Monitor Unit........................................................................................................................1-1
ECDIS Control Unit/Track Control Unit ..............................................................................1-1
Processor Unit ...................................................................................................................1-4
Sensor Adapter MC-3000S/3010A/3020D/3030D (option) ................................................1-6
Intelligent Hub HUB-3000 (option) .....................................................................................1-7
Switching HUB HUB-100 (option) ......................................................................................1-8
2. WIRING....................................................................................................................2-1
2.1
2.2
2.3
2.4
2.5
www.furuno.com
All brand and product names are trademarks, registered trademarks or service marks of their respective holders.
Printed in Japan
A : APR . 2012
B : NOV . 16, 2012
FMD-3200/3200BB/3300
*00017612911*
*00017612911*
* 0 0 0 1 7 6 1 2 9 1 1 *
SAFETY INSTRUCTIONS
The installer of the equipment must read the safety instructions before attempting to
install the equipment.
DANGER
WARNING
CAUTION
Warning, Caution
WARNING
Do not open the equipment
unless totally familiar with
electrical circuits and
service manual.
ELECTRICAL
SHOCK
HAZARD
Mandatory Action
Prohibitive Action
Turn off the power at the mains switchboard before beginning the installation.
Fire, electrical shock or serious injury can
result if the power is left on or is applied
while the equipment is being installed.
Be sure that the power supply is
compatible with the voltage rating of
the equipment.
Connection of an incorrect power supply
can cause fire or damage the equipment.
Use only the specified power cable.
Fire or damage to the equipment can result
if a different cable is used.
Do not install the monitor unit,
processor unit or control unit where
they may get wet from rain or
water splash, or in a dusty environment.
Water in the units can result in fire,
electrical shock, or damage the equipment.
WARNING
Attach protective earth
securely to the ship's body.
The protective earth
(grounding) is required for the
AC power supply to prevent
electrical shock.
CAUTION
Observe the following compass safe
distances to prevent deviation of a
magnetic compass:
Standard
compass
Steering
compass
2.40 m
1.55 m
1.65 m
1.05 m
2.55 m
1.55 m
0.30 m
0.30 m
0.30 m
0.30 m
Intelligent HUB
(HUB-3000)
1.20 m
0.75 m
Switching HUB
(HUB-100)
1.00 m
0.60 m
Sensor Adapter
(MC-3000S)
Sensor Adapter
(MC-3010A)
2.05 m
1.35 m
0.75 m
0.50 m
1.05 m
0.70 m
0.90 m
0.60 m
Processor
Unit (EC-3000)
Monitor Unit
(MU-190)
Monitor Unit
(MU-231)
ECDIS Control
Unit (RCU-024)
Trackball Control
Unit (RCU-026)
Sensor Adapter
(MC-3020D)
Sensor Adapter
(MC-3030D)
SYSTEM CONFIGURATIONS
System with one processor unit
Main Monitor
Sub Monitor
Monitor Unit*
MU-190
(FMD-3200)
or
MU-231
(FMD-3300)
Monitor Unit*
MU-190
(FMD-3200)
or
MU-231
(FMD-3300)
Conning
Monitor
Conning
Monitor*
MU-190/
MU-231
* Viewing distance
MU-190: 1020 mm
MU-231: 1020 mm
ECDIS
Control Unit
RCU-024
ECDIS
Control Unit
RCU-024
or
or
Trackball
Control Unit
RCU-026
(Max. 2)
ii
Switching
Hub
HUB-100
Trackball
Control Unit
RCU-026
(Max. 2)
EC-3000
PROCESSOR
UNIT
Intelligent
Hub
HUB-3000
100-115/
220-230 VAC,
1, 50/60 Hz
Sensor Adapter
MC-3000S
Serial interface
Sensor Adapter
MC-3010A
Analog interface
Sensor Adapter
MC-3020D
Digital IN interface
Sensor Adapter
MC-3030D
Category of units
All units protected
from the weather.
SYSTEM CONFIGURATIONS
ECDIS
Control Unit
RCU-024
ECDIS
Control Unit
RCU-024
or
or
Main Monitor
Sub Monitor
Monitor Unit*
MU-190
(FMD-3200)
or
MU-231
(FMD-3300)
Conning
Monitor
Conning
Monitor*
MU-190/
MU-231
Monitor Unit*
MU-190
(FMD-3200)
or
MU-231
(FMD-3300)
Sub Monitor
Conning
Monitor
Monitor Unit*
MU-190
(FMD-3200)
or
MU-231
(FMD-3300)
Conning
Monitor*
MU-190/
MU-231
ECDIS
Control Unit
RCU-024
or
Trackball
Control Unit
RCU-026
ECDIS
Control Unit
RCU-024
or
Trackball
Control Unit
RCU-026
(Max. 2)
Trackball
Control Unit
RCU-026
(Max. 2)
Trackball
Control Unit
RCU-026
(Max. 2)
Intelligent
Hub
HUB-3000
EC-3000
PROCESSOR
UNIT
EC-3000
Equipment in gateway
PROCESSOR
network
UNIT
(radar, ECDIS)
IF Signal:
- Serial Interface x2 (IEC 61162-1/2)
- Serial Interface x6 (IEC 61162-1)
- Digital Out x6
(power fail/system fail/ NO x2, NC x2)
- Digital In (ack in)
* Viewing distance
MU-190: 1020 mm
MU-231: 1020 mm
IF Signal:
(Same as left.)
100-115/
220-230 VAC,
1, 50/60 Hz
100-115/
220-230 VAC,
1, 50/60 Hz
Switching
Hub
HUB-100
Category of units
All units protected
from the weather.
Sensor Adapter
MC-3000S
Sensor Adapter
MC-3010A
Sensor Adapter
MC-3020D
Sensor Adapter
MC-3030D
Serial
interface
Analog
interface
Digital IN
interface
Digital OUT
interface
iii
EQUIPMENT LIST
Standard Supply
Name
Monitor Unit
Processor Unit
ECDIS Control Unit
Trackball Control Unit
Installation Materials
Accessories
Spare Parts
Type
MU-190
MU-231
EC-3000
RCU-024
RCU-026
CP24-02100
CP24-02201
CP24-02301
FP24-00601
FP24-00701
FP24-00801
SP24-00601
SP24-00602
Code No.
000-020-557
001-170-810
001-170-910
001-170-650
001-170-820
001-170-920
001-170-660
001-170-670
Qty
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
For FMD-3200
For FMD-3300
Console Type
Name
Display Unit
Type
ECN-303
ECN-304
Code No.
-
Qty
Remarks
1
w/FMD-3300
1
w/FMD-3200
Optional Supply
Name
Intelligent HUB
Sensor Adapter
Case Gasket
IPX2 Kit
Flush Mount
Connection Stand
(19)
Connection Stand
(23)
Trackball Control
Unit
ECDIS Control Unit
iv
Type
HUB-3000
MC-3000S
Code No.
-
Qty
1
MC-3010A
MC-3020D
MC-3030D
OP24-28
OP24-29
OP24-23
OP24-24
OP24-27
OP24-25
001-169-970
001-169-960
001-171-780
001-171-790
001-171-820
001-171-800
1
1
1
1
1
1
1
1
1
OP24-26
001-171-810
RCU-026
RCU-024
Remarks
Serial IN/OUT type, w/CP2402401 and SP24-00701
Analog IN, w/CP24-02501
Digital IN, w/CP24-02601
Digital OUT, w/CP24-02701
For MC-3000S
For MC-3010A/3020D/3030D
For EC-3000
For RCU-024
For RCU-026
For RCU-024, FMD-3200
For RCU-024, FMD-3300
EQUIPMENT LIST
Name
Installation Materials
Switching HUB
AC/DC Power Supply Unit
Dust Cover
Type
CP03-28900
CP03-28910
CP03-28920
HUB-100
PR-240
26-007-1201
26-007-2141
03-163-7271
Bracket Assembly
OP26-5
OP26-15
Hood Assembly
OP26-6
OP26-16
Flush Mount Kit
OP26-12
OP26-13
OP26-18
OP26-14
OP26-19
OP26-17
Connection Stand
OP26-20
Mounting Bracket
OP26-21
Monitor ReplaceOP26-22
ment Kit
OP26-23
OP26-26
OP26-27
Hood Assembly
OP26-24
OP26-25
Hand Grip Assembly FP03-09840
Control Unit ReOP24-31
placement Kit
Cable
DTI-C5E350
VCV L=10M
DTI-C5E350
VCV L=20M
DTI-C5E350
VCV L=30M
Terminal Opener
OP24-33
Connector
CP03-28901
Monitor Unit
MU-190
MU-231
Code No.
000-082-658
000-082-659
000-082-660
000-013-632
Qty
1
1
1
1
1
001-116-260-10
001-121-240-10
001-121-230-10
000-016-270
001-116-730
001-080-930
001-116-740
001-116-280
001-116-290
000-017-273
001-116-300
000-017-274
001-116-750
001-139-300
001-139-310
001-139-320
001-139-360
001-139-390
001-139-570
001-139-370
001-139-380
008-535-570
001-181-700
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
001-197-600-10
001-197-610-10
001-197-620-10
001-188-850
008-542-460
-
1
1
1
1
19-inch display
23-inch display
Remarks
LAN cable, 10 m
LAN cable, 20 m
LAN cable, 30 m
For MU-190
For MU-231
For console type
For MU-190, w/knobs
For MU-231
For MU-190
For MU-231
For MU-190
For two MU-190s
For two MU-231s
For three MU-190s
For three MU-231s
For MU-231
For MU-190
For MU-190
For MU-190, flush mounting
For MU-190, desktop mounting
For MU-190, hood
For MU-231, desktop mounting
For MU-190
For MU-231
For MU-201/231CR
For RCU-024
EQUIPMENT LIST
Name
Cable Assy.
Type
DSUB9P-X2L5M
DSUB9P-X2L10M
DSUB9P-X2L5M-WP
DSUB9P-X2L10M-WP
MC1.5-W-L600
MC1.5-WL1000
MC1.5-WL2000
MC1.5-WL3000
6TPSHXH12X2L5.0SP2
6TPSHXH12X2L10SP2
6TPSHXH12X2L20SP2
6TPSHXH12X2L30SP2
6TPSHXH12X2L5.0SP1
6TPSHXH12X2L10SP1
6TPSHXH12X2L20SP1
6TPSHXH12X2L30SP1
DVI-D/D SLINK 5M
DVI-D/D SLINK 10M
OP24-32
Operators Manual
Crimping Tool
vi
DVI-BNCX5L2000
OME-44730-*
OMJ-44730-*
CRIMPFOX10
S
Code No.
001-188-260
Qty
1
Remarks
For monitor unit, 5 m
001-188-270
000-177-053-10
000-177-247-10
001-187-470-10
001-187-480-10
001-187-490-10
001-187-500-10
001-186-310-10
For RCU-026, 5 m
001-186-320-10
For RCU-026, 10 m
001-186-330-10
For RCU-026, 20 m
001-186-340-10
For RCU-026, 30 m
001-186-260-10
For RCU-024, 5 m
001-186-270-10
For RCU-024, 10 m
001-186-280-10
For RCU-024, 20 m
001-186-290-10
For RCU-024, 30 m
001-132-960-10
001-133-980-10
1
1
001-188-300
000-177-046-10
000-176-125-**
000-176-124-**
001-206-920
1
1
1
English
Japanese
For ferrule
1.
