1
Permanent action, unfavourable
b = gGk,supgk1 = 1.1gk1

Permanent action,
P
favourable
0.9gk2

Lead variable action = gQk qk2


k2 = 1.5qk2
Permanent action, unfavourable
b = gGk,supgk2 = 1.1gk2

Permanent action,
P
favourable
0.9gk3

Lead variable action = gQk qk3


k3 = 1.5qk3
Permanent action, unfavourable
b = gGk,supgk3 = 1.1gk3

= 0.75 wk
A

Figure 2.22 Frame with floor variable action as leading variable action

Tables 2.16
& 2.17

See Table 2.17 for values of c0

33

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

b) EQU Treating the rooff imposed load as the leading variable


action

0.75 wk

0.9gk1

1.5q k1
1.1gk1

0.9gk2

1.5 x 0.7 x q k2 = 1.05 q k2


1.1gk2

0.9gk3

Tables 2.16
& 2.17

1.5 x 0.7 x q k3 = 1.05 q k3


1.1gk3

Figure 2.23 Frame with roof variable action as leading variable actttion

c) EQU Treating wind as the leading variable action

1.5 wk

0.9gk1

1.5 x 0.7 x q k1 = 1.05 q k1


1.1gk1

0.9gk2

1.5 x 0.7 x q k2 = 1.05 q k2


1.1gk2

0.9gk3

1.5 x 0.7 x q k3 = 1.05 q k3


1.1gk3

Figure 2.24 Frame with wind as lead variable action

34

Tables 2.16
& 2.17

,3LeZ[l

3 Slabs
3.0 General
Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Ma^\Ze\neZmbhglbgmabll^\mbhgZk^ik^l^gm^]bgma^_heehpbg`ln[&l^\mbhgl3
,'*:lbfierlniihkm^]hg^&pZrleZ[
,'+ :\hgmbgnhnlhg^&pZrleZ[
,', :\hgmbgnhnlkb[[^]leZ[
,'-:[Zrh_ZZmleZ[
,'.:lmZbkb`am'
Ma^l^\Ze\neZmbhglZk^bgm^g]^]mhlahppaZmfb`am[^]^^f^]mrib\ZeaZg]\Ze\neZmbhgl'Ma^r
Zk^ beenlmkZmbo^ h_ ma^<h]^ Zg] Zk^ ghm g^\^llZkber [^lm ikZ\mb\^'Ma^ klm mak^^ ln[&l^\mbhgl
bg\en]^ ]^mZbebg` \a^\dl ^'`' \nkmZbef^gm e^g`mal ]^m^kfbg^] lmkb\mer bg Z\\hk]Zg\^ pbma ma^
ikhoblbhglh_;L>G*22+**'Ma^ZmleZ[\Ze\neZmbhgbllniie^f^gm^][rZ\hff^gmZkr'
:`^g^kZef^mah]h_]^lb`gbg`leZ[lbllahpg[^ehp'
N =^m^kfbg^]^lb`geb_^'

EC0 & NA Table NA.2.1

N :ll^llZ\mbhglhgma^leZ['

EC1 & NA

N :ll^ll]nkZ[bebmrk^jnbk^f^gmlZg]]^m^kfbg^

Table 4.1
BS 8500-1: Tables A4 & A5

\hg\k^m^lmk^g`ma'
N <a^\d\ho^kk^jnbk^f^gml_hkZiikhikbZm^_bk^

k^lblmZg\^i^kbh]'
N <Ze\neZm^fbgbfnf\ho^k_hk]nkZ[bebmr%_bk^Zg]

EC2-1-2: Tables 5.8,


5.9, 5.10 & 5.11
Cl. 4.4.1

[hg]k^jnbk^f^gml'
N =^m^kfbg^pab\a\hf[bgZmbhglh_Z\mbhglZiier'

EC0 & NA Tables


NA.A1.1 & NA.A1.2 (B)

N =^m^kfbg^ehZ]bg`ZkkZg`^f^gml'

Cl. 5.1.3(1) & NA

N :gZerl^lmkn\mnk^mhh[mZbg\kbmb\Zefhf^gmlZg]la^Zk

Cl. 5.4, 5.5, 5.6

_hk\^l'
N =^lb`g_e^qnkZek^bg_hk\^f^gm'

Cl. 6.1

N <a^\d]^_e^\mbhg'

Cl. 7.4

N <a^\dla^Zk\ZiZ\bmr'

Cl. 6.2

N Hma^k]^lb`g\a^\dl3

<a^\dfbgbfnfk^bg_hk\^f^gm
<a^\d\kZ\dbg`!lbs^hkliZ\bg`h_[Zkl"
<a^\d^__^\mlh_iZkmbZeqbmr
<a^\dl^\hg]Zkrk^bg_hk\^f^gm'

Cl. 9.3.1.1(1), 9.2.1.1(1)


Cl. 7.3, Tables 7.2N & 7.3N
Cl. 9.3.1.2(2)
Cl. 9.3.1.1(2), 9.3.1.4(1)

N <a^\d\nkmZbef^gm'

Cl. 9.3.1.1(4), 9.2.1.3, Fig. 9.2

N <a^\dZg\ahkZ`^'

Cl. 9.3.1.2, 8.4.4, 9.3.1.1(4)


Cl. 9.2.1.5(1), 9.2.1.5(2)

N <a^\deZil'

Cl. 8.7.3

35

3.1 Simply supported one-way slab

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Mabl\Ze\neZmbhgblbgm^g]^]mhlahpZmrib\Ze[Zlb\aZg]\Ze\neZmbhg'
Ikhc^\m]^mZbel

<Ze\neZm^][r

chg

Ch[gh'

Simply supported one-way slab

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP 041
1
Oct 09

A 175 mm thick slab is required to support screed, nishes, an


ofce variable action of 2.5 kN/m2 and demountable partitions
(@ 2 kN/m). The slab is supported on load-bearing block walls.
fck = 30 MPa, fyk = 500 MPa. Assume a 50-year design life and a
requirement for 1 hour resistance to re.
qk = 3.3 kN/m2
gk = 5.9 kN/m2
4800

Figure 3.1 Simply


p supported
pp
one-way slab

3.1.1 Actions

kN/m2

Permanent:
Self-weight 0.175 25
50 mm screed
Finishes, services

EC1-1-1: Table A1

Total

= 4.4
= 1.0
= 0.5
gk = 5.9

Total

= 2.5
= 0.8
jk = 3.3

EC1-1-1: Tables
6.1, 6.2 & NA
EC1-1-1: 6.3.12(8)

Variable:
Offices, general use B1
Movable partitions @ 2.0 kN/m

3.1.2 Cover
Nominal cover, cnom:
cnom = cmin + Dcdev

Exp. (4.1)

where
cmin = max[cmin,b ; cmin,dur]
where
cmin,b

Cl. 4.4.1.2(3)
= minimum cover due to bond = diameter of bar

Assume 12 mm main bars.


cmin,dur = minimum cover due to environmental conditions
Assuming XCI and using C30/37 concrete,
cmin,dur = 15 mm
Dcdev = allowance in design for deviation.
Assuming no measurement of cover,
Dcdev = 10 mm
= cnom = 15 + 10 = 25 mm
36

Table 4.1.
BS 8500-1:
Table A4.
Cl. 4.4.1.2(3)

,'*3Lbfierlniihkm^]hg^&pZrleZ[

Fire:
Check adequacy of section for 1 hour fire resistance (i.e. REI 60).
Thickness, hs,min = 80 mm cf. 175 mm proposed
= OK
Axis distance, amin = 20 mm cf. 25 + f/2 = 31 i.e. not critical = OK

EC2-1-2:
4.1(1), 5.1(1)
& Table 5.8

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

= choose cnom = 25 mm

3.1.3 Load combination (and arrangement)


Ultimate load, n:
By inspection, BS EN 1990 Exp. (6.10b) governs
= n = 1.25 5.9 + 1.5 3.3 = 12.3 kN/m2

Fig. 2.5
ECO:
Exp. (6.10b)

3.1.4 Analysis
Design moment:
MEd = 12.3 4.82/8 = 35.4 kNm
Shear force:
V = 12.3 4.8/2 = 29.5 kN/m

3.1.5 Flexural design


Effective depth:
d = 175 25 12/2 = 144 mm
Flexure in span:
K = MEd/bd2fck = 35.4 106/(1000 1442 30) = 0.057
z/d = 0.95
z = 0.95 144 = 137 mm
As = MEd/fydz = 35.4 106/(137 500/1.15) = 594 mm2/m
(r = 0.41%)

Fig. 3.5
Appendix A1
Table C5

Try H12 @ 175 B1 (645 mm2/m)

3.1.6 Deflection
Check span-to-effective-depth ratio.
Basic span-to-effective-depth ratio for r = 0.41% = 20
As,prov/As,req = 645/599 = 1.08
Max. span = 20 1.08 144 = 3110 mm i.e. < 4800 mm
Consider in more detail:
Allowable l/d = N K F1 F2 F3
where
N = 25.6 (r = 0.41%, fck = 30 MPa)
K = 1.0 (simply supported)
F1 = 1.0 (beff/bw = 1.0)
F2 = 1.0 (span < 7.0 m)
F3 = 310/ ss 1.5

Appendix B
Table 7.4N & NA
Exp. (7.17)
= no good

Cl. 7.4.2,
Appendix C7,
Tables C10-C13

37

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
ss = ssu (As,reqq/As,prov) 1/d
where
ssu { 242 MPa (From Figure C3 and
gk/qk = 1.79, c2 = 0.3, gG = 1.25)
d = redistribution ratio = 1.0
= ss { 242 594/645 = 222
= F3 = 310/222 = 1.40 1.5
= Allowable l/
l d = 25.6 1.40 = 35.8
Actual l/
l d = 4800/144 = 33.3

Cl. 7.4.2, Exp. (7.17)


Table 7.4N, & NA
Table NA.5:
Note 5
Figure C3
Figure C3

= OK

Use H12 @ 175 B1 (645 mm2/m)

3.1.7 Shear
By inspection, OK
However, if considered critical:
V = 29.5 kN/m as before
VEd = 29.5 0.14 12.3 = 27.8 kN/m
vEd = 27.8 103/144 103 = 0.19 MPa
vRd,c = 0.53 MPa

Cl. 6.2.1(8)
Cl. 6.2.2(1);
Table C6

= No shear reinforcement required


q

3.1.8 Summary of design

H12 @ 175

Figure 3.2 Simply


p supported
pp
slab: summary

3.1.9 Detailing checks


It is presumed that the detailer would take the design summarised
above and detail the slab to normal best practice, e.g. to SMDSC[9]
or to How to design concrete structures using Eurocode 2
2,[8] Chapter
10, Detailing. This would usually include dimensioning and detailing
curtailment, laps, U-bars and also undertaking the other checks detailed
below. See also 3.2.10 detailing checks for a continuous one-way slab.
a) Minimum areas
Minimum area of reinforcement:
As,min = 0.26 (ffctm/ffyk) bt] 0.0013 btd
where
bt = width of tension zone
fctm = 0.30 fck0.666

38

See Appendix B1.5

Cl. 9.3.1.1, 9.2.1.1


Table 3.1

,'*3Lbfierlniihkm^]hg^&pZrleZ[
LeZ[l

As,min = 0.26 0.30 300.666 1000 144/500 = 216 mm2/m


(r
r = 0.15%)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

= H12 @ 175 B1 OK
Crack control:
OK by inspection.
Maximum spacing of bars:
< 3h < 400 mm

Table 7.2N & NA


OK

Cl. 9.3.1.1.(3)

Secondary reinforcement:
20% As,reqq = 0.2 645 = 129 mm2/m
Use H10 @ 350 (224) B2
Edges: effects of assuming partial fixity along edge
Top steel required = 0.25 594 = 149 mm2/m
Use H10 @ 350 (224) T2 B2 as U-bars
extending 960 mm into slab
b) Curtailment
Curtailment main bars:
Curtail main bars 50 mm from or at face of support.

At supports:
50% of As to be anchored from face of support.

Cl. 9.3.1.1.(2)
Cl. 9.3.1.2.(2)

SMDSC[9]:
Fig. 6.4;
How to[8]:
Detailing
Cl. 9.3.1.2.(1)

Use H12 @ 350 B1 T1 U-bars


In accordance with SMDSC[9] detail MS3 lap U-bars 500 mm with
main steel, curtail T1 leg of U-bar 0.1ll (= say 500 mm) from face
of support.

free unsupported edge is required to use longitudinal and transverse


reinforcement generally using U-bars with legs at least 2h long. For slabs
150 mm deep or greater, SMDSC[9] standard detail recommends U-bars lapping
500 mm with bottom steel and extending 0.1ll top into span.

Cl. 9.3.1.4.(1)

39

3.2 Continuous one-way solid slab

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Mabl\Ze\neZmbhgblbgm^g]^]mhlahpbg]^mZbema^ikhoblbhglh_]^lb`gbg`ZleZ[mh>nkh\h]^+
nlbg`^ll^gmbZeerma^lZf^leZ[Zlnl^]bg>qZfie^,'*'
Ikhc^\m]^mZbel

<Ze\neZm^][r

chg

Ch[gh'

Continuous one-way solid slab

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP 041
1
Oct 09

A 175 mm thick continuous slab is required to support screed, nishes,


an ofce variable action of 2.5 kN/m2 and demountable partitions
(@ 2 kN/m). The slab is supported on 200 mm wide load-bearing block
walls at 6000 mm centres. fck = 30, fyk = 500 and the design life is
50 years. A re resistance of 1 hour is required.

qk = 3.3 kN/m2
gk = 5.9 kN/m2

200

5800

200

5800

Figure 3.3 Continuous solid slab

3.2.1 Actions
kN/m2

Permanent:
As Section 3.1.1

gk = 5.9

Variable:
As Section 3.1.1

jk = 3.3

EC1-1-1:
6.3.1.2(8)

3.2.2 Cover
Nominal cover, cnom:
As Section 3.1.2

cnom = 25 mm

3.2.3 Load combination (and arrangement)


Ultimate action (load):
As Section 3.1.3, BS EN 1990 Exp. (6.10b) governs
= n = 1.25 5.9 + 1.5 3.3 = 12.3 kN/m2

Fig. 2.5
EC0:
Exp. (6.10b)

3.2.4 Analysis
Clear span, ln
a1 = min[h/2; t/2] = min[175/2; 200/2]
a2 = min[h/2; t/2] = min[175/2; 200/2]
leff

40

= 5800 mm
=
87.5 mm
=
87.5 mm
= 5975 mm

Cl. 5.3.2.2(1)

,'+3<hgmbgnhnlhg^&pZrlheb]leZ[
LeZ[l

Bending moment:
End span
1st internal support

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Internal spans
and supports

MEd = 0.086 12.3 5.9752

= 37.8 kNm/m

5.9752

= 37.8 kNm/m

MEd = 0.086 12.3

MEd = 0.063 12.3

5.9752

Cl. 5.1.1(7)
Table C2

= 27.7 kNm/m

Shear:
End support

VEd = 0.40 12.3 5.975

= 29.4 kN/m

1st interior support

VEd = 0.60 12.3 5.975

= 44.1 kN/m

3.2.5 Flexural design: span


a) End span (and 1st internal support)
Effective depth, d:
d = h cnom f/2
= 175 25 12/2 = 144 mm
Relative flexural stress, K:
K = MEd/bd2fck = 37.8 106/1000 1442 30 = 0.061
K' = 0.207
or restricting x/d to 0.45
K' = 0.168
= by inspection, section is under-reinforced
(i.e. no compression reinforcement required).
Lever arm, z:
z = (d/2) [1 + (1 3.53K)0.5] 0.95d
= (144/2) [1 + (1 3.53 0.061)0.5] = 0.945d = 136 mm

Appendix A1

Fig. 3.5
Appendix A1

Area of steel, As:


As = MEd/fydz
= 37.8 106/(500/1.15 136) = 639 mm2/m
(r = 0.44%)
Try H12 @ 175 B1 (645 mm2/m)
b) Internal spans and supports
Lever arm, z:
By inspection, z = 0.95d = 0.95 144 = 137 mm

Fig. 3.5
Appendix A1

Area of steel, As:


As = MEd/fydz
= 27.7 106/(500/1.15 137) = 465 mm2/m
(r = 0.32%)
Try H12 @ 225 B1 (502 mm2/m)

Designers may choose to use another form of this equation:


z/d = 0.5 + (0.25 0.882K)0.5 0.95

41

3.2.6 Deflection: end span

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Check end span-to-effective-depth ratio.


Allowable l/d
d = N K F1 F2 F3

Appendix B

where
N = basic effective depth to span ratio:
r = 0.44%
r0 = fck0.5 103 = 0.55% = use Exp. (7.16a)
1.5fck0.5

3.2fck0.5

Cl. 7.4.2(2)

1)1.5

N = 11 +
r0/r
r+
(r0/r
r
0.5
= 11 + 1.5 30 0.55/0.44 + 3.2 300.5 (0.55/0.44 1)1.5
= 11.0 + 10.3 + 2.2 = 23.5

Exp. (7.16a)

K = structural system factor


= 1.3 (end span of continuous slab)

Cl. 7.4.2

F1 = flanged section factor


= 1.0 (beff/bw = 1.0)

Cl. 7.4.2

F2 = factor for long spans associated with brittle partitions


= 1.0 (span < 7.0 m)
F3 = 310/ ss 1.5

Cl. 7.4.2

where
ss = (ffyk/ gS) (As,reqq/As,prov) (SLS loads/ULS loads (1/d)
= fyd (As,reqq/As,prov) (gk + c2 qk)/(g
gGgk + gQqk) (1/d)
= (500/1.15) (639/645) [(5.9 + 0.3 3.3)/12.3] 1.08
= 434.8 0.99 0.56 1.08 = 260 MPa
F3 = 310/260 = 1.19
Note: As,prov/As,req 1.50

Allowable l/d
d = N K F1 F2 F3
= 23.5 1.3 1.0 1.19
= 36.4
Max. span = 36.4 144 = 5675 mm, i.e. < 5795 mm

= No good

Try increasing reinforcement to H12 @ 150 B1 (754 mm2/m)


ss = 434.8 639/754 0.56 1.08 = 223
F3 = 310/223 = 1.39
Allowable l/d
d = 23.5 1.3 1.0 1.39
= 42.5

42

See Appendix B1.5

The use of Table C3 implies certain amounts of redistribution, which are dened in
Table C14.

Cl. 7.4.2, Exp. (7.17)


Table 7.4N & NA,
Table NA.5:
Note 5
Exp. (7.17)
EC0: A1.2.2
Table C14

Table 7.4N & NA,


Table NA.5:
Note 5

,'+3<hgmbgnhnlhg^&pZrlheb]leZ[
LeZ[l

Max. span = 42.5 144 = 6120 mm, i.e. > 5795 mm


OK
2
= H12 @ 150 B1 (754 mm /m) OK

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

3.2.7 Deflection: internal span


Check internal span-to-effective-depth ratio.
Allowable l/d = N K F1 F2 F3
where
N = basic effective depth to span ratio:
r = 0.32%
r0 = fck0.5 103 = 0.55% = use Exp. (7.16a)
1.5fck0.5

3.2fck0.5

1)1.5

N = 11 +
r0/r
r+
(r0/r
r
= 11 + 1.5 300.5 0.55/0.32 + 3.2 300.5 (0.55/0.32 1)1.5
= 11.0 + 14.1 + 10.7 = 35.8

Cl. 7.4.2(2)
Exp. (7.16a)

K = structural system factor


= 1.5 (interior span of continuous slab)

Cl. 7.4.2

F1 = flanged section factor


= 1.0 (beff/bbw = 1.0)

Cl. 7.4.2

F2 = factor for long spans associated with brittle partitions


= 1.0 (span < 7.0 m)

Cl. 7.4.2

F3 = 310/ ss 1.5

where
ss = fyd (As,reqq/As,prov) (gk + c2 qk)/(g
gGgk + gQqk) (1/d)
= (500/1.15) (465/502) [(5.9 + 0.3 3.3)/12.3] 1.03
= 434.8 0.93 0.56 1.03 = 233 MPa

Cl. 7.4.2, Exp.


(7.17), Table 7.4N
& NA, Table NA.5
Note 5.
Exp. (7.17)
EC0: A1.2.2
Table C14

F3 = 310/233 = 1.33
Allowable l/d
d = N K F1 F2 F3
= 35.8 1.5 1.0 1.33
= 71.4
Max. span = 71.4 144 = 10280 mm i.e. > 5795 mm
OK
Use H12 @ 225 B1 (502 mm2/m) in internal spans
p

3.2.8 Shear
Design shear force, VEd:
At d from face of end support,
VEd= 29.4 (0.144 + 0.0875) 12.3 = 26.6 kN/m

Cl. 6.2.1(8)

At d from face of 1st interior support,


VEd = 44.1 (0.144 + 0.0875) 12.3 = 41.3 kN/m
Shear resistance, VRd,c:
VRd,c = (0.18/ gC)k(100 rl fck)0.333 bwd 0.0035kk1.5fck0.5bwd

Cl. 6.2.2(1)

43

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
k = 1 + (200/d)0.5 2.0 as d < 200 mm
k = 2.0
rl = Asl/bd
Assuming 50% curtailment (at end support)
= 50% 754/(144 1000) = 0.26%
VRd,c = (0.18/1.5) 2.0 (100 0.26/100 30)0.33 1000 144
= 0.12 2 1.97 1000 144
= 0.47 1000 144 = 68.1 kN/m
But VRd,cmin = 0.035k1.5fck0.5 bwd
where
k
= 1 + (200/d)0.5 2.0; as before k = 2.0
VRd,cmin = 0.035 21.5 300.5 1000 144
= 0.54 1000 144 = 77.6 kN/m
= VRd,c = 77.6 kN/m
= OK, no shear reinforcement required at end or 1st internal
supports
= H12 @ 150 B1 & H12 @ 175 T1 OK
By inspection, shear at other internal supports OK.

3.2.9 Summary of design


H12 @ 175
fck = 30 MPa
P
cnom = 25 mm
H12 @ 150

H12 @ 225

Figure 3.4 Continuous solid slab: design summary


Commentary
It is usually presumed that the detailer would take the design
summarised above together with the general arrangement illustrated
in Figure 3.3 and detail the slab to normal best practice. The
detailers responsibilities, standards and timescales should be clearly
dened but it would be usual for the detailer to draw and schedule
not only the designed reinforcement but all the reinforcement
required to provide a compliant and buildable solution. The work
would usually include checking the following aspects and providing
appropriate detailing :
t Minimum areas
t Curtailment lengths
t Anchorages
44

,'+3<hgmbgnhnlhg^&pZrlheb]leZ[
LeZ[l
t Laps
t U-bars
t Rationalisation
t Critical dimensions

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

t Details and sections


The determination of minimum reinforcement areas, curtailment
lengths, anchorages and laps using the principles in Eurocode 2 is
shown in detail in the following calculations. In practice these would
be determined from published tables of data or by using reference
texts[8, 9]. Nonetheless the designer should check the drawing
for design intent and compliance with standards. It is therefore
necessary for the designer to understand and agree the principles
of the detailing used.

3.2.10 Detailing checks


a) Minimum areas
Minimum area of longitudinal tension (flexural) reinforcement
As,min = 0.26(ffctm/ffyk) btd 0.0013 btd
where
bt = width of tension zone
fctm = 0.30 fck0.667
As,min = 0.26 0.30 300.6677 1000 144/500 = 216 mm2/m
(r
r = 0.15%)
= H12 @ 225 B1 OK
Secondary (transverse reinforcement)
Minimum 20% As,req
20% As,reqq = 0.2 502 = 100 mm2/m
Consider As,min to apply as before.
As,min = 216 mm2/m
Try H10 @ 350 B2 (224 mm2/m)

Cl. 9.3.1.1, 9.2.1.1

Table 3.1

Cl. 9.3.1.1(2)
SMDSC[9]

Check edge.
Assuming partial fixity exists at edges, 25% of As is required
to extend 0.2 the length of the adjacent span.

Cl. 9.3.1.2(2)

As,reqq = 25% 639 = 160 mm2/m


As,min as before = 216 mm2/m
= Use H10 @ 350 (224 mm2/m) U-bars at edges

Cl. 9.3.1.1, 9.2.1.1

45

Curtail 0.2 5975 = 1195 mm, say 1200 mm measured from face
of support.

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Maximum spacing of bars


Maximum spacing of bars < 3h < 400 mm

OK

Crack control
As slab < 200 mm, measures to control cracking are unnecessary.
However, as a check on end span:
Loading is the main cause of cracking,
= use Table 7.2N or Table 7.3N for wmax = 0.4 mm and ss = 241 MPa
(see deflection check).
Max. bar size = 20 mm
or max. spacing = 250 mm
= H12 @ 150 B1 OK.
End supports: effects of partial fixity
Assuming partial fixity exists at end supports, 15% of As is required
to extend 0.2 the length of the adjacent span.
As,reqq = 15% 639 = 96 mm2/m
But, As,min as before = 216 mm2/m
(r
r = 0.15%)
One option would be to use bob bars, but choose to use U-bars
Try H12 @ 450 (251 mm2/m) U-bars at supports
pp
Curtail 0.2 5975 = say, 1200 mm measured from face of support.
b) Curtailment
i) End span, bottom reinforcement
Assuming end support to be simply supported, 50% of As should
extend into the support.
50% 639 = 320 mm2/m
Try H12 @ 300 (376 mm2/m) at supports
pp
In theory, 50% curtailment of reinforcement may take place al from
where the moment of resistance of the section with the remaining
50% would be adequate to resist the applied bending moment. In
practice, it is usual to determine the curtailment distance as being
al from where MEd = MEd,max/2.

Detail

MS2 of SMDSC[9], suggests 50% of T1 legs of U-bars should extend 0.3l


(= say 1800 mm) from face of support by placing U-bars alternately reversed.

46

Cl. 9.3.1.2(2)

Cl. 9.3.1.1.(3)
Cl. 7.3.3(1)
Cl. 7.3.3(2),
7.3.1.5

Table 7.2N &


interpolation,
Table 7.3N &
interpolation
Cl. 9.3.1.2(2)

Cl. 9.3.1.1, 9.2.1.1

Cl. 9.3.1.2(2)

Cl. 9.3.1.2(1)

Cl. 9.3.1.2(1)
Note, 9.2.1.3 (2)

,'+3<hgmbgnhnlhg^&pZrlheb]leZ[

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

a) Load arrangement
r

X
MEd,max
MEdx = RAX nXX 2/2

b) Bending moment MEdx

lbd

987
633 lbd

MEdx /z
TTensile force
in reinforcement, Fs

TTensile resistance of reinforcement


c) Tensile
T
force in bottom reinforcement
50%
50%
A
B
633 (say 500)

987
(say 850)

d) Curtailment of bottom reinforcement

Figure 3.5 Curtailment of bottom reinforcement: actions, bending


moments, forces in reinforcement and curtailment
Thus, for a single simply supported span supporting a UDL of n,
MEd,max = 0.086nl 2; RA = 0.4nl
At distance, XX, from end support, moment,
MEd@XX = RAX nX 2/2
= when M@XX = MEd,max/2:
0.086nl 2/2 = 0.4nlXX nX 2/2
47

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Assuming X = xl
0.043nl2 = 0.4nlxll nxx2l2/2
0.043
= 0.4xx x2/2
0
= 0.043 0.4xx + x2/2
x
= 0.128 or 0.672, say 0.13 and 0.66
= at end support 50% moment occurs at 0.13 x span
0.13 5975 = 777 mm
Shift rule: for slabs, al may be taken as d (= 144 mm),
= curtail to 50% of required reinforcement at 777 144
= 633 mm from centreline of support.
Say 500 mm from face of support
pp
A

Cl. 9.2.1.3(2),
6.2.2(5)

= in end span at 1st internal support 50% moment occurs at 0.66


span
0.66 5975 = 3944 mm
Shift rule: for slabs al may be taken as d (= 144 mm),
= curtail to 50% of required reinforcement at 3944 + 144
= 4088 mm from support A
or 5975 4088 = 987 mm from centreline of support B.
Say 850 mm from face of support
pp
B

Cl. 9.2.1.3(2),
6.2.2(5)

ii) 1st interior support, top reinforcement


Presuming 50% curtailment of reinforcement is required this may
take place al from where the moment of resistance of the section
with the remaining 50% would be adequate. However, it is usual to
determine the curtailment distance as being al from where MEd =
MEd,max/2.

Cl. 9.3.1.2(1)
Note, 9.2.1.3(2)

Thus, for the 1st interior support supporting a UDL of n,


MEd,maxTT = 0.086nl 2; RB = 0.6nl
At distance Y from end support, moment,
MEd@Y
Y = MEd,maxTT RAY + nY 2/2
= when M@Y
Y = MEd,maxT /2
0.086nl 2/2 = 0.086nl 2 0.6nlY
Y + nY 2/2
Assuming Y = yl
0.043nl 2 = 0.086nl 2 0.6nlyll + ny 2l 2/2
0 = 0.043 0.6yy + y 2/2
y = 0.077 (or 1.122), say 0.08
= at end support 50% moment occurs at 0.08 span
0.08 5975 = 478 mm
Shift rule: for slabs, al may be taken as d 144 mm
= curtail to 50% of required reinforcement at 478 + 144
= 622 mm from centreline of support.
50% of reinforcement may be curtailed at, say,
600 mm from either face of support
pp
B
48

Cl. 9.2.1.3(2),
6.2.2(5)

,'+3<hgmbgnhnlhg^&pZrlheb]leZ[

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

100% curtailment may take place al from where there is no hogging


moment. Thus,
when M@Y = MEd,maxT/2
0 = 0.086nl2 0.6nlY + nY2/2
Assuming Y = yl
0 = 0.086 0.6y + y2/2
y = 0.166 (or 1.034), say 0.17
= at end support 50% moment occurs at 0.17 span
0.17 5975 = 1016 mm
Shift rule: for slabs, al may be taken as d
= curtail to 100% of required reinforcement at 1016 + 144
= 1160 mm from centreline of support.
100% of reinforcement may be curtailed at, say,
1100 mm from either face of support B.
iii) Support B bottom steel at support
At the support 25% of span steel required

0.25 639 = 160 mm2


As,min as before = 216 mm2/m
For convenience use H12 @ 300 B1 (376 mm2/m)
c) Anchorage at end support
As simply supported, 50% of As should extend into the support.
This 50% of As should be anchored to resist a force of
FE = VEd al/z
where
VEd = the absolute value of the shear force
al = d, where the slab is not reinforced for shear
z = lever arm of internal forces
d = 30.9 kN/m
FE = 29.4 d/0.95
Anchorage length, lbd:
lbd = alb,rqd lb,min
where
a = conservatively 1.0
lb,rqd = basic anchorage length required
= (f/4) (ssd/fbd)
where
f
= diameter of the bar = 12 mm
ssd = design stress in the bar at the ultimate limit state
= FE/As,prov
= 30.9 1000/376 = 81.5 MPa

Cl. 9.3.1.1(4),
9.2.1.5(1),
9.2.1.4(1)
Cl. 9.3.1.1, 9.2.1.1

Cl. 9.2.1.2(1) &


Note, 9.2.1.4(2)
Exp. (9.3)

Cl. 9.2.1.3(2)

Cl. 8.4.4
Exp. (8.4)

Exp. (8.3)

Maximum z = 0.947 at mid-span and greater towards support.


49

fbd

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
n1
n2
fct,d

= ultimate bond stress


= 2.25 n1 n2 fct,d

Cl. 8.4.2(2)

= 1.0 for good bond conditions and 0.7 for all other
conditions = 1.0
= 1.0 for bar diameter 32 mm
= design tensile strength
= act fct,k/ gC. For fck = 30 MPa
= 1.0 2.0/1.5 = 1.33 MPa

Cl. 3.1.6(2) &


NA, Tables 3.1
& 2.1N

=f[] = 2.25 1.33 = 3.0 MPa


lb,rqd = (12/4) (81.5/1.33) = 183 mm
lb,min = max(10d, 100 mm) = 120 mm
lbd = 183 mm measured from face of support
By inspection, using U-bars, OK
d) Laps
Lap H12 @ 300 U-bars with H12 @ 150 straights.
Tension lap, l0 = a1 a2 a3 a5 a6 lb,rqd a l0min
where
a1 = 1.0 (straight bars)
a2 = 1 0.15 (cd f)/f
where
cd = min(pitch, side cover or cover)
= 25 mm
f = bar diameter
= 12 mm
a2 = 0.84
a3 = 1.0 (no connement by reinforcement)
a5 = 1.0 (no connement by pressure)
a6 = 1.5
lb,rqd = (f/4) ssd/fbd
where
ssd = the design stress at ULS at the position from
where the anchorage is measured.
Assuming lap starts 500 mm from face of
support (587.5 mm from centreline of support):
MEd = 29.5 0.59 12.3 0.592/2
= 15.2 kNm
ssd = MEd /(Asz)
= 15.2 106/(376 144/0.95) = 267 MPa
fbd = ultimate bond stress
= 2.25 n1 n2 fct,d
50

Exp. (8.6)
Fig. 9.3

Exp. (8.10)
Table 8.2

Fig. 8.4

Table 8.2

Table 8.3
Exp. (8.3)

Cl. 8.4.2(2)

,'+3<hgmbgnhnlhg^&pZrlheb]leZ[

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
n1 = 1.0 for good conditions
n2 = 1.0 for f < 32 mm
fct,d = act fct,k/gC
where
act = 1.0
fct,k = 2.0
gC = 1.5
=f[] = 2.25 2.0/1.5 = 3.0 MPa
lb,rqd

Cl. 3.1.6 (2) & NA


Table 3.1
Table 2.1N & NA

= (f/4) ssd/fbd
= (12/4) (267/3) = 267 mm

l0min b = max[0.3 a6 lb,rqd; 15f/ 200 mm]


= max[0.3 1.5 229; 15 12; 200]
= max[124; 180; 200] = 200 mm
= l0 = a1 a2 a3 a5 a6 lb,rqd l0min
= 1.0 0.84 1.0 1.0 1.5 329 200 = 414 mm
But good practice suggests minimum lap of max[tension lap; 500]
= lap with bottom reinforcement = 500 mm starting 500 from
face of support.

Exp. 8.6

SMDSC[9]: MS2

3.2.11 Summary of reinforcement details


A
1200
H12 U-bars @ 300

200

500 500

500

H12 @ 150

600

H12 @ 300
500 350

200
600 500
H12 @ 175 T1

H12 @ 225
350 500
200

Figure 3.6 Continuous solid slab: reinforcement details

1200

500

H10 @ 350 B2

Figure 3.7 Section AA showing reinforcement details at edge


51

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

3.3 Continuous ribbed slab


Ikhc^\m]^mZbel

<Ze\neZm^][r

Continuous ribbed slab

chg

Ch[gh'

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

This continuous 300 mm deep ribbed slab has spans of 7.5 m,


9.0 m and 7.5 m and is required for an ofce to support a variable
action of 5 kN/m2. It is supported on wide beams that are the same
depth as the slab designed in Section 4.3. One hour re resistance
is required: internal environment. The ribs are 150 mm wide @ 900
mm centres. Links are required in span to facilitate prefabrication of
reinforcement. Assume that partitions are liable to be damaged by
excessive deections. In order to reduce deformations yet maintain a
shallow prole use fck = 35 MPa and fyk = 500 MPa.
gk = 4.17 kN/m2
gk = 4.3 kN/m2
qk = 5.0 kN/m2
A

7500
550

1000

9000
1000

1000

7500
1000

550

Figure 3.8 Continuous ribbed slab example


p
Notes on ribbed slab design
There are various established methods for analysing ribbed slabs and dealing
with the solid areas:
t Using UDLs simplifies the analysis and remains popular. One method is
to ignore the weight of the solid part of the slab in the analysis of the
ribbed slab. (The weight of the solid area is then added to the loads on the
supporting beam). This ignores the minor effect the solid areas have on
bending in the ribbed slab.
t Alternatively the weight of the solid part of the slab is spread as a UDL
over the whole span. This is conservative both in terms of moment and
shears at solid/shear interfaces but underestimates hogging in internal
spans.
t The advent of computer analysis has made analysis using patch loads
more viable and the resulting analysis more accurate.
t The ribbed part of the slab may be designed to span between solid areas.
(The ribs span d/2 into the solid areas, which are assumed to act as
beams in the orthogonal direction.) However, having to accommodate
torsions induced in supporting beams and columns usually makes it simpler
to design from centreline of support to centreline of support.
t Analysis programs can cope with the change of section and therefore
change of stiffness along the length of the slab. Moments would be
attracted to the stiffer, solid parts at supports. However, the difference in
stiffness between the ribbed and the solid parts is generally ignored.
52

CCIP 041
1
Oct 09

,',3<hgmbgnhnlkb[[^]leZ[

In line with good practice analysis, this example is carried out using
centreline of support to centreline of support and patch loads.
Constant stiffness along the length of the slab has been assumed.
CL

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

CL
A

100
300

A
200

550

1000

200

Figure 3.9 Long section through slab

150

750

150

Figure 3.10 Section AA: section through ribbed slab

3.3.1 Actions
Permanent: UDL kN/m2
Self-weight:
kN/m2
Rib
0.15 0.2 25/0.9
= 0.833
Slope
2 (1/2) 0.2/10 0.2 25/0.9 = 0.112
Slab
0.1 2.5
= 2.500
Cross rib 0.19 0.71 0.2 25/(0.9 7.5) = 0.100
Total self-weight
= 3.545
Ceiling
Services
Raised oor
Total permanent actions
gk

=
=
=

3.55
0.15
0.30
0.30

= 4.30

In this case, assuming the patch load analysis is accurate, taking the weight
of solid area to be spread over the whole span would overestimate span and
support moments by 68% and shears at the solid/rib interface by 89%.
Ignoring the weight of the solid area in the analysis of this ribbed slab would
lead to underestimates of span moments by 1%, support moments by 3% and
no difference in the estimation of shear at the solid shear interface. The latter
may be the preferred option.
53

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Permanent: patch load


Extra over solid in beam area as patch load
(0.2 25 0.833) = 4.167
Variable
Imposed
Allowance for partitions
Total variable action

gk 4.17
= 4.00*
= 1.00*
gk = 5.00

3.3.2 Cover
Nominal cover, cnom:
cnom = cmin + Dcdev
where
cmin = max(cmin,b ; cmin,dur)
where
cmin,b = minimum cover due to bond
= diameter of bar.
Assume 20 mm main bars and 8 mm links
cmin,dur = minimum cover due to environmental conditions.
Assuming XC1 and C30/37 concrete, cmin,durr = 15 mm
Dcdev = allowance in design for deviation. Assuming no
measurement of cover Dcdev = 10 mm
= cnom

Exp. (4.1)

Cl. 4.4.1.2(3)

Table 4.1.
BS 8500-1:
Table A4
Cl. 4.4.1.2(3)

= 20 + 10 to main bars or
= 15 + 10 to links = critical

Fire:
Check adequacy of section for REI 60.

EC2-1-2: 5.7.5(1)

Minimum slab thickness, hs = 80 mm OK

EC2-1-2: Table 5.8

Axis distance required


Minimum rib width
or

bmin = 120 mm with a = 25 mm


bmin = 200 mm with a = 12 mm

EC2-1-2: Table 5.6

= at 150 mm wide (min.) a = 20 mm


By inspection, not critical.
Use 25 mm nominal cover to links

3.3.3 Load combination and arrangement


Ultimate load, n:
By inspection, Exp. (6.10b) is critical
nslab
= 1.25 4.30 + 1.5 5.0 = 13.38 kN/m2
nsolid areas = 1.25 (4.30 + 4.17) + 1.5 5.0 = 18.59 kN/m2

*Client requirements. See also BS EN 199111, Tables 6.1, 6.2, Cl. 6.3.2.1(8) & NA.
54

Fig. 2.5
EC0: Exp. (6.10b)

,',3<hgmbgnhnlkb[[^]leZ[

Arrangement:
Choose to use all-and-alternate-spans-loaded.

Cl. 5.1.3(1) & NA


option b

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

3.3.4 Analysis
Analysis by computer, includes 15% redistribution at support and
none in the span.
90.7 kNm/m

100

EC0: A1.2.2
& NA, 5.3.1 (6)

90.7 kNm/m

80
60
40
20
0
20

40
60
65.3 kNm/m

80

61.1 kNm/m

65.3 kNm/m

a) Elastic moments
100

77.1 kNm/m

80

77.1 kNm/m

60
40
20
0
20

40
60
80

61.7 kNm/m

55.9 kNm/m

61.7 kNm/m

b) Redistributed envelope

Figure 3.11 Bending moment diagrams

Note 1: A ribbed slab need not be treated as discrete elements provided


rib spacing 1500 mm, depth of the rib 4 its width, the ange is > 0.1
distance between ribs and transverse ribs are provided at a clear spacing not
exceeding 10 overall depth of the slab.

Note 2: As 7.5 m < 85% of 9.0 m, coefcients presented in Concise Eurocode 2[5]
are not applicable.
55

80
42.5 kN/m

63.2 kN/m

63.5 kN/m

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

40
0
A

40
63.5 kN/m

80

63.2 kN/m

42.5 kN/m

At solid/rib interface:
AB @ 550 mm from A
= 20.4 kNm/m z 18.3 kNm/rib
MEd (sagging)
VEd
= 32.5 kN/m z 29.3 kN/rib
BA @1000 mm from B
= 47.1 kNm/m z 42.4 kNm/rib
MEd (hogging)
= 45.4 kN/m z 40.9 kN/rib
VEd
BC @ 1000 mm from B
= 43.0 kNm/m z 38.7 kNm/rib
MEd (hogging)
= 45.1 kN/m z 40.6 kN/rib
VEd
Symmetrical about centreline of BC.

3.3.5 Flexural design, span AB


a) Span AB: Flexure
MEd = 61.7 kNm/m
= 55.5 kNm/rib
K = MEd/bd 2fck
where
b = 900 mm
d = 300 25 8 20/2 = 257
assuming 8 mm link at H20 in span
fck = 35 MPa
=K = 55.5 106/(900 2572 35) = 0.027
K' = 0.207
or restricting x/d to 0.45
K' = 0.168
K K' = section under-reinforced and no compression
reinforcement required.

56

Appendix A1

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

,',3<hgmbgnhnlkb[[^]leZ[

z = (d/2) [1 + (1 3.53K)0.5] 0.95d


= (257/2) (1 + 0.951) 0.95 257
= 251 244 = z = 244 mm
But z = d 0.4x
= x = 2.5(d z) = 2.5(257 244) = 33 mm
= By inspection, neutral axis is in ange
As = MEd/fydz
where
_r] = 500/1.15 = 434.8 MPa
= 55.5 106/(434.8 244) = 523 mm2/rib
Try 2 no. H20/rib (628 mm2/rib)
b) Span AB: Deflection
Allowable l/d = N K F1 F2 F3
where

Appendix A1

Appendix A1

Appendix C7

N = Basic l/d: check whether r > r0 and whether to use


Exp. (7.16a) or Exp. (7.16b)

Cl. 7.4.2(2)

r0 = fck0.5/1000 = 350.5/1000 = 0.59%


r = As/Ac = As,req/[bwd + (beff bw)hf]
where

PD 6687[6]

bw = min. width between tension and compression


chords. At bottom assuming 1/10 slope to rib:
= 150 + 2 (25 + 8 + 20/2)/10
= 159 mm
r = 523/(159 ( 257 + (900 159) 100)
= 523/114963
= 0.45%

r < r0 = use Exp. (7.16a)

N = 11 + 1.5fck0.5r /r0 + 3.2fck0.5(r /r0 1)1.5]

Exp. (7.16a)

= 11 + 1.5 350.5 0.055/0.045 + 3.2 350.5


(0.055/0.045 1)1.5
= [11 + 10.8 + 2.0] = 22.8
K = (end span) 1.3

F1 = (beff /bw = 5.66) 0.8


F2 = 7.0/leff = 7.0/7.5 = (span > 7.0 m) 0.93
F3 = 310/ ss 1.5

Table 7.4N &


NA, Table NA.5:
Note 5
Cl. 7.4.2(2)
Cl. 7.4.2, Exp. (7.17)
& NA; Table NA.5

Section 2.18 of PD 6687 [6] suggests that r in T-beams should be based on


the area of concrete above the centroid of the tension steel.

57

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
ss = (fyk/gS) (As,req/As,prov) (SLS loads/ULS loads) (1/d)
= 434.8(523/628) [ (4.30 + 0.3 5.0)/13.38]
(65.3/61.7)
= 434.8 0.83 0.43 1.06
= 164 MPa
F3 = 310/ss
= 310/164 = 1.89# but 1.5, therefore say 1.50
= Permissible l/d = 22.8 1.3 0.8 0.93 1.50 = 33.0
= OK
Actual l/d = 7500/257 = 29.2
Use 2 no. H20/rib (628 mm2/rib)
c) Support A (and D): flexure (sagging) at solid/rib interface
Reinforcement at solid/rib interface needs to be designed for both
moment and for additional tensile force due to shear (shift rule)
MEd,max = 18.3 kNm/rib
VEd,max = 29.3 kNm/rib
At solid/rib interface
As = MEd/fydz + DFtd /fyd
where
z = (d/2) [1 + (1 3.53K)0.5] 0.95d
where
K = MEd/bd2fck
where
b = 900 mm
d = 300 25 8 25 20/2 = 232
assuming 8 mm links and H25B in edge beam
fck = 30
= 18.3 106/(900 2322 35) = 0.011

See

Appendix B1.5

In analysis, 15% redistribution of support moments led to redistribution of span


moments:
d = 61.7/65.3 = 0.94.
#

Both As,prov/As,req and any adjustment to N obtained from Exp. (7.16a) or Exp.
(7.16b) is restricted to 1.5 by Note 5 to Table NA.5 in the UK NA. Therefore, 310/
ss is restricted to 1.5.

