Anda di halaman 1dari 12

LIQUID LEVEL DISPLACER

DEVICES
PROCEDURE

FOR THE

CARTAGENA REFINERY
EXPANSION PROJECT

CB&I CONTRACT NO. 166000


Document No: 166000-000-GE-CM08-0011

Prepared By: Gary Lomax


Information Class:

Confidential

Business

Public

Revision
Number

Revision
Date

Revision Description

CB&I
Prepared
By:

CB&I
Approved
By:

Reficar
Approved
By:

6-Sep-11

Issued for Construction

GL

RKW

OFC

9-Jan-12

Issued for Construction

GL

RKW

OFC

25-Jan-12

Issued for Construction

GL

RKW

OFC

11-Apr-12

Issued for Construction

GL

JHK

OFC

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION DESCRIBING
TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN CONNECTION WITH
WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER THAN WORK PERFORMED BY
CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE SAFEGUARDED AGAINST BOTH DELIBERATE
AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 2 of 12

TABLE OF CONTENTS
1
2
3

4
5
6
7

10

PURPOSE ...................................................................................................................... 3
SAFETY & ENVIRONMENTAL ...................................................................................... 3
ABBREVIATIONS AND DEFINITIONS .......................................................................... 3
3.1
Abbreviations .................................................................................................... 3
3.2
Definitions.......................................................................................................... 6
WINPCS B CHECKSHEETS....................................................................................... 7
NOTES, CAUTIONS AND WARNINGS.......................................................................... 7
REFERENCE DOCUMENTATION ................................................................................. 7
6.1
Documents and Drawings ................................................................................ 7
TEST EQUIPMENT AND GENERAL INFORMATION.................................................... 8
7.1
Test Equipment ................................................................................................. 8
7.2
General............................................................................................................... 8
7.3
Field Calibration ................................................................................................ 9
SPARE PARTS, CONSUMABLES............................................................................... 10
8.1
Spare Parts ...................................................................................................... 10
8.2
Consumables................................................................................................... 10
PROCEDURE............................................................................................................... 11
9.1
Displacer Level Transmitter............................................................................ 11
9.2
System Status ................................................................................................. 12
APPENDIX ................................................................................................................... 12
10.1 Appendix 1 Deviation Table......................................................................... 12

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 3 of 12

PURPOSE

This procedure is developed to provide a clear and safe method for pre-commissioning of Level
Instruments.
This covers the requirements for application of equipment for measuring, transmitting, and indicating fluid
levels.
This is supplemental to the detailed specification sheets. The detailed specification sheets shall govern in
any conflict between the two.
Prior to the execution of this procedure, the following must be completed:

NOTE:

User (s) must read and fully understand the contents of this procedure and its intent.
System walkdown has been completed using the latest Issued for Construction (IFC)
P&IDs
Verify the system is mechanically complete
All required documentation, including A checksheets have been completed and
signed off.

SAFETY & ENVIRONMENTAL

All safe work practices and procedures will be adhered to in accordance with Reficar and Project
Health, Safety and Environmental (HSE) Policies.
Personnel associated with the execution of this procedure must have received all site specific
HSE training.
Proper Personal Protective Equipment (PPE) will worn by all personnel participating in the
execution of this procedure.
Proper barriers and signage to be in place to warn and protect others from any potential or
specific hazards.
The site specific approved Job Safety Analysis, Lock Out / Tag Out (LOTO) and Permit to Work
(PTW) forms must be in place prior to execution of this procedure.

CAUTION:

3
3.1

Emphasis shall be placed on the fact that a real potentially hazard exist during the
work process of this turnaround. Anytime work is being performed on devices that
have been in operation and may still contain product within the boundaries of the
piping, vessels and equipment a hazard exist.

ABBREVIATIONS AND DEFINITIONS


Abbreviations

The following abbreviations are used within this procedure:


CAR

Computer Aided Design

CCR

Central Control Room

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 4 of 12

CCTV

Closed Circuit Television

DCS

Distributed Control System

EDMS

Electronic Document Management System

EMCS

Electrical Monitoring and Control System. This system is


handled by Electrical Engineering.

EPC

Engineering, Procurement and Construction

ESD

Emergency Shutdown System

FAT

Factory Acceptance Test - provided by a Subcontractor or


Vendor during the performance of their Scope of Work and
reviewed by the Instrument and Control Commissioning
Team.

HAZOP

Hazard and Operability Analysis

HVAC

Heating, Ventilation and Air Conditioning

I&E

Instrument and Electrical

IFAT

Integrated Factory Acceptance Test provided by a


Subcontractor or Vendor during the performance of their
Scope of Work and reviewed by the Instrument and Control
Commissioning Team.