MOUNTING
NOTICE
Do not apply paint, anti-corrosive sealant or contact
spray to coating or plastic parts of the equipment.
Those items contain organic solvents that can damage
coating and plastic parts, especially plastic connectors.
1.1
Monitor Unit
To mount the monitor unit, see the operators manual for MU-190/231.
Make sure that the ground wire is connected between the earth terminal on the chassis and the ships earth.
1.2
Mounting considerations
When you select a mounting location, keep in mind the following points:
Select a location where the control unit can be operated conventionally.
Locate the unit away from heat sources because of heat that can build up inside the
cabinet.
Locate the equipment away from places subject to water splash and rain.
Leave sufficient space at the sides and rear of the unit to facilitate maintenance.
Determine the mounting location considering the length of the signal cable between
the control unit and the processor unit.
A magnetic compass will be affected if the control unit is placed too close to the
magnetic compass. Observe the compass safe distances on page i to prevent compass malfunction.
Make sure that the ground
wire is connected between the
earth terminal on the chassis
and the ships earth.
Fasten the USB cable with the
cable tie (supplied) to the cable routing peg.
1-1
1. MOUNTING
1.2.1
Desktop Mounting
Fixing with KB fixing metal
1. Fix the KB fixing metal to the bottom of the control unit.
2. Fix the unit with self-tapping screws (5x20, local supply).
KB fixing metal
RCU-026
RCU-024
Side view of control units
1-2
1. MOUNTING
Flush mounting
Use the optional flush mount kit to mount the control unit in a console panel.
Flush mount kits for RCU-024/025
Control Unit
RCU-024
RCU-026
Type
OP24-24
OP24-27
Code No.
001-171-790
001-171-820
Outline of unit
1702
RCU-024
120
180
3882
1102
180
1702
1.2.2
RCU-026
RCU-024
RCU-026
Side view of control units
1-3
1. MOUNTING
1.3
Processor Unit
1.3.1
Mounting considerations
When you select a mounting location, keep in mind the following points:
Locate the processor unit away from heat sources because of heat that can build
up inside the cabinet.
The vibration at the mounting location should be minimum.
Locate the equipment away from places subject to water splash and rain.
Make the service clearance of 100 mm in front of the vent hole (left side).
Leave sufficient space at the sides and rear of the unit to facilitate maintenance.
Make sure that the ground wire is connected between the earth terminal on the
chassis and the ships earth.
A magnetic compass will be affected if the processor unit is placed too close to the
magnetic compass. Observe the compass safe distances on page ii to prevent compass malfunction.
Do not remove the dummy plate to prevent the wrong operation of the power switch.
The items behind the plate are for use by the serviceman.
Mount the processor unit on the floor, or on a bulkhead with the following direction
(horizontal), because of the DVD drive unit.
UP
OK
1-4
1. MOUNTING
1.3.2
Notches
Notches
Chassis base 2
2. Use six bolts (M6, local supply) to fix the processor unit.
1-5
1. MOUNTING
1.4
MC-3000S
1-6
MC-3010A/3020D/3030D
1. MOUNTING
1.5
Mounting considerations
When you select a mounting location, keep in mind the following points:
Locate the adapter away from heat sources because of heat that can build up inside
the cabinet.
The vibration should be minimal.
Locate the equipment away from places subject to water splash and rain.
Make sure that the ground wire is connected between the earth terminal on chassis
and the ships earth.
Leave sufficient space at the sides and rear of the unit to facilitate maintenance.
A magnetic compass will be affected if the adapter is placed too close to the magnetic compass. Observe the compass safe distances at the front of this manual to
prevent interference to a magnetic compass.
: Screw holes
1-7
1. MOUNTING
1.6
Mounting considerations
When you select a mounting location, keep in mind the following points:
Locate the adapter away from heat sources because of heat that can build up inside
the cabinet.
The vibration should be minimal.
Locate the equipment away from places subject to water splash and rain.
Make sure that the ground wire is connected between the earth terminal on chassis
and the ships earth.
Leave sufficient space at the sides and rear of the unit to facilitate maintenance.
A magnetic compass will be affected if the adapter is placed too close to the magnetic compass. Observe the compass safe distances at the front of this manual to
prevent compass malfunctions.
1-8
2.
WIRING
The illustration on this page shows the general connection between FMD-3200/3300
and external equipment. For detailed information, see the interconnection diagram.
Many of the cables mentioned are JIS (Japan Industry Standard) cables. If not available locally, use the equivalent. See the cable guide in the Appendix for how to select
equivalent cables. For wiring information for the monitor unit MU-190/231, see the applicable operators manual.
Monitor Unit
MU-190
(FMD-3200)
MU-231
(FMD-3300)
Max. three monitor
unit can be connected.
100-230 VAC
DSUB9P-X2-L5M cable,
5 m/10 m
6TPSH-XH12S2-LxxSP1/2 cable
(5 m, option: 10/20/30 m)
Control Unit
RCU-024 or RCU-26
TTYCS-4 or
TTYCSLA-4
TS-20-071-1 cable
6TPSH-XH12X2-LxxSP1/2 cable
(5 m, option: 10/20/30 m)
Control Unit
RCU-024 or RCU-026
(Max. 2)
ALARM SYSTEM
100-230 VAC
TTYCS-1Q or
TTYCSLA-1Q
TTYCS-1Q or
TTYCSLA-1Q
TS-20-071-1 cable
DPYC-1.5
DPYC-1.5
Intelligent HUB
HUB-3000
DTI-C5E350 VCV,
10/20/30 m
Processor Unit
EC-3000
TTYCS-1Q or
TTYCSLA-1Q
AIS
GYRO
GPS
LOG
ECHO
SOUNDER
TTYCS-1Q or
TTYCSLA-1Q ANEMOMETER
TTYCS-1Q or
TTYCSLA-1Q
ALARM
Sensor
Adapter
100-230 VAC
Switching HUB
HUB-100
TTYCS-1Q or
TTYCSLA-1Q
FR-FTPC-CY,
10/20/30 m
TTYCS-10 or
TTYCSLA-10
or
Sensor Adapter
MC-3000S (Serial IN/OUT)
AC-DC Power
Supply Unit
PR-240
100-230 VAC
24 VDC
MC1.5-W-L cable,
0.6/1/2/3 m
Sensor Adapter
-MC-3010A (ANALOG)
-MC-3020D (Digital IN)
-MC-3030D (Digital OUT)
NAVTEX
ALARM
SYSTEM
IEC60320-C13-L5M, 5 m
100-115/
220-230 VAC
2-1
2. WIRING
Notice on wiring
Use the optional USB cable (type: OP24-32) to connect to USB port on the control
unit.
The length of the USB cable should be within 5 m to prevent equipment trouble.
The length of LAN cables should be within 50 m.
Use the CAT5E or CAT6 LAN cables for the network if available locally.
If LAN cables are not available locally, use the optional LAN cables (FR-FTPC-CY
for sensor network, DTI-C5E350 VCV for gateway network).
If extension or division of the DVI or ERGB cables is necessary, use the dividers
shown below.
DVI cable divider: DVI-12A (maker: INAGICS)
RGB divider: CIF-12H, DD-106 or WBD-14F (maker: INAGENICS)
Make sure that the ground wires are connected between the ground terminals on
each equipment and the ships earth.
If a UPS (user supply) is connected to this equipment, be sure that the grounding
lamp does not light.
2.1
Processor Unit
2.1.1
2-2
2. WIRING
COM2
DVI3
Cable clamp
(See the next page.)
MU-190/231
(DVI3: DVI-D/D S-LINK cable
or DVI-BNCX5-L2000 cable,
COM2: DSUB9P-X2-L cable)
DVI2 MU-190/231
LAN1
HUB-3000
(DTI-C5E350 VCV
cable)
Power cable
(IEC60320-C13L5M cable)
(DVI2: DVI-D/D
S-LINK cable
or DVI-BNCX5L2000 cable)
LAN2
Ground wire
(IV-2sq.,
local supply)
USB1
HUB-100/MC-3000S
(FR-FTPC-CY cable,
within 50m)
LAN3
RCU-024/026
(TS-20-071-1 cable)
Not used.
USB4
USB2/3
COM1
DVI1
MU-190/231
(DVI1: DVI-D/D S-LINK cable,
COM1: DSUB9P-X2-L cable)
2-3
2. WIRING
250
30
2
25mm
approx. 9mm
Remove the outer sheath by
approx 25 mm. Be careful
not to damage inner shield
and cores.
approx. 11mm
approx. 9mm
Drain wire
[Cross cable]
1 WHT/GRN
2 GRN
3 WHT/ORG
4 BLU
5 WHT/BLE
6 ORG
7 WHT/BRN
8 BRN
2-4
WHT/ORG 1
ORG 2
WHT/GRN 3
BLU 4
WHT/BLE 5
GRN 6
WHT/BRN 7
BRN 8
[Straight cable]
1 WHT/ORG
2 ORG
3 WHT/GRN
4 BLU
5 WHT/BLE
6 GRN
7 WHT/BRN
8 BRN
WHT/ORG 1
ORG 2
WHT/GRN 3
BLU 4
WHT/BLE 5
GRN 6
WHT/BRN 7
BRN 8
2. WIRING
IPX2 kit
The optional IPX2 kit (Type: OP24-23, Code No.: 001-171-780) protects the connectors shown below to waterproofing standard IPX2.
Contents of IPX2 kit
Name
Binding Screw
Connector Gasket 1
Connector Gasket 2
Rainproof Cover
Gasket Clamping Plate
Type
#4-40UNCX3/16
24-014-0107
24-014-0108
24-014-0109
24-014-0114
24-014-0115
Code No.
000-176-619-10
100-367-730-10
100-367-741-10
100-372-202-10
100-372-210-10
100-372-220-10
Qty
10
2
3
1
2
3
Remarks
For D-sub connectors
For DVI connectors
For D-sub connectors
For DVI connectors
Connector gasket
3. Peel the paper from the double-sided tape on the rainproof cover, then attach the
cover to the position shown below by using four screws preattached to the processor unit.
Processor unit
2-5
2. WIRING
2.1.2
Shield
30
5
Vinyl tape
Cable tie
(supplied)
Length of L
TTYCS-10, TTYCSLA-10
380
400
30
100
Drain wire
L
5
Vinyl tape
Cable tie
(supplied)
Crimp-on lugs
for drain wires
Wiring for WAGO connector
Press downward.
Terminal opener
Wire
Twist
WAGO connector
Procedures
1. Twist the conductor.
2. Press the terminal opener downward.
3. Insert the wire to hole.
4. Remove the terminal opener.
5. Pull the wire to confirm that it is ecure.
2-6
2. WIRING
Connection
1. Unfasten four screws (M4x8) to remove the top cover from the processor unit.
2. Unfasten three bolts shown below to remove the upper plate of the cable clamp.
J5 J8 J3 J12
J11 J6 J9 J4
J14
J7 J10 J13
Clamp holes
(upper)
Loosen this bolt to use
the lower clamp holes.
Clamp holes
(lower)
2-7
2. WIRING
4. Connect the WAGO connectors appropriately to the I/O Board, referring to the interconnection diagram.
5. Bind the cables to the fixing metal in the processor unit with the cable ties (supplied).
Fixing metal
Screws for drain wires
of TTYCSLA cables
(Pass the drain wires through
the shrink tubes (local supply),
then attach these crimp-on lugs
to the drain wire.)