58

Cl. 9.2.1.3.(2)

Cl. 9.2.1.3.(2),
Fig. 9.2

,',3<hgmbgnhnlkb[[^]leZ[

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

25 cover
12 fabric
8 link
16 bar

16 bar
25 bar
8 link
25 cover

20 bar
8 link
25 cover

=z=
=
fyd =
DFtd =

(232/2) (1 + 0.980) 0.95 232


230 220 = z = 220 mm
434.8 MPa
0.5VEd (cot y cot a)

where
y = angle between the concrete compression strut and the
beam axis. Assume cot y = 2.5 (as a maximum)
a = angle between shear reinforcement and the beam axis.
For vertical links, cot a = 0
DFtd = 1.25VEd = 1.25 29.3 = 36.6 kN
As = 18.3 106/(434.8 220) + 36.6 103/434.8
= 191 + 84 mm2 = 275 mm2
=Try 1 no. H20 B in end supports*

Appendix A1

Cl. 6.2.3(7),
Exp. (6.18)
Cl. 6.2.3(1)
Appendix A2
Appendix C,
Table C6
Cl. 6.2.3(1)

d) Support B (and C) (at centreline of support)


MEd = 77.1 kNm/m
= 69.4 kNm/rib
K = MEd/bd2fck
where
d = 300 25 cover 12 fabric 8 link 20/2
= 245
K = 69.4 106/(900 2452 35) = 0.037
By inspection, K K'
z = (245/2) [1 + (1 3.53 K)0.5] 095d
= (245/2) (1 + 0.932) < 0.95d
= 237 mm
As = MEd/fydz
= 69.4 106/434.8 237 = 673 mm2/rib

* An alternative method would have been to calculate the reinforcement required


to resist MEd at the shift distance, al, from the interface.
59

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

e) Support B (and C): exure (hogging) at solid/rib interface


Reinforcement at solid/rib interface needs to be designed for both
moment and for additional tensile force due to shear (shift rule).
MEd,max = 42.4 kNm/rib max.
VEd,max = 40.9 kNm/rib max.
As = MEd/fydz + DFtd/fyd
where
z = (245/2) [1 + (1 3.53 K)0.5] 095d
where
K = MEd/bd2fck
= 42.4 106/(150 2452 35)
= 0.135
Check K K'
K' = 0.168 for d = 0.85 (i.e. 15% redistribution)
= Section under-reinforced: no compression reinforcement required
= z = (245/2) (1 + 0.723) 232 = 211 mm
fyd = 434.8 MPa
DFtd = 0.5VEd (cot y cot a)
where
y = angle between the concrete compression strut and the
beam axis. Assume cot y = 2.5 (as a maximum)
a = angle between shear reinforcement and the beam axis. For
vertical links, cot a = 0
DFtd = 1.25VEd = 1.25 40.9 = 51.1 kN
As
= 42.4 106/(434.8 211) + 51.1 103/434.8
= 462 + 117 mm2 = 579 mm2/rib
To be spread over beff where by inspection, beff = 900.
=Centre of support more critical (679 mm2/rib required).
Top steel may be spread across beff where
beff = bw + beff1 + beff2 b
= bw + 2 0.1 0.15 (l1 + l2)
= 150 + 0.03 (7500 + 9000) 900
= 645 mm
= Use 2 no. H16 above rib and 3 no. H12 between (741 mm2/rib)
where 2 no. H16 and 2 no. H12 are within beff

3.3.6 Flexural design, span BC


a) Span BC: Flexure
MEd = 55.9 kNm/m
= 50.3 kNm/rib

60

Cl. 9.2.1.3.(2)

Cl. 9.2.1.3.(2)

Appendix C,
Table C4
Appendix A

Cl. 6.2.3(7),
Exp. (6.18)
Cl. 6.2.3(1)
Appendix A2;
Table C6
Cl. 6.2.3(1)

Cl. 9.2.1.2(2)
Cl. 5.3.2.1(3)
Cl. 9.2.1.2(2),
5.3.2

,',3<hgmbgnhnlkb[[^]leZ[

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

= MEd/bd2fck
= 50.3 106/900 2572 35
= 0.02 i.e. K (as before K = 0.168)

By inspection,
z = 0.95d = 0.95 257 = 244 mm
By inspection, neutral axis is in ange.
As = MEd/fydz
= 50.3 106/434.8 244 = 474 mm2
Try 2 no. H20/rib (628 mm2/rib)
b) Span BC: Deflection
Allowable l/d = N K F1 F2 F3
where
N = Basic l/d

Section C7
Cl. 7.4.2(2)

r = 474/(159 ( 257 + (900 159) 100)


= 474/114963
= 0.41%
r0 = 0.59% (for fck = 30)
= r < r0 use Exp. (7.16a)
N = 11 + 1.5 fck0.5 r0/r + 3.2fck0.5 (r0/r 1)1.5
= 11 + 1.5

350.5

0.055/0.041 + 3.2

350.5

Exp. (7.16a)
(0.055/0.041

1)1.5

= 11 + 11.9 + 3.8 = 26.7


K = (internal span) 1.5
F1 = (beff/bw = 6.0) 0.8

Table 7.4N, &


NA, Table NA.5:
Note 5
Cl. 7.4.2(2)
Cl. 7.4.2,
Exp. (7.17)
& NA: Table NA.5

F2 = 7.0/leff = 7.0/9.0 = (span > 7.0 m) 0.77


F3 = 310/sS 1.5
where
ss = (fyk /gS) (As,req/As,prov) (SLS loads/ULS loads) (1/d)
= 434.8 (474/628) [(4.30 + 0.3 5.0)/13.38](61.1/55.9)
= 434.8 0.75 0.43 1.09
= 153 MPa
F3 = 310/ ss

NA, Table NA.5:


Note 5

= 310/153 = 2.03 therefore, say = 1.50


= Permissible l/d = 26.8 1.5 0.8 0.77 1.50 = 37.1
= OK

Actual l/d = 9000/257 = 35

=Use 2 H20/rib (628 mm2/rib)

Both A
s,prov/As,req and any adjustment to N obtained from Exp. (7.16a) or
Exp. (7.16b) is restricted to 1.5 by Note 5 to Table NA.5 in the UK NA.

61

3.3.7 Design for shear

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

CL

CL

10
1
b = 150

a) Support A (and D) at solid/rib interface


Shear at solid/rib interface = 29.3 kN/rib
Taking solid area as the support, at d from face of support
VEd = 29.3 0.232 0.90 13.38 = 26.5 kN/rib

Cl. 6.2.1(8)
Cl. 6.2.2(1) & NA

Resistance
VRd,c = (0.18/gC)k (100 rl fck)0.333 bwd
where
gC = 1.5
k = 1 + (200/d)0.5 2
= 1 + (200/257)0.5
= 1.88
rl = Asl/bwd
where
Asl = assume only 1 H20 anchored = 314 mm2
bw = min. width between tension and compression chords.
At bottom assuming 1/10 slope to rib:
= 150 + 2 (25 + 8 + 20/2)/10
= 159 mm
d = 257 mm as before
rl = 314/(159 257) = 0.0077
fck = 35
=VRd,c = (0.18/1.5) 1.88 (100 0.0077 35)0.333 159 257
= 0.68 159 257 = 27.8 kN/rib
= No shear links required.
But use nominal links to allow prefabrication.
b) Support B (and C) at solid/rib interface
Shear at solid/rib interface = 40.9 kN/rib [max(BA; BC)]
At d from face of support
VEd = 40.9 0.245 13.38 0.9 = 37.9 kN/rib

62

Cl. 6.2.1(5)

Cl. 6.2.1(8)

,',3<hgmbgnhnlkb[[^]leZ[

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Resistance:
VRd,c = (0.18/ gC)k (100 rl fck)0.333 bwd

Cl. 6.2.2(1) & NA

where
gC = 1.5
k = 1 + (200/d)0.5 2
= 1 + (200/245)0.5
= 1.90
rl = Asl/bwd
where
Asl = 2 H16 = 402 mm2
bw = 159 mm as before
d = 245 mm as before
rl = 0.0103
fck = 35 MPa
= VRd,c = (0.18/1.5) 1.9 (100 0.0103 35)0.333 159 245
= 0.75 159 245 = 29.2 kN/rib
= Shear links required.
Shear links required for a distance:
(37.9 29.2)/(13.38 0.9) + 245 = 722 + 245 = 967 mm
from interface.
Check shear capacity:
VRd,max = acw bw zvfcd/(cot y + tan y)
where
acw = 1.0
bw = 159 mm as before
z = 0.9d
v = 0.6 (1 fck/250) = 0.528
fcd = 35/1.5 = 23.3 MPa
y = angle of inclination of strut.
Rearranging formula above:
(cot y + tan y) = acwbwzvfcd/VEd
= (1.0 159 0.9 245 0.528 23.3)
41.6 103
= 10.4
By inspection, cot1y << 21.8. But cot y restricted to 2.5 and
= tan y = 0.4.
VRd,max = 1.0 159 0.9 245 0.528 20/(2.5 + 0.4) = 127.6 kN
= OK

Exp. (6.9) & NA

Cl. 6.2.3(2) & NA

63

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Shear links: shear resistance with links


VRd,s = (Asw/s) z fywd cot y VRd,max
where
Asw/s = area of legs of links/link spacing
z
= 0.9d as before
fywd = 500/1.15 = 434.8
cot y = 2.5 as before
= for VEd VRd,s
Asw/s VEd/z fywd cot y
37.9 103/(0.9 245 434.8 2.5) 0.158
Maximum spacing of links = 0.75d = 183 mm
= Use H8 @ 175 cc in 2 legs (Asw /s = 0.57) for min. 967 mm into rib

Exp. (6.8)

Cl. 9.2.2(6)

3.3.8 Indirect supports


As the ribs of the slab are not supported at the top of the
supporting beam sections (A, B, C, D), additional vertical
reinforcement should be provided in these supporting beams and
designed to resist the reactions. This additional reinforcement
should consist of links within the supporting beams (see Beams
design, Section 4.3.9).
Support A (and D) at solid/rib interface:
VEd = 26.5 kN/rib
As,req = 26.3 1000/(500/1.15) = 60 mm2
This area is required in links within h/6 = 300/6 = 50 mm of the
ribbed/solid interface and within h/2 = 300/2 = 150 mm of the
centreline of the rib.

Cl. 9.2.5, Fig. 9.7

Fig. 9.7

Support B (and C) at solid/rib interface:


VEd = 37.9 kN/rib
As,req = 37.9 1000/(500/1.15) = 87 mm2 placed similarly

3.3.9 Other checks


Check shear between web and ange
By inspection, VEd 0.4 fct,d = OK

64

Cl. 6.4.2 (6) & NA

,',3<hgmbgnhnlkb[[^]leZ[

3.3.10 Summary of design


2H16 + 3H12/rib

2H16 + 3H12/rib

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

H8 links in 2 legs
@ 175cc
A
550

2H20/rib

2H20/rib

1050 1000 1000 1050


7500

2H20/rib

1050 1000 1000 1050

9000

D
550

7500

fck = 35 MPa
cnom = 25 mm

Figure 3.15 Summary of design


Commentary
It is usually presumed that the detailer would take the above
design and detail the slab to normal best practice. As stated
in Section 3.2.9, the detailers responsibilities, standards and
timescales should be clearly dened but it would be usual for the
detailer to draw and schedule not only the designed reinforcement
but all the reinforcement required to provide a buildable solution.
The work would usually include checking the following aspects and
providing appropriate detailing:
t Minimum areas
t Curtailment lengths
t Anchorages
t Laps
t U-bars
t Rationalisation
t Details and sections
The determination of minimum reinforcement areas, curtailment
lengths and laps using the principles in Eurocode 2 is shown in
detail in the following calculations. In practice these would be
determined from published tables of data or by using reference
texts [12, 21]. Nonetheless the designer should check the drawing
for design intent and compliance with standards. It is therefore
necessary for the designer to understand and agree the principles
of the details used.

3.3.11 Detailing checks


a) Minimum areas
i) Minimum area of reinforcement in ange
As,min = 0.26 (fctm/fyk) btd 0.0013 btd

Cl. 9.3.1.1

65

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
bt = width of tension zone
fctm = 0.30 fck0.666

Cl. 9.2.1.1,
Exp. (9.1N)
Table 3.1

As,min = 0.26 0.30 350.666 1000 100/500 = 166 mm2/m


(r = 0.17%)
= Use A142 in ange (say OK)

BS 8666[19]

ii) Secondary reinforcement


Not applicable.
iii) Maximum spacing of bars
Maximum spacing of bars < 3 h < 400 mm
By inspection.

OK

iv) Crack control


Loading is the main cause of cracking = use Table 7.2N or Table 7.3N for
wmax = 0.3 mm and max. ss = 200 MPa (see deection check)
Max. bar size = 25 mm
or max. spacing = 250 mm
OK by inspection
v) Effects of partial xity
Assuming partial xity exists at end supports, 15% of As is required
to extend 0.2 the length of the adjacent span.
As,req = 15% 525 = 79 mm2/rib
For the rib in tension:
As,min = 0.26 0.30 300.666 159 257/500 = 55 mm2/rib

Cl. 9.3.1.1.(3)
Cl. 7.3.3(2)
Cl. 7.3.1.5
Table 7.2N
Table 7.3N

Cl. 9.3.1.2(2)

b) Curtailment
Wherever possible simplied methods of curtailing reinforcement
would be used. The following is intended to show how a rigorous
assessment of curtailment of reinforcement might be undertaken.

66

i) End support A: bottom steel at support


Check anchorage.
As simply supported, 25% of As should be anchored in support.
25% 595 = 148 mm2
Use 1 no. H20/rib (314 mm2/rib)

Cl. 9.3.1.1(4),
9.3.1.2(1) &
Note,
Cl. 9.2.1.4(1)
& NA

ii) Check anchorage length


Envelope of tensile force:
To resist envelope of tensile force, provide reinforcement to al or lbd
beyond centreline of support.
For members without shear reinforcement, al = d = 232
By inspection, ssd = 0, lbd = lbd,min = max(10f, 100 mm)

Cl. 9.3.1.1(4),
9.2.1.3(1),
Cl. 9.2.1.3(2),
9.2.1.3(3), Fig. 9.2
Cl. 9.2.1.3

iii) Indirect support


As anchorage may be measured from face of indirect support, check
force to be resisted at solid/rib interface:
Fs = MEd/z + FE

Cl. 9.3.1.1(4),
9.2.1.4(2),
9.2.1.4(3),
Fig. 9.3b

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

,',3<hgmbgnhnlkb[[^]leZ[

where
MEd = 18.3 kNm/rib
z
= 220 as before
FE = VEd al/z
where
VEd = 29.3 kN/rib
al
= z cot y/2

= FE = VEd cot y/2
= 29.3 1.25 = 36.6 kN/rib
Fs = 18.6 106/(220 103) + 36.6 = 121.1 kN
iv) Anchorage length:
lbd = alb,rqd lb,min
where
a = conservatively 1.0
lb,rqd = (f/4) (ssd/fbd)
where
f = 20
ssd = design stress in the bar at the ULS
= 121.1 1000/314 = 385 MPa
fbd = ultimate bond stress
= 2.25 n1 n1 fct,d
where
n1 = 1.0 for good bond conditions
n2 = 1.0 for bar diameter 32 mm
fct,d = act fct,k/gC
= 1.0 2.2/1.5
= 1.47 MPa
fbd = 2.25 1.47 = 3.31 MPa
= lb,rqd = (20/4) (385/3.31) = 581 mm
lb,min = max[10f; 100 mm] = 200 mm
 = lbd = 581 mm measured from solid/rib intersection.
i.e. 31 mm beyond centreline of support.
v) End support A: top steel
Assuming partial xity exists at end supports, 15% of As is required
to extend at least 0.2 the length of the adjacent span.
As,req = 15% 525 = 79 mm2/rib
As,min = 0.26 0.30 350.666 159 257/500 = 68 mm2/rib
Use 2 no. H12 T1/rib in rib and 2 no. H10 T1/rib between ribs
(383 mm2/rib)

Exp. (9.3)
Cl. 9.2.1.3,
Exp. (9.2)

Cl. 8.4.4,
Exp. (8.4)
Exp. (8.3)

Cl. 8.4.2(2)

Cl. 3.1.6(2),
Tables 3.1,
2.1 & NA
Fig. 9.3

Cl. 9.3.1.2(2)

Cl. 9.3.1.1
Cl. 9.2.1.1(1),
Exp. (9.1N)

Whilst this would comply with the requirements of Eurocode 2, it is common practice

to take bottom bars 0.5 a tension lap beyond the centreline of support
(= 250 mm beyond the centreline of support; see model detail MS1 in SMDSC[9]).
It is usual to curtail 50% of the required reinforcement at 0.2l and to curtail the

remaining 50% at 0.3l or line of zero moment (see model detail MS2 in SMDSC[9]).

67

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

vi) Support B (and C): top steel


At the centreline of support (2 no. H16 T + 3 no. H12 T)/rib are
required. The intention is to curtail in two stages, rstly to 2 no.
H16 T/rib then to 2 no. H12 T/rib.
Curtailment of 2 no. H16 T/rib at support
(capacity of 2 no. H12 T/rib + shift rule):
Assume use of 2 no. H12 T throughout in midspan:
Assuming z = 211 mm as before,
MR2H12T = 2 113 434.8 211
= 20.7 kNm/rib (23.0 kNm/m)
(Note: section remains under-reinforced)
From analysis MEd = 23.0 kNm/m occurs at 2250 mm (towards A)
and 2575 mm (towards B).
Shift rule: al = z cot y/2
Assuming z = 211 mm as before
al = 1.25 211 = 264 mm
= 2 no. H12 T are adequate from 2250 + 264 = 2513 mm from B
towards A and 2575 + 263 = 2838 mm from B towards C.
= Curtail 2 no. H16 T @ say 2600 from BA and 2850 from BC
Curtailment of 3 no. H12 T/rib at support (capacity of 2 no. H16
T/rib + shift rule):
MR2H16T = 2 201 434.8 211
= 36.9 kNm/rib (41.0 kNm/m)
(Note: section remains under-reinforced)
From analysis MEd = 41.0 kNm/m occurs at 1310 mm (towards A)
and 1180 mm
(towards C).
Shift rule: al = 263 mm as before
= 2 no. H16 T are adequate from 1310 + 263 = 1573 mm from B
towards A and 1180 + 263 = 1443 mm from B towards C.
= Curtail 3 no. H12 at say 1600 from B (or C).
(See Figure 3.16)

68

vii) Support B (and C): bottom steel at support


At the support 25% of span steel required
0.25 628 = 157 mm2
Try 1 no. H16 B/rib (201)

Cl. 9.3.1.1(4),
9.2.1.5(1),
9.2.1.4(1)

This reinforcement may be anchored into indirect support or carried


through.

Fig. 9.4

,',3<hgmbgnhnlkb[[^]leZ[

a1 = 264

2H16 + 3H12
per rib

MEd = 77.1 x 0.9 = 60.4 kNm/rib


Shift moment

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

MR = As(fyk/gS)z
lbd

2H16/rib

MEd
MEd = 36.79 kNm/rib

2H12/rib
MEd = 20.7 kNm/rib
A

B
264 1310

1180 264

2250

2575

264

264
a) Design moments and moment resistance
2H12

3H12

2H12

2H16
1600
2600

1600
2850

b) Curtailment of reinforcement

viii) Support B (and C): bottom steel curtailment BA and BC


To suit prefabrication 2 no. H20/rib will be curtailed at solid/rib
interface, 1000 mm from BA (B towards A) and BC.
From analysis, at solid/rib interface sagging moment = 0.
From analysis, at a1 from solid/rib interface, i.e. at 1000 + 1.25 244
= 1303 mm
at 1305 mm from BA sagging moment = say 5 kNm/rib
at 1305 mm from BC sagging moment = 0
Use 1 no. H16 B/rib (201)
c) Laps
At AB, check lap 1 no. H20 B to 2 no. H20 B in rib full tension lap:
l0 = a1 a6 lb,rqd > l0,min
where
a1 = 1.0 (cd = 45 mm, i.e. < 3f)
a6 = 1.5 (as > 50% being lapped)
lb,rqd = (f/4) (ssd/fbd)

Exp. (8.10)
Table 8.2

where
f = 20
ssd = 434.8
fbd = 3.0 MPa as before
69

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

l0,min = max. 10f or 100 = 200


l0 = 1.0 1.5 (20/4) 434.8/3.0
= 1087 mm, say = 1200 mm
At BA and BC, check lap 2 no. H12 T to 2 no. H16 T in rib full tension lap:
l0 = a1 a6 lb,rqd > l0,min
where
a1
= 0.7 (cd = 45 mm, i.e. > 3f)
a6 = 1.5 (as > 50% being lapped)
lb,rqd = (f/4) (ssd/fbd)

Exp. (8.10)

where
f = 20
ssd = 434.8
fbd = 2.1 (3.0 MPa as before but n1 = 0.7 for not good bond
conditions)
l0,min = max. 10f or 100 = 120

Cl. 8.4.2

l0 = 0.7 1.5 (12/4) 434.8/2.1


= 651 mm, say = 700 mm
But to aid prefabrication take to solid/rib intersection 1000 mm
from centre of support.
At BA and BC, check lap 1 no. H16 B to 2 no. H20 B in rib:
By inspection, nominal say, 500 mm

Exp. (8.6)
SMDSC[9]

Table 8.2

SMDSC[9]

SMDSC[9]

d) RC detail of ribbed slab


Links not shown for clarity. Cover 25 mm to links.

600
600
1000 1000 1000 1250

200 200 1500


2H12T in rib
and 2H1OT
between

2H12T

2H20B/rib

150 550 1200

2H16 + 3H12/rib
A143
fabric
2H12T/rib

2H16 + 3H12/rib

2H12 2H12 + 2H1O 2H16 3H12 2H12

1H20B

600
1250 1000

2H16 3H12 2H12

2H12 3H12 2H16

1H16B/rib

2H20B/rib

500 1000 1000 500


7500

1H16B/rib
500 1000 1000

9000

Figure 3.17 Curtailment of flexural reinforcement in ribbed slab

70

,',3<hgmbgnhnlkb[[^]leZ[
3.4 Flat slab

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Mabl^qZfie^bl_hkma^]^lb`gh_Zk^bg_hk\^]\hg\k^m^_eZmleZ[pbmahnm\henfga^Z]l'Ma^leZ[
bliZkmh_ZeZk`^k_ehhkieZm^Zg]blmZd^g_khf@nb]^mhma^]^lb`gZg]\hglmkn\mbhgh_k^bg_hk\^]
\hg\k^m^_eZmleZ[lT+0V%pa^k^_bgbm^^e^f^gmZgZerlblZg]]^lb`gmh>nkh\h]^+blbeenlmkZm^]':l
pbmama^@nb]^%`kb]ebg^<pbee[^]^lb`g^][nm%_hkma^lZd^h_beenlmkZmbhg%\h^__b\b^gmlpbee[^
nl^]mh^lmZ[ebla]^lb`gfhf^gmlZg]la^Zklbgmabl\kbmb\ZeZk^Zh_ma^leZ['
Ikhc^\m]^mZbel

<Ze\neZm^][r

chg

Ch[gh'

Flat slab

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP 041
1
Oct 09

The slab is for an ofce where the specied load is 1.0 kN/m2 for
nishes and 4.0 kN/m2 imposed (no partitions). Perimeter load is
assumed to be 10 kN/m. Concrete is C30/37. The slab is 300 mm
thick and columns are 400 mm square. The oor slabs are at 4.50 m
vertical centres. A 2 hour re rating is required.
A

4.0

4.0

Bb

4.0

6.0

D
E

1
200 x 200
hole
8.0

8.0

9.6
300 mm flat slabs
All columns 400 mm sq.

8.6

200 x 200
hole

Figure 3.18 Part p


plan of flat slab

3.4.1 Actions

kN/m2

Permanent:
Self-weight 0.30 25
Finishes
Total
Variable:
Offices

= 7.5
= 1.0
gk = 8.5

EC1-1-1:
Table A1

jk = 4.0

Client requirement. See also BS EN 199111, Tables 6.1, 6.2, Cl. 6.3.2.1(8) & NA.
71

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

3.4.2 Cover
cnom:
cnom = cmin + Dcdev

Exp. (4.1)

where
cmin = max[cmin,b ; cmin,dur; 10 mm]

Cl. 4.4.1.2(3)

where
cmin,b = 20 mm, assuming 20 mm diameter reinforcement
cmin,dur = 15 mm for XC1 and using C30/37
Dcdev = 10 mm
Fire:
For 2 hours resistance, amin = 35 mm = not critical
= cnom = 20 + 10 = 30 mm

Table 4.1.
BS 8500-1:
Table A4.
EC2-1-2:
Table 5.9

3.4.3 Load combination and arrangement


qk = 4.0 kN/m2
gk = 8.5 kN/m2
1

9600

8600

Figure 3.19 Panel centred on grid C


Ultimate load, n:
By inspection, Exp. (6.10b) is critical.
n = 1.25 8.50 + 1.5 4.0 = 16.6 kN/m2
Arrangement:
Choose to use all-and-alternate-spans-loaded load cases and
coefcients.

Fig. 2.5
EC0: Exp. (6.10b)

Cl. 5.1.3(1) & NA:


Table NA.1
(option b)

3.4.4 Analysis grid line C


Consider grid line C as a bay 6.0 m wide. (This may be conservative
for grid line C but is correct for grid line D etc.)
MEd
Effective spans:
9600 2 400/2 + 2 300/2 = 9500 mm
8600 2 400/2 + 2 300/2 = 8500 mm
Check applicability of moment coefcients:
8500/9500 = 0.89 = as spans differ by less than 15% of larger
span, coefcients are applicable.

Tables C2 & C3

The

Cl. 5.3.1 & NA

all-spans-loaded case with 20% redistribution of support moments would


also have been acceptable but would have involved some analysis. The use of Table
5.9 in BS EN 199212 (Fire resistance of solid at slabs) is restricted to where
redistribution does not exceed 15%; the coefcients presume 15% redistribution
at supports.
72

Cl. 5.3.2.2(1)

Table C3

,'-3?eZmleZ[

As two span, use table applicable to beams and slabs noting


increased coefcients for central support moment and shear.

Table C3

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Design moments in bay.


Spans:
MEd = (1.25 8.5 0.090 + 1.5 4.0 0.100) 6.0 9.52 = 842.7 kNm
Support:
MEd = 16.6 0.106 6.0 9.52 = 952.8 kNm
D

6000
1

1500 Column
strip

Middle
strip

1500

Column
1500 strip

1500 1500 3000 1500 1500


Column strip Middle strip Column strip

Figure 3.20 Column and middle strips


p
Apportionment of moments between column strips and middle strips:
Apportionment (as %)
Column strip
ve (hogging) Long span = 70%
Short span = 75%
+ve (sagging) 50%

Middle strip
Long span = 30%
Short span = 25%
50%

Parallel to grid C, column strip is ly/2 = 3 m wide. The middle strip is


also 3 m wide.

Table I.1;
CS Flat slab
guide[27]
Table I.1
NA.3[1a]; Fig. I.1

Long span moments:


MEd
Column strip, 3 m wide
Middle strip, 3 m wide
ve (hogging) 0.70 952.8/3.0 = 222.3 kNm/m 0.30 952.8/3.0 = 95.3 kNm/m
+ve (sagging) 0.50 842.7/3.0 = 140.5 kNm/m 0. 50 842.7/3.0 = 140.5 kNm/m

The Concrete Societys TR 64[27] recommends a percentage, k1, based on ly /lz


Assuming ly /lz = 1.5 the distribution of moments in the long span between column
strips and middle strips is given as 70% and 30%.
73

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Punching shear force, VEd:


At C2,
VEd = 16.6 6.0 9.6 0.63 2 = 1204.8 kN
At C1 (and C3)
VEd = 16.6 6.0 9.6 0.45 + (10 + 0.2 0.3 25) 1.25 6.0
= 516.5 kN

Table C3
Table C3

3.4.5 Design grid line C


Effective depth, d:
d = 300 30 20/2 = 260 mm
a) Flexure: column strip and middle strip, sagging
MEd = 140.5 kNm/m
K = MEd/bd2fck = 140.5 106/(1000 2602 30) = 0.069
z d = 0.94
z/
z = 0.94 260 = 244 mm
As = MEd/ffyd z = 140.5 106/(244 500/1.15) = 1324 mm2/m
(r
r = 0.51%)
Try H20 @ 200 B1 (1570 mm2/m)
b) Deection: column strip and middle strip
Check span-to-effective-depth ratio.
Allowable l/
l d = N K F1 F2 F3
where
N = 20.3 (r = 0.51%, fck = 30)
K = 1.2 (at slab)
F1 = 1.0 (beff/bbw = 1.0)
F2 = 1.0 (no brittle partitions)#
F3 = 310/s
ss 1.5
where*
ss = ssu (As,reqq/As,prov) 1/d
where
ssu = (500/1.15) (8.5 + 0.3 4.0)/16.6 = 254 MPa
(or 253 MPa; from Figure C3
Gk/Qk = 2.1, c2 = 0.3 and gG = 1.25)
d = redistribution ratio = 1.03
= ss 253 (1324/1570)/1.03 = 207
= F3 = 310/207 = 1.50
= Allowable l/
l d = 20.3 1.2 1.50 = 36.5

Table C5

Appendix B
Cl. 7.4.2(2)
Appendix C
Tables C10C13

Cl. 7.4.2, Exp. (7.17)


Table 7.4N, &
NA, Table NA.5
Note 5

Fig. C3
Fig. C14

As punching shear force (rather than a beam shear force) effective span is not

appropriate.
Cladding

and strip of slab beyond centre of support.

# Otherwise

for at slabs 8.5/9.5 = 0.89 as span > 8.5 m.

* See Appendix B1.5


In line with Note 5 to Table NA.5, 1.50 is considered to be a maximum for 310/s
ss.
74

Cl. 7.4.2(2)

,'-3?eZmleZ[

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Actual l/d = 9500/260 = 36.5

= OK
Use H20 @ 200 B1 (1570)

c) Flexure: column strip, hogging


MEd = 222.3 kNm/m
K = MEd/bd2fck = 222.3 106/(1000 2602 30) = 0.109
z/d = 0.89
z = 0.89 260 = 231 mm
As = MEd/fydz = 222.3 106/(231 500/1.15) = 2213 mm2/m
(r = 0.85%)
Try H20 @ 125 T1 (2512 mm2/m)#
d) Flexure: middle strip, hogging
MEd = 95.3 kNm/m
K = MEd/bd2fck = 95.3 106/(1000 2602 30) = 0.069
z/d = 0.95
z = 0.95 260 = 247 mm
As = MEd/fydz = 95.3 106/(247 500/1.15) = 887 mm2/m
(r = 0.34%)
Try H16 @ 200 T1 (1005 mm2/m)
e) Requirements
i) In column strip, inside middle 1500 mm
There is a requirement to place 50% of At within a width equal to
0.125 of the panel width on either side of the column.
Area required = (3 2213 + 3 887)/2 mm2
= 4650 mm2
Over width = 2 0.125 6.0 m = 1500 mm
i.e. require 4650/1.5 = 3100 mm2/m for 750 mm either side of the
column centreline.
Use H20 @ 100 T1 (3140 mm2/m)
750 mm either side of centre of support (16 no. bars)
(r = 0.60%)

Table C5

Table C5

Cl. 9.4.1(2)

ii) In column strip, outside middle 1500 mm


Area required = 3.0 2213 16 314 mm2
= 1615 mm2
Over width = 3000 2 750 mm = 1500 mm
i.e. 1077 mm2/m
Use H20 @ 250 T1 (1256 mm2/m)
in remainder of column strip
Note: Continuity into columns will reduce sagging moments and criticality of
deection check (see Figures 3.26 and 3.27).
Note requirement for at least 2 bars in bottom layer to carry through column.
# The hogging moment could have been considered at face of support to reduce the
amount of reinforcement required.

Cl. 9.4.1(3)
75

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

iii) In middle strip

Use H16 @ 200 T1 (1005 mm2/m)

iv) Perpendicular to edge of slab at edge column


Design transfer moment to column Mt = 0.17 bed 2fck
where
be = cz + y = 400 + 400 = 800 mm
Mt = 0.17 800 2602 30 106 = 275.8 kNm
K = MEd/bd2fck = 275.8 106/(800 2602 30) = 0.170
z/d = 0.82
z = 0.82 260 = 213 mm
As = MEd/fydz = 275.8 106/(213 500/1.15) = 2978 mm2/m
This reinforcement to be placed within cx + 2cy = 1100 mm

Cl. 9.4.2(1),
I.1.2(5)
Fig. 9.9

SMDSC[9]

Try 10 no. H20 T1 U-bars in pairs @ 200 (3140 mm2) local to column
(max. 200 mm from column)
Note:
Where a 200 200 hole occurs on face of column, be becomes 600 mm
and pro rata, As,req becomes 2233 mm2 i.e. use 4 no. H20 each side
of hole (2512 mm2).
v) Perpendicular to edge of slab generally
Assuming that there is partial xity along the edge of the slab, top
reinforcement capable of resisting 25% of the moment in the
adjacent span should be provided
OK
0.25 2213 = 553 mm2/m
vi) Check minimum area of reinforcement
As,min = 0.26 (fctm/fyk) btd 0.0013 btd
where
bt = width of tension zone
fctm = 0.30 fck0.666
As,min = 0.26 0.30 300.666 1000 260/500 = 390 mm2/m
(r = 0.15%)
Use H12 @ 200 (565 mm2/m)
The reinforcement should extend 0.2h from edge = 600 mm

Cl. 9.3.1.2(2),
9.2.1.4(1) & NA

Cl. 9.3.1.1, 9.2.1.1


Table 3.1

Cl. 9.3.1.4(2)

3.4.6 Analysis grid line 1 (grid 3 similar)


Consider grid line 1 as being 9.6/2 + 0.4/2 = 5.0 m wide with
continuous spans of 6.0 m. Column strip is 6.0/4 + 0.4/2 = 1.7 m
wide. Consider perimeter load is carried by column strip only.

76

Cl. 5.1.1(4)

,'-3?eZmleZ[

qk slab
= 20.0 kN/m
gk cladding = 10.0 kN/m
= 42.5 kN/m
gk slab

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

6000

6000

6000

p
Actions:
Permanent from slab
Variable from slab
Permanent perimeter load

gk = 5 8.5 kN/m2 = 42.5 kN/m


qk = 5 4.0 kN/m2 = 20.0 kN/m
gk = 10.0 kN/m

Load combination and arrangement:


As before, choose to use all-spans-loaded case and coefcients
Ultimate load, n:
By inspection, Exp. (6.10b) is critical.
n = 1.25 (42.5 +10) + 1.5 20 = 95.6 kN/m
Perimeter load, 10 1.25 = 12.5 kN/m
Effective span, leff
Effective span = 6000 2 400/2 + 2 300/2 = 5900
Design moments in bay, MEd:
In spans (worst case, end span assuming pinned support)
MEd = 0.086 83.0 5.92 = 248.5 kNm
At supports (worst case 1st support)
MEd = 0.086 83.0 5.92 = 248.5 kNm
Additional moment in column strip only due to perimeter load,
spans (and supports, worst case)
MEd = 0.086 12.5 5.92 = 37.4 kNm
Apportionment to column strips and middle strips:
Apportionment (as %)
Column strip, 1.7 m wide Middle strip
Short span = 25%
ve (hogging) Short span = 75%
50%
+ve (sagging) 50%

Cl. 5.1.3(1) &


NA: Table NA.1
(option c)
Fig. 2.5
EC0: Exp. (6.10b)

Cl. 5.3.2.2(1)

Table C2
Table C2

NA.3[1a]: Fig. I.1


Table I.1
CS Flat slab
guide[27]

Short span moments:


MEd
Column strip, 1.7 m wide
Middle strip, 3.3 m wide
ve (hogging) (0.75 248.5 + 37.4)/1.70 0.25 248.5/3.3
= 131.6 kNm/m
= 18.8 kNm/m
+ve (sagging) (0.50 248.5 + 37.4)/1.70 0.50 248.5/3.3
= 95.1 kNm/m
= 37.6 kNm/m
77

Punching shear force, VEd


For internal supports, as before = 516.5 kN
For penultimate support, 516.5 1.18 = 609.5 kN

Table C3

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

3.4.7 Design grid line 1 (grid 3 similar)


Cover:
cnom = 30 mm as before
d = 300 30 20 20/2 = 240 mm
a) Flexure: column strip, sagging
MEd = 95.1 kNm/m
K = MEd/bd2fck = 95.1 106/(1000 2402 30) = 0.055
z/d = 0.95
z = 0.95 240 = 228 mm
As = MEd/fyd z = 95.1 106/(228 500/1.15) = 959 mm2/m
(r = 0.40%)
Try H16 @ 200 B2 (1005 mm2/m)
b) Deection: column strip
Check span-to-effective-depth ratio.
Allowable l/d = N K F1 F2 F3
where
N = 26.2 (r = 0.40%, fck = 30)
K = 1.2
(at slab)
F1 = 1.0
(beff/bw = 1.0)
F2 = 1.0
(no brittle partitions)
F3 = 310/ ss 1.5
where
ss = ssu (As,req/As,prov) 1/d
where
ssu 283 MPa (from Figure C3 and Gk/Qk
= 3.6, c2 = 0.3, gG = 1.25)
d = redistribution ratio = 1.08
= ss 283 (959/1005)/1.08 = 250
= F3 = 310/250 = 1.24
=Allowable l/d = 26.2 1.2 1.24 = 39.0
Actual l/d = 5900/240 = 24.5 = OK
Use H16 @ 200 B2 (1005 mm2/m)
c) Flexure: middle strip, sagging
MEd = 37.6 kNm/m
By inspection, z = 228 mm
As = MEd/fydz = 37.6 106/(228 500/1.15) = 379 mm2/m
(r = 0.56%)

78

Table C5

Appendix B
Appendix C7
Tables C10C13
Cl. 7.4.2, Exp.
(7.17), Table 7.4N
& NA,
Table NA.5:
Note 5

Fig. C3
Table C14
Fig. C3

,'-3?eZmleZ[

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

By inspection, deection OK.


Check minimum area of reinforcement.
As,min = 0.26 (fctm/fyk) btd 0.0013 btd
where
bt = width of tension zone
fctm = 0.30 fck0.666
As,min = 0.26 0.30 300.666 1000 240/500 = 361 mm2/m
(r = 0.15%)
Use H12 @ 300 T2 (376 mm2/m)
d) Flexure: column strip, hogging
MEd = 131.6 kNm/m
K = MEd/bd2fck = 131.6 106/(1000 2402 30) = 0.076
z/d= 0.928
z = 0.928 240 = 223 mm
As = MEd/fydz = 131.6 106/(223 500/1.15) = 1357 mm2/m
(r = 0.56%)
Try H20 @ 200 T2 (1570 mm2/m)
e) Flexure: middle strip, hogging
MEd = 18.8 kNm/m
By inspection, z = 228 mm
As = MEd/fydz = 18.8 106/(228 500/1.15) = 190 mm2/m
(r = 0.08%)
As,min as before
= 361 mm2/m
(r = 0.15%)
Try H12 @ 300 T2 (376 mm2/m)
f) Requirements
There is a requirement to place 50% of At within a width equal to 0.125
of the panel width on either side of the column. As this column strip is
adjacent to the edge of the slab, consider one side only:
Area required = (1.5 1357 + 3.3 190)/2 mm2
= 1334 mm2
Within
= 0.125 6.0 m = 750 mm of the column centreline,
i.e. require 1334/0.75 = 1779 mm2/m for 750 mm from the column
centreline.

Cl. 9.3.1.1, 9.2.1.1

Table 3.1

Table C5

Table C5

Cl. 9.3.1.1, 9.2.1.1

Cl. 9.4.1(2)

The

hogging moment could have been considered at face of support to reduce


the amount of reinforcement required. This should be balanced against the
effect of the presence of a 200 200 hole at some supports which would
have the effect of increasing K but not unduly increasing the total amount of
reinforcement required in the column strip (a 1.5% increase in total area would
been required).
79

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Allowing for similar from centreline of column to edge of slab:


Use 6 no. H20 @ 175 T2(1794 mm2/m)
(r = 0.68%)
between edge and to 750 mm from centre of support
In column strip, outside middle 1500 mm, requirement is for
1.7 1357 6 314 = 422 mm2 in 750 mm, i.e. 563 mm2/m
Use H12 @ 175 T2 (646 mm2/m) in remainder of column strip
Use H12 @ 300 T2 (376 mm2/m)

In middle strip

3.4.8 Analysis grid line 2


Consider panel on grid line 2 as being 9.6/2 + 8.6/2 = 9.1 m wide
and continuous spans of 6.0 m. Column strip is 6.0/2 = 3.0 m wide.
(See Figure 3.20).
qk slab = 36.4 kN/m
gk slab = 77.4 kN/m
C

6000

6000

6000

Figure 3.22 Internal p


panel on grid 2
Slab gk = 9.1 8.5 kN/m2 = 77.4 kN/m
Slab qk = 9.1 4.0 kN/m2 = 36.4 kN/m
Actions, load combination and arrangement:
Choose to use all-spans-loaded case.
Ultimate load, n:
By inspection, Exp. (6.10b) is critical.
n = 1.25 77.4 + 1.5 36.4 = 151.4 kN/m

Fig. 2.5
EC0: Exp. (6.10b)

Effective span, leff:


Effective span = 5900 mm as before.

Cl. 5.3.2.2(1)

Design moments in bay, MEd:


Spans (worst case, end span assuming pinned support)
MEd = 0.086 151.4 5.92 = 453.2 kNm

Table C2

Support (worst case 1st support)


MEd = 0.086 151.4 5.92 = 453.2 kNm
Additional moment in column strip only due to perimeter load.

80

Cl. 5.1.3(1) &


NA: Table NA.1
(option c)

Table C2

,'-3?eZmleZ[

Apportionment to column strips and middle strips:


MEd

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Column strip, 3.0 m wide Middle strip, 6.1 m wide


0.25 453.2/6.1
ve (hogging) 0.75 453.2/3.0
= 113.3 kNm/m
= 18.5 kNm/m
+ve (sagging) 0.50 453.2/3.0
= 75.5 kNm/m

0.50 453.2/6.1
= 37.1 kNm/m

Punching shear force, VEd, as before.

3.4.9 Design grid line 2


Effective depth, d
d = 300 30 20 20/2 = 240 mm
a) Flexure: column strip, sagging
MEd = 75.5 kNm/m
By inspection, z = 228 mm
As = MEd/fydz = 75.5 106/(228 500/1.15) = 761 mm2/m
(r = 0.32%)
Try H16 @ 250 B2 (804 mm2/m)
Deection: column strip
By inspection, OK.

Table C5

b) Flexure: column strip, sagging


MEd = 37.1 kNm/m
By inspection, z = 228 mm
As = MEd/fydz = 37.1 106/(228 500/1.15) = 374 mm2/m
(r = 0.55%)
By inspection, deection OK.
Try H10 @ 200 B2 (393 mm2/m)
c) Flexure: column strip, hogging
MEd = 113.3 kNm/m
K = MEd/bd2fck = 113.3 106/(1000 2402 30) = 0.065
z/d = 0.94
z = 0.928 240 = 225 mm

Table C5

As = MEd/fydz = 113.3 106/(225 500/1.15) = 1158 mm2/m


(r = 0.48%)
Try H20 @ 250 T2 (1256 mm2/m)
d) Flexure: middle strip, hogging
MEd = 18.5 kNm/m
By inspection, z = 228 mm
The hogging moment could have been considered at face of support to reduce
the amount of reinforcement required.

81

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

As = MEd/fydz = 18.5 106/(228 500/1.15) = 187 mm2/m


(r = 0.08%)
As before minimum area of reinforcement governs
As,min = 0.26 0.30 300.666 1000 240/500 = 361 mm2/m
(r = 0.15%)
Try H12 @ 300 B2 (376 mm2/m)

Table C5
Cl. 9.3.1.1, 9.2.1.1

e) Requirements
Regarding the requirement to place 50% of At within a width equal
to 0.125 of the panel width on either side of the column:
Area required = (3.0 1158 + 6.1 187)/2 mm2
= 2307 mm2
Within
= 2 0.125 6.0 m = 1500 mm centred on the column
centreline,
i.e. require 2307/1.5 = 1538 mm2/m for 750 mm either side of the
column centreline.
Use H20 @ 200T2 (1570 mm2/m)
750 mm either side of centre of support
(r = 0.60%)
In column strip, outside middle 1500 mm, requirement is for
3.0 1158 1.5 1570 = 1119 mm2 in 1500 mm, i.e. 764 mm2/m
Use H16 @ 250 T2 (804 mm2/m) in remainder of column strip
In middle strip:

Use H12 @ 300 T2 (376 mm2/m)

3.4.10 Punching shear, central column, C2


At C2, applied shear force, VEd = 1204.8 kN
a) Check at perimeter of column
vEd = bVEd /uid < vRd,max
where
b = factor dealing with eccentricity; recommended value 1.15
VEd = applied shear force
ui = control perimeter under consideration.
For punching shear adjacent to interior columns
u0 = 2(cx + cy) = 1600 mm
d = mean effective depth = (260 + 240)/2 = 250 mm
= 1.15 1204.8 103/1600 250 = 3.46 MPa
vEd
vRd,max = 0.5vfcd

Column C2 is taken to be an internal column. In the case of a penultimate


column, an additional elastic reaction factor should have been considered.