Insurcol

Subcontractor to CB&I to provide all work and material


related to the Fire and Gas System in all phases of the
Revamp and new units. They will also be providing all work
associated with the process analyzers.

JSA

Job Safety Analysis

LC

Locked Closed

LEL

Lower Explosive Limit

LO

Locked Open

LOB

Local Operator Building

MAC

Main Automation Contractor (Invensys Foxboro).


Responsible to build, program and install the DCS system
for the project. The FAT, IFAT and SAT procedures will be
supplied and test with a team from Invensys.

MCC

Motor Control Center

MSDS

Material Safety Data Sheet

MUX

Mulitplexer

NEC

National Electric Code

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 5 of 12

NFPA

National Fire Protection Association

P&ID

Piping and Instrumentation Diagram

PCS

Process Control System

PDB

Process Design Basis

PHA

Process Hazard Analysis

PIP

Process Industry Practices

PLANT

The entire RCSA Cartagena Refinery Facilities

PLC

Programmable Logic Controller

PPE

Personal Protective Equipment

PSIG

Pounds per square inch gauge

PTW

Permit to Work

QA

Quality Assurance

RFC

Ready For Commissioning

RFSU

Ready For Start Up

RIE

Remote Instrument Enclosure

SAT

Site Acceptance Test provided by a Subcontractor or


Vendor during the performance of their Scope of Work and
reviewed by the Instrument and Control Commissioning
Team.

SIS

Safety Instrumented System

SPI

Smart Plant Instrumentation the instrument database.

Subcontractor

A contractor to CB&I that provides specific services and


work for a given piece/part of the Refinery Activities.

UPS

Uninterruptible Power Supply

Vendor

A company that is contracted to CB&I that provides specific


services and work for a given piece/part of the Refinery
Activities.

WinPCS

Windows Project Completion System

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 6 of 12

3.2

Definitions

The following definitions are used within this procedure:

Bench Calibration

Calibrating an instrument in the shop to applicable accuracy tolerance prior


to installation in the Field. Each device shall be checked against the data
sheet to verify compliance with all specified requirements and As Found
As Left data is recorded. All discrepancies shall be resolved before the
instrument or device is installed in the field.

Brownfield

Area(s)/system(s) of the facility that shall be considered Hot or


Operational (Start-Up is in progress, product is being introduced into
piping and vessels. Process is under pressure, transformers are
energized, and wiring is energized). All PPE requirements shall be utilized.

Field Calibration

Verifying the functionality of the primary instrument through to the logic


solver and back to a field device(s), if the loop is so equipped, during the
loop check process and As Found data collected.

Function Test

Verifying of the ability of the system to safely operate and control


equipment to a pre-determined state. It tests the logic (start up, shutdown,
emergency shutdown, etc) for any process unit or equipment. A
representative point for each function is tested.

Greenfield

Areas of the facility that are considered the period of the project that
transits from Breaking Ground phase to the Construction phase to the
Commissioning phase, where activities are in progress to change the
state of the various area(s)/systems to a Brownfield state, as described
above. Also, All PPE requirements shall be utilized.

Hysteresis

The difference between output measured at the cardinal points during


upscale measurements and the output measured at the cardinal points on
the subsequent downscale measurements.

Linearity

Loop Check
NBS/NIST
Optimum calibrated
accuracy

The difference between a straight line transmitter output (and transducer


response) at the cardinal points in the range and the actual readout
(response) with upscale measurements.
Verifies physical (hardwired) connections for all devices and software definition of
I/O points including verification of device states and direction
National Bureau of Standards / National Institute of Standards and
Terminology.
The calibration that will give the best accuracy in an instruments normal
operating range. Generally, this will be in the 20% to 80% of its calibrated
span. For differential pressure transmitters, optimum calibrated accuracy
should include final zero adjustments that may be required to compensate

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 7 of 12

for high static line pressures.


Traceability

The comparison of test instruments with National Bureau of Standards.

WINPCS B CHECKSHEETS

Obtain the appropriate B Checksheets required for this procedure. The check sheets will be printed from
WinPCS and completed by the appropriate discipline. When each check sheet is completed and signed
off, it must be returned to the WinPCS Administrator who will scan and record the completion of each
check sheet.

NOTES, CAUTIONS AND WARNINGS

This procedure uses the following symbols to draw the Technicians attention to steps in the procedure
that are particularly important or may lead to safety hazards if done incorrectly.
NOTE:
CAUTION:
WARNING:

6
6.1

General information useful to understand a particular step in the procedure.