6. For TTYCSLA series cables, pass the drain wire into the shrink tube (local supply), then fasten crimp-on lugs at the end of drain wires to screws shown above.
2-8
2. WIRING
2.1.3
J3
JP2
J4
J11
1-2
2-3
1-2
2-3
Jumper block J1
SHORT
OPEN
OPEN
SHORT
1-2
2-3
1-2
2-3
Jumper block J2
SHORT
OPEN
OPEN
SHORT
Connector J3
Termination resistor: ON (default setting)
Termination connector: OFF
Connector J4
Termination resistor: ON (default setting)
Termination connector: OFF
2-9
2. WIRING
TD1-A
Out
TD1-B
Out
RD1-A
In
RD1-B
In
5
6
ISOGND1
RD1-H
In
RD1-C
In
Signal
In/Out
Description
Serial CH1, output
IEC61162-1/2
Serial CH1, output
IEC61162-1/2
Serial CH1, input
IEC61162-2
Serial CH1, input
IEC61162-2
Isolation GND (CH1)
Serial CH1, input
IEC61162-1
Serial CH1, input
IEC61162-1
IEC61162-2
TTYCS(LA)-4
IEC61162-1
TTYCS(LA)-4
No connection
No connection
TTYCS(LA)-4
Connector J4
Pin
#
1
TD2-A
Out
TD2-B
Out
RD2-A
In
RD2-B
In
5
6
ISOGND2
RD2-H
In
RD2-C
In
Signal
In/Out
Description
Serial CH2, output
IEC61162-1/2
Serial CH2, output
IEC61162-1/2
Serial CH2, input
IEC61162-2
Serial CH2, input
IEC61162-2
Isolation GND (CH2)
Serial CH2, input
IEC61162-1
Serial CH2, input
IEC61162-1
IEC61162-2
TTYCS(LA)-4
IEC61162-1
TTYCS(LA)-4
No connection
No connection
TTYCS(LA)-4
Connector J5
Pin#
1
2
3
4
5
2-10
Signal
TD3-A
TD3-B
RD3-H
RD3-C
GND
In/Out
Out
Out
In
In
-
Description
Serial CH3, output IEC61162-1
Serial CH3, output IEC61162-1
Serial CH3, input IEC61162-1
Serial CH3, input IEC61162-1
GND
Remarks
Use TTYCS(LA)-1Q,
IREC61162-1 only
2. WIRING
Connector J6
Pin#
1
2
3
4
5
Signal
TD4-A
TD4-B
RD4-H
RD4-C
GND
In/Out
Out
Out
In
In
-
Description
Serial CH4, output IEC61162-1
Serial CH4, output IEC61162-1
Serial CH4, input IEC61162-1
Serial CH4, input IEC61162-1
GND
Remarks
Use TTYCS(LA)-1Q,
IREC61162-1 only
Connector J7
Pin#
1
2
3
4
5
Signal
TD5-A
TD5-B
RD5-H
RD5-C
GND
In/Out
Out
Out
In
In
-
Description
Serial CH5, output IEC61162-1
Serial CH5, output IEC61162-1
Serial CH5, input IEC61162-1
Serial CH5, input IEC61162-1
GND
Remarks
Use TTYCS(LA)-1Q,
IREC61162-1 only
Connector J8
Pin#
1
2
3
4
5
Signal
TD6-A
TD6-B
RD6-H
RD6-C
GND
In/Out
Out
Out
In
In
-
Description
Serial CH6, output IEC61162-1
Serial CH6, output IEC61162-1
Serial CH6, input IEC61162-1
Serial CH6, input IEC61162-1
GND
Remarks
Use TTYCS(LA)-1Q,
IREC61162-1 only
Connector J9
Pin#
1
2
3
4
5
Signal
TD7-A
TD7-B
RD7-H
RD7-C
GND
In/Out
Out
Out
In
In
-
Description
Serial CH7, output IEC61162-1
Serial CH7, output IEC61162-1
Serial CH7, input IEC61162-1
Serial CH7, input IEC61162-1
GND
Remarks
Use TTYCS(LA)-1Q,
IREC61162-1 only
Connector J10
Pin#
1
2
3
4
5
Signal
TD8-A
TD8-B
RD8-H
RD8-C
GND
In/Out
Out
Out
In
In
-
Description
Serial CH8, output IEC61162-1
Serial CH8, output IEC61162-1
Serial CH8, input IEC61162-1
Serial CH8, input IEC61162-1
GND
Remarks
Use TTYCS(LA)-1Q,
IREC61162-1 only
2-11
2. WIRING
12V
Use NH connector
and AWG24 wire.
Contact input
470/ 0.5W
Register
DC12V_OUT
DIGI_INx
DIGI_RTNx
GND(DC12V)
2.2k / 1W
to MC-DIN
circuit
GND
Photocoupler circuit
GND
12V
470/ 0.5W
DC voltage input
(21.6V to 31.2V)
Register
DC12V_OUT
DIGI_INx
DIGI_RTNx
GND(DC12V)
+
-
2.2k / 1W
GND
Photocoupler circuit
to MC-DIN
circuit
GND
Connector J11
Pin
#
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Signal name
In/Out
SYS_FAIL-A
SYS_FAIL-B
PWR_FAIL-A
PWR_FAIL-B
NC1-A
NC1-B
NC2-A
NC2-B
NO1-A
NO1-B
NO2-A
NO2-B
DC12V_OUT
DIGI_IN1
DIGI_RTN1
GND (DC12V)
GND
Out
Out
Out
Out
Out
Out
Out
Out
Out
Out
Out
Out
Out
In
Out
In
-
Description
System fail output
System fail output
Power fail output
Power fail output
Alarm output (NC1)
Alarm output (NC1)
Alarm output (NC2)
Alarm output (NC2)
Alarm output (NO1)
Alarm output (NO1)
Alarm output (NO2)
Alarm output (NO2)
ACK input
ACK input
ACK input
ACK input
GND
Contact input
TTYCS(LA)-10
TTYCS(LA)-10
#13-#14: short
No connection
TTYCS(LA)-10
TTYCS(LA)-10
No connection
NO connection
2-12
Voltage input
2. WIRING
2.2
Monitor Unit
For the wiring of the monitor unit MU-190/231, see the operators manual supplied with
the monitor unit.
Mounting consideration
(Standard type)
Connect the ECDIS main monitor to the DVI1 and COM1 ports.
For the sub ECDIS monitor, connect it to the DVI2 and COM2 port.
(Conning type)
ECDIS main monitor: DVI1 and COM1 ports, conning monitor: DVI3 port and COM2
ports
When an ECDIS sub monitor is added to the above connection, connect it to the
DVI2 port (the brilliance adjustment is not available).
(VDR connection, ask your dealer)
To connect a VDR, it is necessary to output data in analog format. See the installation
manuals for VDR to prepare the cables (BNCX5-DSUB15-Lxxx and 1.5C2V-3C2V-T)
to use.
When connecting a VDR to the DVI3 port::
Use the optional DVI-BNCX5-L2000 cable to output RGB signal from the DVI-I. Adjustment of the output picture is necessary.
When connecting a VDR to the DVI2 port:
Use a DVI/RGB converter (maker: IMAGENICS, type: DVI-12A, local supply) to
convert DVI output from DVI2 port to RGB.
The [INSTALLATION SETTING] menu appears only when the power is turned on for
the first time after installation of the monitor unit.
Menu
INSTALLATION SETTING
EXT BRILL CTRL
RS-485
SERIAL BAUDRATE 4800bps
COLOR CALIBRATION
ON
KEY LOCK
ON
(OFF/DVI1/DVI2/RS-232C/RS-485/USB)
(4800/9600/19200/38400)
(OFF/ON)
(OFF/ON)
(NO/YES)
YES
Menu item
SERIAL
BAIDRATE
4800bps
COLOR
CALIBRATION
ON
KEY LOCK
ON
DVI PWR
SYNC*
YES
*: [DVI PWR SYNC] is the slide switch at the bottom rear of the monitor unit. Confirm
that this switch is set to [ON] (default setting). See Slide switch below for details.
2-13
2. WIRING
Slide switch
Set the slide switch to ON (default setting). This setting automatically powers the
monitor unit on or off according to the DVI signal input. The power switch of the monitor unit is inoperative.
Note: The OFF position provides control of the monitor unit power with the power
switch of the monitor unit.
2-14
2. WIRING
2.3
Cable color
Red
Black
White
Blue
Gray
Signal
24V_OUT or 24V_IN
24V_GND
MODBUS-A
MODBUS-B
GND
Use the ferrule-type terminals (supplied) to connect the cables to the terminals in the
sensor adapters. This connection requires a crimping tool (CRIMPFOX10S, option).
Note 1: Use the MC1.5-W cable between the sensor adapters.
Note 2: The total length of the MC1.5-W cables should be less than 6 m to prevent
malfunction.
How to attach the rod terminal (ferrule type)
Vinyl sheath
6mm
Core
0.5 to 1 mm
2-15
2. WIRING
2.3.1
MC-3000S
Use the LAN cable FR-FTPC-CY cable to connect the MC-3000S and the processor
unit. With HUB-100, a maximum of eight MC-3000S can be connected.
Fabrications
TTYCS-1Q cable
(J8)
#1 to 4: 110
#5 to 8: 95
See section 2.1.2. for
the fabrication.
50
30
80 or
more
30
Vinyl tape
(width: 10)
MC1.5-W-L600/1000/2000/3000 cable
(J9)
#1 to 4: 100
#5 to 8: 90
Core: 6
TTYCSLA-1Q cable
(J8)
#1 to 4: 110
#5 to 8: 95
Shield
(fold back)
Vinyl tape
10
20
2-16
100
Core: 6
80 or
more
Vinyl tape
(width: 10)
(J9)
#1 to 4: 100
#5 to 8: 90
Core: 6
60 mm:
Pass drain wire through
vinyl sheath (local supply),
then attach crimp-on lug
(pre-attached in unit).
2. WIRING
TTYCSLA-1 cable
TTYCS-1 cable
100
30
100
80
Core: 6
Core: 6
80
Vinyl tape
(width: 10)
Vinyl tape
(width: 10)
60
Pass drain wire through
vinyl sheath (local supply),
then attach crimp-on lug
(pre-attached in unit).
TTYCS-4 cable
TTYCSLA-4 cable
80 or
more
Core: 6
Vinyl tape
(width: 10)
20
Vinyl tape
(width: 10)
J4/J6: 100
J5/J7: 120
80 or
more
No use: 50
(Wind tape to insulate.)
J4/J6: 100
J5/J7: 120
60
Core: 6
No use: 50
(Wind tape to insulate.)
Pass drain wire through
shrink tube (local supply),
then attach crimp-on lug
(pre-attached in unit).
DPYC-1.5 cable
Vinyl tape
(width: 10)
Core: 6
80
(or more)
85
2-17
2. WIRING
Connections
Unfasten four screws to remove the cover, pass the cables through the clamps and
attach the cables to respective connectors. The shield part of the cable (or drain wire)
must be fastened by (connected to) the clamp.
For TTYCSLA cables, pass the drain
wire into the shrinking tube (local supply),
then use these crimp-on lugs and screws
to connect drain wires from TTYCSLA cables
to here.