82

Cl. 6.4.3(2),
6.4.5(3)
Fig. 6.21N & NA
Cl. 6.4.5(3)
Exp. (6.32)
Cl. 6.4.5(3) Note

,'-3?eZmleZ[

where
v = 0.6(1 fck/250) = 0.528
fcd = acclfck /gC = 1.0 1.0 30/1.5 = 20

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

= 0.5 0.528 20 = 5.28 MPa

= OK

b) Check shear stress at control perimeter u1 (2d from face of column)


vEd = bVEd/u1d < vRd,c

Table C7
Cl. 6.4.2

where
b, VEd and d as before
u1 = control perimeter under consideration.
For punching shear at 2d from interior columns
u1 = 2(cx + cy) + 2Q 2d = 4741 mm
vEd = 1.15 1204.8 103/4741 250 = 1.17 MPa
vRd,c = 0.18/ gC k (100 rlfck)0.333

Exp. (6.47) & NA

where
gC = 1.5
k = 1 + (200/d)0.5 2 k = 1 + (200/250)0.5 = 1.89
rl = (rly rlz)0.5 = (0.0085 0.0048)0.5 = 0.0064

Cl. 6.4.4.1(1)

where
rer, rlz = Reinforcement ratio of bonded steel in the y and
z direction in a width of the column plus 3d each
side of column#
fck = 30
vRd,c = 0.18/1.5 1.89 (100 0.0064 30)0.333 = 0.61 MPa
= Punching shear reinforcement required

Table C5*

c) Perimeter at which punching shear links are no longer required


uout = VEd b/(d vRd,c)
uout = 1204.8 1.15 103/(250 0.61) = 9085 mm
Length of column faces = 4 400 = 1600 mm
Radius to uout = (9085 1600)/2Q = 1191 mm from face of column
Perimeters of shear reinforcement may stop 1191 1.5 250 = 816 m
from face of column
Shear reinforcement (assuming rectangular arrangement of links):
sr,max = 250 0.75 = 187, say = 175 mm

Fig. 6.13

Exp. (6.54)

Cl. 6.4.5(4) & NA


Cl. 9.4.3(1)

At the perimeter of the column, v


Rd,max assumes the strut angle is 45, i.e. that
cot y = 1.0. Where cot y = < 1.0, vRd,max is available from Table C7.
#The

values used here for r ly , r lz ignore the fact that the reinforcement is
concentrated over the support. Considering the concentration would have given a
higher value of VRd,c at the expense of further calculation to determine r ly , r lz at
3d from the side of the column.
* vRd,c for various values of d and rl is available from Table C6.
83

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Inside 2d control perimeter, st,max = 250 1.5 = 375, say 350 mm


Outside control perimeter st,max = 250 2.0 = 500 mm
Assuming vertical reinforcement:
At the basic control perimeter, u1, 2d from the column:
Asw (vEd 0.75vRd,c) sr u1/1.5fywd,ef)
where
fywd,ef = effective design strength of reinforcement
= (250 + 0.25d) < fyd = 312 MPa
For perimeter u1
Asw = (1.17 0.75 0.61) 175 4741/(1.5 312)
= 1263 mm2 per perimeter
Asw,min 0.08fck0.5(sr st)/(1.5 fyk sin a + cos a)
where
Asw,min = minimum area of a single leg of link
a
= angle between main reinforcement and shear
reinforcement; for vertical reinforcement sin a = 1.0

Cl. 9.4.3(2)

Exp. (6.52)

Cl. 6.4.5(1)

Exp. (9.11)

Asw,min 0.08 300.5 (175 350)/(1.5 500) = 36 mm2


= Try H8 legs of links (50 mm2)
Asw /u1 1263/4741 = 0.266 mm2/mm
Using H8 max. spacing = min[50/0.266; 1.5d]
= min[188; 375] = 188 mm cc
= Use min. H8 legs of links at 175 mm cc around perimeter u1
Perimeters at 0.75d = 0.75 250 = 187.5 mm
say = 175 mm centres
d) Check area of reinforcement > 1263 mm2 in perimeters inside u1
1st perimeter to be > 0.3d but < 0.5d from face of column. Say
0.4d = 100 mm from face of column.

Cl. 9.4.3

Cl. 9.4.3(1)

Fig. 9.10,
Cl. 9.4.3(4)

By inspection of Figure 3.23 the equivalent of 10 locations are available


at 0.4d from column therefore try 2 10 no. H10 = 1570 mm2.
By inspection of Figure 3.23 the equivalent of 18 locations are
available at 1.15d from column therefore try 18 no. H10 = 1413 mm2.
By inspection of Figure 3.23 the equivalent of 20 locations are available
at 1.90d from column therefore try 20 no. H10 = 1570 mm2.
By inspection of Figure 3.23 beyond u1 to uout grid of H10 at 175 x 175 OK.
Clause 6.4.5 provides Exp. (6.52), which by substituting v for v
Ed
Rd,c, allows
calculation of the area of required shear reinforcement, Asw, for the basic control
perimeter, u1.
The same area of shear reinforcement is required for all perimeters inside or
outside perimeter u1. See Commentary on design, Section 3.4.14. Punching shear
reinforcement is also subject to requirements for minimum reinforcement and
spacing of shear reinforcement (see Cl. 9.4.3).

84

Cl. 6.4.5
Exp. 6.5.2

Cl. 9.4.3

,'-3?eZmleZ[

e) Summary of punching shear refreshment required at column C2


uout

S = 112 H10 legs of links


u1 at 2d
from column

175 175 175 175 200 200 200 175 175 175 175

716
100 400 100
716

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Punching shear reinforcement


no longer required
1.5d = 375

uout

175 175 175 175 200 200 200 175 175 175 175
375

716

100

400

100

716

Figure 3.23 Punching shear links at column C2 (112 no. links)


(column D2 similar)

3.4.11 Punching shear, edge column


Assuming penultimate support,
VEd = 1.18 516.5 = 609.5 kN
a) Check at perimeter of column
vEd = b VEd/uid < vRd,max
where
b = factor dealing with eccentricity; recommended value 1.4
VEd = applied shear force
ui = control perimeter under consideration.
For punching shear adjacent to edge columns
u0 = c2 + 3d < c2 + 2c1
= 400 + 750 < 3 400 mm
= 1150 mm
d = as before 250 mm
vEd = 1.4 609.5 103/1150 250 = 2.97 MPa
vRd,max, as before = 5.28 MPa
= OK

Table C3
Cl. 6.4.3(2),
6.4.5(3)
Fig. 6.21N & NA
Cl. 6.4.5(3)

Exp. (6.32)
Cl. 6.4.5(3) Note
85

Cl. 6.4.2

Fig. 6.15

Exp. (6.47) & NA

where
gC = 1.5
k = as before = 1 +(200/250)0.5 = 1.89
rl = (r lyr lz )0.5
where
rer, rlz = Reinforcement ratio of bonded steel in the y and z direction
in a width of the column plus 3d each side of column.
r ly: (perpendicular to edge) 10 no. H20 T2 + 6 no. H12
T2 in 2 750 + 400, i.e. 3818 mm2 in 1900 mm
=r ly = 3818/(250 1900) = 0.0080
r lz : (parallel to edge) 6 no. H20 T1 + 1 no. T12 T1 in 400 +
750 i.e. 1997 mm2 in 1150 mm.
=r lz = 1997/(250 1150) = 0.0069
r l = (0.0080 0.0069)0.5 = 0.0074
fck = 30
vRd,c = 0.18/1.5 1.89 (100 0.0074 30)0.333 = 0.64 MPa
= Punching shear reinforcement required
C

3d = 750

6H20T1 @175

3d = 750
10H20 U-bars in pairs @ 200 cc
400

H12 @ 200 U-bars

400

3d = 750

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

b) Check shear stress at basic perimeter u1 (2.0d from face of column)


vEd = bVEd/u1d < vRd,c
where
b, VEd and d as before
u1 = control perimeter under consideration.
For punching shear at 2d from edge column columns
u1 = c2 + 2c1+ Q 2d = 2771 mm
vEd = 1.4 609.5 103/2771 250 = 1.23 MPa
vRd,c = 0.18/ gC k (100 rlfck)0.333

H12 @ 175T1

Figure 3.24 Flexural tensile reinforcement adjacent to columns


C1 (and C3)

86

vRd,c for various values of d and rl is available from Table C6.

Cl. 6.4.4.1(1)

Table C6

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

,'-3?eZmleZ[

c) Perimeter at which punching shear links no longer required


uout = 609.5 1.4 103/(250 0.64) = 5333 mm
Length attributable to column faces = 3 400 = 1200 mm
= radius to uout from face of column
= say (5333 1200)/Q = 1315 mm from face of column
Perimeters of shear reinforcement may stop 1370 1.5 250
= 940 mm from face of column.
d) Shear reinforcement
As before, sr,max = 175 mm; st,max = 350 mm and
fywd,ef = 312 MPa
For perimeter u1
Asw (vEd 0.75vRd,c) sr u1/1.5fywd,ef
= (1.23 0.75 0.64) 175 2771/(1.5 312)
= 777 mm2 per perimeter
Asw,min 0.08 300.5 (175 350)/(1.5 500) = 36 mm2
Asw/u1 777/2771 = 0.28 mm2/mm
Using H8 max. spacing = 50/0.28 = 178 mm cc
=Use min. H8 (50 mm2) legs of links at 175 mm cc around perimeters:
perimeters at 175 mm centres
e) Check area of reinforcement > 777 mm2 in perimeters inside u1
1st perimeter to be > 0.3d but < 0.5d from face of column. Say
0.4d = 100 mm from face of column
By inspection of Figure 3.27 the equivalent of 6 locations are available
at 0.4d from column therefore try 2 6 no. H10 = 942 mm2

Exp. (6.54)

Cl. 6.4.5(4)
& NA

Cl. 9.4.3(1),
9.4.3(2)
Exp. (6.52)

Exp. (9.11)

Fig. 9.10,
Cl. 9.4.3(4)

By inspection of Figure 3.27 the equivalent of 12 locations are


available at 1.15d from column therefore try 12 no. H10 = 942 mm2
By inspection of Figure 3.27 the equivalent of 14 locations are
available at 1.90d from column therefore try 14 no. H10 = 1099 mm2
By inspection of Figure 3.27 beyond u1 to uout grid of
H10 at 175 x 175 OK.

3.4.12 Punching shear, edge column with hole


Check columns D1 and D3 for 200 200 mm hole adjacent to column.
As previously described use 4 no. H20 U-bars each side of column for
transfer moment.
Assuming internal support, VEd = 516.5 kN
See Commentary on design Section 3.4.14. Punching shear reinforcement is
also subject to requirements for minimum reinforcement and spacing of shear
reinforcement (see Cl. 9.4.3).

Cl. 9.4.3

87

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

a) Check at perimeter of column


vEd = bVEd/uid < vRd,max
where
b = factor dealing with eccentricity; recommended value 1.4
VEd = applied shear force
ui = control perimeter under consideration. For punching shear
adjacent to edge columns u0 = c2 + 3d < c2 + 2c1
= 400 + 750 < 3 400 mm
= 1150 mm
Allowing for hole, u0 = 1150 200 = 950 mm
d = 250 mm as before
vEd = 1.4 516.5 103/950 250 = 3.06 MPa
= OK
vRd,max as before = 5.28 MPa
b) Check shear stress at basic perimeter u1 (2.0d from face of column)
vEd = bVEd/u1d < vRd,c
where
b, VEd and d as before
u1 = control perimeter under consideration. For punching shear
at 2d from edge column columns
u1 = c2 + 2c1+ Q 2d = 2771 mm
Allowing for hole
200/(c1/2): x/(c1/2 + 2d)
200/200: x/( 200 + 500)

  = x = 700 mm
u1 = 2771 700 = 2071 mm
vEd = 1.4 516.5 103/2071 250 = 1.40 MPa
vRd,c = 0.18/gC k (100 rlfck)0.333

Cl. 6.4.3(2),
6.4.5(3)
Fig. 6.21N & NA

Cl. 6.4.5(3)

Exp. (6.32)
Cl. 6.4.5(3) Note
Cl. 6.4.2

Fig. 6.15

Fig. 6.14

Exp. (6.47) & NA

where
gC = 1.5
k = as before = 1 + (200/250)0.5 = 1.89
rl = (r ly r lz )0.5
where
rer, rlz = Reinforcement ratio of bonded steel in the y and
z direction in a width of the column plus 3d each
side of column
rly: (perpendicular to edge) 8 no. H20 T2 + 6 no. H12
T2 in 2 720 + 400 200, i.e. 3190 mm2 in 1640 mm.
=r ly = 3190/(240 1640) = 0.0081
rlz: (parallel to edge) 6 no. H20 T1 (5 no. are
effective) + 1 no. T12 T1 in 400 + 750 200, i.e.
1683 mm2 in 950 mm.
=r lz = 1683/(260 950) = 0.0068
88

Cl. 6.4.4.1(1)

,'-3?eZmleZ[

Table C6

3d = 750

H12 @ 175T1

400

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

rl
= (0.0081 0.0068)0.5 = 0.0074
= 30
fck
vRd,c = 0.18/1.5 1.89 (100 0.0074 30)0.33 = 0.64 MPa
= punching shear reinforcement required

H12 @ 200 U-bars

6H20T @ 175
3d = 750

400

8H20 U-bars in pairs @ 200 cc


3d = 750

Figure 3.25 Flexural tensile reinforcement adjacent to columns


D1 and D3
c) Perimeter at which punching shear links no longer required
uout = 516.5 1.4 103/(250 0.64) = 4519 mm
Length attributable to column faces = 3 400 = 1200 mm
Angle subtended by hole from centre of column D1 (See Figures 3.25
& 3.27) = 2
tan1(100/200) = 2 26.5 = 0.927 rads.
= radius to uout from face of column
= say (4519 1200)/(Q 0.927) = 1498 mm from face of column
Perimeters of shear reinforcement may stop 1498 1.5 250
= 1123 mm from face of column
d) Shear reinforcement
As before, sr,max = 175 mm; st,max = 350 mm and fywd,ef = 312 MPa
For perimeter u1
Asw (vEd 0.75vRd,c) sr u1/1.5fywd,ef) per perimeter
= (1.40 0.75 0.64) 175 2071/(1.5 312)
= 712 mm2 per perimeter

Exp. (6.54)

Cl. 6.4.5(4)
& NA

Cl. 9.4.3(1)
9.4.3(2)
Exp. (6.52)

Asw,min 0.08 300.5 (175 350)/(1.5 500) = 36 mm2


Asw/u1 712/2071 = 0.34 mm2/mm
v
Rd,c for various values of d and rl is available from Table C6.

89

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Using H8 (50 mm2) max. spacing = min[50/0.3; 1.5d]


= min[147; 375] = 147 mm cc No good
Try using H10, max. spacing = 78.5/0.34 = 231 mm cc, say 175 cc
= Use min. H10 (78.5 mm2) legs of links at 175 mm cc around perimeters:
perimeters at 175 mm centres
Check min. 9 no. H10 legs of links (712 mm2) in perimeter u1, 2d from
column face.
e) Check area of reinforcement > 712 mm2 in perimeters inside u1
1st perimeter to be 100 mm from face of column as before.
By inspection of Figure 3.27 the equivalent of 6 locations are available
at 0.4d from column therefore try 2 6 no. H10 = 942 mm2.

Fig. 9.10,
Cl. 9.4.3(4)

By inspection of Figure 3.27 the equivalent of 10 locations are


available at 1.15d from column therefore try 10 H10 = 785 mm2.
By inspection of Figure 3.27 beyond 1.15d to uout grid:
H10 at 175 x 175 OK.

3.4.13 Summary of design


Grid C exure
End supports:
Column strip: (max. 200 mm
from column)
10 no. H20 U-bars in pairs
(where 200 200 hole use 8 no. H20
T1 in U-bars in pairs)
Middle strip:
H12 @ 200 T1
Spans 12 and 23:
Column strip and middle strip:

H20 @ 200 B

Central support:
Column strip centre: for 750 mm
either side of support:
Column strip outer:
Middle strip:

H20 @ 100 T1
H20 @ 250 T1
H16 @ 200 T1

Grid 1 (and 3) exure


Spans:
Column strip:
Middle strip:

H16 @ 200 B2
H12 @ 300 B2

See Commentary on design Section 3.4.14. Punching shear reinforcement is


also subject to requirements for minimum reinforcement and spacing of shear
reinforcement.

90

Cl. 9.4.3

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

,'-3?eZmleZ[

Interior support:
Column strip centre:
Column strip outer:
Middle strip:

6 no. H20 @ 175 T2


H12 @ 175 T2
H12 @ 300 T2

Grid 2 exure
Spans:
Column strip:
Middle strip:

H16 @ 250 B2
H10 @ 200 B2

Interior support:
Column strip centre:
Column strip outer:
Middle strip:

H20 @ 200 T2
H16 @ 250 T2
H12 @ 300 T2
See Figure 3.26

Punching shear
Internal (e.g. at C2):
Generally, use H10 legs of links in perimeters at max. 175 mm
centres, but double up on 1st perimeter
Max. tangential spacing of legs of links, st,max = 270 mm
Last perimeter, from column face, min. 767 mm
See Figure 3.26
Edge (e.g. at C1, C3 assuming no holes):
Generally, use H10 legs of links in perimeters at max. 175 mm
centres but double up on 1st perimeter
Max. tangential spacing of legs of links, st,max = 175 mm
Last perimeter, from column face, min. 940 mm
Edge (e.g. at D1, D3 assuming 200 200 hole on face of column):
Generally, use H10 legs of links in perimeters at max. 175 mm
centres but double up on 1st perimeter
Max. tangential spacing of legs of links, st,max = 175 mm
Last perimeter, from column face, min. 1123 mm
See Figure 3.27

91

10H20 T1 U-bars in pairs @ 200


H12 @ 200 T1 U-bars

6H20 - 175 T2
8H20 T1
U-bars in pairs
@ 200

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

H12 - 200 T1 U-bars

1
H20 @ 200 B1

H16 @ 175 B2*


5H12 @ 175 T2

H12 @ 300 B2
H10 @ 200 T2

4H16 @ 250 T2
3H20 @
250 T1

H16 @ 175 B2*


2

16H20 @ 100 T1

9H20 @ 175 T2*


3H20 @ 250 T1
16H20 @ 100 T1

3H20 @ 250 T1
H16 @ 200 T1
Note:* Spacing rationalised to suit punching shear links

Figure 3.26 Reinforcement details bay CD, 12

3.4.14 Commentary on design


a) Method of analysis
The use of coefcients in the analysis would not usually be
advocated in the design of such a slab. Nonetheless, coefcients
may be used and, unsurprisingly, their use leads to higher design
moments and shears, as shown below.

92

Method

Moment in
Centre support Centre support
9.6 m span per moment per
reaction VEd (kN)
6 m bay (kNm) 6 m bay (kNm)

Coefficients

842.7

952.8

1205

Continuous beam

747.0

885.6

1103

Plane frame columns 664.8


below

834.0

1060

Plane frame columns 616.8


above and below

798.0

1031

,'-3?eZmleZ[

D
375

1123

6H20 @ 175 T2
6H16 @ 175 B2

8H20 T1 U-bars in pairs

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

uout

H10 @ 200 T1 U-bars

H10 @ 200 T1 U-bars

175
175

1
u1

500

175
175
175

1.5d
uout

175
175
175
175
175
Ineffective area
S = 152 H10 legs of links
CL
@ 175 mm centres
175 175 175 175 175 175 200
200 175 175 175 175 175 175
100

100

Note: For internal column see Figure 3.23

Figure 3.27 Punching shear links at column D1 (and D3)


(penultimate support without hole similar)
These higher moments and shears result in rather more reinforcement
than when using other more rened methods. For instance, the nite
element analysis used in Guide to the design and construction of
reinforced concrete at slabs[27] for this bay, leads to:
t H16 @ 200 B1 in spans 12 (cf. H20 @ 200 B1 using coefficients)
t H20 @ 125 T1 at support 2 (cf. H20 @ 100 T1 using coefficients)
t 3 perimeters of shear links at C2 for VEd = 1065 kN (cf. 5 perimeters
using coefficients)
t 2 perimeters of shear links at C3 (cf. 7 perimeters using coefficients)
b)

Effective spans and face of support


In the analysis using coefcients, advantage was taken of using
effective spans to calculate design moments. This had the effect of
reducing span moments.
At supports, one may base the design on the moment at the face of
support. This is borne out by Guide to the design and construction of
reinforced concrete at slabs[27] that states that hogging moments
greater than those at a distance hc/3 may be ignored (where hc is the
effective diameter of a column or column head). This is in line with BS
8110[7] and could have been used to reduce support moments.

Cl. 5.3.2.2(1)

Cl. 5.3.2.2(3)

93

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

c)

Punching shear reinforcement


Arrangement of punching shear links
According to the literal denition of :lp in Exp. (6.52), the same
area of shear reinforcement is required for all perimeters inside or
outside perimeter n* (rather than (:lp/n*)/sr being considered as the
required density of shear reinforcement on and within perimeter n*).
For perimeters inside n*, it might be argued that Exp. (6.50)
(enhancement close to supports) should apply. However, at the time
of writing, this expression is deemed applicable only to foundation
bases. Therefore, large concentrations of shear reinforcement
are required close to the columns in this example, this included
doubling up shear links at the 1st perimeter.

Exp. 6.50

Similar to BS 8110[7] gure 3.17, it is apparent that the requirement


for punching shear reinforcement is for a punching shear zone 1.5d
wide. However, in Eurocode 2, the requirement has been simplied in
Exp. (6.52) to make the requirement for a perimeter (up to 0.75d
wide). It might appear reasonable to apply the same 40%:60% rule
(BS 8110 Cl. 3.7.7.6) to the rst two perimeters to make doubling
of punching shear reinforcement at the rst perimeter unnecessary:
in terms of Eurocode 2 this would mean 80% Asw on the rst
perimeter and 120% Asw on the second. Using this arrangement it
would be possible to replace the designed H10 links in the rst two
perimeters with single H12 links.

BS 8110:
Fig. 3.17

Outside u1, the numbers of links could have been reduced to


maintain provision of the designed amount of reinforcement Asw.
A rectangular arrangement of H12 links would have been possible
(within perimeter u1, 350 175; outside u1, 500 175). However, as
the grid would need to change orientation around each column (to
maintain the 0.75d radial spacing) and as the reinforcement in B2
and T2 is essentially at 175 centres, it is considered better to leave
the arrangement as a regular square grid.

Cl. 9.4.3(1)

Use of shear reinforcement in a radial arrangement, e.g. using stud


rails, would have simplied the shear reinforcement requirements.
VEd/VRd,c
In late 2008, a proposal was made for the UK National Annex to
include a limit of 2.0 or 2.5 on VEd/VRd,c (or vEd/vRd,c) within punching
shear requirements. It is apparent that this limitation could have
major effects on at slabs supported on relatively small columns. For
instance in Section 3.4.12, edge column with hole, VEd/VRd,c = 2.18.
Curtailment of reinforcement
In this design, the reinforcement would be curtailed and this would be
done either in line with previous examples or, more practically, in line
with other guidance[20, 21].

94

Exp. 6.52

BS 8110:
Cl. 3.7.7.6

,'.3LmZbk_eb`am
3.5 Stair flight

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Mabl^qZfie^bl_hkZmrib\ZelmZbk_eb`am'
Ikhc^\m]^mZbel

<Ze\neZm^][r

chg

Ch[gh'

Stair flight

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP 041
1
Oct 09

1750

600

9 @250

600

3450

Figure 3.28 Stair flight

3.5.1 Loads
kN/m2

Permanent (worse case flight)


Assume 160 waist 0.160 305/250 25
Treads
4 0.25 0.175/2 25
50 mm screed
0.5 22
Finishing

Variable action: crowd loading

= 4.88
= 2.19
= 1.10
= 0.03
gk = 8.20
qk = 4.00

EC1-1-1: Table 6.1,


6.2 & NA.3

3.5.2 Moment
MEd = (8.20 1.25 + 4.00 1.5) 3.452/8
= 24.2 kNm/m

3.5.3 Design
d = 160 cnom f/2
where
cnom = 25 mm (for XC1)
f = 12 mm (assumed)
= d = 129 mm

Concise: Table 4.2;


BS 8500

95

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

=
=
z/d =
z =
=
As =
=
=

MEd/bd2fck = 24.2 106/(1000 1292 30)


0.048
0.95
0.95 129
122 mm
MEd/fydz
24.2 106/[(500/1.15) 122]
456 mm2/m (r = 0.35%)
Try H12 @ 250 (452 mm2/m) = OK)

Table C5

3.5.4 Check deflection


Allowable l/d = N K F1 F2 F3
where
N = 32.7
K = 1.0
F1 = 1.0
F2 = 1.0
F3 = 1.0 (say)
= Allowable l/d = 32.7
Actual l/d
= 3450/129
= 26.7 = OK

Appendix C7,
Table C10
Table C11

=Provide H12 @ 250 B.

96

-'*3<hgmbgnhnl[^Zfhgibglniihkml

- Beams
-') General
Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Ma^\Ze\neZmbhglbgmablL^\mbhgZk^ik^l^gm^]bgma^_heehpbg`iZkml3
-'* <hgmbgnhnl[^ZfhgibglniihkmlZlbfierlniihkm^]\hgmbgnhnl[^Zflahpbg`paZm
fb`am[^]^^f^]mrib\ZeaZg]\Ze\neZmbhgl'
-'+ :a^ZoberehZ]^]E&[^Zf'
-', : \hgmbgnhnl pb]^M&[^Zf'Mabl ^qZfie^ bl ZgZerl^] Zg] ]^lb`g^] lmkb\mer bg Z\\hk]Zg\^
pbmama^ikhoblbhglh_>nkh\h]^+'
Ma^rZk^bgm^g]^]mh[^beenlmkZmbo^h_ma^<h]^Zg]ghmg^\^llZkber[^lmikZ\mb\^'
:`^g^kZef^mah]h_]^lb`gbg`[^Zflbllahpg[^ehp'BgikZ\mb\^%l^o^kZeh_ma^l^lm^ilfZr
[^\hf[bg^]'
N =^m^kfbg^]^lb`geb_^'

EC0 & NA
Table NA.2.1

N :ll^llZ\mbhglhgma^[^Zf'

EC1 & NAs

N :ll^ll]nkZ[bebmrk^jnbk^f^gmlZg]]^m^kfbg^\hg\k^m^

Table 4.1
BS 85001:
Tables A4, A5

lmk^g`ma'
N <a^\d\ho^kk^jnbk^f^gml_hkZiikhikbZm^_bk^

k^lblmZg\^i^kbh]'
N <Ze\neZm^fbgbfnf\ho^k_hk]nkZ[bebmr%_bk^Zg][hg]

EC212:
Tables 5.8, 5.9, 5.10, 5.11
Cl. 4.4.1

k^jnbk^f^gml'
N =^m^kfbg^pab\a\hf[bgZmbhglh_Z\mbhglZiier'

EC0 & NA
Tables NA.A1.1, NA.A1.2 (B)

N =^m^kfbg^ehZ]bg`ZkkZg`^f^gml'

Cl. 5.1.3(1) & NA

N :gZerl^lmkn\mnk^mhh[mZbg\kbmb\Zefhf^gmlZg]la^Zk

Cl. 5.4, 5.5, 5.6

_hk\^l'
N =^lb`g_e^qnkZek^bg_hk\^f^gm'

Cl. 6.1

N <a^\d]^_e^\mbhg'

Cl. 7.4

N <a^\dla^Zk\ZiZ\bmr'

Cl. 6.2

N Hma^k]^lb`g\a^\dl3

<a^\dfbgbfnfk^bg_hk\^f^gm'
<a^\d\kZ\dbg`!lbs^hkliZ\bg`h_[Zkl"'
<a^\d^__^\mlh_iZkmbZeqbmr'
<a^\dl^\hg]Zkrk^bg_hk\^f^gm'

Cl. 9.3.1.1(1), 9.2.1.1(1)


Cl. 7.3, Tables 7.2N, 7.3N
Cl. 9.3.1.2(2)
Cl. 9.3.1.1(2), 9.3.1.4(1)

N <a^\d\nkmZbef^gm'

Cl. 9.3.1.1(4), 9.2.1.3,


Fig. 9.2

N <a^\dZg\ahkZ`^'

Cl. 9.3.1.2, 8.4.4, 9.3.1.1(4),


9.2.1.5(1), 9.2.1.5(2)

N <a^\deZil'

Cl. 8.7.3

97

-'* Continuous beam on pin supports


Mabl \Ze\neZmbhg bl bgm^g]^] mh lahp Z mrib\Ze aZg] \Ze\neZmbhg _hk Z \hgmbgnhnl lbfier
lniihkm^][^Zfnlbg`\h^_\b^gmlmh]^m^kfbg^fhf^gmlZg]la^Zkl'

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Ikhc^\m]^mZbel

Continuous beam on pin


supports

<Ze\neZm^][r

chg

Ch[gh'

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP 041
1
Oct 09

A 450 mm deep 300 mm wide rectangular beam is required


to support ofce loads of gk = 30.2 kN/m and qk = 11.5 kN/m
over 2 no. 6 m spans. fck = 30 MPa, fyk = 500 MPa. Assume 300
mm wide supports, a 50-year design life and a requirement for a
2-hour resistance to re in an external but sheltered environment.
qk = 11.5 kN/m
gk = 30.2 kN/m
6000

6000

Figure 4.1 Continuous rectangular beam

450

300

Figure 4.2 Section through beam

4.1.1 Actions
Permanent gk = 30.2 kN/m and variable qk = 11.5 kN/m

4.1.2 Cover
Nominal cover, cnom:
cnom = cmin + Dcdev
where
cmin = max[cmin,b; cmin,dur]
where
cmin,b = minimum cover due to bond
= diameter of bar. Assume 25 mm main bars
cmin,dur = minimum cover due to environmental conditions.
Assuming XC3 (moderate humidity or cyclic wet
and dry) and secondarily XF1 (moderate water

98

Exp. (4.1)

Cl. 4.4.1.2(3)

-'*3<hgmbgnhnl[^Zfhgibglniihkml

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

cmin,dur

saturation without de-icing salt) using C30/37


concrete,
= 25 mm

Table C3
BS 8500-1[14]:
Table A4;
How to: Building
structures[8]

Dcdev = allowance in design for deviation. Assuming no


measurement of cover, Dcdev= 10 mm
= cnom = 25 + 10 = 35 mm

Cl. 4.4.1.2(3)

Fire:
Check adequacy of section for 2 hours re resistance (i.e. REI = 120)
= OK
For bmin = 300 mm, minimum axis distance, a = 35 mm
cnom = 35 mm

EC2-1-2:
5.6.3(1),
Table 5.6

4.1.3 Load combination (and arrangement)


Load combination:
By inspection, BS EN 1990 Exp. (6.10b) governs
= n = 1.25 30.2 + 1.5 11.5 =

50.8 kN/m

Fig. 2.5
EC0: Exp.(6.10b)

Arrangement:
Choose to use all-and-alternate-spans-loaded load cases, i.e. use
coefcients.

Cl. 5.1.3(1) & NA


Table NA.1
(option b)
Table C3

The coefcients used assume 15% redistribution at supports. As the


amount of redistribution is less than 20%, there are no restrictions
on reinforcement grade. The use of Table 5.6 in BS EN 199212 is
restricted to where redistribution does not exceed 15%.

Table C3
Cl. 5.5(4) & NA
EC2-1-2:
5.6.3(1),
Table 5.6

4.1.4 Analysis
Design moments:
Spans
MEd = (1.25 30.2 0.090 + 1.5 11.5 0.100) 6.02
= 122.3 + 62.1 = 184.4 kNm
Support
MEd = 50.8 0.106 6.02 = 193.8 kNm

Appendix C1,
Table C3
Table C3

Shear force:
VAB = 0.45 6.0 50.8 = 137.2 kN
VAB = 0.63 6.0 50.8 = 192.0 kN

4.1.5 Flexural design


Effective depth:
Assuming 10 mm links:
d = 450 35 10 25/2 = 392 mm
99

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Flexure in span:
K = MEd/bd2fck = 184.4 106/(300 3922 30) = 0.133
z/d = 0.864
z = 0.864 392 = 338 mm
As = MEd/fydz = 184.4 106/(434.8 338) = 1255 mm2
Try 3 no. H25 B (1473 mm2)
(r = 1.25%)
Check spacing:
Spacing of outer bars = 300 2 35 2 10 25 = 185 mm
Assuming 10 mm diameter link,
= spacing = 98 mm
Steel stress under quasi-permanent loading:
ss = (fyk /gS) (As,req/As,prov) (SLS loads/ULS loads) (1/d)
= fyd (As,req/As,prov) (gk + c2 qk)/(gGgk + gQqk) (1/d)
= (500/1.15) (1255/1473) [(30.2 + 0.3 11.5)/50.8] (1/1.03)
= 434.8 0.91 0.66 0.97 = 237 MPa
As exposure is XC3, max. crack width wmax = 0.3 mm
= Maximum bar size = 16 mm or max. spacing = 200 mm = OK
= Use 3 H25 B (1473 mm2)
Deection:
Check span-to-effective-depth ratio.
Basic span: effective depth ratio for r = 1.25%:
l/d = 18 + [(1.25 0.5)/(1.5/0.5)] (26 18) = 24.0
Max. span = 24.0 392 = 9408 mm
= OK

Fig. 3.5
Appendix A1
Table C5

Cl. 7.3.3(2)
Cl. 7.3.1(5) & NA
Table 7.2N & NA

Appendix B
Table 7.4N & NA

Flexure, support:
MEd = 193.8 kNm
K = MEd/bd2fck
where
d = 450 35 10 25/2 = 392 mm
K = 193.8 106/(300 3922 30) = 0.142
By inspection, K K' (0.142 0.168)
= no compression reinforcement required.
z = 0.85d
= 0.85 392 = 333 mm
As = MEd/fydz
= 193.8 106/434.8 333 = 1338 mm2
Try 3 no. H25 T (1473 mm2)
(r = 1.13%)
K' is limited to 0.208. However, if, as is usual practice in the UK, x/d is limited to
0.45, z/d is as a consequence limited to 0.82 and K' to 0.168.

100

Appendix A1
Table C5

-'*3<hgmbgnhnl[^Zfhgibglniihkml

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

4.1.6 Shear
a) Support B (critical)
Shear at central support = 192.0 kN
At d from face of support
VEd = 192.0 (0.300/2 + 0.392) 50.8 = 164.50 kN
vEd = VEd /bd
= 164.5 103/(392 300) = 1.40 MPa
Maximum shear capacity:
Assuming fck = 30 MPa and cot y = 2.5#
vRd,max* = 3.64 MPa
vRd,max > vEd = OK

Cl. 6.2.1(8)

Table C7

Shear reinforcement:
Assuming z = 0.9d
Asw /s VEd /(0.9d fywd cot y)
164.5 103/(0.9 392 (500/1.15) 2.5) = 0.429

Cl. 6.2.3(1)
Cl. 6.2.3(3),
Exp. (6.8)

More accurately,
Asw/s VEd/(z fywd cot y)
164.5 103/(333 1087) = 0.454

Cl. 6.2.3(3),
Exp. (6.8)

Minimum shear links,


Asw,min/s = 0.08bwfck0.5/fyk
= 0.08 300 300.5/500 = 0.263. Not critical
Max. spacing = 0.75d = 0.75 392 = 294 mm
Use H8 @ 200 (Asw /s = 0.50)
b) Support A (and C)
Shear at end support = 137.2 kN
At face of support,
VEd = 137.2 (0.150 + 0.392) 50.8 = 109.7 kN
By inspection, shear reinforcement required and cot y = 2.5
Asw /s VEd/(z fywd cot y)
109.7 103/[353 (500/1.15) 2.5] = 0.285
Use H8 @ 200 (Asw /s = 0.50) throughout

Where applied actions are predominantly uniformly distributed, shear may be


checked at d from the face of support. See also Section 4.2.11.

Cl. 9.2.2(5)
Cl. 9.2.2(6)

Cl. 6.2.1(8)
Fig. C1a)
Appendix C5.3

Cl. 6.2.1(8)

# The absolute maximum for v


Rd,max (and therefore the maximum value of vEd)
would be 5.28 MPa when cot y would equal 1.0 and the variable strut angle would
be at a maximum of 45.

* For determination of VRd,max see Section 4.2.10.


As maximum spacing of links is 294 mm, changing spacing of links would appear
to be of limited benet.

101

4.1.7 Summary of design


H8 @ 200 centres in 2 legs

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

3H25

3H25B

3H25B

Figure 4.3 Continuous rectangular beam: Summary of design


Commentary
It is usually presumed that the detailer would take the design
summarised above and detail the beam to normal best practice[8,9].
The design would go no further where standard detailing is all that
is required. Where the element is non-standard (e.g. where there
are point loads), it should be incumbent on the designer to give
the detailer specic information about curtailment, laps, etc. as
illustrated below. The detailers responsibilities, standards and
timescales should be clearly dened but it would be usual for the
detailer to draw and schedule not only the designed reinforcement
but all the reinforcement required to provide a compliant and buildable
solution. The work would usually include the checking the following
aspects and providing appropriate detailing:
t Minimum areas
t Curtailment lengths
t Anchorages
t Laps
t U-bars
t Rationalisation
t Critical dimensions
t Details and sections
The determination of minimum reinforcement areas and curtailment
lengths, using the principles in Eurocode 2 is shown below. In practice
these would be determined from published tables of data or by using
reference texts[8,9]. Nonetheless, the designer should check the
drawing for design intent and compliance with the standards. It is
therefore necessary for the designer to understand and agree the
principles of the detailing used.

4.1.8 Detailing checks


a) Minimum areas
As,min = 0.26(fctm/fyk)btd 0.0013btd
where
102

Cl. 9.2.1.1

-'*3<hgmbgnhnl[^Zfhgibglniihkml

bt = width of tension zone


fctm = 0.30 fck0.666

Table 3.1

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

As,min = 0.26 0.30 300.666 300 392/500 = 177 mm2


b) Curtailment of main bars
Bottom: curtail
75% main bars 0.08l from end support = 480 mm say 450 mm from A
70% main bars 0.30l al = 0.3 6000 1.125 d
= 1800 1.125 392
= 1359 mm say 1350 from A
Top: curtail
40% main bars 0.15l + al = 900 + 441
= 1341 mm say 1350 from B
65% main bars 0.30l + al = 1800 + 441
= 2241 mm say 2250 from B

How to: Detailing

At supports:
25% of As to be anchored at supports
25% of 1225 mm2 = 314 mm2
Use min. 2 no. H16 (402 mm2) at supports A, B and C

Cl. 9.2.1.2.(1),
9.2.1.4(1) & NA
Cl. 9.2.1.5(1)

In accordance with SMDSC[9] detail MB1 lap U-bars tension lap with
main steel
= 780 mm (in C30/37 concrete, H12, poor bond condition)
= say 800 mm

How to: Detailing

c) Summary of reinforcement details


2H12T

3H25
100
800
1350

2H16 U-bars

2H12

2H25 2H12 1H25

3H25 2H16
A
450 800

2H12 2H25 1H25

3H25B

2H12T

1350

100
800

1250

2H12

1H25 2H12 2H25


1H25 2H25 2H12

B
800 600 750 750 600 800
2H16B

2H16 U-bars

2H16 2H25
C
800 450
3H25B

Links omitted for clarity

Figure 4.4 Continuous rectangular beam: reinforcement details


Note Subsequent detailing checks may nd issues with spacing rules especially if
the 'cage and splice bar' method of detailing were to be used. 2H32s T&B would be a
suitable alternative to 3H25s T&B.

103

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

-'+ Heavily loaded L-beam


Ikhc^\m]^mZbel

<Ze\neZm^][r

Heavily loaded L-beam

chg

Ch[gh'

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

Gk2 = 88.7
Qk2 = 138.7
gk1 = 46.0
qk1 = 63.3
A

2000
9000

8000

Figure 4.5 Heavily loaded L-beam


This edge beam supports heavy loads from storage loads. The
variable point load is independent of the variable uniformly
distributed load. The beam is supported on 350 mm square
columns 4000 mm long. fck = 30 MPa; fyk = 500 MPa. The
underside surface is subject to an external environment and a
2-hour re resistance requirement. The top surface is internal
and subject to a 2-hour re resistance requirement. Assume that
any partitions are liable to be damaged by excessive deections.
beff

750

350

Figure 4.6 Section through L-beam

4.2.1 Actions
Permanent:
UDL from slab and cladding gk = 46.0 kN/m
Point load from storage area above = 88.7 kN
Variable:
From slab qk = 63.3 kN/m
Point load from storage area above = 138.7 kN
104

CCIP 041
1
Oct 09

-'+3A^ZoberehZ]^]E&[^Zf

4.2.2 Cover

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

a) Nominal cover, cnom, underside and side of beam


cnom = cmin + Dcdev
where
cmin = max[cmin,b ; cmin,dur]
where
cmin,b = minimum cover due to bond
= diameter of bar. Assume 32 mm main bars and
10 mm links
cmin,dur = minimum cover due to environmental conditions.
Assuming primarily XC3/XC4 exposure (moderate
humidity or cyclic wet and dry); secondarily XF1
exposure (moderate water saturation without
de-icing salt, vertical surfaces exposed to rain and
freezing) and C30/37 concrete,
cmin,dur = 25 mm
Dcdev = allowance in design for deviation. Assuming no
measurement of cover Dcdev = 10 mm

Exp. (4.1)

Cl. 4.4.1.2(3)

Table 4.1
BS 8500-1:
Table A4

Cl. 4.4.1.2(3)

= cnom = 32 + 10 = 42 mm to main bars


or = 25 + 10 = 35 mm to links
Use cnom = 35 mm to links (giving cnom = 45 mm to main bars)
b) Fire
Check adequacy of section for 2 hours re resistance REI 120.
By inspection, web thickness OK.
Axis distance, a, required = 35 mm OK by inspection.

EC2-1-2: 5.6.3
EC2-1-2:
Table 5.6
EC2-1-2:
Table 5.6

= Try 35 mm nominal cover bottom and sides to 10 mm link.


Nominal cover, cnom, top:
By inspection,
cnom = cmin + Dcdev

Exp. (4.1)

where
cmin = max[cmin,b; cmin,dur]
where
cmin,b = minimum cover due to bond
= diameter of bar. Assume 32 mm main bars and
10 mm links
cmin,dur = minimum cover due to environmental conditions.
Assuming primarily XC1 and C30/37 concrete,
cmin,dur = 15 mm

Cl. 4.4.1.2(3)

Table 4.1
BS 8500-1:
Table A4

105

-'+3A^ZoberehZ]^]E&[^Zf

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Dcdev = allowance in design for deviation. Assuming no


measurement of cover Dcdev = 10 mm
= cnom = 32 + 10 = 42 mm to main bars
or = 15 + 10 = 25 mm to links
Use cnom = 35 mm to links (giving cnom = 45 mm to main bars)

Cl. 4.4.1.2(3)

4.2.3 Idealisation, load combination and arrangement


Load combination:
As loads are from storage, Exp. (6.10a) is critical.

Table 2.5;
ECO: A1.2.2, NA
& Exp. (6.10a)

Idealisation:
This element is treated as a continuous beam framing into
columns 350 350 4000 mm long columns below.

Cl. 5.3.1(3)

Arrangement:
Choose to use all-and-alternate-spans-loaded.

Cl. 5.1.3(1) &


NA: Table NA.1
(option b)

4.2.4 Analysis
Analysis by computer (spreadsheet TCC 41 Continuous Beam (A+D).xls
in RC spreadsheets V.3[28] assuming frame action with 350 mm square
columns 4 m long xed at base. Beam inertia based on T-section, beff
wide) with 15% redistribution at central support, limited redistribution
of span moment and consistent redistribution of shear.

ECO:
A1.2.2 & NA;
Cl. 5.3.1 (6)

Table 4.2 Elastic and redistributed moments, kNm


Span number
Elastic M
Redistributed M
d

1
1168
1148
0.98

2
745
684
0.92

2000
1394 kNm

1500
1000
500
195 kNm

108 kNm

0
A

500
684 kNm

1000
1500

1148 kNm

Figure 4.7 Redistributed envelope, kNm


Note:

350 350 is a minimum for columns requiring a re resistance of 120


minutes.

106

EC2-1-2:
Table 5.2a

1000
646 kN

794 kN

500

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

0
A

500

C
499 kN

1000
1098 kN
1500

4.2.5 Flexural design, support A


MEd = 195 kNm in hogging
MEd,min = 1148 0.25 in hogging and in sagging
= 287 kNm
K
= MEd/bd2fck
where
b = beff = beff1 + bw + beff2
where
beff1 =
(0.2b1 + 0.1l0) 0.2 l0 b1
where
b1 = distance between webs/2
l0 = nominal: assume 0

= beff1 = 0 mm = beff2

=b = bw = 350 mm
d = 750 35 10 32/2 = 689 mm
assuming 10 mm link and H32 in support.
fck = 30 MPa
K = 287 106/(350 6892 30)
= 0.058
Restricting x/d to 0.45
K' = 0.168
K K' = section under-reinforced and no compression reinforcement
required.
z = (d/2) [1 + (1 3.53K)0.5] 0.95d
= (689/2) (1 + 0.89) 0.95 689
= 652 654 = z = 652 mm
As = MEd/fydz

The distance l0 is described as the distance between points of zero moment,


which may be obtained from Figure 5.2. In this case l0 = 0. (see Figure 4.11).

