Anda di halaman 1dari 17

Job No.

Page No.

Calculations

Revision

1 of 1

Job

PUBLIC
HEALTH

Date

Checked

Date

By

System

Loading units - Water

CDB

LU' LU'
s
s
Col Hot
d
Fitting
No Of
WC 9 litre flush
0
WC 6ltr flush
2
Basin 15mm sep taps
2
Basin 8mm Mixer tap
0
Sink 15mm Conn
4
Sink 20mm Conn
0
Hand Spray 15mm
0
Shower 15mm conn
0
Bath 20mm Conn
0
Urinal
0
Bidet 8mm mixer
0
Bucket Sink
2
Slop Hopper Cistern onl 0
Slop Hopper inc Taps
0
Drinking Fountain
1
Drench shower
0
Washing Machine (dom) 0
Dishwasher (domestic) 0
Total Appliances

5
3
3
3
5
7
4
3
7
1
3
3
3
5
2
15
5
2

11

Add For Contingencies

0
0
3
3
5
7
4
3
7
0
3
3
0
5
0
0
0
0

M
L
L
H
L
M
H
M
M
M
H
L
M
M
L
M
M
L
Total C

LU's
C
Total
0
6
6
0
20
0
0
0
0
0
0
6
0
0
2
0
0
0
40
0.7

###

10.8

LU Total b/d

72

Total LU

82.8

Total L/S

1.1

FREQUENCY OF USE

Drg No.

L
M
H

= Low
= Hig
Medium
= h

LU's
H
Total
0
0
6
0
20
0
0
0
0
0
0
6
0
0
0
0
0
0
H
L/S

l/s

32
0.6

LU's Total Frequency


0
T300
6
T600
12
T300
0
T300
40
T1200
0
T300
0
T300
0
T1800
0
T1800
0
T1500
0
T300
12
T3600
0
T300
0
T300
2
0
T3600
0
T300
0
T300

L/S

72
1.0

L/S

Job No.

Page No.

Calculations

Revision

1 of 1

Job

PUBLIC
HEALTH

Date

Checked

Date

By

System

Cold Water Storage

Occupancy
Occupancy =

721 Persons

Storage as IOP Guide =


So Toatal Storage =

15 litres/pupil
721

15

10815

Litres

Minimize storage to prevent water quality degradation provide only 50% Storage ( As per IOP
So storage =

50%

of

10815

###Litres

Use 1 No. Sectional Tank 3L x 2W x 1.5H with central division plate


Nominal Capacity 4500 Litres Each
Actual Capacity 3600 Litres each side
Actual total Capacity 7200 litres

Job No.

Page No.

Calculations

Revision

1 of 1

Job

PUBLIC
HEALTH

Date

Checked

Date

By

System

Drg No.

Hot Water Storage


Calorifiers

FIGURES FOR SCHOOL


Private Wash ba
Public Wash Bas
Shower
Kitchen Sink
Cleaners Sink
Sink

= 72
= 2
= 7
= 4
= 4
= 27

x
x
x
x
x
x

5
20
180
140
40
40

=
360
=
40
= ###
=
560
=
160
= ###

TOTAL

3460

LOAD FACTOR 0.8


POSSIBLE MAXIMUM DEMAND

3460

L/hr

PROBABLE MAXIMUM DEMAND

3460

2768

L/hr

Use 2 No Cylinders at
67% Capacity each ###

67%

Total storage

0.80

# litres

0 litres

60 MINUTE RECOVERY TIME


SO INPUT =

### x
3600

Primary Hot water LPHW

11

4.19 x

11 C

119
x 4.19

55 =

119

kw

T
=

3 Kg/s
mass flow rate

Job No.

Page No.

Calculations

Revision

1 of 1

Job

PUBLIC
HEALTH

Date

Checked

Date

By

System

Drg No.