J7
J5
J2 J1
J4
J8
J6
DPYC1.5
J9
TTYCS-4/
TTYCSLA-4
FR-FTPC-CY cable
IV-1.25sq. (Local supply)
TTYCS-1Q/
TTYCSLA-1Q
MC1.5-W-L cable
2-18
Signal name
24V_IN
24V_GND
PWR_FAIL_A
PWR_FAIL_COM
PWR_FAIL_B
In/Out
Out
Out
Out
Description
24 VDC
GND (24 VDC)
Power fail output
Power fail output
Power fail output
NO
DPYC-1.5
TTYCS(LA)-1
No connection
NC
No connection
TTYCS(LA)-1
2. WIRING
Signal
name
TD1-A
Out
TD1-B
Out
RD1-A
In
RD1-B
In
ISOGND1
RD1-H
In
RD1-C
In
In/Out
Description
IEC61162-2
IEC61162-1
Modbus*
TTYCS(LA)-4
TTYCS(LA)-4
TTYCS(LA)-4
No connection
No connection
No connection
TTYCS(LA)-4
Signal
name
TD2-A
Out
TD2-B
Out
RD2-A
In
RD2-B
In
ISOGND2
RD2-H
In
RD2-C
In
In/Out
Description
IEC61162-2
IEC61162-1
Modbus*
TTYCS(LA)-4
TTYCS(LA)-4
TTYCS(LA)-4
No connection
No connection
No connection
TTYCS(LA)-4
2-19
2. WIRING
Connector J6
Pin
#
1
2
3
4
5
6
7
Signal
name
TD3-A
TD3-B
RD3-A
RD3-B
ISOGND3
RD3-H
RD3-C
In/Out
Out
Out
In
In
In
In
Description
IEC61162-2
IEC61162-1
TTYCS(LA)-4
No connection
TTYCS(LA)-4
Connector J7
Pin
#
1
2
3
4
5
6
7
Signal
name
TD4-A
TD4-B
RD4-A
RD4-B
ISOGND4
RD4-H
RD4-C
In/Out
Out
Out
In
In
In
In
Description
IEC61162-2
IEC61162-1
TTYCS(LA)-4
No connection
TTYCS(LA)-4
Connector J8
Pin#
1
2
3
4
5
6
7
8
Signal
name
TD5-A
TD5-B
RD5-H
RD5-C
TD6-A
TD6-B
RD6-H
RD6-C
In/Out
Out
Out
In
In
Out
Out
In
In
Description
Serial CH5, output IEC61162-1
Serial CH5, output IEC61162-1
Serial CH5, input IEC61162-1
Serial CH5, input IEC61162-1
Serial CH6, output IEC61162-1
Serial CH6, output IEC61162-1
Serial CH6, input IEC61162-1
Serial CH6, input IEC61162-1
Used cable
TTYCS-1Q or TTYCSLA-1Q
Connector J9
Pin#
1
2
3
4
5
6
7
8
2-20
Signal
name
TD7-A
TD7-B
RD7-H
RD7-C
TD8-A
TD8-B
RD8-H
RD8-C
In/Out
Out
Out
In
In
Out
Out
In
In
Description
Serial CH7, output IEC61162-1
Serial CH7, output IEC61162-1
Serial CH7, input IEC61162-1
Serial CH7, input IEC61162-1
Serial CH8, output IEC61162-1
Serial CH8, output IEC61162-1
Serial CH8, input IEC61162-1
Serial CH8, input IEC61162-1
Used cable
TTYCS-1Q or TTYCSLA-1Q
2. WIRING
Type
21-014-2051
Code No.
Qty
Remarks
100-367-880-10 2
For MC-3000S
1. Unfasten four binding screws to remove the cover from the adapter.
Binding screw
Cover
2. Peel the paper from the case packing, then attach the case packing to the reverse
side of the cover and the body unit as shown below.
Case packing
Case packing
Case packing
Body unit
Case packing
2-21
2. WIRING
2.3.2
MC-3010A/3020D/3030D
MC-3010A: Inputs analog signal. To set MC-3010A to the current input, connect
short pins to each terminals.
MC-3020D: Inputs digital signal (8ch contact input). Contact or voltage input is selectable (contact input requires jumper pins).
MC-3030D: Outputs digital signal (8ch, normal open/close).
Fabrications
MC1.5-W-L600/1000/2000/3000 cable
(Input)
30
TTYCSLA-1 (MC-3010A)
80
120
60
Core: 6
Vinyl tape
(width: 10)
60
Pass drain wire through
shrink tube (local supply),
then attach crimp-on lug
(pre-attached in unit).
MC1.5-W-L600/1000/2000/3000 cable
(Output)
30
TTYCS-1 (MC-3010A)
80 or
more
100
Vinyl tape
(width: 10)
Core: 6
60
30
Shield
(fold back)
Core: 6
125
80 or
more
2-22
135
80 or
more
95
85
No use: 50
(Wind tape to insulate.)
Core: 6
No use: 50
(Wind tape to insulate.)
Core: 6
2. WIRING
Connection
J5
J3
J2
J1
MC1.5-W-L cable
J4
J2
J6
J3
J5
J1
MPYC-12
MC1.5-W-L cable
MC-3020D/3030D
2-23
2. WIRING
Power voltage: Input the amount of power voltage change to the operational amplifier.
AN +15V
+15V
+VS1
AN-IN
AN-GND
CURR-JP1
Voltage
source
Vin
+VS2
Opeamp
OutGnd
- VS2
InGnd
CURR-JP2
Jumper:
open
- VS1
GND
1k 1%0.5Wx2
Load
- 15V
AN GND AN - 15V
Power current: Pass the power current to the shunt resistor, 1k/parallel (combined
resistance: 500) to input the amount of voltage change at the both ends of the resistor to the operational amplifier.
AN +15V
+15V
+VS1
AN- IN
AN- GND
CURR- JP1
CURR- JP2
Current
source
Jumper
short
Vin
+VS2
Opeamp
OutGnd
- VS2
InGnd
- VS1
GND
1k 1%0.5Wx2
Load
Use the NH connector
and AWG24 wire.
- 15V
AN GND AN - 15V
Connector J3
Pin
#
1
2
3
AN1_IN
AN1_GND
CURR1_JP1
In
-
CURR1_JP2
Signal name
In/Out
Description
Power
voltage
TTYCS(LA)-1
Analog 1 input
Analog 1 GND
Analog 1 input, power current/ Pin #3-#4:
voltage setting jumper 1
open
Analog 2 input, power current/
voltage setting jumper 1
Power
current
Pin #3-#4:
short
Connector J4
Pin
#
1
2
3
AN2_IN
AN2_GND
CURR2_JP1
In
-
CURR2_JP2
2-24
Signal name
In/Out
Description
Power
voltage
TTYCS(LA)-1
Analog 2 input
Analog 2 GND
Analog 2 input, power current/ Pin #3-#4:
voltage setting jumper 1
open
Analog 2 input, power current/
voltage setting jumper 1
Power
current
Pin #3-#4:
short
2. WIRING
Connector J5
Pin
#
1
2
3
AN3_IN
AN3_GND
CURR3_JP1
In
-
CURR3_JP2
Signal name
In/Out
Description
Power
voltage
TTYCS(LA)-1
Analog 3 input
Analog 3 GND
Analog 3 input, power current/ Pin #3-#4:
voltage setting jumper 1
open
Analog 3 input, power current/
voltage setting jumper 1
Power
current
Pin #3-#4:
short
12V
470/ 0.5W
DC voltage input
(21.6V to 31.2V)
+
-
Register
DC12V_OUT
DIGI_IN1
DIGI_RTN1
GND(DC12V)
2.2k / 1W
to Processor unit
circuit
GND
Photocoupler circuit
GND
12V
470/ 0.5W
Use NH connector
and AWG24 wire.
Contact input
Register
DC12V_OUT
DIGI_IN1
DIGI_RTN1
GND(DC12V)
2.2k / 1W
GND
Photocoupler circuit
to Processor unit
circuit
GND
Note 1: The input must not exceed the range of the input voltage, to prevent malfunction.
-Setting for voltage input: 21.6V to 31.2V
-Setting for contact input: Voltage cannot be input (contact signal only).
Note 2: For analog input, see paragraph 2.3.2
2-25
2. WIRING
Connector J3
Pin
#
1
DC12V_OUT
Out
2
3
4
DIGI_IN1
DIGI_RTN1
GND (DC12V)
In
Out
In
DC12V_OUT
Out
6
7
DIGI_IN2
DIGI_RTN2
In
Out
GND (DC12V)
In
Signal name
In/Out
Remarks
ACK1 In
ACK1
contact
Pin #1-#2:
short
ACK
voltage
No connection
MPYC-12
MPYC-12
ACK2
contact
ACK2
voltage
Depending on ACK1
input
No connection
ACK2 In
Pin #1-#2:
short
Depending on ACK2 input
No connection
MPYC12
MPYC-12
NO connection
Connector J4
Pin #
Signal name
In/Out
1
2
DC12V_OUT
DIGI_IN3
Out
In
3
4
5
DIGI_RTN3
GND (DC12V)
DC12V_OUT
Out
In
Out
6
7
DIGI_IN4
DIGI_RTN4
In
Out
GND (DC12V)
In
Remarks
ACK3 In
ACK1
contact
Pin #1-#2:
short
ACK1 voltage
ACK2
contact
ACK2
voltage
No connection
MPYC-12
-
MPYC-12
No connection
ACK4 In
Pin #1-#2:
short
-
No connection
MPYC12
MPYC-12
No connection
Connector J5
Pin #
Signal name
In/Out
DC12V_OUT
Out
2
3
4
DIGI_IN5
DIGI_RTN5
GND (DC12V)
In
Out
In
DC12V_OUT
Out
DIGI_IN6
In
Remarks
ACK5 In
ACK1
contact
Pin #1-#2:
short
ACK
voltage
No connection
MPYC-12
ACK2
contact
MPYC-12
No connection
ACK6 In
Pin #1-#2:
short
-
7
8
2-26
DIGI_RTN6
GND (DC12V)
Out
In
ACK2
voltage
No connection
MPYC12
MPYC-12
NO connection
2. WIRING
Connector J6
Pin #
Signal name
In/Out
DC12V_OUT
Out
2
3
4
DIGI_IN1
DIGI_RTN1
GND (DC12V)
In
Out
In
DC12V_OUT
Out
DIGI_IN2
In
7
8
DIGI_RTN2
GND (DC12V)
Out
In
Remarks
ACK1 In
ACK1
contact
Pin #1-#2:
short
ACK
voltage
No connection
MPYC-12
ACK2
contact
ACK2
voltage
MPYC-12
No connection
ACK2 In
Pin #1-#2:
short
-
No connection
MPYC12
MPYC-12
NO connection
Signal
name
A1
COM1
B1
A2
COM2
B2
In/
Remarks
Out
Out Alarm1
Out
Alarm1 NO
Out
MPYC-12
Alarm1 NC
Out
No connection
MPYC-12
Alarm2 NO
Out
Alarm2 NC
Out
-
No connection
Alarm2
Out
MPYC-12
No connection
MPYC-12
No connection
Connector J4S
Pin
#
1
2
3
4
5
6
Signal
name
A3
COM3
B3
A4
COM4
B4
In/
Remarks
Out
Out Alarm3
Out
Alarm3 NO
Out
MPYC-12
Alarm3 NC
Out
No connection
MPYC-12
Alarm4 NO
Out
Alarm4 NC
Out
-
No connection
Alarm4
Out
MPYC-12
-
No connection
MPYC-12
No connection
2-27
2. WIRING
Connector J5
Pin
#
1
2
3
4
5
6
Signal
name
A5
COM5
B5
A6
COM6
B6
In/
Remarks
Out
Out Alarm5
Out
Alarm1 NO Out
MPYC-12
Alarm1 NC
Out
No connection
MPYC-12
Alarm2 NO
Out
Alarm2 NC
Out
-
No connection
Alarm5
Out
MPYC-12
No connection
MPYC-12
No connection
Connector J6
Pin
#
1
2
3
4
5
6
Signal
name
A7
COM7
B7
A8
COM8
B8
In/
Remarks
Out
Out Alarm7
Out
Alarm7 NO Out
MPYC-12
Alarm7 NC
Out
No connection
MPYC-12
Alarm8 NO
Out
Alarm8 NC
Out
-
No connection
Alarm8
Out
MPYC-12
-
No connection
MPYC-12
No connection
Type
21-014-2052-2
Code No.