Cl. 9.2.1.2(1),
9.2.1.4(1) & NA

Cl. 5.3.2.1,
Fig. 5.3

Fig. 5.2

Appendix A1

Appendix A1

Cl. 5.3.2.1(2)
Fig. 5.2
Fig. 4.11
107

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
fyd = 500/1.15 = 434.8 MPa
= 287 106/(434.8 652) = 1012 mm2
Try 2 no. H32 U-bars (1608 mm2)
Check anchorage of H32 U-bars.
Bars need to be anchored distance A into column

SMDSC: 6.4.2

U-bar

Figure 4.9 Distance A


Assuming column uses 35 mm cover, 10 mm links and 32 mm bars:
Distance A = 2 [350 2 (35 + 10) ] 32/2 32/2 + 750 [2 (35
+ 10)] 2 32/2 (4 ) (3.5 + 0.5) 32
= 488 + 628 110 = 1006 mm
Anchorage length,
lbd = alb,rqd lb,min

SMDSC[9],
BS 8666[19]:
Table 2
Cl. 8.4.4,
Exp. (8.4)

where
a = conservatively 1.0
lb,rqd = (f/4) (ssd/fbd)

Exp. (8.3)

where
f = 32
ssd = design stress in the bar at the ULS
= 434.8 1012/1608 = 274 MPa
f[] = ultimate bond stress
= 2.25 n1 n2 fct,d

108

Cl. 8.4.2 (2)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

-'+3A^ZoberehZ]^]E&[^Zf

where
n1 = 1.0 for good bond conditions
n2 = 1.0 for bar diameter 32 mm
fct,d = act fctk/ gC
= 1.0 2.0/1.5
= 1.33 MPa
fbd = 2.25 1.33 = 3.0 MPa
lb,rqd = (32/4) (274/3.0) = 731 mm
lb,min = max[10f; 100 mm] = 250 mm
= lbd = 731 mm i.e. < 1006 mm

Cl. 3.1.6 (2),


Tables 3.1 & 2.1,
& NA

= OK
Use 2 no. H32 U-bars

4.2.6 Flexural design, span AB


a) Span AB Flexure
MEd = 1148 kNm
K = MEd/bd2fck
where
b = beff = beff1 + bw + beff2
where
beff1 = (0.2b1 + 0.1l0) 0.2 l0 b1
where
b1 = distance between webs/2
Assuming beams at 7000 mm cc
= (7000 350)/2 = 3325 mm
l0 = 0.85 l1 = 0.85 9000 = 7650 mm

Cl. 5.3.2.1,
Fig. 5.3

Fig. 5.2

beff
beff,2

beff,1
bw

bw
b1

b1

b2

b2

Figure 4.10 Effective flange width beff


Anchorage lengths may be obtained from published tables. In this instance, a
gure of 900 mm may be obtained from Table 13 of Section 10 of How to design
concrete structures using Eurocode 2.
The

distance l0 is described as the distance between points of zero shear, which


may be obtained from Figure 5.2. From the analysis, l0 could have been taken as
7200 mm.

Fig. 5.3

How to:
Detailing[8]
Cl. 5.3.2.1(2)
Figure 5.2
109

I0 = 0.85 I1

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

I1

I0 = 0.15 (I1+I2)

I0 = 0.7 I2

I3

l0 for calculation of

flange width
beff1 =
=
=
bw =
beff2 =

I0 = 0.15 (I2+I3)

I2

Fig. 5.2
0.2 3325 + 0.1 7650 0.2 7650 3325
1430 1530 3325
1430 mm
350 mm
(0.2b2 + 0.1l0) 0.2 l0 b2

where
b2 = 0 mm
beff2 = 0 mm
b
= 1430 + 350 + 0 = 1780 mm
d = effective depth
= 750 35 10 32/2 = 689 mm
assuming 10 mm link and H32 in span
fck = 30 MPa
K = 1148 106/(1780 6892 30)
= 0.045
Restricting x/d to 0.45,
K' = 0.168
K K' = section under-reinforced and no compression
reinforcement required.
z = lever arm
= (d/2) [1 + (1 3.53K)0.5] 0.95d
= (689/2) (1 + 0.917) 0.95 689
= 661 654 = z = 654 mm
But z = d 0.4x
= by inspection, neutral axis is in ange and as x < 1.25 hf , design as
rectangular section.
As = MEd/fydz
where
fyd = 500/1.15 = 434.8 MPa
= 1148 106/(434.8 654) = 4037 mm2
Try 5 no. H32 B (4020 mm2) (say OK)
Check spacing of bars.
Spacing of bars = [350 2 (35 + 10) 32]/(5 1)
= 57
Clear spacing = 57 32 mm = 25 mm between bars
110

Appendix A1

Appendix A1

Appendix A1

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

-'+3A^ZoberehZ]^]E&[^Zf

Minimum clear distance between bars


= max[bar diameter; aggregate size + 5 mm]
= max[32; 20 + 5]
= 32 mm i.e. > 25 mm
= 5 no. H32 B no good
For 4 bars in one layer, distance between bars = 44 mm so
Try 4 no. H32 B1 + 2 no. H32 B3

Cl. 8.2(2) & NA

300

d
35 cover
400
32 bar
32 spacers
32 bar
10 link
35 cover
350

Figure 4.12 Span AB bottom reinforcement


d = 750 35 10 32/2 0.333 2 32 = 668 mm
K = 1148 106/(1780 6682 30) = 0.048
K K' = section under-reinforced and no compression reinforcement
required.

Appendix A1

z = (d/2) [1 + (1 3.53K)0.5] 0.95d


= (668/2) (1 + 0.911) 0.95 668
= 639 635 = z = 635 mm

Appendix A1

= by inspection, neutral axis in ange so design as rectangular


section.

Appendix A1

As = MEd/fydz
= 1148 106/(434.8 635) = 4158 mm2
= 4 no. H32 B1 + 2 no. H32 B3 (4824 mm2) OK
b) Span AB Deflection
Check end span-to-effective-depth ratio.
Allowable l/d = N K F1 F2 F3
where
N = Basic l/d: check whether r > r0 and whether to use Exp.
(7.16a) or (7.16b)

Appendix B
Appendix C7
Cl. 7.4.2(2),
Exp. (7.16a),
Exp. (7.16b)
111

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

N =
=
=
K =
F1 =

r = As/Ac = As,req/[bwd + (beff bw)hf]


= 4158/[350 668 + (1780 350) 300]
= 4158/662800
= 0.63%
r0 = fck0.5/1000 = 300.5/1000 = 0.55%
r > r0 = use Exp. (7.16b)

PD 6687[6]

11 + 1.5fck0.5 r0/(r r' ) + fck0.5(r'/r0)0.5/12


11 + 1.5 (300.5 0.055/(0.063 0) + 300.5(0/0.55)1.5
11 + 7.2 + 0 = 18.2
(end span) = 1.3
(beff/bw = 1780/350 = 5.1) = 0.80

Exp. (7.16b)

F2 = 7.0/leff (span > 7.0 m)


where
leff = 9000 mm
F2 = 7.0/9.0 = 0.77
F3 = 310/ss 1.5

where
ss in simple situations = (fyk/gS) (As,req/As,prov) (SLS loads/
ULS loads) (1/d). However in this case separate analysis
at SLS would be required to determine ss. Therefore as a
simplication use the conservative assumption:
310/ss = (500/fyk) (As,req/As,prov)
= (500/500) (4824/4158) = 1.16
= Permissible l/d = 18.2 1.3 0.80 0.77 1.16 = 16.9
Actual l/d = 9000/668 = 13.5
Permissible more than actual
= OK
= 4 no. H32 B1 + 2 no. H32 B3 (4824 mm2) OK

Table 7.4N & NA


Cl. 7.4.2(2),
Appendix C7
Cl. 7.4.2(2)
Cl. 5.3.2.2(1)
Cl. 7.4.2, Exp.
(7.17), Table 7.4N
& NA, Table NA.5
Note 5
Appendix B

Exp. (7.17)

4.2.7 Flexural design, support B


At centreline of support B,
M = 1394 kNm
From analysis, at face of support
MEdBA = 1209 kNm
MEdBC = 1315 kNm
K
= MEd/bwd 2fck
2.18 of PD 6687[6] suggests that r in T sections should be based on the area
of concrete above the centroid of the tension steel.

112

Cl. 5.3.2.2(3)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

-'+3A^ZoberehZ]^]E&[^Zf

where
bw = 350 mm
d = 750 35 12 32/2 = 687 mm
assuming 10 mm link and H32 in support but allowing for
H12 T in slab
fck = 30 MPa
= K = 1315 106/(350 6872 30) = 0.265
for d = 0.85, K' = 0.168: to restrict x/d to 0.45, K' = 0.167
= Compression steel required
z = (d/2) [1 + (1 3.53 K')0.5]
= (687/2) [1 + (1 3.53 0.167)0.5]
= (687/2) (1 + 0.64) < 0.95d
= 563 mm
As2 = (K K')fckbd2/fsc(d d2)
where
d2 = 35 + 10 + 32/2 = 61 mm
fsc = 700(x d2)/x < fyd

Appendix A1
Table C4

Fig. 3.5,
Appendix A1,
How to: Beams

where
x = 2.5 (d z) = 2.5 (687 563) = 310 mm
fsc = 700 (310 61)/310 < 500/1.15
= 562 MPa but limited to 434.8 MPa
=As2 = (0.265 0.167) 30 350 687 2/[434.8(687 61) ] = 1784 mm2
Try 4 no. H25 B (1964 mm2)
As = M'/fydz + As2 fsc/fyd
= K' fck bd 2 /(f yd z) + As2 fsc/fyd
= 0.167 30 350 6872/(434.8 563) + 1570
434.8/434.8
= 3380 + 1784 = 5164 mm2
Try 4 no. H32 T + 4 no. H25 T (5180 mm2)

Appendix A1

This reinforcement should be spread over beff.


beff = beff1 + bw + beff2

Cl. 9.2.1.2(2),
Fig. 9.1
Cl. 5.3.2.1,
Fig. 5.3

where
beff1

= (0.2b1 + 0.1l0) 0.2 l0 b1

where
b1 = distance between webs/2.
Assuming beams at 7000 mm cc
= (7000 350)/2 = 3325 mm
l0 = 0.15 (l1 + l2)
= 0.15 (9000 + 8000) = 2550 mm

Fig. 5.2

113

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

=beff1 =
=
=
bw =
beff2 =

0.2 3325 + 0.1 2550 0.2 2550 3325


920 510 3325
510 mm
350 mm
(0.2b2 + 0.1l0) 0.2 l0 b2

where
b2 = 0 mm
beff2 = 0 mm
= beff = 510 + 350 + 0 = 860 mm
Use 4 no. H32 T + 4 no. H25 T (5180 mm2) @ approx 100 mm cc
beff = 860 mm

4H32

4H25

4H25

bw = 350 mm

Figure 4.13 Support


pp
B reinforcement

4.2.8 Flexural design, span BC


a) Span BC Flexure
MEd = 684 kNm
K = MEd/bd2fck
where
b = beff = beff1 + bw + beff2
where
beff1 = (0.2b1 + 0.1l0) 0.2 l0 b1
where
b1 = distance between webs/2.
Assuming beams at 7000 mm cc
= (7000 350)/2 = 3325 mm
l0 = 0.85 l1 = 0.85 8000 = 6800 mm
beff1 = 0.2 3325 + 0.1 6800 0.2 6800 3325
= 1345 1360 3325
= 1360 mm
114

Cl. 5.3.2.1, Fig. 5.3

Fig. 5.2

-'+3A^ZoberehZ]^]E&[^Zf

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

bw = 350 mm
beff2 = (0.2b2 + 0.1l0) 0.2 l0 b2
where
b2 = 0 mm
beff2 = 0 mm

= b = 1360 + 350 + 0 = 1710 mm
d = 750 35 10 32/2 = 689 mm
assuming 10 mm link and H32 in span.
fck = 30 MPa
= K = 684 106/ (1710 6892 30)
= 0.028
By inspection, K K' = section under-reinforced and no compression
reinforcement required.

Appendix A1

z = (d/2) [1 + (1 3.53K)0.5] 0.95d


= (689/2) (1 + 0.95) 0.95 689
= 672 > 655 = z = 655 mm

Appendix A1

By inspection, x < 1.25 hf ; design as rectangular section

Appendix A1

As = MEd/fydz
= 684 106/(434.8 655) = 2402 mm2
Try 2 no. H32 B + 2 no. H25 B (2590 mm2)
b) Span BC Deflection
By inspection, compared with span AB

OK

4.2.9 Flexural design, support C


By inspection, use 2 no. H25 U-bars as support A.
Use 2 no. H25 U-bars

4.2.10 Design for beam shear, support A


At d from face of support
VEd = 646 (350/2 + 0.689) (1.35 46.0 + 1.5 63.3)

= 646 0.864 157.1 = 510.3 kN


Check maximum shear resistance.
VRd, max = acw bw zvfcd/(cot y + tan y)
where
acw = 1.0
bw = 350 mm as before
z = 0.9d

Cl. 6.2.1(8)
ECO: A1.2.2, NA
& Exp. (6.10a)

Exp. (6.9) & NA


Cl. 6.2.3 & NA
Cl. 6.2.3(1)

115

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

= 0.6 (1 fck/250) = 0.6 (1 30/250) = 0.528

fcd = 30/1.5 = 20.0 MPa


y = angle of inclination of strut.
= 0.5 sin1 {vEd,z /[0.20 fck (1 fck /250) ] } cot12.5
where
vEd,z = VEd/bz = VEd /(b 0.9d)
= 510.3 103/(350 0.9 689) = 2.35 MPa
y = 0.5 sin1 {2.35/[0.20 30 (1 30/250) ] } cot12.5
= 0.5 sin1 (0.445) cot12.5
= 0.5 26.4 21.8
= 21.8
= VRd,max = 1.0 350 0.90 689 0.528 20.0/(2.5 + 0.4) = 790 kN
= OK
Shear reinforcement:
Shear links: shear resistance with links
VRd,s = (Asw /s) z fywd cot y
= Asw /s VEd/z fywd cot y
where
Asw/s = area of legs of links/link spacing
z
= 0.9d as before
fywd = 500/1.15 = 434.8
cot y = 2.5 as before
Asw/s 510.3 103/(0.9 689 434.8 2.5) = 0.76
Minimum Asw/s = rw,minbwsin a
where
rw,min = 0.08 fck0.5/fyk = 0.08 300.5/500
bw
a

Cl. 6.2.3(3)
Note 1, Exp.
(6.6N) & NA
Cl. 2.4.2.4(1) & NA
Exp. (6.9),
Appendix A2

Exp. (6.8)

Cl. 2.4.2.4(1)
& NA

Cl. 9.2.2(5),
Exp. (9.4)
Exp. (9.5N) & NA

= 0.00088
= 350 mm as before
= angle between shear reinforcement and the longitudinal
axis. For vertical reinforcement sin a = 1.0

= Minimum Asw/s = 0.00088 350 1 = 0.03


But,
maximum spacing of links longitudinally = 0.75d = 516 mm
= Try H10 @ 200 cc in 2 legs (Asw /s = 0.78)

Cl. 9.2.2(6)

4.2.11 Design for high beam shear, support B


As uniformly distributed load predominates consider at d from
face of support.

116

Cl. 6.2.1(8)

-'+3A^ZoberehZ]^]E&[^Zf

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

VEd = 1098 (350/2 + 0.689) (1.35 46.0 + 1.5 63.3)


= 1098 0.864 157.1 = 962.3 kN
By inspection, shear reinforcement required and cot y < 2.5.
Check VRd, max (to determine y)
Check maximum shear resistance.
As before,
VRd, max = a\p bw zvfcd/(cot y + tan y).
where
acw, bw, z, v and fcd as before
y = 0.5 sin1 {vEd,z/[0.20 fck (1 fck/250) ] } cot12.5
where
vEd,z = VEd/bz = VEd/(b0.9d)
= 962.3 103/(350 0.9 687) = 4.45 MPa
y = 0.5 sin1 {4.45/[0.20 30 (1 30/250) ] } cot12.5
= 0.5 sin1 (0.843) cot12.5
= 0.5 57.5 21.8
= 28.7
cot y = 1.824 i.e. > 1.0 =OK
tan y = 0.548
= VRd,max = 1.0 350 0.90 687 0.528 20.0/(1.824 + 0.548)
= 963.4 kN
OK
(i.e. VRd,max VEd)
Shear reinforcement:
Shear links: shear resistance with links
VRd,s = (Asw/s)zfywd cot y
= Asw/s VEd/zfywd cot y
Asw/s 962.3 103/(0.9 687 434.8 1.824) = 1.96
= Use H10 @ 150 cc in 4 legs (Asw /s = 2.09)

4.2.12 Design for beam shear (using design chart),


support BC

At d from face of support,


VEd = 794 0.864 157.1 = 658.3 kN
vEd,z = VEd/bz = VEd/(b0.9d)
= 658.3 103/ (350 0.9 687) = 3.04 MPa
From chart Asw /sreqd/m width = 2.75
Asw /sreqd = 2.75 0.35 = 0.96
= Use H10 in 2 legs @ 150 mm cc (Asw/s = 1.05)

Exp. (6.9) & NA

Exp. (6.9)
Cl. 6.2.3(1)
Exp. (6.9)

Cl. 6.2.3(2) & NA

Exp. (6.8)

Cl. 6.2.1(8)

Fig. C1b)

117

4.2.13 Check shear capacity for general case


In mid span use H10 in 2 legs @ 300 mm cc (Asw/s = 0.52)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

z Asw/sreqd/m width = 1.48 and an allowable vEd,z = 1.60 MPa


z 1.60 350 0.90 687 = VEd = 346 kN

Fig. C1b)

From analysis, VEd = 346.2 kN occurs at:


(646 346)/157.1
= 1900 mm from A,
(1098 346 1.25 88.7 1.5 138.7)/157.1 = 2755 mm from BA,
(794 346)/157.1
= 2850 mm from BC
and
(499 346)/157.1
= 970 mm from C

4.2.14 Summary of design


1
H10 links in 2 legs @ 150cc
2H32 U-bars

4H32 + 4H25T

2H25 U-bars

H10 links in 2 legs

@ 150

@ 300

@ 150

@ 150

4H32 B1 + 2H32 B3

4H25B

B
1950

2850

2850
1

Figure 4.14 Summary of L-beam design

4H32

4H25

350

510

H10 in 4 legs
@ 150

Figure 4.15 L-beam section 11

118

@ 300

@ 150

2H32 + 2H25B
C
1050

-',3<hgmbgnhnlpb]^M&[^Zf
-', Continuous wide T-beam
Ikhc^\m]^mZbel

<Ze\neZm^][r

Continuous wide T-beam

chg

Ch[gh'

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

CCIP 041
1
Oct 09

qk = 45.8 kN/m
gk = 47.8 kN/m
A

B
7500

C
7500

D
7500

E
7500

Figure 4.16 Continuous wide T-beam


This central spine beam supports the ribbed slab in Example 3.3.
The 300 mm deep ribbed slab is required for an office to support
a variable action of 5 kN/m2. The beam is the same depth as the
slab and is supported on 400 mm square columns, see Figure
4.17. fck = 35 MPa; fyk = 500 MPa. A 1-hour fire resistance is
required in an internal environment. Assume that partitions are
liable to be damaged by excessive deflections.
CL

100
200

1000

200

800

Figure 4.17 Section through T-beam

4.3.1 Actions
Permanent, UDL:
From analysis of slab, gk = 47.8 kN/m
Variable:
From analysis of slab, qk = 45.8 kN/m
The actions may also have been estimated assuming an elastic reaction factor
of 1.1 for the slab viz:
kN/m
Permanent: UDL
Loads from ribbed slab (7.50 + 9.0)/2 4.30 1.1 =
39.0
Self-weight/patch load extra over solid 2.0 4.17 =
8.3
47.3
Variable:
Imposed (7.50 + 9.0)/2 5.00 1.1 =
45.4

119

4.3.2 Cover
Nominal cover, cnom:
cnom = cmin + Dcdev

Exp. (4.1)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
cmin = max[cmin,b; cmin,dur]
where
cmin,b = minimum cover due to bond
= diameter of bar. Assume 25 mm main bars and
8 mm links
cmin,dur = minimum cover due to environmental conditions.
Assuming XC1 and C30/37 concrete, cmin,dur = 15 mm
Dcdev = allowance in design for deviation. Assuming no
measurement of cover Dcdev = 10 mm
= cnom = 15 + 10 = 25 mm to links
or = 25 + 10 = 35 mm to main bars
Use 10 mm diameter links to give cnom = 35 mm to main bars
and 25 mm to links (as per ribbed slab design).
Fire:
Check adequacy of section for REI 60.
Axis distance required:
Minimum width bmin = 120 mm with a = 25 mm
or
bmin = 200 mm with a = 12 mm
= at 2000 mm wide (min.) a < 12 mm
By inspection, not critical.
Use 25 mm nominal cover to links

Cl. 4.4.1.2(3)
Table 4.1
BS 8500-1;
Table A4
Cl. 4.4.1.2(3)

EC2-1-2: 5.6.3
EC2-1-2:
Table 5.6
EC2-1-2:
Table 5.6

4.3.3 Idealisation, load combination and arrangement


Load combination:
By inspection, Exp. (6.10b) is critical.
47.8 1.25 + 45.8 1.5 = 128.5 kN/m

Fig. 2.5
EC0: Exp. (6.10b)

Idealisation:
This element is treated as a beam on pinned supports.
The beam will be provided with links to carry shear and to
accommodate the requirements of Cl. 9.2.5 indirect support of
the ribbed slab described in Section 3.3.8.
Arrangement:
Choose to use all-and-alternate-spans-loaded.

120

cf. 126.7 kN/m from analysis of slab (63.2 kN/m + 63.5 kN/m). See Figure 3.12.

Cl. 5.1.3(1) &


NA: Table NA.1
(option b)

-',3<hgmbgnhnlpb]^M&[^Zf

4.3.4 Analysis

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Analysis by computer, assuming simple supports and including


15% redistribution at supports (with in this instance consequent
redistribution in span moments).

EC0: A1.2.2 &


NA;
Cl. 5.3.1 (6)
5.3.1(6)

Table 4.3 Elastic and redistributed moments, kNm


Span number

Elastic M

641.7

433.0

433.0

641.7

Redistributed M

606.4

393.2

393.2

606.4

0.945

0.908

0.908

0.945

800

657.4 kNm

600

657.4 kNm
516.0 kNm

400
200
0
200

400

393.2 kNm

600

393.2 kNm

606.4 kNm

606.4 kNm

800

Figure 4.18 Redistributed envelope, kNm


800
569.1 kN

600
400

517.9 kN
394.6 kN

462.6 kN

200
0
200

400
462.6 kN
600

395.6 kN
517.9 kN

569.1 kN

800

Figure 4.19 Redistributed shears, kN


121

4.3.5 Flexural design, span AB

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

a) Span AB (and DE) Flexure


MEd = 606.4 kNm
K = MEd/bd2fck
where
b = beff = beff1 + bw + beff2
where
beff1 = (0.2b1 + 0.1l0) 0.2l0 b1
where
b1 = distance between webs/2
Referring to Figures 3.8 and 3.9
= (7500 1000 550)/2 = 2975 mm
l0 = 0.85 l1 = 0.85 7500 = 6375 mm
beff1 = 0.2 2975 + 0.1 6375 0.2 6375 2975
= 1232 1275 2975
= 1232 mm
bw = 2000 mm
beff2 = (0.2b2 + 0.1l0) 0.2 l0 b2
where
b2 = distance between webs/2.
Referring to Figures 3.8 and 3.9
= (9000 1000 550)/2 = 3725 mm
l0 = 6375 mm as before
beff2 = 0.2 3725 + 0.1 6375 0.2 6375 3725
= 1382 1275 3725
= 1275 mm

Cl. 5.3.2.1,
Fig. 5.3

Fig. 5.2

b = 1232 + 2000 + 1275 = 4507 mm


d = 300 25 10 25/2 = 252 mm
assuming 10 mm link and H25 in span.
fck = 35 MPa
K = 606.4 106/(4507 2522 35)
= 0.061
K' = 0.207
or restricting x/d to 0.45
K' = 0.168
K K' = section under-reinforced and no compression
reinforcement required.
z = (d/2) [1 + (1 3.53K)0.5] 0.95d
= (252/2) (1 + 0.886) 0.95 252
= 238 239 = z =238 mm
122

Appendix A1

Appendix A1

-',3<hgmbgnhnlpb]^M&[^Zf

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

But z = d 0.4 x
= x = 2.5(d z) = 2.5( 252 236) = 32 mm
= neutral axis in ange.
Asx < 1.25hf design as rectangular section.
As = MEd/fydz
where
fyd = 500/1.15 = 434.8 MPa
= 606.4 106/(434.8 239) = 5835 mm2
Try 12 no. H25 B (5892 mm2)
b) Span AB Deflection
Check span-to-effective-depth ratio.
Allowable l/d = N K F1 F2 F3
where
N = Basic l/d: check whether r > r0 and whether to use Exp.
(7.16a) or (7.16b)
r =
=
=
=
r0 =
N =
=
=
K =
F1 =

As/Ac = As,req/[bw d + (beff bw)hf]


5835/[2000 252 + (4507 2000) 100]
5835/754700
0.77%
fck0.5/1000 = 300.5/1000 = 0.59%
r > r0 = use Exp. (7.16b)

11 + 1.5fck0.5 r0/(r r') + fck0.5(r'/r0)0.5/12


11 + 1.5 (350.5 0.059/(0.077 0) + 350.5(0/0.59)1.5
11 + 6.8 + 0 = 17.8
(end span) = 1.3
(beff/bw = 4057/2000 = 2.03) = 0.90

F2 = 7.0/leff (span > 7.0 m)


where
leff = 7100 + 2 300/2 = 7400 mm
F2 = 7.0/7.4 = 0.95
F3 = 310/ss 1.5
where
ss = (fyk/gS) (As,req/As,prov) (SLS loads/ULS loads) (1/d)
= 434.8 (5835/5892) [(47.8 + 0.3 45.8)/(1.25
47.8 + 1.5 45.8)] (1/0.945)
= 434.8 0.99 0.48 1.06
= 219 MPa

Appendix A1

Appendix B
Appendix C7
Cl. 7.4.2(2),
Exp. (7.16a),
Exp. (7.16b)
PD 6687[6]

Exp. (7.16b)

Table 7.4N & NA


Cl. 7.4.2(2),
Appendix C7
Cl. 7.4.2(2),
5.3.2.2(1)

Cl. 7.4.2, Exp.


(7.17), Table 7.4N
& NA, Table NA.5
Note 5

2.18 of PD 6687[6] suggests that r in T sections should be based on the area


of concrete above the centroid of the tension steel.

See Appendix B1.5


123

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

F3 = 310/ss
= 310/219 = 1.41
= Permissible l/d = 17.8 1.3 0.90 0.95 1.41 = 27.9
Actual l/d = 7500/252 = 29.8
= no good
Try 13 no. H25 B (6383 mm2)
F3 = 310/ss
= 310/219 13/12 = 1.53 = say 1.50
= Permissible l/d = 17.8 1.3 0.90 0.95 1.50 = 29.7
Say OK
Actual leff /d = 7400/252 = 29.4
Use 13 no. H25 B (6383 mm2)

4.3.6 Flexural design, support B (and D)


At centreline of support:
M
= 657.4 kNm
At face of support:
MEd = 657.4 0.2 517.9 + 0.202 128.5/2
= 657.4 101.0
= 556.4 kNm
K
= MEd/bwd2fck

Cl. 5.3.2.2(3)

where
bw = 2000 mm
d = 300 25 cover 12 fabric 8 link 16 bar 25/2 bar
= 226 mm
25 cover
12 fabric
8 link
16 bar

20 bar
8 link
25 cover

16 bar
25 bar
8 link
25 cover

Figure 4.20 Section at rib-beam interface


K = 556.4 106/(2000 2262 35) = 0.156
By inspection, K < K'
K' = 0.167 maximum (or for d = 0.85, K' = 0.168)
= No compression steel required.

Appendix A1
Table C.4

Both

NA, Table NA.5

As,prov/As,req and any adjustment to N obtained from Exp. (7.16a) or Exp.


(7.16b) is restricted to 1.5 by Note 5 to Table NA.5 in the UK NA.

124

-',3<hgmbgnhnlpb]^M&[^Zf

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

z = (226/2)[1 + (1 3.53 K' )0.5]


= (226/2)[1 + (1 3.53 0.156)0.5]
= (226/2) (1 + 0.67) < 0.95d
= 189 mm
As = MEd/fydz
= 556.4 106/(434.8 189) = 6770 mm2
Try 14 no. H25 T (6874 mm2)
To be spread over beff
beff = beff1 + bw + beff2
where
beff1 = (0.2b1 + 0.1l0) 0.2l0 b1
where
b1 referring to Figure 3.9
= (7500 1000 550)/2 = 2975 mm
l0 = 0.15 (l1 + l2) = 0.15 (7500 + 7500) = 2250 mm
beff1 = 0.2 2975 + 0.1 2250 0.2 2250 2975
= 820 450 2975
= 450 mm
bw = 2000 mm
beff2 = 450 mm as before
= beff = 450 + 2000 + 450 = 2900 mm

Cl. 9.2.1.2(2),
Fig. 9.1
Cl. 5.3.2.1,
Fig. 5.3

Fig. 5.2

Check cracking:
Spacing = 2900 2 (25 10 25/2)/(14 1) = 216 mm
ss = (fyk/gS) (As,req/As,prov) (SLS loads/ULS loads) (1/d)
= 434.8 (6770/6874) [ (47.8 + 0.3 45.8)/
(1.25 47.8 + 1.5 45.8) (1/0.85)
= 434.8 0.98 0.48 1.18 = 241 MPa

Cl. 7.3.3

As loading is the cause of cracking satisfy either Table 7.2N or Table 7.3N

Cl. 7.3.3(2) &


Note

For wk = 0.4 and ss = 240 MPa max. spacing = 250 mm

= OK

Table 7.3N

4.3.7 Flexural design, span BC (and CD similar)


a) Flexure
MEd = 393.2 kNm
K = MEd/bd2fck
where
b = beff = beff1 + bw + beff2
where
beff1 = (0.2b1 + 0.1l0) 0.2l0 b1

Cl. 5.3.2.1,
Fig. 5.3

125

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
b1 referring to Figure 3.9
= (7500 1000 550)/2 = 2975 mm
l0 = 0.70 l2 = 0.7 7500 = 5250 mm
beff1 = 0.2 2975 + 0.1 5250 0.2 5250 2975
= 1120 1050 2975
= 1050 mm
bw = 2000 mm
beff2 = (0.2b2 + 0.1l0) 0.2l0 b2

Fig. 5.2

where
b2 = distance between webs/2
Referring to Figures 3.8 and 3.9
= (9000 1000 550)/2 = 3725 mm
l0 = 5250 mm as before
beff2 = 0.2 3725 + 0.1 5250 0.2 5250 3725
= 1270 1050 3725
= 1270 mm
b = 1050 + 2000 + 1270 = 4320 mm
d = 252 mm as before
assuming 10 mm link and H25 in span
fck = 30
K = 393.2 106/(4320 2522 35)
= 0.041
By inspection, K K' = section under-reinforced and no compression
reinforcement required.

Appendix A1

z = (d/2) [1 + (1 3.53K)0.5] 0.95d


= (252/2) (1 + 0.924) 0.95 252
= 242 > 239 = z = 239 mm
By inspection, x < 1.25 hf = design as rectangular section

Appendix A1

As = MEd/fydz
= 393.2 106/(434.8 239) = 3783 mm2
Try 8 no. H25 B (3928 mm2)
b) Deflection
By inspection, compared to span AB
OK
But for the purposes of illustration:
Check span-to-effective-depth ratio.
Allowable l/d = N K F1 F2 F3
where
N = Basic l/d: check whether to use Exp. (7.16a) or (7.16b)

126

Appendix A1

Appendix B
Appendix C7
Cl. 7.4.2(2)

-',3<hgmbgnhnlpb]^M&[^Zf

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

r0 = 0.59% (for fck = 35)


r = As/Ac = As,req /[bwd + (beff bw)hf]
where
bw = 2000 mm
r = 3783/(2000 252 + (4320 2000) 100)
= 3783/736000
= 0.51%
r < r0 = use Exp. (7.16a)
N =
=
=
=
K =
F1 =

11 + 1.5fck0.5 r0 /r + 3.2fck0.5(r0 /r 1)1.5


11 + 1.5 350.5 0.059/0.051 + 3.2 350.5(0.059/0.051 1)1.5
11 + 10.2 + 23.5 = 17.8
44.7
(internal span) = 1.5
(beff/bw = 4320/2000 = 2.16) = 0.88

F2 = 7.0/leff = 7.0/7.4 = (span > 7.0 m) = 0.95


F3 = 310/ss 1.5

Exp. (7.16a)

Table 7.4N & NA


Cl. 7.4.2(2),
Appendix C7
Cl. 7.4.2(2)
Cl. 7.4.2,
Exp. (7.17)
Table 7.4N, &
NA, Table NA.5
Note 5

where
ss = (fyk/gS) (As,req/As,prov) (SLS loads/ULS loads) (1/d)
= 434.8 (3783/3828) [(47.8 + 0.3 45.8)/(1.25
47.8 + 1.5 45.8)] (1/0.908)
= 434.8 0.99 0.48 1.10
= 227 MPa
F3 = 310/ ss
= 310/227 = 1.37
= Permissible l/d = 44.7 1.37 0.88 0.95 1.37 = 70.1
Actual l/d = 7500/252 = 29.8
= OK
Use 8 no. H25 B (3928 mm2)#
c) Hogging
Assuming curtailment of top reinforcement at 0.30l + al,
From analysis MEd
at 0.3l from BC (& DC) = 216.9 kNm
at 0.3l from CB (& CD) = 185.6 kNm
K = 216.9 106/(2000 2262 35) = 0.061
By inspection, K < K'

How to: Detailing

2.18 of PD 6687[6] suggests that r in T sections should be based on the area


of concrete above the centroid of the tension steel.
See
#

Appendix B1.5

12 no. H20 B (3768 mm2) used to suit nal arrangement of links.


127

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

(226/2)[1 + (1 3.53 K')0.5]


(226/2)[1 + (1 3.53 0.061)0.5]
(226/2) (1 + 0.89) < 0.95d
214 mm < 215 mm
MEd/fydz
216.9 106/(434.8 214) = 2948 mm2
Use 12 no. H20 T (3748 mm2)
(to suit links and bottom steel)
Top steel at supports may be curtailed down to 12 no. H20 T at
0.3l + al = 0.3 7500 + 1.25 214 = 2518 say 2600 mm from
centreline of support.
z =
=
=
=
As =
=

Cl. 9.2.1.3(2)

4.3.8 Flexural design, support C


At centreline of support,
M = 516.0 kNm
At face of support,
MEd = 516.0 0.2 462.6 + 0.202 128.5/2
= 516.0 90.0
= 426.0 kNm
K = MEd/bwd2fck

Cl. 5.3.2.2(3)

where
bw = 2000 mm
d = 226 mm as before
K = 426.0 106/(2000 2262 35) = 0.119
By inspection, K < K'
z

= (226/2) [1 + (1 3.53K)0.5]
= (226/2) [1 + (1 3.53 0.119)0.5]
= (226/2) (1 + 0.76) < 0.95d
= 199 mm

As = MEd/fydz
= 426.0 106/(434.8 199) = 4923 mm2
Try 10 no. H25 T (4910 mm2)

4.3.9 Design for beam shear


a) Support A (and E)
At d from face of support,
VEd = 394.6 (0.400/2 + 0252) 128.5 = 336.5 kN
Maximum shear resistance:
By inspection, VRd,max OK and cot y = 2.5

128

12 no. H25 used to suit nal arrangement of links.

Cl. 6.2.1(8)

-',3<hgmbgnhnlpb]^M&[^Zf

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

However, for the purpose of illustration: check shear capacity,


VRd,max = acw bw zvfcd/ (cot y + tan y)
where
acw =
bw =
z =
v =
fcd =
y =

Exp. (6.9) & NA


1.0
2000 mm as before
0.9d
0.6 [1 fck/250] = 0.516
35/1.5 = 23.3 MPa
angle of inclination of strut.
By inspection, cot1 y << 21.8. But cot y restricted to
2.5 and = tan y = 0.4.

VRd,max = 1.0 2000 0.90 252 0.516 23.3/(2.5 + 04)


= 2089.5 kN
= OK
Shear links: shear resistance with links
ORd,s = (Asw/s) z fywd cot y VEd
= for VEd VRd,s
Asw /s VEd/z fywd cot y
where
Asw /s
z
fywd
cot y

=
=
=
=

Cl. 6.2.3(1)

Cl. 6.2.3(2)
& NA

Exp. (6.8)

area of legs of links/link spacing


0.9d as before
500/1.15 = 434.8
2.5 as before

Asw /s 336.5 103/(0.9 252 434.8 2.5) = 1.36


Minimum Asw /s = rw,minbwsin a

Cl. 9.2.2(5),
Exp. (9.4)

where
rw,min = 0.08 fck0.5/fyk = 0.08 350.5/500 = 0.00095

Exp. (9.5N) & NA

= 2000 mm as before
= angle between shear reinforcement and the longitudinal axis.
For vertical reinforcement sin a = 1.0
Minimum Asw /s = 0.00095 2000 1 = 1.90
But,
maximum spacing of links longitudinally = 0.75d = 183 mm
Maximum spacing of links laterally = 0.75d 600 mm = 183 mm
H10s required to maintain 35 mm cover to H25
= Use H10 @ 175 cc both ways
i.e. H10 in 12 legs @ 175 mm cc (Asw /s = 5.38)
bw
a

Cl. 9.2.2(6)
Cl. 9.2.2(8)

(2000 mm 2 25 mm cover 10 mm diameter)/175 = 11 spaces, = 12 legs.

129

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

b) Support B (and C and D)


By inspection, the requirement for minimum reinforcement and, in
this instance, for H10 legs of links will outweigh design requirements.
Nonetheless check capacity of Asw/s = 5.38
VRd,s = (Asw/s) z fywd cot y
= 5.38 0.9 252 434.8 2.5 = 1326.3 kN
Maximum shear at support = 517.9 kN
i.e. capacity of minimum links not exceeded.
By inspection, the requirement for indirect support of the ribs of the
slab using 87 mm2/rib within 150 mm of centreline of ribs (at 900 mm
centres) and within 50 mm of rib/solid interface is adequately catered
for and will not unduly effect the shear capacity of the beam.
Use 150 mm centres to tie in with 900 mm centres of ribs

Exp. (6.8)

Cl. 9.2.5,
Section 3.4.8

= Use H10 in 12 legs @ 150 mm cc (Asw/s = 6.28) throughout beam

4.3.10 Check for punching shear, column B


As the beam is wide and shallow it should be checked for punching shear.
At B, applied shear force, VEd = 569.1 + 517.9 = 1087.0 kN.
Check at perimeter of 400 400 mm column:
vEd = b VEd/uid < vRd,max
where
b = factor dealing with eccentricity; recommended value 1.15
VEd = applied shear force
ui = control perimeter under consideration. For punching shear
adjacent to interior columns u0 = 2(cx + cy) = 1600 mm
d = mean d = (245 + 226)/2 = 235 mm
= 1.15 1087.0 103/1600 235 = 3.32 MPa
vEd
vRd,max = 0.5vfcd
where
v = 0.6(1 fck/250) = 0.516
fcd = acclfck/gC = 1.0 1.0 35/1.5 = 23.3
vRd,max = 0.5 0.516 23.3 = 6.02 MPa
= OK
Check shear stress at basic perimeter u1 (2.0d from face of column):
vEd = bVEd /u1d < vRd,c
where
b, VEd and d as before

In this case, at the perimeter of the column, it is assumed that the strut angle
is 45, i.e. that cot y = 1.0. In other cases, where cot y < 1.0, vRd,max is available
from Table C7.
130

Cl. 6.4.3(2),
6.4.5(3)

Fig. 6.21N & NA


Cl. 6.4.5(3)
Exp. (6.32)
Cl. 6.4.5(3) Note
Exp. (6.6) & NA
Table C7
Cl. 6.4.2

Fig. 6.13

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

-',3<hgmbgnhnlpb]^M&[^Zf

u1 = control perimeter under consideration. For punching shear


at 2d from interior columns
= 2(cx + cy) + 2 2d
= 1600 + 2 2 235 = 4553 mm
vEd = 1.15 1087.0 103/4553 235 = 1.17 MPa
vRd,c = 0.18/ gC k (100 rlfck)0.333
where
gC = 1.5
k = 1 + (200/d)0.5 2
= 1 +(200/235)0.5 = 1.92
rl = (rly, rlz)0.5
where
rly, rlz = Reinforcement ratio of bonded steel in the y and
z direction in a width of the column plus 3d each
side of column.
= 6874/(2000 226) = 0.0152
= 741/(900 245) = 0.0036
rlz
rl = (0.0152 0.0036)0.5 = 0.0074
fck = 35
vRd,c = 0.18/1.5 1.92 (100 0.0074 35)0.333 = 0.68 MPa
= punching shear reinforcement required
Shear reinforcement (assuming rectangular arrangement of links):
At the basic control perimeter, u1, 2d from the column:
Asw (vEd 0.75vRd,c) sr u1 /1.5fywd,ef)
where
sr
= 175 mm
fywd,ef = effective design strength of reinforcement
= (250 + 0.25d) < fyd = 309 MPa

Exp. (6.47) & NA

Cl. 6.4.4.1(1)

Table C6#

Exp. (6.52)
Cl. 9.4.3(1)
Cl. 6.4.5(1)

For perimeter u1
Asw = (1.17 0.75 0.68) 175 4553/(1.5 309) = 1135 mm2 per
perimeter
Try 15 no. H10 (1177 mm2)

See Section 3.4.14 with respect to possible limit of 2.0 or 2.5 on V /V


Ed Rd,c
within punching shear requirements.
#

vRd,c for various values of d and rl is available from Table C6.


131

By inspection of Figure 4.21. the equivalent of 14 locations are


available between 70 mm and 117 mm from face of column therefore
say OK.
CL
900
470

200 200

470

150 150 150 150 150 150

H10 legs
of links

CL

175 175 175 175 175 175

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Check availability of reinforcement:


1st perimeter to be > 0.3d but < 0.5d, i.e between 70 mm and 117
mm from face of column. Say 0.4d = 100 mm from face of column.

s = 150 mm
u1

600
70

24 H10 legs
in u1 perimeter
58

Figure 4.21 Shear links and punching shear perimeter u1


Perimeter at which no punching shear links are required:
uout = VEd b/(d vRd,c)
uout = 1087 1.15 103/(235 0.68) = 7826 mm
Length of column faces = 4 400 = 1600 mm
Radius to uout = (7823 1600)/2 = 990 mm
from face of column i.e. in ribs, therefore beam shear governs

The same area of shear reinforcement is required for all perimeters inside or
outside perimeter u1. See Section 3.4.13.

Punching shear reinforcement is also subject to requirements for minimum


reinforcement and spacing of shear reinforcement (see Cl. 9.4.3). The centre of
links from the centreline of the column shown in Figure 4.21 have been adjusted to
accommodate a perimeter of links at between 0.3d and 0.5d from the column face.
132

Fig. 9.10,
9.4.3(4)

-',3<hgmbgnhnlpb]^M&[^Zf

4.3.11 Summary of design


X

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

H10 links in
12 legs @ 150 cc

12H20T
14H25T

B
13H25B

12H20T
12H25T

C
12H20B

14H25T

D
12H20B

E
13H25B

Figure 4.23 Section XX

133

. Columns
.') General
Ma^\Ze\neZmbhglbgmabll^\mbhgbeenlmkZm^3

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

.'*=^lb`gh_Zghg&le^g]^k^]`^\henfgnlbg`aZg]\Ze\neZmbhg'
.'+=^lb`gh_Zi^kbf^m^k\henfgnlbg`bm^kZmbhgh_^jnZmbhglmh]^m^kfbg^k^bg_hk\^f^gm
k^jnbk^f^gml'
.',=^lb`gh_Zgbgm^kgZe\henfgpbmaab`aZqbZeehZ]'
.'-=^lb`gh_Zle^g]^k\henfgk^jnbkbg`Zmph&ahnkk^k^lblmZg\^'
Bg`^g^kZe%ZqbZeehZ]lZg]klmhk]^kfhf^gmlZk^Zllnf^]mh[^ZoZbeZ[e^'Ma^]^lb`gl\hglb]^k
le^g]^kg^llbghk]^kmh]^m^kfbg^]^lb`gfhf^gml%F>]'Ma^\henfglZk^]^lb`g^]Zg]\a^\d^]
_hk[bZqbZe[^g]bg`'Ma^^__^\mlh_Zeehpbg`_hkbfi^k_^\mbhglZk^beenlmkZm^]'
:`^g^kZef^mah]h_]^lb`gbg`\henfglblZl_heehpl'BgikZ\mb\^%l^o^kZeh_ma^l^lm^ilfZr[^
\hf[bg^]'
N =^m^kfbg^]^lb`geb_^'

EC0 & NA Table NA 2.1

N :ll^llZ\mbhglhgma^\henfg'

EC1 (10 parts) & UK NAs

N =^m^kfbg^pab\a\hf[bgZmbhglh_Z\mbhglZiier'

EC0 & NA Tables NA A1.1


& NA A1.2(B)

N :ll^ll]nkZ[bebmrk^jnbk^f^gmlZg]]^m^kfbg^\hg\k^m^

BS 85001

lmk^g`ma'
N <a^\d\ho^kk^jnbk^f^gml_hkZiikhikbZm^_bk^

k^lblmZg\^i^kbh]'

Approved Document B,
EC212

N =^m^kfbg^\ho^k_hk_bk^%]nkZ[bebmrZg][hg]'

Cl. 4.4.1

N :gZerl^lmkn\mnk^_hk\kbmb\Ze\hf[bgZmbhgfhf^gml

Section 5

Zg]ZqbZe_hk\^l'

134

N <a^\dle^g]^kg^llZg]]^m^kfbg^]^lb`gfhf^gml'

Section 5.8

N =^m^kfbg^Zk^Zh_k^bg_hk\^f^gmk^jnbk^]'

Section 6.1

N <a^\dliZ\bg`h_[ZklZg]ebgdl'

Sections 8 & 9

<henfgl
.'* Edge column

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Ma^bgm^gmbhgh_mabl\Ze\neZmbhgblmhlahpZmrib\ZeaZg]\Ze\neZmbhgmaZmfZd^lk^_^k^g\^
mh]^lb`g\aZkml'
Ikhc^\m]^mZbel

<Ze\neZm^][r

chg

Ch[gh'

Edge column

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP 041
1
Oct 09

A 300 mm square column on the edge of a at slab structure


supports an axial load of 1620 kN and rst order moments of
38.5 kNm top and 38.5 kNm bottom in one direction only. The
concrete is grade C30/37, fck = 30 MPa and cover, cnom, = 25 mm.
The 250 mm thick at slabs are at 4000 mm vertical centres.