Hot Water Storage


Gas Fired Heaters

Using procedure and data from CIBSE Guide G


From:

Recovery Period
Table
Plant Sizing Curves Figure
Plant Sizing Curves Figure

2.10
2.10 - Service
2.11 - Catering

Recovery Period

120 minutes

Service
Storage Capacity litre/person
Boiler Output kW/person

1.1
0.04

Catering
Storage Capacity litre/meal
Boiler Output kW/meal

2.3
0.08

Number of Persons
Number of Meals

731
432

Service
Storage Capacity litres
Boiler Output kW

1.10
0.04

x
x

731
731

=
=

804
26

Catering
Storage Capacity litres
Boiler Output kW

2.3
0.08

x
x

432
432

=
=

994
35

= ###

So:

Both Catering and Service from the same plant so:Total Storage Capacity Litres
Total Boiler Output kW

804

994

26

35

60

Add 25% allowance for mixing of incoming water with hot water
Total Storage Capacity Litres

###

25%

= ### Litres

Add System heat losses through pipework:Total Boiler Output kW


Use 2 No. Units at
#

60

67% Capacity each


67%

###

Litres each

64 kW

Job No.

Page No.

Calculations

Revision

1 of 1

Job

PUBLIC
HEALTH

Date

Checked

Date

By

System

Drg No.

Hot Water Storage


Gas Fired Heaters

Using procedure and data from CIBSE Guide G


From:

Plant Sizing Curves Figure


Plant Sizing Curves Figure

2.10 - Service
2.11 - Catering

Take recovery period as 60 minutes


Service
Storage Capacity litre/person
Boiler Output kW/person

0.9
0.06

Catering
Storage Capacity litre/meal
Boiler Output kW/meal

1.6
0.1

Number of Persons
Number of Meals

467
280

Service
Storage Capacity litres
Boiler Output kW

0.90
0.06

x
x

467
467

=
=

420
28

Catering
Storage Capacity litres
Boiler Output kW

1.6
0.1

x
x

280
280

=
=

448
28

So:

Both Catering and Service from the same plant so:Total Storage Capacity Litres
Total Boiler Output kW

420

448

868

28

28

56

Add 25% allowance for mixing of incoming water with hot water
Total Storage Capacity Litres

868

25%

56

= ### Litres

Add System heat losses through pipework


Total Boiler Output kW
Use 2 No. Units at
#

67% Capacity each


67%

727

Litres each

60 kW

FLOW RATE DEMAND

STARAGE DEMAND REQUIREMENTS

Job Name
Job number

Maximum Demand
Flow
Capacity Rate Loading
No. of
Litres
L/Sec Units
units
Hot & cold

Cold water storage Requirements


litrs per 24 hours

Total flow Total


Rates
Demand
l/s
Rates LU

Basin, 15mm sep taps

0.22

2.00

0.44

12.00

90

180.00

Basin, 2 X 8mm mixer

5 0.183

4.5

0.00

0.00

0.00

45

0.00

Sink, 15mm sep Tap

12

0.3

10

4.00

1.20

40.00

130

520.00

Sink, 20mm sep.mix tap

18

0.32

11

0.00

0.00

0.00

150

0.00

Bath, 15mm Sep/mix tap

80

0.3

10

0.00

0.00

0.00

90

0.00

Bath, 20mm sep/mix tap

80

0.36

14

0.00

0.00

0.00

90

0.00

WC 9 ltr flush

0.2

0.00

0.00

0.00

WC 6 ltr flush

0.15

2.00

0.30

6.00

180

360.00

Hand Spray 15mm

0.22

0.00

0.00

0.00

35

0.00

Shwr, 15mm head

6 0.183

4.5

0.00

0.00

0.00

190

0.00

urinal bowl

0.5

0.00

0.00

0.00

11

0.00

Bidet, 8mm mix tap

3 0.125

0.00

0.00

0.00

90

0.00

0.00

Drench Shower

150

0.35

15

0.00

0.00

0.00

90

0.00

25

0.22

2.00

0.44

12.00

150

300.00

0.15

0.00

0.00

0.00

90

0.00

Slop Hopper, cistern only

7.5

0.15

0.00

0.00

0.00

160

0.00

Slop Hopper, cistern/taps

7.5

0.2

0.00

0.00

0.00

180

0.00

Drinking Fountain

1 0.125

1.00

0.13

2.00

11

11.00

Dom Cloths washer mach

5 0.125

0.00

0.00

0.00

90

0.00

Bucket Sink, 15mm


Dishwasher (Domestic)