100-367-961-10
Qty
Remarks
2
MC-3010A/3020D/3030D
1. Unfasten four binding screws to remove the cover from the adapter.
Cover
Binding screw
2-28
2. WIRING
2. Peel the paper from the case packing, then attach the case packing to the reverse
side of the cover and the body unit as shown below.
Case packing
Case packing
Cover (reverse side)
Case packing
Case packing
Chassis
2-29
2. WIRING
2.3.3
J22
J23
J15
J16
J17
S2
J19
J20
J21
Connector J1
Termination resistor: ON (default setting)
Termination resistor: OFF
Set the jumper blocks J14 through J17 to turn the termination resistors on connectors
J4 through J7 respectively.
2-30
2. WIRING
Connector J4 (CH1)
Termination resistor: ON (default setting)
Connector J5 (CH2)
Termination resistor: ON (default setting)
Set the jumper blocks J20 and J21 to choose the communication type (IEC-61162-1/
2 or MODBUS) of the connector J4 (CH1).
The setting of the jumper block JP20 and JP21 must be identical.
Jumper block J20/J21
1-2
2-3
1-2
2-3
OPEN
SHORT
SHORT
OPEN
Communication type of J4
(between RD1 and TD1)
IEC-61162-1/2 (default setting)
MODBUS (The setting of J14 is different depending on the
unit position (starting/ending terminal).)
The jumper blocks J22 and J23 are used to set the communication type of the connector J5 (CH2).
Jumper block J22/J23
1-2
2-3
1-2
2-3
OPEN
SHORT
SHORT
OPEN
Communication type of J5
(between RD2 and TD2)
IEC-61162-1/2 (default setting)
MODBUS (The setting of J14 is different depending
on the unit position (starting/ending terminal).)
2-31
2. WIRING
MC-3010A/3020D/3030D
This paragraph shows how to set the MC-ANLG Board (24P0115, for MC-3010A),
MC-DIN Board (24P0116, for MC-3020D) and MC-DOUT Board (24P0117, for MC3030D).
Rotary switch: Use the rotary switch (U18) to set the MODBUS address with a digit
of number from 0. When multiple sensor adapters are connected to the MC-3000S,
the same number cannot be used among them. (It is allowed to use the same number
between the MC-3000S and a sensor adapter.)
J25
J3
J4
U18
J5
MC-ANLG Board (24P0115)
J25
J25
U18
U18
Jumper block
Use the jumper block J25 to set the termination resistor on/off for the MODBUS communication on the connector J1. For the first and last sensor adapter in a series, their
termination resistors should be set to ON. If not, communication between sensor
adapters is not possible.
Jumper block J25
1-2
OPEN
2-3
SHORT
1-2
SHORT
2-3
OPEN
2-32
Connector J1
Termination resistor: ON (default setting)
Termination resistor: OFF
2. WIRING
2.4
Power port
DPYC-1.5 cable
Ground wire
(IV-1.25sq., supplied)
LAN cable
LAN port
No use.
to INS network (ECDIS, radar, etc.)
Attach the LAN cap (supplied) to the unused connector
holes to provide waterproofing standard IPX2.
Cable clamp
2-33
2. WIRING
2.5
2.5.1
2. Unfasten two pan head screws (M3x12) to remove the clamp and cable clamp
from the control unit, then disconnect the control unit cable from the J1 connector.
J1 connector
Clamp
Cable clamp
2-34
2. WIRING
8. Unfasten three bolts to remove the cable clamp (upper) as shown below.
J5 J8 J3
J11 J6 J9 J4
J7 J10
J12
J14
J13
Clamp holes
(upper)
Loosen this bolt to use
the lower clamp holes.
Clamp holes
(lower)
9. Disconnect the control unit cable from the processor unit, then connect the cable
assy (6TPSH-XH12X2-LxxSP1).
10. Set the shield part of cables under the cable clamp then tighten the cable clamp.
2-35
2. WIRING
2.5.2
2. Remove the cable clamp from the control unit, then disconnect the control unit cable from the J1 connector.
Binding screw
Cable clamp
J1 connector
2-36
2. WIRING
5. Fasten the shield part of the cable assy with the cable clamp (removed at step 2),
then connect the connector at the end of the cable assy to the J1 on the control
unit board.
Note: When clamping, the shield part of the cable must not touch the circuit board.
Shield part
Cable assy
Cable clamp
Board
J5 J8 J3
J11 J6 J9 J4
J7 J10
J12
J14
J13
Clamp holes
(upper)
Loosen this bolt to use
the lower clamp holes.
Clamp holes
(lower)
9. Disconnect the control unit cable from the processor unit, then connect the cable
assy (6TPSH-XH12X2-LxxSP2).
2-37
2. WIRING
10. Set the shields of cables under the cable clamp then tighten the cable clamp.
2-38
3.
ECN-303/304 (OPTION)
This section provides the information necessary for installing the display unit console
ECN-303/304.
Processor unit
3.1
Screws (M6x25)
Front cover
4. Fix the console to the channel base with six hexagon head bolts (M12, local supply).
5. Remove the four eye bolts. Cover the four holes for the eye bolts with the caps
supplied.
3-1
3. ECN-303/304 (OPTION)
3.2
Power switch
2. Unfasten two hex. bolts (M6) to pull the rack for the processor unit toward you until
you hear a click.
The rack comes to a stop against the stoppers on the right and left rails.
Hex. bolt
(M6x12, left and right)
3-2
3. ECN-303/304 (OPTION)
3. Release all cables other than the power cable from their cable clamps.
There are six cable clamps on the rack as shown below.
4. Press the stoppers with your fingers to unlock them to release the rack, then pull
out the rack slowly.
Note 1: When dismounting the processor unit from the console, be careful not to
apply tension on the cables.
Note 2: The processor unit weighs 20 kg. Hold the rack securely so that it will not
drop to the deck.
3-3
3. ECN-303/304 (OPTION)
3.3
TTYCS-1Q/TTYCSLA-1Q
(3 pcs.)
TTYCS-4/TTYCSLA-4
(2 pcs.)
TTYCS-1Q/TTYCS-1Q
TTYCS-10/
(3 pcs.)
TTYCSLA-10
Note 1: The illustration below shows where to locate cables on the cable clamp. The
location for the TTYCS-4/TTYCSLA-4 cables can alternately accommodate TTYC1Q/TTYCSLA-1Q cables. In this case, unfasten two hex. bolts to remove the clamp
plate and fasten it behind the clamp base.
Spacers
Note 2: For TTYCSLA cables, attach their drain wires to the crimp-on lugs pre-fastened near the terminal board.
Use these crimp-on lugs.
3-4
3. ECN-303/304 (OPTION)
Armor
Shield
100
100 or more
30
Vinyl tape
6
Clamp here by cable clamp.
70
Sheath
100 or more
Drain wire
100
5
Pass the drain wire through the shrink tube
(local supply), then attach the crimp-on lug
supplied in the console.
Vinyl tape
6
Clamp here by cable clamp.
WAGO driver
Wire
WAGO driver
Twist
WAGO
connector
Procedure
1. Twist the conductor.
2. Press the terminal opener downward.
3. Insert the wire to hole.
4. Remove the terminal opener.
5. Pull the wire to confirm that is ecure.
Terminal board
(at the bottom of the console)
Connectors J3/J4 on the I/O Board in the processor unit can be set to IEC61162-1
or 2. This console is shiped with the setting for IRC61162-2.
The connector J11 on the I/O Board in the processor unit can be set to the contact
input or digital input. This console is shipped with the setting for the contact input.
3-5
3. ECN-303/304 (OPTION)
3.4
Stopper
If you could not put the rack on the rails immediately, you can rest the rack on the
spacers shown below.
Spacers
3. Fasten the cables from the processor unit with clamps at the left and right hand
sides of the rack at the position of the red-colored marks on the cables.
Clamp
Rack (left)
3-6
Clamp
Marks (red)
Rack (right)
3. ECN-303/304 (OPTION)
4. Press the stoppers with your fingers to unlock them to release the rack, then push
the rack into the console.
5. Fasten two hex. bolts (M6, removed at step 2 in section 3.2.) to fix the rack to the
console.
6. Fasten the cables from the processor unit with four clamps at the front of the rack.
(behind
the chassis)
