Application Notes
(AP) 6-74
VK
VK
48 * ,n * (RCT + 2RL) for X/R < 40, 15,n < ,f < 40,n and 40 <X/R
< 120, ,f < 15,n
Where:
VK
,n
RCT
RL
,f
The high impedance restricted earth fault element shall maintain stability for through faults
and operate in less than 40ms for internal faults provided the following equations are met:
Rst
VK
,F (RCT + 2RL)
,s
4 * ,s * Rst
Where:
VK
Rst
,f
VK
,S
RCT
RL
Class x CTs should be used for high impedance restricted earth fault
applications.
"
Where American/IEEE standards are used to specify CTs, the C class voltage rating can be
checked to determine the equivalent Vk (knee point voltage according to IEC). The
equivalence formula is
VK