MAX Storage Requirement


Total no. of Appliances
Total Simultanious
Demand

11.00
Total ltrs per 24hours 1371.00

Total Flow - l/s and Demand -LU


Water demand Results
LU Sizing Demand Results

2.51

72.00

TOTAL
LOADING
UNITS

Litres
Per
Second

Gravity FED Systems


0.8 m/s

Pipe Size mm
8000
7650
7350
7000
6800
6600
6300
6000
5650
5350
5000
4895
4675
4445
4225
4000
3850
3675
3450
3250
3000
2850
2750
2565
2350
2000
1985
1965
1900
1865
1822
1800
1750
1700
1675
1645
1625
1575
1545
1525
1500

30
29
28
27
26
25
24
23
22
21
20
19.5
19
18.5
18
17.5
17
16.5
16
15.5
15
14.5
14
13.5
13
12.5
12
11.5
11
10.5
10
9.9
9.8
9.7
9.6
9.5
9.4
9.3
9.2
9.1
9

159
159
159
159
159
159
159
159
159
159
159
159
159
159
159
159
133
133
133
133
133
133
133
133
133
133
108
108
108
108
108
108
108
108
108
108
108
108
108
108
108

Boosted Cold Water System


not more than 2.5 M/S

Pipe Size mm
108
108
108
108
108
108
108
108
108
108
108
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76

1475
1445
1410
1385
1350
1325
1295
1265
1235
1200
1175
1148
1124
1100
1050
1035
1021
1012
1000
994
967
951
934
917
900
884
867
851
834
817
800
765
735
700
690
680
670
660
650
640
630
620
610
600
575
554
534
517
500
465
433
400
390
380

8.9
8.8
8.7
8.6
8.5
8.4
8.3
8.2
8.1
8
7.9
7.8
7.6
7.5
7.4
7.3
7.2
7.1
7
6.9
6.8
6.7
6.6
6.5
6.4
6.3
6.2
6.1
6
5.9
5.8
5.7
5.6
5.5
5.4
5.3
5.2
5.1
5
4.9
4.8
4.7
4.6
4.5
4.4
4.3
4.2
4.1
4
3.9
3.8
3.7
3.6
3.5

108
108
108
108
108
108
108
108
108
108
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
67
67

67
67
67
67
67
67
67
67
67
67
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
42
42
42
42
42
42
42
42
42
42
42
42
42
42
35
35

370
360
350
330
310
290
270
250
240
230
220
210
200
190
182
165
156
143
130
125
100
90
80
75
70
65
60
55
50
47
42
38
34
30
25
24
23
22.5
21
20.5
20
19.5
19
18.5
18
10
9
8
7
6
5
4.5
4
3

3.4
3.3
3.2
3.1
3
2.9
2.8
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.95
0.9
0.85
0.8
0.75
0.7
0.65
0.6
0.55
0.5
0.49
0.48
0.47
0.46
0.45
0.44
0.43
0.42
0.41
0.4
0.3
0.28
0.26
0.24
0.22
0.2
0.183
0.175
0.15

67
67
67
54
54
54
54
54
54
54
54
54
54
42
42
42
42
42
42
42
42
35
35
35
35
35
35
35
35
28
28
28
28
28
28
22
22
22
22
22
22
22
22
22
22
22
15
15
15
15
15
15
15
15

35
35
35
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
22
22
22
22
22
22
22
22
22
22
22
22
22
22
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

2
1.5
1

0.125
0.1
0.05

15
15
15

15
15
15

NOTES
page 3 IOP
Minimum Storage Requirements
Ltr per
Hostel
90 / bed space
Hotel

135 /bed space

Offices
with canteen
45 / person
without
40 /person
Resaurant 7 /meal
Day school
nursery
15 /pupil
Primary
15 /pupil
Secondary 20 /pupil
technical 20 /pupil
Boarding school
90 /pupil
Childs home / Residential nursery
135 /bed space
Nuses home
120 / bed spacce
Nursing or convelescent home
135 / bed space
District Hospital
600 /bed space

Anda mungkin juga menyukai