7. Use the clamp (see step 1 in section 3.2) to refasten the power cable.
3-7
3. ECN-303/304 (OPTION)
3-8
1. Core Type
2. Insulation Type
D Double core power line P Ethylene Propylene Rubber
T Triple core power line
M Multi core
TT Twisted pair communications (1Q=quad cable)
3. Sheath Type
Y PVC (Vinyl)
4. Armor Type
C Steel
6. Shielding Type
SLA All cores in one shield,
DPYCY
5. Sheath Type
Y Anticorrosive vinyl sheath
TPYCY
-SLA
Designation type
MPYC - 4
Designation type
TTYCSLA-4
# of cores
The following reference table lists gives the measurements of JIS cables commonly used with Furuno products:
Core
Cable
Core
Cable
Area
Diameter
Diameter
DPYC-1.5
1.5mm2
1.56mm
11.7mm
DPYC-2.5
2.5mm
DPYC-4
4.0mm
2.55mm
13.9mm
TPYCY-4
4.0mm
DPYC-6
6.0mm2
3.12mm
15.2mm
TPYCYSLA-1.5
1.5mm2
1.56mm
13.9mm
DPYC-10
10.0mm2
4.05mm
17.1mm
TTYC-7SLA
0.75mm2
1.11mm
20.8mm
DPYC-16
16.0mm2
5.10mm
19.4mm
TTYCSLA-1
0.75mm2
1.11mm
9.4mm
DPYCY-1.5
1.5mm2
1.56mm
13.7mm
TTYCSLA-1Q
0.75mm2
1.11mm
10.8mm
DPYCY-2.5
2.5mm
0.75mm
1.11mm
15.7mm
4.0mm
0.75mm
1.11mm
19.5mm
1.5mm
0.75mm
1.11mm
11.2mm
2.5mm
2.01mm
13.0mm
0.75mm
1.11mm
17.9mm
1.0mm
1.29mm
10.0mm
MPYC-4
1.0mm
1.29mm
11.2mm
MPYC-7
1.0mm2
1.29mm
13.2mm
MPYCY-12
1.0mm2
1.29mm
19.0mm
MPYCY-19
1.0mm2
1.29mm
22.0mm
Type
DPYCY-4
DPYCYSLA-1.5
DPYCYSLA-2.5
MPYC-2
2.01mm
2.01mm
2.55mm
1.56mm
12.8mm
14.8mm
15.9mm
11.9mm
Area
TPYCY-1.5
1.5mm2
1.56mm
14.5mm
TPYCY-2.5
2.5mm
2.01mm
15.5mm
2.55mm
16.9mm
TTYCSLA-4
TTYCY-4SLA
TTYCYSLA-1
TTYCYSLA-4
Diameter
Diameter
Type
AP-1
J1
Connector #
J2
Connector #
J4
Connector #
J5
Connector #
J6
AP-2
Pin #
1
2
3
4
5
Signal name
24V_VOUT
24V_GND
MODBUS-A
MODBUS-B
GND
Pin #
1
2
3
4
5
6
Signal name
24V_IN
24V_OUT
PWR_FAIL-A
PWR_FAIL-COM
PWR_FAIL-B
NC
Pin #
1
2
3
4
5
6
7
Signal name
TD1-A
TD1-B
RD1-A
RD1-B
ISOGND1
RD1-H
RD1-C
Pin #
1
2
3
4
5
6
7
Signal name
TD2-A
TD2-B
RD2-A
RD2-B
ISOGND2
RD2-H
RD2-C
Pin #
1
2
3
4
5
6
7
Signal name
TD3-A
TD3-B
RD3-A
RD3-B
ISOGND3
RD3-H
RD3-C
AI 0.14-8 GY (gray)
Connected cable
MC1.5-W-Lxxx
Connected cable
DPYC-1.5
AI 0.75-6 GY (Gray)
TTYCS-4
TTYCSLA-4
AI 0.75-6 GY (Gray)
AI 0.75-6 GY (gray)
AI 0.75-6 GY (gray)
Connected cable
TTYCS-4
TTYCSLA-4
Connected cable
TTYCS-4
TTYCSLA-4
Connected cable
TTYCS-4
TTYCSLA-4
Connector #
J7
Connector #
J8
Connector #
J8
Pin #
1
2
3
4
5
6
7
Signal name
TD4-A
TD4-B
RD4-A
RD4-B
ISOGND4
RD4-H
RD4-C
Pin #
1
2
3
4
5
6
7
8
Signal name
TD5-A
TD5-B
RD5-H
RD5-C
TD6-A
TD6-B
RD6-H
RD6-C
Pin #
1
2
3
4
5
6
7
8
Signal name
TD7-A
TD7-B
RD7-H
RD7-C
TD8-A
TD8-B
RD8-H
RD8-C
AI 0.75-6 GY (gray)
Connected cable
TTYCS-4
TTYCSLA-4
Connected cable
TTYCS-1Q
TTYCSLA-1Q
AI 0.75-6 GY (gray)
TTYCS-1Q
TTYCSLA-1Q
Rod terminal to use
Connected cable
TTYCS-1Q
TTYCSLA-1Q
AI 0.75-6 GY (gray)
TTYCS-1Q
TTYCSLA-1Q
AP-3
J1
Connector #
J2
Connector #
J3*
Connector #
J4*
Connector #
J5*
Pin #
1
2
3
4
5
Signal name
24V_IN
24V_GND
MODBUS-A
MODBUS-B
GND
Pin #
1
2
3
4
5
Signal name
24V_OUT
24V_GND
MODBUS-A
MODBUS-B
GND
Pin #
1
2
3
4
Signal name
AN1_IN
AN1_GND
CURR1_JP1
CURR1_JP2
Pin #
1
2
3
4
Signal name
AN2_IN
AN2_GND
CURR2_JP1
CURR2_JP2
Pin #
1
2
3
4
Signal name
AN3_IN
AN3_GND
CURR3_JP1
CURR3_JP2
AI 0.14-8 GY (gray)
AI 0.14-8 GY (gray)
Connected cable
MC1.5-W-Lxxx
Connected cable
MC1.5-W-Lxxx
Connected cable
TTYCS-1
TTYCSLA-1
Connected cable
TTYCS-1
TTYCSLA-1
Connected cable
TTYCS-1
TTYCSLA-1
*: For pin #3 and 4, no cable is connected. However the jumper connection is necessary depending on the input specification.
AP-4
J1
Connector #
J2
Connector #
J3*
Connector #
J4*
Connector #
J5*
Pin #
1
2
3
4
5
Signal name
24V_IN
24V_GND
MODBUS-A
MODBUS-B
GND
Pin #
1
2
3
4
5
Signal name
24V_OUT
24V_GND
MODBUS-A
MODBUS-B
GND
Pin #
1
2
3
4
5
6
7
8
Signal name
DV12V_OUT1
DIGI_IN1
DIGI_RTN1
GND
DC12V_OUT2
DIGI_IN2
DIGI_RTN2
GND
Pin #
1
2
3
4
5
6
7
8
Signal name
DV12V_OUT3
DIGI_IN3
DIGI_RTN3
GND
DC12V_OUT4
DIGI_IN4
DIGI_RTN4
GND
Pin #
1
2
3
4
5
6
7
8
Signal name
DV12V_OUT5
DIGI_IN5
DIGI_RTN5
GND
DC12V_OUT6
DIGI_IN6
DIGI_RTN6
GND
AI 0.14-8 GY (gray)
AI 0.14-8 GY (gray)
AI 1-6 RD (red)
AI 1-6 RD (red)
AI 1-6 RD (red)
Connected cable
MC1.5-W-Lxxx
Connected cable
MC1.5-W-Lxxx
Connected cable
MPYC-12
Connected cable
MPYC-12
Connected cable
MPYC-12
*: Pin #1 and 5: no cable connection. However the jumper connection is necessary between #1
and 2 and #5 and 6 depending on the input specification.
AP-5
Connector #
J6*
Pin #
1
2
3
4
5
6
7
8
Signal name
DV12V_OUT7
DIGI_IN7
DIGI_RTN7
GND
DC12V_OUT8
DIGI_IN8
DIGI_RTN8
GND
AI 1-6 RD (red)
Connected cable
MPYC-12
*: Pin #1 and 5: no cable connection. However the jumper connection is necessary between #1
and 2 and #5 and 6 depending on the input specification.
AP-6
J1
Connector #
J2
Connector #
J3
Connector #
J4
Connector #
J5
Connector #
J6
Pin #
1
2
3
4
5
Signal name
24V_IN
24V_GND
MODBUS-A
MODBUS-B
GND
Pin #
1
2
3
4
5
Signal name
24V_OUT
24V_GND
MODBUS-A
MODBUS-B
GND
Pin #
1
2
3
4
5
6
Signal name
A1
COM1
B1
A2
COM2
B2
Pin #
1
2
3
4
5
6
Signal name
A3
COM3
B3
A4
COM4
B4
Pin #
1
2
3
4
5
6
Signal name
Pin #
1
2
3
4
5
6
A5
COM5
B5
A6
COM6
B6
Signal name
A7
COM7
B7
A8
COM8
B8
AI 0.14-8 GY (gray)
AI 0.14-8 GY (gray)
AI 1-6 RD (red)
AI 1-6 RD (red)
AI 1-6 RD (red)
AI 1-6 RD (red)
Connected cable
MC1.5-W-Lxxx
Connected cable
MC1.5-W-Lxxx
Connected cable
MPYC-12
Connected cable
MPYC-12
Connected cable
MPYC-12
Connected cable
MPYC-12
AP-7
DOCUMENT
000-176-720-1*
**
(*2)
(*1)
(*1)
Q'TY
CP24-02100
000-176-423-11
IEC60320-C13-L5M
001-170-630-00
CP24-02101
000-176-663-10
DSUB9P-X2-L5M
001-170-650-00
FP24-00601
001-170-670-00
SP24-00602
001-170-660-00
SP24-00601
000-020-737-00
EC-3000-*
DESCRIPTION/CODE
EC-3000
1.-[**]
CODE NUMBER ENDING WITH "**" INDICATES THE CODE NUMBER OF REPRESENTATIVE MATERIA
2.(*1)(*2)(*3)(*4)
(*1)(*2)(*3)(*4)INDICATE SPECIFICATION SELECTIVE ITEM.
OPERATOR'S MANUAL CD
CD
AC CABLE
OUTLINE
INSTALLATION MATERIALS
ACCESSORIES
SPARE PARTS
UNIT
INSTALLATION MATERIALS
CABLE ASSEMBLY
()
ACCESSORIES
SPARE PARTS
SPARE PARTS
PROCESSOR UNIT
NAME
OUTLINE
000-176-139-1*
IME-36100-*
000-176-137-1*
IME-36060-*
000-176-135-1*
IME-36040-*
000-176-129-1*
IM*-44730-*
000-176-133-1*
OSE-36040-*
000-176-127-1*
OS*-44730-*
000-176-722-1*
000-176-721-1*
DESCRIPTION/CODE
(*4)
(*4)
(*4)
(*4)
(*3)
(*3)
(*2)
(*2)
Q'TY
C4473-Z01-E
TWO TYPES AND CODES MAY BE LISTED FOR AN ITEM. THE LOWER PRODUCT MAY BE SHIPPED IN
PLACE OF THE UPPER PRODUCT. QUALITY IS THE SAME.
**
**
1/1
A-1
INSTALLAION MANUAL
INSTALLAION MANUAL
INSTALLAION MANUAL
INSTALLAION MANUAL
OPERATOR'S GUIDE
OPERATOR'S GUIDE
OPERATOR'S MANUAL CD
CD
OPERATOR'S MANUAL CD
CD
NAME
24AL-X-9851 -4
DOCUMENT
000-176-722-1*
000-176-721-1*
000-176-720-1*
**
(*1)
(*1)
(*1)
Q'TY
CP24-02100
000-176-423-11
IEC60320-C13-L5M
001-170-630-00
CP24-02101
000-176-663-10
DSUB9P-X2-L5M
001-170-650-00
FP24-00601
000-020-737-00
EC-3000-*
DESCRIPTION/CODE
EC-3000*V
1.-[**]
CODE NUMBER ENDING WITH "**" INDICATES THE CODE NUMBER OF REPRESENTATIVE MATERIAL.
2.(*1)(*2)(*3)
(*1)(*2)(*3)INDICATE SPECIFICATION SELECTIVE ITEM.
OPERATOR'S MANUAL CD
CD
OPERATOR'S MANUAL CD
CD
OPERATOR'S MANUAL CD
CD
AC CABLE
OUTLINE
INSTALLATION MATERIALS
ACCESSORIES
UNIT
INSTALLATION MATERIALS
CABLE ASSEMBLY
()
ACCESSORIES
PROCESSOR UNIT
NAME
OUTLINE
000-176-139-1*
IME-36100-*
000-176-137-1*
IME-36060-*
000-176-135-1*
IME-36040-*
000-176-129-1*
IM*-44730-*
000-176-133-1*
OSE-36040-*
000-176-127-1*
OS*-44730-*
(*3)
(*3)
(*3)
(*3)
(*2)
(*2)
Q'TY
C4473-Z13-E
TWO TYPES AND CODES MAY BE LISTED FOR AN ITEM. THE LOWER PRODUCT MAY BE SHIPPED IN
PLACE OF THE UPPER PRODUCT. QUALITY IS THE SAME.