A step that, if done incorrectly, could cause a safety hazard leading to personal
injury, equipment or environmental damage, or a delay in the start-up schedule.
A step that, if done incorrectly, could cause a serious safety hazard leading to
death, serious personal injury, major equipment damage, fire or a large
environmental release.

REFERENCE DOCUMENTATION
Documents and Drawings

The following table provides a list of reference documentation descriptions for this procedure that is part
of the Loop Folder. The document numbers are not listed to the large number of them.
Descriptions
Project Specification Procedures
System Descriptions
Instrument Data Sheets
System Delineated P&ID
Installation Detail Diagrams
Manufacturer Manuals and Specifications
Loop Sheets
Wiring Connection Diagram
Instrument Pre-commissioning / Commissioning 166000-000-GE-CM01-0005

Rev

The above documents shall be verified with Document Control to be the current revision at the time of
testing.

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 8 of 12

7
7.1

TEST EQUIPMENT AND GENERAL INFORMATION


Test Equipment

The following describes the requirements for test equipment associated with this procedure.
All test equipment used for qualitative data, shall have a standard Certificate of Accredited Calibration
on file with the Commissioning team. As a minimum, a standard certificate shows the following for the
equipment being tested and the equipment used to certify, with traceability back to NBS/NIST:
Manufacture
Model Number
Serial Number
Last Calibration Date
Calibration Due Date
As Found / As Left Calibration data
Any uncertainties, if applicable
Test Equipment Tag Number, if applicable
A calibration sticker shall be filled out and placed in a conspicuous location on the device, after
calibration. The calibration sticker is to be of the moisture and dirt resistant type.
For commissioning purposes, if the As Found data from the instrument is within spec, record the data in
the As Left space on the calibration check sheet. Typically, prior to the instrument being installed, each
instrument is Bench Cald and the As Found / As Left data is collected then. If there is a problem, it
will become known during the commissioning process.

7.2

General

The following discusses the Level Instruments associated with this procedure.
Level instruments not covered by this standard are to be selected and installed according to the
manufacturers recommendations and API RP-550 Part I, Section 2, Level (latest revision).
Block valves should normally be installed between the vessel and the level instrument except for
instruments that are inserted into the vessel or nozzle such as capacitance probes or extended
diaphragms. Top mounted instruments do not require block valves
Displacers are designed to measure liquid level, interface level, or density/specific gravity inside a vessel.
The torque tube assembly consists of a hollow torque tube with a shaft welded inside it at one end and
protruding from it at the other end.
The displacer always exerts a downward force on one end of the displacer rod. The other end of the
displacer rod rests on the knife-edge of the driver bearing. A change in liquid level, interface level, or
density/specific gravity buoys up the displacer by a force equal to the weight of the liquid displaced which
results in an angular movement of the displacer rod around the knife edge.

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 9 of 12

Level transmitters used for process interlocks or SIS systems inputs shall be connected to separate
vessel nozzles. SIS transmitters shall not share level bridles with each other or with control or alarm
transmitters due to common mode / common cause failures without approval from Reficar.
Transmitters are to be two-wire, loop powered producing a 4-20mA output. Transmitters are to be
"SMART" type. Transmitters shall be capable of digital communication with a hand held electronic
calibrator to allow for field re-ranging and calibration.
Transmitter self-diagnostics should be able to detect sensor burnout or transmitter failure and shall drive
the output to user selectable upscale (above 21mA) or downscale (below 3.9mA) points.

7.3

Field Calibration

Differences between bench and field calibrations, in excess of deviation table tolerances, indicates that
the instrument is suspect and shall be recalibrated or replaced. Following recalibration, the instrument
shall be exercised several times to insure repeatability.
Discrepancies in range or calibration between the field instrument and any loop devices shall be resolved
using the most recent instrument data sheet available. Discrepancies shall be referred to your lead
technician, who will pass it along to engineering for resolution.
All instrument components shall be calibrated as separate stand-alone devices.

Field calibration checks include at least a 5-point test at 0 %, 25 %, 50 %, 75 % and 100 %. If the device
has mechanical linkages that may produce hysteresis, the calibration will include a 9-point test ascending
and descending at the same cardinal points. Note: See Loop Check Sheet I29B.
Hook up of electronic components with calibration test instruments shall be made with high quality test
leads having the appropriate terminal connectors. Leads can be a source of failure in a test setup and
should be inspected and tested regularly to be sure they are in good condition.
For any questions that arise during the use of this procedure, contact your lead technician.