38.5 kNm
NEd = 1620 kN

38.5 kNm

Figure 5.1 Forces in edge column

5.1.1 Check slenderness, l


Effective length, l0 = factor l
where
factor = from Table C16, condition 2 each end
= 0.85
l
= clear height = 3750 mm
= l0 = 0.85 3750 = 3187 mm
Slenderness l = l0/i

Cl. 5.8.3.2
Table C16,
PD 6687: 2.10

Exp. (5.14)

For examples of load take-downs and 1st order moment analysis see Section
5.3.2
Effective lengths are covered in Eurocode 2 Cl. 5.8.3.2 and Exp. (5.15). The
effective length of most columns will be l /2< l0 < l (see Eurocode 2 Figure 5.7f).
PD 6687[6] Cl. 2.10 suggests that using the procedure outlined in Eurocode 2
(5.8.3.2(3) and 5.8.3.2(5)) leads to similar effective lengths to those tabulated
in BS 8110[7] and reproduced in Table 5.1 of Concise Eurocode 2[5] and in this
publication as Table C16. For simplicity, tabular values are used in this example.
However, experience suggests that these tabulated values are conservative.

Fig. 5.7
PD 6687[6]:
Cl. 2.10
Cl. 5.8.3.2(3)
5.8.3.2(5)
Table C16
135

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
i = radius of gyration
= h/120.5 for rectangular sections
l = 3187 3.46/300

= 36.8

5.1.2 Limiting slenderness, llim

llim = 20 ABC/n0.5
where
A = 0.7 (default)
B = 1.1 (default)
C = 1.7 rm = 1.7 M01/M02
= 1.7 38.5/(38.5) = 2.7
n = NEd/Acfcd = 1620 103/(3002 0.85 30/1.5)
= 1.06
0.5
llim = 20 ABC/n
= 20 0.7 1.1 2.7/1.060.5
In this example llim = 40.4 i.e. > 36.8
= Column not slender

Exp. (5.13N)
Cl. 5.8.3.1(1)

5.1.3 Design moments


MEd = max[M02; M0Ed + M2; M01 + 0.5M2]
where
M02 =
where
M
ei
e0
M02 =
=
=
M0Ed =
=
=
=
M2 =
M01 =

Cl. 5.8.8.2(1)

M + eiNEd e0NEd

Cl. 5.8.8.2, 6.1.4

= 38.5 kNm
= l0/400
= max[h/30; 20] = max[300/30; 20] = 20 mm
38.5 + 1620 3.187/400 0.02 1620
38.5 + 12.9 32.4 kNm
51.4 kNm
0.6M02 + 0.4M01 0.4M02
0.6 51.4 + 0.4 (38.5 + 12.9) 0.4 51.4
20.6 20.6
20.6
0 (column is not slender)
M02

= max[M02 ; M0Ed + M2 ; M01 + 0.5M2] = 51.4 kNm

Cl. 5.2.7, 5.2.9


Cl. 6.1.4

= MEd = 51.4 kNm

5.1.4 Design using charts (see Appendix C)


d2 = cnom + link + f/2 = 25 + 8 + 16 = 49
d2/h = 49/300 = 0.163
= interpolating between d2/h = 0.15 and 0.20
for
NEd/bhfck = 1620 103/(3002 30) = 0.60
136

Figs. C5c), C5d)

.'*3>]`^\henfg

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

MEd/bh2fck = 51.4 106/(3003 30) = 0.063


Asfyk/bhfck = 0.24
As = 0.24 3002 30/500 = 1296 mm2
Try 4 no. H25 (1964 mm2)

5.1.5 Check for biaxial bending


ly /lz 1.0
i.e. ly /lz 2.0 = OK but check Exp. (5.38b)

Cl. 5.8.9
Exp. (5.38a)

As a worst case MEdy may coexist with e0NEd about the orthogonal axis:

Cl. 6.1(4)

ey/heq
ez/beq

(MEdz/NEd)/h
(MEdy/NEd)/b

MEdz
MEdy

Exp. (5.38b)

Imperfections need to be taken into account in one direction only.


= As a worst case for biaxial bending

Cl. 5.8.9(2)

MEdz = M + 0 = 38.5 kNm


MEdy = e0NEd = 32.4 kNm
38.5
MEdz
=
= 1.19 i.e. > 0.2 and < 5.0
32.4
MEdy

Exp. (5.38b)
= Biaxial check required

Cl. 5.8.9(4)

Check whether
(MEdz/MRdz)a + (MEdy/MRdy)a 1.0

Exp. (5.39)

where
MEdz = 38.5 kNm
MEdy = 32.4 kNm
MRdz = MRdy

Figs. C5c), C5d)

To determine MRdz, nd MEd/bh2fck (and therefore


moment capacity) by interpolating between d2/h = 0.15
(Figure C5c) and 0.20 (Figure C5d) for the proposed
arrangement and co-existent axial load.
Assuming 4 no. H25,
Asfyk/bhfck = 1964 500/(3002 30) = 0.36
Interpolating for NEd/bhfck = 0.6,
MEd/bh2fck = 0.094
= MRdz = MRdy = 0.094 3003 30 = 76.1 kNm
a is dependent on NEd/NRd
where
NEd = 1620 kN as before

Cl. 5.8.9(4),
Notes to Exp.
(5.39)

137

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

NRd

= Acfcd + Asfyd
= 3002 0.85 30/1.5 + 1964 500/1.15
= 1530.0 + 853.9
= 2383.9 kN
NEd/NRd = 1620/2383.9 = 0.68
=a = 1.48 by interpolating between values given for NEd/NRd =
0.1, (1.0) and NEd/NRd = 0.7, (1.5)
(MEdz/MRdz)a + (MEdy/MRdy)a

= (38.5/76.1)1.48 + (32.4/76.1)1.48
= 0.36 + 0.28
= 0.64 = OK.
= 4 no. H25 OK

Exp. (5.39)

5.1.6 Links
Diameter min. f/4 = 25/4 = 8 mm
Max. spacing = 0.6 300 = 180 mm

Cl. 9.5.3 & NA


Cl. 9.5.3(3),
Cl. 9.5.3(4)
Links at say 175 mm cc

5.1.7 Design summary


4 H25
H8 links @ 175 cc
25 mm cover
fck = 30 MPa

Figure 5.2 Design summary: edge column

138

.'+3I^kbf^m^k\henfg
.'+ Perimeter column (internal environment)
Mabl^qZfie^blbgm^g]^]mhlahpZaZg]\Ze\neZmbhg_hkZghg&le^g]^ki^kbf^m^k\henfg
nlbg`bm^kZmbhg!h_q"mh]^m^kfbg^ma^k^bg_hk\^f^gmk^jnbk^]'

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Ikhc^\m]^mZbel

Perimeter column
(internal environment)

<Ze\neZm^][r

chg

Ch[gh'

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP 041
1
Oct 09

This 300 300 mm perimeter column is in an internal environment


and supports three suspended floors and the roof of an office block.
It is to be designed at ground floor level where the storey height
is 3.45 m and the clear height in the NS direction (z direction) is
3.0 m and 3.325 m in the EW direction (y direction). One-hour fire
resistance is required and fck = 30 MPa.

M02yy
3575

250
325
300 300
Column under
consideration

Figure 5.3 Perimeter column


(internal environment)
From first order analysis, load case 1:
NEd = 1129.6 kN; M02yy = 89.6 kNm; M02zz = 0
Load case 2:
NEd = 1072.1 kN; M02yy = 68.7 kNm; M02zz = 6.0 kNm

5.2.1 Cover
cnom = cmin + Dcdev
where
cmin = max[cmin,b; cmin,dur]
where
cmin,b = diameter of bar. Assume 32 mm bars and 8 mm links
= 32 mm to main bars, 32 8 = 24 mm to links
= say 25 mm
cmin,dur = minimum cover due to environmental conditions.
Assume XC1.
cmin,dur = 15 mm
cmin = 25 mm
Dcdev = 10 mm
Therefore cnom = 25 + 10 = 35 mm to links

Exp. (4.1)

Cl. 4.4.1.2(3)

Cl. 4.4.1.3(3)
cnom = 35 mm to links.
139

5.2.2 Fire resistance


Check validity of using Method A and Table 5.2a of BS EN 199212:

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

l0, 0.7 3.325 i.e. < 3.0 m = OK.


e

= M02yy /NEd = 89.6 106/1129.6 103 = 79 mm

EC2-1-2: 5.3.2,
Table 5.2a
EC2-1-2:
5.3.3(3)
EC2-1-2:
5.3.2 & NA

emax = 0.15h = 0.15 300 = 45 mm = no good.


Check validity of using Method B and Table 5.2b:
emax = 0.25b = 75 mm = no good.

EC2-1-2:
5.3.3

Use BS EN 199212 Annex C Tables C1C9.

EC2-1-2:
Annex C
EC2-1-2: 5.3.3(2)

Assume min. 4 no. H25 = 1964 mm2 (z 2.2%)


w = Asfyd/Acfcd = 0.022 (500/1.15)/(0.85 30/1.5)
= 0.56
e 0.25b and 100 mm
l = l0 /i
where
l0 = 0.7 3.325 = 2327 mm
i = radius of gyration = (I/A)0.5 = h/120.5
where
I = inertia = bh3/12
A = area = bh
h = height of section
b = breadth of section
= 300/120.5 = 87 mm
l = 2327/87 = 276
n = N0Ed,/0.7(Acfcd + Asfyd)

EC2-1-2:
5.3.3(2),
5.3.3(3)

EC2-1-2: 5.3.3(2)

1129.6/0.7(3002

0.85 30/1.5 + 1964 500/1.15)


= 0.7
= 1129.6/2383.9
= 0.47
= interpolate for l = 30 and n = 0.47 between
from Table C.5 of BS EN 199212 (w = 0.5, e = 0.25b):
minimum dimension, bmin = 235, and axis distance, a = 35 mm
and
from Table C.8 of BS EN 199212 (w = 1.0, e = 0.25b):

Using 4 no. H20 gives w = 0.34, n = 0.54 and bmin = 310 mm = no good.
140

EC2-1-2:
Table C.5
EC2-1-2:
Table C.8

.'+3I^kbf^m^k\henfg

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

bmin = 185, and


a = 30 mm
 = for w = 0.56,
bmin = 228, and
a = 35 mm
OK to use Method B but use min. 4 no. H25

5.2.3 Structural design: check slenderness


Effective length, l0:
l0 = 0.5l [1 + k1 /(0.45 + k1) ]0.5 [1 + k2/(0.45 + k2) ]0.5
where
k1, k2 = relative stiffnesses top and bottom

Exp. (5.15)

But conservatively, choose to use tabular method. For critical


direction, the column is in condition 2 at top and condition 3 at
bottom (pinned support).
l0 = 0.95 3325 = 3158 mm

Table C16

Slenderness ratio, l:
l = l0/i
where
i = radius of gyration = (I/A)0.5 = h/120.5
l = 3158 120.5/300 = 36.5

Cl. 5.8.3.2(1)

Limiting slenderness ratio, llim


llim = 20 ABC/n0.5
where
A = 1/(1 + 0.2 fef). Assume 0.7
B = (1 + 2 Asfyd/Acfcd)0.5
= (1 + 2w)0.5
Assuming min. 4 no. H25 (for re)
w = 0.56 as before
B = (1 + 2 0.56)0.5 = 1.46
C = 1.7 rm
where
rm = M01/M2
Assuming conservatively that M01 = 0
rm = 0
C = 1.7
n = NEd/Acfcd
= 1129.6 103/(3002 0.85 30/1.5)
= 0.74

l = 36.5
Cl. 5.8.3.1(1)
& NA
Cl. 5.8.4
Cl. 5.8.3.1(1)

Cl. 5.8.3.1(1)

See footnote to Section 5.1.1.


141

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

llim = 20 0.7 1.46 1.7/0.740.5


= 40.4
llim = 40.4
= as l < llim column is not slender and 2nd order moments are not
required.
Column is not slender

5.2.4 Design moments, MEd


MEd = MOEd + M2 e0NEd

But as column is not slender, M2 = 0, =


MEd = MOed = M + eiNEd e0NEd

Cl. 5.8.8.2(1),
5.8.8.2(3)
Cl. 6.1.4

where
M
= moment from 1st order analysis
eiNEd = effect of imperfections
where
ei = l0 /400
e0 = h/30 > 20 mm

Cl. 5.2(7), 5.2.9,


5.8.8.2(1)
Cl. 6.1.4

Load case 1:
MEdy = 89.6 + (3158/400) 1129.6 103 > 0.02 1129.6
= 89.6 + 8.9 > 22.6 = 98.5 kNm
Load case 2:
MEdy = 68.7 kNm
MEdz = 6.0 + (l0/400) 1072.1 103 > 0.02 1072.1
where
l0 = 0.9 3000
= 13.2 > 21.4 = 21.4 kNm

Table C16

5.2.5 Design using iteration of x


For axial load:
AsN/2 = (NEd accnfckbdc /gC)/(ssc sst)

142

Concise:
Section 6.2.2,
Appendix A3

For moment:
[MEd accnfckbdc (h/2 dc/2)/ gC]
AsM/2 =
(h/2 d2) (ssc sst)
where
MEd = 98.5 106
NEd = 1129.6 103
acc = 0.85
n = 1.0 for fck 50 MPa

Cl. 3.1.6(1) & NA


Exp. (3.21)

The effects of imperfections need only be taken into account in the most
unfavourable direction.

Cl. 5.8.9(2)

Appendices A3,
C9.2,

.'+3I^kbf^m^k\henfg

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

fck
b
h
dc

= 30
= 300
= 300
= depth of compression zone
= lx
= 0.8x < h
where
x = depth to neutral axis
d2
= 35 + 8 + 25/2 = 55 mm assuming H25
= 1.5
gC
ssc, (sst) = stress in reinforcement in compression (tension)
o

fcd = accnfck/gC
o

ecu2

Table 2.1N

d2
ssc

As2

esc

Exp. (3.19)

dc

x
h

n. axis
ey
o
a) Strain diagram

As1

sst

d2
o

b) Stress diagram

Figure 5.4 Section in axial compression and bending

Fig. 6.1

Try x = 200 mm
= ecu2 = 0.0035
ecu
0.0035 (x d2) 0.0035 (200 55)
esc
=
=
x
200
= 0.0025
ssc = 0.0025 200000 fyk/gS
= 500 500/1.15
= 434.8 MPa
= 0.0035(h x d2)/x = 0.0035(300 200 55)/200
est
= 0.0008
sst = 0.0008 200000 500/1.15
= 160 MPa
1129.6 103 0.85 1.0 30 300 200 0.8/(1.5 103)
AsN/2 =
434.8 160
= (1129.6 816.0) 103
= 1141 mm2
274.8
143

98.5 106 0.85 1.0 30 300 200 0.8 (300/2 200 0.8/2)/(1.5 103)
(300/2 55) (434.8 + 160)
6
(98.5 57.1) 10
=
= 733 mm2
95 594.8

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

AsM/2 =

Similarly for x = 210 mm


ecu = 0.0035
esc = 0.0026
= ssc = 434.8
est = 0.0006 = sst = 120 MPa
AsN/2 =

(1129.6 856.8) 103


= 866 mm2
434.8 120

AsM/2 =

(98.5 56.5) 106


= 796 mm2
95 554.8

Similarly for x = 212 mm


ssc = 434.8
= 0.00054 =est = 109 MPa
est
AsN/2 =

(1129.6 865.0) 103


= 812 mm2
434.8 109

AsM/2 =

(98.5 56.3) 106


= 816 mm2
95 543.8

= as AsN/2 AsM/2, x = 212 mm is approximately correct and


AsN AsM, 1628 mm2
= Try 4 no. H25 (1964 mm2)

5.2.6 Check for biaxial bending


By inspection, not critical.
[Proof:
Section is symmetrical and MRdz > 98.5 kNm.
Assuming ey/ez > 0.2 and biaxial bending is critical, and assuming
exponent a = 1 as a worst case for load case 2:
(MEdz/MRdz)a + (MEdy/MRdy)a = (21.4/98.5)1 + (68.7/98.5)1
= 0.91 i.e. < 1.0
= OK.]

Cl. 5.8.9(3)

Exp. (5.39)

5.2.7 Links
Minimum size links = 25/4 = 6.25, say 8 mm
Spacing: minimum of
a) 0.6 20 25 = 300 mm,
b) 0.6 300
= 180 mm or
c) 0.6 400
= 240 mm

Cl. 9.5.3(3),
9.5.3(4)
Use H8 @ 175 mm cc

144

.'+3I^kbf^m^k\henfg

5.2.8 Design summary

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

4 H25
H8 links @ 175 cc
cnom = 35 mm to links

Figure 5.5 Design summary: perimeter column

145

.', Internal column

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Ma^ZmleZ[lahpgbg>qZfie^,'-!k^ikh]n\^]Zl?b`nk^.'/"bliZkmh_Zg1&lmhk^rlmkn\mnk^
Z[ho^`khng]pbmaZ[Zl^f^gm[^ehp`khng]'Ma^ikh[e^fblmh]^lb`g\henfg<+[^mp^^g
`khng]hhkZg]*lmhhk'

Ikhc^\m]^mZbel

<Ze\neZm^][r

chg

Ch[gh'

Internal column

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP 041
1
Oct 09

The design forces need to be determined. This will include the


judgement of whether to use Exp. (6.10) or the worse case of
Exp. (6.10a) and (6.10b) for the design of this column.
The suspended slabs (including the ground floor slab) are 300
mm thick flat slabs at 4500 mm vertical centres. Between ground
and 5th floors the columns at C2 are 500 mm square; above 5th
floor they are 465 mm circular. Assume an internal environment,
1-hour fire resistance and fck = 50 MPa.
A

4.0

4.0

Bb

4.0

6.0

D
E

200 x 200
hole
8.0

8.0

9.6
300 mm flat slabs
All columns 400 mm sq.

200 x 200
hole

8.6

Figure 5.6 Part plan of flat slab

5.3.1 Design forces


In order to determine design forces for this column it is rst
necessary to determine vertical loads and 1st order moments.

5.3.2 Load take-down


Actions:
Roof:
gk = 8.5, qk = 0.6

146

EC1-1-1:
6.3.4, NA &
Table NA.7

.',3Bgm^kgZe\henfg

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Floors:
gk = 8.5, qk = 4.0

Section 3.4

In keeping with Section 3.4 use coefcients to determine loads in


take-down.

Section 3.4

Consider spans adjacent to column C2:


Along grid C, consider spans to be 9.6 m and 8.6 m and C2 to be
the internal of 2 - span element.
Therefore elastic reaction factor = 0.63 + 0.63 = 1.26
Along grid 2 consider spans to be 6.0 m and 6.2 m and internal of
multiple span.
Elastic reaction factor = 0.5 + 0.5 = 1.00

Table C3

Load take-down for column C2.


Item

Calculation

Gk
From
item

= [erfy (lz1 + lz2)/2 ] [erfz (l y1 + ly2)/2 ]


(gk + qk)
= [1.0 (6.0 + 6.2)/2 ] [1.26 (9.6
+ 8.6)/2 ] (8.5 + 0.6)
= 69.9 (8.5 + 0.6)
=
Col 8 R = (0.465/2)2 (4.5 0.3) 25 =
8th
= 1.0 (6.0 + 6.2)/2 1.26 (9.6 +
8.6)/2 (8.5 + 4.0)
=
Col 7 8
as before
7th
a.b.
Col 6 7
a.b.
6th
a.b.
Col 5 6 a.b.
5th
a.b.
Col 4 5
= 0.5 0.5 (4.5 0.3) 25
=
4th
as before
Col 3 4
a.b.
3rd
a.b.
Col 2 3
a.b.
2nd
a.b.
Col 1 2
a.b.
1st
a.b.
Col G 1
a.b.
At above ground floor

Qk
Cumulative From
total
item

Cumulative
total

Roof

594.5
17.9
594.5
17.9
594.5
17.9
594.5
17.9
594.5
26.3
594.5
26.3
594.5
26.3
594.5
26.3
594.5
26.3

42.0
612.4

42.0
279.7

1224.8

321.7
279.7

1837.2

601.4
279.7

2449.6

881.1
279.7

3070.4

1160.8
279.7

3691.2

1440.5
279.7

4312.0

1720.2
279.7

4932.8

1999.7
279.8

5553.6
5553.6

2279.5
2279.5

147

5.3.3 Design axial load, ground 1st floor, NEd

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

a) Axial load to Exp. (6.10)


NEd = gGGk + gQQk1 + c0gQQki
where
gG =
gQ =
c0,1 =
Qk1 =
Qki =

1.35
1.50
0.7 (ofces)
leading variable action (subject to reduction factor aA or an)
accompanying action (subject to aA or an)

EC0:
Exp. (6.10) & NA
EC0:
A1.2.2 & NA

EC1-1-1:
6.3.1.2 (10),
6.3.1.2 (11), & NA

where
aA = 1 A/1000 0.75
= 1 9 69.9/1000 = 0.37 0.75
= 0.75
an = 1.1 n/10 for 1 n 5
= 0.6 for 5 n 10 and
= 0.5 for n > 10
where
n = number of storeys supported
an= 0.6 for 8 storeys supported
= as an < aA, use an = 0.6

Assuming the variable action of the roof is an independent variable


action:
NEd = 1.35 5553.6 + 1.5 (2279.5 42.0) 0.6 + 0.7 1.5 42.0
= 1.35 5553.6 + 1.5 2237.5 + 0.7 1.5 42.0
= 7497.4 + 2013.8 + 44.1
= 9555.3 kN
To Exp. (6.10), NEd = 9555.3 kN
b) Axial load to Exp. (6.10a)
NEd = gGGk + c0,1gQQk1 + c0,1gQQki
= 1.35 5553.6 + 0.7 1.5 0.6 ( 279.8 + 1999.7)
= 7497.4 + 1436.1
= 8933.4 kN
To Exp. (6.10a), NEd = 8933.4 kN
c) Axial load to Exp. (6.10b)
NEd = jgGGk + gQQk1 + c0,1gQQki

According to BS EN 199111 6.3.1.2[11] the imposed load on the roof is category


H and therefore does not qualify for reduction factor an.

148

EC0:
Exp. (6.10a)
& NA

EC0:
Exp. (6.10)
& NA

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

.',3Bgm^kgZe\henfg

assuming the variable action of the roof is an independent variable


action:
= 0.925 1.35 5553.6 + 1.5 (2279.5 42.0) 0.6 + 0.7 1.5 42.0
= 1.25 5553.6 + 1.5 2237.5 0.6 + 0.7 1.5 42.0
= 6942.1 + 2013.8+ 44.1
= 9000.0 kN
To Exp. (6.10b), NEd = 9000.0 kN

5.3.4 First order design moments, M


a) Grid C
Consider grid C to determine Myy in column (about grid 2)
gk = 6.1 x 8.5 = 51.9 kN/m

qk = 6.1 x 4.0 = 24.4 kN/m

300 thick ave 6100 wide

8600

4500

1
500 sq

4500

9600

Actions:
gk = (6.0 + 6.2)/2 8.5 = 51.9 kN/m
qk = (6.0 + 6.2)/2 4.0 = 24.4 kN/m
Relative stiffness of lower column:
Assuming remote ends of slabs are pinned, relative stiffness
blcdlc3/Llc
=
3
3
blcdlc /Llc + bucduc /Luc + 0.75b23d233/L23 + 0.75b21d213/L21
where
b = breadth
d = depth
L = length
lc = lower column, uc = upper column
23 = beam 23, similarly 21 = beam 21
0.54/4.5
=
4
2 0.5 /4.5 + 0.75 6.1 0.33/8.6 + 0.75 6.1 0.33/9.6
= 0.0139/(0.0278 + 0.0144 + 0.0129) = 0.252

149

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

1st order moment using Exp. (6.10)


FEM 23 = 1.35 51.9 8.62/12 = 431.8 kNm
FEM 21 = (1.35 51.9 + 1.5 24.4) 9.62/12
= 106.7 9.62/12 = 819.5 kNm
Mlower,yy = 0.252 [819.5 431.8] = 97.7 kNm
1st order moment using Exp. (6.10a)
FEM 23 = 1.25 51.9 8.62/12 = 399.8 kNm
FEM 21 = (1.25 51.9 + 1.5 24.4) 9.62/12
= 101.5 9.62/12 = 779.5 kNm
Mlower,yy = 0.252 (779.5 399.8) = 95.7 kNm
1st order moment using Exp. (6.10b)
FEM 23 = 1.35 51.9 8.62/12 = 431.8 kNm
FEM 21 = (1.35 51.9 + 0.7 1.5 24.4 ) 9.62/12
= 95.7 9.62/12 = 735.0 kNm
Mlower,yy = 0.252 (735.0 431.8) = 76.4 kNm
= Exp. (6.10a) critical
b) Grid 2
Consider grid 2 to determine Mzz in column (about grid C)

qk = 45.9 kN/m

gk = 97.5 kN/m

300 thick ave 11470 wide

4500

4500

500 sq

6200

6000

Figure 5.8 Subframe on column C2 along grid 2


Actions:
gk = 0.63 (8.6 + 9.6) 8.5
= 11.47 8.5 = 97.5 kN/m
qk = 11.47 4.0 = 45.9 kN/m
Relative stiffness of lower column:
Assuming remote ends of slabs are xed, relative stiffness
FEM

150

23 = Fixed end moment in span 23 at grid 2.

Cl. 5.8.3.2(4)
PD 6687

.',3Bgm^kgZe\henfg

0.54/4.5
2 0.54/4.5 + 11.47 0.33/6.2 +11.47 0.33/6.0

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

= 0.0139/(0.0278 + 0.0500 + 0.0516) = 0.107


1st order moment using Exp. (6.10)
FEM CB = (1.35 97.5 + 1.5 45.9) 6.22/12
= 200.5 6.22/12 = 642.3 kNm
FEM CD = 1.35 97.5 6.02/12 = 394.9 kNm
Mlower,zz = 0.107 (642.3 394.9) = 26.5 kNm
1st order moment using Exp. (6.10a)
FEM CB = 1.25 97.5 6.02/12 = 365.6 kNm
FEM CD = (1.25 97.5 + 1.5 45.9) 6.22/12
= 190.7 6.22/12 = 611.0 kNm
Mlower,zz = 0.107 (611.0 365.6) = 26.3 kNm
1st order moment using Exp. (6.10b)
FEM CB = (1.35 97.5 + 0.7 1.5 45.9) 6.22/12
= 190.7 6.22/12 = 576.0 kNm
FEM CD = 1.35 97.5 6.02/12 = 394.9 kNm
Mlower,zz = 0.107 (576.0 394.9) = 19.4 kNm
= Exp. (6.10a) critical again

5.3.5 Summary of design forces in column C2 ground1st


Design forces
Method

NEd

Using Exp. (6.10)


Using Exp. (6.10a)
Using Exp. (6.10b)

9555.3 kN
8933.4 kN
9000.0 kN

Myy
about grid 2
97.7 kNm
95.7 kNm
76.4 kNm

Mzz
about grid C
26.5 kNm
26.3 kNm
19.4 kNm

Notes:
1) To determine maximum 1st order moments in the column, maximum out-ofbalance moments have been determined using variable actions to one side of
the column only. The effect on axial load has, conservatively, been ignored.
2) It may be argued that using coefficients for the design of the slab and
reactions to the columns does not warrant the sophistication of using Exps
(6.10a) and (6.10b). Nevertheless, there would appear to be some economy
in designing the column to Exp. (6.10a) or Exp. (6.10b) rather than Exp.
(6.10). The use of Exp. (6.10a) or Exp. (6.10b) is perfectly valid and will be
followed here.

To avoid duplicate designs for both Exps (6.10a) and (6.10b), a worse
case of their design forces will be used, thus:
NEd = 9000 kN, Myy = 95.7 kNm, Mzz = 26.3 kNm
151

5.3.6 Design: cover

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

cnom = cmin + Dcdev


where
cmin = max[cmin,b; cmin,dur]
where
cmin,b
cmin,dur
cmin,dur

Exp. (4.1)

= diameter of bar. Assume 32 mm bars and 8 mm links.


= 32 8 = 24 mm to link
= minimum cover due to environmental conditions.
Assume XC1.
= 15 mm

cmin = 24 mm, say 25 mm to link


Dcdev = 10 mm
= cnom = 25 + 10

= 35 mm

Cl. 4.4.1.2(3)

BS 8500-1:
Table A4

Cl. 4.4.1.3 & NA

5.3.7 Design: fire resistance


Check validity of using Method A and Table 5.2a
a) Check l0,fi 3.0 m
where
l0 = effective length of column in re
= 0.5 clear height
= 0.5 (4500 300)
= 2100 mm
b) Check e emax = 0.15h = 0.15 500 = 75 mm
e = M0Ed,/N0Ed,
= M0/NEd
= 99.5 106/8933 103 = 11 mm

EC2-1-2:
5.3.2, Table 5.2a

OK

EC2-1-2: 5.3.2(2)
OK

c) Check amount of reinforcement 4%


OK
Assuming m = 0.7
bmin = 350 with
OK
amin = 40 mm
For re using Method A and Table 5.2a is valid

EC2-1-2:
Table 5.2a

5.3.8 Structural design: check slenderness


Effective length, l0:
l0 = 0.5l [1 + k1/(0.45 + k1)]0.5 [1 + k2/(0.45 + k2)]0.5
where
k1 and k2 are relative exibilities at top and bottom of the
column.
ki = (EIcol/lcol)/S(2EIbeam/lbeam) 0.1
PD 6687 states that to allow for cracking, the contribution of each beam
should be taken as 2EI/lbeam

152

Exp. (5.15)

PD 6687[6]

.',3Bgm^kgZe\henfg

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Critical direction is where k1 and k2 are greatest i.e. where slab spans
are greater
blcdlc3/Llc
k1 = k2 =
2b23d233/L23 + 2b21d213/L21

How to[8]:
Columns

= (0.54/4.5)/(2 6.1 0.33/8.6 + 2 6.1 0.33/9.6)


= (0.0625)/(0.0383 + 0.0343)
= 0.86
l0 = 0.5 (4500 300) [1 + 0.86/(0.45 + 0.86)]0.5 [1 + 0.86/(0.45
+ 0.86)]0.5
l0 = 0.5 4200 1.66
= 0.828 4200 = 3478 mm
Slenderness ratio, l:
l = l0/i
where
i = radius of gyration = (I/A)0.5 = h/120.5
= l = 3478 120.5/500 = 24.1

Cl. 5.8.3.2(1)

Limiting slenderness ratio, llim:


llim = 20 ABC/n0.5
where
A = 1/(1 + 0.2 fef). Assume 0.7 as per default
B = (1 + 200)0.5. Assume 1.1 as per default
C = 1.7 kf
where

kf = M01/M2 = 84.9/109.3 = 0.78
C = 1.7 + 0.78 = 2.48
n = NEd /Acfcd
= 8933 103/(5002 0.85 50/1.5)
= 1.26
= llim = 20 0.7 1.1 2.48/1.260.5 = 34.0
= as l < llim column is not slender
and 2nd order moments are not required

Cl. 5.8.3.1(1) & NA


Exp. (5.13N)

5.3.9 Design moments, MEd


MEd = M + eiNEd e0NEd

where
M
= moment from 1st order analysis
eiNEd = effect of imperfections

Cl. 5.8.8.2(1),
6.1(4)

Cl. 5.8.8.2(1)

153

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
ei
= l0/400
e0NEd = minimum eccentricity

Cl. 5.2.7
Cl. 6.1(4)

where
e0 = h/30 20 mm
MEdyy = 95.7 + (3570/400) 8933 103 0.02 8933
= 95.7 + 79.7 178.7
= 175.4 < 178.7 kNm
MEdzz = 18.8 + 79.7 178.7
= 178.7 kNm
= Both critical.
However, imperfections need only be taken in one direction where
they have the most unfavourable effect
= Use MEdzz = 178.7 with MEdyy = 95.7 kNm

Cl. 5.8.9(2)

5.3.10 Design using charts


MEdyy /bh2fck = 178.9 106/(5003 50) = 0.03
NEd/bhfck = 9000 103/(5002 50) = 0.72
Choice of chart based on d2/h
where
d2 = depth to centroid of reinforcement in half section assuming
12 bar arrangement with H32s
d2 = 35 + 8 + (32/2) + (2/6) [500 + 2 (35 + 8 + 32/2 )/3]
= 59 + (1/3) 127
= 101
Use Figure C5d)
= d2/h = 101/500 = 0.2

Figs C5a) to C5e)

d2
CL

d2, to centroid of reinforcement in half section


From Figure C5d)
Asfyk/bhfck = 0.30
= 0.29 500 500 50/500
As
= 7500 mm2
Try 12 no. H32 (9648 mm2)

Using design actions to Exp. (6.10) would have resulted in a requirement for
8500 mm2.

154

Fig. C5d)

.',3Bgm^kgZe\henfg

Cl. 5.8.9

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

5.3.11 Check biaxial bending


Slenderness: ly lz = OK.
Eccentricities: as h = b check ey/ez
MEdz critical. (Imperfections act in z direction.)
95.7 106/9000 103
ey/ez =
178.7 106/9000 103
= 0.54 i.e. > 0.2 and < 5
= Design for biaxial bending.

Cl. 5.8.9(3)

Cl. 5.9.3(3),
Exp. (5.38b)

C
z
ey

MEdy

Centre of
reaction

ez
y 2

MEdz

Figure 5.10 Eccentricities

5.3.12 Design for biaxial bending


Check (MEdz/MRdz)a + (MEdy/MRdy)a 1.0
For load case 2
where
MEdz = 178.7 kNm
MEdy = 95.7 kNm
MRdz = MRdy = moment resistance. Using charts:
From Figure C4d), for d2/h = 0.20 and
Asfyk/bhfck = 9648 500/500 500 50
= 0.39
NEd/bhfck = 9000 x 103/(5002 x 50)
= 0.72
2
MRd/bh fck = 0.057

Cl. 5.9.3(4),
Exp. (5.39)

Fig. C5d)

= MRd 0.057 5003 50


= 356.3 kNm

155

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

a = exponent dependent upon NEd/NRd


where
= Acfcd + Asfyd
NRd
= 500 500 0.85 50/1.5 + 9648 500/1.15
= 7083 + 3216
= 10299 kN
NEd/NRd = 9000/10299 = 0.87.
Interpolating between values given for NEd/NRd = 0.7
(1.5) and for NEd/NRd = 1.0 (2.0)
= a = 1.67

Cl. 5.8.3(4)

Notes to
Exp. (5.39)

Check (MEdz/MRdz)a + (MEdy/MRdy)a 1.0


(178.7/356.3)1.67 + (95.7/356.3)1.67

= 0.32 + 0.11
= 0.43 i.e. < 1.0
= OK
Use 12 no. H32

5.3.13 Links
Minimum diameter of links: = f/4 = 32/4
= 8 mm
Spacing, either:
a) 0.6 20 f
= 12 32 = 384 mm,
b) 0.6 h
= 0.6 500 = 300 mm or
c) 0.6 400
= 240 mm.
= Use H8 links at 225 mm cc
Number of legs:
Bars at 127 mm cc i.e. < 150 mm = no need to restrain bars in face
but good practice suggests alternate bars should be restrained.
= Use single leg on face bars both ways @ 225 mm cc

5.3.14 Design summary


12 H32
H8 links @ 225 cc
35 mm to link
500 mm sq
fck = 50 MPa

Figure 5.11 Design summary: internal column

156

Cl. 9.5.3 & NA

Cl. 9.5.3(3),
9.5.3(4)

Cl. 9.5.3(6)
SMDSC: 6.4.2

.'-3LfZeei^kbf^m^k\henfg
.'- Small perimeter column subject to two-hour fire
resistance

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Mabl \Ze\neZmbhg bl bgm^g]^] mh lahp Z lfZee le^g]^k \henfg ln[c^\m mh Z k^jnbk^f^gm _hk
+&ahnkk^k^lblmZg\^'Bmbl[Zl^]hgma^^qZfie^lahpgbgL^\mbhg-'+'
Ikhc^\m]^mZbel

Small perimeter column


subject to two-hour fire resistance

<Ze\neZm^][r

chg

Ch[gh'

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP 041
1
Oct 09

The middle column, B, in Figure 4.5, supports two levels of storage


loads and is subject to an ultimate axial load of 1824.1 kN. From
analysis it has moments of 114.5 kNm in the plane of the beam and
146.1 kNm perpendicular to the beam (i.e. about the z axis).
The column is 350 mm square, 4000 mm long, measured from top
of foundation to centre of slab. It is supporting storage loads, in
an external environment (but not subject to de-icing salts) and is
subject to a 2-hour re resistance requirement on three exposed
sides. Assume the base is pinned.
Slab
300
450
350 x 350
column
4000
Paving

Foundation

Figure 5.12 Perimeter column

5.4.1 Cover
Nominal cover, cnom
cnom = cmin + Dcdev
where
cmin = max[cmin,b; cmin,dur]

Exp. (4.1)

Gk = 562.1; Qk = 789.1; as column supports loads from 2 levels an = 0.9; as


imposed loads are from storage c0 = 1.0 =gQ = 1.50 and gQ= 1.35. =Ultimate
axial load, NEd = 1.35 562.1 + 1.5 0.9 789.1 = 1824.1 kN.
157

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
cmin,b

= diameter of bar. Assume 32 mm main bars and


10 mm links
cmin,dur = minimum cover due to environmental conditions.
Assuming primarily XC3/XC4, secondarily XF1,
cmin,dur = 25 mm
Dcdev = allowance in design for deviation
= 10 mm
= Try cnom = 32 + 10 = 42 mm to main bars
or
= 25 + 10 = 35 mm to 8 mm links
Try cnom = 35 mm to 8 mm links.

Cl. 4.4.1.2(3)
BS 8500-1[14] :
Table A4

5.4.2 Fire resistance


a) Check adequacy of section for R120 to Method A
Axis distance available = 43 mm + f/2
Required axis distance to main bars, a for 350 mm square column
For m = 0.5, a = 45 mm; and
for m = 0.7, a = 57 mm, providing:

EC1-1-2: 5.3.1(1) &


NA 5.3.2,
Table 5.2a

t 8 bars used OK but check later


t l0,fi 3 m OK but check
t e emax = 0.15h = 0.15 350 = 52 mm
but e = M0Ed,/N0Ed,
= 0.7 146.1 106/0.7 1824.1 103
= 80 mm = no good
Try Method B
b) Check adequacy of section for R120 to Method B
Determine parameters n, w, and e, and check l.
Assume 4 no. H32 + 4 no. H25 = (5180 mm2: 4.2%)
(say 4.2% OK integrity OK)
n = N0Ed,/0.7(Acfcd + Asfyd)
= 0.7 1824.1 103/0.7 (350 350 acc fck/ gC + 5180 500/gS)
= 1276.9 103/0.7 (350 350 0.85 30/1.5 + 5180 500/1.15)
= 1276.9 103/0.7 (2082.5 + 2252.0)
= 0.42
OK
w = mechanical ratio
= Asfyd/Acfcd 1.0
= 2252/2082
= 1.08 1
But say within acceptable engineering tolerance =use w = 1.0
OK
e = rst order eccentricity
= M0Ed,/N0Ed,
158

EC2-1-2: 5.3.3,
Table 5.2b
Cl. 9.5.2(3)
EC2-1-2: Exp.
(5.8a)

EC2-1-2: 5.3.3(2)

EC2-1-2: Exp.
(5.8b)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

.'-3LfZeei^kbf^m^k\henfg

= 0.7 146.1 106/0.7 1824.1 103


= 80 mm as before z 0.23h.
OK
l = slenderness in re
= l0,/i
where
l0, = effective length of column in re
= 0.7l = 0.7 4000 = 2800 mm
i = radius of gyration
= h/3.46 for a rectangular section
= l = 2800/(350/3.46)
= 27.7 < 30
= OK
Table 5.2b valid for use in this case.
Interpolating from BS EN 199212 Table 5.2b for n = 0.42 and
w = 1.0, column width = 350 mm and axis distance = say, 48 mm
= Axis distance = 43 mm + f/2 is OK
c) As additional check, check adequacy of section to Annex B3 and
Annex C
Using BS EN 199212 Table C.8
For w = 1.0, e = 0.25b, R120, l = 30
and interpolating between n = 0.3 and n = 0.5,
bmin = 350 mm, amin = 48 mm.
= Axis distance = 43 mm + f/2 is OK
= 4 no. H32 + 4 no. H25 with 35 mm cover to 8 mm links
(a = 55 mm min.) OK

EC2-1-2: 2.4.2(3)

EC2-1-2: 5.3.2(2)
Note 2

EC2-1-2:
5.3.3(1), Annex C
& NA
EC2-1-2:
Annex C(2)

5.4.3 Structural design: check slenderness about z axis


Effective length, l0, about z axis:
l0z = 0.5l [1 + k1/(0.45 + k1) ]0.5 [1 + k2/(0.45 + k2) ]0.5
where
l
= clear height between restraints
= 4000 300/2 = 3850 mm
k1, k2 = relative exibilities of rotational restraints at ends 1
and 2 respectively
k1
= [EIcol/lcol]/[2EIbeam1/lbeam1 + 2EIbeam2/lbeam2] 0.1
where
Treating beams as rectangular and cancelling E throughout:
= 3504/(12 3850) = 3.25 105
Icol/lcol
Ibeam1/lbeam1 = 8500 3003/12 6000
= 31.8 105
Ibeam2/lbeam2 = 0

Exp. (5.15)
PD 6687: 2.10

Cl. 5.8.3.2(3)
PD 6687

k1 = 3.25/(2 31.8) = 0.051 0.1


k1 = 0.1
k2 = by inspection (pinned end assumed) =
159

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

= l0z = 0.5 3850 [1 + 0.1/(0.45 + 0.1) ]0.5 [1 + /(0.45 + )]0.5


= 0.5 3850 1.087 1.41
= 0.77 3850 = 2965 mm
Slenderness ratio, lz:
lz = l0z/i
where
i = radius of gyration = h/3.46
lz = 3.46l0z/h = 3.46 2965/350

Cl. 5.8.3.2(1)

= 29.3

Limiting slenderness ratio, llim:


llim,z = 20 ABC/n0.5

Cl. 5.8.3.1(1)
Exp. (5.13N)

where
A = 0.7
B = 1.1
C = 1.7 rm
where
rm = M01/M02
say M01 = 0 (pinned end) =rm = 0
C = 1.7 0 = 1.7
n = relative normal force = NEd/Acfcd
= 1824.1 103/(3502 0.85 30/1.5)
= 0.88
= llim,z = 20 0.7 1.1 1.7/0.880.5

= 27.9
= As lz > llim,z column is slender about z axis.

5.4.4 Check slenderness on y axis


Effective length, l0, about z axis:
l0y = 0.5ly [1 + k1/(0.45 + k1) ]0.5 [1 + k2/(0.45 + k2) ]0.5
where
ly
= clear height between restraints
= 4000 + 300/2 750 = 3400 mm
= relative column exibility at end 1
k1
= (Icol/Icol)/[S2(Ibeam/Ibeam)]
where
Icol /Icol = 3504/12 3400 = 3.68 105

On rst pass the default value for B is used. It should be noted that in the
nal design w = Asfyd/Acfcd = 6432 (500/1.15) / (3502 30 0.85/1.5) =
2796/2082 = 1.34. So B = (1 + 2 w)0.5 = (1 + 1.34)0.5 = 1.92 and the column
would not have been deemed slender. B = 1.1 relates approximately to a column
with fck = 30 MPa and r = 0.4%.

* PD 6687 states that to allow for cracking, the contribution of each beam
should be taken as 2EI/lbeam
160

Exp. (5.15)

Cl. 5.8.3.1(1),
& NA,
EC2-1-2: 5.3.3(2)
PD 6687*

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

.'-3LfZeei^kbf^m^k\henfg

Treating beams as rectangular


IbeamAB/lbeamAB = 350 7503/[12 (9000 350)]
= 14.2 105
IbeamBC/lbeamBC = 350 7503/[12 (8000 350)]
= 16.1 105
k1 = 3.68/(2 (16.1 + 14.2) = 0.060 0.1
k1 = 0.1
k2 = (pinned end assumed)
=l0y = 0.5 3400 [1 + 0.1/(0.45 + 0.1) ]0.5 [1 +/(0.45 + ) ]0.5
= 0.5 3400 1.087 1.41
= 0.77 3400 = 2620 mm
Slenderness ratio, ly:
ly
= 3.46l0y/h = 3.46 2620/350

Exp. (5.15)

= 25.9

Limiting slenderness ratio, llim:


llim,y = llim,z
= 27.9
As ly < llim,y, column not slender in y axis.