**
**
DESCRIPTION/CODE
1/1
A-2
INSTALLAION MANUAL
INSTALLAION MANUAL
INSTALLAION MANUAL
INSTALLAION MANUAL
OPERATOR'S GUIDE
OPERATOR'S GUIDE
NAME
24AL-X-9866 -4
0#/'
176.+0'
3 6;
%<#
%<#
%2
(2
4%7
&'5%4+26+10%1&'
+056#..#6+10/#6'4+#.5
#%%'5514+'5
176.+0'
+056#..#6+10/#6'4+#.5
#%%'5514+'5
64#%-$#..%10641.70+6
70+6
0#/'
3 6;
A-4
#.:
%2
(2
4%7
&'5%4+26+10%1&'
4%7
+056#..#6+10/#6'4+#.5
#%%'5514+'5
70+6
A-3
#.:
+056#..#6+10/#6'4+#.5
#%%'5514+'5
'%&+5%10641.70+6
'%&+5
4%7
$+0&+0)*'#&5%4'9
$+0&+0)*'#&5%4'9
%4+/210.7)
%#$.'6+'
%#$.'6+'
9+4+0)2.#6'#55;
%*#55+5$#5'
%*#55+5$#5'
9+4+0)2.#6'
176.+0'
%1&'01
/:575
%1&'01
/:575
%1&'01
(8
.(4'&
%1&'01
%80
%1&'01
%80
%1&'01
%2
%1&'01
%1&'01
%1&'01
&'5%4+26+105
3 6;
4'/#4-5
&+/'05+105+0&4#9+0)(144'('4'0%'10.;
%/$
6916;2'5#0&%1&'5/#;$'.+56'&(14#0+6'/6*'.19'4241&7%6/#;$'5*+22'&+02.#%'1(6*'722'4241&7%6
37#.+6;+56*'5#/'
0#/'
5'.(6#22+0)5%4'9
0#/'
176.+0'
&'5%4+26+105
%2
%1&'01
:575
6;2'
%1&'01
3 6;
4'/#4-5
#.:
A-6
&+/'05+105+0&4#9+0)(144'('4'0%'10.;
%/#
6916;2'5#0&%1&'5/#;$'.+56'&(14#0+6'/6*'.19'4241&7%6/#;$'5*+22'&+02.#%'1(6*'722'4241&7%6
37#.+6;+56*'5#/'
01
+056#..#6+10/#6'4+#.5
01
+056#..#6+10/#6'4+#.5
#.:
%2
6;2'
%1&'01
A-5
3 6;
4'/#4-5
&7562411(5210)'
0#/'
176.+0'
%1&'01
&'5%4+26+105
3 6;
4'/#4-5
&+/'05+105+0&4#9+0)(144'('4'0%'10.;
%/#
&+/'05+105+0&4#9+0)(144'('4'0%'10.;
%(#
6916;2'5#0&%1&'5/#;$'.+56'&(14#0+6'/6*'.19'4241&7%6/#;$'5*+22'&+02.#%'1(6*'722'4241&7%6
37#.+6;+56*'5#/'
01
#.:
6916;2'5#0&%1&'5/#;$'.+56'&(14#0+6'/6*'.19'4241&7%6/#;$'5*+22'&+02.#%'1(6*'722'4241&7%6
37#.+6;+56*'5#/'
%1&'01
/:575
%1&'01
:575
&'5%4+26+105
(2
9#5*'4*'#&5%4'9$
5'.(6#22+0)5%4'9
176.+0'
6;2'
%1&'01
A-8
0#/'
#%%'5514+'5
01
+056#..#6+10/#6'4+#.5
#.:
%2
6;2'
%1&'01
A-7
4'/#4-5
9#5*'4*'#&5%4'9$
75$5*''6
75$
&'5-612(+:+0)2.#6'
0#/'
176.+0'
%1&'01
/:575
%1&'01
%1&'01
&'5%4+26+105
3 6;
4'/#4-5
&+/'05+105+0&4#9+0)(144'('4'0%'10.;
%(#
&+/'05+105+0&4#9+0)(144'('4'0%'10.;
%(#
6916;2'5#0&%1&'5/#;$'.+56'&(14#0+6'/6*'.19'4241&7%6/#;$'5*+22'&+02.#%'1(6*'722'4241&7%6
37#.+6;+56*'5#/'
%1&'01
/:%9/$0+
%1&'01
%1&'01
&'5%4+26+105
#.:
176.+0'
(2
6;2'
6916;2'5#0&%1&'5/#;$'.+56'&(14#0+6'/6*'.19'4241&7%6/#;$'5*+22'&+02.#%'1(6*'722'4241&7%6
37#.+6;+56*'5#/'
9#5*'4*'#&5%4'9$
$
75$5*''6
75$
&'5-(+:+0)2.#6'
0#/'
%1&'01
A-10
01
01
#%%'5514+'5
3 6;
#%%'5514+'5
#.:
(2
6;2'
%1&'01
A-9
(75').#55
67$'6;2'
()/$8
#2$(
4'/#4-5%1&'01
5'652'4
8'55'.
$1:012
%2$
52#4'
A-11
#.:
&+/'05+105+0&4#9+0)(144'('4'0%'10.;
6916;2'5#0&%1&'5/#;$'.+56'&(14#0+6'/6*'.19'4241&7%6/#;$'5*+22'&+02.#%'1(6*'
722'4241&7%637#.+6;+56*'5#/'
&9)01
914-+0)
2'4
2'4
5'6
8'5
37#06+6;
75'
52
6;2'
&9)01
14
6;2'01
(74701'.'%64+%%1.6&
176.+0'
52#4'2#465.+56(14
0#/'1(
2#46
/(4 50#/'
+6'/
01
5*+201
%1&'01
).#5567$'
(75'
()/$8#
2$(
&9)01
14
6;2'01
&9)01
914-+0)
2'4
2'4
5'6
8'5
52#4'
A-12
4'/#4-5%1&'01
5'652'4
8'55'.
$1:012
%2$
37#06+6;
75'
52
&+/'05+105+0&4#9+0)(144'('4'0%'10.;
6916;2'5#0&%1&'5/#;$'.+56'&(14#0+6'/6*'.19'4241&7%6/#;$'5*+22'&+02.#%'1(6*'
722'4241&7%637#.+6;+56*'5#/'
(74701'.'%64+%%1.6&
176.+0'
52#4'2#465.+56(14
0#/'1(
2#46
/(4 50#/'
+6'/
01
5*+201
6;2'
%1&'01
2/Nov/2012
Y.NISHIYAMA
D-1
D-2
D-3
D-4
D-5
D-6
D-7
D-8
13/Jan/2012 Y.NISHIYAMA
D-9
13/Jan/2012 Y.NISHIYAMA
DN : cn=
, o, ou=
email=yoshih
nishiyama@fu
o.co.jp, c=JP : 2012.01
14:54:40 +09'0
D-10
13/Jan/2012 Y.NISHIYAMA
D-11
13/Jan/2012 Y.NISHIYAMA
D-12
28/Aug/2012
Y.NISHIYAMA
D-13
28/Aug/2012
Y.NISHIYAMA
D-14
*1
DPYC-2.5
PE *1
IV-2sq.
NOT USED
PE *1
IV-1.25sq.
*1
DPYC-1.5
*1
DPYC-1.5
1
2
PRINTER
12
*2
MONITOR UNIT
MU-190/231
24
DVI2
LAN3
LAN1
USB4
USB3
USB2
USB1
COM2
DVI3
COM1
DVI1
12
12
12
KEY3
KEY2
KEY1
IEC61162-1
NR203PF-VVS1.25
3.5m,8.6
XH12P
XH12P
XH12P
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
J5
TD3-A
TD3-B
RD3-H
RD3-C
GND
J6
TD4-A
TD4-B
RD4-H
RD4-C
GND
J7
TD5-A
TD5-B
RD5-H
RD5-C
GND
J8
TD6-A
TD6-B
RD6-H
RD6-C
GND
J9
TD7-A
TD7-B
RD7-H
RD7-C
GND
J10
TD8-A
TD8-B
RD8-H
RD8-C
GND
MU-23110m
DRAWN
NOTE
*1: SHIPYARD SUPPLY.
*2: OPTION.
*3: 10 m CABLE NOT AVAILABLE FOR MU-231.
SCALE
31/Oct/2012
CHECKED
31/Oct/2012
APPROVED
5/Nov/2012
DWG.No.
C4473-C01- C
LAN2
REF.No.
J11
SYS_FAIL-A 1
SYS_FAIL-B 2
PWR_FAIL-A 3
PWR_FAIL-B 4
NC1-A 5
NC1-B 6
NC2-A 7
NC2-B 8
NO1-A 9
NO1-B 10
NO2-A 11
NO2-B 12
DC12V_OUT 13
DIGI_IN1 14
DIGI_RTN1 15
GND(DC12V) 16
GND 17
1
2
3
4
5
6
7
J4
TD2-A
TD2-B
RD2-A
RD2-B
ISOGND
RD2-H
RD2-C
ALARM SYSTEM
NAVTEX
ALARM
ANEMOMETER
ECHO SOUNDER
LOG
GPS
GYRO
STP(CAT5) CABLE
NORMAL OPEN
NORMAL CLOSE
*1
TTYCS(LA)-10
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-4
AIS
100-230VAC
1,50/60Hz
*2 *3
DVI-D/D_SLINK5/10M
5/10m,7
NOT USED
DTI-C5e350_VCV
10/20/30m,13
*1
USB CABLE,MAX.5m
*2
6TPSH-XH12X2-L5.0SP2,5m
(10/20/30m:OPTION)
B TYPE
*2
5
5
TS-20-071-1,5m
*2
6TPSH-XH12X2-L5.0SP2,5m
(10/20/30m:OPTION)
B TYPE
*2
5
5
TS-20-071-1,5m
6TPSH-XH12X2-L5.0SP1,5m
(10/20/30m:OPTION)
B TYPE
5
5
TS-20-071-1,5m
24
24
*1
TTYCS(LA)-4
ALARM SYSTEM
12
12
*2 *3
DVI-D/D_SLINK5M
5m,7(10m:OPTION)
*2 *3
DSUB9P-X2-L5M,5m
(10m:OPTION)
*3
DVI-D/D_SLINK5M
5m,7(10m:OPTION)
*3
DSUB9P-X2-L5M,5m
(10m:OPTION)
J1
24P0124
ECDIS
ECDIS CONTROL UNIT
RCU-024
24
PROCESSOR UNIT
EC-3000
EXTERNAL MONITOR
(FMD-3200-BB)
DITTO
MONITOR UNIT
MU-190(FMD-3200)
MU-231(FMD-3300)
TB1
PE *1
IV-2sq.
1
2
IEC60320-C13-L5M,5m
IEC61162-1/2
100-230VAC
1,50/60Hz
100-230VAC
1,50/60Hz
C
100-115/220-230VAC
1,50/60Hz
B
1
2
3
4
5
6
7
J3
TD1-A
TD1-B
RD1-A
RD1-B
ISOGND
RD1-H
RD1-C
1
4
5
*2
FR-FTPC-CY,
10/20/30m,13
T.YAMASAKI
H.MAKI
MASS
kg
24-014-6011-1
Y.NISHIYAMA
OR
SENSOR ADAPTER
MC-3000S(SERIAL 8ch)
MC-3010A(ANALOG 3ch)
MC-3020D(DIGITAL IN)
MC-3030D(DIGITAL OUT)
S-1
NETWORK EQUIPMENT
SWITCHING HUB *2
HUB-100 (8 PORTS)
PE *1
IV-1.25sq.
C4473-C02
REFER TO C4473-C02 FOR DETAIL
TITLE
FMD-3200(-BB)/3300
NAME
ECDIS
INTERCONNECTION DIAGRAM
DRAWN
1/Nov/2012
CHECKED
1/Nov/2012
APPROVED
SCALE
5/Nov/2012
DWG.No.