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 10 of 12

SPARE PARTS, CONSUMABLES

8.1

Spare Parts
The following table is the recommended list of the different types of devices to be available
during the calibration of this procedure.
Devices
Description

TBD

8.2

Item
1
2

Consumables
The following table is the recommended list of consumable items that should be available during
the calibration of this procedure.
Description
Quantity
Fuses
Teflon Tape

10
1

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 11 of 12

PROCEDURE

9.1
9.1.1
9.1.2
9.1.3

9.1.4
9.1.5
9.1.6
9.1.7
9.1.8
9.1.9

9.1.10
9.1.11
9.1.12
9.1.13
9.1.14
9.1.15
9.1.16

9.1.17
9.1.18
9.1.19
9.1.20
9.1.21
9.1.22

Displacer Level Transmitter


Verify that this is the correct instrument to be checked conforms to the data sheet.
Perform an inspection of the transmitter for missing insulation, broken flex-conduit or any
discrepancy that may affect proper operation of the device.
Process residue can build up in the bottom of the cage or at the connections which may restrict
flow in and out of the cage or interfere with displacer motion. Check the cage to insure cage is
clean and displacer moves freely.
Close any block valves to isolate level instrument. Relieve process pressure in the instrument
where the sensor is installed. Use caution when loosening flange bolting or pipe plug
Drain and if needed, fluids from the chamber. Use safe procedures for high pressures and
hazardous materials with proper PPE shall be followed.
Clean out any process residue if necessary.
The output shall be measured using a digital multimeter or a documenting calibrator of transfer
standard quality (Fluke 744).
Prior to the start of loop checking/calibration, ensure the wiring is complete and landed on the
correct terminals as indicated on the loop sheets, for the entire loop.
Notify the control board operator the loop is ready for checkout. Using the hart communicator or
laptop simulate the level for a 5-point calibration. Note: see loop check sheet I29B. At each
step have the board technician call out the DCS indication and record the as found data. Verify
the correct engineering units and range is configured in the DCS.
Install the loop fuse for the loop if required in the DCS cabinet per the loop sheet. Verify correct
voltage at the instrument.
Field calibration checks include at least a 5-point test at 0 %, 25 %, 50 %, 75 % and 100 %.
Note: see loop check sheet I29B.
Instrument calibration should be made with a laptop or hart communicator.
Check that the configuration in the transmitter conforms with the data sheet.
Simulate any level alarm points while the control room operator reports the DCS indication.
Disconnect the signal wire from the transmitter to simulate the signal loss while the operator
verifies the correct alarm received
If a problem is found the technicians will make a reasonable attempt to determine the cause and
make repairs in a reasonable amount of time. If the problem cannot be readily solved and will
require additional resources, remove power (pull the fuse,) and note the problem in the comments
section and notify your lead technician.
Reconnect wiring to the transmitter and verify with control room operator that the transmitter
indication is indicating correctly.
Inspect instrument connections, covers, fittings and all associated hardware also verify all
documents are filled in as required.
When calibration is complete, ensure the root valve(s) are open and place the instrument in a
Ready for Service condition.
Verify local reading conforms with reading on DCS.
Leave the device in the ready to run state unless directed differently.
For any questions that arise during the use of this procedure, contact your lead technician.

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Document No.:
166000-000-GE-CM08-0011

LIQUID LEVEL DISPLACER


DEVICES
PROCEDURE

Revision: 3
Date: 11-Apr-12
Page: 12 of 12

9.2

System Status

NOTE:

When this pre-commissioning procedure has been successfully completed, ensure the
following:
Required B checksheets have been completed, signed by an authorized Reficar
representative, and recorded into the WinPCS completions database.
Ready for Commissioning Certificate issued.

10 APPENDIX
The following appendix is included:
10.1 Appendix 1 Deviation Table
Maximum Deviation Table
Type
Fisher Transmitter

% of full-scale accuracy
0.065%

COMPLETION AUTHORIZED SIGNATURES


Commissioning Lead: ________________________________________ Date: ________
Commissioning Superintendent: ________________________________ Date: ________
RCSA Authority: ____________________________________________ Date: ________

THIS DOCUMENT IS THE PROPERTY OF CHICAGO BRIDGE & IRON COMPANY ("CB&I"). IT MAY CONTAIN INFORMATION
DESCRIBING TECHNOLOGY OWNED BY CB&I AND DEEMED TO BE COMMERCIALLY SENSITIVE. IT IS TO BE USED ONLY IN
CONNECTION WITH WORK PERFORMED BY CB&I. REPRODUCTION IN WHOLE OR IN PART FOR ANY PURPOSE OTHER
THAN WORK PERFORMED BY CB&I IS FORBIDDEN EXCEPT BY EXPRESS WRITTEN PERMISSION OF CB&I. IT IS TO BE
SAFEGUARDED AGAINST BOTH DELIBERATE AND INADVERTENT DISCLOSURE TO ANY THIRD PARTY.

Anda mungkin juga menyukai