5.4.5 Design moments: MEdz about z axis


MEdz = max[M02; M0Ed + M2; M01 + 0.5M2]
where
M02 = Mz + eiNEd e0NEd
where
Mz = 146.1 kNm from analysis
eiNEd = effect of imperfections

where
ei = l0/400
e0 = 20 mm
= M02 = 146.1 + (2965/400) 1824.1 0.02 1824.1
= 146.1 + 13.4 > 36.5
= 159.5 kNm

Cl. 5.8.8.2
Cl. 5.8.8.2(1),
6.1.4

Cl. 5.2.7

M0Ed = equivalent 1st order moment at about z axis at about


mid-height may be taken as M0ez where
M0ez = (0.6M02 + 0.4M01) 0.4M02
= 0.6 159.5 + 0.4 0 0.4 159.5 = 95.7 kNm
= nominal 2nd order moment = N>]e2
M2
where
e2 = (1/r) l02/10
where
1/r = curvature = KvKh[fyd/(Es 0.45d)]
where
Kv = a correction factor for axial load
= (nu n)/(nu nbal)

Cl. 5.8.8.2(2)
Cl. 5.8.8.2(3)
Cl. 5.8.8. 3
Exp. (5.34)

161

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
nu = 1 + w
where
w = mechanical ratio
= Asfyd/Acfd
= 1.08 as before
nu = 2.08
n = NEd/Acfcd
= 1824.1/2082 = 0.88
nbal = the value of n at maximum moment
resistance
= 0.40 (default)
(2.08 0.88)/(2.08 0.40)
1.20/1.68 = 0.71
a correction factor for creep
1 + bhef

Kv =
=
Kh =
=
where
b =
=
=
=
hef =
=

0.35 + (fck/200) (l/150)


0.35 + 30/200 29.3/150
0.35 + 0.15 0.195
0.305
effective creep coefcient
h(,t0) M0,Eqp/M0Ed

where
h(,t0) = nal creep coefcient
= from Figure 3.1 for inside conditions
h
= 350 mm, C30/37, t0 = 15

2.4
M0,Eqp = 1st order moment due to quasipermanent loads

Gk + h2 Qk
Mz + eiNEd

jgGGk + h0gQQk
=
=

M0Ed

Cl. 5.8.4(2)

Cl. 3.1.4(2)
Fig. 3.1a

63.3 + 0.8 46.0


Mz + eiNEd
1.35 63.3 + 1.5 46.0
100.1
146.1 + 13.4
154.5

= 108.1 kNm
= M02

= 159.5 kNm

With reference to Exp. (5.13N), hef may be taken as equal to 2.0. However, for the
purpose of illustration the full derivation is shown here.

162

Exp. (5.1.3N)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

.'-3LfZeei^kbf^m^k\henfg

Kh = 1 + 0.305 2.4 108.1/159.5


= 1.50
fyd = 500/1.15 = 434.8 MPa
Es = 200000 MPa
d = effective depth
= 350 35 8 16 = 291 mm
1/r = 0.71 1.50 434.8/(200000 0.45 291)
= 0.0000177
l0 = 2965 mm as before
e2 = (1/r) l02/10
= 15.6 mm
= 0.0000177 29652/10
 =M2 = NEde2 = 1824.1 103 15.6
= 28.4 kNm
=0
M01
= MEdz = max[M02z; M0Edz + M2; M01 + 0.5M2]
= max[159.5; 95.7 + 28.4; 0 + 28.4/2]
= 159.5 kNm

Mz = 146.1 kNm

Mz = 0

M2/2 = 14.2 kNm

a) 1st order moments


from analysis

MEdz = 159.5 kNm

eiNEd = 13.4 kNm

M2 = 28.4 kNm

Cl. 3.2.7(3)

MOEdz = 95.8 kNm

Mz = 0

c) Design moments: MEdz


b) Including 2nd order moments:
about z axis
MEdz = max [M02, MOEd + M2, M01 = 0.5M2]

Figure 5.13 Design moments MEdz

5.4.6 Design moments: MEdy about y axis

MEdy = max[ M02y ; M0Edy + M2 ; M01 + 0.5M2]

where
M02y =
=
=
M0Edy =
=

My + eiNEd e0NEd
114.5 + 13.4 36.7 kNm
127.9 kNm
(0.6M02y + 0.4 M01y) 0.4M02y
0.6 114.5 + 0.4 0

Imperfections need to be taken into account in one direction only.

Cl. 5.8.9(2)
163

M2

= 68.7 kNm
= 0 (as column is not slender not slender about y axis).
= MEdy = 127.9 kNm

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

5.4.7 Design in each direction using charts


= 1824.1 103/(3502 30)
= 0.50
2
MEd/bh fck = 159.5 106/(3503 30)
= 0.124
Assuming 8 bar arrangement, centroid of bars in half section:
d2 35 + 8 + 16 + (350/2 35 8 16) 1/4

59 + 29 = 88 mm
d2/h = 0.25

In z direction: NEd/bhfck

From Figure C4e)


Asfyk/bhfck = 0.50
= 0.50 3502 30/500 = 3675 mm2
As
= 4 no. H32 + 4 no. T25 (5180 mm2) OK.

Fig. C4e)

Fig. C4e)

In y direction: MEd/bh2fck = 127.9 106/(3503 30)


= 0.10
NEd/bhfck = 0.50
From Figure C4e)
Asfyk/bhfck = 0.34
= 0.34 3502 30/500 = 2499 mm2
As
= 4 no. H32 + 4 no. T25 (5180 mm2) OK.

5.4.8 Check biaxial bending


ly lz = OK.
ez = MEdy/NEd
ey = MEdz/NEd
MEdz 159.5
ey/heq
=
=
= 1.25
MEdy 127.9
ez/beq
= need to check biaxial bending
(MEdz/MRdz)a + (MEdy/MRdy)a 1.0
where
MRdz = MRdy = moment resistance=
Using Figure C4e)
Asfyk/bhfck = 5180 500/(3502 30)
= 0.70
for NEd/bhfck = 0.50
MEd/bh2fck = 0.160

= MRd = 0.160 3503 30
164

Exp. (5.38a)

Exp. (5.38b)

Exp. (5.39)

Fig. C4e)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

.'-3LfZeei^kbf^m^k\henfg

= 205.8 kNm
a depends on NEd/NRd
where
= Acfcd + Asfyd
NRd
= 3502 0.85 30/1.5 + 5180 500/1.15
= 2082.5 + 2252.2
= 4332.7 kN
NEd/NRd = 1824.1/4332.7 = 0.42

= a = 1.27
(159.5/205.8)1.27 + (114.5/205.8)1.27 = 0.72 + 0.47
= 1.19
= No good
= Try 8 no. T32 (6432 mm2)
For Asfyk/bhfck =
=
for NEd/bhfck =
=
MEd/bh2fck
= MRd
=

6432 500/(3502 30)


0.88
0.50
0.187
240.5 kNm

Check biaxial bending


(159.5/245.7)1.27 + (114.5/245.7)1.27

= 0.59 + 0.39

Cl. 5.8.9(4)

Fig. C4e)

= 0.98 OK

5.4.9 Check maximum area of reinforcement


As/bd = 6432/3502 = 5.2% > 4%
However, if laps can be avoided in this single lift column then the
integrity of the concrete is unlikely to be affected and 5.2% is
considered OK.
OK

Cl. 9.5.2(3) & NA

PD 6687: 2.19

5.4.10 Design of links


Diameter min. = 32/4 = 8 mm
Spacing max. = 0.6 350 = 210 mm

Cl. 9.5.3 & NA


Cl. 9.5.3(3),
9.5.3(4)
= Use H8 @ 200 mm cc

5.4.11 Design summary


8 H32
H8 links @ 200 cc
35 mm cover to link
No laps in column section
Note
The beam should be checked for torsion.

Figure 5.14 Design summary: small perimeter column


165

/ Walls

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

/') General
PZeel Zk^ ]^g^] Zl [^bg` o^kmb\Ze ^e^f^gml pahl^ e^g`mal Zk^ _hnk mbf^l `k^Zm^k maZg ma^bk
mab\dg^ll^l'Ma^bk]^lb`g]h^lghm]b__^klb`gb\Zgmer_khfma^]^lb`gh_\henfglbgmaZmZqbZe
ehZ]lZg]fhf^gmlZ[hnm^Z\aZqblZk^Zll^ll^]Zg]]^lb`g^]_hk'
Ma^\Ze\neZmbhglbgmabll^\mbhgbeenlmkZm^ma^]^lb`gh_Zlbg`e^la^ZkpZee'
@^g^kZeer%ma^f^mah]h_]^lb`gbg`pZeelblZl_heehpl'BgikZ\mb\^%l^o^kZeh_ma^l^lm^ilfZr[^
\hf[bg^]'
N =^m^kfbg^]^lb`geb_^'

EC0 & NA Table NA 2.1

N :ll^llZ\mbhglhgma^pZee'

EC1 (10 parts) & UK NAs

N =^m^kfbg^pab\a\hf[bgZmbhglh_Z\mbhglZiier'

EC0 & NA: Tables NA A1.1 &


NA: A1.2(B)

N :ll^ll]nkZ[bebmrk^jnbk^f^gmlZg]]^m^kfbg^\hg\k^m^

BS 85001

lmk^g`ma'
N <a^\d\ho^kk^jnbk^f^gml_hkZiikhikbZm^_bk^

k^lblmZg\^i^kbh]'

Approved Document B
EC212

N =^m^kfbg^\ho^k_hk_bk^%]nkZ[bebmrZg][hg]'

Cl. 4.4.1

N :gZerl^lmkn\mnk^_hk\kbmb\Ze\hf[bgZmbhgfhf^gml

Section 5

Zg]ZqbZe_hk\^l'

166

N <a^\dle^g]^kg^llZg]]^m^kfbg^]^lb`gfhf^gml'

Section 5.8

N =^m^kfbg^Zk^Zh_k^bg_hk\^f^gmk^jnbk^]'

Section 6.1

N <a^\dliZ\bg`h_[Zkl'

Sections 8 & 9

PZeel

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

/'* Shear wall


>qZfie^ /'* lahpl ma^ ]^lb`g h_ Z lbfie^ ebg^Zk la^Zk pZee Zl mrib\Zeer nl^] bg f^]bnf&
kbl^ [nbe]bg`l' LbfbeZk ikbg\bie^l fZr [^ Ziieb^] mh pZeel maZm Zk^ laZi^] Zl<% E%M% S Zg]
k^\mZg`e^lbg&ieZg%[nmblln^lh_ebfbmbg`Zg`^]bf^glbhglZg]la^ZkZm\hkg^klg^^]mh[^
Z]]k^ll^]'Ma^ ^qZfie^ lahpl hger NEL ]^lb`g Zl% ZiZkm _khf fbgbfnf Zk^Zl h_ lm^^e mh
\hgmkhe \kZ\dbg`% LEL blln^l Zk^ `^g^kZeer ghg&\kbmb\Ze bg f^]bnf&kbl^ lmkn\mnk^l' ?hk la^Zk
pZeelbgab`a&kbl^lmkn\mnk^l%k^_^k^g\^lahne][^fZ]^mhli^\bZeblmebm^kZmnk^T+2V'
Ma^^qZfie^blbgm^g]^]mhlahpahpZla^ZkpZeeikhob]bg`iZkmh_ma^eZm^kZelmZ[bebmrbghg^
]bk^\mbhgbgZf^]bnfkbl^lmkn\mnk^fb`am[^]^lb`g^][raZg]'
:qbZeehZ]lZg]klmhk]^kfhf^gmlZk^]^m^kfbg^]'Ma^]^lb`g\hglb]^klle^g]^kg^llbghk]^k
mh ]^m^kfbg^ ]^lb`g fhf^gml% F>]% bg ma^ ieZg^ i^ki^g]b\neZk mh ma^ pZee'Ma^ ^__^\ml h_
Zeehpbg`_hkbfi^k_^\mbhglZk^ZelhbeenlmkZm^]'
Ikhc^\m]^mZbel

<Ze\neZm^][r

chg

Ch[gh'

Shear wall

<a^\d^][r

web

La^^mgh'

<eb^gm

TCC

=Zm^

CCIP 041
1
Oct 09

Wall A is 200 mm thick and, in addition to providing vertical support


to 200 mm at slabs at roof level and oors 1 to 3, it helps to
provide lateral stability to the four-storey ofce block. Assuming the
stair itself provides no lateral stability, the wall is to be designed for
the critical section at ground and rst oor level using BS EN 1990
Exp. (6.10). The concrete is C30/37. The wall is supported on pad
foundations and the ground oor is ground bearing.
X
300

1300

4800

4400

Wall A

1500

4800

7200

4800
300
300 3600 6000

6000

6000

6000 2500 300


N

30700

Figure 6
6.11 Typical floor plan
900

Roof
3rd

4@3300

2nd
1st

600
900

Gnd

Figure 6.2 Section XX

167

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

6.1.1 Actions

Roof

Paving 40 mm
Waterproong
Insulation
Suspended ceiling
Services
Self-weight 200 mm slab
Imposed load

Floor
slabs

Carpet
Raised oor
Suspended ceiling
Services
Self-weight 200 mm slab

Permanent Variable
actions
actions
gk
qk
kN/m2
1.00
0.50
0.10
0.15
0.30
5.00
7.05
0.60

Ground
oor
slab
(ground
bearing)

Carpet
Raised oor
Services
Self-weight 200 mm slab

Stairs

150 waist @ 30
Treads 0.15 0.25 25 4/2 =
Screed 0.05 22 =
Plaster
Tiles and bedding

Section 2.4.2

3.00

Section 2.4.2
Section 2.8

4.40
1.88
1.10
0.21
1.00
8.59
2.50

Imposed load

168

2.50
0.03
0.30
0.15
5.00
5.48

Imposed load

Cavity
wall

102 mm brickwork
50 mm insulation
100 mm blockwork
Plaster

2.37
0.02
1.40
0.21
4.00

RC wall

200 mm wall
Plaster both sides

5.00
0.42
5.42

Wind

wk =

Section 2.4.2

Section 2.8

0.03
0.30
0.15
0.30
5.00
5.78

Imposed load

Section 2.8

Section 2.4.2
Section 2.8

Section 2.8

1.10

EC1-1-4 & NA

/'*3La^ZkPZee

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

6.1.2 Load take-down


Consider whole wall.
Gk
Item
Calculation
From item Cum. total
Roof
(6.0/2 + 2.5/2) (4.4 + 1.5/2) (7.05
+ 0.6) =
154.3
Roof
(6.0/2) (1.3/2) (7.05 + 0.6) =
13.7
Wall
3.3 4.4 5.42 =
78.7
246.7
At above 3rd oor
246.7
3rd oor (6.0/2) (1.3/2 + 4.4 + 1.5/2)
(5.78 + 2.5) =
100.6
Landing (2.5/2 1.5/2) (5.78 + 2.5)
11.6
Wall
a. b.
78.7
Stair
say 1.1 4.4 (8.59 + 2.5)
41.6
232.5
At above 2nd oor
479.2
2nd oor, landing, wall and stair a. b.
232.5
At above 1st oor
711.7
1st oor, landing, wall and stair a. b.
232.5
At above ground oor
944.2
Ground oor assume 1 m all round =
2 (1.3/2 + 4.40 + 1.5/2) (5.48 + 3.0) = 63.6
250 mm wall to foundation 4.4 0.2 0.6 25 =
13.2
76.8
At above foundation
1021.0

Qk
From item Cum. total
13.1
1.2
14.3
14.3
43.5
5.0
12.1
60.6
74.9
60.6
135.5
60.6
196.1
34.8

230.9

6.1.3 Design actions due to vertical load at ground1st


Gk = 944.2
Gk/m = 944.2/4.4 = 214.6 kN/m
Qk = an 196.1
where
an = 1.1 n/10
where
n = no. of storeys qualifying for reduction
=3
= 1.1 3/10 = 0.8
Qk/m = 156.9/4.4 = 35.7 kN/m
= Qk = 0.8 196.1 = 156.9 kN

EC1-1-1:
6.3.1.2(11) & NA

Includes storeys supporting Categories A (residential and domestic), B (ofce),


C (areas of congregation) and D (shopping), but excludes E (storage and
industrial), F (trafc), G (trafc) and H (roofs).
169

6.1.4 Vertical loads from wind action: moments in plane


Consider wind loads, NS
300 3600

6000

6000

6000

6000

2500 300

2400 o/a

Wall A

4400

2400

Lift shaft
200 thick
walls
N

wk = 1.10 kN/m2

Figure 6.3 Lateral stability against wind loads NS


Check relative stiffness of lift shaft and wall A to determine share
of load on wall A.
Lift shaft: ILS
= 2.44/12 2.04/12 0.2 1.63/12
= 1.36 m4
Wall A:
IWallA = 0.2 4.43/12
= 1.41 m4
where I = inertia
= Wall A takes 1.41/(1.41 + 1.36) = 51% of wind load.
Check shear centre to resolve the effects of torsion.
Determine centre of gravity, CoGL of the lift shaft.
2.4 2.4 =

Area, A

Lever arm, x

Ax

5.76

1.2

6.912

2.0 2.0 =

4.00

1.2

4.800

1.6 0.2 =

0.32

2.3

0.732

1.44

1.38

1600 200 200

2400

2400

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

30700

CoGL

x
170

Figure 6.4 Lift shaft

/'*3La^ZkpZee

x = Ax/A = 1.38/1.44 = 0.956 m


i.e. from face of lift shaft to CoG of shaft
= 2.40 0.956 = 1.444 m

=
or

ILS (1.44 + 24.00 + 0.05) 1.36 25.49


=
= 12.56 m from wall A
1.36 + 1.41
ILS + IWallA

= 12.56 + 2.80 0.05 = 15.31 from east end of building.

1.45

CL Wall A
2.80

24.00
15.31

Wall A

* Cw

CoGL

Wk

15.35

Figure 6.5 Shear centre, Cw and centre of action, Wk


Centre of action (30.7/2 = 15.35 m from end of building) and shear
centre (almost) coincide. = there is no torsion to resolve in the
stability system for wind in a NS direction.#
Roof

900
3300
3300
3300
3300
600
900

3rd
14100

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Shear centre, Cw of walls, from centreline of wall A

2nd

wk = 17.2 kN/m

1st
Gnd

Figure 6.6 Wall A


wind loads NS
300 4400 300

= Wall A takes 51% of wind load, so characteristic wind load on wall A,


wk, wall A = 51% wk Lx = 51% 1.1 30.7 = 17.2 kN/m
Assuming centreline of wall A is 50 mm to right hand side of grid.
#Had

there been signicant torsion this would have been resolved into +/ forces
in a couple based on the shear walls.
171

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

= at just above ground oor, characteristic in-plane moment


in wall A, Mk, due in this case to wind
= 17.2 14.12/2 = 1709.8 kNm
Resolving into couple using 1 m either end of wall, characteristic wind
load in each end, Wk
= 1709.8/3.4
= 502.9 kN

6.1.5 Effects of global imperfections in plane of wall A


Roof

HIR

yI

3rd
2nd
1st
Gnd

HI3
HI2
HI1
HIG

Figure 6.7 Global imperfections


Global imperfections can be represented by forces Hi at oor level
where
Hi = yi(Nb Na)
where
yi = (1/200) aham
where
ah = 0.67 2/l 0.5 1.0
= 0.67 2/14.70.5 1.0
= 0.67 0.52 1.0
= 0.67
am = [0.5(1 + 1/m)]0.5
where
m = no. of members contributing to the total effect
= 25 vertical elements on 4 oors
= 100

For medium-rise shear walls there are a number of methods of design. Cl. 9.6.1
suggests strut-and-tie (see Volume 2 of these worked examples[30]). Another
method[26] is to determine elastic tensile and compression stresses from NEd/bL
+/ 6MEd/bL2 and determine reinforcement requirements based on those maxima.
The method used here assumes a couple, consisting of 1.0 m of wall either end of
the wall. The reinforcement in tension is assumed to act at the centre of one end
and the concrete in compression (with a rectangular stress distribution) acts at
the centre of the other end. The forces generated by the couple add or subtract
from the axial load in the 1 m ends of the walls. The method is useful for typical
straight shear walls of say 2.5 to 5.0 m in length.

172

Exp. (5.4)
Cl. 5.2(1), 5.2(5),
5.2(8) & NA

Vol. 2

/'*3La^ZkpZee

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

= am = 0.71
= yi = 0.67 0.71/200
= 0.0024
= axial forces in members below and above
Nb, Na
(Nb Na) = axial load from each level

At roof level
Area
= 30.4 14.5 1.3 2.5 3.6 4.8 = 420.3 m3
Perimeter = 2 (30.4 + 14.5)
= 89.8 m
(Na Nb) = axial load from roof level
= 420.3 (7.05 + 0.6) + 89.8 0.9 4.0 = 3286.4 + 252.2 kN
At 3rd oor
(Na Nb) = 420.3 (5.78 + 2.5) + 89.8 3.3 4.0

= 3615.7 + 1050.8 kN

At 2nd oor
(Na Nb) = 3615.7 + 1050.8 kN
At 1st oor
(Na Nb) = 3615.7 + 1050.8 kN
HiR = 0.0024 (3286.4 + 252.2) = 7.9 + 0.6 = 8.5 kN
Hi3 = Hi2 = Hi1 = 0.0024 (3615.7 + 1050.8) = 8.7 + 2.5 = 11.2 kN
Characteristic design moment at ground oor,
Mk = 8.5 13.2 + 11.2 (9.90 + 6.60 + 3.30)
= 112.2 + 221.8 = 334.0 kNm
As before, wall A resists 51% of this moment. Resolving into couple
using 1 m either end of wall,
= GkH = 0.51 334.0/3.4 = 50.1 kN
i.e. GkH = 50.1 kN/m

6.1.6 Check for global second order effects


To check whether the building might act as a sway frame check
FV,Ed kl

SEcd Ic
ns
=
ns + 1.6
L2

Cl. 5.8.3.3(1)
Exp. (5.18)

where
FV,Ed = Total vertical load (on braced and bracing members)
where
Floor area = (30.7 2 0.15) 14.4 (2 0.15) 3.6
4.8 1.3 2.5
= 428.6 20.5 = 408.1

As H derives mainly from permanent actions its resulting effects are


i
considered as being a permanent action too.

173

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Loads
from roof: 408 (7.05 + 0.6) =
31 oors: 3 408 (5.78 + 2.5) =
Allow cavity wall at 1st oor and above

Gk
2876
7075

(3 3.30 + 0.9) 2 (30.4 + 14.1) 4.0 =

3845
13705

Imposed load reduction 20% (see 6.2.3)


13705

Qk
245
3060

3305
661
2644

=FV,Ed 13705 1.35 + 1.5 2644


= 22468 kN
= 0.31
kl
= number of storeys
ns
= 4 (including roof)
= Ecm/gCE = 33/1.2 = 27.5 GPa
Ecd
= Inertia of bracing members
Ic
in NS direction
Ic = 1.36 + 1.41 = 2.77 m4 (See Section 6.1.4)
in EW direction
ILS, with reference to Figure 6.4
hd
2.4 2.4 =

Area, A

Ax

Ax 2

5.76

1.2

6.912

8.294

2.765

2.0 2.0 = 4.00

1.2

4.800

5.760

1.333

1.6 0.2 = 0.32

2.3

0.732

1.683

0.001

1.38

0.851

1.44

1.431

as before (6.1.4), x = 1.38/1.44


= 0.956 m
ILS = INU = Ax 2 + I Ax 2
= 0.851 + 1.431 1.44 0.956
= 0.965 m4
L = total height of building above level of moment restraint
= 14.7 (see Figure 6.6)
Check
ns
SEcdIc

on weak EW axis:
kl
L2
ns + 1.6
= 0.31 [4/(4 + 1.6)] 27500 103 (0.965/14.72)
= 27200 kN
= no need to design for 2nd order effects.
i.e. > FV,Ed

174

Cl. 5.8.2(6) & NA


Table 3.1,
5.8.6(3) & NA

/'*3La^ZkpZee

6.1.7 Design moments perpendicular to plane of wall


CL
150

650

B
1350

1st

4400

200

A
Gnd

750

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

CL

up

CL

Figure 6.8 Plan of wall A and location


of sections AA and BB

Figure 6.9 Section AA

Section AA @ 1st oor


The slab frames into the wall. For the purposes of assessing xed
end moments, the width of slab contributing to the moments in the
wall is assumed to be the length of the wall plus distances half way
to adjacent supports either end. Therefore, consider the xed end
moment for 1.50/2 + 4.40 + 1.30/2 = 5.8 m width of adjoining slab
framing into the 4.4 m long shear wall (see Figure 6.8).

kw

n
ks

kw

Figure 6.10 Subframe section AA @ 1st floor


FEM: assuming imposed load is a leading variable action:
= nl2/8
= 5.8 (1.35 5.78 + 1.5 2.5) 6.02/8
= 5.8 11.6 62/8 = 302.8 kNm

EC0: Exp. (6.10)


& NA

FEM: xed end moment


175

Similarly, assuming imposed load is an accompanying action:


FEM = 5.8 (1.35 5.78 + 0.7 1.5 2.5) 62/8
= 5.8 10.4 62/8 = 271.4 kNm
=M = 271.4 0.42/4.40
= 25.9 kNm/m @ ULS
Section AA @ ground oor
By inspection not critical nominal moment.
Section BB @ 1st
Consider the landing inuences half of wall (2.2 m long) and that
this section of wall is subject to supporting half the slab considered
before at 1st oor level at Section AA.
1st
1650

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

kw = EI/l = E 4400 2003/(12 3300)


= E 8.88 105
ks = EI/2l = E 5800 2003/(2 12 6000)
= E 3.22 105
M = 302.8 8.88/(2 8.8 + 3.22)
= 302.8 0.42
= 121.2 kNm
i.e. 121.2/4.40
= 27.5 kNm/m @ ULS

Landing

Gnd

Figure 6.11 Section BB


FEM = 302.8/2 = 151.4 kNm
kw = I/l
= 2200 2003/(12 1650) = 8.88 105
ks = 3.22 105/2 = 1.61 105
M = 151.4 8.88/(2 8.88 + 1.61)
= 151.4 0.46
= 69.6 kNm
i.e. 63.8/2.2
= 31.6 kNm/m @ ULS
176

/'*3La^ZkpZee

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Similarly, assuming imposed load is an accompanying action:


FEM = 5.8 (1.35 5.78 + 0.7 1.5 2.5) 62/8
= 5.8 10.4 62/8 = 271.4 kNm
=M = 271.4 0.46/(2 2.2)
= 28.4 kNm/m @ ULS
Section BB @ landing level and ground oor
By inspection not critical

6.1.8 Consider slenderness of wall at ground floor


To derive maximum slenderness (at south end of wall), ignore effect
of landing.
Effective length, l0 = 0.75 (3300 200) = 2325
l = 3.46 l0/h = 3.46 2325/200 = 40.2
Limiting slenderness, llim = 20 ABC/n0.5
where
A = 0.7
B = 1.1
C = 1.7 rm
where
rm = M01/M02
= say = 0.25
C = 1.95
n = NEd/Acfd
where
NEd = 214.6 1.25 + 31.2 1.5 0.7 + 502.9 1.5 +
98.2 1.5 0.7
= 268.3 + 32.8 + 754.4 + 103.1
= 1158.6 kN
Acfd = 200 1000 0.85 30/1.5 = 3400 kN

= n = 0.34
= llim = 20 0.7 1.1 1.95/0.340.5 = 51.5
= As l < llim wall is not slender and = no secondary moments

Table C16
Cl. 5.8.3.2(1)
Cl. 5.8.3.1(1),
Exp. (5.13N)

6.1.9 Summary: design forces on wall, ground1st floor


At ground to 1st consider maxima.
Vertical loads

Gk = 214.6 kN/m
Qk = 35.7 kN/m

Vertical load due to in-plane bending and wind

Wk = 502.9 kN/m

Vertical load due to in-plane bending and imperfections


GkH = 50.1 kN/m
Maximum moment out of plane, oor imposed load as leading action
M = 31.6 kN/m @ ULS
Maximum moment out of plane, oor imposed load as accompanying action
M = 28.4 kN/m @ ULS
Assuming

wind load is lead variable action.


177

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

6.1.10 Combinations of actions at ground1st floor


a) At ULS, for maximum axial load, Wk is leading variable action
NEd = 1.35Gk + 1.5Qk1 + 1.5c0Qki
= 1.35 (214.6 + 50.1) + 1.5 502.9 + 1.5 0.7 35.7
= 357.3 + 754.4 + 37.5
= 1149.2 kN/m
MEd = M + eiNEd e0NEd
where
M = moment from 1st order analysis
= 28.4 kNm/m
ei = l0 /400 = 2325/400 = 5.8 mm
e0 = h/30 20 mm = 20 mm
MEd = 28.4 + 0.0058 1149.2.1 0.020 1149.2
= 28.4 + 6.7 23.0 = 35.1 kNm/m
b) At ULS, for minimum axial load, Wk is leading variable action
NEd = 1.0 214.6 1.35 50.1 1.5 502.9 + 0 35.7
= 607.4 kN/m (tension)
MEd = 28.4 + 0.0058 607.4 0.020 602.4
= 28.4 + 3.5 23.0
= 31.9 kNm/m
c) At ULS, for maximum out of plane bending assuming Qk is leading
variable action
NEd = 1.35 (214.6 + 50.1) + 1.5 35.7 + 1.5 0.5 502.9
= 357.3 + 53.6 + 377.2
= 788.1 kN/m
MEd = 31.6 + 0.0058 788.1 0.020 788.1
= 31.6 + 4.6 15.8
= 36.2 kNm/m
or
NEd = 1.0 214.6 1.35 50.1 0 31.2 1.5 0.5 502.9
= 214.6 67.6 0 377.2
= 230.2 kN/m (tension)
MEd = 31.6 + 0.0058 230.2
= 33.0 kNm/m
d) Design load cases
Consolidate c) into a) and b) to consider two load cases:
NEd = 1149.4 kN/m,
MEd = 36.2 kN/m (out of plane)
and
NEd = 607.4 kN/m,
MEd = 36.2 kN/m (out of plane)

178

Strictly incompatible with Qk = 0. However, allow Qk = 0.

Cl. 5.8.8.2(1),
6.1.4

Cl. 5.2(7), 5.2(9)


Cl. 6.1.4

/'*3La^ZkpZee

6.1.11 Design: cover above ground


cnom = cmin + Dcdev

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

where
cmin = max[cmin,b ; cmin,dur]

Exp. (4.1)

where
cmin,b = diameter of bar = 20 mm vertical or 10 mm lacers
cmin,dur = for XC1 = 15 mm
Dcdev = 10 mm
25 mm to lacers
=cnom = 15 + 10 =
(35 mm to vertical bars)

6.1.12 Fire resistance


Assuming 1-hour re resistance required for, as a worst case, = 0.7
and re on both sides.
Min. thickness = 140 mm, min. axis distance = 10 mm
i.e. not critical

EC2-1-2: Table 5.4

6.1.13 Design using charts


For compressive load:
d 2/h = (25 + 10 + 16/2)/200 = 0.215
= interpolate between charts C5d) and C5e) for
NEd/bhfck = 1149.4 103/(200 1000 30) = 0.192
MEd/bh2fck = 36.2 106/(2002 1000 30) = 0.030
Gives:
Asfyk/bhfck = 0 = minimum area of reinforcement required
= 0.002 Ac
= 0.002 200 1000
= 400 mm2/m
= 200 mm2/m each face
max. 400 mm cc, min. 12 mm diameter
Try T12 @ 400

Figs C5d), C5e)

Cl. 9.6.2 & NA

Cl. 9.6.2(3);
SMDSC

As /2

sst2

sst1

As /2
0

Moment

Tension

Combined

Combined

Figure 6.12 Stresses and strains in wall subject to tension and


out of p
plane moment
179

For tensile load and moment:


Working from rst principles, referring to Figure 6.12 and ignoring
contribution from concrete in tension,
NEd

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

and MEd
so

= (sst1 + sst2) As/2


= (sst1 sst2) As/2 (d d2)

sst1 + sst2 = 2NEd/As

and sst1 sst2 = 2MEd/[(d d2)As]


=

2sst1

= 2NEd/As + 2MEd/[(d d2)As]

As

= (NEd/sst1) + MEd/(d d2)sst1

sst1

= fyk/gS = 500/1.15 = 434.8

As

= 607.4 103/434.8 + 36.2 106/[(157 43) 434.8]

= 1397 + 730
= 2127 mm2
sst2

= 2NEd/As sst1 = 571.7 434.8 = 136 MPa

By inspection all concrete is in tension zone and may be ignored.


Use 6 no. H16 @ 200 cc both sides for at least
1 m each end of wall (2412 mm2).

6.1.14 Horizontal reinforcement


As, hmin = 0.001As or 25% As vert
= 200 mm2 or 0.25 2036 = 509 mm2/m

= requires 254 mm2/m each side
Spacing 400 mm
Links not required.
Use H10 @ 300 (262 mm2/m) both sides.

Cl. 9.6.3(1) & NA

Cl. 9.6.3(2)
Cl. 9.6.4(1)

6.1.15 Check for tension at top of foundation

180

Permanent and variable:


= 1021.0/4.4 = 232.0 kN/m
Gk
= 230.9/4.4 = 52.5 kN/m
Qk

Section 6.1.2

Wind:
= 17.2 14.1 [14.1/2 + 0.6] = 1855.3 kN/m
Mk
Resolved into couple 1 m either end of wall
= 1855.3/3.4 = 545.7 kN/m
Wkw

Section 6.1.4

Global imperfections:
= 8.5 13.8 + 11.2 (10.5 + 7.2 + 3.9 + 0.6)
Mk
= 365.9 kNm
= 365.9 0.51/3.4 = 54.9 kN/m
GkH

Section 6.1.5

/'*3La^ZkpZee

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

At ULS for maximum axial tension Wk is lead imposed load:


= 1.0 232.0 1.35 54.9 1.5 545.7 + 0 52.5
NEd
= 660.7 kN/m
= nominal = e2NEd = 0.02 660.7
MEd
= 13.2 kNm/m

Cl. 6.1.4

As before
As

NEd
MEd
+
fyk/gM
(d d2)fyk/gM

= 660.7 103/434.8 + 13.2 106/[(157 43) 434.8]


= 1520 + 266
= 1786 mm2 i.e. not critical
= Use 6 no. H16 @ 200 cc b.s. for at least 1 m either end of wall
(2412 mm2).

6.1.16 Check for axial compression at top of foundation


At ULS for maximum axial compression Wk is lead imposed load:
NEd = 1.35 232.0 + 1.35 54.9 + 1.5 545.7 + 0.7 1.5 52.5
= 1261.0 kN/m
MEd = nominal = e2NEd = 0.02 1261.0
= 25.2 kNm/m
By inspection not critical (minimum reinforcement required).
= tension critical as above.

Cl. 6.1.4
Section 6.1.13

6.1.17 Design: cover below ground


cnom = cmin + Dcdev
where
cmin = max[cmin,b ; cmin,dur]
where
cmin,b = diameter of bar = 16 mm vertical or 10 mm lacers
cmin,dur = for assumed Aggressive Chemical Environment for
Concrete (ACEC) class AC1 ground conditions
= 25 mm

Exp. (4.1)

BS 8500-1
Annex A[14],
How to: Building
structures[8]

Dcdev = 10 mm
cnom = 25 + 10 =

35 mm to lacers
(45 mm to vertical bars)
In order to align vertical bars from foundation into Gnd1st oor lift
as starter bars, locally increase thickness of wall to say
250 mm thick with cnom = 50 mm

181

6.1.18 Check stability

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Assume base extends 0.3 m beyond either end of wall A, i.e. is 5.0 m long
and is 1.2 m wide by 0.9 m deep.
Overturning moments
Wind (see Figure 6.6)
Mk = 17.2 14.1 [14.1/2 + 1.5]
= 2073.5 kNm
Global imperfections (see Section 6.1.5)
Mk = 0.51 x [8.5 14.7 + 11.2 (11.4 + 8.1 + 4.8 + 1.5)]
= 0.51 x [125.0 + 11.2 25.8]
= 0.51 x 414.0
= 211 kNm

EC0: Table
A1.2(A) & NA
Fig. 6.6

Fig. 6.7

Restoring moment
Mk = (1021.0 + 5.0 x 1.2 x 0.9 x 25 + 0 x 230.9 ) x (0.3 + 2.2)
= 2890 kNm
At ULS of EQU,
Overturning moment
= fn(gQ,1Qk1 + gG,supGk)
= 1.5 x 2073.5 + 1.1 x 211.0 = 3342.4 kNm
Restoring moment
= fn(gG,infGk)
= 0.9 x 2890 = 2601 kNm i.e. > 1818.4 kNm

EC0: Table
A1.2(A) & NA

= no good

Try 1.05 m outstand


Restoring moment
Mk = 2890 (1.05 + 2.2) / (0.3 + 2.2)
= 3757.0 kNm
At ULS, restoring moment = 0.9 x 357.0
= 3381.3 kNm
=OK. Use 1.05 m outstand to wall.

6.1.19 Design summary


1st
Lacers H10 @
300 m outside
25 mm cover to 200 mm
wall above ground floor
H12 @ 400 b.s

1050

182

12

12

24H16 @ 200
Gnd (12NF, 12FF)
50 mm cover
to 250 wall
below ground floor
1050

EC0:
Table A1.2(A)
& NA

03K^_^k^g\^lZg]_nkma^kk^Z]bg`

7 References and further reading

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

References




1 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L>G*22+**%>nkh\h]^+IZkm**3=^lb`gh_
\hg\k^m^lmkn\mnk^l@^g^kZekne^lZg]kne^l_hk[nbe]bg`l';LB%+))-'
 1a GZmbhgZe:gg^qmh>nkh\h]^+IZkm**';LB%+)).'
2 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L>G*22+*+%>nkh\h]^+IZkm*+3=^lb`gh_
\hg\k^m^lmkn\mnk^l@^g^kZekne^lLmkn\mnkZe_bk^]^lb`g';LB%+))-'
 2a GZmbhgZe:gg^qmh>nkh\h]^+IZkm*+';LB%+)).'

3 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L>G*22++%>nkh\h]^+IZkm+3=^lb`gh_
\hg\k^m^lmkn\mnk^l;kb]`^l';LB%+)).'
3a GZmbhgZe:gg^qmh>nkh\h]^+IZkm+';LB%+))0'

4 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L>G*22+,%>nkh\h]^+IZkm,3=^lb`gh_
\hg\k^m^lmkn\mnk^lEbjnb]&k^mZbgbg`Zg]\hgmZbgf^gmlmkn\mnk^l';LB%+))/' 
4a GZmbhgZe:gg^qmh>nkh\h]^+IZkm,';LB%+))0'



5 K
 LG:K:R:G:G<A@HH=<ABE='Ma^<hg\k^m^<^gmk^'<hg\bl^>nkh\h]^+'
<<BI&)).'M<<%+))/'

6 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG'I=//10;Z\d`khng]iZi^kmhma^NDGZmbhgZe
:gg^q^l;L>G*22+*';LB%+))/'

7 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L1**)Lmkn\mnkZenl^h_\hg\k^m^IZkm*3<h]^h_
ikZ\mb\^_hk]^lb`gZg]\hglmkn\mbhg';LB%*220'

8 ;
 KHHD>K%H^mZe'Ahpmh]^lb`g\hg\k^m^lmkn\mnk^lnlbg`>nkh\h]^+'<<BI&))/'
Ma^<hg\k^m^<^gmk^%+))/'Ni]Zm^]_hk]hpgehZ]hger+))2'

9 M A>BGLMBMNMBHGH?LMKN<MNK:E>G@BG>>KL(MA><HG<K>M>LH<B>MR(=MB'LmZg]Zk]
f^mah]h_]^mZbebg`lmkn\mnkZe\hg\k^m^%Mabk]>]bmbhg'BLmkn\m>%+))/'










10 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L>G*22)%>nkh\h]^3;Zlblh_lmkn\mnkZe]^lb`g'
;LB%+))+'
 10a GZmbhgZe:gg^qmh>nkh\h]^';LB%+))-'
11 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L>G*22*%>nkh\h]^*3:\mbhglhglmkn\mnk^l
!*)iZkml"';LB%+))++))/'
 11a GZmbhgZe:gg^q^lmh>nkh\h]^*';LB%+)).+))1Zg]bgik^iZkZmbhg'
12 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L>G*220*%>nkh\h]^0'@^hm^\agb\Ze]^lb`g'
@^g^kZekne^l';LB%+))-'
 12a GZmbhgZe:gg^qmh>nkh\h]^0;L>G*220*';LB%+))0'
13 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L>G*221*%>nkh\h]^1'=^lb`gh_lmkn\mnk^l_hk
^ZkmajnZd^k^lblmZg\^'@^g^kZekne^l'L^blfb\Z\mbhgl_hk[nbe]bg`l';LB%+))-'
 13a GZmbhgZe:gg^qmh>nkh\h]^1;L>G*221*';LB%+))1'

14 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L1.))*3<hg\k^m^<hfie^f^gmZkr;kbmbla
LmZg]Zk]mh;L>G+)/*3F^mah]h_li^\b_rbg`Zg]`nb]Zg\^mhma^li^\b_b^k';LB%+))+'

15 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L---23Lm^^e_hkma^k^bg_hk\^f^gmh_\hg\k^m^
P^e]Z[e^k^bg_hk\bg`lm^^e;Zk%\hbeZg]]^\hbe^]ikh]n\mLi^\b_b\Zmbhg';LB%+)).'

16 <
 HGLMKN<M'GZmbhgZelmkn\mnkZe\hg\k^m^li^\b_b\Zmbhg_hk[nbe]bg`\hglmkn\mbhg%Mabk]
>]bmbhg%<L*.+'Ma^<hg\k^m^Lh\b^mrhg[^aZe_h_<hglmkn\m%+))-'

17 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L>G*,/0)3>q^\nmbhgh_\hg\k^m^lmkn\mnk^lIZkm*3
<hffhg';LB%bgik^iZkZmbhg%]n^+)*)'

18 <
 HGLMKN<M'GZmbhgZelmkn\mnkZe\hg\k^m^li^\b_b\Zmbhg_hk[nbe]bg`\hglmkn\mbhg%?hnkma
^]bmbhg%bgik^iZkZmbhg'
183

19 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L1///3+)).%L\a^]nebg`%]bf^glbhgbg`%[^g]bg`
Zg]\nmmbg`h_lm^^e_hkk^bg_hk\^f^gm3Li^\b_b\Zmbhg';LB%+)).'

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

20 M A>JN>>G LIKBGM>KH?:<MLH?I:KEB:F>GM%Ma^;nbe]bg`K^`neZmbhgl+)))'Ma^


LmZmbhg^krH__b\^Ebfbm^]%+)))'


21 M A>LM:MBHG>KRH??B<>EBFBM>=!MLH"%;nbe]bg`!:f^g]f^gm"!Gh+"K^`neZmbhgl+))+
Zg]ma^;nbe]bg`!:iikho^]Bgli^\mhkl^m\'"!:f^g]f^gm"K^`neZmbhgl+))+'MLH%+))+'

22 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG'==>GO*,/0)*3+)))3>q^\nmbhgh_\hg\k^m^
lmkn\mnk^l3<hffhg';LB%+)))'

23 <
 HHD%G'=^lb`g^kl`nb]^mh>G*22*-:\mbhglhglmkn\mnk^l'Pbg]Z\mbhgl'MahfZl
M^e_hk]%Ehg]hg%+))0'

24 =
 <E@'@nb]^mhma^nl^h_>G*22**-Pbg]Z\mbhgl'=<E@In[eb\Zmbhgl%+))/'
ppp'\hffngbmb^l'`ho'nd(ieZggbg`Zg][nbe]bg`(ieZggbg`[nbe]bg`(
[nbe]bg`k^`neZmbhglk^l^Zk\a([nbe]bg`]boblbhgk^l^Zk\a(

25 ;
 KBMBLALM:G=:K=LBGLMBMNMBHG';L>G*22**-3>nkh\h]^*':\mbhglhglmkn\mnk^l'
@^g^kZeZ\mbhgl'Pbg]Z\mbhgl';LB%+)).'
 25a GZmbhgZe:gg^qmh>nkh\h]^*IZkm*-';LB%+))1'




26 ;
 KHHD>K%H'<hg\k^m^[nbe]bg`ll\a^f^]^lb`gfZgnZe%!><+^]bmbhg"'<<BI&).*'Ma^
<hg\k^m^<^gmk^%+))2'

27 M A><HG<K>M>LH<B>MR'M^\agb\ZeK^ihkm/-%@nb]^mhma^]^lb`gZg]\hglmkn\mbhgh_K<
_eZmleZ[l%<<BI&)++'Ma^<hg\k^m^Lh\b^mr%+))0'

28 @
 HH=<ABE=%<AP>;LM>K%KF'K<lik^Z]la^^mlo,%<<BI&))1<='Nl^k`nb]^mhK<
lik^Z]la^^mlO,%<<BI&))1'Ma^<hg\k^m^<^gmk^%+))/'

29 BKPBG%:P'=^lb`gh_la^ZkpZee[nbe]bg`l%K^ihkmK*)+'<BKB:%*21-'

30 M A><HG<K>M><>GMK>'Phkd^]^qZfie^lmh>nkh\h]^+%Ohenf^+'<<BI&)-+'Bg
ik^iZkZmbhg'

31 F
 HL>E>R%;%;NG@>R%CANEL>%K'K^bg_hk\^]\hg\k^m^]^lb`gmh>nkh\h]^+%Lbqma
>]bmbhg'IZe`kZo^F\FbeeZg%+))0'

32 M A><HG<K>M>LH<B>MR'=^_e^\mbhglbg\hg\k^m^leZ[lZg][^Zfl'MK.1'Ma^<hg\k^m^
Lh\b^mr%+)).'

33 ;
 >>;R%:'Fh]b_b^]ikhihlZel_hk\hgmkheebg`]^_e^\mbhgl[rf^Zglh_kZmbhlh_liZgmh^__^\mbo^
]^ima%M^\agb\ZeK^ihkm-./%<^f^gmZg]<hg\k^m^:llh\bZmbhg%P^qaZfLikbg`l%*20*'

34 :EE>G%:A'K^bg_hk\^]\hg\k^m^]^lb`gmh;L1**)lbfier^qieZbg^]'Lihg%Ehg]hg%*211'

35 BGLMBMNMBHGH?LMKN<MNK:E>G@BG>>KL'FZgnZe_hkma^]^lb`gh_\hg\k^m^[nbe]bg`
lmkn\mnk^lmh>nkh\h]^+'BLmkn\m>%+))/'

Further reading

184

N

 >>;R:PG:K:R:G:GKL'=^lb`g^kl`nb]^mhma^>nkh\h]^l>G*22+**
;
Zg]>G*22+*+>nkh\h]^+3=^lb`gh_\hg\k^m^lmkn\mnk^l'@^g^kZekne^lZg]kne^l_hk
[nbe]bg`lZg]lmkn\mnkZe_bk^]^lb`g'MahfZlM^e_hk]%+)).'

