The following table shows when different BIN Revs have been released and which are to be
used. The BIN files all have the same filename (4010.bin) so the dates below are the only
means of identification. On your laptop they are stored in different folders under C:\4010BIN
Note: Version mismatch may be caused by a bad filename.
Only use 8 characters (A-Z and 0-9) and the last character should be the Rev letter.
Compatibility Chart
4010 Programmer
741-107

4010 Bin
741-108

File date

1.01
1.02

1.01
1.02

1/23/98
2/4/99

2.01
2.01.02
2.02
2.03

2.01
2.02

4/5/99
8/30/00

2.03.03

2.02.05

6/29/01

3.01
3.02

3.01
3.02
3.02.05
3.02.06

5/15/02
8/16/02
11/22/02
1/20/03

3.03
3.03.01
3.03.02

3.03
3.03.01
3.03.04

4/7/03
4/23/03
6/11/04

4.01

4.01

1/9/06

NOTE:
An upload must be
performed with the
Revision with which
the job was
downloaded.

4010 SFIO chip 742-147


Any Rev of the SFIO chip will work with any Programmer and any BIN file, but the functions
depend on the Rev of the chip as shown in this chart.
Revision
2.01
2.03
2.03.02
2.05.05

3.01

3.02
3.02.01
4.01

Description
Added 4009A functionality
Added Short Search functionality
Delay reporting battery TBL for 2 seconds
Temporal code changed to insure all NACS begin together
Changed IDNet to inhibit inadvertent reporting excessive dirty from devices
Fixed SFIO chip rebooting itself with cards going missing failed (ferrite
beads also needed on IDNet field wiring)
Added the suppression release device to the software.
Changed 60 beats per minute to 20 beats per minute for SFIO NACs and
IDNet channel coding.
Changed commands to the 4009a so that the 4009a could support 20
beats per minute coding.
Output Abnormal trouble does not report after Suppression Release
Peripheral has turned ON (found in 3.01)
Software filtering added to eliminate false reporting of Channel Failure
th
UL864 9 Edition ECO
Suppression Release Peripheral now reports a supervisory condition when
disabled or disconnected
AC Failure report on city circuit will be delayed (default is 2 hours).

See SB99025.pdf for details of all 4010 problems and fixes.