Inspections: Daily
1. Read indications of dial thermometers (Oil and Winding Temperature). Compare them with the
data previously obtained. Also consider load current. Report major variances
Read indication of the dial oil level gauge on the conservator and level in oil filled bushings
Check oil leaks visually from radiators, flanges, pipes, and transformer tank.
Abnormal vibration can be checked comparatively easily by hand and listening to humming.
Check the breathing action in oil pot and discoloration (Blue to Pink) of silica gel visually. Also
check the color of oil in oil pot.
6. Check visually that all connections are normal with no discoloration due to local heating.
7. Check for water leaks from Rectifier Transformer Coolers and also whether the control valve is
opened. Check for blockage at the collection point(funnel) to the return sump
2.
3.
4.
5.
1. Dust -Clean the transformer as dust may reduce cooling capacity of radiators.
2. Oil Leaks -Check for oil leaks. If oil leaks are due to gasket, tighten bolts or exchange gasket. In
case of oil leaks from welded parts, apply adhesive material or weld again on the leaking part.
3. Abnormal noise and vibration- Tighten all loose bolts, change bearings on oil pump and fan
motor if applicable
4. Silica gel breather- Replace or regenerate the silica gel if it shows serious signs of discoloration.
Check that silica gel breathers are dry, well sealed, and not blocked.
5. Connections- Clean and check tightness of all bolts and fittings. Replace missing bolts. Check
visual signs of overheating. Check bonding and earthing of all non-current carrying metal
structures
6. Bushings- Clean all porcelain bushings and check for leaks and damage/cracks and replace if
necessary
7. Lightning Arresters- Check that all lightning arresters are correctly earthed
8. Gas trapped in Buchholz relay- If any gas is trapped in the relay, Dissolved/accumulated gas
analysis (DGA) should be conducted.
9. Oil Tests- Take oil samples for tests (BDV using 2.5mm gap) and gas analysis (DGA). If any
measured values are not satisfactory, filtration or replacement of insulating oil is recommended.
10. Oil level- Top up with clean oil if low. Check that all oil control valves are open
11. Appearance- Check general appearance of all equipment and paint work. Repaint if need be
1. Temperature Tests (Winding & Oil) - Check oil level in thermometer pockets. Heat
thermometer bulbs and record maximum temperature. Compare readings with that of a
standard thermometer. Also record temperature at which Alarm and Trip cuts in and
compare with the setting.
2. Buchholz Test - Use the push button to check the Buchholz relay operation. The Gas Kit
is only used when no push button is available. Restore Buchholz relay to normal state
after tests.
3. Insulation Resistance Test - Disconnect conductors from transformer bushings, open
transformer neutral links, and remove earths as required, and using Insulation tester(2.5
kV or above), Megger the transformer between windings and between windings and
earth. Also Megger the LV and HV surge arresters. Polarization Index should also be
recorded.
4. Winding Resistance Tests- Winding resistance tests to be carried out for the two or
three windings depending on the transformer design. Results should always be recorded
for future reference.
10minutes
PI
HV-MV
LV-MV
HV-Ground
LV-Ground
MV-Ground
NOTE
Polarization Index
Less than 1.0
1.0-1.1
1.1-1.25
1.25-2.0
Above 2.0
Insulation Condition
Dangerous
Poor
Questionable
Fair
Good
2.
Using the transformer protection schematic operate all relays ensuring that they initiate the
correct Annunciator and operate the master trip relay.
3.
Check that the master trip relay and direct contact trips from other relays operate the breakers as
indicated on the schematic.
4.
Check the operation of HV and LV breaker from local and remote control ensuring that with the
breaker selected to local, it does not operate from remote and when selected to remote it does
not operate electrically from local.
5.
BATTERY