N

 KBMBLALM:G=:K=LBGLMBMNMBHG'II*22)3+))0'Lmkn\mnkZe>nkh\h]^l%>qmkZ\ml_khf
;
ma^lmkn\mnkZe>nkh\h]^l_hklmn]^gmlh_lmkn\mnkZe]^lb`g%l^\hg]^]bmbhg';LB%Ehg]hg%
+))0'

N

 >G=R<KLFBMA=:'%=^lb`g^kl`nb]^mhma^>nkh\h]^l>G*22++>nkh\h]^+3
A
=^lb`gh_\hg\k^m^lmkn\mnk^l'IZkm+3<hg\k^m^[kb]`^l%MahfZlM^e_hk]%+))0'

N

M A><HG<K>M>LH<B>MR'M^\agb\ZeK^ihkm/-%@nb]^mhma^]^lb`gZg]\hglmkn\mbhgh_K<
_eZmleZ[l%<<BI&)++'Ma^<hg\k^m^Lh\b^mr%+))0'

:ii^g]bq:3=^kbo^]_hkfneZ^

Appendix A: Derived formulae


A1 Flexure: beams and slabs
Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

A1.1 Singly reinforced sections


Ma^k^\mZg`neZklmk^ll[eh\dlahpg[^ehpbg?b`nk^:*fZr[^nl^]'
d2
x

nfcd

ec
esc

As2

lx

neutral axis

h d

Fc

Fsc
z

As

Fst

es
a) Section

b) Strain

Fig. 3.5

c) Forces

Figure A1
Strains and forces in a section

?hk`kZ]^lh_\hg\k^m^nimh<.)(/)%e\n6)')),.%n6*Zg]l6)'1
_\]6a\\ _\d (g<6)'1._\d (*'.
_r]6_rd (gL6_rd (*'*.6)'10_rd

3.1.6(1), 2.4.2.4(1)
& NA
2.4.2.4(1) & NA

?hklbg`erk^bg_hk\^]l^\mbhgl%ma^]^lb`g^jnZmbhgl\Zg[^]^kbo^]Zl_heehpl3
Lever arm, z
0.8x

Fc

z = d 0.4x
Fst

Figure A2
Beam lever arm

?\6!)'1._\d (*'."[!)'1q"6)'-.,_\d[q
?lm6)'10:l _rd
<hglb]^kfhf^gm%F%Z[hnmma^\^gmk^h_ma^m^glbhg_hk\^3
F6)'-.,_\d[qs
Ghp s6 ])'-q
=

q6 +'.!]s"

F

 6 )'-.,_\d[+'.!]s"s

 6 *'*,,,!_\d[s]_\d[s+"

E^mD  6 F([] +_\d




 6 *'*,,,!_\d[s]_\d[s+"([]+_\d

 6 *'*,,,!s]s+"(] +

=)  6 *'*,,,T!s(]"+!s(]"V$D


 6 !s(]"+!s(]"$)'11+,.D

BgikZ\mb\^ma^]^lb`gfhf^gm%F

>]phne][^nl^]'

185

Lheobg`ma^jnZ]kZmb\^jnZmbhg3
s(]6T*$!*,'.+2D")'.V(+
s6]T*$T*,'.+2D")'.V(+

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Table C5

Bmbl\hglb]^k^]`hh]ikZ\mb\^bgma^NDmhebfbms(]mhZfZqbfnfh_)'2.]'!Mabl`nZk]lZ`Zbglm
k^erbg` hg o^kr mabg l^\mbhgl h_ \hg\k^m^ pab\a Zm ma^ ^qmk^f^ mhi h_ Z l^\mbhg fZr [^ h_
jn^lmbhgZ[e^lmk^g`ma'"MZ[e^l`bobg`oZen^lh_s(]Zg]q(]_hkoZen^lh_DfZr[^nl^]'
Area of reinforcement, As
MZdbg`fhf^gmlZ[hnmma^\^gmk^h_ma^\hfik^llbhg_hk\^3
F6)'10:l _rds
:l6F(!)'10_rd s"
Limiting value of relative exural compressive stress, K'
:llnfbg` gh k^]blmkb[nmbhg mZd^l ieZ\^% Z ebfbmbg` oZen^ !hg ma^ lmk^g`ma h_ \hg\k^m^ bg
\hfik^llbhg"_hkD\Zg[^\Ze\neZm^]!]^ghm^]D "Zl_heehpl'

Table 3.1

e\n, 6 \hg\k^m^lmkZbg6)')),.
6 k^bg_hk\^f^gmlmkZbg
el

6 .))(!*'*.+))*),"6)'))++
?khflmkZbg]bZ`kZf%?b`nk^:*
q
6 )')),.](!)')),.$)'))++"

6 )'/]
?khf^jnZmbhglZ[ho^3
F
6 )'-.,_\d[qs
F  6 )'-.,_\d[)'/]!])'-)'/]"

6 )'+)0_\d[]+
=D 6)'+)0
Bm bl h_m^g \hglb]^k^] `hh] ikZ\mb\^ mh ebfbm ma^ ]^ima h_ ma^ g^nmkZe Zqbl mh Zohb] ho^k&
k^bg_hk\^f^gm!b'^'mh^glnk^maZmma^k^bg_hk\^f^gmblrb^e]bg`Zm_Zbenk^%manlZohb]bg`[kbmme^
_Zbenk^h_ma^\hg\k^m^"'H_m^gq(]blebfbm^]mh)'-.'Mablblk^_^kk^]mhZlma^[ZeZg\^]l^\mbhg
[^\Znl^Zmma^nembfZm^ebfbmlmZm^ma^\hg\k^m^Zg]lm^^ek^Z\ama^bknembfZm^lmkZbglZmma^
lZf^mbf^T,*V'MablblghmZ>nkh\h]^+k^jnbk^f^gmZg]blghmZ\\^im^][rZee^g`bg^^kl'
Ghg^ma^e^ll_hkq6)'-.]
?khf^jnZmbhglZ[ho^3
F
6 )'-.,_\d[qs
F  6 )'-.,_\d[)'-.]!])'-)'-.]"

6 )'*/0_\d[]+
=D  6 )'*/0

Cl. 5.5(4)

q(]blZelhk^lmkb\m^][rma^Zfhngmh_k^]blmkb[nmbhg\Zkkb^]hnm'?hk_\d.)FIZ
d)'-$!)'/$)'))*-e\n"qn(]
pa^k^

] 6 k^]blmkb[nm^]fhf^gm(^eZlmb\[^g]bg`fhf^gm[^_hk^k^]blmkb[nmbhg

qn 6 ]^imah_ma^g^nmkZeZqblZmNELZ_m^kk^]blmkb[nmbhg
e\n 6 \hfik^llbo^lmkZbgbgma^\hg\k^m^ZmNEL
Mabl`bo^lma^oZen^lbgMZ[e^:*'


186

:ii^g]bq:3=^kbo^]_hkfneZ^

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Table A1
Limits on D with respect to redistribution ratio, d
d

0.95

0.9

0.85

0.8

0.75

0.7

% redistribution

)

.

*)

*.

+)

+.

,)

K'

)'+)1

)'*2.

)'*1+

)'*/1

)'*.,

)'*,0

)'*+)

B_D7D ma^l^\mbhglahne][^k^lbs^]hk\hfik^llbhgk^bg_hk\^f^gmblk^jnbk^]'Bgebg^pbma
\hglb]^kZmbhg h_ `hh] ikZ\mb\^ hnmebg^] Z[ho^% this publication adopts a maximum value
of K'= 0.167'

A1.2 Compression reinforcement, As2


Ma^fZchkbmrh_[^Zflnl^]bgikZ\mb\^Zk^lbg`erk^bg_hk\^]%Zg]ma^l^[^Zfl\Zg[^]^lb`g^]nlbg`
ma^_hkfneZ]^kbo^]Z[ho^'Bglhf^\Zl^l%\hfik^llbhgk^bg_hk\^f^gmblZ]]^]bghk]^kmh3
N Bg\k^Zl^l^\mbhglmk^g`mapa^k^l^\mbhg]bf^glbhglZk^k^lmkb\m^]%b'^'pa^k^D7D
N Mhk^]n\^ehg`m^kf]^_e^\mbhg
N Mh]^\k^Zl^\nkoZmnk^(]^_hkfZmbhgZmnembfZm^ebfbmlmZm^

As2

As
Figure A3
Beam with compression reinforcement

Pbmak^_^k^g\^mh?b`nk^:*%ma^k^blghpZg^qmkZ_hk\^
?l\6)'10:l+ _rd
Ma^Zk^Zh_m^glbhgk^bg_hk\^f^gm\Zgghp[^\hglb]^k^]bgmphiZkml%ma^_bklmiZkmmh[ZeZg\^
ma^\hfik^llbo^_hk\^bgma^\hg\k^m^%ma^l^\hg]iZkmmh[ZeZg\^ma^_hk\^bgma^\hfik^llbhg
lm^^e'Ma^Zk^Zh_m^glbhgk^bg_hk\^f^gmk^jnbk^]blma^k^_hk^3
:l6D _\n[] +(!)'10_rds"$:l+
pa^k^

sbl\Ze\neZm^]nlbg`D'bglm^Z]h_D

:l+\Zg[^\Ze\neZm^][rmZdbg`fhf^gmlZ[hnmma^\^gmk^h_ma^m^glbhg_hk\^3

F6F $)'10_rd:l+!]]+"

F6D _\n[] +$)'10_rd:l+!]]+"
K^ZkkZg`bg`3
:l+6!DD " _\d[] +(T)'10_rd!]]+"V

A2 Shear
A2.1 Shear resistance (without shear reinforcement), VRd,c
OK]%\6T<K]%\d!*))r*_\d "*(,$d*s\iV[p]!ofbg$d*s\i "[p]

Exp. (6.2)

pa^k^

<K]%\ 6 )'*1(g<6)'*1(*'.6)'*+

NA

d

6 *$!+))(]")'.+')

187

r* 6 :l (![p]")')+


d*

6 )'*.

s\i 6 )_hkghg&ik^lmk^ll^]\hg\k^m^


ofbg 6 )'),.d*'._\d)'.

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

=OK]%\6)'*+d!*))r*_\d"*(,[p])'),.d*'._\d)'.[p]

A2.2 Shear capacity


Ma^\ZiZ\bmrh_Z\hg\k^m^l^\mbhgpbmao^kmb\Zela^Zkk^bg_hk\^f^gmmhZ\m
ZlZlmknm%OK]%fZq3
Exp. (6.9)

Cl. 6.2.3(3) Note 1,


Exp. (6.6N) & NA

OK]%fZq6a\p[pSv* _\] (!\hmy$mZgy"


pa^k^
a\p 6 *')
v*  6 v6)'/T*_\d (+.)V

_\] 6 a\\ _\d (g<6*'))_\d (*'.
=OK]%fZq6)'-)[ps_\dT*_\d (+.)V(!\hmy$mZgy"
K^ZkkZg`bg`mabl^jnZmbhg`bo^l3
y6)'.lbg*To>]s (!)'+)_\dT*_\d (+.)V"V\hm*+'.
pa^k^

o>]s6O>] ([s6O>] (![)'2]"
Bgfhlm\Zl^l%pa^k^\hmy6+'.%y6+*'1
oK]%fZq%\hmy6+'.6)'*,1[ps_\dT*_\d (+.)V
hk
oK]%fZq%\hmy6+'.6)'*,1_\dT*_\d (+.)V
pa^k^

oK]%fZq%\hmy6+'. 6OK]%fZq%\hmy6+'.(![s"


6OK]%fZq%\hmy6+'.(!)'2[]"
Pa^k^\hmy7+'.%ma^Zg`e^h_ma^lmknmZg]oK]%fZqlahne][^\Ze\neZm^]%hkoK]%fZqfZr[^
ehhd^]nibgmZ[e^lhk\aZkml!^'`'MZ[e^<0hk?b`nk^<*"'

A2.3 Shear reinforcement


Exp. (6.13)

OK]%l6!:lp(l"s_rp]!\hmy$\hma"lbgaO>]
pa^k^

:lp 6

l 6

s 6

_rp] 6
a 6




\khll&l^\mbhgZeZk^Zh_ma^la^Zkk^bg_hk\^f^gm
liZ\bg`
e^o^kZkf!ZiikhqbfZm^oZen^h_)'2]fZrghkfZeer[^nl^]"
_rpd (gL6]^lb`grb^e]lmk^g`mah_ma^la^Zkk^bg_hk\^f^gm
Zg`e^h_ma^ebgdlmhma^ehg`bmn]bgZeZqbl'?hko^kmb\Zeebgdl%
\hma6)Zg]lbga6*')

K^ZkkZg`bg`_hko^kmb\Zeebgdl3
:lp(lO>] (s_rp]\hmy
hk
:lp(lo>]%s[p(_rp]\hmy

Exp. (9.5N) & NA

FbgbfnfZk^Zh_la^Zkk^bg_hk\^f^gm
:lp%fbg (!l[plbga")')1_\d)'.(_rd
pa^k^

l 6 ehg`bmn]bgZeliZ\bg`h_ma^la^Zkk^bg_hk\^f^gm

[p 6 [k^Z]mah_ma^p^[

188

:ii^g]bq:3=^kbo^]_hkfneZ^
a 6 Zg`e^h_ma^la^Zkk^bg_hk\^f^gmmhma^ehg`bmn]bgZeZqblh_ma^f^f[^k'?hko^kmb\Ze
ebgdllbga6*')'
K^ZkkZg`bg`_hko^kmb\Zeebgdl3

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Alp%fbg (l)')1[plbga_\d)'.(_rd

A3 Columns

el\

_\]6a\\n_\d(g<
sl\ ]
+
:

e\n+

l+

]\

q
a

g'Zqbl
er

:l*

slm

e\
a) Strain diagram

Fig. 6.1

]+

b) Stress diagram

Figure A4
Section in axial
compression and
bending

?hkZqbZeehZ]
G>]6_\] []\$:l+sl\:l*slm
;nmZl:l+6:l*6:lG(+
G>]6_\] []\$:lG!sl\slm"(+
G>]_\] []\6:lG!sl\slm"(+
!G>]_\] []\"(!sl\slm"6:lG(+
:lG(+6!G>]_\] []\"(!sl\slm"
=:lG(+6!G>]a\\n_\d[]\ (g<"(!sl\slm"
?hkfhf^gmZ[hnm\^gmk^h_\henfg
F>]6_\] []\!a(+]\ (+"$:l+sl\!a(+]+"$:l*slm!a(+]+"
;nmZl:l+6:l*6:lF(+
F>]6_\] []\!a(+]\ (+"$:lF!sl\$slm"!a(+]+"(+
F>]_\] []\!a(+]\ (+"6:lF!sl\$slm"!a(+]+"(+
TF>]_\] []\!a(+]\ (+"V(!sl\$slm"!a(+]+"6:lF(+
=:lF(+6TF>]a\\n_\d []\!a(+]\ (+"(g<V(T!sl\$slm"!a(+]+"V
Lhenmbhg
Bm^kZm^qln\amaZm:lG6:lF
Note

?hkl^\mbhglpaheerbg\hfik^llbhg%ma^lmkZbgblebfbm^]ln\amaZmZo^kZ`^lmkZbg
e\l6)'))*0.!Zllnfbg`[bebg^Zklmk^lllmkZbgk^eZmbhglabi"'

Cl. 6.1(6), Fig. 6.1,


Table 3.1

189

Appendix B: Serviceability limit state


B1 Deflection
Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

BgfZgr\Zl^l%iZkmb\neZkerpbmaleZ[l%]^_e^\mbhgbl\kbmb\Zemh]^lb`g'
>nkh\h]^+%<e'0'-Zeehpl_hk]^_e^\mbhgmh[^\hgmkhee^][rnlbg`liZg3]^imakZmbh!E(]"\a^\dl
bgZ\\hk]Zg\^pbma<e'0'-'+hk[r\Ze\neZmbhgbgZ\\hk]Zg\^pbma<e'0'-','BmblbfihkmZgmmh
]b__^k^gmbZm^[^mp^^gma^oZkbhnlf^mah]lnl^]bg\a^\dbg`]^_hkfZmbhgZlma^rpbee^Z\a`bo^
]b__^k^gmZglp^kl'Mak^^ihineZkf^mah]lZk^]bl\nll^][^ehp'HgermaZm]^l\kb[^]bgL^\mbhg
;*'*[^ehpbllnbmZ[e^_hkaZg]\Ze\neZmbhg'

B1.1 TCC method[5,19]


Ma^bg&l^kob\^lmk^llh_k^bg_hk\^f^gm%sl%blnl^]mh]^m^kfbg^Z_Z\mhk%,*)(sl %pab\ablnl^]
mhfh]b_rma^[Zlb\liZg 3 ^__^\mbo^]^imakZmbhZlZeehp^]bg<e'0'-'+!+"h_>nkh\h]^+T+VZg]
fh]^kZm^][rma^GZmbhgZe:gg^qT+ZV'Mablf^mah]%ab`aeb`am^]Zl_Z\mhk?,bg<hg\bl^>nkh\h]^
+T.V% bl bgm^g]^] mh [^ nl^] bg aZg] \Ze\neZmbhgl mh ]^kbo^ !\hgl^koZmbo^" oZen^l h_ sl _khf
ZoZbeZ[e^NELfhf^gml'BgZ\\hk]Zg\^pbmaGhm^.h_MZ[e^G:'.h_ma^NDG:T+ZV%ma^kZmbh_hk
:l%ikho (:l%k^jblk^lmkb\m^]mh*'.3bg^__^\mmablebfbmlma^_Z\mhk,*)(slmh*'.'
pa^k^
sl6!_rd (gL"!pji (pnem"!:l%k^j (:l%ikho"(d,*)(*'.







pa^k^
_rd 6 \aZkZ\m^kblmb\lmk^g`mah_k^bg_hk\^f^gm6.))FIZ
gL 6 iZkmbZe_Z\mhk_hkk^bg_hk\^f^gm6*'*.
pji 6 jnZlb&i^kfZg^gmehZ]!N=EZllnf^]"
pi^kf6 nembfZm^ehZ]!N=EZllnf^]"
:l%k^j 6 Zk^Zh_k^bg_hk\^f^gmk^jnbk^]
:l%ikho6 Zk^Zh_k^bg_hk\^f^gmikhob]^]
d

6 k^]blmkb[nmbhgkZmbh

B1.2 RC Spreadsheets method[28]


Ma^K<lik^Z]la^^mlM<<qq'qelT+1Vnl^ma^liZg3]^imaf^mah]h_\a^\dbg`]^_hkfZmbhg[nmnl^
ZgZ\\nkZm^f^mah]_hk]^m^kfbgbg`sl!l^^;,'+[^ehp"%pab\aZ`Zbgblnl^]mh]^m^kfbg^ma^
fh]^kZmbg`_Z\mhk6,*)(sl':`Zbg%bgZ\\hk]Zg\^pbmaGhm^.h_MZ[e^G:'.h_ma^NDG:T+ZV%
ma^kZmbh_hk:l%ikho(:l%k^jblk^lmkb\m^]mh*'.3bg^__^\mmablebfbmlma^_Z\mhk,*)(slmh*'.'
L^iZkZm^ZgZerl^lnlbg`jnZlb&i^kfZg^gmehZ]lg^^]mh[^\Zkkb^]hnm'?hk^Z\aliZg%ZgLEL
g^nmkZe Zqbl ]^ima bl ]^m^kfbg^]% ma^g s\ Zg] sl Zk^ ]^kbo^] _hk ma^ jnZlb&i^kfZg^gm ehZ]
\hg]bmbhgl'Ma^ _Z\mhk sl bl nl^] bg Z\\hk]Zg\^ pbma >nkh\h]^ +T+V Zg] ma^ \nkk^gm GZmbhgZe
:gg^qT+ZV%mhfh]b_rma^[Zlb\liZg 3 ^__^\mbo^]^imakZmbh'
Pabelm mabl f^mah] `bo^l Z fhk^ Z\\nkZm^ Zg] e^ll \hgl^koZmbo^ Zll^llf^gm h_ sl% bm bl hger
lnbmZ[e^_hk\hfinm^klik^Z]la^^mZiieb\Zmbhgl'L^^Zelh:ii^g]bq;.'
Bgma^ZgZerlblh_leZ[lZg][^Zfl%lniihkmlZk^nlnZeerZllnf^]mh[^ibgg^]'Bgk^Zebmrlniihkml
aZo^ lhf^ \hgmbgnbmr% ^li^\bZeer Zm ^g] lniihkml' NlnZeer% ghfbgZe mhi lm^^e bl Zllnf^] Zg]
ikhob]^]bgma^mhih_liZglZg]blnl^]bgma^]^m^kfbgZmbhgh_l^\mbhgikhi^kmb^l'

B1.3 Rigorous analysis


Kb`hkhnlZgZerlbl%ln\aZlmaZmnl^]bgma^l^kb^lh_K<Lik^Z]la^^mlM<<qqK'qelfZr[^nl^]mh
Zll^ll]^_hkfZmbhgbgZ\\hk]Zg\^pbma>nkh\h]^+%<e'0'-','
L^^:ii^g]bq;*'.

190

:ii^g]bq;3L^kob\^Z[bebmrebfbmlmZm^

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Bg ma^ lik^Z]la^^ml% l^\mbhgl Zm *(+)ma ihbgml Zehg` ma^ e^g`ma h_ Z liZg Zk^ \a^\d^] mh
]^m^kfbg^pa^ma^kma^_e^qnkZem^glbe^lmk^llbgma^l^\mbhgblebd^ermh^q\^^]ma^m^glbe^lmk^g`ma
h_ma^\hg\k^m^]nkbg`^bma^k\hglmkn\mbhghkl^kob\^eb_^3l^iZkZm^ZgZerl^lZk^ng]^kmZd^gnlbg`
_k^jn^gmehZ]l%jnZlb&i^kfZg^gmZg]m^fihkZkrehZ]l'B_ma^_e^qnkZem^glbe^lmk^g`mabl^q\^^]^]
ng]^k_k^jn^gmehZ]l%ma^gma^l^\mbhgblZllnf^]mh[^\kZ\d^]Zg]k^fZbg\kZ\d^]3\kZ\d^]
l^\mbhg ikhi^kmb^l Zk^ nl^] mh ]^m^kfbg^ ma^ kZ]bnl h_ \nkoZmnk^ _hk maZm *(+)ma h_ liZg' B_
_e^qnkZem^glbe^lmk^g`mablghm^q\^^]^]%ng&\kZ\d^]l^\mbhgikhi^kmb^lZk^nl^]'
KZ]bbh_\nkoZmnk^Zk^\Ze\neZm^]_hk^Z\a*(+)maliZgbg\k^f^gmh_ma^^e^f^gmnlbg`ma^k^e^oZgm
ikhi^kmb^lZg]fhf^gml]^kbo^]_khfZgZerlblh_jnZlb&i^kfZg^gmZ\mbhgl'=^_hkfZmbhgbl\Ze\neZm^]
_khfma^bg\k^f^gml\nkoZmnk^lobZgnf^kb\Zebgm^`kZmbhgho^kma^e^g`mah_^Z\aliZg'
Ma^f^mah]blbgZ\\hk]Zg\^pbmaMa^<hg\k^m^Lh\b^mrlin[eb\ZmbhgMK.1T,+V':`Zbgma^f^mah]
bllnbmZ[e^hger_hk\hfinm^kZiieb\ZmbhglZg]ghm_hkaZg]\Ze\neZmbhg'

B1.4 Differing results


=nkbg`+))1%bm[^\Zf^bg\k^Zlbg`erZiiZk^gmmaZmma^k^Zk^bg\hglblm^g\b^l[^mp^^gma^k^lneml
`bo^g [r ma^ kb`hkhnl \Ze\neZmbhg f^mah] Zg] liZg3]^ima f^mah]l ]^l\kb[^] bg >nkh\h]^ +'
Nlbg` ma^ kb`hkhnl f^mah] `bo^l ]^_e^\mbhgl maZm Zk^ `k^Zm^k maZg phne] [^ ^qi^\m^] _khf
ma^ZllnfimbhgllmZm^]_hkE(]f^mah]lb'^']^_e^\mbhgebfbmlh_E(+.)ho^kZee!l^^<e'0'-'*!-""
hkE(.))Z_m^k\hglmkn\mbhg!l^^<e'0'-'*!.""'Bmbllnli^\m^]maZmmabl]bliZkbmrblma^lZf^Zl
maZm ^qi^kb^g\^] [^mp^^g liZg3]^ima Zg] \Ze\neZmbhg f^mah]l bg ;L 1**)3 Z ]bliZkbmr maZm
pZlk^\h`gbl^]Zlehg`Z`hZl*20*T,,V'Ma^kb`hkhnlf^mah]]^l\kb[^]Z[ho^k^eb^lhgfZgr
Zllnfimbhgl Zg] bl eZk`^er ng\Zeb[kZm^] Z`Zbglm k^Ze lmkn\mnk^l':l ghm^] bgMK.1% ma^k^ bl Zg
nk`^gmg^^]_hk]ZmZ_khfZ\mnZelmkn\mnk^llhmaZmf^mah]lfZr[^\Zeb[kZm^]'Bmlahne][^
ghm^]maZmma^kb`hkhnlZgZerlblf^mah]h[l^koZmbhglp^k^fZ]^nlbg`_k^jn^gmehZ]lpa^k^%bg
Z\\hk]Zg\^pbma>nkh\h]^+%jnZlb&i^kfZg^gmehZ]lZk^\Zee^]_hk'
>g]liZglZk^nlnZeer\kbmb\Ze'Pbmak^li^\mmhma^kb`hkhnlZgZerlblf^mah]%bmaZl[^^gln``^lm^]maZm
_hk^g]&liZgl%ma^M<<Zg]K<&lik^Z]la^^mf^mah]lk^lnembg]^_e^\mbhgl\ehl^mhma^ebfbmllmZm^]
bg>nkh\h]^+%ikhob]^]maZmZghfbgZe^g]&lniihkmk^lmkZbgbg`fhf^gmblik^l^gmpa^k^ghg^bl
Zllnf^]bgZgZerlbl'<Znmbhgblma^k^_hk^g^\^llZkrbgmkn^ibgg^]^g]&lniihkmlbmnZmbhgl[nmpa^k^
lhf^ \hgmbgnbmr ^qblml% mabl ]bliZkbmr fZr [^ Z]]k^ll^] [r ^glnkbg` maZm ZiikhikbZm^ Zfhngml h_
k^bg_hk\^f^gm%bgZ\\hk]Zg\^pbmama^<h]^Zg]GZmbhgZe:gg^q%Zk^ikhob]^]Zm^g]lniihkml'
Ma^G=I_hk<e'2'+'*'+!*"bgma^NDG:T+ZVmh;L>G*22+*+lmbineZm^lmaZm+.h_^g]liZg
fhf^gmlahne][^nl^]mh]^m^kfbg^^g]lniihkmk^bg_hk\^f^gm'MablblnlnZeerZ\\hffh]Zm^]
[rikhob]bg`+.h_^g]liZg[hmmhflm^^eZlmhilm^^eZm^g]lniihkml'Bmblhgmabl[ZlblmaZm
ma^\Ze\neZmbhglbgmablin[eb\ZmbhgZk^\hglb]^k^]Zl[^bg`_nkma^kln[lmZgmbZm^]'

B1.5 Note regarding factor 310/ss (factor F3)


:mma^mbf^h_in[eb\Zmbhg!=^\^f[^k+))2"ma^Znmahklp^k^ZpZk^h_Zikh[Z[e^\aZg`^mh
NDG:T+ZVMZ[e^G:'.pab\a%bg^__^\m%phne]f^ZgmaZmma^_Z\mhk,*)(sl!?,"6:l%ikho(:l%k^j
 *'.% manl ]blZeehpbg` ma^ Z\\nkZm^ f^mah] hnmebg^] bg L^\mbhgl ,'*% ,'+% ,',% ,'-% -', Zg]
:ii^g]b\^l;*'*%;*'+Zg]<0'

B2 Neutral axis at SLS


Mh_bg]q%g^nmkZeZqbl%Zg]l^kob\^llmk^ll^ls\Zg]sl_hkZ\hg\k^m^l^\mbhg%ZmLEL%\hglb]^kma^
\kZ\d^]l^\mbhgbg?b`nk^;*

191

Relative modulus
E/Ec
ae 1

As2

d2
x

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

ae

As

Where ae = modular ratio Es/Ec

Figure B1
Cracked concrete section at SLS

?khf_bklmikbg\bie^l%_hkZ_neer\kZ\d^]mkZgl_hkf^]l^\mbhg%
MhmZeZk^Zh_l^\mbhg%:6[q$:la^$:l+!a^*"
*lmfhf^gmh_Zk^Z%:r6[q+(+$:l]a^$:l+]+!a^*"
?hkZleZ[%[6*)))%ma^k^_hk^
: 6*)))q$:la^$:l+!a^*"
:r6.))q+$:l]a^$:l+]+!a^*"
G^nmkZeZqbl]^ima%q
q 6 :r (:
 6 T.))q+$:l]a^$:l+]+!a^*"V(T*)))q$:la^$:l+!a^*"V
Ma^k^_hk^
qT*)))q$:la^$:l+!a^*"V6T.))q+$:l]a^$:l+]+!a^*"V
)

6T.))q+$:l]a^$:l+]+!a^*"VqT*)))q$:la^$:l+!a^*"V

6.))q+qT*)))qV$:l]a^$:l+]+!a^*"VqT:la^$:l+!a^*"V

6.))q+qT:la^$:l+!a^*"V$T:l]a^$:l+]+!a^*"V

Lheobg`ma^jnZ]kZmb\
q6[[+-a\")'.V(+Z
q 6


T:la^$:l+!a^*"tT:la^$:l+!a^*"V+$-.))T:l]a^$:l+]+!a^*"Vv)'.V
!+q.))"

hkmkZglihlbg`%
T!a^*":l+a^:l$tT!a^*":l+$a^:lV+$+)))T!a^*":l+]+$a^:l]Vv)'.V

q6


*)))

hk
q6


T!a^*":l+a^:l$tT!a^*":l+$a^:lV+$+[T!a^*":l+]+$a^:l]Vv)'.V
[

Mabl^qik^llbhgblnl^]bgma^K<lik^Z]la^^mlT+1V'

192

:ii^g]bq;3L^kob\^Z[bebmrebfbmlmZm^
B3 SLS stresses in concrete, sc, and reinforcement, ss
B3.1 Singly reinforced section
<hglb]^kma^lbg`erk^bg_hk\^]l^\mbhgbg?b`nk^;+'

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

b
Fc

x/3
x

Mqp

z
As

Fs

a) Section

b) Dimensions and forces

Figure B2
SLS stresses: singly
reinforced section

<hglb]^kfhf^gmlZ[hnm?\3
Fji 6?l s6?l!]q(,"
?l 6Fji (!]q(,"
sl 6Fji (T:l!]q(,"V
sl :l6Fji (!]q(,"6q[s\ (+
s\ 6+sl :l (q[

B3.2 Doubly reinforced section


<hglb]^kma^lbg`erk^bg_hk\^]l^\mbhgbg?b`nk^;,'

E/Ec = ae 1
s = sc(ae 1)(x d2)/x

E/Ec = ae
s = sc
d2

b
As2

x
Mqp

As

a) Section

E/Ec = ae
s = ss
b) Dimensions, modular
ratios and stresses

Figure B3
SLS stresses

<hglb]^kfhf^gm%Fji%Z[hnm[hmmhfk^bg_hk\^f^gm%:lT,-V'
Fji6 :l+!]]+"!a^*"t!q]+"(qvs\$s\[!q(+"!]q(,"
Ma^k^_hk^
s\ 6 Fji(T:l+!]]+"!a^*""t!q]+"(qv$[!q(+"!]q(,"V
:g]_khflmk^ll]bZ`kZf
sl 6 s\a^!]q"(q
193

Appendix C: Design aids

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Ma^ _heehpbg` mZ[e^l% m^qm Zg] _b`nk^l aZo^ [^^g ]^kbo^] _khf >nkh\h]^ + Zg] Zk^ ikhob]^]
Zl]^lb`gZb]l_hk]^lb`g^klbgma^ND'Ma^l^]^lb`gZb]laZo^[^^gk^_^k^g\^]bgma^m^qmZg]
`^g^kZeeraZo^[^^gmZd^g_khfL^\mbhg*.h_<hg\bl^>nkh\h]^+T.V'

C1 Design values of actions


?hkma^NELh_lmk^g`ma!LMK"pa^k^ma^k^blZlbg`e^oZkbZ[e^Z\mbhgnl^^bma^k3
>qi'!/'*)"_khf;L>G*22)T*)V
 hkma^phkl^\Zl^h_

N *',.@d$*'.Jd

N *',.@d$c)*'.Jd >qi'!/'*)Z"

 Zg]
N *'+.@d$*'.Jd

>qi'!/'*)["
pa^k^c)6*')_hklmhkZ`^%)'._hklghp[nmhma^kpbl^)'0%l^^MZ[e^+'+'

Bg fhlm \Zl^l >qi' !/'*)[" pbee [^ ZiikhikbZm^% ^q\^im _hk lmhkZ`^ pa^k^ ma^ nl^ h_ >qi' !/'*)Z"
blebd^ermh[^fhk^hg^khnl'
?hkma^LELh_]^_hkfZmbhg%jnZlb&i^kfZg^gmehZ]llahne][^Ziieb^]'Ma^l^Zk^*')@d$c+Jd
pa^k^c+bl]^i^g]^gmhgnl^%^'`')',_hkh__b\^lZg]k^lb]^gmbZeZg])'0_hklmhkZ`^'

C2 Values of actions
Ma^oZen^lh_Z\mbhgl!b'^'ehZ]l"Zk^]^_bg^]bg>nkh\h]^*T**V'Ma^iZkmlh_>nkh\h]^*Zk^`bo^g
bgMZ[e^<*'Ma^l^oZen^lZk^mZd^gZl\aZkZ\m^kblmb\oZen^l':mma^mbf^h_in[eb\Zmbhg%ma^ND
GZmbhgZe:gg^q^lmhma^l^iZkmlZk^bgoZkbhnllmZm^lh_k^Z]bg^ll'
:lI=//10T/VfZd^l\e^Zk%ngmbema^ZiikhikbZm^>nkhi^ZglmZg]Zk]l[^\hf^ZoZbeZ[e^%]^lb`g^kl
fZr\hglb]^knlbg`\nkk^gmikZ\mb\^hk\nkk^gm;kbmblaLmZg]Zk]lbg\hgcng\mbhgpbma>nkh\h]^+%
ikhob]^]ma^rZk^\hfiZmb[e^pbma>nkh\h]^+Zg]maZmma^k^lnembg`k^ebZ[bebmrblZ\\^imZ[e^'
;L>G*22***lmZm^lmaZmma^]^glbmrh_\hg\k^m^bl+-dG(f,%k^bg_hk\^]\hg\k^m^%+.dG(f,
Zg]p^mk^bg_hk\^]\hg\k^m^%+/dG(f,'
Table C1
The parts of Eurocode 1[11]

194

Reference

Title

BS EN 1991-1-1

=^glbmb^l%l^e_&p^b`amZg]bfihl^]ehZ]l

BS EN 1991-1-2

:\mbhglhglmkn\mnk^l^qihl^]mh_bk^

BS EN 1991-1-3

LghpehZ]l

BS EN 1991-1-4

Pbg]Z\mbhgl

BS EN 1991-1-5

Ma^kfZeZ\mbhgl

BS EN 1991-1-6

:\mbhgl]nkbg`^q^\nmbhg

BS EN 1991-1-7

:\\b]^gmZeZ\mbhgl]n^mhbfiZ\mZg]^qiehlbhgl

BS EN 1991-2

MkZ__b\ehZ]lhg[kb]`^l

BS EN 1991-3

:\mbhglbg]n\^][r\kZg^lZg]fZ\abg^kr

BS EN 1991-4

:\mbhglbglbehlZg]mZgdl

:ii^g]bq<3=^lb`gZb]l
C3 Analysis

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

:gZerlbl bl ]^Zem pbma bg L^\mbhg . h_ <hg\bl^>nkh\h]^+'Pa^k^ ZiikhikbZm^ ma^ \h^__b\b^gml
`bo^gbgMZ[e^l<+Zg]<,\Zg[^nl^]mh]^m^kfbg^]^lb`gfhf^gmlZg]la^Zk_hkleZ[lZg]
[^ZflZmNEL'
Table C2
Coefficients for use with one-way spanning slabs to Eurocode 2
Coefficient Location
End support/slab connection

Internal supports and spans

Pinned end support

Continuous

Outer
support

Near
middle of
end span

Outer
support

Near
middle of
end span

Moment

)')

)')1/

)')-

Shear

)'-)

)'-/

At 1st
interior
support

At
middle of
interior
spans

At
interior
supports

)')0.

)')1/

)')/,

)')/,

)'/)3)'/)

)'.)3)'.)

Notes
1:iieb\Z[e^mhhg^&pZrliZggbg`leZ[lpa^k^ma^Zk^Zh_^Z\a[Zr^q\^^]l,)f+%Jd*'+.@dZg]jd.
dG(f+%ln[lmZgmbZeerngb_hkfehZ]bg`!Zme^Zlm,liZgl%fbgbfnfliZg)'1.fZqbfnf!]^lb`g"liZg'
2=^lb`gfhf^gm6\h^__qgqliZg+Zg]]^lb`gla^Zk6\h^__qgqliZgpa^k^gblZN=EpbmaZlbg`e^oZkbZ[e^
Z\mbhg6g@ `d$cgJjdpa^k^`dZg]jdZk^\aZkZ\m^kblmb\i^kfZg^gmZg]oZkbZ[e^Z\mbhglbgdG(f'
3;Zlbl3Rb^e]ebg^]^lb`g!Zllnf^]+)k^]blmkb[nmbhgT0V"

Table C3
Coefficients for use with beams (and one-way spanning slabs) to Eurocode 2
Coefficient

Location
Outer support Near middle
of end span

At 1st interior At middle of


At interior
support
interior spans supports

Moment `k
and jk

+.liZga

)')2-

)')0.

Moment `k

)')2)

)')//

Moment jk

)'*))

)')1/

Shear

)'-.

)'/,3)'..

)'.)3)'.)b

Notes
1?hk[^ZflZg]leZ[l%,hkfhk^liZgl'!Ma^rfZrZelh[^nl^]_hk+&liZg[^Zfl[nmlniihkm
fhf^gm\h^__b\b^gm6)'*)/Zg]bgm^kgZela^Zk\h^__b\b^gm6)'/,[hmalb]^l"'
2@^g^kZeerJd@d%Zg]ma^ehZ]bg`lahne][^ln[lmZgmbZeerngb_hkfer]blmkb[nm^]'Hma^kpbl^li^\bZe
\nkmZbef^gmh_k^bg_hk\^f^gmblk^jnbk^]'
3FbgbfnfliZg)'1.qfZqbfnf!Zg]]^lb`g"liZg'
4=^lb`gfhf^gmZmlniihkml 6 \h^__qgqliZg+
 hkbgliZgl
6 !\h^__`dqg@`d$\h^__jdqcgJjd"qliZg+'
5=^lb`gla^ZkZm\^gmk^ebg^h_lniihkml6\h^__qgqliZgpa^k^gblZN=EpbmaZlbg`e^oZkbZ[e^Z\mbhg
 6g@`d$cgJjdpa^k^`dZg]jdZk^\aZkZ\m^kblmb\i^kfZg^gmZg]oZkbZ[e^Z\mbhglbgdG(f'
g@Zg]cgJZk^]^i^g]^gmhgnl^h_;L>G*22)%>qik^llbhgl!/'*)"%!/'*)Z"hk!/'*)["'L^^L^\mbhg<*'
6;Zlbl3:ee&Zg]Zem^kgZm^&liZgl&ehZ]^]\Zl^lZlNDGZmbhgZe:gg^qZg]*.k^]blmkb[nmbhgZm
lniihkml'
Key
a:mhnm^klniihkm+.liZgk^eZm^lmhma^NDGZmbhgZeer=^m^kfbg^]IZkZf^m^k_hk>nkh\h]^+%
<e'2'+'*'+!*"_hkfbgbfnfi^k\^gmZ`^h_liZg[^g]bg`fhf^gmmh[^Zllnf^]Zmlniihkmlbg[^Zfl
bgfhghebmab\\hglmkn\mbhg'*.fZr[^ZiikhikbZm^_hkleZ[l!l^^>nkh\h]^+%<e'2','*'+"'
b?hk[^Zflh__bo^liZgl%)'..Ziieb^lmh\^gmk^liZg'

Cl. 9.2.1.2
Cl. 9.3.1.2

195

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

C4 Design for bending


N =^m^kfbg^pa^ma^kDD hkghm!b'^'pa^ma^kng]^k&k^bg_hk\^]hkghm"'
 pa^k^

D 6 F>] (![]+_\d"

pa^k^

] 6 ^__^\mbo^]^ima6a\ho^kf(+

[ 6 pb]mah_l^\mbhgbg\hfik^llbhg

D fZr[^]^m^kfbg^]_khfMZ[e^<-Zg]bl]^i^g]^gmhgma^k^]blmkb[nmbhgkZmbhnl^]'
Table C4
Values for D
Redistribution ratio, d

s/] for D

1d

1.00

)'0/!)'1+"

)'+)1!)'*/1"

)

0.95

)'01!)'1+"

)'*2.!)'*/1"

.

0.90

)'1)!)'1+"

)'*1+!)'*/1"

*)

0.85

)'1+

)'*/1

*.

0.80

)'1-

)'*.,

+)

0.75

)'1/

)'*,0

+.

0.70

)'11

)'*+)

,)

Note
<eZll:k^bg_hk\^f^gmblk^lmkb\m^]mhZk^]blmkb[nmbhgkZmbh%d)'1
Key
aBmblk^\hff^g]^]maZmq(]blebfbm^]mh)'-.T,.V':lZ\hgl^jn^g\^s(]blebfbm^]mhZfbgbfnfh_
)'1+)Zg]D mhZfbgbfnfh_)'*/1'
N B_DD %l^\mbhgblunder-reinforced'
 ?hkk^\mZg`neZkl^\mbhgl3
 :l* 6 F>] (_r]s
 pa^k^

:l* 6 Zk^Zh_m^glbe^k^bg_hk\^f^gm

F>]6 ]^lb`gfhf^gm

_r] 6 _rd (gL6.))(*'*.6-,-'1FIZ

s 6 ]T)'.$)'.!*,'.,D")'.V)'2.]
OZen^lh_s(]!Zg]q(]"fZr[^mZd^g_khfMZ[e^<.





How to: Beams[8]

?hk_eZg`^][^Zflpa^k^q5*'+.a_%
:l* 6 F>] (_r]s
pa^k^ q 6 ]^imamhg^nmkZeZqbl'OZen^lh_q(]fZr[^mZd^g_khfMZ[e^<.

a_ 6 mab\dg^llh__eZg`^

 ?hk_eZg`^][^Zflpa^k^q*'+.a_%k^_^kmhAhpmh]^lb`g\hg\k^m^lmkn\mnk^lnlbg`>nkh\h]^+T1V'
N B_D7D %l^\mbhgblover-reinforcedZg]k^jnbk^l\hfik^llbhgk^bg_hk\^f^gm'
 :l+6!F>]F "(_l\!]]+"
 pa^k^

:l+6 \hfik^llbhgk^bg_hk\^f^gm
B_]+(q7)',0.ma^gma^m^kf:l+lahne][^k^ieZ\^][rma^m^kf
*'/!*]+(q":l+

F  6 D []+_\d

_l\ 6 0))!qn]+"(qn_r]



196

pa^k^
]+ 6 ^__^\mbo^]^imamh\hfik^llbhgk^bg_hk\^f^gm

:ii^g]bq<3=^lb`gZb]l


qn 6 !d)'-"]




pa^k^
d 6k^]blmkb[nmbhgkZmbh

 MhmZeZk^Zh_lm^^e:l*6F (!_r]s"$:l+_l\ (_r]

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Table C5
Values of s/] and q/] for singly reinforced rectangular sections
D

s/]

q/]

(1 d)maxa

0.04

)'2.)b

)'*+.

,)

0.05

)'2.)b

)'*+.

,)

0.06

)'2--

)'*-)

,)

0.07

)'2,-

)'*/.

,)

0.08

)'2+-

)'*2*

,)

0.09

)'2*,

)'+*0

,)

0.10

)'2)+

)'+-.

,)

0.11

)'12*

)'+0+

,)

0.12

)'11)

)',)*

,)

0.13

)'1/1

)',,*

+0

0.14

)'1./

)',/*

+-

0.15

)'1-,

)',2,

+*

0.16

)'1,)

)'-+.

*1

0.17

)'1*/c

)'-/)c

*-

0.18

)'1)+c

)'-2.c

**

0.19

)'010c

)'.,,c

0

0.20

)'00*c

)'.0+c

,

0.208

)'0.1c

)'/)/c

)

Note
_\d.)FIZ
Key

aFZqbfnfZeehpZ[e^k^]blmkb[nmbhg
bIkZ\mb\Zeebfbm
cBmblk^\hff^g]^]maZmq(]blebfbm^]mh)'-.)T,.V':lZ\hgl^jn^g\^s(]blebfbm^]mhZfbgbfnfh_
)'1+)Zg]D mh)'*/1'

C5 Design for beam shear


C5.1 Requirement for shear reinforcement
B_o>]7oK]%\ma^gla^Zkk^bg_hk\^f^gmblk^jnbk^]
pa^k^

o>] 6 O>] ([p]%_hkl^\mbhglpbmahnmla^Zkk^bg_hk\^f^gm!b'^'leZ[l"

oK]%\ 6 la^Zkk^lblmZg\^pbmahnmla^Zkk^bg_hk\^f^gm%_khfMZ[e^</'

197

Table C6
Shear resistance without shear reinforcement, oRd,c (MPa)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

rl = :sl/
[w]

Effective depth ] (mm)


G 200

225

250

275

300

350

400

450

500

600

750

0.25%

)'.-

)'.+

)'.)

