LOK 200:
Pole Mounted
Reliable Directional Fault Detection and
Classification
Remote Signalling and Monitoring
Time-Tagged Fault Data Logging
Indicative Line-Load Monitoring
Self-Powered by Solar and Battery
LOK SERVER
Alarms and maintenance related information
can be received and processed by Sipronika
LOK SERVER, and forwarded to several users.
The server consists of different application
modules, providing functionalities according
to the customers specific needs:
SCADA Gateway & SMS forwarding with
event database
Monitoring of LOK 200 devices for the
maintenance
Remote LOK Configuration and
firmware upload
Advanced graphical Event Diagnostics &
Analysis with 20 ms resolution
*For availability and ordering information please
contact Sipronika or your local representative
Sipronika, d.o.o., Traka c. 2, SI-1000 Ljubljana, Slovenia
www.sipronika.si, info@sipronika.si
LOK200-Tech-Info_eng_1-0.docx
SIPRONIKA LOK SERVER for flexible connectivity, monitoring, maintenance and event analysis
SCADA Gateway & SMS forwarding:
Protocols: IEC 60870-5-104, DNP 3.0, OPC UA for
easy integration into the existing SCADA
SMS forwarding on several user groups with alarm
filtering (i.e. fault related messages can be
transmitted to the different group than health-check
messages)
Event database for event and device function
analysis
Monitoring:
Data visualization by using a http connection to the
web server
Monitoring of all LOK 200 signals, alarms and
condition (GSM signal, battery condition,
communication status etc.)
Event database: all received events are stored in the
local database
Configuration:
Configuration files with all LOK 200 parameters are
stored in the server and can be automatically
transferred to the device
Firmware in LOK 200 devices can be upgraded by
remote upload
Local configuration by micro-switches and/or by a
laptop and LOK 200 Configuration software
LOK200-Tech-Info_eng_1-0.docx
Technical specification:
Range of application:
medium-voltage overhead
distribution network:
Earth-Fault detection:*
Fault discrimination:
Earth-fault current
detection sensitivity dI/dt:
Fault discrimination:
Phase-to-Phase absolute
current sensitivity:
Time delay before trip:
Time delays:*
Inrush restraint:
Fault indication: *
Indication duration:
Reset of indication:
Permanent / Transient
fault discrimination
Remote fault signalization:
Local:
Automatically:
Test results:
Battery lifetime:
4 ... 35 kV, 50 Hz *
Environment of operation:
Operation temperature
range:
Dimensions and weight:
Device:
Solar module:
MODEL SPECIFIC: **
transient / permanent
2 A to 150 A, adjustable in steps
of 1 A
40 ms ... 5 s, adjustable in steps
of 20 ms/1s
transient / permanent
100 A to 800 A, adjustable in
steps of 1 A
40 ms ... 5 s, adjustable in steps
of 20 ms/1s
Configuration:
Local (micro-switches and by
the software), remote (GPRS,
SMS, short range radio)
Transient method
Communication possibilities:
GSM/GPRS, SMS text, serial port, USB, ZigBee, Short range RF,
ZigBee.
DNP 3.0, IEC 60870-5-104 or
Communication protocols:
Modbus RTU slave **
Peripheral modules:
GSM/GPRS modem:
ZigBee module:
Digital Input/Output
module
RS-232 module:
RS-485 module:
Module for supply from
external DC source
Other:
Real-time clock:
Data logging:
Firmware upgradable:
*
**
***
Power supply:
LOK200-Tech-Info_eng_1-0.docx