MASS
Y.NISHIYAMA
C4473-C02- C
REF.No.
NOTE
*1: SHIPYARD SUPPLY.
*2: OPTION.
*3: A:NORMAL OPEN, B:NORMAL CLOSE.
T.YAMASAKI
H.MAKI
kg
24-014-6003-1
*1
TITLE
FCR-2819 SER.
FMD-3200/3300
NAME
1
2
3
4
5
6
*1
(24VDC CURRENT)
DIGITAL MPYC-12
IN 5-8
DITTO
1
2
3
4
1
2
3
4
1
2
3
4
SERIAL
(IEC61162-1)
DITTO
*1
TTYCS(LA)-1Q
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
J8
TD5-A
TD5-B
RD5-H
RD5-C
TD6-A
TD6-B
RD6-H
RD6-C
J9
TD7-A
TD7-B
RD7-H
RD7-C
TD8-A
TD8-B
RD8-H
RD8-C
J4
TD1-A
TD1-B
RD1-A
RD1-B
ISOGND
RD1-H
RD1-C
J5
TD2-A
TD2-B
RD2-A
RD2-B
ISOGND
RD2-H
RD2-C
J6
TD3-A
TD3-B
RD3-A
RD3-B
ISOGND
RD3-H
RD3-C
J7
TD4-A
TD4-B
RD4-A
RD4-B
ISOGND
RD4-H
RD4-C
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
SERIAL
(IEC61162-2)
*3
MC-3000S/3010A/3020D/3030D
SENSOR ADAPTER
INTERCONNECTION DIAGRAM
DITTO
SERIAL
(IEC61162-1)
*1
TTYCS(LA)-4
*1
TTYCS(LA)-4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
*1
ANALOG TTYCS(LA)-1
1
2
3
4
5
*2
MC1.5-W-L600/
1000/2000/3000,
0.6/1/2/3m
*1
IV-1.25sq.
1
2
3
4
5
6
(CONTACT CLOSURE)
DIGITAL
IN 1-4
*1
MPYC-12
1
2
3
4
5
6
7
8
1
2
3
4
5
J1
J2
24V_IN
24V_GND
MOD_BUS-A
MOD_BUS-B
GND
J3
AN1_IN
AN1_GND
CURR1_JP1
CURR1_JP2
J4
AN2_IN
AN2_GND
CURR2_JP1
CURR2_JP2
J5
AN3_IN
AN3_GND
CURR3_JP1
CURR3_JP2
SELECT
DIGITAL MPYC-12
OUT 5-8
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
J1
J2
24V_IN
1
24V_GND 2
MOD_BUS-A 3
MOD_BUS-B 4
5
GND
J3
DC12V_OUT1
DIGI_IN1
DIGI-RTN1
GND
DC12V_OUT2
DIGI_IN2
DIGI-RTN2
GND
J4
DC12V_OUT3
DIGI_IN3
DIGI-RTN3
GND
DC12V_OUT4
DIGI_IN4
DIGI-RTN4
GND
J5
DC12V_OUT5
DIGI_IN5
DIGI-RTN5
GND
DC12V_OUT6
DIGI_IN6
DIGI-RTN6
GND
J6
DC12V_OUT7
DIGI_IN7
DIGI-RTN7
GND
DC12V_OUT8
DIGI_IN8
DIGI-RTN8
GND
MC-3010A
*2
(ANALOG 3ch)
*2
SENSOR ADAPTER
MC-3000S(SERIAL 8ch)
DIGITAL MPYC-12
OUT 1-4
*1
*1
A IV-1.25sq.
B
1
2
3
4
5
*1
IV-1.25sq.
*2
MC1.5-W-L600/
1000/2000/3000,
0.6/1/2/3m
*1
IV-1.25sq.
J2
J1
24V_IN
24V_GND
MOD_BUS-A
MOD_BUS-B
GND
J3
A1
COM1
B1
A2
COM2
B2
J4
A3
COM3
B3
A4
COM4
B4
J5
A5
COM5
B5
A6
COM6
B6
J6
A7
COM7
B7
A8
COM8
B8
C
MC-3020D *2
(DIGITAL IN)
J2
24V_IN
24V_GND
PWR_FAIL-A
PWR_FAIL-COM
PWR_FAIL-B
NC
J1
24V_VOUT
24V_GND
MOD_BUS-A
MOD_BUS-B
GND
8
*2
MC1.5-W-L600/
1000/2000/3000,
0.6/1/2/3m
1
2
3
4
5
6
SWITCHING
HUB
HUB-100
ALARM SYSTEM
*1
DPYC-1.5
*1
TTYCS(LA)-1
PROCESSOR
UNIT
EC-3000
OR
1
2
3
4
5
MC-3030D *2
(DIGITAL OUT)
B
24VDC
A
*2
FR-FTPC-CY,
10/20/30m,13
1
3
S-2
3-4
PE
*1
IV-2sq.
D
*2
TYPE
MC-3000S
3
REMARK
UPS
INDCLUDES OPTIONAL UNITS
AND UPS FIXTURE.
NOTE
*1: SHIPYARD SUPPLY.
*2: OPTION.
*3: A CONSOLE CAN INCLUDE THREE UNITS (MC-3000S INCLUDED)
AMONG SENSOR ADAPTERS.
*1
TTYCS(LA)-1
DRAWN
13/Nov/2012
CHECKED
13/Nov/2012
APPROVED
14/Nov/2012
SCALE
DWG.No.
C4473-C03- D
T.YAMASAKI
H.MAKI
Y.NISHIYAMA
MASS
kg
REF.No.
24-014-6301-2
FMD-3200/3300
1
2
3
4
5
6
7
1
2
3
4
5
6
7
J1
1
2
3
4
1
2
3
4
1
2
3
4
J3
AN1_IN
AN1_GND
CURR1_JP1
CURR1_JP2
J4
AN2_IN
AN2_GND
CURR2_JP1
CURR2_JP2
J5
AN3_IN
AN3_GND
CURR3_JP1
CURR3_JP2
J2
5
AI.14-8AI.34-6L600
1
2
3
4
5
6
7
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
J5
TD3-A
TD3-B
RD3-H
RD3-C
GND
J6
TD4-A
TD4-B
RD4-H
RD4-C
GND
J7
TD5-A
TD5-B
RD5-H
RD5-C
GND
J8
TD6-A
TD6-B
RD6-H
RD6-C
GND
J9
TD7-A
TD7-B
RD7-H
RD7-C
GND
J10
TD8-A
TD8-B
RD8-H
RD8-C
GND
1
2
3
4
5
6
7
J3
TD1-A
TD1-B
RD1-A
RD1-B
ISOGND
RD1-H
RD1-C
J4
TD2-A
TD2-B
RD2-A
RD2-B
ISOGND
RD2-H
RD2-C
55
56
57
58
50
51
52
53
54
45
46
47
48
49
40
41
42
43
44
35
36
37
38
39
30
31
32
33
34
25
26
27
28
29
20
21
22
23
24
15
16
17
18
19
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-1Q
*1
TTYCS(LA)-4
*1
TTYCS(LA)-4
ECHO SOUNDER
WIND
NAVTEX
POSITION2
POSITION1
LOG
GYRO
AIS
IEC61162-1
CONNECTION FOR IEC61162-1
*1
J4-J7
TTYCS(LA)-1Q
SERIAL
1 TD*-A
(IEC61162-1)
2 TD*-B
3 RD*-A
4 RD*-B
5 ISOGND
6 RD*-H
7 RD*-C
MC-3000S
(SERIAL 8ch)
1
2
3
4
5
6
7
SENSOR ADAPTER *2 *3
AI.14-8AI.34-6L1000
IEC61162-1
J3
5
LAN2
KEY3
KEY2
KEY1
DITTO
PR-240 *2
8
1
2
3
4
5
6
7
MOD-Z072-020+
12
12
12
NORMAL OPEN
NORMAL CLOSE
ALARM
SYSTEM
*1
TTYCS(LA)-4
SERIAL
(IEC61162-2)
NR203PF-VVS1.25-0.3M
AI1.5-6BK-FV2-4L850
P
1
2
3
4
5
6
SWITCHING HUB *2
HUB-100 (8 PORTS)
*1
SERIAL TTYCS(LA)-4
(IEC61162-2)
ALARM SYSTEM
AI1.5-6BK-FV2-4L730
MOD-Z072-020+
DVI2
LAN3
LAN1
USB4
USB3
USB2
USB1
XH12P
13
14
J2
24V_IN
24V_GND
PWR_FAIL-A
PWR_FAIL-COM
PWR_FAIL-B
NC
J4
TD1-A
TD1-B
RD1-A
RD1-B
J1
ISOGND
RD1-H
RD1-C
J5
TD2-A
TD2-B
RD2-A
RD2-B
ISOGND
J8
RD2-H TD5-A 1
RD2-C TD5-B 2
RD5-H 3
J6
TD3-A RD5-C 4
TD3-B TD6-A 5
RD3-A TD6-B 6
RD3-B RD6-H 7
ISOGND RD6-C 8
RD3-H
J9
RD3-C TD7-A 1
TD7-B 2
J7
TD4-A RD7-H 3
TD4-B RD7-C 4
RD4-A TD8-A 5
RD4-B TD8-B 6
ISOGND RD8-H 7
RD4-H RD8-C 8
RD4-C
*2
IOK-V0024-2
COM2
DVI3
COM1
DVI1
J1
*1
TTYCS(LA)-10
FR-FTPC-CY,
NETWORK EQUIPMENT 10/20/30m,13
B TYPE
4 TS-20-071-1,5m
STANDARD CONSOLE
ECN-303/304
*1
DPYC-1.5
1
2
ECDIS
ECDIS CONTROL UNIT
RCU-024
DSUB9P-X2-L5M,5m
6TPSH-XH12X2-L5MSP1
24
DVI-D/D_SLINK5M
24
PROCESSOR UNIT
EC-3000
12
MONITOR UNIT
MU-190(ECN-304)
MU-231(ECN-303)
TB1
IEC60320-C13-L1.7M
IEC61162-1/2
ALARM SYSTEM
5
6
1
2
FV2W-VVS2.0X
2C-L1050
1
2
3
4
TB4
24P0124
DTI-C5E350-VCV
NETWORK EQUIPMENT 10/20/30m,13.5
1
2
TB1
*1
DPYC-2.5
TB3
1
2
3
4
5
6
7
8
9
10
11
12
100-115/
220-230 VAC
1,50/60Hz
J11
SYS_FAIL-A 1
SYS_FAIL-B 2
PWR_FAIL-A 3
PWR_FAIL-B 4
NC1-A 5
NC1-B 6
NC2-A 7
NC2-B 8
NO1-A 9
NO1-B 10
NO2-A 11
NO2-B 12
DC12V_OUT 13
DIGI_IN1 14
DIGI_RTN1 15
GND(DC12V) 16
GND 17
1
6
S-3
MC-3010A(ANALOG IN)
MC-3020D(DIGITAL IN)
MC-3030D(DIGITAL OUT)
SELECT
C4473-C02
REFER TO C4473-C02 FOR DETAIL
MC-3010A(ANALOG 3ch)
*1
TTYCS(LA)-1Q
TITLE
ECN-303/304-A/B/C
NAME
STANDARD CONSOLE
INTERCONNECTION DIAGRAM
ANALOG
SERIAL
(IEC61162-1)
AI1.5-6BK-FV2-4L1200
FV2W-VVS2.0X2C-L800