)'-1

)'-0

)'-.

)'-,

)'-*

)'-)

)',1

)',/

0.50%

)'.2

)'.0

)'./

)'..

)'.-

)'.+

)'.*

)'-2

)'-1

)'-0

)'-.

0.75%

)'/1

)'//

)'/-

)'/,

)'/+

)'.2

)'.1

)'./

)'..

)'.,

)'.*

1.00%

)'0.

)'0+

)'0*

)'/2

)'/1

)'/.

)'/-

)'/+

)'/*

)'.2

)'.0

1.25%

)'1)

)'01

)'0/

)'0-

)'0,

)'0*

)'/2

)'/0

)'//

)'/,

)'/*

1.50%

)'1.

)'1,

)'1*

)'02

)'01

)'0.

)'0,

)'0*

)'0)

)'/0

)'/.

1.75%

)'2)

)'10

)'1.

)'1,

)'1+

)'02

)'00

)'0.

)'0,

)'0*

)'/1

2.00%

)'2-

)'2*

)'12

)'10

)'1.

)'1+

)'1)

)'01

)'00

)'0-

)'0*

Notes
1MZ[e^]^kbo^]_khf>nkh\h]^+Zg]NDGZmbhgZe:gg^q'
2MZ[e^\k^Zm^]_hk_\d6,)FIZZllnfbg`o^kmb\Zeebgdl'
3?hkr e)'-Zg]
 _\d6+.FIZ%Ziier_Z\mhkh_)'2-

_\d6-)FIZ%Ziier_Z\mhkh_*'*)

_\d6.)FIZ%Ziier_Z\mhkh_*'*2

 _\d6,.FIZ%Ziier_Z\mhkh_*').

_\d6-.FIZ%Ziier_Z\mhkh_*'*-

GhmZiieb\Z[e^_hk_\d7.)FIZ

C5.2 Section capacity check


B_o>]%s7oK]%fZqma^gl^\mbhglbs^blbgZ]^jnZm^
pa^k^

o>]%s 6 O>] ([ps6O>] ([p)'2]%_hkl^\mbhglpbmala^Zkk^bg_hk\^f^gm

oK]%fZq6 \ZiZ\bmrh_\hg\k^m^lmknml^qik^ll^]ZlZlmk^llbgma^o^kmb\ZeieZg^


6 OK]%fZq ([ps


6 OK]%fZq ([p)'2]
oK]%fZq\Zg[^]^m^kfbg^]_khfMZ[e^<0%bgbmbZeer\a^\dbg`Zm\hmy6+'.'Lahne]bm[^k^jnbk^]%
Z`k^Zm^kk^lblmZg\^fZr[^Zllnf^][rnlbg`ZeZk`^klmknmZg`e^%y'
Table C7
Capacity of concrete struts expressed as a stress, oRd,max
_ck

oRd,max (MPa)
cot y

2.50

2.14

1.73

1.43

1.19

1.00

2.18

25

30

35

40

45

20

+'.-

+'1+

,'*2

,'-/

,'/+

,'/1

)'..+

25

,'*)

,'-.

,'2)

-'+,

-'-,

-'.)

)'.-)

30

,'/-

-')-

-'.0

-'2/

.'+)

.'+1

)'.+1

35

-'*.

-'/*

.'+*

.'//

.'2,

/')+

)'.*/

40

-'/,

.'*.

.'1+

/',*

/'/+

/'0+

)'.)-

45

.')2

.'/.

/',2

/'2,

0'+0

0',1

)'-2+

50

.'.+

/'*,

/'2,

0'.+

0'11

1'))

)'-1)

Notes
1MZ[e^]^kbo^]_khf>nkh\h]^+Zg]NDGZmbhgZe:gg^qZllnfbg`o^kmb\Zeebgdl%b'^'\hma6)
2v6)'/T*!_\d (+.)"V
3oK]%fZq6v_\]!\hmy$\hma"(!*$\hm+y"

198

Strength
reduction
factor, v

:ii^g]bq<3=^lb`gZb]l

:lp(lo>]%s[p(_rp]\hmy
pa^k^

:lp 6 Zk^Zh_la^Zkk^bg_hk\^f^gm!o^kmb\ZeebgdlZllnf^]"

l 6 liZ\bg`h_la^Zkk^bg_hk\^f^gm

o>]%s 6 O>] ([ps%Zl[^_hk^

[p 6 [k^Z]mah_ma^p^[

_rp] 6 _rpd (gL6]^lb`grb^e]lmk^g`mah_la^Zkk^bg_hk\^f^gm
@^g^kZeer:lp(lo>]%s[p(*)10
pa^k^_rpd6.))FIZ%gL6*'*.Zg]\hmy6+'.
:em^kgZmbo^er% :lp(l i^k f^mk^ pb]ma h_ [p fZr [^ ]^m^kfbg^] _khf ?b`nk^ <*Z" hk <*[" Zl
bg]b\Zm^] [r ma^ [en^ Zkkhpl bg ?b`nk^<*Z"'Ma^l^ _b`nk^l fZr Zelh [^ nl^] mh ^lmbfZm^ ma^
oZen^h_\hmy'
;^ZflZk^ln[c^\mmhZfbgbfnfla^Zkebgdikhoblbhg':llnfbg`o^kmb\Zeebgdl%
:lp%fbg (l[p)')1_\d)'.(_rd!l^^MZ[e^<1"'
Table C8
Values of :sw,min/l[w for beams for vertical links and _yk = 500 MPa and compatible resistance, oRd
Concrete class

C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60

Asw,min/sbw for beams (x 103) )'0+

)'1)

)'11

)'2.

*')*

*')0

*'*,

vRd for Asw,min /sbw (MPa)

)'10

)'2.

*'),

*'*)

*'*0

*'+,

)'01

vRd,max for cot y = 2.5

8.0

2.14

1.73

1.43
C50/60

7.0

1.19
C45/55
C40/50

fywk = 500 MPa

1.00

C35/45

6.0
C30/37
5.0
vEd,z (MPa)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

C5.3 Shear reinforcement design

C25/30
4.0

C20/25

See Fig. C1b)


3.0
2.0
1.0
0.0
0

6
8
10
Asw/s required per metre width of bw

12

14

Figure C1a)
Diagram to determine :sw/l required (for beams with high shear stress)

199

4.0

C30/37
0

C25/3

fywk = 500 MPa

C20/25

vEd,z (MPa)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

3.0

2.0

Range of vRd,c for range


d = 200 mm, r = 2.0%
to d = 750 mm, r = 0.5%

C20/25
C25/30
C30/37
C35/45
C40/50
C45/55
C50/60

1.0
Asw,min/s
for beams

0.0

2
Asw/s required per metre width of bw

Figure C1b)
Diagram to determine :sw/l required (for slabs and beams with low shear stress)

C6 Design for punching shear


=^m^kfbg^ b_ ing\abg` la^Zk k^bg_hk\^f^gm bl k^jnbk^]% bgbmbZeer Zm n*% ma^g b_ g^\^llZkr Zm
ln[l^jn^gmi^kbf^m^kl%nb'B_o>]7oK]%\ma^ging\abg`la^Zkk^bg_hk\^f^gmblk^jnbk^]
pa^k^

o>] 6 bO>] (nb]






pa^k^
b 6 _Z\mhk]^Zebg`pbma^\\^gmkb\bmr
O>] 6 Ziieb^]la^Zk_hk\^
nb 6 e^g`mah_ma^i^kbf^m^kng]^k\hglb]^kZmbhg
] 6 f^Zg^__^\mbo^]^ima
oK]%\ 6 la^Zkk^lblmZg\^pbmahnmla^Zkk^bg_hk\^f^gm!l^^MZ[e^</"

?hko^kmb\Zela^Zkk^bg_hk\^f^gm
!:lp(lk"6 n*!o>])'0.oK]%\"(!*'._rp]%^_"
pa^k^

:lp 6 Zk^Zh_la^Zkk^bg_hk\^f^gmbghg^i^kbf^m^kZkhng]ma^\henfg'
?hk:lp%fbgl^^<hg\bl^>nkh\h]^+%L^\mbhg*)'-'+Zg]_hkeZrhnml^^L^\mbhg*+'-',

lk
6 kZ]bZeliZ\bg`h_i^kbf^m^klh_la^Zkk^bg_hk\^f^gm
Concise: 10.4.2,
12.4.3

 
 _rp]%^_

n* 6 [Zlb\\hgmkhei^kbf^m^k+]_khf\henfg_Z\^
6 ^__^\mbo^]^lb`glmk^g`mah_k^bg_hk\^f^gm6!+.)$)'+.]"_rp]'?hk@kZ]^
.))la^Zkk^bg_hk\^f^gml^^MZ[e^<2

Table C9
Values of _ywd,ef for grade 500 reinforcement
]
fywd,ef

150

200

250

300

350

400

450

+10'.

,))

,*+'.

,+.

,,0'.

,.)

,/+'.

:mma^\henfgi^kbf^m^k%\a^\do>]OK]fZq_hk\hmy6*')`bo^gbgMZ[e^<0'
200

:ii^g]bq<3=^lb`gZb]l
C7 Check deflection

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Bg `^g^kZe% ma^ LEL lmZm^ h_ ]^_e^\mbhg fZr [^ \a^\d^] [r nlbg` ma^ liZg&mh&^__^\mbo^&]^ima
ZiikhZ\a'Fhk^\kbmb\ZeZiikZblZeh_]^_hkfZmbhgblhnmlb]^ma^l\hi^h_mablin[eb\Zmbhg'Mhnl^
ma^liZg&mh&^__^\mbo^&]^imaZiikhZ\a%o^kb_rmaZm3
:eehpZ[e^e(]6GqDq?*q?+q?,Z\mnZee(]
pa^k^

G 6 [Zlb\liZg&mh&^__^\mbo^&]^imakZmbh]^kbo^]_hkD6*')Zg]r 6)_khfL^\mbhg*)'.'+
h_<hg\bl^>nkh\h]^+hkMZ[e^<*)hk?b`nk^<+

D 6 _Z\mhkmhZ\\hngm_hklmkn\mnkZelrlm^f'L^^MZ[e^<**

?*6 _Z\mhkmhZ\\hngm_hk_eZg`^]l^\mbhgl'Pa^g[^__ ([p6*')%_Z\mhk?*6*')'
Pa^g[^__([pbl`k^Zm^kmaZg,')%_Z\mhk?*6)'1)'
?hkoZen^lh_[^__ ([p[^mp^^g*')Zg],')%bgm^kiheZmbhgfZr[^nl^]!l^^MZ[e^<*+"

pa^k^

[^__bl]^_bg^]bgL^\mbhg.'+'+h_<hg\bl^>nkh\h]^+

[p 6 pb]mah_p^[

  BgB[^Zfl[p6fbgbfnfpb]mah_p^[bgm^glbe^Zk^Z'

  BgmZi^k^]p^[l[p6pb]mah_p^[Zm\^gmkhb]h_k^bg_hk\^f^gmbgp^['

?+6 _Z\mhkmhZ\\hngm_hk[kbmme^iZkmbmbhglbgZllh\bZmbhgpbmaehg`liZgl'@^g^kZeer?+
6*')[nmb_[kbmme^iZkmbmbhglZk^ebZ[e^mh[^]ZfZ`^][r^q\^llbo^]^_e^\mbhg%?+
lahne][^]^m^kfbg^]Zl_heehpl3

  Z"bg_eZmleZ[lbgpab\ama^ehg`^kliZgbl`k^Zm^kmaZg1'.f%?+61'.(e^__

  ["bg[^ZflZg]hma^kleZ[lpbmaliZglbg^q\^llh_0')f%?+60')(e^__

  OZen^lh_?+fZr[^mZd^g_khfMZ[e^<*,

?,6 _Z\mhkmhZ\\hngm_hkl^kob\^lmk^llbgm^glbe^k^bg_hk\^f^gm6,*)(sl*'.
<hgl^koZmbo^er%b_Zl^kob\^lmk^ll%sl%h_,*)FIZblZllnf^]_hkma^]^lb`g^]Zk^Z
h_k^bg_hk\^f^gm%:l%k^jma^g?,6:l%ikho (:l%k^j*'.'








Concise: 10.5.2

Concise: 5.2.2

Fhk^Z\\nkZm^er%ma^l^kob\^Z[bebmrlmk^ll%sl%fZr[^^lmbfZm^]Zl_heehpl3
sl6_rd (gLT!@d$c+ Jd"(!*'+.@d$*'.Jd"VT:l%k^j (:l%ikhoV!*(d"
hk
sl6slnT:l%k^j (:l%ikhoV!*(d"
pa^k^
sln

6 ma^ ngfh]b_b^] LEL lm^^e lmk^ll% mZdbg` Z\\hngm h_ gF _hk
k^bg_hk\^f^gmZg]h_`hbg`_khfnembfZm^Z\mbhglmhl^kob\^Z[bebmr
Z\mbhgl

6 .))(gL!@d$c+ Jd"(!*'+.@d$*'.Jd"
slnfZr[^^lmbfZm^]_khf?b`nk^<,Zlbg]b\Zm^][rma^[en^
Zkkhp
:l%k^j (:l%ikho 6 Zk^Zh_lm^^ek^jnbk^]]bob]^][rZk^Zh_lm^^eikhob]^]'
!*(d"
6 _Z\mhkmhng&k^]blmkb[nm^NELfhf^gmllhma^rfZr[^nl^]bg
mablLELo^kb_b\Zmbhg!l^^MZ[e^<*-"

:\mnZee(]6Z\mnZeliZg]bob]^][r^__^\mbo^]^ima%]'

L^^:ii^g]bq;*'.
201

Table C10
Basic ratios of span-to-effective-depth, G, for members without axial compression
Required
reinforcement, r

_ck
20

25

30

35

40

45

0.30%

+.'2

,+'+

,2'+

-/'/

.-'/

/,')

0*'1

0.40%

*2'*

++'-

+/'+

,)'-

,.')

,2'1

-.')

50

0.50%

*0')

*1'.

+)'.

+,')

+.'1

+1'1

,+')

0.60%

*/')

*0',

*1'.

*2'1

+*',

+,'*

+.'+

0.70%

*.',

*/'-

*0'-

*1'.

*2'/

+)'/

+*'0

0.80%

*-'1

*.'0

*/'/

*0'/

*1'.

*2'-

+)'-

0.90%

*-',

*.'+

*/')

*/'1

*0'0

*1'.

*2',

1.00%

*-')

*-'1

*.'.

*/',

*0')

*0'1

*1'.

1.20%

*,'.

*-'*

*-'1

*.'-

*/')

*/'/

*0',

1.40%

*,'*

*,'0

*-'+

*-'1

*.',

*.'1

*/'-

1.60%

*+'2

*,',

*,'1

*-',

*-'1

*.'+

*.'0

1.80%

*+'0

*,'*

*,'.

*,'2

*-',

*-'1

*.'+

2.00%

*+'.

*+'2

*,',

*,'/

*-')

*-'-

*-'1

2.50%

*+'+

*+'.

*+'1

*,'*

*,'-

*,'0

*-')

3.00%

*+')

*+',

*+'.

*+'1

*,')

*,',

*,'.

3.50%

**'2

*+'*

*+',

*+'.

*+'0

*+'2

*,'*

4.00%

**'1

**'2

*+'*

*+',

*+'.

*+'0

*+'2

4.50%

**'0

**'1

*+')

*+'+

*+',

*+'.

*+'0

5.00%

**'/

**'1

**'2

*+'*

*+'+

*+'-

*+'.

)'.)

)'..

)'.2

)'/,

)'/0

)'0*

)'-.
Reference
reinforcement ratio,r0

Notes
1Pa^k^r6:l ([]'
2?hkM&l^\mbhglrblma^Zk^Zh_k^bg_hk\^f^gm]bob]^][rma^Zk^Zh_\hg\k^m^Z[ho^ma^\^gmkhb]h_
ma^m^glbhgk^bg_hk\^f^gm'
3Ma^oZen^l_hkliZg&mh&^__^\mbo^&]^imaaZo^[^^g[Zl^]hgMZ[e^0'-Gbg>nkh\h]^+%nlbg`D6*
!lbfierlniihkm^]"Zg]r 6)!gh\hfik^llbhgk^bg_hk\^f^gmk^jnbk^]"'
4Ma^liZg&mh&^__^\mbo^&]^imakZmbhlahne][^[Zl^]hgma^lahkm^kliZgbgmph&pZrliZggbg`leZ[lZg]
ma^ehg`^kliZgbg_eZmleZ[l'

32
Basic span-to-effective-depth ratio N (l/d)

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Table 7.4N

30

fck = 50

28

fck = 45
fck = 40

26

fck = 35

24
fck = 30
22
20
18
16
14
12
0.40%

fck = 25
fck = 20
0.60%

1.40% 1.60%
1.20%
0.80% 1.00%
Design tension reinforcement (100As,req /bd)

Figure C2
Basic span-to-effective depth ratios, G, for D = 1, r' = 0

202

1.80% 2.00%

:ii^g]bq<3=^lb`gZb]l
Table C11
D factors to be applied to basic ratios of span-to-effective-depth
D

Beams

Slabs

Lbfierlniihkm^][^Zfl

Hg^&hkmph&pZrliZggbg`lbfierlniihkm^]leZ[l

*')

>g]liZgh_\hgmbgnhnl[^Zfl

>g]liZgh_hg^&pZrliZggbg`\hgmbgnhnlleZ[l%hk
mph&pZrliZggbg`leZ[l\hgmbgnhnlho^khg^ehg`^]`^

*',

Bgm^kbhkliZglh_\hgmbgnhnl[^Zfl

Bgm^kbhkliZglh_\hgmbgnhnlleZ[l

*'.

?eZmleZ[l![Zl^]hgehg`^kliZg"

*'+

<Zgmbe^o^kl

<Zgmbe^o^k

)'-

Table C12
Factor F1, modifier for flanged beams
[eff/[w

1.0

1.5

2.0

2.5

3.0

Factor

*'))

)'2.

)'2)

)'1.

)'1)


Table C13
Factor F2, modifier for long spans supporting brittle partitions
Span, m

eeff

7.0 7.5

8.0

8.5

9.0

10.0

11.0

12.0

13.0

14.0

15.0

16.0

Flat slabs

8.5/eeff

*'))

*'))

*'))

*'))

)'2-

)'1.

)'00

)'0*

)'/.

)'/*

)'.0

)'.,

Beams and other slabs 7.0/eeff

*'))

)'2,

)'11

)'1+

)'01

)'0)

)'/-

)'.1

)'.-

)'.)

)'-0

)'--

320
35

y2 = 0.8, gG = 1.

300
Unmodified steel stress ssu

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Structural system

280
y2=

260
240

0.6,

gG

y 2 = 0.6, g G =

25
= 1.

.3, g G

y2 = 0

.25
=1
g
G
.25
.3,
=1
=0
g
G
y2
.2,
=0
y2

1.35

= 1.35
.35

, gG = 1

y 2 = 0.2

220
200
180

1.00

2.00

3.00

4.00

Ratio Gk/Qk
Figure C3
Determination of unmodified SLS, stress in reinforcement, ssu

203

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Table C14
(1/d) factor to be applied to unmodified ssu to allow for redistribution used
Average redistribution used

20%

15%

10%

5%

0%

5%

10%

15%

20%

25%

30%

Redistribution ratio used, d

1.20

1.15

1.10

1.05

1.00

0.95

0.90

0.85

0.80

0.75

0.70

(1/d)

1,

10

2*

2.

*))

*).

***

**1

*+.

*,,

*-,

Notes
1 Pa^k^\h^__b\b^gml_khfMZ[e^<+aZo^[^^gnl^]bg]^lb`gZg]pa^k^Jd&*'+.@d%ma^\h^__b\b^gmlbgMZ[e^<+fZr[^\hglb]^k^]mh
k^ik^l^gmfhf^gm]blmkb[nmbhgh_3
1g^Zkfb]]e^h_^g]liZgpbmaibgg^]^g]lniihkm
++Zm_bklmbgm^kbhklniihkm%ZlZphklm\Zl^
$,g^Zkfb]]e^h_bgm^kgZeliZgl%ZlZphklm\Zl^
+1Zmbgm^kbhklniihkml%ZlZphklm\Zl^'
2 Pa^k^\h^__b\b^gml_khfMZ[e^<,aZo^[^^gnl^]bg]^lb`gZg]pa^k^Jd&@d%ma^\h^__b\b^gmlbgMZ[e^<,fZr[^\hglb]^k^]mhk^ik^l^gm
fhf^gmk^]blmkb[nmbhgh_3
$,g^Zkfb]]e^h_^g]liZgpbmaibgg^]^g]lniihkm%ZlZphklm\Zl^
$2g^Zkfb]]e^h_bgm^kgZeliZgl%ZlZphklm\Zl^
*.ZmZeebgm^kbhklniihkml'

C8 Control of cracking
<kZ\dbg` fZr [^ \hgmkhee^] [r k^lmkb\mbg` ^bma^k fZqbfnf [Zk ]bZf^m^k hk fZqbfnf [Zk
liZ\bg`mhma^k^e^oZgm]bZf^m^klZg]liZ\bg`l`bo^gbgMZ[e^<*.'Ma^ZiikhikbZm^LELlmk^llbg
k^bg_hk\^f^gm%sl%fZr[^]^m^kfbg^]Zlhnmebg^]_hk?,bgL^\mbhg<0'
FbgbfnfZk^ZlZg]Zli^\mlh_]^mZbebg`lahne][^\a^\d^]'
Table C15
Maximum bar diameters f or maximum bar spacing for crack control
Steel stress (MPa) ss

Maximum bar size (mm)

Maximum bar spacing (mm)

pk = 0.3 mm

pk = 0.4 mm

pk = 0.3 mm

pk = 0.4 mm

160

,+

-)

,))

,))

200

+.

,+

+.)

,))

240

*/

+)

+))

+.)

280

*+

*/

*.)

+))

320

*)

*+

*))

*.)

360

*)

.)

*))

OR

Notes
1Ma^ghkfZeebfbmh_)',fffZr[^k^eZq^]mh)'-ff_hkQHZg]Q<*^qihlnk^\eZll^lb_ma^k^bl
ghli^\b_b\k^jnbk^f^gm_hkZii^ZkZg\^'
2MZ[e^Zllnfimbhglbg\en]^\ghf6+.ffZg]_\m%^__!6_\mf"6+'2FIZ'



204

:ii^g]bq<3=^lb`gZb]l
C9 Design for axial load and bending
C9.1 General

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Bg\henfgl%]^lb`gfhf^gmlF>]Zg]]^lb`gZiieb^]ZqbZe_hk\^G>]lahne][^]^kbo^]_khfZgZerlbl%
\hglb]^kZmbhgh_bfi^k_^\mbhglZg]%pa^k^g^\^llZkr%+g]hk]^k^__^\ml'
Bmblg^\^llZkrmh\Ze\neZm^^__^\mbo^e^g`malbghk]^kmh]^m^kfbg^pa^ma^kZ\henfgblle^g]^k
!l^^>nkh\h]^+%<e'.'1','+Zg]>qik^llbhg!.'*.""'Ma^^__^\mbo^e^g`mah_fhlm\henfglpbee[^
e(+5e)5e!l^^>nkh\h]^+?b`nk^.'0_"'I=//10T/V<e'+'*)ln``^lmlmaZmnlbg`ma^ikh\^]nk^
hnmebg^] bg >nkh\h]^ + !.'1','+!," Zg] .'1','+!."" e^Z]l mh lbfbeZk ^__^\mbo^ e^g`mal mh mahl^
mZ[neZm^] bg ;L 1**)T0V Zl k^ikh]n\^] [^ehp ZlMZ[e^ <*/' >qi^kb^g\^ ln``^lml maZm ma^l^
mZ[neZm^]oZen^lZk^\hgl^koZmbo^'
Table C16
Effective length e0: conservative factors for braced columns
End condition
at top

End condition at bottom


1

)'0.

)'1)

)'2)

)'1)

)'1.

)'2.

)'2)

)'2.

*'))

Key
<hg]bmbhg* <
 henfg\hgg^\m^]fhghebmab\Zeermh[^Zflhg^Z\alb]^maZmZk^Zme^ZlmZl]^^iZlma^
ho^kZee]^imah_ma^\henfgbgma^ieZg^\hglb]^k^]


Pa^k^ma^\henfgbl\hgg^\m^]mhZ_hng]Zmbhgmabllahne][^]^lb`g^]mh\Zkkrfhf^gm
bghk]^kmhlZmbl_rmabl\hg]bmbhg

<hg]bmbhg+ <
 henfg\hgg^\m^]fhghebmab\Zeermh[^Zflhg^Z\alb]^maZmZk^laZeehp^kmaZgma^
ho^kZee]^imah_ma^\henfgbgma^ieZg^\hglb]^k^][r`^g^kZeerghme^llmaZgaZe_ma^
\henfg]^ima
<hg]bmbhg, <
 henfg\hgg^\m^]mhf^f[^klmaZm]hghmikhob]^fhk^maZgghfbgZek^lmkZbgmmh
khmZmbhg
Note
MZ[e^mZd^g_khfFZgnZe_hkma^]^lb`gh_\hg\k^m^[nbe]bg`lmkn\mnk^lmh>nkh\h]^+T,.V'Ma^oZen^lZk^
mahl^nl^]bg;L1**)3IZkm*3*220T0V_hk[kZ\^]\henfgl'Ma^l^oZen^lZk^\ehl^mhmahl^oZen^lmaZm
phne][^]^kbo^]b_ma^\hgmkb[nmbhg_khfZ]cZ\^gm\henfglp^k^b`ghk^]'

C9.2 Design by calculation


:llnfbg`mpheZr^klh_k^bg_hk\^f^gm%:l*Zg]:l+%ma^mhmZeZk^Zh_lm^^ek^jnbk^]bgZ\henfg%
:l%fZr[^\Ze\neZm^]Zllahpg[^ehp'
N ?hkZqbZeehZ]

:lG(+6!G>]a\\n_\d[]\ (g<"(!sl\slm"
pa^k^

:lG6mhmZeZk^Zh_k^bg_hk\^f^gmk^jnbk^]mhk^lblmZqbZeehZ]nlbg`mablf^mah]'
:lG6:l*$:l+Zg]:l*6:l+

pa^k^

:l*!:l+"6 Zk^Zh_k^bg_hk\^f^gmbgeZr^k*!eZr^k+"

G>] 6 ]^lb`gZiieb^]ZqbZe_hk\^
a\\ 6 )'1.
n 6 *_hk<.)(/)

[ 6 [k^Z]mah_l^\mbhg

]\ 6 ^__^\mbo^]^imah_\hg\k^m^bg\hfik^llbhg6lqa

Concise:
Fig. 6.3

Concise:
Fig. 6.4

205





pa^k^
l
6
q
6
a
6
sl\%!slm" 6

)'1_hk<.)(/)
]^imamhg^nmkZeZqbl
a^b`amh_l^\mbhg
lmk^llbg\hfik^llbhg!Zg]m^glbhg"k^bg_hk\^f^gm

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

N ?hkfhf^gm

:lF(+6TF>]a\\n_\d[]\!a(+]\ (+"(g<V(T!a(+]+"!sl\$slm"V
pa^k^

:lF 6 m hmZeZk^Zh_k^bg_hk\^f^gmk^jnbk^]mhk^lblmfhf^gmnlbg`mablf^mah]
:lF6:l*$:l+Zg]:l*6:l+
Pa^k^k^bg_hk\^f^gmblghm\hg\^gmkZm^]bgma^\hkg^kl%Z\hgl^koZmbo^ZiikhZ\ablmh\Ze\neZm^
Zg^__^\mbo^oZen^h_]+ZlbeenlmkZm^]bg?b`nk^l<-Z"mh^"'
N Lhenmbhg3bm^kZm^qln\amaZm:lG6:lF

C9.3 Rectangular column charts


:em^kgZmbo^er:lfZr[^^lmbfZm^]_khf\henfg\aZkml'
?b`nk^l<-Z"mh<-^"`bo^ghg&]bf^glbhgZe]^lb`g\aZkml_hklrff^mkb\Zeerk^bg_hk\^]k^\mZg`neZk
\henfglpa^k^k^bg_hk\^f^gmblZllnf^]mh[^\hg\^gmkZm^]bgma^\hkg^kl'
Bgma^l^\aZkml3
a\\ 6 )'1.
_\d  .)FIZ
_rd  .))FIZ
Lbfieb_b^]lmk^ll[eh\dZllnf^]'
:l 6 mhmZeZk^Zh_k^bg_hk\^f^gmk^jnbk^]
 6 !:l _rd ([a_\d"[a_\d (_rd
pa^k^

!:l _rd ([a_\d"bl]^kbo^]_khfma^ZiikhikbZm^]^lb`g\aZkmbgm^kiheZmbg`Zlg^\^llZkr
[^mp^^g\aZkml_hkma^oZen^h_]+(a_hkma^l^\mbhg'
[6[k^Z]mah_l^\mbhg
a6a^b`amh_l^\mbhg
Pa^k^k^bg_hk\^f^gmblghm\hg\^gmkZm^]bgma^\hkg^kl%Z\hgl^koZmbo^ZiikhZ\ablmh\Ze\neZm^
Zg^__^\mbo^oZen^h_]+ZlbeenlmkZm^]bg?b`nk^l<-Z"mh^"'
]+ 6 ^__^\mbo^]^imamhlm^^ebgeZr^k+

206

:ii^g]bq<3=^lb`gZb]l
1.3
Kr = 0.2

d 2 /h = 0.05

hf
c

1.2
k /b

0.3

h/2

fy

1.1

0.8
NEd/bhfck

d2

0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1

0.9

0.7
0.6
0.5

Centroid of bars in
half section

0.5
0.6
0.7

0.8

0
0.4

0.9
0.3

1.0

0.2
0.1
0

0.05

0.10

0.15

0.20

0.25
MEd/bh2fck

0.30

0.35

0.45

0.40

Figure C4a)
Rectangular columns ]2/a = 0.05

1.3

Kr = 0.2
ck

d 2 /h = 0.10

1.2

k /b

hf

0.3

h/2

fy

1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1

1.0
0.9
0.8
NEd/bhfck

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

0.4

1.0

1.0

0.7
0.6
0.5

0.4

d2
Centroid of bars in
half section

0.5
0.6
0.7

0.8

0
0.4

0.9
0.3
Kr = 1

0.2
0.1
0

0.05

0.10

0.15

0.25
0.20
MEd/bh2fck

0.30

0.35

0.40

0.45

Figure C4b)
Rectangular columns ]2/a = 0.10

207

1.3
Kt = 0.2

d 2 /h = 0.15
k

1.2

hf
c

0.3

k /b

h/2

fy

1.1

1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1

0.9

NEd/bhfck

0.8
0.7
0.6
0.5

0.4

d2
Centroid of bars in
half section

0.5
0.6

0.7
0.8

0
0.4

0.9
0.3
Kr = 1

0.2
0.1
0

0.05

0.10

0.15

0.20
MEd/bh2fck

0.25

0.40

0.35

0.30

Figure C4c)
Rectangular columns ]2/a = 0.15

1.3

Kr = 0.2

d 2 /h = 0.20

hf

ck

1.2

h/2

fy

k /b

0.3

1.1

A
1.0

1.0
0.9
0.8
0.7
0.6
0.5

0.9
0.8
NEd/bhfck

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

1.0

0.7

0.4

d2

0.6

0.4
0.3
0.2
0.1

0.6
0.5

Centroid of bars in
half section

0.5

0.7

0.8

0.4

0.9

0.3
0.2

Kr = 1

0.1
0

0.05

Figure C4d)
Rectangular columns ]2/a = 0.20

208

0.10

0.15

0.20
MEd/bh2fck

0.25

0.30

0.35

:ii^g]bq<3=^lb`gZb]l
1.3
Kr = 0.2

d 2 /h = 0.25

hf
c

1.2

h/2

fy

k /b

0.3

1.1

A
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1

0.9
0.8
NEd/bhfck

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

1.0

0.7
0.6
0.5

d2

0.4

Centroid of bars in
half section
0.5

0.6

0.7

0.4

0.8

0.3

0.9

0.2
0.1

Kr = 1
0

0.05

0.10

0.15
MEd/bh2fck

0.20

0.25

0.30

Figure C4e)
Rectangular columns ]2/a = 0.25

C9.4 Biaxial bending in rectangular columns


:lZ_bklmlm^i%l^iZkZm^]^lb`gbg^Z\aikbg\biZe]bk^\mbhg%]blk^`Zk]bg`[bZqbZe[^g]bg`%fZr[^
ng]^kmZd^g'Gh_nkma^k\a^\dblg^\^llZkrb_)'.l r (l s+')Zg]%_hkk^\mZg`neZkl^\mbhgl%)'+
!^r(a^j"(!^s ([^j"hk!^r(a^j"(!^s ([^j".')'Hma^kpbl^l^^L^\mbhg.'/',h_<hg\bl^>nkh\h]^+'

Concise: 5.6.3

?hkljnZk^\henfgl!^r (a^j "(!^s ([^j"6F>]r(F>]s'

C9.5 Circular column charts


BgZlbfbeZkfZgg^kmh<2',%ma^Zk^Zh_k^bg_hk\^f^gm_hk\bk\neZk\henfgl:lfZr[^^lmbfZm^]
_khfma^\aZkmlbg?b`nk^l<.Z"mh<.]"'
Bgma^l^\aZkml3
a\\6 )'1.
_\d  .)FIZ
_rd 6 .))FIZ
:l 6 mhmZeZk^Zh_k^bg_hk\^f^gmk^jnbk^]
 6 !: l _ rd (a +_ \d"a + _ \d (_ rd
 pa^k^!:l _rd (a+_\d"bl]^kbo^]_khfma^ZiikhikbZm^]^lb`g\aZkmbgm^kiheZmbg`Zlg^\^llZkr'
](a6 ^__^\mbo^]^ima(ho^kZee]bZf^m^k'

C9.6 Links
Ebgdl bg \henfgl lahne] [^ Zm e^Zlm 1 ff hk fZqbfnf ]bZf^m^k h_ ehg`bmn]bgZe [Zkl(- bg
]bZf^m^kZg]Z]cZ\^gmmh[^ZflZg]leZ[lliZ\^]Zmma^e^Zlmh_3
N *+mbf^lma^fbgbfnf]bZf^m^kh_ma^ehg`bmn]bgZe[Zk%
N /)h_ma^e^ll^k]bf^glbhgh_ma^\henfg%hk
N +-)ff'

209

k /h 2
fc
k

1.2

Ratio d/h = 0.6

fy

0.2

1.1

1.0
1.0

0.9

0.9

0.8

0.3

0.4

NEd /h2fck

0.5

0.6
0.5

0.7

0.6

0.4
0.6

0.3
0.2

0.5

0.7

0.1
0

0.4

0.8
0.9

0.3
0.2

Kr =1

0.1
0

0.01

0.02

0.03

0.04

0.06

0.05

0.07

MEd /h3fck
Figure C5a)
Circular columns ]/a = 0.6

k /h 2
fc
k

1.2
0.2

Ratio d/h = 0.7

fy

1.1

1.0

1.0

0.9
0.8
0.7

0.9
0.8
NEd /h2fck

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

0.7
0.8

0.6

0.5
0.6

0.2
0.1

0.5

0.4

0.6
0.5
0.4
0.3

0.7

0.4

0.3

0.7

0.3

0.8

0.2
Kr =1

0.1
0
0

Figure C5b)
Circular columns ]/a = 0.7

210

0.02

0.04

0.06
MEd /h3fck

0.08

0.10

0.12

:ii^g]bq<3=^lb`gZb]l

Af
s y / 2
k h f
c

1.2
0.2
1.1

0.8
0.7

0.8

NEd /h2fck

0.5

0.4
0.3

0.6

0.6

0.2
0.1
0

0.5
0.4

0.7
0.8

0.3

0.9

0.2
0.1
0

0.4

0.6
0.5

0.7

Kr =1

0.02

0.06

0.04

0.08

0.10
MEd /h3fck

0.12

0.16

0.14

0.18

0.20

Figure C5c)
Circular columns ]/a = 0.8

Af
s y /h 2
k
f

ck

1.2
0.2
1.1

1.0

1.0

Ratio d/h = 0.9


d

0.3

0.9
0.9

0.8
0.7
0.6

0.8

0.4
0.5

0.5
0.4
0.3

0.7
NEd /h2fck

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

0.9

0.3

1.0
0.9

1.0

Ratio d/h = 0.8

0.6

0.6

0.2
0.1

0.5
0.4

0.7

0.8

0.3
0.9

0.2
0.1
0

Kr =1
0.05

0.10

0.15

0.20

0.25

0.30

MEd /h3fck
Figure C5d)
Circular columns ]/a = 0.9

211

Eurocode 2 resources
Publications
Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Concise Eurocode 2
<<BI&)).%Ma^<hg\k^m^<^gmk^%+))/
:aZg][hhd_hkma^]^lb`gh_bg&lbmn\hg\k^m^[nbe]bg`lmh>nkh\h]^+Zg]bmlNDGZmbhgZe:gg^q

How to design concrete structures using Eurocode 2


<<BI&))-%Ma^<hg\k^m^<^gmk^%+))/
@nb]Zg\^_hkma^]^lb`gZg]]^mZbebg`h_Z[khZ]kZg`^h_\hg\k^m^^e^f^gmlmh>nkh\h]^+

Economic concrete frame elements to Eurocode 2


<<BI&)+.%Ma^<hg\k^m^<^gmk^%+))2
:l^e^\mbhgh_k^bg_hk\^]\hg\k^m^_kZf^^e^f^gmlbgfnemb&lmhk^r[nbe]bg`l

Precast Eurocode 2: Design manual


<<BI&)*-%;kbmblaIk^\Zlm<hg\k^m^?^]^kZmbhg%+))1
:aZg][hhd_hkma^]^lb`gh_ik^\Zlm\hg\k^m^[nbe]bg`lmkn\mnk^lmh>nkh\h]^+Zg]bmlGZmbhgZe:gg^q

Precast Eurocode 2: Worked examples


<<BI&),-%;kbmblaIk^\Zlm<hg\k^m^?^]^kZmbhg%+))1
Phkd^]^qZfie^l_hkma^]^lb`gh_ik^\Zlm\hg\k^m^[nbe]bg`lmh>nkh\h]^+Zg]bmlGZmbhgZe:gg^q

Concrete buildings scheme design manual


<<BI&).*%Ma^<hg\k^m^<^gmk^+))2
:aZg][hhd_hkma^BLkn\m>\aZkm^k^]f^f[^klabi^qZfbgZmbhg%[Zl^]hg><+

Properties of concrete for use in Eurocode 2


<<BI&)+2%Ma^<hg\k^m^<^gmk^%+))1
Ahpmhhimbfbs^ma^^g`bg^^kbg`ikhi^kmb^lh_\hg\k^m^bg]^lb`gmh>nkh\h]^+

Standard method of detailing structural concrete


Bglmbmnmbhgh_Lmkn\mnkZe>g`bg^^kl(Ma^<hg\k^m^Lh\b^mr%+))/
:fZgnZe_hk[^lmikZ\mb\^

Manual for the design of concrete building structures to Eurocode 2


Bglmbmnmbhgh_Lmkn\mnkZe>g`bg^^kl%+))/
:fZgnZe_hkma^]^lb`gh_\hg\k^m^[nbe]bg`lmh>nkh\h]^+Zg]bmlGZmbhgZe:gg^q

BS EN 1992-1-1, Eurocode 2 Part 1-1: Design of concrete structures


General rules and rules for buildings
;kbmblaLmZg]Zk]lBglmbmnmbhg%+))-

National Annex to Eurocode 2 Part 1-1


;kbmblaLmZg]Zk]lBglmbmnmbhg%+)).

Software
RC spreadsheets: V3. User guide and CD
<<BI&))1'Ma^<hg\k^m^<^gmk^%+))/
>q\^elik^Z]la^^ml_hk]^lb`gmh;L1**)Zg]>nkh\h]^+Zg]bmlNDGZmbhgZe:gg^q

Websites
Eurocode 2 www.eurocode2.info
Eurocodes Expert www.eurocodes.co.uk
The Concrete Centre www.concretecentre.com
Institution of Structural Engineers www.istructe.org
212

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

F^f[^klh_ma^Lm^^kbg`@khni
ChagFZlhg
LmnZkm:e^qZg]^k
IZe<aZgZ
<aZke^l@hh]\abe]
MhgrChg^l
:g]rEre^
Kb\aZk]Fhll
GZkrGZkZrZgZg
Kb\aZk]LabifZg
Kh[^kmOheenf
KnllPhelm^gahef^
Kh]P^[lm^k

:eZg;Zqm^k:llh\bZm^l!<aZbkfZg"
PLI@khniie\
Fbg^kZeIkh]n\ml:llh\bZmbhg<^f^gm
Ma^<hg\k^m^<^gmk^
:kni
GKF<hglnemZgml
Ihp^eeMheg^k:llh\bZm^l
<eZkdLfbmaIZkmg^klabi
=<E@
Bfi^kbZe<hee^`^%Ngbo^klbmrh_Ehg]hg
PL:mdbgl=MBIkhc^\mH_\^k
<hg\k^m^BgghoZmbhgZg]=^lb`g

F^f[^klh_ma^<hg\k^m^Bg]nlmkr>nkh\h]^+@khni!<B>@"
ChagFhhk^
<ebo^;n]`^
IZe<aZgZ
Chag<eZkd^
<hebg<e^o^ker
<aZke^l@hh]\abe]
AZb`@neoZg^llbZg
@^h__AZk]bg`
MhfAZkkblhg
MhgrChg^l
ChagFZlhg
Kb\aZk]Fhll
GZkrGZkZrZgZg
Kb\aZk]LabifZg
FZkmbgLhnma\hmm
KnllPhelm^gahef^
Kh]P^[lm^k

<hglnemZgm!<aZbkfZg"
;kbmblaIk^\Zlm<hg\k^m^?^]^kZmbhg
Fbg^kZeIkh]n\ml:llh\bZmbhg<^f^gm
Ma^<hg\k^m^Lh\b^mr
<hglmkn\m
Ma^<hg\k^m^<^gmk^
;K>
=<E@
Fbg^kZeIkh]n\ml:llh\bZmbhg<hg\k^m^
:kni
:eZg;Zqm^k:llh\bZm^l
Ihp^eeMheg^k:llh\bZm^l
<eZkdLfbmaIZkmg^klabi
=<E@
<hglnemZgm
PL:mdbgl
<hg\k^m^BgghoZmbhgZg]=^lb`g

BgbmbZel^\mbhg]kZ_ml
* Bgmkh]n\mbhg
+ :gZerlbl%Z\mbhglZg]ehZ]ZkkZg`^f^gml
, LeZ[l
- ;^Zfl
. <henfgl
/ PZeel
:ii^g]bq:3=^kboZmbhgh__hkfneZ^
:ii^g]bq;3L^kob\^Z[bebmrebfbmlmZm^
:ii^g]bq<3=^lb`gZb]l

GZkrGZkZrZgZg
GZkrGZkZrZgZg
<aZke^l@hh]\abe]
<aZke^l@hh]\abe]%Kh]P^[lm^k
MhgrChg^l%C^glMZg]e^k
MhgrChg^l%C^glMZg]e^k
<aZke^l@hh]\abe]%Kh]P^[lm^k%Hp^g;khhd^k
<aZke^l@hh]\abe]%GZkrGZkZrZgZg
<aZke^l@hh]\abe]%Kh]P^[lm^k

Licensed copy from CIS: IMPERIAL, IMPERIAL COLLEGE, 12/11/2015, Uncontrolled Copy.

Phkd^]>qZfie^lmh>nkh\h]^+3Ohenf^*

Mablin[eb\Zmbhg`bo^l^qZfie^lh_ma^]^lb`gmh
>nkh\h]^+h_\hffhgk^bg_hk\^]\hg\k^m^^e^f^gml
bgk^bg_hk\^]\hg\k^m^_kZf^][nbe]bg`l'
Pbma^qm^glbo^\eZnl^k^_^k^g\bg`%k^Z]^klZk^`nb]^]
makhn`a]^lb`g^qZfie^lmh>nkh\h]^+Zg]hma^kk^e^oZgm
>nkh\h]^lZg]k^_^k^g\^l'Ma^in[eb\Zmbhg%pab\abg\en]^l
]^lb`gZb]l%Zbflmha^ei]^lb`g^klpbmama^mkZglbmbhgmh
]^lb`gmh>nkh\h]^l'

<aZke^l@hh]\abe]blikbg\biZelmkn\mnkZe^g`bg^^k
_hkMa^<hg\k^m^<^gmk^pa^k^a^ikhfhm^l^_\b^gm
\hg\k^m^]^lb`gZg]\hglmkn\mbhg';^lb]^likhc^\m
fZgZ`bg`Zg]Znmahkbg`mablin[eb\Zmbhga^aZl
ng]^kmZd^gfZgrikhc^\mlmha^eipbmama^bgmkh]n\mbhg
h_>nkh\h]^+mhma^ND'

Ohenf^*Phkd^]>qZfie^lmh>nkh\h]^+bliZkmh_ZkZg`^
h_k^lhnk\^lZoZbeZ[e^_khfMa^<hg\k^m^<^gmk^mhZllblm
^g`bg^^klpbma]^lb`gmh>nkh\h]^l'?hkfhk^bg_hkfZmbhg
oblbmppp'^nkh\h]^+'bg_h'

<<BI&)-*
In[ebla^]=^\^f[^k+))2
BL;G*&2)-1*1&1-&0
Ikb\^@khniI
FI:Ma^<hg\k^m^<^gmk^
Kbo^klb]^Ahnl^%-F^Z]hpl;nlbg^llIZkd%
LmZmbhg:iikhZ\a%;eZ\dpZm^k%<Zf[^ke^r%Lnkk^r@N*02:;
M^e3$--!!)"*+//)/1))?Zq3$--!)"*+0//)/1)*
ppp'\hg\k^m^\^gmk^'\hf
4

Anda mungkin juga menyukai